984 and 800 IO Spec Guide
984 and 800 IO Spec Guide
984 Programmable
Logic Controllers and
800-Series Input/Output
Modules
3-1
Benefits of a Full Range, High Performance Family of PLCs
When selecting a PLC system to meet your automation strategy, The Modicon 984 Family helps achieve your goals by offering a
you have three main goals: full range of high performance, compatible control products.
They are full range, providing control solutions for applications
1. Minimize investment to get your system up and running. requiring 1.5k to 64k of logic memory and 256 to 16,384 discrete
I/O points. They provide high performance: 984s solve logic
Many costs are not apparent during system specification, but faster than any other full range of programmable logic control-
appear in training, start-up, and upgrades. With a compatible lers. They are compatible: 984s share common I/O modules,
family, you not only reduce costs, you speed system start-up, base instruction sets, programmers, and programming software.
giving you a faster return on investment.
2. Minimize risk of obsolescence when your automation
needs change.
3-3
Family Compatibility
A family of compatible PLCs reduces some of the “hidden” Easier System Upgrades
costs of automating. These are the costs that really add up
throughout the life cycle of your automation system — costs As your system grows, the control system must also grow. You
incurred when there are delays in training your staff, starting-up may need to enhance the system to provide better diagnostics,
your system, or upgrading. improve report generation, or monitor and control more I/O.
System growth requires more memory, more I/O or both, which
Reduce Training Costs can mean replacing the PLC, reprogramming the logic, and
even replacing the I/O system.
To implement a successful control system, programmers,
control engineers, and installation personnel must thoroughly All 984s share common software and base instruction sets.
understand the system.
If you need a larger 984 controller, you can load all or part of the
Training is necessary, but not always productive. Training costs existing program into the new 984. Then you install additional
accumulate when you consider the cost of initial training I/O, program additional logic, and your system is up and running.
(courses and related expenses), time away from productive
work, and the time it takes to become proficient. Most 984s can accommodate growing memory requirements
through modular memory upgrades. This feature eliminates
With Schneider Automation's Modicon 984 Family, your some controller replacements, giving you significant savings
personnel learn only one base instruction set, one system when you must add memory to a system.
architecture, and one set of programming software. They apply
the same skills to the full range of 984 sizes. They become Thus, the 984 Family reduces your risk during initial system
experts at designing, programming, installing, and maintaining specification and reduces development time and equipment
the system. costs associated with upgrades.
You invest in all the costs associated with training just once.
This adds up to significant savings.
Speed System Start-up
Our 984 products have common features to help you save the
time and money associated with designing, installing,
programming, and debugging a new control system.
With the 984's software libraries, you program and debug
commonly used functions once. Our software tools allow your
engineers to develop libraries of programs for control,
diagnostics, alarming, and recipe loading. You can easily
incorporate these libraries into new systems, saving
development and start-up time.
The quicker the start-up, the quicker you produce products,
giving you a faster return on investment.
3-4
Invest in the Family Concept Without
Compromising Performance
With scans ranging from .75 ... 5 ms/k, our 984s solve logic
faster than any other full family of PLCs. A high-speed remote
I/O network communicates at 1.5 megabits per second. Fast
logic solving and fast I/O servicing optimize machine or process
throughput for better system performance.
Powerful Instructions Support Applications
Throughout the Plant
3-5
984 Functional Overview
3-6
Communications
Peripheral devices, such as programming panels or host
computers, may be connected directly to a 984 PLC through
built-in Modbus ports, standard on every 984 PLC. Modbus is
an RS 232 based communication protocol used for data
acquisition, program editing, and archiving operations.
Most 984s include communication ports to link up to Modbus
Plus. Modbus Plus is a peer-to-peer, token-bus network with a
speed of one megabit per second. Modbus Plus supports data
application and programming operations. For more information
on communications, refer to the Section 7 - Networking.
Most 984 PLCs also have ports to support ASCII communications.
For more information on ASCII communications, refer to the I/O
portion of this Section.
3-7
Range of 984 Performance
User Data Discrete I/O Register I/O Local Local Remote Scan Modbus Modbus-
Controller Type Memory Memory Points (Max.) (Max.) Drops Housings Drops Time Ports Plus Ports
3-8
Optional Processors Increase Performance
Many 984 PLCs support option modules that further extend the
flexibility and performance of your control system. The options
available include networking with Modbus and Modbus Plus;
support for distributed control and hot-standby configurations;
and coprocessing.
The following chart identifies the options and the PLCs that
support them.
Options
PC-A984-120 X
PC-A984-130 X
PC-A984-131 X
PC-A984-141 X
PC-A984-145 X X
PC-E984-241 X
PC-E984-245 X X
PC-E984-251 X
PC-E984-255 X X
PC-E984-381 X X
PC-E984-385 X X X
PC-D984-385 X X X
PC-E984-480 X X
PC-K984-485 X X X
PC-E984-485 X X X
PC-E984-685 X X X X X X
PC-D984-785 X X X X X X
PC-K984-785 X X X X X X
PC-E984-785 X X X X X X
P1-984X-008 X X X X X
Px-984A-xxx X X X X X
Px-984B-xxx X X X X X
AM-0984-AT2 X X
AM-0984-AT4 X X
AM-0984-MC0 X
AM-0984-VM0 X
AM-0984-VM4 X X
Note: For information on the communication options, see the Communication Section. For information on remote input/output processing, see the
section on Configuring A Remote I/O System in the 800 Series I/O section. For other options, see the appropriate PLC description.
3-9
984 Instruction Set
Slot-Mount Chassis-Mount
Optional Optional
Category Instructions Included Loadables Included Loadables
Contacts NO, NC, Pos Trans, Neg Trans X X
Coils Normal, Latch X X
Timers 1.0, 0.1, 0.01 Sec X X
Counters Up/Down X X
Arithmetic (4-digit) Add, Sub, Mult, Div X X
Sq Root, Process Sq Root, X X
Log, Anti-log
Arithmetic (Dbl Prec) Add, Sub, Mult, Div X X
Arithmetic (Fl Pt) Add, Sub, Mult, Div, Comp, X
Sq Root, Log, Natural Log,
Exponential
Trig Sin, Cos, Tan, Arcsin, X
Arccos, Arctan
Math Conv. Fl Pt->Int, Int->Fl Pt, Deg->Rad, X
Deg->Rad, Change Sign
Move Reg->Table, Table->Reg, X X
Table->Table, Block Move,
Search, First In, First Out
Table->Block, Block->Table X X
Subroutines Jump to Sub, Lavel, Return X
Drum Sequencer Drum, Input Compare X X
Matrix And, Or, XOR, Somplement, X X
Compare
Bit Bit Modify, Bit Sense, Bit Rotate X X
ASCII Read, Write X1 X
Diagnostics Status X X
Event Alarm Recording X X
Scan Ops Skip Network(s), Constant Sweep, X X
Single Sweep, Segment Scheduler
Other PID X X
Checksum X2 X2
Modbus Plus (MSTR) X3 X3
Custom Loadable X
Option Processor Hot Standby (HSBY) X4 X
Support C996 DOS CoPro (CALL) X4
C986 CoPro (CALL) X
Process Control A_IN, ALARM, A_OUT, AVER, X5
Function Library CALC, EQN, DELAY, FNGEN,
(PCFL) INTEG, LIMIT, L_LAG, LIM_V,
MODE, ONOFF, PID, RAMP,
RMPLN, RATE, SEL
16 Bit Math TEST, AD16, SU16, MU16, DV16, X5
ITOF, FTOI
1. Available in controllers which support remote I/O capability (984-48x, 685, 785)
2. Available in controllers without built-in Modbus Plus support
3. Available in controllers with built-in or optional Modbus Plus support (these controllers do not support Checksum function)
4. Available in controllers which support option processors (984-685, 785)
5. Available in the 685 and 785 only.
3-10
Compact ModConnect
Optional Optional
Category Instructions Included Loadables Included Loadables
Contacts NO, NC, Pos Trans, X X
Neg Trans
Coils Normal, Latch X X
Timers 1.0, 0.1, 0.01 Sec X X
Counters Up/Down X X
Arithmetic (4-digit) Add, Sub, Mult, Div X X
Sq Root, Process Sq Root, X X
Log, Anti-log
Arithmetic (Dbl Prec) Add, Sub, Mult, Div X X
Arithmetic (Fl Pt) Add, Sub, Mult, Div, X X
Comp, Sq Root, Log,
Natural Log, Exponential
Trig Sin, Cos, Tan, Arcsin, X X
Arccos, Arctan
Math Conv. Fl Pt->Int, Int->Fl Pt, X X
Deg->Rad, Rad->Deg,
Change Sign
Move Reg->Table, Table->Reg, X X
Table->Table,
Block Move, Search,
First In, First Out
Table->Block, X X
Block->Table
Subroutines Jump to Sub, Lavel, X X
Return
Drum Sequencer Drum, Input Compare X X
Matrix And, Or, XOR, X X
Complement, Compare
Bit Bit Modify, Bit Sense, X X
Bit Rotate
ASCII Read, Write X
Diagnostics Status X X
Event Alarm Recording X X
Scan Ops Skip Network(s), X X
Constant Sweep,
Single Sweep,
Segment Scheduler
Other PID X X
Checksum X1
Modbus Plus (MSTR) X2 X
Custom Loadable X X
Option Processor Support Hot Standby (HSBY)
C996 DOS CoPro (CALL)
C986 CoPro (CALL)
1. Available in controllers without built-in Modbus Plus support
2. Available in controllers with built-in or optional Modbus Plus support (these controllers do not support Checksum function)
3-11
984 PLCs – Individual Product Descriptions
3-12
984 Slot-Mount PLCs
If you need multiple, independent Modbus Plus networks, you Each series offers up to three types of communication features.
should consider the S985-800. This optional Modbus Plus The following chart shows the three options within each series
module can also be used in redundant cable Modbus Plus and what type of application best fits the PLCs. (The 48x, 685,
configurations. This optional processor is further described in and 785 series have two or three communication ports).
Section 7: Networking. Communication
Features Applications
1 Modbus Port RS 232-based communication network
for communicating with programming
panels, man/machine interfaces, and
host computers.
2 Modbus Ports RS 232-based communication network as
above. Multiple ports allow simultaneous
access to multiple hosts.
1 Modbus Port, Allows both RS 232-based communication
1 Modbus Plus Port (Modbus) and high speed, peer-to-peer
or: networking between multiple PLCs, man
2 Modbus Ports, machine interfaces, and host computers.
1 Modbus Plus Port Good for applications requiring high data
throughput.
To decide which slot-mount PLC best fits your needs:
1. Choose the series that best fits your application’s input/
output configuration and memory requirements.
3-13
984-38x Series
PC-E984-381 √ √ 3
PC-E984-385 √ √ √ 3
PC-D984-385 √ √ √ 3
3-14
Local I/O
Architecture
Memory
User logic 16k 16k 16k
Registers 1920 1920 1920
Total 18k 18k 18k
I/O Capacity
Max. discrete I/O 512 any mix 512 any mix 512 any mix
Max. analog I/O 32 In/32 Out 32 In/32 Out 32 In/32 Out
Local I/O Capacity
Total I/O bits 512 In/512 Out 512 In/512 Out 512 In/512 Out
Total I/O racks 2 2 2
Remote I/O Capacity NA NA NA
Internal Coils
(Includes Disc I/O) 2048 2048 2048
Performance 3 ms/k 3 ms/k 3 ms/k
Communication ports 2 Modbus 1 Modbus 1 Modbus
1 Modbus Plus 1 Modbus Plus
Electrical
Power Supply
Input voltage 115 Vac 115 Vac 125 Vdc
230 Vac 230 Vac
24 Vdc 24 Vdc 24 Vdc
I/O power capacity 3 amps 3 amps 3 amps
Environmental
Temperature 0 ... 60˚C 0 ... 60˚C 0 ... 60˚C
Humidity 0 ... 95% 0 ... 95% 0 ... 95%
Shock resistance 10G (11 ms) 10G (11 ms) 10G (11 ms)
Physical
Dimensions
WxHxD 2.54 x 10.5 x 8 in 2.54 x 10.5 x 8 in 2.54 x 10.5 x 8 in
(39.4 x 266 x 203 mm) (39.4 x 266 x 203mm) (39.4 x 266 x 203mm)
Space Requirements Slot 1 in H8xx-20x Slot 1 in H8xx-20x Slot 1 in H8xx-20x
3-15
984-48x Series
PC-E984-480 √ 3
PC-K984-485 √ √ 3 √
PC-E984-485 √ √ 3
3-16
984-48x Technical Specifications
Architecture
Memory
User logic 16k 16k 16k
Registers 1920 1920 1920
Total 18k 18k 18k
I/O Capacity
Max. discrete I/O 2048 any mix 2048 any mix 2048 any mix
Max. analog I/O 224 In/224 Out 224 In/224 Out 224 In/224 Out
Local I/O Capacity
Total I/O bits 512 In/512 Out 512 In/512 Out 512 In/512 Out
Total I/O racks 2 2 2
Remote I/O Capacity
Max. I/O bits per drop 512 In/512 Out 512 In/512 Out 512 In/512 Out
Max. # drops 6 6 6
Total I/O bits 3584 In/ 3584 Out 3584 In/ 3584 Out 3584 In/ 3584 Out
Max. # ASCII ports 12 12 12
Internal Coils (Includes Disc. I/O) 2048 2048 2048
Performance 3 ms/k 3 ms/k 3 ms/k
Communication ports 2 Modbus 1 Modbus 1 Modbus
1 Modbus Plus 1 Modbus Plus
Key Switch No Yes No
Electrical
Power Supply
Input voltage 115 Vac 115 Vac 115 Vac
230 Vac 230 Vac 230 Vac
24 Vdc 24 Vdc 24 Vdc
I/O power capacity 3 amps 3 amps 3 amps
Environmental
Temperature 0 ... 60°C 0 ... 60°C 0 ... 60°C
Humidity 0 ... 95% 0 ... 95% 0 ... 95%
Shock resistance 10 G (11 ms) 10 G (11 ms) 10 G (11 ms)
Physical
Dimensions
WxHxD 2.54 x 10.5 x 8 in 2.54 x 10.5 x 8 in 2.54 x 10.5 x 8 in
(39.4 x 266 x 203 mm) (39.4 x 266 x 203 mm) (39.4 x 266 x 203 mm)
Space Requirements Slot 1 in H8xx-20x Slot 1 in H8xx-20x Slot 1 in H8xx-20x
housing housing housing
Weight 6.6 lbs (3.0 kg) 6.6 lbs (3.0 kg) 6.6 lbs (3.0 kg)
3-17
984-685
PC-E984-685 √ √ 1
3-18
984-685 Technical Specifications
Remote I/O
PC-E984-685 (Single Cable)
Architecture
Memory
User logic 16k
Registers 9999
Total 26k Up to Five Housings
I/O Capacity
Max. Discrete I/O 8192 In/8192 Out
Max. Analog I/O 1088 In/1088 Out
Local I/O Capacity
Total I/O Bits 1024 In/1024 Out
Total I/O Racks 5
Remote I/O Capacity
Max. I/O Bits per Drop 512 In/512 Out or 1024 In/1024 Out
Max. # Drops 31 16 Up to Five Housings Up to Five Housings
Total I/O Bits 16,384
Max. # ASCII Ports 32
Internal Coils S908 Remote I/O Network Up to 31 Drops
(Includes Disc. I/O) 8192
Performance 1 ms/k
Communication Ports 2 Modbus
1 Modbus Plus
Remote I/O
Electrical
(Dual Cable)
Power Supply
Input Voltage 115 Vac
230 Vac
24 Vdc
I/O Power Capacity 8 amps
Up to Five Housings
Environmental
Temperature 0 ... 60°C
Humidity 0 ... 95%
Shock Resistance 10 G (11 ms)
Physical
Dimensions
WxHxD 2.54 x 10.5 x 8 in Up to Five Up to Five
(39.4 x 266 x 203 mm) Housings Housings
Space Requirements Slots 1 and 2 in H8xx-209 housing
Weight 8.6 lbs (3.6 kg) S908 Remote I/O Network Up to 31 Drops
3-19
984-785 Series
PC-D984-785 √ √ √
PC-K984-785 √ √ √
PC-E984-785 √ √
3-20
984-785 Technical Specifications*
Electrical
Power Supply
Input Voltage 125 Vdc 115 Vac 115 Vac
230 Vac 230 Vac
24 Vdc 24 Vdc 24 Vdc
I/O power capacity 8 amps 7 amps 8 amps 8 amps
Environmental
Temperature 0 ... 60°C 0 ... 60°C 0 ... 60°C
Humidity 0 ... 95% 0 ... 95% 0 ... 95%
Shock Resistance 10 G (11 ms) 10 G (11 ms) 10 G (11 ms)
Physical
Dimensions, W x H x D 2.54 x 10.5 x 8 in 2.54 x 10.5 x 8 in 2.54 x 10.5 x 8 in
(39.4 x 266 x 203 mm) (39.4 x 266 x 203 mm) (39.4 x 266 x 203 mm)
Space Requirements Slots 1 and 2 in H8xx-209 Slots 1 and 2 in H8xx-209 Slots 1 and 2 in H8xx-209
housing housing housing
Weight 8.6 lbs (3.6 kg) 8.6 lbs (3.6 kg) 8.6 lbs (3.6 kg)
* A 785 upgrade kit (AM-E785-QK0) is available for 16 drop Quantum I/O, S908 network. See the S908 section on page 2-22 for details.
