CT600 Multi Crystalline Manual
CT600 Multi Crystalline Manual
6.9 Control Cabinet with Power Supply and PLC.....................94 9.2 Start Screen....................................................................144
9.5 “Cooling Water” function..................................................148 11.3.7 Maintaining Warning Labels and Inscriptions...................190
11.3.8 Maintaining Electrical Components..................................190
9.6 “Moving Technology” - function .......................................150 11.3.9 Checking High-Voltage Lines ..........................................191
11.3.10 Maintaining Measuring Equipment...................................191
9.7 “Temp IW selection” - function.........................................152 11.3.11 Maintaining Control Elements..........................................191
11.3.12 Maintaining Guide Rails ..................................................191
9.8 “Heating Parameters” - function.......................................154 11.3.13 Maintaining the Guide Rods of the Handling Tool ............192
11.3.14 Maintaining the Melting Crucible......................................192
9.9 “Process Data” - function.................................................156 11.3.15 Inspecting the Support Crucible.......................................192
11.3.16 Inspecting the Hot Zone Integrated Safety Barrier ...........192
9.10 “Processes” - function .....................................................158 11.3.17 Inspecting Graphite and CFC Components .....................192
11.3.18 Inspecting the Current Feed Through ..............................193
9.11 “Process Status” - function ..............................................160 11.3.19 Maintaining the Overall Furnace......................................193
11.3.20 Maintaining the Chamber Interior ....................................193
9.12 „Diagrams” - function.......................................................162 11.3.21 Inspecting the Argon Piping.............................................193
11.3.22 Measuring Cooling Water................................................193
9.13 „CSV Archive” - function..................................................164 11.3.23 Cleaning the Touch Panel ...............................................194
11.3.24 Replace Cooling Water Filter...........................................194
9.14 „Profibus Diagnostics” function........................................166
11.4 Restart after Maintenance ...............................................195
9.15 “Service Maintenance” function .......................................168
9.17 „Service Sensor Setup” function ......................................172 12.1 Instructions for Dismantling the Furnace..........................196
9.18 “Process Data Online” function........................................174 12.2 Dismantling the hot zone.................................................196
11 Maintenance.......................................................................179
1.3 Used Symbols The structure of warnings always contains the same elements:
symbol, warning level, cause and remedy.
In this Operating Manual instructions are weighted and labeled with a
corresponding symbol in accordance with the effect the instruction can Example:
have if not observed.
The safety and warning instructions do not claim to be complete.
DANGER Hazardous voltage!
Warning Levels There are three warning levels.
There is an electric shock hazard when touching or approaching live
parts.
Warning Level Cause and Remedy Take all safety precautions relating to high voltage.
DANGER Immediate risk of death or serious injury. If not Shut off power supply and UPS and secure against restart.
avoided, the hazardous situation will result in
death or serious injury.
WARNING Risk of death or serious injury. If not avoided, the
hazardous situation could result in death or Mandatory Instructions Symbol Instruction Explanation
serious injury.
Mandatory Wear safety Disobeying this instruction can
CAUTION Risk of minor or moderate injury. If not avoided, symbols such as helmet! result in bodily injury.
the hazardous situation could result in minor or
moderate injury.
Additional Information Additional information, tips and tricks are indicated with the symbol.
Example:
Symbol Hazard
Risk of death or injury!
This symbol indicates a location with immediate
risk of death or injury. The situation can result
in life-threatening or even fatal injuries.
This symbol also indicates hazards not covered
by other symbols.
This symbol indicates a fire hazard. This symbol indicates that fire and open flames
are prohibited in this area.
Crush hazard!
No smoking!
This sign is in front of activities involving a risk
of being crushed This symbol indicates that smoking is
prohibited in this area.
Hand crush hazard!
This symbol indicates a hand crush hazard. No pacemakers!
This symbol indicates that pacemaker wearers
do not have access to this area.
Tip over hazard!
This symbol indicates a tip over hazard during No food or beverages!
transport.
This symbol indicates that food and beverages
Fall hazard! are prohibited in this area.
