MTU8V1600DS400 400kW Standby

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

DIESEL GENERATOR SET

MTU 8V1600 DS400


400 kWe /60 Hz /Standby
208 - 600V

Reference MTU 8V1600 DS400 (365 kWe) for Prime Rating Technical Data

SYSTEM RATINGS
Standby
Voltage (L-L) 208V* 240V* 380V 440V 480V* 600V*
Phase 3 3 3 3 3 3
PF 0.8 0.8 0.8 0.8 0.8 0.8
Hz 60 60 60 60 60 60
kW 400 400 400 400 400 400
kVA 500 500 500 500 500 500
Amps 1388 1203 760 656 601 481
skVA@30%
Voltage Dip 800 820 640 920 1277 1100
Generator Model 572RSL4025 572RSL4025 572RSL4025 433CSL6220 433CSL6220 433PSL6248
Temp Rise 130 °C/40 °C 130 °C/40 °C 130 °C/40 °C 130 °C/40 °C 130 °C/40 °C 130 °C/40 °C
Connection 12 LEAD WYE 12 LEAD DELTA 12 LEAD WYE 12 LEAD WYE 12 LEAD WYE 4 LEAD WYE

* UL 2200 Offered

CERTIFICATIONS AND STANDARDS


// Emissions – EPA Tier 3 Certified // Performance Assurance Certification (PAC)
- Generator Set Tested to ISO 8528-5 for Transient Response
// Generator set is designed and manufactured - Verified product design, quality and performance integrity
in facilities certified to standards ISO 9001:2008 and - All engine systems are prototype and factory tested
ISO 14001:2004
// Power
Rating
// Seismic Certification – Optional - Accepts Rated Load in One Step Per NFPA 110
– IBC Certification - Permissible average power output during 24 hours of
– OSHPD Pre-Approval operation is approved up to 85%.

// UL 2200 / CSA – Optional


– UL 2200 Listed
– CSA Certified
2 / // / MTU 8V1600 DS400 (400 kWe) - Standby

STANDARD FEATURES*
// MTU Onsite Energy is a single source supplier // Generator
// Global Product Support - Brushless, Rotating Field Generator
// 2 Year Standard Warranty - 2/3 Pitch Windings
// 8V1600 Diesel Engine - 300% Short Circuit Capability with Permanent Magnet
- 14.0 Liter Displacement Generator (PMG)
- Common Rail Fuel Injection ○ PMG Standard for 570 frame and larger
- 4-Cycle ○ PMG Optional for 430 frame and smaller
// Engine-generator resilient mounted // Digital Control Panel(s)
// Complete Range of Accessories - UL Recognized, CSA Certified, NFPA 110
- Complete System Metering
- LCD Display
// Cooling System
- Integral Set-Mounted
- Engine-Driven Fan

STANDARD EQUIPMENT*
// Engine

Air Cleaners Brushless Alternator with Brushless Pilot Exciter


Oil Pump 4 Pole, Rotating Field
Oil Drain Extension and S/O Valve 130 °C Max. Standby Temperature Rise
Full Flow Oil Filters 1 Bearing, Sealed
Closed Crankcase Ventilation Flexible Coupling
Jacket Water Pump Full Amortisseur Windings
Thermostats 125% Rotor Balancing
Blower Fan and Fan Drive 3-Phase Voltage Sensing
Radiator - Unit Mounted ±0.25% Voltage Regulation (570 frame)
Electric Starting Motor - 24V ±1% Voltage Regulation (430 frame)
Governor – Electronic Isochronous 100% of Rated Load - One Step
Base - Formed Steel 5% Max. Total Harmonic Distortion
SAE Flywheel and Bell Housing
Charging Alternator - 24V
Battery Box and Cables // Digital Control Panel(s)
Flexible Fuel Connectors
Flexible Exhaust Connection Digital Metering
EPA Certified Engine Engine Parameters
Generator Protection Functions
Engine Protection
// Generator CANBus ECU Communications
Windows®-Based Software
NEMA MG1, IEEE and ANSI standards compliance for temperature rise Multilingual Capability
and motor starting Remote Communications to RDP-110 Remote Annunciator
Sustained short circuit current of up to 300% of the rated current for Programmable Input and Output Contacts
up to 10 seconds UL Recognized, CSA Certified, CE Approved
Self-Ventilated Event Recording
Superior Voltage Waveform IP 54 Front Panel Rating with Integrated Gasket
Digital, Solid State, Volts-per-Hertz Regulator NFPA110 Compatible
No Load to Full Load Regulation

* Represents standard product only. Consult Factory/MTU Onsite Energy Distributor for additional configurations.
3 / // / MTU 8V1600 DS400 (400 kWe) - Standby