Remote I/O
(Single Cable) Remote I/O
Up to Five Housings
Up to Five Housings
S908 Remote I/O Network Up to 31 Drops S908 Remote I/O Network Up to 31 Drops
3-21
S908 Remote I/O Processor
3-22
S908 Technical Specifications
Power Supply
Power Supply 984-685, 785
Power Draw
+5.0 Vdc 1500 mA
+4.3 Vdc 0 mA
-5.0 Vdc 0 mA
Environmental
Operating Temperature 0 ... 60°C
Relative Humidity 0 ... 95% non-condensing
Shock Resistance 10G (11 ms)
3-23
S911-800 Hot Standby Systems For Slot-Mount PLCs
Ordering Information
3-24
S911-800 Hot Standby Technical Specifications 984 / S911 Dual Cable Hot Standby System
Configuration Information
PLCs that use S911-800 984-685/785
Environmental
Operating Temperature 0 ... 60°C
Relative Humidity 0 ... 95% non-condensing
Shock Resistance 10G (11 ms)
Physical
Space Requirements One option slot in H8xx-209
subrack
Max. Distance
between PLCs 30 ft (9 m)
Weight 4.5 lbs (2 kg)
3-25
C996 Integrated Control Processor
3-26
The AM-C996-80x DOS CoProcessor provides DOS Call Function Block
compatible coprocessing and interface
capability to 984, 685 and 785 controllers. Ladder Logic Interface
to C Language Tasks
3-27
C996 Technical Specifications
Description Software
C996 CoPro Option module for the 984-685, 785 BIOS: Award Software ver. 3.04 or higher
Operating System MS-DOS or IBM-PC DOS ver. 3.3
Components Required Software Modicon P/N SW-AP98-CXA
C996 CoPro AM-C996-802 1.5 slots Includes:
AM-C996-804 2 slots • IBM/P190 CALL Function Block
• C996 Utilities Software
M996 AS-M996-001 Mass Storage • C996 "C" Libraries
Includes: • Immediate Call Block routines
• 40 Megabyte hard disk Device Driver C996 SYS 70k
• 3.5 floppy disk (1.4 megabyte (included in config. sys.)
capacity) Programming Language C Programming Language
• W996 comm cable Compiler "User-supplied" Microsoft C ver. 5.1
• AC power cable
Documentation
Cables (Modicon P/N) AS-W950-006 (C996 to Modem, 6 ft.) C996 Installation Manual GX-C996-002
AS-W951-012 (C996 to IBM XT, 12 ft) C996 Software Manual GX-C996-001
AS-W952-012 (C996 to IBM AT, 12 ft)
AS-W488-006 (C996 to IEEE-488, 6 ft) Expandability
AS-W996-006 (C996 to M996, 6 ft)
PA-0407-000 (Floppy, 3 ft) IBM-XT Card Requirements
984 Family Compatibility Expansion Slots
C996-802 2 XT slots
C996s Per 984 Controller two maximum C996-804 4 XT slots
C996-802 1.5 slots, 6.3 Watts Max. Size (H x D) 4.2 in x 5.5 in
C996-804 2 slots, 6.3 Watts Power Consumption for XT Cards:
S908 1 slot, 7.5 Watts Maximum Per Card 1.25 A (6.2W)
S911 1 slot, 5.8 Watts Maximum Cumulative Power
S985 1 slot, 5.0 Watts C996-802 1.8 A (9W)
984-785, 685 1.5 slots Total Power, 40 Watts max. C996-804 3.6 A (18W)
Total option power for two C996-804s must not exceed 25 Watts.
Hardware Environmental
CPU 80286 at 8 MHz Operating Temperature 0 to 60°C
Optional Math Coprocessor 80287 at 5.3 MHz Storage Temperature -40° to 80°C
Memory 1 Megabyte of Dynamic RAM Relative Humidity 0 to 95% (non-condensing)
C996 LED Indicators Ready Shock Resistance 10G (11ms)
Status 1 (user definable) Space Requirements:
Battery Low C996-802 1.5 system bus slots in
H8xx-209 housing (fits with CPU)
Battery Operational Life: 1 year C996-804 2 system bus slots in H8xx-209
Shelf Life: 5 years housing
Front panel accessible Weight
Battery Lithium AA Cell C996-802 3.5 lbs (1.6 kg)
Communications Ports 2 serial ports RS-232 C996-804 4.5 lbs (2.0 kg)
Baud rate 150-9600 software
selectable
Default 9600/8 bit/no parity
3-28
984 Chassis-Mount PLCs
The 984X chassis supports only two option modules. The 984X
is only available in a four-card chassis.
The R911-000 Hot Standby Processor is useful in applications
that require fault tolerance and high availability. It allows you
to have a backup control system immediately available in case
of failure.
The C986 Control Processor, or CoPro, extends the processing
capabilities of the PLC by offloading complex logic from the
PLC. This way you can increase system speed through
multiprocessing and flexible multi-tasking capabilities.
The S985 Modbus Plus interface provides connectivity to a
Modbus Plus peer-to-peer communication network for data
transfer and remote programming capabilities. The S985 also
supports Modbus Plus cable redundancy. The S978 Dual
Modbus Modem provides two modems to connect the 984 in a
twisted-pair Modbus network.
3-29
984A
3-30
984A / S908 Dual Cable Remote I/O Network 984A Technical Specifications
Architecture
Memory
User logic 6k 32k
Registers 920 1920
Total 8k 34k
I/O Capacity
Max. Discrete I/O 2048 any mix
Max. Analog I/O 1920
Total I/O Bits 32,768
Local I/O Capacity N/A
Remote I/O Capacity
Max. I/O Bits per Drop 1024 In/1024 Out
Max. # Drops 32
Total I/O Bits 32,768 any mix
Max. # ASCII Ports 32
Internal Coils 2048
Logic Solve Time .75 ms/k
Communication Ports 3 Modbus, 1 Simple ASCII Output
Electrical
Power Supply
Input Voltage 115 Vac
230 Vac
I/O Power Capacity N/A
Environmental
Temperature 0 ... 60°C
Humidity 0 ... 95% non-condensing
Shock Resistance 10 G (11 ms)
Dimensions (WxHxD)
4-slot Chassis 11.6 x 19.2 x 10.2 in
(295 x 488 x 259 mm)
7-slot Chassis 17.3 x 19.2 x 10.2 in
(440 x 448 x 259 mm)
Weight
4-slot Chassis 46 lbs (21 kg)
7-slot Chassis 55 lbs (25 kg)
Up to 32 drops
3-31
984B
3-32
984B / S908 Dual Cable Remote I/O Network 984B Technical Specifications
Architecture
Memory
User Logic 32k 64k
Registers 9999 9999
Extended Memory Registers up to 96k up to 96k
Total 42 ... 138k 74 ... 138k
I/O Capacity
Max. Discrete I/O 8192 In / 8192 Out
Max. Analog I/O 2048 In / 2048 Out
Total I/O Bits 32,768 In/32,768 Out
Dimensions (WxHxD)
4-slot Chassis 11.6 x 19.2 x 10.2 in
(295 x 488 x 259 mm)
7-slot Chassis 17.3 x 19.2 x 10.2 in
(440 x 448 x 259 mm)
Weight
4-slot Chassis 46 lbs (21 kg)
Up to 32 drops
7-slot Chassis 55 lbs (25 kg)
3-33
984X
3-34
Remote I/O Configuration 984X Technical Specifications
Architecture
Memory
User Logic 8K
Registers 1920
Total 10K
I/O Capacity
Max. Discrete I/O 2048 any mix
Max. Analog I/O 224 In/224 Out
Local I/O Capacity
Total I/O Bits 512 In /512 Out
Total I/O Racks 5
Remote I/O Capacity
Max. I/O Bits per Drop 512 In/512 Out
Max. # Drops 6
Total I/O Bits 3584 In/3584 Out
Max. # ASCII Ports 12
Internal Coils 2048
Logic Solve Speed .75 ms/k
Communication Ports 2 Modbus
Electrical
Power Supply
Input Voltage 115 Vac
230 Vac
I/O Power Capacity N/A
Environmental
Temperature 0 ... 60°C
Humidity 0 ... 95% (non-condensing)
Shock Resistance 10 G (11 ms)
Dimensions (WxHxD)
4-slot Chassis 11.6 x 19.2 x 10.2 in
(295 x 488 x 259 mm)
Weight
4-slot Chassis 46 lbs (21 kg)
Up to 32 drops
3-35
ModConnect AT2-984 or AT4-984 PLC for AT bus/EISA
Personal Computers and EISA Workstations
The AT-984 PLC’s NetBIOS interface for DOS and OS/2 is the
same interface used on the SA85 AT bus, the SM85 Micro
Channel Modbus Plus, and MC-984 Micro Channel controller
boards. It supports many existing applications including:
• Modicon Modsoft Programming and Documentation Software
• Integrated software architecture to speed application
development (AT4-984 only)
• Peer Cop Process Control Function Library (PCFL)
• Modicon FactoryLink Man-Machine Interface Software
• Modicon P230 Emulation Software
• Modicon MBPSTAT program for monitoring Modbus
Plus networks
• Other third party programming Panel Software, MMI
software, and operating system device drivers for
Modbus Plus
3-36
AT2-984 Technical Specifications
Part Number AM-0984-AT2* AT-984 processor board and support software
Architecture
Memory
User Logic1 16k
Registers2 1920
Total 18k
I/O Capacity
Max. Discrete I/O 2048 any mix
Max. Analog I/O 224 in/224 out
Local I/O Capacity N/A
Remote I/O Protocol S908 protocol
Remote I/O Capacity
Max I/O Bits per Drop4 512 in/512 out
Max. Drops 7
Max Cable Distance 4,000 ft.
Total I/O Bits 3548 in/3548 out
Max. # ASCII Ports 14
Max Internal Coils3 2048
Performance 1.5 ms/K words
Communication Ports 1 Redundant Modbus Plus Port, 1 R10
Time of Day Clock ± 8.0 sec/day accuracy @ 60°C
Physical
Hardware AT-984 processor board
Software NetBIOS device driver for DOS and OS/2,
NETLIB.C C library, TESTXX.C sample programs,
MBPSTAT diagnostic
Software Media 5 1/4 inch, 360k diskettes, 3 1/2 inch, 720k diskette
Documentation GM-HBDS-001 IBM Host-based Devices Users Guide
Optional Supporting
Documentation GM-0984-SYS Systems Manual, GM-MBPL-001
Modbus Plus Network Planning and Installation Guide
Host Software Information
Operating System MS-DOS Ver. 3.1 or higher, OS/2 Ver. 1.3 or higher
C Library IBM C V1.1
AT-984 Boards per Computer 2 any type; SA85, AT-984
Selectable Options Address, memory, interrupts (DIP switches & jumpers)
Battery 2430 coin type lithium
LED Indicators None
Power 750 mA typical
Size (HxD) Standard full-size AT card
4.5 x 13.3 in (114 x 338 mm)
Weight
Net 1.0 lbs (.45 kg)
Shipping 2.0 lbs (.9 kg)
Environmental
Temperature
Operating 0 ... 60°C
Storage -40 to 80°C
Humidity 0 to 95% (non-condensing)
Shock 10 G’s for 11 msec
1
Deduct approximately 1k words for system overhead
2
Includes analog/register I/O and internal register space
3
Includes discrete I/O and internal coils
4
Each discrete I/O points requires 1 bit, each analog/register point requires 16 bits
3-37
AT4-984 Technical Specifications
Part Number AM-0984-AT4*AT-984 processor board and support software • Subroutine
• MSTR for Modbus Plus
• CKSUM
Architecture
• 16 bit signed/unsigned math
Memory Add Div.
