Installation and operation manual
Central Controller Unit
UMatch Inverter Systems
MultiSplit Inverter Systems
TCONTADPYCJA2A
SAFETY WARNING
Only qualified personnel should install and service the equipment. The installation, starting up, and servicing of
heating, ventilating, and air-conditioning equipment can be hazardous and requires specific knowledge and training.
Improperly installed, adjusted or altered equipment by an unqualified person could result in death or serious injury.
When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that are
attached to the equipment.
April 2021
MS-SVX081A-EN
Confidential and proprietary Trane information
User manuals and installation manuals for remote control detector
TCONTADPYCJA2A
Functions Introduction
Remote control detector(short form:Detector)is essential equipment of remote monitor
system of Haier commercial A/C.By connecting the interface in indoot units or outdoor
units,this detector can reach functions of remote an central control
◆ Communication function
1. with air conditioning communication:
① . YCJ-A002 can at most connect two same model units by six-pin fixed screw. It can
realize double switching function. It can control air conditioning to work in different
ways according to the requirement of detector, at the same time query the air
conditioner's operation information and fault information.
2. communication with RS-485:
① . Communication with the central controller
BM1 dip switch as (1: OFF, 2: OFF)
Communicate with the central controller via RS-485 interface bus (A, B). It receives
commands from central controller according to the units address what is set by
detector dip switch. And to realize internal control or query request, and answer the
reception status and air conditioning operation information and fault information.
② Communication with the central controller
BM1 dip switch as (1: ON, 2: OFF)
Communicate with the central controller by RS-485 bus port. According to the
detector within the dip switch setting address, Receive commands from the central
controller. Have internal control or query request, and answer the reception status
and air conditioning operation informationand fault information.
③ Communicate with remote devices. Detector has RS-485 port, and the protocol is
Modbus RTU, users can use the private network and open protocol to create remote
control program, no need other accessories.
The BM1 dip switch as (1: OFF, 2: ON).
④ communication with the central control system
Dip switch BM1 (1: ON,2: ON)
Communicate with the central control system by RS-485 bus port(A, B). it receives
1
commands from central controller according to the units address what is set by detector
dip switch. And to realize internal control or query request, and answer the reception
status and air conditioning operation information and fault information.
【1】 【2】 BM1
0:OFF 1:ON numbe 485communication mode details
0 0 ① TCONTCCMYCZG1/TCONTCCMYCZ256 single unit
1 0 ② /
0 1 ③ Modbus rtu standard protocol
1 1 ④ BMS system
◆ Dual switch function
In order to improve the reliability of air conditioning, the detector has double switching
function, set SW1 to single unit mode, detector controls the A unit according to the
command from the host equipment. Set SW1 to double switching mode, it can realize
double switching function.
Double switching function realization: under normal condition, the detector control one
unit ON and another unit OFF, when reach the switch time, detector wake up the OFF
state unit and the ON state unit will still work half an hour and then OFF.
If any air conditioner has failure, switch time will stop, the detector automatically wake
up another unit, and let the failure unit OFF, then upload the failure information. After the
failure restore, automatically change to the double switching function; if air-conditioner
operate for some time and cannot reach setting temperature, switch time will stop,
the detector automatically wake up another air conditioner, double units operate until
reaching the setting temperature, then automatically turn off that air conditioner, and
automatically restore the double switching function. Factory default switch time is 12
hours
◆ Address setting function
The detector with 8-bit dip switch (SW1), the highest bit D8 bit, for setting the single
mode or double-switch mode,(D7, D6, D5, D4, D3, D2, D1) is used to set the number
(central control network or double switch time when select the dual switch mode)
◆ Operation status displasy function
Detector has three lights, yellow light is for RS-485 communication , red and green
lights are for the air conditioner communication, When the communication is normal,
lights in accordance with the frequency of 0.5s flashing, when have failure, lights in
according with the frequency of 1s flashing, stop 2s flashing
◆ Delay control function
Through the RS-485 bus to build a central control network, In order to reduce the
impact of unified operation of air conditioning on the power grid, the detector set the
delay start function, the delay time is automatically generated by the detector
2
System Overview
◆ Double switching function instructions
Detector connects with the two same model units
through six-pin fixed screw. Set the dip switch
to double switching model. Only use the double
switching function, the system does not need
connect the other components; double switching
time can be chosen 8,10,12,14 hours by dip
switch setting. Detectors
the specific settings and the corresponding time
see dip switch list
+12V COM GND +12V COM GND
◆ use central controller for
central control function Indoor Unit Indoor Unit
12V、COM、GND ports of
detector connect with air
conditioner. Dip switch set to
single
mode, the specific settings and
the corresponding address
Outdoor Unit Outdoor Unit
see dip switch list, The system
also needs to connect with
central controller, Each detector
connect with central Controller
by 2-pin fix screw(A,B).