• Irritant
• Dermal sensitizer Symbol Instruction
• Acute toxicity (harmful)
• Narcotic effects Wear safety helmet!
• Respiratory tract
• Irritation
Warning – gases under pressure!
This symbol indicates a hazard from gases Wear ear protection!
under pressure.
Misuse The furnace system was exclusively designed for the purpose
2 Safety indicated in the "Intended Use" section. Any use beyond that purpose,
This chapter contains the intended use of the tandem system and a such as melting or heating up other material, is regarded as misuse.
summary of all the important safety provisions. This chapter is Abuse can result in personal injuries to users or third parties.
therefore suitable for the initial, basic induction of new employees. Furthermore, the Furnace System itself or other material property can
be damaged.
2.1 Intended Use
The manufacturer is not liable for any personal injury or material
The CT600 Multi-Crystalline Ingot Furnace is intended for melting and damage resulting from any such misuse.
directional solidification of silicon in a specified quality to produce
multi-crystalline ingots. 2.2 General Safety Information
• Charging In the event of faults which impair safety and changes in the operating
conditions, stop the furnace system immediately and report the
o Charging the crucible up to the filling edge freely selectable malfunction to personnel responsible.
o Feedstock material sorting freely selectable
• Function test 2.2.1 CE-marking
o Assessment and storage of heating and cooling times The system meets the basic health and safety requirements of the
o Evaluation via parameter database relevant EU directives.
The CE mark and the EU declaration of conformity were issued by
• Leakage measurement centrotherm SiTec GmbH.
o Measurement of the leakage rate and analysis of the results
Other Persons Other persons are persons who do not fall under the above
2.3 Personnel Qualification definitions. The owner/operator must assume that those persons do
not have knowledge of the possible hazards of the furnace. By means
2.3.1 General of appropriate measures, make sure that other persons do not enter
The plant's owner/operator must clearly define the responsibilities of operation or hazardous areas and that they observe the general
personnel regarding operation, maintenance and repair. safety instructions.
Personnel must be in good health and mentally fit for operating the
plant. Table 2-1: Personnel Qualification
Personnel to be trained or instructed or personnel in training shall only
work at the furnace under constant supervision of an experienced Personnel Instructed Engineer Operation Electrically Industrial
person. Activity Person for Personnel Skilled Mechanic
Special Person
The individual tasks to be carried out at the furnace require different Tasks
personnel qualification listed in the following in Table 2-1.
If the specified personnel qualifications are not observed, hazards can Transport • •
result during work on the plant. Assembly • • •
Instructed Person for Special Person instructed by an engineer about the assigned tasks and
Tasks possible hazards which can result from improper use and trained, if
Electrical installation •
required. Person moreover instructed about required safeguards and Start-up, operation, shutdown • •
protective measures.
Mechanical & Electrical
Engineer An engineer is someone who, due to suitable education and training, • • • •
Disassembly
is able to carry out the assigned tasks and recognize possible hazards
as well as to read and understand piping and instrument diagrams Cleaning •
(PID). The engineer must be familiar with the regulations for e.g.
Mechanical work: troubleshooting,
accident prevention, occupational safety, fire protection and •
environmental protection applicable at the operating site, as well as repair and maintenance
with the plant's operating conditions and risks. The engineer must Work on the electrical system:
have knowledge of process engineering to be able to understand, troubleshooting, repair and •
control and adapt the processes in the plant. maintenance
Operation Personnel Operation personnel are persons who, due to suitable education and
Disposal • •
training, are able to carry out the assigned tasks, recognize possible
hazards as well as to read and understand piping and instrument
diagrams (PID).
2.3.2 Personnel Training
The operator must have knowledge of process engineering to be able
to understand and control the processes in the plant. Personnel must have been trained – either by centrotherm SiTec
Operation personnel must be familiar with the regulations for e.g. GmbH, or by persons who themselves have been trained by
accident prevention, occupational safety, fire protection and centrotherm SiTec GmbH.
environmental protection applicable at the operating site as well as Training must be repeated regularly by the operating company and
with the plant's operating conditions and risks. confirmed by signature. The owner/operator is responsible for
Electrically skilled personnel must be able to read and understand arranging the first training and regular refresher trainings.
