160-250kVA CPCBIV Genset

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Diesel Generator Set

QSB6.7 Series
160 - 250 kVA, 128 - 200 kWe Prime
CPCB IV+ Emission Compliant

Latest Technology and Lowest Operating Cost and


Unmatched Performance Comprehensive Warranty
The Cummins® QSB6.7 series rugged Highly reliable and durable product
engine and world class Stamford alternator Maximum efficiency even at part loads, offering the
powered diesel generator set advantage of lowest operating costs
Proven technology with common rail Either 750 or 500 Hours/ 1 year service interval
electronic fuel system Industry acknowledged best-in-class comprehensive
Exhaust after-treatment and in-cylinder warranty on the entire package including rubber
solution to meet stringent emission norms components
Superior finish and aesthetics
Compact in size with optimum power
to weight ratio
Single Source Power Assurance
Environment Friendly Power All the major components - the engine, alternator,
Class defining and technologically advanced aftertreatment system, control system and canopy
engine to meet stringent exhaust emission norms are designed, manufactured, and tested by
as per the latest MoEF notification Cummins India
The Cummins® diesel generator sets are available Best and largest customer support network in
with the lowest noise levels in its range India, capable of providing round-the-clock service
and spares support
Diesel Generator Set QSB6.7 Series Specification Sheet

Engine PS0602 Features


Cummins® QSB6.7 series, 6 cylinder, In-line 4 stroke, Cummins® PowerStart™
radiator cooled engine PS0602 control is a
Robust and efficient air handling system with microprocessor based generator
• Dry type and replaceable paper element air cleaner set monitoring, metering and
with restriction indicator control system with LCD display
• Optimized turbocharger for increased designed to meet the demands
altitude capabilities of today's engine driven generator set
Optimized fuel consumption with common rail electronic AMF Functionality
injection Electronic Governing
Spin on single fuel filter with water separator CAN (J1939) Compatible
Cooling system is designed and tested for 50°C ambient Sync Compatible (Capable to accept external speed
conditions signal from 3rd party sync controller)
Full flow spin on lube oil filter Intuitive operator interface which includes LED backlit
First fill of lube oil and coolant 128X64 pixel graphic display with tactile feel soft-switches
Electrical starter motor with soft start engagement feature & generator set status LED lamps
Battery charging alternator Remote start-stop
2 x 12 V DC battery Audible & Visual warning for Inducement
Suitable for FAE based engine architecture
Engine Metering: Oil pressure, Engine temperature,
Starting battery voltage, Engine running hours
AC Alternator Metering: L-L Voltage and L-N Voltage,
Current (phase and total), kVA (phase and total) and
Frequency. kwh, Total & per phase (kw & kVA), PF, Utility
Voltage and Freq
Engine Protection: Low lube oil pressure, High/Low
coolant temperature, Battery High/Low/Weak Volts, Fail to
Crank/Start, Sensor failure, Cranking lockout, Low fuel level
AC Alternator Protection: Over/Under Voltage, Over/Under
Frequency, Loss of AC sensing. Overspeed, Over Current,
kW Overload
Data Logging: Engine hours, Control hours and upto 5 recent
Alternator fault codes
Configurable glow plug control
STAMFORD S3L1D alternator frames from Cummins 12/24 Volt DC operation
Generator Technologies Sleep mode
Brushless type, Screen protected, Revolving field, Modbus interface (RS485 RTU)
Self-excited alternator conforming to IS/IEC 60034-1 In Power compatible (PC based service tool)
Better motor starting capability Certifications - meets the requirement of relevant ISO, EN,
Best in class efficiency Mil Std. and CE standards.
Compact design with sealed bearings for longer life Maintenance due alarm based on Engine Run Time and
and lesser maintenance due date
Impregnation on all wound components for Fuel and DEF level visual display
better mechanical strength Exerciser scheduler