User Logic1 32k Sub Int. to Float
Registers2 32,224 Mult Float to Integer
Total 64k Test = ,>,<
Logic Solve Time 1.5 ms/K • PCFL
Input/Output I/O Series 800/500/2005 Optional Software • FNxx Custom Loadable
I/O Capacity Loadables • DRUM and ICMP Drum Sequencer
Max Discrete I/O3 16,384 in/16,384 out Segment Scheduler
Max Analog I/O3 1024 in/1024 out Segment scheduler – I/O Scan optimization allows selection of I/O
Total Drops 16 update sequence for time-critical applications
Remote IOP Diagnostics
S908/800: Remote I/O Interface J890/J892 Power-Up diagnostics: CPU, RAM/ROM, Communications
P890/P892 Continuous per Scan: CPU, I/O Module Health, State Table
I/O Bits4 Drop 1024/1024 Memory, Detection of error causes an orderly shut-down of the
S908/200: Remote I/O Interface J290/J291 controller and logging of error type
I/O Bits4 Drop 256/256 Time of Day Clock
Cable Distance 4000 feet 1 year battery backed. Accuracy ±8.0 sec./Day 0-60˚
ASCII Ports: 2/Drop Logic Word Size – 24 Bits
32/System Memory – Battery backed for 1 year
I/O Modules per Drop 32
Environmental Characteristics
1
Deduct approximately 1k words for system overhead
2
Ambient 0-60˚C
Includes Analog/Register I/O and Internal Register Space
Temperature –40 to 80˚C
3
Each Analog/Register I/O Point requires 16 bits Humidity 0-95% non-condensing
4
Each Discrete I/O Point requires 1 bit. Each Analog/Register I/O Point Shock 10G's for 11 msec
requires 16 bits Vibration .625 @ 50-500 Hz
5
500-Series I/O Modules via P45x/J540 Interface (Discrete only) RFI/EMI Emission Complies with applicable FCC
Communications – Modbus Plus requirements
RFI/EMI Susceptibility ML-STD-461B
Speed 1 Megabit per second CS02-Conducted
Mode Peer-to-Peer RS03-Radiated
Number of Nodes UL Listing Approval Pending
on One Network 64 with one repeater CSA Listing Approval Pending
Media Twisted Pair Part Number AM-0984-AT4
Distance 1500 ft./section without repeaters Description AT-984 Programmable Controller for
6000 ft./(Max.) between any two AT and EISA-bus
nodes with repeaters Included AT-984 board
Connectors Two 9-Pin D for cable redundancy Media: 5-1/4" 360K
Instructions 3-1/2" 720K diskettes
Language • Ladder Logic/Function Block NETBIOS Drive
Instructions • Relays – NO, NC, Transitional NETLIB.CC Library
• Timers – 1.0, 0.1, 0.01 sec. TESTXX.C Sample Programs
• Counters – Up, Down MBPSTAT Diagnostic
Arithmetic • 4-digit Add, Sub, Mult, Div GM-HBDS-001 Manual, IBM Host
• 4-digit BCD values Based Devices Users Guide
Data Transfer • Register-to-Table Operating System MS-DOS ver. 3.1 or higher
• Table-to-Table C Library Microsoft C 5.1, Large Model
• Block Move DESCview 2.24
• First-In, First-Out Selectable Options Station Address, Memory and
• Search, Status Interrupts are all set by dip switches
Matrix • Logical AND, OR, Exclusive OR and jumpers
• Compare and Complement Battery 2430 coin type lithium
Bit Operations • Bit Modify, Bit Sense, and Bit Rotate Indicators LEDs provided for installation: RIO,
ASCII • Read and Write Functions up to Modbus Plus, and Run
32 ASCII Ports Power 750mA Typ, 1.1A Max.
Enhanced • Table to Block Size Standard AT Card 4.5" high, 13.3" long
Instructions • Double Precision Math: Add, Sub, Mult, Div Weight Net 1.0 lbs
• Floating Point Math: Add, Sub, Mult, Div, Shipping 2.0 lbs
Compare, Sq Root Optional Supporting Documentation
• Trigonometric Sin, Cos, Tan, Deg to Rad
• PID2 GM-0984-SYS Modicon 984 Programmable Controller Systems
• Skip Manual.
• Constant Scan GM-MBPL-001 Modicon Modbus Plus Network Planning and Installation
Guide
* Redundant Modbus Plus Cable
3-38
R911-000 Hot Standby System for Chassis-Mount PLCs
• One MA-0186-000 coaxial line splitter AS-911K-106 Kit with 6 foot W911 Cable
AS-911K-112 Kit with 12 foot W911 Cable
3-39
984 / R911 Hot Standby System R911 Hot Standby Technical Specifications
(Dual Cable is Optional)
Configuration Information
PLCs that use R911 984A, 984B, 984X
Part #, HSBY Function Block SW-AP9X-RXA
Data Exchange Rate 10 megabits/sec
Worst Case Switchover Time 13 ... 48 milliseconds
Power Source Mainframe PLC power supply
Environmental
Operating Temperature 0 ... 60°C
Relative Humidity 0 ... 95% (non-condensing)
Shock Resistance 10G (11 ms)
Physical
Space Requirements One option slot in chassis
Max. Distance Between PLCs 30 ft (9 m)
3-40
C986 Integrated Control Processor
3-41
C986 Technical Specifications
Configuration Information
PLCs with C986 Option 984A, 984B, 984X
Power Source Mainframe power supply
Architecture
Processor Chip 80186
Math Coprocessor Chip 8087
Operating System VRTX multi-tasking op. sys.
Language "C" programming language
Memory
Program & Data 256 kbyte battery-backed RAM
Data 512 kbyte dynamic RAM
Environmental
Operating Temperature 0 ... 60°C
Storage Temperature -40 to 80°C
Relative Humidity 0 ... 95% (non-condensing)
Shock Resistance 10G (11 ms)
Physical
Space Requirements 1 option slot in chassis
Weight 4.6 lbs (2.1 kg)
3-42
800-Series Input/Output Modules
3-43
3-44
Overview
3-45
Benefits
3-46
Broad Range of
Discrete In
Module Types
Required
Number of Number per Addressing Required With over 50 modules to
Voltage Points Common I/O Bits Module # Connector choose from, the Modicon I/O
115 Vac 32 8 32/0 AS-B807-132 AS-8535-000 line offers one of the industry’s
115 Vac 16 8 16/0 AS-B805-016 AS-8534-000 broadest range of I/O
115 Vac 16 1 16/0 AS-B817-116 AS-8535-000 modules.
115 Vac 8 1 8/0 AS-B803-008 AS-8534-000
230 Vac 16 8 16/0 AS-B809-016 AS-8534-000
230 Vac 16 1 16/0 AS-B817-216 AS-8535-000
24 Vdc Supr. Wire 32 8 64/0 AS-B863-132 AS-8535-000
24 Vdc (TH) 32 32 32/0 AS-B827-032 AS-8535-000
24 Vdc (TH) 16 8 16/0 AS-B825-016 AS-8534-000
24 Vdc (TL) 16 8 16/0 AS-B833-016 AS-8534-000
24 Vdc (LATCH) 16 8 16/16 AS-B881-001 AS-8534-000
24 Vdc* 32 16 16/0 AS-B863-032 AS-8535-000
10-60 Vdc (TH) 8 2 8/0 AS-B821-108 AS-8534-000
24 Vac/DC 16 8 16/0 AS-B837-016 AS-8534-000
48 Vac/DC 16 8 16/0 AS-B849-016 AS-8534-000
115 Vac 16 8 16/0 AS-B853-016 AS-8534-000
5 V TTL 16 8 16/0 AS-B829-116 AS-8534-000
TTL Register 16 — 16/0 AS-B865-001 AS-8535-000
12 Vdc Intr. Safe 16 1 16/0 AS-B855-016 AS-8535-000
*Monitored Input.
Discrete Out
Required
Number of Number per Addressing Required
Voltage Points Common I/O Bits Module # Connector
115 Vac 32 16 0/32 AS-B806-032 AS-8535-000
115 Vac 16 8 0/16 AS-B804-116 AS-8534-000
115 Vac 8 1 0/8 AS-B810-008 AS-8534-000
115 Vac 8 2 0/8 AS-B802-008 AS-8534-000
115 Vac Protected 8 1 16/16 AS-B881-108 AS-8535-000
48 Vac 16 8 0/16 AS-B804-148 AS-8534-000
24 Vac 32 16 0/32 AS-B806-124 AS-8535-000
230 Vac 16 8 0/16 AS-B808-016 AS-8534-000
24 Vdc Supr. Wire 16 8 16/16 AS-B882-116 AS-8534-000
24 Vdc (TH) 32 8 0/32 AS-B838-032 AS-8535-000
24 Vdc (TH) 32 32 0/32 AS-B826-032 AS-8535-000
24 Vdc (TH) 16 8 0/16 AS-B824-016 AS-8534-000
24 Vdc (TL) 16 8 0/16 AS-B832-016 AS-8534-000
24 Vdc Diagnostic 32 8 32/32 AS-B882-032 AS-8535-000
10-60 Vdc (TH) 8 2 0/8 AS-B820-008 AS-8534-000
12-250 Vdc 16 1 0/16 AS-B836-016 AS-8535-000
Relay (NO/NC) 8 1 0/8 AS-B814-108 AS-8534-000
Reed Relay (NO/NC) 8 1 0/8 AS-B840-108 AS-8534-000
5 V TTL 16 16 0/16 AS-B828-016 AS-8534-000
TTL Register — — 0/128 AS-B864-001 AS-8535-000
125 Vdc 8 — 16/16 AS-B881-508 AS-8535-000
3-47
Analog In
Required
Number of Addressing Required
Application/Range Points I/O Bits Module # Connector
Fast A/D: 4-20 mA; +5 V; +10 V;
0-10 V; 0-5 V; 1-5 V 8 128/0 AS-B875-102 Included
Analog Out
Required
Number of Addressing Required
Application/Range Points I/O Bits Module # Connector
D/A: 4-20 mA 4 0/64 AS-B872-100 AS-8535-000
D/A: ± 10 V; ± 5 V; 0-10 V; 0-5 V 4 0/64 AS-B872-200 AS-8535-000
Intelligent/Special Purpose
3-48
Individual Module Descriptions
Technical Specifications, Mechanical Keying, and Wiring Diagrams
TOP TOP
BOTTOM BOTTOM
3-49
Specification AS-B804-116 Specification AS-B804-148
Description 115 Vac output Description 48 Vac output
Number of Points 16 Number of Points 16
Operating Voltage 80 ... 130 Vac / 47 ... 63 Hz Operating Voltage 40 ... 56 Vac / 47 ... 63 Hz
Number of Groups 2 Number of Groups 2
Outputs per Group 8 Outputs per Group 8
ON Current ON Current
Max. per Point 2 A continuous Max. per Point 2 A continuous
50 A one cycle 50 A one cycle
Max. per Group 6A Max. per Group 6A
Max. per Module 12.0 A Max. per Module 12.0 A
Leakage Current 3 mA (max) @ 115 Vac Leakage Current 3 mA (max)
Max. Response Time Max. Response Time
OFF to ON 8.3 ms @ 60 Hz OFF to ON 8.3 ms @ 60 Hz
ON to OFF 8.3 ms @ 60 Hz ON to OFF 8.3 ms @ 60 Hz
Power Required Power Required
+5 V 76 mA +5 V 76 mA
+4.3 V 480 mA +4.3 V 480 mA
-5 V 0 mA -5 V 0 mA
Dimensions Dimensions
Space Required 1 slot Space Required 1 slot
Weight 2.75 lbs (1.25 kg) Weight 2.75 lbs (1.25 kg)
Terminal Connector AS-8534-000 Terminal Connector AS-8534-000
Fusing One per group Fusing One per group
TOP TOP
BOTTOM BOTTOM
3-50
Specification AS-B805-016 Specification AS-B806-032
Description 115 Vac input Description 115 Vac output
Number of Points 16 Number of Points 32
Operating Voltage 80 ... 130 Vac / 47 ... 63 Hz Operating Voltage 80 ... 130 Vac / 47 ... 63 Hz
Number of Groups 2 Number of Groups 2
Inputs per Group 8 Outputs per Group 16
Max. Input Voltage ON Current
Continuous 130 Vac Max. per Point 1 A continuous
Surge 220 Vac for one cycle 15 A one cycle
ON Conditions 80 ... 130 Vac (Z<1kΩ) Max. per Group 8A
OFF Conditions 0 ... 35 Vac (Z=0 Ω) Max. per Module 16 A
0 ... 130 Vac (Z>40 kΩ) Leakage Current 2 mA (max) @ 115 Vac
Wetting Current 6 mA (typical) @ 115 Vac Max. Response Time
Max. Response Time OFF to ON 8.3 ms @ 60 Hz
OFF to ON 6 ms (4 ms typical) ON to OFF 8.3 ms @ 60 Hz
ON to OFF 18 ms (11 ms typical) Power Required
Power Required +5 V 210 mA
+5 V 40 mA +4.3 V 1 mA
+4.3 V 1 mA -5 V 0 mA
-5 V 14 mA Dimensions
Dimensions Space Required 1 slot
Space Required 1 slot Weight 2.49 lbs (1.13 kg)
Weight 2.2 lbs (1.01 kg) Terminal Connector AS-8535-000
Terminal Connector AS-8534-000 Fusing None
TOP
TOP
BOTTOM
BOTTOM
3-51
Specification AS-B806-124 Specification AS-B807-132
Description 24 Vac output 115 Vac 125 Vdc
Number of Points 32 Description 115 Vac hi-density input 125 Vdc input
Operating Voltage 20 ... 28 Vac / 47 ... 63 Hz Number of Points 32 32
Number of Groups 2 Operating Voltage 80 ... 130 Vac/ 115 ...140 Vdc cont.
Outputs per Group 16 47 ... 63 Hz
ON Current Number of Groups 4 4
Max. per Point 1 A continuous Inputs per Group 8 8
15 A one cycle Max. Input Voltage
Max. per Group 8A Continuous 130 Vac
Max. per Module 16 A Surge 200 Vac for 1 cycle
Leakage Current 2 mA (max.) ON Conditions 80 ... 130 Vac (Z<1kΩ) 115 ...140 Vdc
Max. Response Time OFF Conditions 0 ... 35 Vac (Z=0 Ω) 0 ... 20 Vdc
OFF to ON 8.3 ms @ 60 Hz 0 ... 130 Vac (Z>40 kΩ)
ON to OFF 8.3 ms @ 60 Hz Wetting Current 6 mA (typical) @ 115 Vac
Power Required Max. Response Time
+5 V 210 mA OFF to ON 6 ms 1.2 ms
+4.3 V 1 mA ON to OFF 12 ms 55ms
-5 V 0 mA Power Required
Dimensions +5 V 80 mA 80 mA
Space Required 1 slot +4.3 V 2 mA 2 mA
Weight 2.49 lbs (1.13 kg) -5 V 0 mA 0 mA
Terminal Connector AS-8535-000 Dimensions
Fusing None Space Required 1 slot 1 slot
Weight 2 lbs (0.91 kg) 2 lbs (0.91 kg)
Terminal Connection AS-8535-000 AS-8535-000
TOP
BOTTOM
BOTTOM
(Optional)
(When facing housing, place
(When facing housing, place
pins in holes shown by black
pins in holes shown by black
circles.)
circles.)