Electrically Skilled Person
electric circuit diagrams, to put electrical systems into service, to The owner/operator determines the suitability of experts and operating
maintain them, to wire control cabinets, to ensure the functionality of personnel.
electrical components and to identify possible hazards from handling
Repeat safety training every six months.
electrical and electronic systems.
Industrial Mechanic Industrial mechanics must be able to read and understand machine
drawings, piping and instrument diagrams (PID) and process flow
diagrams (PFD), to execute or supervise the safe assembly of plant
components, to maintain it mechanically, to ensure the functionality of
mechanical components, to prepare the plant for start-up, to identify
possible damage and to recognize potential hazards relating to the
plant.
2.5.2 "Messages and warnings" Signal Tower The workstations are illustrated on the figures below.
A "Messages and warnings" signal tower is installed near the control 1 Carriage with top part of
cabinet. It indicates every general message or warning. chamber 1
2 Control panel
2.6 Personal Protective Equipment
2m
2.10 Escape Routes 2.11 Safety Information for Transport, Assembly and
Commissioning
Escape routes are special routes that should
Only instructed skilled workers with appropriate protective equipment
• be kept clear of all obstructions are authorized to carry out transport, assembly and commissioning of
• be at least one meter wide the furnace system. This also applies to re-commissioning after
• lead to a safe place, usually outside and away from the extensive repair work.
building. Please observe the following instructions for transport, assembly and
commissioning:
Doors on escape routes must be unlocked.
Lifting and transporting • Never stand under suspended loads.
There must be at least two separate escape routes per floor leading • Observe accident prevention regulations! Use personal protective
out of the building. equipment for work: wear safety footwear, protective gloves and
All doors in the escape routes should open in the direction of the protective glasses.
escape route. They have to be easily accessible. There must not be • Use only appropriate means of transport and separate lifting
any elevators in an escape route. accessories which can safely bear the weight of the load!
Emergency lighting should be available and powered by an Assembly and Commissioning • For overhead work, use a stable ladder or other safe ascending
independent power source. aids.
• Observe the relevant product safety regulations when handling
oils or grease.
• If work using open flame must be performed, such as welding,
Mark escape routes, footpaths and transport routes. flame-cutting, soldering, outside or inside the vessel or in a narrow
space, the person responsible must issue a written permit. When
work with open flame is performed, all persons present in the
vessel or narrow space must wear flame-resistant protective
clothing.
• A responsible person equipped with adequate fire extinguishing
equipment must be present in areas where sparks from welding or
burning can be present. All areas near the welding or cutting
scene, including the floors above and below shall be carefully
inspected and patrolled during work and for a certain time after
work has been completed.
• When work is interrupted or during breaks, all welding and
soldering tools must be removed from the vessel or narrow space.
• After completion of maintenance, inspection or repair:
o Clean the whole area.
o Re-establish the safe furnace condition.
2.12 Safety Information for Operation • Do not eat, drink or smoke when working.
Please observe the following instructions for furnace operation: • Use soap and water to clean skin covered with graphite or silicon.
• Installed safety devices may not be put out of operation. Only
• The furnace may only be operated by instructed persons
operate the furnace system when all the safety and protective
authorized by the owner/operator.
devices are in full working order.
• Responsibilities for furnace operation must be clearly assigned
• If it is necessary to touch a heated component, put on heat-
and observed so that there are no unclear competencies which
resistant protective gloves.
could result in hazards.
• Ensure that no unauthorized persons are on the system (in the
• Do not do anything which could affect furnace safety.
immediate vicinity of the furnace) during movement of the
• Always operate the furnace in proper and safe condition. carriage.
• Only operate the furnace with parameters indicated in the • Activate EMERGENCY STOP button in the event of danger!
technical data. The process recipe that is provided by centrotherm
• Only work on the system with hall lighting switched on and
SiTec GmbH is only valid for the corresponding hardware design
illumination of the system components (cooling water supply).
of the hot zone and the corresponding net weight of the silicon.
Otherwise hazardous!
