VRLA/AGM Battery GetPower GP12-70L / 12v - 70ah (English)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Machine Translated by Google

The GP-12V Series batteries have AGM (Absorbed Glass Mat) technology, electrolyte absorbed in a glass microfiber blanket, and
are valve regulated (VRLA-Valve Regulated Lead Acid), enabling a gas recombination process with efficiency greater than 99%. .

GP/AGM-12V Series Battery Technology allows use in a variety of applications. It requires less maintenance, reducing operating
costs, without the need to add water or electrolyte.
GP12-70L
(12V-70AH)
These differences mean that GetPower GP/AGM-12V Series Batteries are classified according to the Eurobat Guide as “Multi
Purpose” or General Use batteries. They are widely used in TELECOMMUNICATIONS systems, UPS, AUXILIARY SUBSTATION
VRLA/AGM technology
SYSTEMS, PHOTOVOLTAICS among other applications.

TECHNICAL CHARACTERISTICS BATTERY IMAGE


Rated voltage 12Vdc
Capacity 65Ah/10h-1.75Vpe at 25ºC
Weight 18.40 kg±5%
Length: 260mm
Width: 169mm
Dimensions ±2mm
Height: 210mm
Total Height: 214mm
Internal Resistance 5.70mÿ
Short Circuit Current 398.25A
Self Discharge <3% per month
Vessel and Lid Material ABS-FR/HB
Separator Special AGM
Discharge:-15°C ~ 50°C
Operating Temperature Range Load: -20°C ~ 40°C
Stock: -15°C ~ 40°C
Recommended Operating Temperature 25±3°C
Coef. voltage x temperature correction 3mV/elem./°C - 5mV/elem./°C
Load Voltage Fluctuation 2.25~2.30Vpe at 25°C
Load Voltage Equalization (cyclic use) 2.35~2.40Vpe at 25°C
Recommended Load Current 13A
Maximum Load Current 0.2C10
Maximum Discharge Current Types of 700A at 5S
Terminals Period in Metal insert M6x16mm Image for illustrative purposes only
stock without recharging 6 months at 25°C

MAIN APPLICATIONS MAIN FEATURES


Telecom Grids: Plate grids are made of PbCaSn, greater resistance to corrosion, less gases and less self-discharge.
UPS Excellent performance: Meets the most stringent regulatory requirements such as IEC, CE, UL etc.
Solar energy Number of Starts/Cycles: Minimum 1,200 cycles at 30% DOD
Substation Auxiliary Systems Poles: Pole/lid sealing system uses special epoxy resin with a low contraction rate.
Photovoltaic Systems AGM Separator: High quality AGM separators provide excellent cycling and prevent short circuits.
Railway Signaling Projected Service Life: For floating use at 25ºC it is 10 years.
Security, Alarm and Emergency Mixed use: Technology allows use in long, medium and high discharge intensity.

DISCHARGE CHARACTERISTICS
CONSTANT DISCHARGE CURRENT (AMPERES) AT 25°C (77°F)

TF/Time 5min 10min 15min 20min 30min 45min 1 hour 2 hours 3h 4h 5h 6 am 8 am 10am 8pm

1.60Vpe 169,600 119,300 105,300 81,700 62,500 115,400 102,200 79,700 44,700 37,900 23,100 17,000 37,300 22,700 13,200 11,400 9,800 7,550 6,210 3,260

1.65Vpe 163,800 61,600 113,600 100,750 78,600 61,150 111,800 99,300 44,100 16,900 37,050 22,550 16,800 36,800 13,100 11,200 9,730 7,450 6,140 3,220

1.67Vpe 161,050 77,500 60,700 104, 900 93,500 73,100 59,500 86,300 43,750 22,400 16,700 36,100 22,000 16,400 13,000 11,100 9,710 7,400 6,100 3,200

1.70Vpe 158,300 67,700 58,300 76,200 59,900 53,600 67,282 52,999 43,400 34,400 20,900 16.1 00 33,200 20,200 12,900 11,000 9,690 7,350 6,060 3,180

1.75Vpe 148,000 49,279 42,600 14,800 32,042 19,523 13,605 12,700 10,800 9,640 7,240 6,030 3,150