APPLICATION DATA

// Engine // Fuel Consumption



Manufacturer MTU At 100% of Power Rating: L/hr (gal/hr) 109 (28.8)
Model 8V1600G80S At 75% of Power Rating: L/hr (gal/hr) 88 (23.4)
Type 4-Cycle At 50% of Power Rating: L/hr (gal/hr) 68 (18)
Arrangement 8-V
Displacement: L (Cu In) 14 (854)
Bore: cm (in) 12.2 (4.8) // Cooling - Radiator System
Stroke: cm (in) 15 (5.91)
Compression Ratio 17.5:1 Ambient Capacity of Radiator: °C (°F) 50 (122)
Rated RPM 1,800 Max. Restriction of Cooling Air: Intake
Engine Governor Electronic Isochronous (ADEC) and Discharge Side of Rad.: kPa (in. H20) 0.2 (0.8)
Max. Power: kWm (bhp) 448 (601) Water Pump Capacity: L/min (gpm) 362 (95)
Speed Regulation ±0.25% Heat Rejection to Coolant: kW (BTUM) 205 (11,658)
Air Cleaner Dry Heat Rejection to After Cooler: kW (BTUM) 120 (6,824)
Heat Radiated to Ambient: kW (BTUM) 48.1 (2,735)
Fan Power: kW (hp) 17.1 (22.9)
// Liquid Capacity (Lubrication)

Total Oil System: L (gal) 46 (12.2) // Air Requirements


Engine Jacket Water Capacity: L (gal) 50 (13.2)
System Coolant Capacity: L (gal) 80.3 (21.2) Aspirating: *m3/min (SCFM) 36 (1,271)
Air Flow Required for Rad.
Cooled Unit: *m3/min (SCFM) 510 (18,010)
// Electrical Remote Cooled Applications;
Air Flow Required for Dissipation
Electric Volts DC 24 of Radiated Generator Set Heat for a
Cold Cranking Amps Under -17.8 °C (0 °F) 1,050 Max. of 25 °F Rise: *m3/min (SCFM) 174.7 (6,169)

* Air density = 1.184 kg/m3 (0.0739 lbm/ft3)


// Fuel System

Fuel Supply Connection Size -10 JIC 37° Female // Exhaust System
M20 x 1.5 Male Adapter Provided
Fuel Return Connection Size -6 JIC 37° Female Gas Temp. (Stack): °C (°F) 466 (871)
M14 x 1.5 Male Adapter Provided Gas Volume at Stack
Max. Fuel Lift: m (ft) 5 (16) Temp: m3/min (CFM) 85.2 (3,008)
Recommended Fuel Diesel #2 Max. Allowable Back Pressure: kPa (in. H20) 15 (61)
Total Fuel Flow: L/hr (gal/hr) 402 (106)
4 / // / MTU 8V1600 DS400 (400 kWe) - Standby

WEIGHTS AND DIMENSIONS

Drawing above for illustration purposes only, based on standard open power 480 volt generator set. Lengths may vary with other voltages. Do not use for installation design. See website
for unit specific template drawings.

System Dimensions (L x W x H) Weight (dry/less tank)


Open Power Unit (OPU) 3,001 x 1,877 x 1,975 mm (118.13 x 73.88 x 77.75 in) 3,785-4,602 kg (8,343-10,146 lb)
Weights and dimensions are based on open power units and are estimates only. Consult the factory for accurate weights and dimensions for your specific generator set.

SOUND DATA

© MTU Onsite Energy. Subject to alteration due to technological advances. OE 23 545 (77 3E) 2017-02
Unit Type Standby Full Load
Level 0: Open Power Unit dB(A) 88.6
Sound data is provided at 7 m (23 ft). Generator set tested in accordance with ISO 8528-10 and with infinite exhaust.

EMISSIONS DATA RATING DEFINITIONS AND CONDITIONS


NOx + NMHC CO PM // Standby ratings apply to installations served by a reliable
5.01 0.52 0.04 utility source. The standby rating is applicable to varying
loads for the duration of a power outage. No overload
All units are in g/hp-hr and shown at 100% load capability for this rating. Ratings are in accordance with
(not comparable to EPA weighted cycle values). ISO 8528-1, ISO-3046-1, BS 5514, and AS 2789. Average
Emission levels of the engine may vary with ambient load factor: ≤ 85%.
temperature, barometric pressure, humidity, fuel type and // Deration Factor:
quality, installation parameters, measuring instrumentation, etc. Altitude: Consult your local MTU Onsite Energy Power
The data was obtained in compliance with US EPA regulations. Generation Distributor for altitude derations.
The weighted cycle value (not shown) from each engine is Temperature: Consult your local MTU Onsite Energy Power
guaranteed to be within the US EPA Standards. Generation Distributor for temperature derations.

C/F = Consult Factory/MTU Onsite Energy Distributor


N/A = Not Available

MTU Onsite Energy


A Rolls-Royce Power Systems Brand

www.mtuonsiteenergy.com