3-52
Specification AS-B808-016 Specification AS-B809-016
Description 230 Vac output Description 230 Vac input
Number of Points 16 Number of Points 16
Operating Voltage 160 ... 260 Vac / 47 ... 63 Hz Operating Voltage 160 ... 260 Vac / 47 ... 63 Hz
Number of Groups 2 Number of Groups 2
Outputs per Group 8 Inputs per Group 8
ON Current Max. Input Voltage
Max. per Point 2 A continuous Continuous 260 Vac
50 A one cycle 300 Vac for 10 sec.
Max. per Group 6A Surge 400 Vac for 1 cycle
Max. per Module 12 A ON Conditions 112 ... 148 Vac (RS=1 Kmax)
Leakage Current 8 mA (max) @ 230 Vac OFF Conditions 0 ... 90 Vac (Z=0 Ω)
Max. Response Time Wetting Current 8.5 mA (typical) @ 230 Vac
OFF to ON 8.3 ms Max. Response Time
ON to OFF 8.3 ms OFF to ON 7 ms (5 ms typical)
Power Required ON to OFF 18 ms (12 ms typical)
+5 V 76 mA Power Required
+4.3 V 480 mA +5 V 42 mA
-5 V 0 mA +4.3 V 1 mA
Dimensions -5 V 15 mA
Space Required 1 slot Dimensions
Weight 2.75 lbs (1.25 kg) Space Required 1 slot
Terminal Connector AS-8534-000 Weight 2.38 lbs (1.08 kg)
Fusing One per group Terminal Connector AS-8534-000
TOP TOP
BOTTOM BOTTOM
3-53
Specification AS-B820-008 Specification AS-B821-108
Description 10 ... 60 Vdc (True High) output Description 10 ... 60 Vdc input
Number of Points 8 Type of Operation True High
Operating Voltage 10 ... 60 Vdc Number of Points 8
Number of Groups 4 Operating Voltage 10 ... 60 Vdc
Outputs per Group 2 Number of Groups 4
ON Current Inputs per Group 2
Max. per Point 2A Max. Input Voltage
Max. per Group 6A Continuous 10 ... 60 Vdc
Max. per Module 12 A Surge 80 Vdc for 10 msec
Leakage Current 5 mA (max.) @ 60 Vdc Wetting Current 2 mA (max.) @ 10 Vdc
Max. Response Time 5 mA (max.) @ 24 Vdc
OFF to ON 1 ms (.1 ms typical) 10 mA (max.) @ 48 Vdc
ON to OFF 1 ms (.1 ms typical) 12 mA (max.) @ 60 Vdc
Power Required Max. Response Time
+5 V 90 mA OFF to ON 11 ms
+4.3 V 80 mA ON to OFF 11 ms
5V 0 mA Power Required
External Power Supply 10 ... 60 Vdc, 200 mA @ 60 Vdc +5 V 27 mA
(Excluding field load current) +4.3 V 1 mA
Dimensions 5V 10 mA
Space Required 1 slot External Power Supply 10 ... 60 Vdc, 200 mA @ 60 Vdc
Weight 2.55 lbs (1.16 kg) Dimensions
Terminal Connector AS-8534-000 Space Required 1 slot
Fusing One per group Weight 2.11 lbs (0.96 kg)
Terminal Connector AS-8534-000
TOP TOP
BOTTOM BOTTOM
3-53
Specification AS-B824-016 Specification AS-B825-016
Description 24 Vdc (True High) output Description 24 Vdc input
Number of Points 16 Type of Operation True High
Operating Voltage 20 ... 28 Vdc Number of Points 16
Number of Groups 2 Operating Voltage 20 ... 28 Vdc
Outputs per Group 8 Number of Groups 1
ON Current Inputs per Group 16
Max. per Point 2 A continuous Max. Input Voltage
5 A for 10 ms Continuous 30 Vdc
Max. per Group 6A Surge 500 Vdc for 3 ms
Max. per Module 12 A ON Conditions < 1000 Ω
Leakage Current 1 mA (max.) @ 24 Vdc OFF Conditions > 25,000 Ω
Max. Response Time Wetting Current 6 mA (typical) @ 24 Vdc
OFF to ON 1 ms Max Response Time
ON to OFF 1 ms OFF to ON 11 ms (2.5 ms typical)
Power Required ON to OFF 11 ms (2.5 ms typical)
+5 V 32 mA Power Required
+4.3 V 260 mA +5 V 27 mA
5V 0 mA +4.3 V 2 mA
External Power Supply 24± 4 Vdc, 175 mA 5V 15 mA
(Excluding field load current) External Power Supply 24±4 Vdc, 200 mA
Dimensions Dimensions
Space Required 1 slot Space Required 1 slot
Weight 2.75 lbs (1.25 kg) Weight 2.75 lbs (1.25 kg)
Terminal Connector AS-8534-000 Terminal Connector AS-8534-000
Fusing One per group
TOP TOP
BOTTOM BOTTOM
3-54
Specification AS-B826-032 Specification AS-B827-032
Description 24 Vdc True High output Description 24 Vdc hi-density input
Number of Points 32 Type of Operation True High
Operating Voltage 20 ... 28 Vdc Number of Points 32
Number of Groups 1 Operating Voltage 20 ... 28 Vdc
Outputs per Group 32 Number of Groups 1
ON Current Inputs per Group 32
Max. per Point 0.25 A Max. Input Voltage
2.5 A for .5 ms Continuous 30 Vdc
Max. per Group 8A Surge 40 Vdc for 10ms
Max. per Module 8A ON Conditions 8 ... 11 kΩ
Leakage Current 0.1 mA (typical) @ 24 Vdc OFF Conditions 6 ... 8 kΩ
Max. Response Time Wetting Current 6 mA (typical) @ 24 Vdc
OFF to ON 1 ms Max Response Time
ON to OFF 1 ms OFF to ON 1 ms
Power Required ON to OFF 1 ms
+5 V 90 mA Power Required
+4.3 V 1 mA +5 V 30 mA
5V 0 mA +4.3 V 1 mA
External Power Supply 24 Vdc, 600 mA -5 V 0 mA
(Excluding field load current) External Power Supply 24± 6 Vdc, 70 mA
Dimensions Dimensions
Space Required 1 slot Space Required 1 slot
Weight 2.55 lbs (1.16 kg) Weight 2.31 lbs (1.05 kg)
Terminal Connector AS-8535-000 Terminal Connector AS-8535-000
Fuse One per group
TOP TOP
BOTTOM BOTTOM
3-55
Specification AS-B828-016 Specification AS-B829-116
Description 5 V TTL output Description 5 V TTL input
Number of Points 16 Type of Operation TTL
Operating Voltage 5 V TTL Number of Points 16
Number of Groups 1 Operating Voltage 5 V TTL
Outputs per Group 16 Number of Groups 1
OFF Current Inputs per Group 16
Max. per Point 75 mA max. (sinking) Max. Input Voltage
100 mA for 10 ms Continuous 8 Vdc
Max. Response Time Surge 15 Vdc for 10 ms
OFF to ON 1 ms Max. Response Time
ON to OFF 1 ms OFF to ON 1 ms
Power Required ON to OFF 1 ms
+5 V 32 mA Power Required
+4.3 V 220 mA +5 V 27 mA
-5 V 0 mA +4.3 V 1 mA
External Power Supply 5.0± .25 Vdc, 325 mA -5 V 0 mA
(Excluding field load current) External Power Supply 5.0 ±.25 Vdc, 325 mA
Dimensions Dimensions
Space Required 1 slot Space Required 1 slot
Weight 2.33 lbs (1.06 kg) Weight 2.26 lbs (1.03 kg)
Terminal Connector AS-8534-000 Terminal Connector AS-8534-000
Fusing One per group
TOP TOP
BOTTOM BOTTOM
3-56
Specification AS-B832-016 Specification AS-B833-016
Description 24 Vdc True Low output Description 24 Vdc True Low input
Number of Points 16 Type of Operation True Low
Operating Voltage 20 ... 28 Vdc Number of Points 16
Number of Groups 2 Operating Voltage 20 ... 28 Vdc
Outputs per Group 8 Number of Groups 2
ON Current Inputs per Group 8
Max. per Point 250 mA Max. Input Voltage
1A for 10 ms Continuous 30 Vdc
Max. per Group 2A Surge 500 Vdc for 3 ms
Max. per Module 4A ON Conditions < 200 Ω
Leakage Current 0.5 mA (typical) @ 24 Vdc OFF Conditions > 10,000 Ω
Max. Response Time Wetting Current 6 mA (typical) @ 24 Vdc
OFF to ON 1 ms Max. Response Time
ON to OFF 1 ms OFF to ON 11 ms
Power Required ON to OFF 11 ms
+5 V 32 mA Power Required
+4.3 V 235 mA +5 V 27 mA
5V 0 mA +4.3 V 2 mA
External Power Supply 24± 4 Vdc, 600 mA -5 V 0 mA
Dimensions External Power Supply 24 ± 4 Vdc, 300 mA
Space Required 1 slot (Excluding field load current)
Weight 2.75 lbs (1.25 kg) Dimensions
Terminal Connector AS-8534-000 Space Required 1 slot
Fusing One per module Weight 2.75 lbs (1.25 kg)
Terminal Connector AS-8534-000
Fusing One per module
TOP TOP
BOTTOM BOTTOM
3-57
Specification AS-B836-016 Specification AS-B837-016
Description 12 ... 250 Vdc isolated output Description 24 Vac/DC input
Number of Points 16 Number of Points 16
Operating Voltage 12 ... 250 Vdc Operating Voltage 20 ... 27 Vac/47 ... 63 Hz; 19 ... 30
Number of Groups 16 Vdc
Outputs per Group 1 Number of Groups 2
ON Current Inputs per Group 8
Max. per Point 0.75 A (typical) @ 250 Vdc Max. Input Voltage
1 A (typical) @ 125 Vdc Continuous 27 Vac / 30 Vdc
1.5 A (typical ) @ 48 Vdc Surge 32 Vac / 36 Vdc
Max. per Module 8A ON Conditions >20.4 Vac or 19.2 Vdc
Leakage Current 1mA (max.) @ 12 Vdc w/lnp Z of 1 K max.
Surge Current 5 A for 10 ms at repetition rate OFF Conditions < 6 Vac/ 10 Vdc
of 1 sec. < 27 Vac w/Inp Z > 15 K
Max. Response Time < 30 Vac w/Inp Z > 30 K
OFF to ON 1 ms Wetting Current 7.5 mA (typical) @ 24 Vdc
ON to OFF 5 ms Max. Response Time
Power Required OFF to ON 6 ms
+5 V 50 mA ON to OFF 18 ms
+4.3 V 603 mA Power Required
-5 V 0 mA +5 V 40 mA
Dimensions +4.3 V 1 mA
Space Required 1 slot -5 V 15 mA
Weight 2.55 lbs (1.16 kg) External Power Supply 24 Vac/DC, 300 mA
Terminal Connector AS-8535-000 Dimensions
Fusing One per group Space Required 1 slot
Weight 2.75 lbs (1.25 kg)
Terminal Connector AS-8534-000
TOP TOP
BOTTOM BOTTOM
3-59
Specification AS-B838-032 Specification AS-B840-108
Description 24 Vdc True High output Description Reed Relay (NO/NC) output
Number of Points 32 Number of Points 8
Operating Voltage 20 ... 28 Vdc Operating Voltage 0 ... 300 Vdc;
Number of Groups 4 0 ... 230 Vac / 47 ... 63 Hz
Outputs per Group 8 Number of Groups 8
ON Current Outputs per Group 1
Max. per Point 0.5 A ON Current
2.5 A for .5 ms Max. per Point 3 A continous
Max. per Group 4A 2 A switching current
Max. per Module 12 A Max. per Module 24 A
Leakage Current 1 mA (typical) @ 30 Vdc Switching Capability 100 vA
Max. Response Time Max. Response Time
OFF to ON 1 ms OFF to ON 6 ms (2 ms typical)
ON to OFF 1 ms ON to OFF 6 ms (2 ms typical)
Power Required Power Required
+5 V 160 mA +5 V 67 mA
+4.3 V 1 mA +4.3 V 400 mA
-5 V 0 mA 5V 0 mA
External Power Supply 24 ± 4Vdc, 125 mA Dimensions
(Excluding field load current) Space Required 1 slot
Dimensions Weight 2.62 lbs (1.19 kg)
Space Required 1 slot Terminal Connector AS-8534-000
Weight 2.4 lbs (1.09 kg) Fusing One per group
Terminal Connector AS-8535-000
TOP TOP
BOTTOM BOTTOM
3-60
Specification AS-B846-001 Specification AS-B846-002
Description Analog Input Multiplexer Description Analog Input Multiplexer
Number of Channels 16, potential isolated to each other Number of Channels 16, potential isolated to each other
Address Capacity 1 register out (channel select) Address Capacity 1 register out (channel select)
I/O Range -10 to 10 Vdc (voltage) I/O Range 4 to 20 mA (current)
Input Impedance Equal to B873 or B875 Input Impedance 250 Ω
Response Time 3 ms Response Time 3 ms
Switching Behavior Break before Make, Switching Behavior Break before Make,
switching time: 3 ms switching time: 3 ms
Power Required Power Required
+5 Vdc 65 mA +5 Vdc 65 mA
+4.3 Vdc 1 mA +4.3 Vdc 1 mA
-5 Vdc 0 mA -5 Vdc 0 mA
Dimensions Dimensions
Space Required 1 slot Space Required 1 slot
Weight 2.55 lbs (1.16 kg) Weight 2.55 lbs (1.16 kg)
Terminal Connector AS-8535-000 Terminal Connector AS-8535-000
TOP
BOTTOM
BOTTOM
3-61
Specification AS-B849-016 Specification AS-B853-016
Description 48 Vac / DC input Description 115 Vac
Number of Points 16 Number of Points 16
Operating Voltage 41 ... 53 Vac / 47 ... 63 Hz; Operating Voltage 80 ... 130 Vac / 47 ... 63 Hz;
39 ... 58 Vdc Number of Groups 2
Number of Groups 2 Inputs per Group 8
Inputs per Group 8 Max. Input Voltage
Max. Input Voltage Continuous 130 Vac
Continuous 53 Vac / 58 Vdc Surge 150 Vac
Surge 63 Vac / 70 Vdc for 10 sec 280 V for 10 ms
110 V for 10 ms ON Conditions > 80 Vac
ON Conditions > 41 Vac or 39 Vdc w/Inp Z of 1 K max.
