AC Grid With Embedded VSC-HVDC For Secure and Efficient Power Delivery
AC Grid With Embedded VSC-HVDC For Secure and Efficient Power Delivery
Atlanta, GA USA
17-18 November, 2008
Jiuping Pan and Reynaldo Nuqui are with ABB Corporate Research,
Raleigh NC 27606 USA (e-mail: [email protected],
[email protected]).
Kailash Srivastava and Tomas Jonsson are with ABB Corporate Research,
72178 Vasteras, Sweden (e-mail: [email protected],
[email protected]).
Figure 1 HVDC station with current source converters
Per Holmberg and Ying Jiang-Hafner are with ABB Power Systems/DC, Today there are about 100 classical projects around the
Ludvika, Sweden (email: [email protected], ying-
[email protected]). world. Typically, a classical HVDC transmission has a power
Authorized licensed use limited to: Hochschule Hannover. Downloaded on July 08,2024 at 10:44:50 UTC from IEEE Xplore. Restrictions apply.
of more than 100 MW and many are in the 1,000-3,000 MW
range. One of the major efforts for classical HVDC today is Table 1 Reference list of HVDC Light®
the development of Ultra High Voltage DC Systems (±800
kV) to transport more power over longer distances. The
largest HVDC project so far, (6400 MW, ±800kV) is already
under construction in China. More such projects have been
planned in China and India as well as in Southern Africa and
Brazil [2].
One major reason for the increased interest in HVDC is
that more power can be transmitted more efficiently over long
distance, say over 1000-2500 km, than by ac lines. HVDC
systems can carry 2-5 times the capacity of an ac line of
similar voltage. As such the environmental impact of HVDC
is more favorable than ac lines because less right-of-way land
is needed. HVDC transmission has been widely used to Estlink 350 MW 105 km Connecting asynchronous
networks
2006
interconnect two ac systems where ac ties would not be NORD E.ON 1 400 MW 203 km Offshore wind power 2009
feasible because of system stability problems or different CAPRIVI LINK 300 MW 970 km (OH) Connecting weak AC 2009
nominal frequencies of the two systems. HVDC transmission networks
is also needed for underwater cables longer than 50 km where VALHALL 78 MW 292 km offshore electrification 2010
Authorized licensed use limited to: Hochschule Hannover. Downloaded on July 08,2024 at 10:44:50 UTC from IEEE Xplore. Restrictions apply.
Table 2 Comparison of classical HVDC and VSC-HVDC allows the System Operators to utilize more economic and less
Attributes Classical HVDC VSC-HVDC pollutant generation resources and implement effective
Converter Thyristor valve, Transistor valve congestion management strategies.
technology grid commutation (IGBT), self
commutation Fast Response to Disturbances – Fast control of active and
Max converter 6400 MW, ±800 1200 MW, ±320 reactive power of VSC-HVDC systems can improve power
rating at present kV (overhead line) kV (cable) grid dynamic performance under disturbances. For example, if
Relative size 4 1 a severe disturbance threatens system transient stability, fast
Typical delivery 36 months 24 months power run-back and even instant power reversal control
time functions can be used to help maintain synchronized power
Active power flow Continuous ±0.1Pr Continuous 0 to grid operation. VSC-HVDC systems can also provide
control to ±Pr (Due to the ±Pr effective damping to mitigate electromechanical oscillations
change of polarity, by active and reactive power modulation.
normally changing Multiterminal Configurations – Another advantage is that
the power
the power direction is changed by changing the direction of
direction takes
the current and not by changing the polarity of the dc voltage.
some time, which
This makes it easier to build VSC-HVDC systems of more
is not the case for
VSC-HVDC) than a few terminals. These terminals can be connected to
Reactive power Reactive power No reactive different points in the same ac network or to different ac
demand demand = 50% power demand networks. The resulting dc grids can be radial, meshed or a
power transfer combination of both. Multiterminal VSC-HVDC systems are
Reactive power Discontinuous Continuous particularly attractive for integration of large-scale renewable
compensation & control (Switched control (PWM energy sources such as offshore wind farms and for
control shunt banks) built-in in reinforcement of interconnected regional ac grids.
converter
control) B. Prospective Applications
Independent No Yes In the following, a number of existing and likely future
control of active applications of VSC-HVDC in meshed ac grid are discussed.