Detector
Detector
Indoor Unit Indoor Unit
Outdoor Unit Outdoor Unit
3
Maintenance
◆ Status check
•• When select the single unit mode and control A unit, when A unit failure occurs, the
detector will query fault information and upload it, when select double switch mode
,detectorcontrolA unit and B unit, if one of air conditioner is faulty, the detector will query
the fault information and upload it
•• Detector operating status and running lamp display: When operation properly, running
lamp for 0.5 seconds off 0.5 secondsfor a cycle to indicate,When have the fault to flash
1 second, stop 2 seconds to cycle to indicate, yellow lamp for the central control of
communication status indication, red light for the air conditioner A unit communication
Status indication, green lamp for air conditioning B unit communication status indication
◆ When servicing, be sure to power off the power supply
•• Wipe clean with a soft cloth and be careful not to touch the electrical parts.
•• Do not use gasoline, thinner, decontamination powder, chemical wipes, etc. to avoid
damage to electrical parts.
•• Check whether the wiring with the central control and air conditioning is normal, there
is no broken wire or the existence of loosening of the connection.
Dimension drawing
Air conditioning A communication port, three-core shielded communication wire
Connection, wirelength requirements of not more than 10meter 60mm
Interface Description:
1-air conditioning A communication port,
three-core shielded communication wire
connection, wire length is not more than 100mm
10meter
2-air conditioning B communication port,
three-core shielded communication wire
connection, wire length is not more than
10meter
3 - dial switch is used for centralized control
interface of detector detector 40mm
Communication Association
4-central control interfaces, providing 485 communications
+12V COM GND +12V COM GND
1
5 - Fault output port, faulty disconnect, normal connect
6
6-Dip switch for selecting the addressfor centralcontrol
and dual switching function
5
7-wifi module interface, you can connect home kit module,
7
IOS device to achieve remote control.
4
Installation and commissioning
4
◆ installation and wiring of the basic requirements:
Use a screw driver to install detector, screw spacing see the right figure.
Keep the detector on a wall or other reliable location to ensure that there is no water
and other creatures that may cause failure to enter.
1. Central control network design planning principles:
(1) Detector, in order to maintain the appropriate response speed and communication
reliability, the number of detectors in one central system should not exceed 64 pieces
(2)A/C should be ready for network ,bu sure to be installed and us according to
instructions
(3) Detector installation position does not leave the air conditioner too far; do not
exceed the wiring length
(4) Detector address number in strict accordance with the order from small to large
allocation
(5) Detector power from the indoor unit, 12V, need have distance with the high voltage
cable .and the shieldlayer needs earth one side
(6) Central control bus wire length limit less than 1000 meters
(7) both ends of the bus in the A bus and B bus were connected between the 100 ohm
metal film precision resistance (depending on the scene to match)
(8) bus shielded wire single point grounding, the proposed layout in the middle of the
communication bus location, and centralized controller similar
(9) Central controller installation location in principle arranged in the middle of the
communication bus position, and the communication bus shield ground similar
2. Detector and air conditioning connection: Detector through the air conditioning
interface six screws fixed terminal (12V、COM1、GND、12V、COM2、GND) ,and
up to two air-conditioning (A, B) for wired communication; detector and air conditioning
connection with the uniform wiring, one end of the wiring terminal with plug connect to
air conditioning indoor PCB remote control terminal. If the detector does not operation
properly during commissioning, it can be check by change the wiring polarity + - . Also
can be based on the running lamp show the operation status of the air conditioning and
communication interface to determine whether the normal.
3. After the communication bus wiring is completed, connect the detector and the
communication bus: the connection method of hand by hand type, all A ports in the
same Bus, all B ports on another bus, the communication bus shielding line in the
communication bus in a single point of grounding, communication bus total length
Limited to less than 1000 meters.
