Industrial VFD Catalog - Web
Industrial VFD Catalog - Web
Industrial VFD Catalog - Web
VFD CABLE
R
U
S
T
VFD W
V MOTOR
PE PE
V LL
AmerCable believes the information presented throughout this catalog to be reliable and current.
All information is subject to change without notice. The information listed is approximate, and is
presented only as a guide for product selection. We make no claims or warranties for the suitability
of any product for any particular application.
Made in America
AmerCable® is a registered trademark of AmerCable Incorporated © 2024, AmerCable Incorporated
OUR COMMITMENT INDUSTRIAL VFD CABLES
TO INDUSTRIAL
PRODUCTIVITY
AmerCable’s Industrial VFD Cables are specially
engineered to provide 100% containment of EMI
emissions and provide longer cable life in harsh
operating conditions.
www.AmerCable.com
e-mail: [email protected]
1
37-108VFD
FLEXIBLE TC-ER
VFD POWER CABLE
Three Conductor • 90°C • 1000V*
APPLICATION
Power Conductors (x3)
Symmetrical
A flexible shielded power cable specifically
Soft annealed flexible Ground engineered for use in variable frequency
stranded tinned copper Conductors (x3) AC motor drive (VFD) applications.
per ASTM B-33 Three symmetrically
placed flexible FEATURES
Insulation stranded tinned copper
Cross-linked, flexible, low conductors in direct n Specially engineered cable design produces a
dielectric constant compound contact with the shield. longer cable life in VFD applications.
rated 90°C.
Metallic Shield n Overall shield provides 100% coverage
Sizes larger than 4/0 AWG – Sizes 8 AWG and Larger –
individual conductors Helically applied bare
containing VFD EMI emissions.
colored black with
conductor number surface
copper tape. n Symmetrical ground conductors reduce induced
printed in contrasting ink. Sizes Smaller than voltage imbalances and carry common mode
8 AWG – tin-coated
Sizes 4/0 AWG and copper braid plus noise back to the drive.
smaller – individually aluminum/polyester tape.
colored conductors – n High strand count design is much more flexible,
red, white,black. Both shielding systems easier to install and more resistant to vibration
provide 100%
coverage. than Type MC cable.
Jacket n Meets crush and impact requirements for
Flame retardant, moisture Type MC cable.
and sunlight resistant
Polyvinyl Chloride
n AmerCable’s specially formulated insulation
(PVC). Colored black. material has a lower dielectric constant (standard
XLPE and EPR insulation materials have higher
dielectric constants) which withstands reflected
TC-ER Ratings & Approvals
voltages. This allows for longer output cable
* n UL Listed as Type TC-ER 600V distances and minimizes the effect of high
* n UL Listed as 1000V flexible motor supply cable frequency noise induced into the plant
(up to 4/0 AWG) ground system.
n 90°C Temperature Rating n Permitted for Exposed Run (“ER”)
n FT-4 and IEEE 1202 flame ratings use in accordance with the NEC.
n Sunlight resistant n Permitted for use in Class I, Division 2 and Zone 2
n Direct burial industrial hazardous locations per the NEC.
n Gas and vapor tight – impervious to water
and air.
n Reduced tray fill (up to 35% less) than Type MC.
n Reduced installation time and cost compared
to Type MC.
n Glands for this product cost up to 50% LESS
than those for Type MC.
n Bend radius 12X O.D.
APPLICATION
POWER CONDUCTORS (X3)
SYMMETRICAL GROUND TC-ER VFD cable is used to supply power to motors,
Soft annealed stranded bare CONDUCTORS (X3)
copper per ASTM B3, B496 Three symmetrically
or for connection to other power devices in industrial
placed stranded bare settings. Primary installations include cable trays,
copper conductors in raceways, and outdoor locations supported by a
INSULATION direct contact with the messenger wire. Type TC-ER VFD is Listed for direct
Low dielectric constant XLPE shield.
meeting XHHW-2 burial or in underground ducts and for use in Class 1,
per UL 44 Division 2 hazardous locations and Class 1 control
METALLIC SHIELD circuits. This cable may be used in wet or dry loca-
Helically applied bare tions at temperatures not to exceed 90°C. The cable
copper tape for is specifically engineered for use in variable frequency
provide 100% AC motor drive (VFD) applications.
coverage.
FEATURES
n Specially engineered cable design produces a
longer cable life in VFD applications.
JACKET
Flame retardant, moisture
n Overall shield provides 100% coverage
and sunlight resistant containing VFD EMI emissions.