& reactive power
Scheduled Typically < 1% Typically < 0,5% 1) Network Interconnections
maintenance In recent years, due to increased volumes of bulk power
transactions in competitive energy markets, some regional
Typical system 2.5 - 4.5 % 4-6% network tie lines are frequently fully loaded and thus restrict
losses the economic power transfer between adjacent regions.
Multiterminal Complex, limited Simple, no Regional interconnections enhanced through VCS-HVDC
configuration to 3 terminals limitations links can effectively improve the transfer capability between
regional networks. In addition, precise power flow control of
dc links makes the settlement of pricing power transfers,
III. AC GRID WITH EMBEDDED VSC-HVDC billing customers, and preventing free riders become
VSC-HVDC transmission technologies provide necessary uncomplicated tasks. VSC-HVDC system can also be
features for embedded applications in meshed ac grids [5]. operated as a merchant transmission facility, similar to a
The resulting hybrid AC/DC grid structure enables more merchant generator. One example is the Murry-link project
efficient congestion management, reliable integration of large- which benefits both South Australia and Victoria by enabling
scale renewable energy sources, and improved system electricity trading in Australia’s deregulating power market.
dynamic response against disturbances. Another example is the Estlink project which enables the
exchange of electric power between the national grids of
A. Technology Advantages Estonia and Finland.
The most attractive technical advantages of VSC-HVDC
2) Bottleneck Mitigations
systems for embedded applications in ac grid are power flow
Transmission congestion occurs when actual or scheduled
control flexibility, fast response to disturbances and feasible
flows of electricity across a portion of network are restricted
multiterminal configurations.
below desired levels either by physical capacity or by system
Power Flow Control Flexibility – The power flow on the operational security restrictions. Transmission bottlenecks
VSC-HVDC systems can be optimally scheduled based on have resulted in consumers of some areas paying higher prices
system economics and security requirements. It is also feasible for electricity and system reliability concerns. In many cases,
to dispatch VSC-HVDC systems in real-time power grid the capacity of ac lines comprising the bottleneck is not fully
operations. Such increased power flow control flexibility utilized because of stability concerns. VSC-HVDC system
Authorized licensed use limited to: Hochschule Hannover. Downloaded on July 08,2024 at 10:44:50 UTC from IEEE Xplore. Restrictions apply.
may be a desirable solution in comparison with ac short circuit levels. The feasibility of direct dc infeed to large
alternatives. It has been shown in system studies that the urban areas has been discussed in [8]. Figure 4 shows the two
transfer capability of those voltage or transient stability envisioned city infeed schemes with VSC-HVDC system. In
constrained bottlenecks can be increased by more than the one scheme, point-to-point or multiterminal VSC-HVDC
rating of the VSC-HVDC system due to effective damping system directly deliver power to in-city load pockets. Another
control and dynamic voltage support [6]. For parallel AC/DC scheme is equivalent to closing an open loop of ac circuit
transmission schemes, full power flow controllability of VSC- which gives extended system without increasing the short
HVDC system allows optimized power sharing between ac circuit power. Figure 5 shows a version of multiterminal
lines and dc link. VSC-HVDC network that is embedded in the existing city
power grid. Power is fed from transmission grid radially from
3) Integration of Renewable Energy Sources
different sources and distributed through a dc-cable ring to the
With several GWs of offshore wind generation now in the
inverter stations located at different load pockets.
advanced stages of planning, particularly in Europe, the
demand for reliable and robust power transmission to shore is
now a fact. In this case, VSC-HVDC is the most appropriate
duo to compact converter station and flexible voltage and
frequency control [2, 7]. Figure 3 shows the converter station
at sea in the Nord E.ON 1project where 400 MW wind power
will be transmitted from the North Sea to Northern Germany,
a distance of 200 km. VSC-HVDC transmission allows
efficient use of long-distance land or submarine cables.
Authorized licensed use limited to: Hochschule Hannover. Downloaded on July 08,2024 at 10:44:50 UTC from IEEE Xplore. Restrictions apply.