◆ According to the host equipment to select RS-485 interface protocol
by dip switch BM1:
Detector built a variety of different protocols to correspond to different host equipment,
the use of four different protocols corresponding to four different conditions:
1. The host equipment is a centralcontroller, central controller can choose to select the
device type for single unit, in order to be able to deal with different system structure,
the detector has two built-in protocols that communicate with the central controller.
5
① central controller, select the communication mode for the single unit, then dip switch:
BM1: 1: OFF; 2: OFF.
The system diagram is as follows:
RS-485
+12V COM GND +12V COM GND +12V COM GND +12V COM GND
A
+12V COM GND +12V COM GND
6
② the host equipment for the third party communication equipment, the detector
provides the standard Modbusrtu protocol, BM1 dip switch: 1: ON; 2: OFF, The
communication between the detector and the air conditioner is consistent with the
other 3. When the detector is used as a third-party protocol converter, it should be
specificAccess to the requirements of third-party host device connection; the basic
functions are as follows:
The address of the address set by SW1 changes to the slave address in the Modbus
RTU communication
Serial port 9600,8,n,1
130B modbusrtu query01 control 05/15
WORD name Unit Range Remarks
01 function code
0 Indoor units on/off Read operation to obtain the current switchunit status 0: off 1: on
Write operation to change the switch state 0: off 1: on
03 function code query 03 control 06/16
0 Internal setting℃ 16-30 Read operation Get current setting temperature, write operation
temperature Change set temperature
Read operation to obtain the current operating mode: 1 - cooling 2 -
heating 3 - dehumidification4 – Fan only
within the machine 5 - automatic
1 1--5
running mode
Write operation to change the operating mode: 1 - cooling 2 - heating
3 - dehumidification 4 – Fan only 5 - automatic
Read operation to obtain the current fan speed: 1 - low speed 2 –
middle speed 3 - high speed4 – Automatic speed
2 Fan speed 1--4
Write operation to change the fan speed: 1 - low speed 2 – middle
speed 3 - high speed 4 -Automatic speed
indoor control 1 is not locked; 2 empty - query back to 1, issued to write 1; 3 query
3 1--4 back to 1,Issued to write 1; 4 - lock
mode
read
04 function code
only
0 indoortemp ℃ 30 1℃
1 Fault code 0-256 within the indoor fault code 0-256 value of 0 that no error ,
2 machine number The number of internal indoor This address exists , query back 0
7
◆ Power test:
1. Power test: After the equipment is connected, the power test
① first verify the detector and air conditioner communication status, the red light
should be light 0.5 seconds off 0.5 seconds as a cycle to indicate, If the indicator does
not light or flashes for 1 second and stops for 2 seconds, it should check whether the
communication wire of the air conditioner and detector are the connection is correct and
the air conditioner is powered up until the indicator flashes normally.
② check 485 communication indicator (yellow lamp), should be light 0.5 seconds off 0.5
seconds as a cycle to indicate, if the instructions If the lamp does not light or flashes for
1 second and stops for 2 seconds, it should check whether the BM1 protocol is correct;
the communication wire is connectedWhether it is correct; whether there is a device
with a repeated address, etc., until the indicator flashes normally
2. The detector and the host equipment communication, if the host equipment to normal
monitoring and control of air conditioners, the completion of debugging.
Performance parameters and accessories
Performance parameter
performance parameter DC12V
Power consumption Power consumption is less than 3W
Detector code number 0151800130B
air conditioning communication 3 core shielded wire, special number
Accessories
0010452854, color white, yellow, and red
◆ RS485 interface dip switch instructions
Detector built a variety of different protocols to correspond to different equipment, the
use of four different protocols corresponding to four different conditions:
1. The host equipment is a centralcontroller, central controller can choose to select the
device type for single unit , in order to be able to deal with different the system
structure, the detector has two built-in protocols that communicate with the central
controller.
① central controller, select the communication mode for the unit, then dip switch BM1
:1: OFF; 2: OFF.
