0% found this document useful (0 votes)
15 views81 pages

Generator Protection-SHANMUGANATHAN

210MW Turbo Generator Protection Scheme

Uploaded by

udayakumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views81 pages

Generator Protection-SHANMUGANATHAN

210MW Turbo Generator Protection Scheme

Uploaded by

udayakumar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 81

Shanmuga Nathan.

K, AEE/E/NCTPS-II, 11-01-2021

1
Name K.Shanmuganathan
Qualification B.E.(Distn.) & M.Tech.(Hons.)
PG Specialization Power Systems
Designation Asst. Executive Engineer/E/C&I
Posts Held AE/MRT-II/TTPS, AEE/MRT/NCTPS-I
Place of working NCTPS-II
Power System Exp. 21 years
Contact Detail [email protected]
CUG 9445858547

Self Introduction

2
References

1. TD on Generator Protection - Er.A.Krishnavel EE/MRT-II/TTPS

2. ALSTOM MICOM P34X - Technical Manual

3. Network Protection & Automation Guide – ALSTOM

4. The Art & Science of Protective Relaying – C.Russell Mason

5. Protective Relaying Theory and Applications – Walter A. Elmore

3
Contents Introduction

Trip Logics

Classes of Tripping

Protection Over view

System Grounding

Protection Functions

Conclusion
4
INTRODUCTION

5
Single Line Diagram of a Power System

400kV Bus From remote end


stations / Grid
600 MW

110kV Bus
Distn. SS
21 / 400kV

400 /
Generating Station 230/110kV

Receiving SS
110 / 22kV
433V Bus

End User 22 / 0.433kV


22kV Bus
( Load)

Distn.Transfo,
6
Function of Protective Relaying
Trip Logics

8
210MW Units
Class A:
Urgent isolation for in-zone abnormalities
Trips Turbine, GCB, FB & UAT Changeover

Class B:
Non Urgent isolation, for in-zone abnormalities
Trips Turbine & UAT Changeover, Time delayed trips for GCB
& FB

Class C:
Isolation for out-zone abnormalities
Trips GCB, Unit under House Load
9
Class A1:
Trips Turbine, GCB, GT HV Main & Tie Breakers, F.B &
UT Change over
Class A2:
Trips Turbine, GCB & F.B
UT in Service
Class C:
Trips GT HV Main & Tie Breakers
Unit in House Load Operation
Class D:
Trips GCB & F.B
Provided for LF & RP Protection with Turbine Trip

10
Classes of tripping

11
• Negative Phase Sequence (46G)
• Over Fluxing (24 or 99)
• GT Differential, O/C, Overall Differential (87GT, 51GT, 87QA)
• UT Differential, REF (87 , 64AUT)
• Inadvertent Energizing (50/27)
• Backup Impedance (21G)
• GCB LBB (50LBB)
• Neutral over current (51NGT)
• LV Backup E/F (51N)
• GT Mechanical Protections (PRV, SPRV,OLTC, Buchholz, Fire)
• UT Mechanical Protections (PRV, OLTC, Buchholz, Fire)

12
• Stator Earth Fault ( 59N, 27TN+59N, 59X+59N, 64S)
• Rotor Earth Fault (64F or 100F)
• Over Voltage (59G)
• Under Voltage (27G)
• Over Fluxing (24 or 99)
• Loss of Excitation (40)
• Generator Differential Protection (87G)
• Generator Inter turn fault Protection (87G)
• Reverse Power (WOTT) (32G)
• Low Forward (WOTT) (37)

13
• Negative Phase Sequence
(46G)
• Pole Slipping (78G)
• Under Frequency (81GUF)
• GT Backup E/F (51NGT)
• GT OT & WT Protection

• Reverse Power (WTT) (32G)


• Low Forward (WTT) (37)

14
Protection Overview

15
16
17
18
19
20
21
22
23
System Grounding

24
Vrg = Vrn + Vng
Vyg = Vyn + Vng
Vbg = Vbn + Vng
V0 = (Vrg + Vyg + Vbg) / 3
V0 = Vng = Zero Seq. Voltage

25
26
27
28
29
• To reduce the stator fault current & over voltages while
detecting ground fault condition quickly enough to
prevent core burning

• Our generators are high impedance grounded through


distribution transformer whose secondary is shunted
with reactor/resistor

• This reactor will neutralize the generator system zero


sequence capacitive reactance

30
Protection Functions

31
32
 Neutral Over Voltage (95% Stator winding E/F
Protection)

 Monitoring of Zero sequence voltage across the


grounding reactor is used for this over voltage
protection element
 This relay insensitive to third harmonic voltages
present in the neutral
 This protection roughly covers 95% of stator
winding depending upon the location of the winding
fault
 This will not cover 0-5% of winding as neutral to
ground faults will not produce phase shift