IV. WAMS ENHANCED VSC-HVDC SYSTEMS damping via injecting modulated voltage signals in the
converter voltage control circuit. The feedback signal could
A. WAMS Enabled VSC-HVDC Control come from any desired ac quantity based on observability
A broad range of application control functions can be analysis. Logically, both P and Q could be modulated
implemented in VSC-HVDC systems for enhancement of ac concurrently to achieve a more effective means of damping
network steady-state and dynamic performance. These control oscillations. Embedded VSC-HVDC could damp both local
functions are shown in Figure 6 by three categories along the and inter-area modes of oscillations. In the latter, the
time line for a disturbance that is pre-disturbance, transient feedback signal could come from remote synchrophasor
and post-disturbance. measurements of bus voltage angles from a wide area
measurement system such as depicted in Figure 8.
Wide area measurement systems could enhance the Figure 8 WAMS enabled control for oscillation damping
performance of VSC-HVDC systems by providing the
necessary remote measurements to initiate effective control
for transfer capability improvement and against disturbances C. WAMS Enabled Control for Maximum Power Transfer
such as power oscillations. A wide area measurement system, A system with voltage stability limits along a transmission
as shown in Figure 7, consists of phasor measurement units corridor experience congestion due to accompanying
deployed at geographically dispersed locations in the system transmission constraint. Embedded VSC-HVDC provides
[10]. The phasors are collected and aligned by a phasor data countermeasures for both transient and longer term voltage
concentrator. WAMS applications range from monitoring instability mechanisms. Fast modulation of its reactive power
such as state estimation and voltage security monitoring to could provide the VAR requirements for the transient
wide area control such as power oscillations damping. problem. In the longer term instability, where tap-changers,
excitation system responses come into play, VSC-HVDC can
help prevent voltage collapse via gradual P and Q modulation,
including reducing active power to increase reactive power
nal
PMU PMU
capability if needed. By operating the converter as an SVC or
Si g
Authorized licensed use limited to: Hochschule Hannover. Downloaded on July 08,2024 at 10:44:50 UTC from IEEE Xplore. Restrictions apply.
Figure 9 shows an example transmission corridor VII. BIOGRAPHIES
configuration with VSC-HVDC infeed into a weak load area Jiuping Pan received his B.S. and M.S. in Electric Power Engineering from
constrained by loadability limits. A direct Q injection or Shandong University, China and his Ph.D. in Electrical Engineering from
Virginia Tech, USA. He is currently a Principal Scientist with ABB US
voltage control from VSC-HVDC will increase real power Corporate Research Center. Prior to joining ABB, He was with the faculty of
into the area by providing local reactive power support. Electric Power Engineering Department of Shandong University in China.
From 1993 to 1995, He was a visiting scholar at the Center of Energy and
Similarly, the same effect could be achieved by modulating Global Environment at Virginia Tech USA. His expertise includes power
the local voltage. Alternatively, increased corridor transfer system modeling, HVDC transmission, transmission planning, T&D asset
capability could be achieved by modulating both P and Q management, energy market simulation studies.
injections from the VSC-HVDC. To realize this maximum Reynaldo F. Nuqui received his Ph.D. in Electrical Engineering from
Virginia Tech in 2001. He graduated from the University of the Philippines
power transfer scheme requires measurement of the bus with BS and MS degrees in Electrical Engineering. He is a Principal Scientist
voltage angle difference by phasor measurement units in bus 1 with ABB US Corporate Research Center in Raleigh, NC USA. Previously, he
and bus 2. Any status change in the ac transmission infeed was employed by the National Power Corporation in several positions related
to transmission planning, system operations and protection. His research
would automatically be reflected as a change in the phasor
interests are synchronized phasor measurements, High Voltage Direct Current
angle. With this angle as reference point, we could adjust P Transmission, protection, voltage stability, and state estimation. Dr. Nuqui is
and Q to achieve maximum power transfer. a member of the IEEE Power Engineering Society and the North American
Synchrophasor Initiative Working Group.