8
SW1(1mean ON,0 mean BM1code
OFF) 1:OFF;2:OFF 1:ON;2:OFF 1:OFF;2:ON 1:0N;2:ON
Definition: Definition:BMS
[1] [2] [3] [4] [5] [6] [7] [8] Definition:VRF Definition:Modbus RTU
unitary air conditione Gate addr Unitaddr
1 - - - 0 0 0 0 Dual modeaddr=1 Dual modeaddr=1-1 Dual modeslaveID=1 Dual mode31 0
1 - - - 0 0 0 1 Dual modeaddr=2 Dual modeaddr=2-2 Dual modeslaveID=2 Dual mode31 1
—— —— —— —— —— ——
1 - - - 1 1 1 0 Dual modeaddr=15 Dual modeaddr=15-15 Dual modeslaveID=15 Dual mode31 14
1 - - - 1 1 1 1 Dual modeaddr=16 Dual modeaddr=16-16 Dual modeslaveID=16 Dual mode31 15
- 0 0 0 0 0 0 0 Single modeaddr=1 Single modeaddr=1-1 Single modeslaveID=1 Single mode31 0
- 0 0 0 0 0 0 1 Single modeaddr=2 Single modeaddr=2-2 Single modeslaveID=2 Single mode31 1
—— —— —— —— —— ——
- 0 1 0 0 1 1 0 Single modeaddr=39 Single modeaddr=39-39 Single modeslaveID=39 Single mode31 38
- 0 1 0 0 1 1 1 Single modeaddr=40 Single modeaddr=40-40 Single modeslaveID=40 Single mode31 39
- 0 1 0 1 0 0 0 Single modeaddr=41 Single modeaddr=41-41 Single modeslaveID=41 Single mode30 0
- 0 1 0 1 0 0 1 Single modeaddr=42 Single modeaddr=42-42 Single modeslaveID=42 Single mode30 1
—— —— —— —— —— ——
- 1 0 0 1 1 1 0 Single modeaddr=79 Single modeaddr=79-79 Single modeslaveID=79 Single mode30 38
- 1 0 0 1 1 1 1 Single modeaddr=80 Single modeaddr=80-80 Single modeslaveID=80 Single mode30 39
- 1 0 1 0 0 0 0 Single modeaddr=81 Single modeaddr=81-81 Single modeslaveID=81 Single mode29 0
- 1 0 1 0 0 0 1 Single modeaddr=82 Single modeaddr=82-82 Single modeslaveID=82 Single mode29 1
—— —— —— —— —— ——
- 1 1 1 0 1 1 0 Single modeaddr=119 Single modeaddr=119-119 Single modeslaveID=119 Single mode29 38
- 1 1 1 0 1 1 1 Single modeaddr=120 Single modeaddr=120-120 Single modeslaveID=120 Single mode29 39
- 1 1 1 1 0 0 0 Single modeaddr=121 Single modeaddr=121-121 Single modeslaveID=121 Single mode28 0
- 1 1 1 1 0 0 1 Single modeaddr=122 Single modeaddr=122-122 Single modeslaveID=122 Single mode28 1
—— —— —— —— —— ——
- 1 1 1 1 1 1 0 Single modeaddr=127 Single modeaddr=127-127 Single modeslaveID=127 Single mode28 6
- 1 1 1 1 1 1 1 Single modeaddr=128 Single modeaddr=128-128 Single modeslaveID=128 Single mode28 7
9
◆ Address setting function
SW01
Definition
[1] [2] [3] [4] [5] [6] [7] [8]
0 — — — — — — — Single mode
1 — — — — — — — Double Switch mode
— 0 0 — — — — — Double Switch time 8 hours
— 0 1 — — — — — Double Switch time 10 hours
— 1 0 — — — — — Double Switch time 12 hours
— 1 1 — — — — — Double Switch time 24 hours
Dual operation at ambient
— — — 0 — — — —
temperature of 34 ℃
Dual operation at ambient
— — — 1 — — — —
temperature of 32 ℃
Double Switch mode and ad-
1 — — — 0 0 0 0
dress=1
Double Switch mode and ad-
1 — — — 0 0 0 1
dress=2
— — —
Double Switch mode and ad-
1 — — — 1 1 1 0
dress=15
Double Switch mode and ad-
1 — — — 1 1 1 1
dress=16
0 0 0 0 0 0 0 0 Single mode and address=1
0 0 0 0 0 0 0 1 Single mode and address=2
— — —
0 1 1 1 1 1 1 0 Single mode and address=127
0 1 1 1 1 1 1 0 Single mode and address=128
10
Trane - by Trane Technologies (NYSE: TT), a global climate innovator - creates comfortable, energy
efficient indoor environments for commercial and residential applications. For more information,
please visit trane.com or tranetechnologies.com.
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without
notice. We are committed to using environmentally conscious print practices.
©2020 Trane