MV & LV System Technical Sharing 2024 - JUN

Circuit Breaker
Technical Sharing
Sun Power Automation S.B.
By : Philip Chang

Malaysia National Grid


National Grid – Taking Shape In 1964, LLN – 1965, TNB – 1990.

Hydro Power Plant


Transmission

N. Gas & Coal


Power Plant
TX
Sub-station

Power Generation, Transmission Power Distribution


HV : 132kV, 275kV, 500kV MV : 6.6kV ~ 66kV
LV : 400V / 230V.

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 1
MV & LV System Technical Sharing 2024 - JUN

Distribution
Electrical Distribution System
G
e
n
e
r
a
t
i
o SSB
n T
r
MSB
a
n
s
m
i
s DB
s
S i Meter
u o
b n

S
t Utilities.
a
t
i
o
n
Distribution

Distribution
Electrical Distribution System – Full Protection Solution

MSB SSB DB

ACB, MCCB ACB, MCCB MCCB, MCB, RCCB

Outgoing To Switch, SSO.

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 2
MV & LV System Technical Sharing 2024 - JUN

LS Electric
LS Electric Introduction

1954 – 1973. Goldstar

1974 – 2004. LG - LG Industrial Systems


Lucky Goldstar (Industrial)
Life’s Good (Consumer)

2005 – 2020. LS - LS Industrial Systems


Leading Solution

March 2020 - LS Electric


New Corporate Identity

Sun Power Automation S.B.


Since 2004 - Exclusively Represents LS Products
In Malaysia.
CB

Circuit Breakers

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 3
MV & LV System Technical Sharing 2024 - JUN

Circuit Breaker
IEC Standards For Circuit Breaker
Circuit Breaker

IEC 60947-1 : Low-voltage switchgear and controlgear


– Part 1 : General rules
IEC 60947-2 : Low-voltage switchgear and controlgear
– Part 2 : Circuit breakers

Circuit Breaker
A mechanical switching device, capable of making,
Circuit Breaker carrying current under normal & breaking current under
abnormal conditions.
Air Circuit A circuit breaker in which the contacts open or close in
Breaker normal air atmospheric pressure.

Molded Case A circuit breaker having a supporting housing of moulded


Circuit Breaker insulating material.

Electrical fault conditions :

Overcurrent Short Circuit Earth Fault

ACB MCCB

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 4
MV & LV System Technical Sharing 2024 - JUN

Circuit Breaker
Application
Distribution System Full Protection

DB

SSB

MSB

Circuit Breaker
Application

MSB Physical Layout SSB Physical Layout

DB Physical Layout

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 5
MV & LV System Technical Sharing 2024 - JUN

LS Circuit Breaker
Type Test

Type Test Requirement


LS Circuit Breakers are tested by International
accredited test laboratory certified by KEMA

Certification :
IEC Standards – KEMA Netherlands
Korean Industrial Standards – KSA Korea
Under Inspection :
CE – European Market
UL – American Market
JIS – Japanese Market
EAC – Russian Market
Vessel Standards
Lloyd’s Register, KR, BV, GL, DNV, ABS, NK.

SAFETY, RELIABILITY

LS Circuit Breaker
Test Laboratory
LS Power Testing & Technology Institute (PT&T) – International Accredited Test Laboratory

Quality Test at PT&T


KOLAS – Korea
Korea Laboratory
Accreditation Scheme The world-class Power Testing & Technology Institute guarantees
certified products and global brands.

ASTA – UK
Association of Short-Circuit
Authorities

KEMA – Netherlands
Keuring van Elektrotechnische
Materialen te Arnhem.