Any changes on the process recipes or on the hot zone, or higher
silicon net weights can be critical. • Avoid operating high-frequency, remote controlled and radio
equipment in the vicinity of the equipment electronics and their
• The temperature measurement of the system must be checked
cables.
and calibrated regularly. Even marginal displacement of a
thermocouple or not correctly adjusted pyrometers can lead to • The settings of the flow meters and pressure control valves of the
wrong measured values. furnace system may only be altered by authorized skilled workers.
• Observe the maintenance schedule of the system components. • Clean the area around the system daily. Remove loose parts.
Not properly maintained components may lead to hazards. Clean up liquids on the floor immediately. Danger of slipping!
Especially the graphite components may change its thermal
properties during process deployment and must be replaced
according to the maintenance schedule even if there are no visible
defects. DANGER Suffocation hazard!
• Any changes of process data, hot zone design and net weight During operation, there is a suffocation hazard in the chamber interior
which are not in accordance to the specification will cause serious resulting from
damage.
o vacuum
• You must immediately report changes of the furnace which affect
safety to the owner/operator. o high temperatures
o Argon supply.
• Observe the applicable national and local rules and regulations for
accident prevention, occupational safety, fire protection and
environmental protection. • Prior to every process start-up, make sure there is no person
inside the chamber.
• Observe all safety labels and information in the plant.
• Observe the safety instructions relating to process media.
• If the plant's operating behaviour changes drastically, the plant or
the affected section of the plant must be brought to a safe state
immediately. The supervisor must be informed about the changes.
The malfunction or damage must be repaired without delay. If this
is not your responsibility or if you do not have the required
technical abilities and knowledge, a supervisor must be
immediately informed about the failure, so that the replacement of
missing or damaged parts can be organized.
• Damaged or missing parts must be replaced immediately. Spare
parts must comply with the technical requirements specified by
centrotherm SiTec GmbH. This is ensured if original spare parts
from centrotherm SiTec GmbH are used.
• Wearing baggy clothing, loose long hair and jewelry are forbidden.
• Avoid any metal contamination inside the process chamber. Do
not carry any material in your pockets when entering the system
area, for example pens or mobile phones.
• Change dirty clothing.
Maintenance • Observe all maintenance intervals. o The hose springing out of the fitting
• Maintenance, inspection and repair work may only be carried out o Corrosion of fittings reducing function and strength
by suitably qualified experts. o Failure to observe installation requirements
• Repairs and maintenance work on the hot zone may only be o Exceeding storage life and durability
performed by skilled personnel after prior instruction.
All work on the hot zone must only be performed when the • For overhead maintenance work, use a stable ladder or other safe
machinery is shut down. ascending aids.
• If malfunctions are detected during inspections, notify the • Observe the relevant product safety regulations when handling
personnel responsible of the malfunction in order to remedy the oils or grease.
fault. Only start operating the system again when the fault has
• If work using open flame must be performed, such as welding,
been remedied.
flame-cutting, soldering, outside or inside the vessel or in a narrow
• The unit or individual equipment or pipes or other parts to be space, the person responsible must issue a written permit. When
maintained must be put in safe condition before maintenance is work with open flame is performed, all persons present in the
started. vessel or narrow space must wear flame-resistant protective
• All activities must be coordinated with all other persons working clothing.
inside the unit. In case of shift work, adequate communication • A responsible person equipped with adequate fire extinguishing
between the personnel of the individual shifts must be organized. equipment must be present in areas where sparks from welding or
• Before replacing large modules, use suitable lifting tackle to burning can be present. All areas near the welding or cutting
secure them against falling or tipping over. scene, including the floors above and below, shall be carefully
inspected and patrolled during work and for a certain time after
• Spare parts must comply with the technical specifications by
work has been completed.
centrotherm SiTec GmbH. This is always guaranteed for original
spare parts of centrotherm SiTec GmbH. • If it is necessary to dismantle protective devices or safety
The installation and/or use of spare and accessory parts not equipment during maintenance and repair, the parts must be
supplied and released by centrotherm SiTec GmbH can negatively reinstalled and their function checked immediately after the work
affect furnace characteristics. has been completed.
