Q-Start DAT210 V1c
Q-Start DAT210 V1c
DAT210/213
Version V1c
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 1
MOUNTING
This manual covers a programmed DAT 210 (single phase mains) or DAT 213 (3 phase mains) inverter.
The inverter is usually set up for a specific application and requires only installation wiring to operate
correctly at startup. If the application is changed or flexible, refer to the section on tuning the inverter
in this or the complete standard manual.
DAT means Digital Automatic Tuning that allows the inverter to maintain constant power into an ozone
system load over changing gas pressures and flow rates. It does this by:
Mechanical Installation
Do not mount the inverter in a cabinet and then start drilling holes in the cabinet. Metal chips
on the circuit board can destroy it.
Check that there is adequate clearance in front of the fan for adequate cooling.
Hole pattern:
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 2
ELECTRICAL INSTALLATION
Observe all wiring codes. Install wiring separating the control and low power wires from the high
power mains or any high voltage wiring.
190 to 240 VAC operating voltage. DO NOT apply 480 VAC to this inverter.
Mains wiring
Power ratings (208 – 240 VAC):
Greater than 2 KVA use 3 phase power – Use a soft start and link choke on the DC after
the mains rectifier.
The three phase effective power factor will be 0.9
The soft start prevents high inrush currents due to filter capacitor charging when power is
applied. The link choke reduces the ripple current in the filter capacitors (and mains 3rd
harmonic) and improves the power factor from 0.6 to 0.9.
The inverter is capable of 25 Amps RMS 1.0 power factor mains current continuous. This means
at 240 VAC mains, 6 KW is available with the voltage potentiometer turned full clockwise
maximum. Take care so your equipment is not over powered.
For greater detail to help with system design and configuration refer to the complete manual.
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 3
DAT210
TRANSFORMER
CONNECTION MAINS POWER
208 TO 240 VAC
CONFIGURATION
SWITCHES
STATUS
LEDS
PlasmaView
SERIAL
CONNECTOR
MANUAL ADJUSTMENTS
FLASH PROCESSOR
TO LOAD POWER
AND FREQUENCY LOW VOLTAGE CONTROL I/O
FOR NEW PRESSURE
AND FLOW CONDITIONS
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 4
LOW POWER CONNECTIONS
Basic control connection for PDM, ON/OFF, Frequency, Voltage, Enable out, +15vdc, +5vdc are the
same as all other Plasma Block® products that have utilized the DAT210 control board. Note below
that many new outputs are available and the enunciation outputs have been changed from 0-5v logic
level types to open collector for easier interface to a wider variety of PLC’s. The open collector outputs
are all active low [Active low means that the terminal output is at 0V (Pin 3) when the alarm or other
condition is present]. Terminal current is positive source only and is limited to 100 ma.
TERMINAL
1. +15, aux use limit = 1 Amp maximum.
2. Frequency Adjust (optional) external control, selected by jumper J10. Use 5k Ω pot, 0-10vdc
only (10v= 100%). 10 volts can be derived with a 2.0 K resistor in series with the pot to +15 (Pin
1).
3. Signal Common, tied to #9 internally.
4. Flooded cell detector. (Current production inverter)
5. +5vdc, aux use limit = 3 Amps The 5V can be used to drive a 5 V coil relay for input current
pre-charge and for PLC use for low voltage power supply status. There is a 1 – 2 second delay
before +5 V after application of mains voltage.
6. PDM input (optional), selected by jumper J11, use 5kΩ pot, 0-10vdc (10v= 100%). 10 volts can
be derived with a 2.0 K resistor in series with the pot to +15 (Pin 1). 0 – 10 volt control or 4 – 20
& 0 – 20 ma is selected with J12. All voltages/currents are with respect to Pin 3 (0V).
7. Inverter Start, output pulls low via open collector ( MMBT4401 ) when inverter is engaged.
Follows Inv_ON LED. 10k Ω pull-up to +5. 100Ω in series with the transistor for current limit.
8. Inverter OFF when pulled low to terminal 9 via momentary or continuous. 10kΩ pull-up to +5v.
9. Logic Common for # 8 and 10.
10. Inverter ON when pulled low to terminal 9 via momentary or continuous. 10kΩ pull-up to +5v.
11. FAULT OUT pulls low via open collector ( MMBT4401 ) when inverter faults due to: Operating
cell current is above or below customer programmed set point. Over temp cell, over temp
electronics, sustained instantaneous over current. 100Ω on board. (See jumper J4)
12. System LOCKED. Digital auto-tune feature has found and confirmed the proper operating point.
If pressure changes cause significant re-tuning the LOCKED LED will flash. The locked LED will
also flash during the initial tuning acquisition, which lasts for a few seconds.