1.80Vpe 136,300 96,700 41,100 12,400 10,600 9,560 7,200 6,000 3,120

1.85Vpe 119,800 85,200 38,800 11,600 10,100 8,900 6,850 5,670 3,010

1.90Vpe 105,297 75,068 36,629 10,852 9,624 8,286 6,517 5.358 2.904

CONSTANT DISCHARGE POWER (WATTS) AT 25°C (77°F)

TF/Time 5min 10min 15min 20min 30min 45min 1 hour 2 hours 3h 4h 5h 6 am 8 am 10am 8pm

1.60Vpe 289,500 207,300 193,200 152,600 118,600 83,000 73,800 45,400 33,800 26,400 22,800 19,100 15,300 12,700 6,680

1.65Vpe 285,500 204,500 190,500 150,500 118,100 82,600 73,200 45,000 33,600 26,200 22,500 19,000 15,200 12,600 6,610

1.67Vpe 283,200 202,850 189,000 149,300 117,700 82,250 72,900 44,800 33,550 26,050 22,350 19,000 15,100 12,500 6,575

1.70Vpe 280,900 201,200 187,500 148,100 117,300 81,900 72,600 44,600 33,500 25,900 22,200 19,000 15,000 12,400 6,540

1.75Vpe 267,200 191,400 178,300 140,900 115,900 80,800 71,500 43,900 33,000 25,500 21,900 18,900 14,800 12,300 6,480

1.80Vpe 250,400 179,300 167,100 132,000 114,500 78,500 68,500 41,800 32,400 25,100 21,600 18,800 14,800 12,200 6,420

1.85Vpe 223,800 160,300 149,400 118,000 106,000 74,600 66,500 40,700 30,000 23,600 20,600 17,600 14,100 11,700 6,200

1.90Vpe 196,708 141,236 131,915 104,405 97,455 70,425 64,180 39,337 27,578 22,077 19,628 16.385 13.415 11.057 5.981

STANDARDS/CERTIFICATIONS
CERTIFICATIONS STANDARDS
ISO9001 IATF16949 CE
ISO14001 EUROBAT UL
ISO45001 IEC60896.21

CNPJ 06.282.480/0001-07
Rua Senador Vergueiro, 100 - Centro – São Caetano do Sul - SP - 09521-320
11 4227-2477 | www.powersafe.com.br | [email protected]
Machine Translated by Google

BATTERY/TERMINALS DESIGN
Metal insert

PERFORMANCE CURVES

Cyclability Curve X DOD (25°C) Floating Service Life Curve

1200 10

1000
8

800

6
NUMBER

600 LIFE

4
400

two

200

0 0
30 40 50 60 70 80 90 100 25 30 35 40 45

DISCHARGE DEPTH (%) TEMPERATURE (°C)

Self Discharge x Temperature Load Characteristic Curve

ÿÿÿÿÿÿÿ ÿÿÿÿÿÿÿÿÿ
ÿÿÿÿÿ ÿÿÿÿÿ
ÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿ
100 ÿÿÿ ÿÿÿÿÿÿ ÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿ ÿÿÿ

10°C
80 ÿÿÿÿ
ÿÿÿ
ÿÿÿÿ

25°C ÿÿÿ
ÿÿÿÿ
ÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿ

RESIDUAL
60 ÿÿÿ
ÿÿÿÿ
ÿÿ

ÿÿ ÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿ
ÿÿÿÿ
40 40°C 30°C ÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿ
ÿÿ
ÿÿÿÿ
ÿÿ
ÿÿÿÿ ÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿ
20 ÿÿ
ÿÿÿÿ
ÿÿ
ÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿ
ÿÿ
ÿÿÿÿ
0 ÿÿ ÿÿÿÿ

two 4 6 8 10 12 ÿÿ
ÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿÿ
ÿ ÿ ÿ
STORAGE (MONTHS) ÿ ÿ ÿ ÿÿ ÿÿ ÿÿ ÿÿ ÿÿ ÿÿ ÿÿ ÿÿ

Note: The information is descriptive only and is not intended to represent the warranty of the batteries under any circumstances. The data g
General terms are subject to changes or modifications without prior notice.

CNPJ 06.282.480/0001-07
Rua Senador Vergueiro, 100 - Centro – São Caetano do Sul - SP - 09521-320
11 4227-2477 | www.powersafe.com.br | [email protected]

You might also like