EATS Silencer
Hospital Grade Silencer inside canopy with rain cap
Single module architecture supplied by
suitably optimized to meet stringent noise limit
Cummins Emission Solutions.
Silencer specifically tuned to EATS
Compact design enabling optimized genset size
Integrated control module for engine and EATS
Best in class proven technology for meeting Mounting Arrangement
stringent emission norms
Engine and alternator are mounted on a common MS
fabricated base frame with AVM pads
Control Panel Skid mounted radiator
Base frame with integral fuel tank and DEF tank is provided
Control panel is powder coated for weather-proof and long-
with drain plug, air vent, inlet and outlet connection and
lasting finish. The control panel consists of the following parts:
provision for cleaning

PS0602 Controller
Bus bars with suitable capacity with incoming/ Optional
outgoing terminals
Indicating lamps for 'Load ON' and 'Set Running' Engine: Heated Architecture & HD Air cleaner
Instrument fuses duly wired and ferruled. Alternator: PMG and Space Heater
MCCB of suitable rating with short circuit protections EATS: Heated Architecture
AC/DC separation inside control panel for safety Controller: PCC3.3
Diesel Generator Set QSB6.7 Series Specification Sheet

Acoustic Enclosure Remote monitoring system


Specially designed to meet stringent MoEF/ CPCB norms Compact & robust device
of 75 dBA@1mtr at 75% load under free field conditions Real time DG status & monitoring
The acoustic enclosure is made CRCA sheets in 4G compatible
Munsell green shade and a structural/sheet metal Compatible for 12/24 V DC
base frame painted in black Reports & Notification – Alerts & Warning
11 tank pretreatment process and UV resistant powder Isolated RS 485 interface
coating of all parts to withstand extreme environment Device location using triangulation
High quality noise absorbent and fire-retardant grade
acoustic Insulation material (Rockwool) complying to IS 8183
Top lifting for easy handling at customer site
External fuel & DEF filling provision

Technical Data
Generator Set Specification
Technical Data
Model CI 160D5P CI 180D5P CI 200D5P CI 225D5P CI 250D5P

Duty Prime Prime Prime Prime Prime

Power Rating kVA / kWe 160/128 180/144 200/160 225/180 250/200

No. of Phases 3 Phase 3 Phase 3 Phase 3 Phase 3 Phase

Output Voltage and Frequency 415 V, 50 Hz 415 V, 50 Hz 415 V, 50 Hz 415 V, 50 Hz 415 V, 50 Hz


(V and Hz)
Power Factor 0.8 (lagging) 0.8 (lagging) 0.8 (lagging) 0.8 (lagging) 0.8 (lagging)

Current (A) 223 250 278 313 348

RPM 1500 1500 1500 1500 1500

Engine Specification

Make Cummins®

Model QSB6.7-G21 QSB6.7-G22 QSB6.7-G22 QSB6.7-G23 QSB6.7-G23

Required Power for


206.8 249.1 249.1 306.9 306.9
Rated kVA (hp)

Cooling Liquid Cooled (EG Compleat 50:50)

DEF AUS 32 (Premix) as per ISO 22241

Aspiration Turbocharged , Intercooled

No. of cylinders 6, In-line 6, In-line 6, In-line 6, In-line 6, In-line

Bore (mm) x Stroke (mm) 107 X 124 107 X 124 107 X 124 107 X 124 107 X 124

Compression ratio 17.3:1 17.3:1 17.3:1 17.3:1 17.3:1

Displacement (litre) 6.7 6.7 6.7 6.7 6.7

Fuel High Speed Diesel High Speed Diesel High Speed Diesel High Speed Diesel High Speed Diesel

Performance class of generator set ISO 8528-5 G2 ISO 8528-5 G2 ISO 8528-5 G2 ISO 8528-5 G2 ISO 8528-5 G2

Starting system 24 V DC Electrical 24 V DC Electrical 24 V DC Electrical 24 V DC Electrical 24 V DC Electrical

Lube oil specification CK4 CK4 CK4 CK4 CK4


Lube oil sump capacity,
15-19.5 15-19.5 15-19.5 15-19.5 15-19.5
High-Low level (litre)
Total lubrication system capacity
(litre) 21.5 21.5 21.5 21.5 21.5