13. Analog 0 – 5vdc, follows average DC bus current out. Direct op amp (MC33272AD) thru 100Ω
resistor.
14. Analog 0 – 5vdc, follows DC bus voltage. Direct op amp (MC33272AD). 10kΩ series resistor.
15. Voltage Adjust input (optional), selected by jumper J9, use 5kΩ pot, 0-10vdc only (10v= 100%),
impedance 10k Ω.
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 5
16. Clock Freq out (1x). Output pulls low via open collector ( MMBT4401 ). 10kΩ pull-up to +5.
100Ω series protection resistor.
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 6
DAT 210 JUMPER CHART
SWITCH
SW1 SWITCH POSITION NAME FUNCTION IF INSTALLED
S1 ON PDM Enable If PDM is remotely commanded, remove to test 100% output
level. This is especially useful if the unit is hard wired to a PLC or
ORP controller.
S2 OFF LOW PDM Lower PDM period than 30 Hz
S3 OFF Not implemented
S4 ON HIGH/LOW current fault A window of normal operating current. This will cause a fault if
either the LOW or HIGH value is exceeded.
S5 OFF Soft fault Produces a wink in fault line #11 if one or more operational
windows are exceeded beyond the factory limit. Will not shut
down the inverter like a hard fault but attention is needed. The
fault is being managed by the inverter processor.
S6 OFF PDM Ramp Default – 5 sec. for inverter to ramp from 0 – 100% power.
Switch ON is immediate ramp to 100% inverter power.
S7 OFF Spare
S8 OFF 4/20 ma. Configuration for 4 - 20 ma. control 0 - 100% ozone output. At 2
ma the INV_ON LED will flash. At 3 ma. The output is reinabled.
If the jumper is removed, 0 - 10 (0 - 100%) volts controls the
ozone output. If the command is for zero ozone, the inverter will
be in standby.
JUMPER INSTALLED
DEFAULT
J101 OUT ON with power up ON-OFF command change. The inverter will turn ON 5 seconds
after power is applied and turned OFF when power is removed.
This is not recommended because it eliminates gas purge.
J1, J2 Alternate methods of inverter startup. See Pages 17 – 19.
J3 OUT SEMI-AUTO Tune J5 out, voltage pot active to set maximum power. Frequency
control is automatic.
J4 OUT Manual fan Fan goes on when power is applied and off when removed.
J5 IN Full AUTO-TUNE Voltage and frequency pots are not active. These parameters
are controlled automatically. In SEMI-AUTO mode, the voltage
pot controls total power but frequency control is automatic.
J9 IN Voltage control pot 1 - 2 jumper = internal control. 2 - 3 = external
J10 IN Frequency control pot 1 - 2 jumper = internal control. 2 - 3 = external
J11 IN PDM control pot 1 - 2 jumper = internal control. 2 - 3 = external
J12 *Stow Installed = 4/20 ma. Or
Adds 500 ohm resistor to control input. If two or more DAT 210s
0/20 ma.
are to be controlled via one current loop, wire all Connector
OUT = 0 - 10 VDC
CON12 term. 3 together and all term. 6 together and install J12
on one DAT 210 inverter. Usually S8 ON and J12 jumper are used
together.
*Jumpers that are available for customer needs are stored on one pin.
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 7
TUNING THE INVERTER
Safety Considerations
DANGEROUS VOLTAGES ARE ON THIS CIRCUIT BOARD
To avoid injury to personnel and/or damage to equipment only qualified personnel should
perform the procedures outlined in this chapter. This person must understand both the electrical
and mechanical components associated with the application.
Thoroughly read and understand the following procedures before beginning the start-up process.
The following specific safety procedures must be observed when performing any maintenance or
adjustments on the amplifier.
Always turn off and lock out AC power at the main machine disconnects switch. Do this before
touching any electrical or mechanical components.
High voltage may be present even with all electrical power supplies disconnected.
Use an appropriate meter to verify that all DC bus capacitor banks have been discharged before
working on any equipment. Do not rely exclusively on high voltage RED LED indicator for bus
voltage, as dangerous voltage levels may remain even when the indicator is off.