w/Inp Z of 1 K max. OFF Conditions < 35 Vac
OFF Conditions < 15 Vac / 20 Vdc < 130 Vac w/Inp Z > 40 K
< 53 Vac w/Inp Z > 25 K < 150 Vac w/Inp Z > 80 K
< 58 Vac w/Inp Z > 50 K Wetting Current 6 mA (typical) @ 125 Vdc
Wetting Current 6.5 mA (typical) @ 48 Vdc Max. Response Time
Max. Response Time OFF to ON 6 ms
OFF to ON 6 ms ON to OFF 18 ms
ON to OFF 18 ms Power Required
Power Required +5 V 40 mA
+5 V 40 mA +4.3 V 1 mA
+4.3 V 1 mA 5V 15 mA
5V 15 mA Dimensions
External Power Supply 48 Vac/DC, 200 mA Space Required 1 slot
Dimensions Weight 2.75 lbs (1.25 kg)
Space Required 1 slot Terminal Connector AS-8534-000
Weight 2.75 lbs (1.25 kg)
Terminal Connector AS-8534-000
TOP
TOP
BOTTOM
BOTTOM
3-62
Specification AS-B855-016 Specification AS-B863-032
Description 12 Vdc intrinsically safe input Description 24 Vdc hi-density monitored input
Mode of Operation True Low Type of Operation True High
Number of Points 16 Number of Points 32
Operating Voltage 11.4 ... 12.6 Vdc Operating Voltage 18 ... 30 Vdc
Number of Groups 1 Number of Groups 2
Inputs per Group 16 Inputs per Group 16
Max. Input Voltage Max. Input Voltage
Continous 12 Vdc (± 5%) Continuous 30 Vdc
Surge 500 Vdc for 3 ms Surge 40 Vdc for 10ms
ON Conditions ≤ 100 Ω total impedance ON Conditions 8 ... 11 kΩ
OFF Conditions >100,000 Ω; 0 Vdc OFF Conditions 6 ... 8 kΩ
Max. Response Time Wetting Current 2 mA (typical) @ 24 Vdc
OFF to ON 1 ms Max Response Time
ON to OFF 5 ms OFF to ON 10 ms
Power Required ON to OFF 10 ms
+5 V 80 mA Power Required
+4.3 V 1 mA +5 V 250 mA
5V 1.5 mA +4.3 V 0 mA
External Power Supply 12 Vdc±5%, 1 A minimum 5V 0 mA
Dimensions External Power Supply 24±6 Vdc, 20 mA
Space Required 1 slot Dimensions
Weight 2.4 lbs (1.1 kg) Space Required 1 slot
Terminal Connector AS-8535-000 Weight 2.31 lbs (1.05 kg)
Agency Factory mutual 3610 (Requires Terminal Connector AS-8535-000
use of key pins and MD-8741-000
barrier strip, included with module)
TOP TOP
BOTTOM BOTTOM
3-63
Specification AS-B863-132 Specification AS-B864-001
Description 24 Vdc Supervised wire input Description TTL register ouput
Senses & reports broken wire Number of Points 8 channels, 16 data lines
faults for each I/O point to PLC
Operating Voltage 5V TTL
Type of Operation True High
Number of Points 32 Number of Groups NA
Number of Groups 4 (8 inputs per group) Outputs per Group NA
Reference Current 9 to 15 mA per group
ON Current
Threshold Voltage 11 to 15 Vdc
Working Voltage 0 to 30 Vdc Max. per Point NA
Reference Voltage 19.2 to 30 Vdc Max. per Group NA
Input Current 1.8 to 3 mA low state
Max. per Module NA
5.75 to 7.1 mA high state
Transition Time Leakage Current NA
ON Vin = 20 Vdc 200 ms minimum Max. Response Time
Vin = 30 Vdc 25 ms minimum OFF to ON 11.3 ms
OFF Vin = 20 Vdc 100 ms maximum
Vin = 30 Vdc 250 ms maximum ON to OFF 11.3 ms
Max. Response Time 2.0 ms, contact opening Power Required
OFF to ON and/or closing 100 ms, fault +5 V 220 mA
ON to OFF detection time maximum
Power Required +4.3 V 180 mA
+ 5V 350 mA -5 V 0 mA
+4.3V 10 mA Dimensions
-5V 0mA (not used)
External Power Supply 30 Vdc maximum Space Required 1 slot
Dimensions Weight 3.99 lbs (1.81 kg)
Space Required 1 slot Terminal Connector AS-8535-000
Weight 2 lbs (0.91 kg.)
Terminal Connector AS-8535-000
TOP TOP
BOTTOM BOTTOM
3-64
Specification B865-001 Specification AS-B872-100
Description TTL register input Description D/A; 4 ... 20 mA
Number of Inputs 8 channels, 16 data lines Number of Channels 4
Operating Range 4 ... 20 mA
Operating Voltage 5 VTTL Max. Loop Supply Voltage 60 Vdc
Max. Response Time Resolution 12 bit
OFF to ON 20 ms Accuracy ± 0.1% of full scale at 25°C
Linearity 0 to 60°C, ± 1 LSB
ON to OFF 20 ms Update Times <1 ms, all 4 channels
Power Required Isolation
+5 V 400 mA Channel to Channel 1000 V continuous
Channel to Case 1000 V continuous
+4.3 V 600 mA
Channel to Module 1000 V continuous
-5 V 0 mA Power Required
Dimensions +5 V 475 mA
+4.3 V 5 mA
Space Required 1 slot
-5 V 0 mA
Weight 2.75 lbs (1.25 kg) Dimensions
Terminal Connector AS-8535-000 Space Required 1 slot
Weight 3 lbs (1.4 kg)
Terminal Connector AS-8535-000
B865-001 Terminal Numbering B865-001 Mechanical Keying AS-B872-100 Terminal AS-B872-100 Mechanical
and Wire Connections for Housings Numbering and Wire Keying for Housings
Connections
TOP TOP
BOTTOM BOTTOM
3-65
Specification AS-B872-200 Specification AS-B873-001
Description D/A; ± 10 Vdc, ± 5 Vdc, Description A/D: 4 ... 20 mA; 1 ... 5 Vdc
0 ... 10 Vdc, 0 ... 5 Vdc Number of Channels 4
Number of Channels 4 Operating Range
Operating Range Voltage/Current 1 ... 5 Vdc / 4 ... 20 mA
Voltage -10 to 10 Vdc; -5 to 5 Vdc; Impedance 1 MΩ (voltage mode)
0 ... 5 Vdc, 0 ... 10 Vdc, 250 Ω (current mode)
selectable per channel Resolution 12 bit
Resolution 12 bit Accuracy 7 mV
Accuracy ± 0.1% at 25°C Linearity ± .05% of full scale @ 25°C
± 0.17% at 0-60°C Update Time 400 ms for 4 channels
Linearity 0 to 60°C, ±1 LSB Isolation
Update Times <1 ms, all 4 channels Channel to Channel 250 Vac coninuous
Isolation Channel to Module 300 Vac continuous
Channel to Channel 1000 V continuous Power Required
Channel to Case 1000 V continuous +5 V 300 mA
Channel to Module 1000 V continuous +4.3 V 300 mA
Power Required -5 V 0 mA
+5 V 750 mA Dimensions
+4.3 V 5 mA Space Required 1 slot
-5 V 0 mA Weight 3.3 lbs (1.5 kg)
Dimensions Terminal Connector Included
Space Required 1 slot
Weight 3 lbs (1.4 kg)
Terminal Connector AS-8535-000
BOTTOM
BOTTOM
3-66
Specification AS-B873-011 Specification AS-B875-002
Description A/D: -10 to 10 Vdc Description A/D: 4 ... 20 mA; 1 ... 5 Vdc
Number of Channels 4 Number of Channels 8
Operating Range Operating Range
Voltage/Current -10 to 10 Vdc Voltage/Current 1 ... 5 Vdc / 4 ... 20 mA
Impedance 1 MΩ Impedance 1 MΩ (voltage mode)
Resolution 13 bit 250 Ω (current mode)
Accuracy 17 mV Resolution 12 bit
Linearity ± .05% of full scale @ 25°C Accuracy 7 mV
Update Time 400 ms for 4 channels Linearity ± .05% of full scale @ 25°C
Isolation Update Time 710 ms for 8 channels
Channel to Channel 250 Vac continuous Isolation
Channel to Module 300 Vac continuous Channel to Channel 250 Vac continuous
Power Required Channel to Module 300 Vac continuous
+5 V 300 mA Transfer Times
+4.3 V 300 mA Power Required
-5 V 0 mA +5 V 300 mA
Dimensions +4.3 V 300 mA
Space Required 1 slot -5 V 0 mA
Weight 3.3 lbs (1.5 kg) Dimensions
Terminal Connector Included Space Required 1 slot
Weight 3.3 lbs (1.5 kg)
Terminal Connector Included
TOP
TOP
BOTTOM
BOTTOM
3-67
Specification AS-B875-012 Specification AS-B875-102
Description A/D: -10 to 10 Vdc Description Fast A/D: ± 10 Vdc; ± 5 Vdc;
Number of Channels 8 0 ... 10 V; 0 ... 5 Vdc; 1 ... 5 Vdc
Operating Range user selectable
Voltage/Current -10 to 10 Vdc Number of Channels 4 or 8
Impedance 1 MΩ Operating Range
Resolution 13 bit Voltage/Current 1 ... 5 Vdc / 4 ... 20 mA
Accuracy 17 mV 0 ... 5 Vdc / 0 ... 20 mA
Linearity ± .05% of full scale @ 25°C 0 ... 10 V / 0 ... 40 mA
Update Time 710 ms for 8 channels -5 ... 5 V / -20 ... 20 mA
Isolation -10 ... 10 V / -40 ... 40 mA
Channel to Channel 250 Vac continuous Output Impedance 10 MΩ (voltage mode)
Channel to Module 300 Vac continuous 250 Ω (current mode)
Power Required Resolution 12 bit
+5 V 300 mA Accuracy ± 0.1% of full scale @ 25°C
+4.3 V 300 mA Linearity ± .02% of full scale @ 25°C
-5 V 0 mA Update Time 2.4 ms for 4 channels
Dimensions 3.0 ms for 8 channels
Space Required 1 slot Isolation
Weight 3.3 lbs (1.5 kg) Channel to Channel 30 Vac continuous
Terminal Connector Included Channel to Module 1500 Vac for 1 minute
Power Required
+5 V 650 mA
+4.3 V 975 mA
-5 V 0 mA
Dimensions
Space Required 1 slot
Weight 4 lbs (1.8 kg)
Terminal Connector Included
BOTTOM BOTTOM
3-68
Specification AS-B875-111 Isolation
Description A/D: 4 ... 20 mA; 1 ... 5 Vdc; Channel to Channel 30 Vac
-10 to 10 Vdc; 0 ... 20 mA; Channel to Module 1500 Vac for 1 minute
-5 to 5 Vdc Power Required
Number of Channels 8 differential or +5 V 500 mA
16 single-ended (user selectable) +4.3 V 900 mA
Operating Range -5 V 0 mA
Voltage/Current -5 Vdc to +5 Vdc Dimensions
0 to 5 Vdc Space Required 1 slot
1 Vdc to 5 Vdc Weight 3.52 lbs (1.6 kg)
-10 Vdc to +10 Vdc Terminal Connector AS-8535-000
0 to 10 Vdc
-20 mA to +20 mA
0 to 20 mA
4 to 20 mA
Output Impedance > 10 MΩ (voltage mode)
250 Ω (current mode)
Resolution 14 bit
Accuracy ± 0.1%
Linearity ± .05%
Update Time
8 inputs 10 ms
16 inputs 20 ms
AS-B875-111 Terminal
Numbering and Wire
Connections
8 Differential Inputs 16 Single-Ended Inputs AS-B875-111 Mechanical
Keying for Housings
TOP
BOTTOM
3-69
Specification AS-B875-200 List of 5B Packs
Description A/D; Thermocouples, RTD Part Number Description
Strain Gauges, 4 ... 20 mA Voltage Input, 4 Hz.
Various Input Voltage Ranges AS-5B30001A 0 to +10 mV
Number of Channels 4/8 AS-5B30002A 0 to +50 mV
Operating Range Selectable per channel AS-5B30003A 0 to +100 mV
Resolution 12 bit AS-5B30004A -10 to +10 mV
Accuracy AS-5B30005A -50 to +50 mV
Calibration Accuracy ± .15% at 25° C AS-5B30006A -100 to +100 mV
Non-Linearity ± .05% AS-5B31001A 0 to +1 V
Gain Drift ± .01%/° C AS-5B31002A 0 to +5 V
Zero Drift ± .002%/° C AS-5B31003A 0 to +10 V
Update Times 4 ms, all 4 channels AS-5B31004A -1 to +1 V
Isolation AS-5B31005A -5 to +5 V
Channel to Channel 1500 V continuous AS-5B31006A -10 to +10 V
Power Required Voltage Input, 10KHz.
+5 V < 600 mA AS-5B40001A 0 to +10 mV
+4.3 V < 10 mA AS-5B40002A 0 to +50 mV
-5 V 0 mA AS-5B40003A 0 to +100 mV
Dimensions AS-5B40004A -10 to +10 mV
Space Required 2 slots AS-5B40005A -50 to +50 mV
Weight 3 lbs (1.4 kg) AS-5B40006A -100 to +100 mV
Terminal Connector AS-8535-000 AS-5B41001A 0 to +1 V
AS-5B41002A 0 to +5 V
AS-5B41003A 0 to +10 V
AS-5B41004A -1 to +1 V
AS-5B41005A -5 to +5 V
AS-5B41006A -10 to +10 V
Current Input, 4 Hz.
AS-5B32001A 4 to 20 ma
AS-5B32002A 0 to 20 ma
AS-B875-200 Terminal AS-B875-200 Mechanical Thermocouple Input, Linear, 4 Hz.
Numbering and Wire Keying for Housings AS-5B47J01A (Type J) 0 to +760°C
Connections AS-5B47J02A (Type J) -100 to +300°C
AS-5B47J03A (Type J) 0 to +500°C
TOP AS-5B47K04A (Type K) 0 to +1000°C
AS-5B47K05A (Type K) 0 to +500°C
AS-5B47T06A (Type T) -100 to +400°C
AS-5B47T07A (Type T) 0 to +200°C
AS-5B47E08A (Type E) 0 to +1000°C
AS-5B47R09A (Type R) +500 to +1750°C
AS-5B47S10A (Type S) +500 to +1750°C
AS-5B47B11A (Type B) +500 to +1800°C
RTD Input, Isolated, 4 Hz.
BOTTOM AS-5B34P01A -100 to +100°C
AS-5B34P02A 0 to +100°C
AS-5B34P03A 0 to +200°C
AS-5B34P04A 0 to +600°C
AS-5B34C01A 0 to +120°C, 10 Ω @ 0°C
AS-5B34C02A 0 to +120°C, 10 Ω @ 25°C
AS-5B34N01A 0 to +300°C
Strain Gauge, 10 KHz.
AS-5B38002A Full Bridge, 3 mV/V 300 Ω min.
AS-5B38004A Half Bridge, 3 mV/V 300 Ω min.
(When facing housing, place
AS-5B38005A Full Bridge, 2 mV/V 300 Ω min.
pins in holes shown by black
circles.)