SAFETY, STANDARDS COMPLIANCE CB Sel

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 6
MV & LV System Technical Sharing 2024 - JUN

Circuit Breaker Selection

LS Circuit Breaker
Standard Compliance Ics = 100% Icu

ACB MCCB

Ics = 100% Icu

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 7
MV & LV System Technical Sharing 2024 - JUN

LS Circuit Breaker
Standard Compliance Icu
IEC 60947-2 Test Standard Compliance
Clause 8.3.5.3 Rated Ultimate Short Circuit Breaking Capacity (Icu)
Test sequence O – t – CO (2 x Trippings) [t = 3 mins]

Example : MCCB Icu 50kA


50kA

1st trip - 3 min - 2nd trip

Icu = 50kA

LS Circuit Breaker
Standard Compliance Ics
IEC 60947-2 Test Standard Compliance
Clause 8.3.4.2 Rated Service Short Circuit Breaking Capacity (Ics)
Test sequence O – t – CO – t – CO (3 x Trippings) [t = 3 mins]

Example : MCCB Ics 50kA


50kA

1st trip - 3 min - 2nd trip - 3 min - 3rd trip

Ics = 50kA

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 8
MV & LV System Technical Sharing 2024 - JUN

LS Circuit Breaker
Standard Compliance Ics = 100% Icu
IEC 60947-2 Test Standard Compliance
Clause 8.3.5.3 Rated Ultimate Short Circuit Breaking Capacity (Icu)
Test sequence O – t – CO (2 x Trippings) [t = 3 mins]
Example : MCCB Icu 50kA

Clause 8.3.4.1 Rated Service Short Circuit Breaking Capacity (Ics)


Test sequence O – t – CO – t – CO (3 x Trippings) [t = 3 mins]
Example : MCCB Ics 50kA

Icu : 50kA, Ics : 50kA => Ics = 100% Icu


LS Circuits Breakers Are Tested To Comply :

Ics = 100% Icu.


SAFETY, RELIABILITY

LS Circuit Breaker
Standard Compliance Icw
IEC 60947-2 Test Standard Compliance
Clause 8.3.6.5 Short Time Withstand Current (Icw)
Circuit breaker instantaneous release is being intentionally override resulting the ACB
to remain in CLOSED position during the short-time withstand test.
Example : ACB Icw 1 sec : 50kA
50kA Short Time Withstand Current Icw,
current value which the circuit breaker
can withstand for a short period of time
without the circuit breaker getting damage.

LS ACB Short Time Withstand Current Rating


Icw 1 sec : 50 ~ 100kA,
2 sec : 42 ~ 85kA,
3 sec : 36 ~ 75kA.

ACB

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 9
MV & LV System Technical Sharing 2024 - JUN

Air Circuit Breaker

Air Circuit Breaker


ACB External

OCR Protection Relay


Spring Charge Handle
On/Off Button
On/Off Indicator
Spring Charge Indicator
Counter (Optional)

ACB Position Indicator


Connected / Test / Disconnected
Padlocking

Spring Press ACB


Fully ON Turned
Charge button ON.

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 10
MV & LV System Technical Sharing 2024 - JUN

Air Circuit Breaker


ACB Internal

Closing coil
Turn ON ACB in Auto operation

Shunt Trip coil


Trips ACB when external E/F &
O/C relay detects fault condition

UVT coil
ACB for Generator set operation
(Trips ACB when system voltage drops < 70%,
ACB turn on possible when voltage > 85%)

Motor charging device


Charges ACB spring in Auto
operation.

Air Circuit Breaker


ACB Mechanical Interlock

Mechanical interlock
(Automatic change-over operation)
2 Way - 2 ACB Change-over
3 Way - 3 ACB Change-over + Bus coupler

Keylock (Manual change-over operation)

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 11
MV & LV System Technical Sharing 2024 - JUN

Air Circuit Breaker


ACB Mechanical Interlock – Auto Operation

Load Load 1 Load 2

GEN COUPLER
TNB TNB 1 TNB 2
Auto –2 Way M.I. Auto – 3 Way M.I.
( 2 ACB Change-over ) ( 3 ACB, Change-over + Bus coupler )
Manual – 2 Locks, 1 Key Manual – 3 Locks, 2 Keys.

Meta

Air Circuit Breaker


LS Metasol ACB Range
Current Rating : 630 ~ 6300A In 4 Frame Sizes,
Icu : 65 ~ 120kA , Ics = 100% Icu,
Icw 1s : 50 ~ 100kA, 2s : 42 ~ 85kA, 3s : 36 ~ 75kA.

