Generator Protection-SHANMUGANATHAN
Generator Protection-SHANMUGANATHAN
K, AEE/E/NCTPS-II, 11-01-2021
1
Name K.Shanmuganathan
Qualification B.E.(Distn.) & M.Tech.(Hons.)
PG Specialization Power Systems
Designation Asst. Executive Engineer/E/C&I
Posts Held AE/MRT-II/TTPS, AEE/MRT/NCTPS-I
Place of working NCTPS-II
Power System Exp. 21 years
Contact Detail [email protected]
CUG 9445858547
Self Introduction
2
References
3
Contents Introduction
Trip Logics
Classes of Tripping
System Grounding
Protection Functions
Conclusion
4
INTRODUCTION
5
Single Line Diagram of a Power System
110kV Bus
Distn. SS
21 / 400kV
400 /
Generating Station 230/110kV
Receiving SS
110 / 22kV
433V Bus
Distn.Transfo,
6
Function of Protective Relaying
Trip Logics
8
210MW Units
Class A:
Urgent isolation for in-zone abnormalities
Trips Turbine, GCB, FB & UAT Changeover
Class B:
Non Urgent isolation, for in-zone abnormalities
Trips Turbine & UAT Changeover, Time delayed trips for GCB
& FB
Class C:
Isolation for out-zone abnormalities
Trips GCB, Unit under House Load
9
Class A1:
Trips Turbine, GCB, GT HV Main & Tie Breakers, F.B &
UT Change over
Class A2:
Trips Turbine, GCB & F.B
UT in Service
Class C:
Trips GT HV Main & Tie Breakers
Unit in House Load Operation
Class D:
Trips GCB & F.B
Provided for LF & RP Protection with Turbine Trip
10
Classes of tripping
11
• Negative Phase Sequence (46G)
• Over Fluxing (24 or 99)
• GT Differential, O/C, Overall Differential (87GT, 51GT, 87QA)
• UT Differential, REF (87 , 64AUT)
• Inadvertent Energizing (50/27)
• Backup Impedance (21G)
• GCB LBB (50LBB)
• Neutral over current (51NGT)
• LV Backup E/F (51N)
• GT Mechanical Protections (PRV, SPRV,OLTC, Buchholz, Fire)
• UT Mechanical Protections (PRV, OLTC, Buchholz, Fire)
12
• Stator Earth Fault ( 59N, 27TN+59N, 59X+59N, 64S)
• Rotor Earth Fault (64F or 100F)
• Over Voltage (59G)
• Under Voltage (27G)
• Over Fluxing (24 or 99)
• Loss of Excitation (40)
• Generator Differential Protection (87G)
• Generator Inter turn fault Protection (87G)
• Reverse Power (WOTT) (32G)
• Low Forward (WOTT) (37)
13
• Negative Phase Sequence
(46G)
• Pole Slipping (78G)
• Under Frequency (81GUF)
• GT Backup E/F (51NGT)
• GT OT & WT Protection
14
Protection Overview
15
16
17
18
19
20
21
22
23
System Grounding
24
Vrg = Vrn + Vng
Vyg = Vyn + Vng
Vbg = Vbn + Vng
V0 = (Vrg + Vyg + Vbg) / 3
V0 = Vng = Zero Seq. Voltage
25
26
27
28
29
• To reduce the stator fault current & over voltages while
detecting ground fault condition quickly enough to
prevent core burning
30
Protection Functions
31
32
Neutral Over Voltage (95% Stator winding E/F
Protection)
33
100% Stator winding E/F protection using 27TN + 59N
35
100% Stator winding E/F protection using Sub harmonic
injection 64S
36
37
The basic of the rotor is to
produce a magnetic field of
the size and shape
necessary to induce
desired voltage in stator
The magnetic flux radiates
from rotor and follows the
magnetic circuit across the
air gap, stator core back
across air gap again into
the rotor
Field winding provides
path for the DC current
needed to magnetize the
field
38
Due to deterioration of rotor
conductor, turn to turn
insulation rotor E/F is
created
If a large portion of winding
is short circuited in 2nd E/F,
the flux may concentrate on
one pole and widely
dispersed over the other
and results in unbalanced
force.
This may cause violent
vibration, bearing surface
damage even possible for a
rotor foul to stator
39
Low frequency injection technique
A DC voltage injected into the rotor circuit, the polarity of
the voltage is reversed at low frequencies (0.25 Hz to 1 Hz)
The voltage source is symmetrically coupled to the
excitation circuit via high resistance resistors. It is also
connected to the earthing brush of the rotor via a low
resistance measuring shunt
Every time the DC voltage is reversed in polarity, a
charging current is applied due capacitance of the rotor
windings to earth
Under no fault conditions, the charging current should be
discharged to zero
When a rotor earth fault occurs, the steady state current
will no longer be zero, the magnitude of which can then be
used to calculate the fault resistance
40
41
42
43
44
1. Biased differential protection
• The through current is used to increase the setting
of the differential element
• Through current is calculated as the average sum of
the current entering and leaving the zone
51
52
53
54
Most common causes for generator unbalance currents
are system asymmetries, unbalanced loads, unbalanced
system faults & open circuits
Highest source of NPS component is generator Ph-Ph
faults
NPS current creates double frequency flux will create
Eddy current at the surface of the pole face, teeth and
retaining rings
This protection protects rotor of the generator from
damage resulting from heating effects of NPS currents
Also Act as a backup protection for uncleared
asymmetric faults
55
O/V in generator may occur due to
1. Transient Surges
Created by Switching and atmospheric
disturbances of transmission system
2. Sustained power frequency O/V
Mal operation of AVR when the m/c in isolated
operation
Sudden variation load while Man mode AVR
Sudden loss of load
56
How to protect?
1. Transient Surges
Shunt gaps, surge diverters, stator slot surge
capacitors
57
E = 4.44 X f X A X N X Bm X 10 ‾ ⁸
Bm α E / f
58
Effects
59
60
Causes
Case Study
64
65
What is LOE?
When excitation is reduced or lost generator
absorbs reactive power from grid and operates in
the under excitation region of Capability Curve
Generator may run as induction generator for total
loss of field
This change is not instantaneous but occurs over a
time period ( generally in seconds)
Causes of LOE?
Field open circuit
Field short circuit
Accidental tripping of FB
AVR control failure
66
Effects of LOE?
67
68
Protection Scheme
69
Typically occurs under prolonged fault condition which
cause a transient torque on the generator which
exceeds the ability of the field to hold the rotor
synchronized with stator
More possibility when system fault happens during
under excitation operation
“Pole Slip” occurs when rotor experience sudden
physical electrical shift in position relative to stator
Creates violent acceleration and deceleration leads to
enormous stress on generator and prime mover
Can even cause winding movement & shaft fracture if
left unprotected
70
Methods of protection
71
Methods of protection
Using lenticular
characteristics by
measuring impedance of
the generator and using
lenticular impedance
characteristics
Normal operation in zone
R1
During pole slip,
impedance locus
traverse through zones
R2, R3 & R4
When entering zone R4
trip signal is issued
72
73
Reverse power protection is applied to prevent
77
Protection schemes
Using loss of excitation, reverse power,
NPS, breaker failure & system backup
relays
78
CONCLUSION
79
80
81