3-70
Specification AS-B881-001 Specification AS-B881-108
Description 24 Vdc (LATCH) input Description 115 Vac protected output
Type of Operation True High Number of Points 8
Number of Points 16 Operating Voltage 80 ... 130 Vac / 47 ... 63 Hz
Operating Voltage 20 ... 28 Vdc Number of Groups 8
Number of Groups 1 Outputs per Group 1
Inputs per Group 16 ON Current
Max. Input Voltage Max. per Point 2 A continuous
Continuous 30 Vdc 30 A for one cycle
Surge 40 Vdc for 10ms Max. per Group 2A
Wetting Current 6 mA (typical) @ 24 Vdc Max. per Module 16 A
Min. Pulse Width 0.5 ms Leakage Current 5 mA max @ 130 Vac
Repetition Rate One per second Max. Response Time
Power Required OFF to ON 9 ms @ 60 Hz
+5 V 30 mA ON to OFF 9 ms @ 60 Hz
+4.3 V 1.1 mA Power Required
-5 V 0 mA +5 V 285 mA
External Power Supply 24± 4 Vdc, 310 mA +4.3 V 240 mA
Dimensions -5 V 0 mA
Space Required 1 slot Dimensions
Weight 2.75 lbs (1.25 kg) Space Required 1 slot
Terminal Connector AS-8534-000 Weight 2.4 lbs (1.1 kg)
Fusing One per group Terminal Connector AS-8535-000
TOP TOP
BOTTOM BOTTOM
3-71
Specification AS-B881-508 Specification AS-B882-032
Description 125 Vdc True High output Description 24 Vdc diagnostic output
Number of Points 8 Number of Points 32
Operating Voltage 5 ... 140 Vdc Operating Voltage 20 ... 28 Vdc
Number of Groups 8 Number of Groups 4
Outputs per Group 1 Outputs per Group 8
ON Current ON Current
Max. per Point 4.0 A Max. per Point 1A
Max. per Module 29 A Max. per Group 6A
Leakage Current < 30 mA Max. per Module 24 A
Max. Response Time Leakage Current 1 mA max. @ 28 Vdc
OFF to ON < 75 µs Max. Response Time
ON to OFF < 100 µs OFF to ON 1 ms
Power Required ON to OFF 1 ms
+5 V 300 mA Power Required
+4.3 V 0 mA +5 V 300 mA
-5 V 0 mA +4.3 V 10 mA
External Power Supply 5 ... 140 Vdc -5 V 0 mA
Dimensions External Power Supply 24± 4 Vdc, 600 mA
Space Required 1 slot (Excluding field load current)
Weight 2.4 lbs (1.1 kg) Dimensions
Terminal Connector AS-8535-000 Space Required 1 slot
Weight 2.42 lbs (1.1 kg)
Terminal Connector AS-8535-000
Fusing Electronic, one-per point
TOP TOP
BOTTOM BOTTOM
3-72
Specification AS-B882-116
Description 24 Vdc Supervised wire output
Detects open or short circuits on each I/O point and reports fault to PLC
Number of Points 16
Working Voltage 19.2 to 30.0 Vdc
Number of Groups 2
Outputs per Group 8
Continuous Current
Max. Per Point 0.5 A
Max. Per Group 4.0 A
Max. Per Module 8.0 A
Off State Leakage Current 3 mA max. at 30 Vdc, max. allowable load resistance is 6K Ω
On State Voltage Drop 0.5 Vdc maximum at 0.5A
Inrush Current 1.0A peak for 0.1 ms at 4 pulses per second while carrying 0.5A DC
minimum load current 10 mA
Power Required
+5 Vdc 350 mA maximum all outputs ON
+4.3 Vdc 10 mA
-5 Vdc 0 mA (not used)
External Power Supply Nominal 24 Vdc at external load current plus 0.5 amps.
Supply must be capable of pulse current of external load plus 5 amps.
Dimensions
Space Required 1 slot
Weight 2 lbs (0.91 kg)
Terminal Connector AS-8535-000
Fusing No internal fusing
TOP
BOTTOM
3-73
Specifications AS-B882-239
B882-239 High Speed Counter Module
Number of Counters 2
Number of Auxiliary Inputs 6
The B882-239 High Speed Counter Module has two identical and Number of Outputs 6
independent counters for applications that require counting or Number of Groups 1
comparisons. Because the module handles the counting within its Input Voltage Range 0-32 Vdc
own internal logic, the PLC is free to do other tasks. Input Current 8.1 mA with 32 Vdc supply
5 mA with 28 Vdc supply
Each counter counts to 9999, and the two counters can be Output ON Voltage 1.0 Vdc (max.) @ 0.5 A
cascaded to count to 99,999,999. Each counter counts up 0.3 Vdc (typ.) @ 0.5 A
to 30,000 pulses per second. The module has two modes of 0.4 Vdc (max.) @ 0.1 A
operation, high frequency and low frequency, so its maximum 0.2 Vdc (typ.) @ 0.1 A
count rate varies from 350 Hz (low frequency) to 30 KHz Output OFF Leakage Current 1.0 mA (max.) @ 32 Vdc
(high frequency). Output Load Current 0.5 A continuous per output
1.5 A fusing per group
Because the module acts independently of the PLC, it counts Max. Count Frequency
the high speed pulses from the field independently of the PLC High Frequency Mode 30 KHz
scan. The counter automatically reports its current count to the Low Frequency Mode 350 Hz
Reset Pulse Width 13 µs (min.)
PLC every scan. Where high performance is required, the Enable Set Up Time
module’s own outputs can trigger independently of the High Frequency Mode 11 µs (max.)
controller scan. Low Frequency Mode 1.3 µs (max.)
Range of Signal Values
The major features of the B882-239 High Speed Counter -Log “1” Neg. Threshold 1.1 Vdc (min.), 2.2 Vdc (typ.)
Module include: -Log “0” Pos. Threshold 3.5 Vdc (max.), 2.7 Vdc (typ.)
-Hysteresis 0.36 Vdc (min.), 0.49 Vdc (typ.)
• Two independent counters (0-32 Vdc, True Low) Power Required
• 0-30 Khz operation with selectable low frequency filter + 5 Vdc 188 mA
• Six auxiliary field inputs (0-32 Vdc, True Low) + 4.3 Vdc 0 mA
• Six field outputs (0-32 Vdc, True Low) -5 Vdc 0 mA
• Self-diagnostics Dimensions
Space Required 1 slot
Weight 2.94 lbs (1.34 kg)
Terminal Connector Included
Fusing One per group
TOP
BOTTOM
3-74
Specifications AS-B883-001 B883-001 High Speed Counter Module
Number of Counters 2
Number of Auxiliary Inputs 6 The Modicon B883-001 High Speed Counter Module is a
Number of Outputs 3 powerful control tool providing solutions for both simple high
Voltage Range speed counting and more involved timing and sampling control
5 Vdc 2.4 to 5.5 Vdc applications, all at speeds up to 50 kHz.
12 Vdc 6 to 16 Vdc
24 Vdc 12 to 32 Vdc While programmed directly through a Modicon programmable
Transition 0 to 1 1 to 0 controller, the High Speed Counter Module is microprocessor-
5 Vdc 2.4 Vdc 1.6 Vdc based and operates independent of the PLC. The module
12 Vdc 5.6 Vdc 4.0 Vdc provides two counters that can operate separately or jointly,
24 Vdc 11.2 Vdc 8.0 Vdc depending on the control system's needs.
Output Load Current At 5 Vdc, 140 mA per output
Max Count Frequency 50 kHz
Ramp Time 7 V per sec Counter #1 Counter #2
Power Required Bi-direction (up/down) count Unidirectional up counter
+ 5 Vdc 677 mA
Pulse or Quadrature encoder
+ 4.3 Vdc 0 mA
input modes 1 kHz and 1 MHz internal
-5 Vdc 0 mA
clock
Dimensions
Space Required 1 slot Counts up to 9,999,999 Counts up to 9,999
Weight 3.3 lbs (1.49 kg) Two programmable outputs
Terminal Connector Included with three modes of operation Hardwire reset and enable
Hardwire enable and preset Software reset and enable
Software enable and preset Programmable match output
TOP
BOTTOM
3-75
B883-101 and B883-111 CAM Emulator Modules Specifications AS-B883-101/111
Number of Inputs 12
The B883-101 and B883-111 CAM emulator modules are Number of Outputs 8
used to automate the operation of metal shaping and cutting Supply Voltage Max. 7 Vdc
presses for any mass production industry such as automobile Internal Signal Loading RTH = 10 kΩs
parts fabrication. VTH = 0.925 x VDD,
(VDD = 5 Vdc ± 5%)
The CAM module receives a 12-bit (plus control) parallel Working Voltage 20 to 28 Vdc
position code from an encoder. The module then transmits an Peak Voltage 32 Vdc max for 10 ms
ON State Voltage Drop 0.6 Vdc max at 200 mA
8-bit parallel control code to its discrete outputs based on the one channel on
received position data. Inrush Current Max. 2.5 A per channel
0.5 ms at 5% duty cycle
Programming and operation of the CAM module is simple. You OFF State Leakage Current Max. 0.75 mA at 28.8 Vdc
load the operating instructions into a CAM module through the Typ. 0.1 mA
PLC via the I/O system. You can define up to 16 output intervals Response Time Max. 20 ms
distributed at random among the 8 outputs. The CAM module Transition Time Max. 32 ms
accepts inputs in binary, binary coded decimal, or Gray code. Power Required
Once programmed, the module receives, processes, and +5 Vdc 1000 mA
outputs the position codes at a rate of 4,000 Hz (once every +4.3 Vdc 0 mA
250 microseconds). –5 Vdc 0 mA
Dimensions
If your application requires velocity compensation, choose the Space Required 1 slot
B883-111 module. The B883-111 module compensates for Weight 3.98 lbs (1.81 kg)
changes in velocity. Terminal Connector Included
TOP
3-76
Specifications AS-B883-200 B883-200 Thermocouple Input Module
Description Thermocouple input
Type B,E,J,K,R,S,T,N The Modicon B883-200 Thermocouple Input Module is a smart
or linear mV I/O module that multiplexes up to ten thermocouples into three
Inputs per Module 10 consecutive input registers of the control system.
Max. Common Mode Voltage 200 Vdc/Vac (peak)
Resolution 1°C, 1°F, 10 mV Each B883-200 module provides reference junction temperature
Under Program Control 0.1°C, 0.1°F, 1 mV compensation, open circuit detection, and linearization for ten
Update Time 100 ms per selected channel thermocouples. Also built-in are self-calibration, internal
1 sec. max. all channels diagnostics, and 800-Series bus diagnostics.
Power-up Time 13 sec. max.
Warm-up Time 2 Min. max. Any mix of type B, E, J, K, R, S, T, or N thermocouple operations
Power Required or simple -20 to +80 mV input operations may be set by the
+5 Vdc 400 mA
user under program control.
+4.3 Vdc 5 mA
-5 Vdc 0 mA For thermocouple inputs, the PLC can access individual
Dimensions
Space Required 1 slot
temperature readings in degrees Centigrade, Fahrenheit, or in
Weight 4 lbs (1.8 kg) compensated millivolts. Each time the PLC scans the B883-200
Terminal Connector Included module, it receives the specified temperature or millivolt reading
along with open-circuit and module health data. The thermocouple
wire is terminated on a special isothermal connector assembly on
the housing. Each B883-200 module uses three consecutive input
registers and three output registers.
TOP
BOTTOM
3-77
B883-201 RTD Input Module Specifications AS-B883-201
Description RTD input
The Modicon B883-201 Resistance Temperature Detector (RTD) American or European
module is a smart I/O module that multiplexes up to eight two- 100 Ω Platinum
or three-wire RTDs into three consecutive input registers of a Inputs per Module 8
control system. Max. Common Mode Voltage 7 Vdc/Vac (peak)
Resolution 1°C, 1°F, 10 Ω
Each B883-201 module provides linearization for any mix of Under Program Control 0.1°C, 0.1°F, 1 Ω
8 RTDs. Also built-in are self-calibration, internal diagnostics, Update Time 125 ms per selected channel
1 sec. max. all channels
and 800-Series bus diagnostics. Power-up Time 13 sec. max.
Warm-up Time 2 min. max.
American standard platinum, European standard platinum per
Power Required
DIN, or linear resistance input can be selected by the user +5 Vdc 640 mA
under program control. +4.3 Vdc 5 mA
-5 Vdc 0 mA
When an RTD is selected, the PLC can access each individual Dimensions
temperature reading in Centigrade, Fahrenheit, or in Space Required 1 slot
compensated millivolts. Each time the PLC scans the B883-201 Weight 4 lbs (1.8 kg)
module, it receives the specified temperature or millivolt reading Terminal Connector AS-8535-000
along with open-circuit and module health data.
Each B883-201 uses three consecutive input registers and
three output registers. These registers are assigned to the
same slot within the channel.
TOP
BOTTOM
3-78
Specifications AS-B884-002 B884-002 PID Module
Analog Inputs 4, current/voltage
Input Range 4 ... 20 mA, 1 ... 5 Vdc, 0 ... 10 Vdc The B884-002 PID Module provides two completely
Common-mode Rejection > -90 db, 50/60 Hz independent and separate Proportional Integral Derivative
Max. Common-mode Voltage 180 Vdc/Vac peak (PID) loops. You can configure the PID loops for control
Normal Mode Rejection 60 db strategies including open loop, closed loop, PID, PID on
Accuracy (at 25° C) 0.05% typ, +0.02% max error squared, and cascade control.
Thermocouple Inputs 2 You configure the PID module using a configuration program
Types B,E,J,K,N,R,S,T (Part # SW-B8DD-3DA) on an IBM or compatible personal
Common-mode Rejection > -120 db, 50/60 Hz
Max. Common-mode Voltage 180 Vdc/Vac peak
computer. You can download the data either through the PLC
Normal Mode Rejection 60 db or directly to the modules, where it is stored in a non-volatile
Repeatability (constant temp.) +0.5° F, +0.3° C in 24 hours EEPROM memory.
Frequency Inputs 1, sine wave/magnetic pick-up
(bipolar) and rectangular To ensure the highest accuracy and reliability, the module has
wave (unipolar) fully floating, isolated, and protected inputs and outputs. The
Input Voltage Range module has seven independently configured analog inputs (4
Unipolar 2 Vpp to 50 Vpp voltage/current, 2 thermocouple, 1 frequency), two analog
Bipolar 10 mVpp to 360 Vpp outputs, two discrete inputs, and two discrete outputs. Each
loop is assigned two voltage and one thermocouple inputs.
Discrete inputs 2 There is no need for any analog adjustments such as trimpots
Input Voltage 24 Vdc, potential isolated
for zero, offset, or span, which results in superior accuracy,
ON Threshold 5.0 Vdc or more
OFF Threshold 0.8 Vdc or less
stability, and reliability.
Min. Turn On Current 5 mA
Dimensions
Space Required 1 slot BOTTOM
Weight 4 lbs (1.81kg)
Terminal Connector Included
3-79
B885-002 ASCII / BASIC Module Specifications AS-B885-002
Data Exchange
The B885-002 ASCII / BASIC Module runs user-written BASIC Module to PLC Via OURBUS, 6 input registers,
programs independently of the controller’s memory logic and 6 output registers
scan. It also performs READ and WRITE commands to and
from serial devices connected to either of the module’s two RS Module to Terminal Via 2 ports, RS 232C or RS 422
232/422 ports (jumper selectable). In addition, its real-time Transmission Rate 110, 300, 600, 1200, 2400,
4800, 9600, 19200 baud
clock/calendar allows the module to run a BASIC program or
software selectable
flag and return a value to the PLC at a user specified date
and time. Power Required RS 422 mode RS 232 mode
+5 Vdc 500 mA 400 mA
The module provides report generation, interactive operator +4.3 Vdc 1760 mA 1000 mA
interface, high level math, peripheral communications, and -5 Vdc 0 mA 0 mA
data storage.
Dimensions
Using a dumb terminal or an IBM personal computer with Space Required 1 slot
Emulator Software (Part # SW-E885-1DA), you program the Weight 3 lbs (1.4 kg)
module’s 53K of user memory. If you need more memory, Terminal Connector Included
you may provide an additional 32K of user EPROM. You can
designate part of the memory as retentive variable memory to
store formulas or other process parameters.