Ics = 100% Icu

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 12
MV & LV System Technical Sharing 2024 - JUN

Air Circuit Breaker


LS ACB Test Report
JKR Material Approved List EMAL
KEMA Test Report Validity : 15th Feb 2026

Air Circuit Breaker


Case Study
Reported Incident

ACB ON, Spring CHARGED

Normal

ACB Turn ON, Spring DISCHARGED

ACB Spring Charge Indicator MCCB

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 13
MV & LV System Technical Sharing 2024 - JUN

Moulded Case Circuit Breaker

Moulded Case Circuit Breaker


Tripping Mechanism

1. Thermal & Magnetic trip – General protection


(Overcurrent & Short circuit protection)

2. Electronic Trip – Adjustable time, current


(Overcurrent & Short circuit protection)

3. Magnetic Only Trip – Motor Protection


(Short circuit protection).
Magnetic Thermal

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 14
MV & LV System Technical Sharing 2024 - JUN

Moulded Case Circuit Breaker


Thermal Magnetic Tripping Curve

Thermal Curve.
Meta

Metasol Moulded Case Circuit Breaker


LS Metasol MCCB Range
Current Rating of 15 to 800A in 8 frame sizes
Breaking Capacity Icu : 14 ~ 65kA
High Performance Ics = 100% Icu
Trip Unit Type : Fixed Thermal Magnetic

Ics = 100% Icu

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 15
MV & LV System Technical Sharing 2024 - JUN

Metasol Moulded Case Circuit Breaker


LS Metasol MCCB Test Report

KEMA Test Report

Metasol Moulded Case Circuit Breaker


LS Metasol MCCB JKR EMAL Approval
JKR Material Approved List EMAL Validity : 15th June 2025

Sus

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 16
MV & LV System Technical Sharing 2024 - JUN

Susol Moulded Case Circuit Breaker


LS Susol MCCB Range
Current Rating Of 16 ~ 1600A In 6 Frame Sizes
High Breaking Capacity Icu : 50 ~ 150kA
High performance Ics = 100% Icu
Trip Unit Type : Inter-changeable Trip Units Available

Ics = 100% Icu

Susol Moulded Case Circuit Breaker


LS Susol MCCB Test Report

KEMA Test Report JKR Material Approved List EMAL Validity : 15th June 2026

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 17
MV & LV System Technical Sharing 2024 - JUN

Metasol, Susol Moulded Case Circuit Breaker


MCCB External

Toggle To Turn MCCB to ON / OFF


Visual indication
MCCB ON / OFF / TRIP condition

Test trip button :


MCCB manual test trip

Connection terminals.

Susol Moulded Case Circuit Breaker


MCCB External

OFF Position ON Position TRIP Position.

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 18
MV & LV System Technical Sharing 2024 - JUN

Metasol, Susol Moulded Case Circuit Breaker


Accessories - Electrical

Shunt Trip Coil - SHT

Under Voltage Trip Coil - UVT

Auxiliary Switch - AX
(BAS On / Off Status)

Alarm Switch - AL
(BAS Trip Status)

Motor Operator - MOP


Remote ON / OFF Function.

Safety – No Live Contact Parts Exposed In Accessory Compartment

Metasol, Susol Moulded Case Circuit Breaker


Accessories - Mechanical

Direct rotary handle (IP40)


Protection solid object : > 1mm
Protection water ingress : No

Extended rotary handle (IP65)


Dust protection
Low pressure water jet
(limited ingress).

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 19
MV & LV System Technical Sharing 2024 - JUN

Metasol, Susol Moulded Case Circuit Breaker


Insulation Barriers

Prevent flash-over
accident
in the event of an
electric arc discharge
when circuit breaker
trips to break the
fault current.

Metasol, Susol Moulded Case Circuit Breaker


Case Study

MCCB without
safety barriers
seriously damaged

MCB

2B

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 20
MV & LV System Technical Sharing 2024 - JUN

Miniature Circuit Breaker

MCB – IEC Standard Of Compliance


IEC Standards For Miniature Circuit Breaker
Miniature Circuit Breaker

IEC 60898-1 : Electrical accessories


– Circuit-breakers for overcurrent protection for household
and similar installations
– Part 1 : Circuit-breakers for A.C. operation

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 21
MV & LV System Technical Sharing 2024 - JUN

MCB
Classification

Number of poles : 1, 2, 3 & 4 Poles

Method of connection : Terminal lug type

Instantaneous tripping curve : B, C, D type

Operating time
B type : 3 ~ 5 x In
Instrumentation protection

C type : 5 ~ 10 x In
General protection
D type : 10 ~ 20 x In
Small motors, welding machines & transformers
protection where higher inrush current occurs.