Follow industry recognized safety procedures. Use only one hand to hold test equipment probes,
wear approved eye protection, etc. Before energizing the inverter, make sure that device(s)
connected to the output of the inverter will not result in injury or damage to equipment. Keep
unnecessary personnel out of the immediate work area. Never leave an inverter cabinet open
and unattended.
Start-up Checklist
To ensure a complete checkout and test, check off each step as it is completed. If the proper event does not
occur while performing this start-up procedure, do not continue. Take the appropriate action to correct the
malfunction before proceeding.
• Ensure the main disconnect switch is locked off. High voltage may be present even with all electrical
power supplies are disconnected. Use an appropriate meter to verify that all DC bus capacitor banks have
been discharged before working on any equipment. Do not rely exclusively on RED LED indicator of bus
voltage, as dangerous voltage levels may remain even when indicator is off.
• Verify that the inverter mounting has been performed in accordance with the guidelines listed in
• Chapter 2.
• Inspect the inverter to verify that all optional modules have been selected and installed according to the
system drawings and documentation.
• Verify that all wiring has been installed according to the wiring plan produced by the design engineer and
according to the guidelines listed in Chapter 3 for proper connection, grounding, wire size, labeling,
routing and applicable codes. The DAT 210 does not have internal fusing. Install input and output
(optional) fusing per suggestions Page 23.
• Verify that all electrical terminals, screws, nuts, and bolts are securely fastened.
• Apply high voltage DC or single-phase AC power to the inverter as specified.
• Check to make sure that the RED Bus voltage LED is on, indicating bus voltage.
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 8
PROGRAMMING AND TROUBLESHOOTING
The DAT210 board on all Plasma Block® products contains 10 LED’s which are used to indicate status during normal
operation, board programming and troubleshooting of the unit.
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 9
The DAT210 board's 10 LED's are shown below in various patterns with related status/description information.
Under normal running conditions, the LED light pattern will appear as shown here.
The INV ON and +5VOLTS will be solid ; the LOCKED will be flickering.
Press the START button and hold briefly until these LED’s show, then release.
S
S
PERFORMING CALIBRATION MODE – STEP 3
F This light pattern indicates T1 is set higher than 2% of the original set point. Adjust the T1
voltage pot to a value within the 2% range where the HIGH PWR led turns off. Proceed to
the final step below.
S
B
S
S OR
PERFORMING CALIBRATION MODE – STEP 3A
F This light pattern indicates T1 is set lower than 2% of the original set point. Adjust the T1
voltage pot to a value within the 2% range where the LOW PWR led turns off. Proceed to the
final step below.
S
B
S
S
PERFORMING CALIBRATION MODE – STEP 4
FINAL STEP. Press the start button and hold it briefly until the LED’s light up, release the
start button to exit calibration mode. The unit has now been adjusted to the original
factory set values.
B
B
B
S
S
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 10
The DAT210 board's 10 LED's are shown below in various patterns with related status/description information.
Under normal running conditions, the LED light pattern will appear as shown here.
The INV ON and +5VOLTS will be solid throughout this process; the LOCKED will be
flickering.
F
S
S
PERFORMING START BUTTON SWEEP – STEP 2
Holding the START button down until the LOCKED, LOW_PWR, and HIGH_PWR blink
simultaneously.
B
B
B
S
S
PERFORMING START BUTTON SWEEP – STEP 3
After a second or two the LOAD_FLT and HOT_LOAD will blink simultaneously, along with
B the blinking LEDs in the previous step. When this occurs, release the START button.
B
B
B
B
S
S
PERFORMING START BUTTON SWEEP – STEP 4
Upon release the LOCKED LED will blink rapidly. This indicates the frequency is
sweeping up and down to find optimum value. The LOCKED LED will blink then flicker as
normal after a few seconds completing the process. Verify the power or amperage draw
values are within acceptable range for the model being used.
B
S
S
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 11
The DAT210 board's 10 LED's are shown below in various patterns with related status/description information.
NOTE – the unit must be in semi-auto mode (J5 removed) to program the power setpoint.
When T1 has been turned to the desired set point press and hold the OP_OK button until this
B pattern shows --- then release.