TOP
Pin # Direction Signal
1 N/A Protective ground
2 OUT RS232 Send data
3 IN RS232. Receive data
4 OUT RS232 Request to send
5 IN RS232 Clear to send
6 IN RS232 Data set ready
7 N/A RS232 & RS422 Common
12 OUT RS422 Request to send high
13 OUT RS422 Request to send low
14 OUT RS422 Send data high
15 OUT RS422 Send data low BOTTOM
16 IN RS422 Clear to send low
17 IN RS422 Clear to send high
18 OUT +5V (Current limited,
5mA by 1K)
19 IN Select input-RS422 high/
RS232 low
20 OUT RS232 Data terminal ready
21 IN RS422 Receive data high
25 IN RS422 Receive data low
3-80
B885-101 and B885-111 Motion Modules The PLC communicates with the motion modules through six
input and six output registers with the control instructions
Modicon B885-1xx Motion Modules are high performance, providing a powerful, smooth and fast link between the two.
single axis servo motion controllers contained in a single-width Adjustable command buffering and direct register to function
800-Series I/O module. They are designed to plug directly into bits provide added communication speed for high
the I/O rack of the Modicon 984 PLC, although they are response functions.
capable of standalone operation. They can control brushless
and brush-type servo motors, as well as hydraulics. Motion programs, developed using MMDS, are either stored
directly in the flash memory of the motion module or as registers
The modules use Schneider Automation's patented Direct in the PLC.
Numerical Processing (DNP) technology. Advanced digital
brushless motion control eliminates potentiometer adjustments The Modicon Motion Development Software (MMDS) is an on-
and analog velocity loops for optimal control. line/off-line, menu driven package (Part # SW-MMDS-1DB) for
the IBM-AT or compatible computers. It enables the user to set
The B885-101 module uses a resolver to provide feedback for up, program, operate and diagnose operation of the motion
the position, velocity, and commutation of the motor. module. The program and file manipulation features are a
Essentially, a rotary brushless transformer that provides versatile system for application management. The MMDS
absolute position information to the motion module, the communicates via a computer serial port to the Modbus port on
resolver gives the module a high degree of noise immunity. the motion module.
The B885-111 module additionally has two quadrature encoder
interfaces for extra position and velocity feedback.
Control communication interface to the B885-1xx modules can
be either through the 800 I/O system backplane or the
Modbus/RS-232 serial port. The module is designed to work
directly with the Modicon Cyberline 1000 series brushless
servo amplifiers as well as those of third-party vendors.
TOP
BOTTOM
3-81
Specifications AS-B885-1xx
Motion
Absolute Positioning Range 232 bits; in., mm, or other units
Speed Range 232 to 1; counts/sec, in/sec, mm/sec, RPM, etc.
Digital Servo Loop
Position Loop Update 1 msec
Velocity Loop Update 0.5 msec
Commutation Update 0.25 msec
Potentiometer Adjustments None; parameters set in software
Feedback
Resolver Modicon "T" type brushless
Used for position, velocity and commutation
Max. Speed 6,000 RPM, motor/drive dependent
Resolution 65535 (16-bit) counts/revolution (maximum)
System Accuracy
Typical ± 10 arcmin
Worst Case ± 15 arcmin
Position Repeatability ± 3 arcmin
Encoder (-110 only, two channels) Encoders supplied by customer. Used for position
and velocity
Type Differential or single end
Voltage 5 ... 24 volt ± 20%
Impedance >500 Ω @ 5V nominal
Frequency
Nominal 200 KHz
Maximum 500 KHz
Input Multiplier 4X
Maximum Speed Encoder dependent, 2 MHz internal pulse rate max.
System Accuracy Encoder dependent; 0.5 arcmin maximum
Source Power Supplied by
Module (Encoder may be 400 mA @ 5 Vdc ± 10% and/or
powered externally) 200 mA @ 12 Vdc ± 10%
I/O
Digital Inputs 7 (24 Vdc, ± 20 %)
Digital Outputs 3 (24 Vdc, ± 20 %, 150 mA max. each)
Analog Output ± 10 V, 3 mA max., 12 bit resolution
Analog Input ± 10 V, 10 bit resolution
Communications
Port RS-232 serial, Modbus slave
Baud Rate 300 ... 9600 baud, software selectable (9600 default)
Connector DB9, female
Backplane I/O bus, 6 input/6 output registers
Power Requirements
External Power Supply 24 Vdc ± 20% @ .375 A max. plus output current draw
I/O Rack Power
+5.0 V 25 mA
+4.3 V 0 mA
-5.0 V 0 mA
Physical
Space Required 1 slot
Weight 2 lbs (.9 kg)
3-82
Specification AS-B984-100/101 B984 Discrete High Speed Logic Solver Module
Mode of Operation True high
Working Voltage 20 ... 28 Vdc The Modicon B984-100 Discrete High Speed Logic Solver offers
Response Time the power of a 984 PLC with the response of an intelligent I/O
Inputs 100 µsec max (no filtering) module. With a total system throughput of less than one
Outputs 1 msec max. millisecond, the module provides the capability to control high
Input speed applications not possible with conventional PLCs.
Number of Inputs 16
Number of Groups 1 The full 984 basic instruction set makes the module compatible
Source Resistance 1000 Ω
with existing 984 application and programming software, and
ON Level (<1M Source Impedence) 19.2 Vdc
OFF Level (0 Source Impedence) 6 Vdc 4K user logic plus 2K registers provide ample space for
ON Condition Threshold 18 Vdc application programs.
Input Wetting Current 6 mA minimum at 24 Vdc
Outputs The B984-100 is fully compatible with the rest of the 984 Family.
Number of Outputs 8 It services its own dedicated I/O and communicates with the
Number of Groups 1 host PLC via the I/O bus. The B984 module and the host PLC
Min. ON State Output Voltage 19.2 Vdc pass four or eight 16-bit registers bi-directionally each time the
ON Current Max. 1 A per channel host PLC scans its logic. A built-in Modbus port on the B984
Max. 8 A per module allows connection to programmers, operator interfaces, local
Max. OFF State Leakage 1 mA area networks, and host computers.
Min. Load Current 100 mA
Inputs on the B984 have programmable filtering to allow for
Diagnostic Information Open Load, Short to quick response and maximum system reliability. Outputs
*
Ground or Supply, Current provide fault diagnostic information which is annunciated in the
limit, Over temperature
B984 and is available to the host PLC.
Power Required
+5 Vdc 0 mA Multiple B984 modules may be used in any control system
+4.3 Vdc 0 mA
using 800-Series I/O. They can be inserted in any slot, and are
-5 Vdc 0 mA
External Power Required CPU 20 ... 30 Vdc, 2A limited only by the I/O bits available in the system.
(Excluding field
load current)
Output 20 ... 30 Vdc, 10A
Dimensions
Space Required 1 slot
Weight 2 lbs (0.9 kg)
Terminal Connector Included
AS-B984-100 AS-B984-100
Terminal Numbering Mechanical Keying for
and Wire Connections Housings
TOP
BOTTOM
MAX WIRE SIZE IS ONE 14 AWG WIRE; TWO 18 PIN CONNECTORS *AS-B984-101 does not support open load detection.
3-83
Housings
3-84
800 Series Housing Technical Specifications H810-208 Primary Housing
Description
The H810-208 is a primary subrack for local 984-38x and
AS-H819-209 Primary Housing, 19"
AS-H827-209 Primary Housing, 27" 48x systems, or remote I/O drops using P89x interfaces.
AS-H819-103 Primary Housing, 19" This rack is used stand-alone and cannot be connected to
AS-H827-103 Primary Housing, 27" secondary subracks.
AS-H819-100 Secondary Housing, 19"
AS-H827-100 Secondary Housing, 27" The H810-208 is designed to be mounted on a wall or in a
AS-H810-208 Primary Housing, 10" standard NEMA enclosure.
w/OURBUS only
AS-H810-209 Primary, 10" w/System Bus Secondary Housings
and OURBUS
for 685, 785 controllers All housings in a local or remote I/O drop, except the primary
AS-H810-100 Secondary, 10" housing, must be secondary housings. Incoming power and
w/OURBUS only signal cables connect on the top of the housing. Outgoing
Maximum Available I/O Slots power and signal cables connect on the bottom. Secondary
AS-H819-209 6 housings available are the H810-100, H819-100 and H827-100
AS-H827-209 10
AS-H819-103 4
secondary housings.
AS-H827-103 8 H810-100, H819-100 and H827-100 Secondary Housings
AS-H819-100 7
AS-H827-100 11
AS-H810-xxx 3 The H810-100, H819-100 and H827-100 housings are
Earth Connection Earth ground screw on lower secondary housings for local or remote 800 Series I/O drops.
edge of subrack The H819 contains 7 slots that may house I/O modules. The
Environmental H827 contains 11 slots that may house I/O modules. The H810
Operating Temperature 0 ... 60°C contains 4 slots that may house I/O modules. If auxiliary I/O
Relative Humidity 0 ... 95% (non-condensing) power is required, the power supply must be located in the
Shock Resistance 10 G for 10 ms first slot.
Physical The H810, H819 and the H827 may be mounted on a wall or
Space Requirement (W x H x D) inside a protective NEMA cabinet. The H819 may also be
AS-H810 ... xxx 10.25 x 13.5 x 8.9 in mounted in a 19 inch standard rack; special mounting flanges
(261 x 343 x 255 mm)
AS-H819 ... xxx 17.5 x 13.5 x 8.9 in
are provided for a rack mount installation.
(444 x 343 x 225 mm) Because they are used only as secondary housings, the H810-
AS-H827 ... xxx 27.1 x 13.5 x 8.9 in
(688 x 343 x 225 mm)
100, H819-100 and H827-100 housings must never contain an
Weight RIO interface device.
AS-H810 ... xxx 10 lbs (4.6 kg)
AS-H819 ... xxx 15 lbs (6.8 kg)
AS-H827 ... xxx 20 lbs (9.1 kg)
3-85
800-Series I/O Cabling
(1) 984-38x/48x, P89x occupy slot 1, slot 2 available for I/O module.
(2) 984-68x/78x occupy slot 1 and 2.
* Maximum 32 modules per drop (Maximum 2 racks for 984-38x/48x).
Available Lengths
Model Description 1.5 ft 5 ft 6 ft 12 ft 20 ft
AS-W801-xxx I/O signal cable between racks -002 N/A -006 -012 N/A
AS-W808-xxx I/O power cable to added rack w/o power supply -002 -005 N/A N/A N/A
AS-W802-xxx I/O power cable to added rack w/o power supply N/A N/A N/A -012 N/A
AS-W804-xxx I/O power cable to added rack with power supply -002 -005 N/A -012 N/A
AS-W929-xxx Local I/O cable for 984X N/A N/A -006 -012 -020
3-86
I/O Cable Configurations
w/H8xx-103 Primary Housing
3-87
800-Series I/O Power Supplies
A local or remote I/O system requires a power supply for the I/O
modules and for communications support between the modules
and the PLC. In some cases, the power supply is built into the
PLC or into the remote I/O interface where, in other cases, the
power supply and the I/O interface are separate components.
Certain applications will require an auxiliary power supply
should the I/O requirements exceed the capacity of the primary
supply. Below is a list of 800-Series I/O power supplies, both
integrated and auxiliary. To determine the power requirements
of your system, you must add together the individual power
requirements of the I/O and option modules within your system.
AS-P802-001 Remote Primary & Secondary 24 Vdc 1.5 2500 10100 500
AS-P810-000 Remote Primary & Secondary 115/230 Vac 1.5 5000 5000 300
PC-X984-68x/78x Internal Supply for Local I/O 115/230 Vac, 24 Vdc 1.5 8000 6000 5001
PC-X984-38x/48x Internal Supply for Local I/O 115/230 Vac, 24 Vdc 1 3000 3000 2502
AS-P890/892-000 Internal Supply for Remote I/O 115/230 Vac, 24 Vdc 1 3000 3000 2502
AS-P830-000 Secondary 115/230 Vac, 24 Vdc 1.5 5000 6000 5003
AS-P840-000 Remote Primary/Secondary 115/230 Vac 1.5 50004 100004 500
1
Total max. = 8,000 mA
2
Total max. = 3,000 mA
3
Total max. = 6,000 mA
4
Total max. sum of (+4.3V and +5V) @ 55°C = 15000 mA
@ 60°C = 12000 mA
Note: Model PC-X984 is for E984 controllers.
3-88
P802 I/O Power Supply P810 I/O Power Supply
A P802 Power Supply may serve as either a primary or A P810 Power Supply may serve as either a primary or
auxiliary power unit in an 800-Series I/O drop. Its input auxiliary power unit in a 800-Series I/O drop. Its input
voltage is 24 Vdc. voltage (115 Vac or 230 Vac) is determined by the way the
input terminal block is wired.
The P802 is 1.5 slots wide. When used in a primary housing,
it consumes the first 1.5 slots and is followed immediately by The P810 is 1.5 slots wide. When used in a primary
a remote I/O interface. When used as an auxiliary power housing, it consumes the first 1.5 slots, and is followed
supply, it consumes the first two slots in a secondary housing. immediately by a remote I/O interface. When used as an
auxiliary power supply, it consumes the first two slots in a
secondary housing.
Environmental Environmental
Operating Temperature 0 ... 60°C Operating Temperature 0 ... 60°C
Relative Humidity 0 ... 95% (non-condensing) Relative Humidity 0 ... 95% (non-condensing)
Shock Resistance 10 G (11 ms) Shock Resistance 10 G (11 ms)
Physical Physical
Space Requirements 1.5 slots in an H8xx-103 Space Requirements 1.5 slots in an H8xx-103
Primary housing, or 2 slots in Primary housing, or 2 slots
an H8xx-100 Secondary in an H8xx-100 Secondary
housing housing
Weight 7 lbs (3.2 kg) Weight 7 lbs (3.2 kg)
3-89
P830 I/O Power Supply P840 I/O Power Supply
A P830 Power Supply serves as an auxiliary power unit in an A P840 Power Supply may serve as either a primary or
800-Series I/O drop when the power limitations of the primary auxiliary power unit in a 800-Series I/O drop. Its input
power supply are exceeded. voltage (115 Vac or 230 Vac) is determined by the way you
wire the input terminal block.
The P830 is 1.5 slots wide. It must be installed in the two left-
most slots of a secondary housing. The P840 is 1.5 slots wide. When used in a primary housing,
it consumes the first 1.5 slots, and is followed immediately by
a remote I/O interface. When used as an auxiliary power
supply, it consumes the first two slots in a secondary housing.