Total coolant capacity(litre) 20.3 20.3 20.3 20.3 21.3

Exhaust pipe size (inch) 5 5 5 5 5

Total wet weight


725 751 751 751 844
(Engine+Radiator)* (kg)

Length X Width X Height


1534 X 980 X 1219 1466 X 858 X 1132 1466 X 858 X 1132 1466 X 858 X 1132 1517 X 1064 X 1451
(Coolpac) (mm)

Mean Piston speed (m/s) 6.2 6.2 6.2 6.2 6.2

Combustion air intake @100%


362 436 436 516 516
load (±5%) (cfm)

Exhaust Temperature (0C) 515 521 521 524 524


Diesel Generator Set QSB6.7 Series Specification Sheet

Alternator Specification
Make STAMFORD (CGT) STAMFORD (CGT) STAMFORD (CGT) STAMFORD (CGT) STAMFORD (CGT)

Alternator Frame S3L1D-F41 S3L1D-G41 S3L1D-H41 S3L1D-J41 S3L1D-K41

Enclosure IP 23 IP 23 IP 23 IP 23 IP 23

Voltage regulation (Max.) ±0.5% ±0.5% ±0.5% ±0.5% ±0.5%

Class of Insulation H Class H Class H Class H Class H Class

Winding Pitch 2/3 2/3 2/3 2/3 2/3

Stator Winding Double layer concentric

Rotor Dynamically Balanced

Waveform distortion/ No load < 1.5%, Non distorting balanced linear load < 5 %
Total Harmonic Distortion
Maximum Unbalanced less than or equal to 25%
Load across phases•

Telephonic Harmonic factor < 2%

Rating Definitions Conformance Standards

• IS/IEC 60034-1
Prime Power (PRP):
• ISO 1460
Applicable for supplying power to
• ISO 8528
varying electrical load for unlimited hours.
• ISO 3046
Prime Power (PRP) is in accordance with
• ISO 9001
ISO 8528.
• ISO 13018

Typical Enclosed Genset Dimensions

DEF Tank Standard Fuel tank


Genset Model Rating (kVA) Length (mm) Width (mm) Height (mm) Wet Weight" (kg)
Capacity (litre) Capacity (litre)

CI 160D5P 160 4050 1350 1850 3025 60 385

CI 180D5P 180 4050 1350 1850 3055 60 385

CI 200D5P 200 4050 1350 1850 3120 60 385

CI 225D5P 225 4050 1350 1850 3170 60 385

CI 250D5P 250 4050 1350 2000 3180 60 395

" Approximate Weight

Cummins Power Systems Offices

Bengaluru: Tel.: (080) 2325 9161 / 63, 2325 9165 / 67 | Fax: (080) 2325 9164
Authorised Representative
Chandigarh: Tel.: (0172) 224 0371-73 | Fax: (0172) 224 0372
Chennai: Tel.: (044) 2446 8110 / 2446 8113 | Fax: (044) 2491 1120
Gurgaon: Tel.: (0124) 391 0900-01 | Fax: (0124) 391 0916
Hyderabad: Tel.: (040) 2340 9970 / 2340 9980 | Fax: (040) 2340 9990
Jaipur: Tel.: (0141) 236 4944 | Fax: (0141) 403 8794
Kolkata: Tel.: (033) 2287 8065 / 2287 2481 | Fax: (033) 2290 3839
Lucknow: Tel.: (0522) 230 5049 / 230 5059 | Fax: (0522) 230 5035
Mohali: Tel.: (0172) 224 0371 I 72 / 73 | Fax: (0172) 224 0371 / 72 / 73
Vadodara: Tel.: (0265) 233 0627 / 3053627 | Fax: (0265) 234 0623

Visit our Facebook page at :


Cummins Power Generation India
Cummins India Limited
"Our energy working for you." Power Systems Business
Cummins India Office Campus
Tower-A, 8th Floor, S. No. 21
Balewadi, Pune - 411 045 (India)
Cummins is registered trademarks of Cummins Inc.
Specifications are subject to change without notice. Email : [email protected]
PSBU/CPCB IV+/QSB6.7/Rev-00/07 2023 www.cummins.com

You might also like