B
S
S
S
PROGRAMMING A POWER SET POINT – STEP 2
Upon release, the HIGH_PWR and LOW_PWR LED's will blink alternately. The unit may
be in a tolerance set point of +/- 40%, +/- 20% or +/- 10%. Pressing the OP_OK button
will cycle/repeat thru these three choices with a varying LED blink time (10% fast, 20%
B medium, 40% slow). To exit this mode or select a tolerance, move to STEP 3.
B
S Once desired tolerance band has been selected press and hold OP_OK longer than in the first
S step to attain this LED light pattern and then release.
S
S
S
S
S
S
PROGRAMMING A POWER SET POINT – STEP 4
S
S If successful, this pattern of LED’s will display. The INV_ON will blink once followed by a
S blink of the LOW_PWR LED. This pattern is a response to let the user know that the
S programming of the power setpoint has been successful.
S
B
S
B
S
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 12
TROUBLESHOOTING DAT210 PROBLEMS
S
LOW POWER WARNING – PATTERN 1
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 13
POWER LIMIT WARNING.
F HS_TEMP and HOT_LOAD lights will flicker Step 1 Turn T1 pot counterclockwise until LED
F rapidly in an alternating pattern. Power level pattern ceases.
is reaching or at a dangerous point; unit will
S not increase wattage past this limit. DAT210 Step 2 Continue decreasing T1 until HIGH PWR
will shut itself off after approximately 20 LED turns off.
F seconds.
S
S
LOAD FAULT - PATTERN 1
Pattern is caused by the DAT210 detecting a Step 1 Does unit display a hard fault? PATTERN 3
problem with Plasma Block cell or the Yes – Go to step 2.
B transformer. After 5 – 10 seconds board will No – Go to step 3.
display pattern 2 shown below.
Step 2 Check for proper connection of transformer
F To PCB and Plasma Block cell.
S
S
LOAD FAULT - PATTERN 2 Step 3 Replace the transformer with a known
Functioning transformer.
After 10 – 15 seconds board will display
pattern 3 shown below. Step 4 Turn unit on.
B Does the light pattern remain ?
(ANY OF THE THREE)
Yes – Turn unit off. Proceed to Step 5.
B No – Transformer has gone bad.
S
Step 5 Using original transformer, swap the cell.
S LOAD FAULT - PATTERN 3
Step 6 Turn unit on.
Hard fault indicated by this LED pattern. The
Does the light pattern remain ?
unit has shut itself off to prevent damage to
S (ANY OF THE THREE)
the cell, transformer, or PCB .
Yes – PCB has malfunctioned, contact PTI.
No – There is a problem with the cell block
or other component.
S
S SOFT CHARGE RELAY FAILURE. Step 1 Check proper connections by referring
to “Single phase soft start” manual
This pattern of lights indicates a soft charge on PTI’s website.
relay failure.
B Step 2 Remove AC from relay.
B Step 3 Remove wires from DAT210
(on 12 terminals 3 & 5).
S
Step 4 Apply 5VDC to those removed wires
and listen for an immediate click sound.
If no CLICK, bad relay.
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 14
START-UP PROCEDURE POWER ADJUSTMENT
1. For PlasmaBlocks®
By altering the ‘Voltage’ setting, you can easily modify the full power operational point if need be. Remember
that the purpose of the PDM control is to provide a turndown from the 100% power set-point established by the
VOLTAGE pot. The goals are 1) Maximum power and 2) Current High/Low limits. Adjustment is very easy.
If it is determined that the Plasma Block® has much more ozone output than the application requires. You
would know this if, for example, if the closed loop control from an ORP unit always had the PDM adjusted to a
very low value of current, like 6-10ma.
OR
A PlasmaBlock® is going to be applied at pressure and flow range that is different from the factory setup.
OR
If the inverter was purchased to be used with a PTI resonating inductor and transformer set to drive a new cell
or changed cell configuration, the inverter would have to be tuned.
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 15
8. Lock in the new operating point by pushing and hold the ‘Op_OK’ button until the Red LEDs come ON.
Then release it. Then ALL the LEDs will come ON (except FAULT) momentarily to acknowledge your input
and the inverter will turn OFF. This action permanently stores the new parameters in the processors
memory and causes a reboot of the unit.
9. Set Switches S1, S4 and S5 to ON. Reinstall J5 (AUTO_Tune). Re-enable by cycling the inverter OFF and
ON.
10. Now observe the inverter gradually increase power to the new programmed level automatically at 100%
PDM. Frequency control is automatic and the LOCKED LED will cycle indicating frequency lock. The
inverter PDM can now control power from 1% to the 100% new programmed value.