The manufacturer cannot be held liable for damage resulting from • When work is interrupted or during breaks, all welding and
the use of non-original parts and non-original accessory parts. soldering tools must be removed from the vessel or narrow space.
Standard parts can be purchased in specialist shops.
• After completion of maintenance, inspection or repair:
• Damaged or defective parts must be immediately replaced.
o Clean the whole area.
• With appropriate measures, you must prevent that the furnace is o Re-establish the safe furnace condition.
operated with damaged or defective components.
• Before parts of the equipment are loosened (for replacement) Cleaning Please observe the following instructions for cleaning the furnace:
always secure them against tipping over or falling down by fixing
them to the ground whenever possible or by supporting with
mechanical measures. Before transporting the equipment to be
replaced, always make sure the hoisting gear is sufficiently CAUTION Open electrical control cabinets!
dimensioned and securely fixed. Never stand under overhead Water or dust can penetrate into open electrical control cabinets.
loads. Possible consequences are:
• If bolted connections must be loosened for maintenance, o Short circuit
inspection or repair, re-tighten them after work has been
completed and make sure they are securely seated. o Damage to electrical components
o Failure of process control.
• Inspect all cables, hoses and couplings regularly for leaks and
externally detectable damage. Have all damage remedied
immediately. • Close all electrical control cabinets.
Hoses should be replaced at once in the event of:
o Damage to the external shell (abrasion marks, cuts, cracks,
embitterment) • Do not clean the furnace during operation. Make sure that no
o Deformation in a depressurized or pressurized condition which other work is carried out during cleaning.
does not correspond to the normal shape of the flexible hose • Regularly clean the furnace to enhance its life, ensure its proper
o Leaks condition and allow trouble-free operation.
o Damage or deformation of hose fittings (reduced sealing ability); • The furnace may only be cleaned by instructed persons
minor surface damage does not constitute grounds for authorized by the owner/operator.
replacement
• Only fill the melting crucible to its maximum weight, filling level and
height. Even if the maximum weight is not reached, melted silicon
may flow over as a result of wrong silicon filling height or packing
density.
• Measure the weight of the loaded melting crucible before and after
the process cycle. Discrepancy regarding the weight indicates a
silicon overflow. In this case check the integrated safety barrier
(chapter 11.3.16, page 192).
• Ensure that the net weight and the ingot weight is in
accordance to the specification!
CAUTION If the process control fails, the process cannot be controlled anymore
Process gas supply failure!
and PLC and temperature recording can also fail. Possible
If the process gas supply fails, no more argon can be fed to the consequences are:
process chamber. Possible consequences are:
o Damage to the furnace
o Failure of the emergency purge function o Critical process conditions
o No redundancy of the cooling system o Uncontrolled solidification of melt.
o Oxygen purge in might occur
o Graphite might be polluted. • There is a risk of injury from spilling melt and hot vapours.
• Observe the inspection intervals in “11 Maintenance” on page 179.
• Provide for redundant process gas supply
• If the process control fails, purge the furnace with argon.
(chapter 5.1.5, page 73).
• Existing process gas is cooled through circulation.
• If the process gas supply fails, the cooling power of the water
cooling system is sufficient to safely complete the process. DANGER Critical process conditions!
Wrong operation of the furnace can result in critical process
conditions. There is a risk of injury from spilling melt and hot vapours.
2.15.9 Voltage supply • Only personnel sufficiently instructed about the process may
operate the furnace.
2 Provide for cooling water supply by leaving the main valves open.
This chapter contains the technical data of a single furnace system Electrical input 3/N/PE Input voltage V 3 x 400
(see chapter 1.1 ID N°). Each tandem system consists of two furnace Frequency Hz 50
systems. The described projects consist of two tandem systems.