33
 100% Stator winding E/F protection using 27TN + 59N

 3rd harmonic voltages are generated in the stator


winding due to non-linearity in the generator.
 Due to this circulation of 3rd harmonic capacitive
charging currents resulting in 3rd harmonic voltage
appearing between ground and neutral of the
generator
 For a ground fault the 3rd harmonic voltage at the
neutral becomes zero and amount varies depend
upon the fault location
 This protection can provide adequate coverage for 0
– 30% of the stator winding measured from the
neutral
34
 100% Stator winding E/F protection using 3rd harmonic
ROV 59X + 59N

 For a fault near neutral, level of 3rd harmonic voltage


at the generator terminal increases
 Over voltage relay detecting 3rd harmonic voltage
level at the terminals of the generator is employed
 The residual voltage at the generator terminals is
supplied by the Wye grounded open delta VTs.
 This voltage is passed through 150Hz tuned filter
and an over voltage detector

35
 100% Stator winding E/F protection using Sub harmonic
injection 64S

 Entire stator winding of a generator is protected by


deploying signal injection equipment to inject a low
frequency current (generally at 12.5Hz or 20Hz)
between the stator star point and earth
 An earth fault at any winding location will result in
the flow of a measurable injection current to cause
protection operation
 This form of protection can also provide earth fault
protection when the generator is at standstill, prior
to run-up

36
37
 The basic of the rotor is to
produce a magnetic field of
the size and shape
necessary to induce
desired voltage in stator
 The magnetic flux radiates
from rotor and follows the
magnetic circuit across the
air gap, stator core back
across air gap again into
the rotor
 Field winding provides
path for the DC current
needed to magnetize the
field

38
 Due to deterioration of rotor
conductor, turn to turn
insulation rotor E/F is
created
 If a large portion of winding
is short circuited in 2nd E/F,
the flux may concentrate on
one pole and widely
dispersed over the other
and results in unbalanced
force.
 This may cause violent
vibration, bearing surface
damage even possible for a
rotor foul to stator

39
Low frequency injection technique
A DC voltage injected into the rotor circuit, the polarity of
the voltage is reversed at low frequencies (0.25 Hz to 1 Hz)
The voltage source is symmetrically coupled to the
excitation circuit via high resistance resistors. It is also
connected to the earthing brush of the rotor via a low
resistance measuring shunt
Every time the DC voltage is reversed in polarity, a
charging current is applied due capacitance of the rotor
windings to earth
Under no fault conditions, the charging current should be
discharged to zero
When a rotor earth fault occurs, the steady state current
will no longer be zero, the magnitude of which can then be
used to calculate the fault resistance
40
41
42
43
44
1. Biased differential protection
• The through current is used to increase the setting
of the differential element
• Through current is calculated as the average sum of
the current entering and leaving the zone

2. High Impedance differential protection


• Based on the consideration of saturation of one side
CT for external fault
• The secondary current produced by healthy CT
flows through the saturated CT
• The maximum voltage across the relay circuit equals
to the Secondary Fault Current X Connected
Impedance
45
46
47
48
49
50
• Possibility of winding inter turn fault for multi-turn
stator windings
• Detection with conventional protection arrangement is
difficult otherwise the fault becomes stator E/F
• Types
1) Protection using Separate CTs
2) Protection using core balance CTs

51
52
53
54
 Most common causes for generator unbalance currents
are system asymmetries, unbalanced loads, unbalanced
system faults & open circuits
 Highest source of NPS component is generator Ph-Ph
faults
 NPS current creates double frequency flux will create
Eddy current at the surface of the pole face, teeth and
retaining rings
 This protection protects rotor of the generator from
damage resulting from heating effects of NPS currents
 Also Act as a backup protection for uncleared
asymmetric faults

55
 O/V in generator may occur due to
1. Transient Surges
 Created by Switching and atmospheric
disturbances of transmission system
2. Sustained power frequency O/V
 Mal operation of AVR when the m/c in isolated
operation
 Sudden variation load while Man mode AVR
 Sudden loss of load

 Will lead to Generator insulation failure

56
 How to protect?

1. Transient Surges
 Shunt gaps, surge diverters, stator slot surge
capacitors

2. Sustained power frequency O/V


 Time delayed power frequency O/V protection
either IDMTL or DTL elements
 Highset element with Flat Frequency Response

57
 E = 4.44 X f X A X N X Bm X 10 ‾ ⁸

 E – induced rms voltage in volts, f – frequncy in herts,


A - cross sectional area of the core in sq inch, N- No. of
turns, Bm – flux density in maxwell / sq inch