AS-P830-000 AS-P840-000
I/O Power Supply Technical Specifications I/O Power Supply Technical Specifications
Power Supply
Power Supply Input Voltage 115/230 Vac
Input Voltage 115/230 Vac Output Voltage
24 Vdc +5 Vdc 5.0 A1
Output Voltage +4.3 Vdc 10.0 A1
+5 Vdc 5000 mA -5 Vdc 0.5 A
+4.3 Vdc 6000 mA Environmental
-5 Vdc 500 mA Operating Temperature 0 ... 60°C
Total current must not Relative Humidity 0 ... 95% (non-condensing)
exceed 6000 mA Shock Resistance 15 G (11 ms)
Environmental Physical
Operating Temperature 0 ... 60°C Space Requirements 1.5 slots in an H8xx-103
Relative Humidity 0 ... 95% (non-condensing) Primary housing, or 2 slots
Shock Resistance 10 G (11 ms) in an H8xx-100 Secondary
Physical housing
Space Requirements 2 slots in a secondary Weight 7 lbs (3.2 kg)
subrack 1
Total max. sum of
Weight 3 lbs (1.4 kg) (+4.3V and +5V) @ 55° C = 15000 mA
@ 60° C = 12000 mA
3-90
Remote I/O Drop Interfaces
Interfaces
Feature J890 J892 P890 P892 D908 J290 J291
3-91
J890/J892 RIO Interfaces
Description
AS-J890-101 Single Cable RIO Interface
AS-J890-102 Redundant Cable RIO
Interface
AS-J892-101 Single Cable RIO Interface
w/ ASCII
AS-J892-102 Redundant Cable RIO
Interface w/ ASCII
Communication
Coaxial Cable Connectors 1 or 2
J892 ASCII Device Support 2
RIO Communication Protocol S908 (HDLC)
Environmental
Operating Temperature 0 ... 60°C
Relative Humidity 0 ... 95% (non-condensing)
Shock Resistance 10 G (11 ms)
Physical
Space Requirements 1.5 slots in H8xx-103
housing (Slots 2 & 3)
Weight 5 lbs (2.25 kg)
3-92
P890/P892 RIO Interfaces
Description
AS-P890-000 Single Cable RIO Interface
AS-P892-000 Single Cable RIO Interface
w/ ASCII
Communication
Coaxial Cable Connectors 1
P892 ASCII Device Support 2 ports
RIO Communication Protocol S908 (HDLC)
Power Supply
Input Voltage 115/230 Vac
24 Vdc
Output Voltage
+5 Vdc 3 A (max.)
+4.3 Vdc 3 A (max.)
-5 Vdc 0.25 A
Total 3A
Environmental
Operating Temperature 0 ... 60°C
Relative Humidity 0 ... 95% (non-condensing)
Shock Resistance 10 G (11 ms)
Physical
Space Requirements 1 Slot in H8xx-209 or
H810-208 housing
Weight 5 lbs (2.25 kg)
3-93
Remote I/O with ASCII Communication
The J812 and J892 RIO Interfaces (for 800 Series I/O) and the
P453 RIO Interface (for 200 and 500 Series I/O) have 25-pin
female ASCII ports; the P892 RIO Interface (for 800 Series I/O)
has 9-pin female ASCII ports:
25-Pin Male RIO ASCII Port 9-Pin Male RIO ASCII Port
J812, J892, P453 P892
Shield 1 Shield 1
TX 2 RX 2
RX 3 TX 3
RTS 4 DTR 4
CTS 5 Ground 5
DSR 6 DSR 6
Ground 7 RTS 7
DTR 20 CTS 8
3-94
Configuring A Local I/O System
Local I/O configurations are where the PLC and I/O modules The following tools are designed to assist you in the
communicate directly via the backplane and through cables configuration of 984 local I/O systems. Refer to the
that extend the I/O bus (OURBUS). configuration pages that follow associated with the controller
CPU you have chosen.
The 984 PLCs that support local configurations include all
models except the 984A and 984B. A local I/O system consists 1. Local 984-381/385 and 984-480/485 systems in H810, H819
of the PLC, I/O and associated housings, power and signal and H827-209 housings.
cables, and, where required, auxiliary power supplies.
2. Local 984-381/385 and 984-480/485 in H810-208 four-slot
Local I/O must be addressed as Drop #1 in the 984 Traffic Cop. housing.
An auxiliary power supply is required when total power 3. Local 984-685 and 984-785 systems.
consumption by all modules in the local drop exceeds the
capacity of the primary supply. Auxiliary power supplies provide 4. Local 984X system.
all I/O power to modules beyond its location and provide no
power to modules located before it.
The table below provides you with maximum local drop size
figures for the PLCs that support local I/O. Local drops cannot
exceed the figures shown.
Note: Each discrete I/O point requires 1 bit of addressing. Each analog point or register word requires 16 bits of addressing.
3-95
3-96
984-381/385/480/485 Configuration (local I/O) System Number _____
(page )
984- 8 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
CPU I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8 -209
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #1
W80___-0__ W80___-0__
Power Signal I/O slots may contain:
Cable Cable Any B8xx-xxx I/O Module or a J878-000 Modbus modem
984- 8 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8___-100
or
P8___0-000
Aux. Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-97
3-98
H810-208 Configuration (local I/O) System Number _____
(381/385/480/485) (page )
Configuration 1 (Controllers)
984- 8 8 - 8 - 8 - Housing
CPU I/O slot I/O slot I/O slot H8 -208
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #1
3-99
3-100
984-685/785 Local Drop Configuration System Number _____
(page )
984- 8 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - Housing
CPU I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8 -209
or or or or
9 - 9 - 9 - 9 - 9 -
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #1
W80___-0__ W80___-0__
Power Signal System slots may contain: S908/S975/S911/D908
Cable Cable
8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8___-100
or
P8___0-000
Aux. Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-101
984-685/785 Local Drop Configuration System Number _____
(page )
W80___-0__ W80___-0__
Power Signal
Cable Cable
8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8 -100
or
P8___0-000
Aux. Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #1
W80___-0__ W80___-0__
Power Signal System slots may contain:
Cable Cable Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8___-100
or
P8___0-000
Aux Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-102
984-685/785 Local Drop Configuration System Number _____
(page )
W80___-0__ W80___-0__
Power Signal System slots slots may contain:
Cable Cable Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 - 8 - 8 - 8 - 8 - 8 - 8 - Housing
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H81 -100
H8 -100
or
P8___0-000
Aux. Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-103
3-104
984X Local Drop Configuration System Number _____
(page )
984- 8 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
Auxillary Power I/O slot I/O slot I/O slot I/O slot /O slot I/O slot I/O slot I/O slot I/O slot H8 -100
Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #1
W80___-0__ W80___-0__
Power Signal System slots may contain:
Cable Cable Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8___-100
or
P8___0-000
Aux. Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-105
984X Local Drop Configuration System Number _____
(page )
W80___-0__ W80___-0__
Power Signal
Cable Cable
8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8 -100
or
P8___0-000
Aux Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #1
W80___-0__ W80___-0__
Power Signal System slots may contain:
Cable Cable Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8___-100
or
P8___0-000
Aux Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-106
984X Local Drop Configuration System Number _____
(page )
W80___-0__ W80___-0__
Power Signal System slots slots may contain:
Cable Cable Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 - 8 - 8 - 8 - 8 - 8 - 8 - Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H81 -100
or
P8___0-000
Aux Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-107
Configuring a Remote I/O System
All 984 PLCs, except the 38x series, can communicate with
remote I/O, a feature facilitated by the S908 communications
protocol. This protocol is either built into the mainframe (as in
the 984X, 984X, 984B, 984-480, and -485) or added as an
optional module ( -685, and -785). If you use the S908 with any
of the slot mount 685 or 785 series, you must also install an
E908-131 or a E908-016 plug-in executive cartridge in the S908.
The S908 Remote Input/Output Processor supports up to 32
drops of remote I/O, depending on the upper limit of the 984
PLC to which it is applied. Each drop can support up to two
ASCII devices, depending on the remote input/output interface
device at the drop. S908 processors are available with either
one or two coaxial cable connectors. (984X, 984-480/485
support single cable only).
The S908 is required for hot standby configurations.
3-108
S908 remote input/output processing is designed to support
communication with 800 I/O. However, the S908 can also
Remote I/O (Redundant Cable)
support remote communications with 200 and 500 Series I/O,
when you install these field modification kits and remote input/
output interfaces:
Modification Kit Interface Function
The S908 can also communicate with the 500 Series I/O through
the J290/J291 and a J540 adapter.
Environmental
Operating Temperature 0 ... 60°C
Relative Humidity 0 ... 95% (non-condensing)
Shock Resistance 10G (11ms)
Physical
Space Requirements
AS-S908-1x0 One option slot in H8xx-209
housing
Weight
AS-S908-1x0 2.5 lbs (1.2 kg)
3-109
Remote I/O Cable Recommendations
It is important to plan your system topology before you install Modicon RG-11/U Cable, Technical Specifications
the system. Our Application and Service personnel can help
you design a system to meet your application requirements. The RG-11/U coaxial cable (part #97-5951-000) is a 3/8 inch
You should consider the following recommendations when flexible cable with good noise immunity and low signal loss. It is
planning your cable layout. Your facility may have unique suitable for use as a trunk cable in most industrial environments
requirements that demand special considerations, so use these and may be used as a drop cable in high noise environments.
recommendations as guidelines only.
Specification RG-11/U Cable, # 97-5951-000
Trunk Cables Shield type Bonded foil quad shield
Minimum bend radius 2.5 in (6.35 cm)
The trunk cable runs from the PLC to the remote I/O Capacitance: 16.2 pfd/ft
subsystems. Remote I/O communications operate at 1.544 Attenuation @ 1.544 MHz 0.2 dB/100 ft (.79 dB/100 m)
MHz. Standard cable television cables cannot be used to
support remote I/O communication. Three types of cable are Semi-rigid Cable
recommended: RG-6/U coaxial, RG-11/U coaxial, or semirigid.
Semi-rigid cable construction is similar to flexible cable
Use one type of trunk cable throughout the entire remote I/O construction except that it uses a solid aluminum shield to
system. Do not mix cable types. The reflections that occur if provide 100% shield coverage. Semi-rigid cable is available in
signals move from one type of cable to another increase the sizes from .5 to 1 inch, with .5 being the most widely used. It
voltage standing wave ratio (VSWR) in the system. Trunk has high noise immunity and very low signal loss. Semi-rigid
cables must be terminated with a 75 Ωs cable terminator. cable may be used as trunk cable when maximum distance
There are limits to the length of the three trunk cable types, and/or high noise immunity are required. Because it is not very
as follows: flexible, it should not be used as a drop cable.
The RG-6/U coaxial cable (part #97-5750-000) is a 5/16 inch As a general rule, adjacent high-energy cables should be
flexible cable with moderate noise immunity and signal loss; it is separated by 12 to 14 inch/kV (30.48 ... 35.56 cm/kV). If they
used frequently as a drop cable and may be used as a trunk must cross, make sure they cross at right angles.
cable in some installations. Running Taps and Drop Cables to the I/O Subsystems
Specification RG-6/U Cable, #97-5750-000
Drops should be located no more than 100 feet (30 m) and no
Shield type Bonded foil quad shield
Minimum bend radius 2.0 in (5 cm) less than 8 ft (2 m) from a trunk cable. Taps should be placed
Capacitance: 16.2 pfd/ft as close as possible to the drop for ease of maintenance. The
Attenuation @ 1.544 MHz 0.41 dB/100 ft (1.44dB/100 m) drop cable need not be the same cable type as the trunk cable.
RG-6/U is normally used as the drop cable in systems that use
RG-11/U or semirigid trunk cable.
3-110
The following table shows the attenuation for the three different
cable types:
Cable Attenuation
RG-6/U ~7 dB/1000 ft (305 m)
RG-11/U ~2 dB/1000 ft (305 m)
0.5 inch semirigid ~0.8 dB/1000 ft (305 m)
3-111
Modicon Connectors Keep in mind, when you plan a remote I/O layout, that the
maximum allowable attenuation loss between the PLC and any
A series of connectors, installation packs, crimp tools, and remote I/O drop is 35 dB. If you use the single cable mode and
blade packs is also available. you want to service a large number of remote drops, you may
be forced to use a splitter.
Connector Installation Crimp Blade
Part # Description Tool Tool Pack
52-0400-000 RG-6/U Male
F Connector 60-0528-000 N/A 60-0529-000
52-0488-000 RG-6/U Male
BCN Connector N/A 0435 09432 N/A
52-0401-000 RG-11/U Male
F Connector 60-0530-000 N/A 60-0531-000
52-0399-000 Self Terminating
F Connector, for
Non-quad Shielded
RG-6/U Drop Cables
52-0411-000 Self-terminating
F Connector for
RG-6/U Drop Quad
Shielded Cables
MA-0329-001 Type F, Quad cassette, pack of 10
A linear cable run with a tap to each remote drop is the easiest
and most reliable topology. We recommend that you use
Modicon Rev. C taps with your installation. We also recommend
that you avoid the use of splitter configurations unless you have
a compelling application need for such a topology.
3-112
The following tools are designed to help you configure 800 Series
remote I/O systems. Refer to the following configuration pages
associated with the remote I/O interface you have chosen.
1. P890 or P892 remote drop in H810-208 four-slot housing.
2. P890 or P892 remote drops in H810, H819 or H827-209
housings.
3. J890 or J892 remote I/O drops.
3-113
3-114
H810-208 Configuration (Remote I/O) System Number _____
(P890/P892)
(page )
Configuration 2 I/O Drop
P89_-001 8 - 8 - 8 - Housing
PS/RIO I/O slot I/O slot I/O slot H810-208
Interface
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #1
3-115
3-116
P890/P892 Remote Drop Configuration System Number _____
(page )
P89_-000 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
PS/RIO I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8 -209
Interface
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #1
W80___-0__ W80___-0__
Power Signal I/O slots may contain:
Cable Cable Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8 -100
or
P8___0-000
Aux Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-117
P890/P892 Remote Drop Configuration System Number _____
(page )
W80___-0__ W80___-0__
Power Signal
Cable Cable
P89_-000 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
PS/RIO I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8 -100
Interface
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #1
W80___-0__ W80___-0__
Power Signal System slots may contain:
Cable Cable Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8___-100
or
P8___0-000
Aux Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-118
P890/P892 Remote Drop Configuration System Number _____
(page )
W80___-0__ W80___-0__
Power Signal System slots slots may contain:
Cable Cable Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 - 8 - 8 - 8 - 8 - 8 - 8 - Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H81 -209
or
P8___0-000
Aux. Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-119
AS-H827-103
AS-H819-103
3-120
J890/J892 Remote Drop Configuration System Number _____
(page )
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #1
W80___-0__ W80___-0__
Power Signal I/O slots may contain:
Cable Cable Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8___-100
or
P8___0-000
Aux. Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-121
J890/J892 Remote Drop Configuration System Number _____
(page )
W80___-0__ W80___-0__
Power Signal
Cable Cable
8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8 -100
or
P8___0-000
Aux Power Su pply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
W80___-0__ W80___-0__
Power Signal I/O slots may contain:
Cable Cable Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 - 8 -
Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H8___-100
or
P8___0-000
Aux Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-122
J890/J892 Remote Drop Configuration System Number _____
(page )
W80___-0__ W80___-0__
Power Signal I/O slots slots may contain:
Cable Cable Any B8xx-xxx I/O Module or a J878-000 Modbus modem
8 - 8 - 8 - 8 - 8 - 8 - 8 - Housing
I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot I/O slot H81 -100
or
P8___0-000
Aux Power Supply
Discrete Inputs
Discrete Outputs
Total Discrete I/O
Input Bits
Output Bits
+5Vdc
+4.3Vdc
-5Vdc
Total Power
Housing #2
3-123
Notes
3-124