Further on the specification of the cooling water is described. Maximal power consumption kVA 320
Maximal rated current A 463
3.1 Technical Data – Furnace
Sound pressure level SIHI measurement DIN ISO 9614 db (A) < 80
Table 3-1: Technical Data – Furnace
Ambient conditions Temperature °C 10 - 35
Description Unit Value Relative humidity (non-condensing) % 20 – 80
Weight (entire tandem system) kg approx. 7500
Weight components Support frame kg approx. 3000
(without water and 3.2 Specification of cooling water
attached peripherals) Carriage kg approx. 1500
Chamber brackets with drag chains kg approx. 500
Table 3-2: Specification of cooling water
Control cabinet kg approx. 750
Transformer (2 units) kg approx. 630 each Description Unit Value
Top part of chamber kg approx. 1800 Chloride (CI) mg/l < 150
• Electrodes
• Carriage (with drive units)
• Control cabinet with power circuitry and PLC
• Transformer
• Argon supply-piping and instrumentation
• Heat exchanger
• Cooling water supply and return piping, distributor, valves and
instrumentation
o Main connection valve
o Duplex filter with backwash capability
o Safety valve with steam discharge
5 Lift the top part and the bottom part of the chamber separately and
carefully.
6 Balance the system carefully, if necessary shift position points.
Figure 13: Control cabinet with eyelets
Now you can continue to lift and carefully transport the top and
afterwards the bottom part to the desired location. How to lift the control cabinet: 1Disconnect supply fittings to the cabinet
2Fasten the hoisting gear or chain to the eyelets (e.g. with load hooks)
3Pass the crane hook over the center of gravity of the control cabinet.
When transporting the system with a forklift truck, the chamber system 4Hitch the hoisting gear in the crane hook.
must be secured to avoid tipping over. Use long forks with bars to
support the frame.
Now you can continue to lift and carefully transport the control cabinet
to the desired location.
The control cabinets of the system must be packed in accordance with
valid normative documents (fragile goods). In addition, they must be
protected from falls and other damage during transportation.
How to lift big parts of the hot 1 Dismount every small part from the big ones, like the Argon shield
zone: and the top and bottom heating.
2 Start lifting the single big parts as follows:
o At the upper hot zone fasten four suitable eyebolts to the hot
zone.
o Hitch a suitable hoisting gear there.
o At the hot security box use the delivered lifting tool from
centrotherm Sitec GmbH and screw the four screws into the
windings in the corners.
o At the heat sink screw use a suitable eyebolt into the winding in
the middle of it to lift it with a suitable hoisting gear hitched
there.
o At the lower isolation box use the four ropes under each corner
and attach them to a suitable hoisting gear and lift it.
3 Lift the big parts of the hot zone carefully until it is suspended
unsupported.
4 Balance the big parts of the hot zone, if necessary.
Now you can continue to lift and carefully transport the big parts of the
hot zone to the desired location.
7 8 9 10
Figure 15: Main components of the tandem system (side view)
3
6 3
1
2
5
13
2
11
3
3
12
4
1 2
10
5
If the pressure decrease exceeds 1 bar, the second filter should be
Figure 21: Schematic view of the cooling water supply put into operation and the contaminated filter should be cleaned. The
decrease is not monitored at the PLC!
If a particular flow rate of cooling water is not reached a process run
can not be started. If the flow rate of electrode cooling water is not
sufficient, the particular heater is switched off.
The process instrument diagram (P&ID CT600) shows the internal
cooling water supply of the furnace system.
The cooling water supply to the furnace consists of the following 6.4.2 Heat exchanger
cooling water loops:
The heat exchanger has a cooling efficiency of approx. 60 kW. It is
o Chamber top part intended to cool the exhaust gas extracted from the furnace to prevent
o Chamber bottom part the pumps from being damaged. The heat exchanger needs a
o Heat exchanger permanent cooling water supply while operating the furnace.
o Electrodes top part
6.4.3 Vacuum Operation
o Electrodes bottom part
The pump station is continuously running during process. It is used for
o Vacuum pump system
different operations like evacuation, pressure control and recirculation.
6.3.3 Cooling water return and cooling water redundancy 1 Heat exchanger
The cooling water flow can only adjusted in the cooling water return 2 Pipe connection 1
collector.
3 Roots blower
o Vacuum pump system: 5 l / min
4 Bypass pipe 2 4
o Per Electrodes: 25 l / min
o Per Chamber: 82.5 l / min 5 SIHIdry pump
o Heat exchanger: 40 l / min
3
All furnaces must be supplied with the complete cooling water flow
continuously, also during loading and unloading of the furnace to
avoid malfunctions.