You should now observe that the PDM level (power control) being commanded from the ORP unit is much
greater, for example, hence making the control loop more stable.
OR
The inverter is now properly configured for the new ozone cell components
OR
The inverter is now properly configured for new pressure or flow ranges.
Make sure the inverter has the correct code for the frequency range of interest. Either the factory has or will set
this up before shipment or you will need a PC in terminal mode connected via USB to RS-232 to the inverter
board. Call the factory for the correct codes and instructions.
Monitor the line current with a true RMS ammeter. The following assumes power factor correcting components
are installed. See the 700250 inverter assembly.
Procedure:
1. Observe the current or power meter and reduce the frequency by turning the Frequency pot CCW.
The power will peak at a lower power because the Voltage pot is turned down.
If the frequency is lowered too far (CCW) the power will reduce. You want the peak.
2. Increase the voltage at the current (power) peak until ½ of the maximum desired current per leg
(power) is reached.
3. Readjust the frequency slightly to find the current peak.
4. Increase the voltage until the current reaches 90% of the expected maximum power.
5. Verify the frequency is still at peak with the frequency pot.
6. Increase the voltage pot CW to reach 100% expected power.
7. Set the High/Low power limits.
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 16
Push the OP_OK push switch once (1 to 5 seconds). Two Yellow LEDS will come on and blink slowly.
This is the +/- 40% power fault tolerance limits.
Push OP_OK once again. The Yellow LEDS will flash faster. This is the +/- 20% limit.
Push OP_OK once again. The Yellow LED will flash even faster. This is the +/- 10% limit.
Keep pushing OP_OK and the cycle repeats.
The normal factory recommended limit is +/- 20% (40% total).
8. Lock in the new operating point by pushing and hold the ‘Op_OK’ button until the Red LEDs come
ON. Then release it. Then ALL the LEDs will come ON (except FAULT) momentarily to acknowledge your
input and the inverter will turn OFF. This action permanently stores the new parameters in the
processors memory and causes a reboot of the unit.
9. Set Switches S1, S4 and S5 to ON. Reinstall J5 (AUTO_Tune). Re-enable by cycling the inverter OFF and
ON.
10. Now observe the inverter gradually increase power to the new programmed level automatically at
100% PDM. Frequency control is automatic and the LOCKED LED will cycle indicating frequency lock. The
inverter PDM can now control power from 1% to the 100% new programmed value.
If during the manual portion of the tuning effort it is not possible to reach the current peak, then call the factory
to help diagnose the reason. It may be that the load is very insensitive to the frequency and that Auto-Tune is
not feasible. In that case, expect the inverter to be left in the manual mode.
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 17
TROUBLESHOOTING
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 18
IGBT FAULTED 2 Is IGBT faulted light ON? Yes - There is a short in the inverter
output section that has exceeded
the allowable event limit. Look for
damaged or loose wires, metal
chips, water corrosion or anything
that could cause a short.
No - Go to step 3
HS TEMP 3 Is HS TEMP faulted light ON? Yes - Review Status LED description
for detail
No - Go to Step 4
HOT LOAD 4 Is HOT LOAD faulted light ON Yes - Review Status LED description
Section 6 for detail.
No - Go to Step 5
LOAD FAULT 5 Is LOAD FAULT light ON? Yes - Possible water flooded cell due
to the process entering the cell. If
the process water is clean, empty
the water out of the cell and flush
with DI water or 91% alcohol.
EMPTY FLUSH WATER FROM CELL!
Then dry with very dry oil free air or
oxygen for several minutes. Try to
operate again. Do not disassemble
the cell. Call the factory.
No - Go to Step 6.
HIGH POWER 6 Is HIGH POWER light ON? Yes - Review Status LED description
Section 6 for detail.
LOW POWER 1 Is LOW POWER flashing? Yes - This is non-critical indication
that the power is less than the
programmed window.
No - Go to Step 2
2 Is LOW POWER ON steady? Yes - Output current is too low than
the programmed window. If this
condition remains for more than 32
seconds, a hard fault will shut off
ozone and turn on the fault LEDs for
diagnostics. Review Status LED
description in Section 7 for more
detail.
Plasma Technics Inc. 1900 William St. Racine, WI 53404-1875 Phone : (262) 637-7180 Fax : (262) 637-7157
Web Page : http://www.plasmatechnics.com E-Mail : [email protected] Page 19