Kailash Srivastava was born at Fatehpur in India, on October 3, 1962. He
V. CONCLUSIONS graduated in Electrical Engineering from MMM Engineering College
VSC-HVDC technology is now emerging as a robust and Gorakhpur (India) in 1983 He did his MTech and PhD in Power Systems from
IIT Kanpur (India) in 1986 and 1995 respectively. He worked in India and
economical alternative for future transmission grid expansion. Italy for different companies before joining ABB Corporate Research Sweden
In particular, embedded VSC-HVDC applications, together where he has been working for past 11 years.
with the wide area measurement system, in meshed AC grids Tomas Jonsson received his M. Sc. degree in Electrical Engineering from the
could significantly improve overall system performance, Lund Institute of Technology in 1987. He has been employed by ABB in
enabling smart operation of transmission grids with improved Ludvika and Västerås since 1988. From the year 1988 to 1993 he was working
with control system design, system studies and commissioning related to
security and efficiency. VSC-HVDC transmission also offers HVDC systems. Between 1993 and 1999, he worked with development of
a superior solution for many challenging technical issues capacitor commutated and voltage source converters for HVDC. Since 1999,
associated with integration of large-scale renewable energy he has been employed at ABB Corporate Research as HVDC expert and
sources such as offshore wind power. The technology is under project leader for power electronic development for HVDC and FACTS
applications.
continuous development rapidly into higher voltage, higher
power and more flexibility. Per Holmberg received his M.Sc. in Electrical Engineering from the
Technical University of Chalmers, Sweden in 1986. Since then he has been
working for ABB Power Systems/HVDC with control design, digital
VI. REFERENCES simulation, technical coordination and commissioning of HVDC projects. In
[1] Mikael P. Bahrman and Brian .K. Johnson, “The ABCs of HVDC 2007 he was appointed Specialist in the field Power System Analysis and
Transmission Technologies”, IEEE Power and Energy Magazine, Control of HVDC Systems. He is presently working with dynamic
March-April 2007. performance studies for both conventional HVDC and HVDC Light®.
[2] Gunnar Asplund, “Electric Transmission System in Change”, Key Notes, Ying Jiang-Hafner received her B. Sc. And M. Sc. Degrees in electrical
IEEE Power Electronics Specialists Conference, June 2008, Rhodes, engineering from Huazhong University of Science and Technology, China,
Greece, respectively in 1984 and 1987. She received Ph. D. Degree in electrical
[3] It’s time to connect – Technical description of HVDC Light® engineering from Royal Institute of Technology (KTH) of Sweden in 1998.
technology, ABB Power Technologies AB, 2006. She joined the System Development Department of ABB Power System in
(http://www.abb.com/hvdc). Sweden in 1998. She has been involved in the development and design of
[4] Jochen Kreusel, “Integrated AC/DC Transmission Systems – Benefits of control system for HVDC Light since she joined ABB. She is now a senior
Power Electronics for Security and Sustainability of Power Supply”, specialist in the technical area of HVDC Light control.
Power System Computation Conference, July 2008, Glasgow, UK.
[5] Jiuping Pan, Reynaldo Nuqui, Le Tang and Per Holmberg, “VSC-HVDC
Control and Application in Meshed AC Networks”, Panel Paper, IEEE
PES General Meeting, July 2008, Chicago, USA.
[6] Stefan G Johansson, Gunnar Asplund, Erik Jansson, Roberto Rudervall,
“Power System Stability Benefits with VSC DC-Transmission Systems”,
CIGRE Conference, 2004, Paris, France.
[7] Peter Sandeberg and Lars Stendius, “Large scale Offshore Wind Power
Energy evacuation by HVDC Light®”, European Wind Energy
Conference & Exhibition, March-April 2008, Brussels Belgium.
[8] Bjorn Jacobson, Paulo Fischer de Toledo, and Gunnar Asplund, “City
Infeed with HVDC Light® and Extruded Cables, CEPSI, November
2006, Mumbai, India.
[9] Harrison Clark, Abdel-Aty Edris, Mohamed EI-Gasseir, Ken Epp,
Andrew Isaacs, and Dennis Woodford, Softening the Blow of
Disturbances, IEEE Power and Energy Magazine, Vol. 6, No. 1, 2008.
[10] Reynaldo. F. Nuqui, “State Estimation and Voltage Security Monitoring
Using Synchronized Phasor Measurements”, PhD Dissertation,
Department of Electrical and Computer Engineering, Virginia
Polytechnic Institute and State University, Blacksburg, VA, USA 2001.
Authorized licensed use limited to: Hochschule Hannover. Downloaded on July 08,2024 at 10:44:50 UTC from IEEE Xplore. Restrictions apply.