3 5 10 20
Multiple of rated current

MCB
MCB For Overload & Short Circuit Protection
Model : BK63S
Current rating : 1 to 63A
Breaking capacity : 6 kA
Curve type : B, C, D
Terminal : Lug up to 25mm

Overload Short Circuit

1P 2P 3P 4P
RCCB

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 22
MV & LV System Technical Sharing 2024 - JUN

RCCB – IEC Standard Of Compliance


IEC Standards For Residual Current Circuit Breaker
Residual Current Circuit Breaker
IEC 61008-1 : Residual current operated circuit-breakers
without integral overcurrent protection for household and
similar uses (RCCBs) – Part 1: General rules
IEC 61008-2-1 – Part 2-1 : Applicability of the general rules to
RCCB's functionally independent of line voltage

RCCB
RCCB For Earth Fault Protection
Model : RKN
Current rating : 25, 32, 40, 63A
Terminal : Lug up to 35mm

Sensitivity : 10mA (Water heater, fountain, wet floor)


: 30mA (Direct contact S.S.O.)
: 100mA (Indirect contact equipment)

Earth Fault
10mA 30mA 100mA

2P 4P

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 23
MV & LV System Technical Sharing 2024 - JUN

RCCB
Effects Of Electric Shock To Human Body

BO

RCBO – IEC Standard Of Compliance


IEC Standards For Residual Current Circuit Breaker With
Integral Overcurrent Protection (RCBO)
IEC 61009-1 : Residual current operated circuit-breakers with
integral overcurrent protection for household and similar uses
(RCBOs) – Part 1: General rules
IEC 61009-2-1 – Part 2-1 : Applicability of the general rules to
RCBO's functionally independent of line voltage

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 24
MV & LV System Technical Sharing 2024 - JUN

RCBO
RCBO For Overload, Short Circuit & Earth Fault Protection
Model : RKP
Current rating : 3A (C, D curve)
6 ~ 32A (B, C, D )
Terminal : Lug up to 35mm
Sensitivity : 30, 100mA

Overload Short Circuit Earth Fault

2P

RCBO
RCCB Application

RCCB Protection

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 25
MV & LV System Technical Sharing 2024 - JUN

RCBO
RCBO Application

OK

RCBO Protection MC

Magnetic Contactor

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 26
MV & LV System Technical Sharing 2024 - JUN

Metasol Magnetic Contactor


LS Metasol Magnetic Contactor Range
Current Rating 9 to 800A,
AC-3 Duty, 8 frame sizes,
3 & 4 Poles.

Metasol Magnetic Contactor


Motor Starter & Magnetic Contactor Application

Motor Starter Application Contactor Applications. Cap

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 27
MV & LV System Technical Sharing 2024 - JUN

ELCO P.F. Improvement Capacitor

ELCO Capacitor
ELCO Capacitor
ISO 9001 Certified, founded in
1979, over 40 years of capacitor
manufacturing expertise
Made in Malaysia product with
Switzerland Technology
JKR EMAL approved - 525V
Capacitor
Complies to IEC 60831-1 & 2
Standard
High quality self healing dielectric
polypropylene film

Built-in Safety Over Pressure


Disconnector

Operating hours > 100,000


( > 10yrs, 24hrs daily under
normal operating condition ).

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 28
MV & LV System Technical Sharing 2024 - JUN

ELCO PFC Capacitor


ELCO Power Factor Improvement Capacitor Selection

JKR Projects Private Projects


ELCO 205 Series – 5 to 30kVAR 525V ELCO 700 Series – 5 to 30kVAR 440V

LS5_EL5

Product Warranty
LS Circuit Breaker Warranty ELCO Capacitor Warranty

QnA

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 29
MV & LV System Technical Sharing 2024 - JUN

Disclaimer: This presentation is intended to present our company products only, and do not replace independent
professional judgment. Each person who has received a copy of this presentation is deemed to have agreed not to
reproduce or distribute this presentation materials in whole or in part. 30