 Bm α E / f

 Condition when V/f ratio exceeds permissible limit is


called as overfluxing or overexcitation

58
 Effects

 Hysteresis and eddy current losses are each


proportional to the power of flux density
 Core saturates due to high flux density and results
in stray flux occurring in components not designed
to carry it leading to thermal stress
 Eddy currents also cause interlaminar voltages
which further degrade the insulation and results in
severe iron damage
 Sustained O/F can arise during run up if excitation is
applied too early

59
60
 Causes

 Attempt to maintain rated voltage during coast-down


 Keeping manual excitation at fixed level during
acceleration
 Loss of AVR voltage feedback due to reference VT
problem
 Most frequently occurs during unit is offline, prior to
synchronization & operator manually prepares unit
for synchronization
 Possibility during Auto synchronization also
 Sudden loss of nearby generators or inter
connection
61
62
63
 Protection schemes

 Inverse time volts per hertz relaying


 Two stage DTL & IDMTL relaying is recommended

 Case Study

 HOUSE LOAD OPERATION – TURBINE TRIP, FB


TRIP…?

64
65
 What is LOE?
 When excitation is reduced or lost generator
absorbs reactive power from grid and operates in
the under excitation region of Capability Curve
 Generator may run as induction generator for total
loss of field
 This change is not instantaneous but occurs over a
time period ( generally in seconds)
 Causes of LOE?
 Field open circuit
 Field short circuit
 Accidental tripping of FB
 AVR control failure
66
 Effects of LOE?

 Induction generator mode of operation will act as a


large reactive drain and causes problem to the
adjacent units
 Higher speed will create slip induced eddy currents
in field winding, rotor body, wedges& retaining rings
 Can overload and heat stator winding also due to
high reactive current
 Loss as well as draining of reactive power will cause
wide voltage collapse & power swings in the power
system

67
68
 Protection Scheme

 Using off-set MHO


type distance relays
sensing the stator
current raise ,
terminal voltage
drop and change in
power factor

69
 Typically occurs under prolonged fault condition which
cause a transient torque on the generator which
exceeds the ability of the field to hold the rotor
synchronized with stator
 More possibility when system fault happens during
under excitation operation
 “Pole Slip” occurs when rotor experience sudden
physical electrical shift in position relative to stator
 Creates violent acceleration and deceleration leads to
enormous stress on generator and prime mover
 Can even cause winding movement & shaft fracture if
left unprotected

70
 Methods of protection

 Using straight line ohm


characteristics
 Normal operation the
generator lies in zone A
 During pole slip, the
impedance traverses zone
B and C and tripping
occurs when the
impedance characteristics
enters zone C

71
 Methods of protection
 Using lenticular
characteristics by
measuring impedance of
the generator and using
lenticular impedance
characteristics
 Normal operation in zone
R1
 During pole slip,
impedance locus
traverse through zones
R2, R3 & R4
 When entering zone R4
trip signal is issued
72
73
 Reverse power protection is applied to prevent

damage to mechanical plant items in the event of


failure of the prime mover

 The reverse power protection should be provided


with a definite time delay on operation to prevent
spurious operation with transient power swings that
may arise following synchronisation or in the event of
a power transmission system disturbance
74
It is not good practice to open the main circuit
breaker simultaneously with tripping of the prime
mover for non-urgent trips

This is to minimize the risk of plant overspeeding


when the electrical load is removed from a high-speed
cylindrical rotor generator

For a steam turbine there is a risk of overspeeding


due to energy storage in the trapped steam, after
steam valve tripping, or in the event that the steam
valve(s) do not fully close for some reason
75
 Need
 Accidental energization of generator while off-bar on
barring gear or coasting down
 Generator behaves as induction motor, can be
damaged within few seconds
 Turbine damage also occurs
 Complete destruction costs repair and replacement
and purchase of power
 Causes
 Operating errors
 Breaker head flashovers
 Control circuit malfunctions
 Complex schemes like 1.5 breaker, ring bus…
76
 Response of generator
 During 3-ph energization at standstill, a rotating flux
at synchronous frequency is induced in the
generator rotor
 The resulting rotor current is forced to flow in rotor
body and damper windings causing rapid thermal
heating
 If the generator is connected to strong system,
initial stator current range will be 3-4 times, voltage
in 50-70%
 If the generator is connected to weak system, initial
stator current range will be 1-2 times, voltage in 20-
40%

77
 Protection schemes
 Using loss of excitation, reverse power,
NPS, breaker failure & system backup
relays

 Dedicated protection system using over


current and under voltage elements

78
CONCLUSION

79
80
81

You might also like