Polyvinyl Chloride (PVC)
per UL 1277. Colored black.
n Symmetrical ground conductors reduce induced
voltage imbalances and carry common mode
noise back to the drive.
n Meets crush and impact requirements for Type MC
RATINGS & APPROVALS n AmerCable’s specially formulated XLPE insulation
n UL Listed as Type TC-ER 600V material has a lower dielectric constant which
n 90°C Wet/Dry Temperature Rating withstands reflected voltages. This allows for longer
n FT-4/ IEEE 1202 Flame Rating output cable distances and minimizes the effect
of high frequency noise induced into the plant
n Sunlight Resistant
ground system.
n For Direct Burial
n Permitted for Exposed Run (“ER” use in
accordance with the NEC 336.10(7).
n Permitted for use in Class I, Division 2 and Zone 2
industrial hazardous locations per the NEC.
n Gas and vapor tight – impervious to water and air.
n Bend radius 12X O.D.
n Color code per ICEA S-58-679 Method 4
APPLICATION
POWER CONDUCTORS (X3) TC-ER VFD cable is used to supply power to motors,
SYMMETRICAL GROUND
Soft annealed stranded bare CONDUCTORS (X3) or for connection to other power devices in industrial
copper per ASTM B3, B496 Three symmetrically settings. Primary installations include cable trays,
placed stranded bare raceways, and outdoor locations supported by a
copper conductors in
INSULATION messenger wire. Type TC-ER VFD is Listed for direct
direct contact with the
Low dielectric constant XLPE shield. burial or in underground ducts and for use in Class 1,
meeting RHH/RHW-2 Division 2 hazardous locations and Class 1 control
per UL 44 circuits. This cable may be used in wet or dry loca-
METALLIC SHIELD tions at temperatures not to exceed 90°C. The cable
Helically applied bare is specifically engineered for use in variable frequency
copper tape for AC motor drive (VFD) applications.
provide 100%
coverage.
FEATURES
n Specially engineered cable design produces a
longer cable life in VFD applications.
JACKET n Overall shield provides 100% coverage containing
Flame retardant, moisture VFD EMI emissions.
and sunlight resistant
Polyvinyl Chloride (PVC) n Symmetrical ground conductors reduce induced
per UL 1277. Colored black. voltage imbalances and carry common mode noise
back to the drive.
n Meets crush and impact requirements for Type MC
RATINGS & APPROVALS n AmerCable’s specially formulated XLPE insulation
n UL Listed as Type TC-ER 2000V material has a lower dielectric constant which
withstands reflected voltages. This allows for longer
n 90°C Wet/Dry Temperature Rating
output cable distances and minimizes the effect
n FT-4/ IEEE 1202 Flame Rating of high frequency noise induced into the plant
n Sunlight Resistant ground system.
n For Direct Burial n Permitted for Exposed Run (“ER” use in accordance
with the NEC 336.10(7).
n Permitted for use in Class I, Division 2 and Zone 2
industrial hazardous locations per the NEC.
n Gas and vapor tight – impervious to water and air.
n Bend radius 12X O.D.
n Color code per ICEA S-58-679 Method 4
n Cables are fully compliant with NFPA 79-2018
Grounding
Power Converter Conductors
Transformer Motor
Inverter
CT
CM
Shield
CC1 CC2 l1
l2
If symmetrical grounding conductors and an overall EMI shield are not used, EMC - EMI problems are very
likely to occur.
For cables used with voltage source PWM drives, a number of features are required to ensure correct
operation, avoid overheating and achieve longer service life.
The essential features of a medium voltage cable for PWM drives are :
• Insulation designed to withstand the transients produced by the PWM
• Insulation with a dielectric constant no greater than 3.0 to minimize capacitance
• Voltage rating of 3x the operating voltage to prevent corona
• Three symmetrical grounding conductors. Some cables only have one grounding conductor. This is not
acceptable as it produces circulating currents in the earth system
• Extremely fine strands to carry the harmonic currents without overheating
(i.e. the inductance of fine stranded conductors is less than 7, 19, 37 strand conductors)
• Overall shield to stop the radiation of voltage EMI fields
• Correct termination at both ends Connection
• Semi-conducting shield around each insulation layer (MMV only) Ring
Insulated
• Metallic layer around each semi-conducting shield to earth the Grounding
semi-conducting shield (MMV only). Conductor
EMI
Shield
Earth Connection
F I G U R E 3
Figures 1 - 3 courtesy of Converteam