The cooling water supply system must have a redundant supply unit,
provided by the plant’s owner/operator, to avoid damage of the system
when having power supply failure or cooling water breakdown. If the
supply fails completely an emergency supply system for the pumps or
5
an emergency cooling water supply system (water network, elevated
tanks or accumulator tank), provided by the plant’s owner/operator,
must be operated until the furnace parts have been safely cooled
down. Figure 22: Components of the vacuum pump station
The leak and desorption rate can be up to 0.05 mbar l/s, for empty,
dry chambers, (measured after 8 hours of pump operating time). The 6.6 Carriage
pump operating time at 0.1 mbar is up to 10 min. The carriage unit is used for opening and closing the process chamber
and moves the top part of chamber between parking and furnace
6.5 Transformer position.
The transformer is set up on the system and consists of the following The carriage unit consists of the following modules:
components:
• Carriage rack
• Housing • Lifting unit two-sided
• Primary-secondary transformer unit • Hoisting frame two-sided
• Cable for heating electrodes • Vertical drive motors two-sided
The transformers can be heavily magnetized during process. • Drag chains on two-sided
Therefore, no operating personnel should work near the transformers • Top part of chamber
or touch them.
1 Drag chain
2 Lifting unit
3 Carriage
4 Top part of chamber
Drive unit vertical / lifting The vertical drive unit consists of a frequency-controlled motor which
lifts and lowers the top part of the carriage. The drive units are
installed on both sides of the top part of the chamber. The frequency
converters itself are located in the control cabinet. Main functionality of
the vertical drive unit is to open and close the furnace chamber.
Drive unit horizontal / moving Track system The horizontal drive unit consists of two frequency 6.7 Parking Position
controlled drive motors mounted on both sides of the carriage. These
motors move the top part of chamber between the furnace and the The parking position of a tandem system is designed to park one top
parking position. The frequency converters itself are located in the part of a chamber while the second furnace system is in operation.
control cabinet. Main functionality of the horizontal drive unit is to This configuration offers the advantage of a process flow optimized
move the furnace chamber. design and makes optimum use of the parking position.
The track system is securely mounted and aligned on the rack. It gives The top parts of the chambers can be parked at the parking position
Track system for two purposes crucible charging and maintenance.
a guided way for the horizontal movement of the carriage carrying the
top part of the chamber. Take care that the second carriage is locked and the selected carriage
Drag chain The drag chains are flexible cables and hose guides which are has received all necessary clearances from the control unit before you
respectively mounted on both sides of the chamber on the brackets. move the selected top chamber to the parking position.
The drag chains enable vertical and horizontal movement of the top The operator should take care of all safety measures to avoid collision
part of chamber. All flexible parts of the drag chains the cables and of the carriages as well as personnel hazard.
hoses inside must be regularly checked for wear and tear.
Screen By the TFT screen all major process data can be either displayed or
analyzed as charts.
Operator interface The operator interface is described in chapter “7.1 Control Elements”
on page 98.
Keyboard with trackball The PC keyboard with trackball allows the interactive handling of the
industry PC.
1 2 3 4 1
7
6
2
4
Top heater Bottom heater
EMERGENCY STOP In case of an emergency, the operator can STOP the whole system by
pushing the EMERGENCY STOP button.
All processes are stopped and the furnace control system is set into a
3
safe level.
3 1
4 2
5
1 Indicator light Indicator light is on when the top part 1 Horn signal Chamber moves.
"End position of chamber has reached the parking 2 Yellow flashing light Chamber moves.
assembly" position.
2 Emergency stop In case of an emergency the 7.1.4 "Messages, warnings and alarms" signal unit
button EMERGENCY STOP BUTTON is General messages, warnings and alarms are indicated by visual
used to set the whole furnace system signals. The signals follow the logic of a traffic light (red, yellow,
into a safe mode. green). In case of a warning or an alarm the effect is supported by a
3 Indicator light Indicator light is on when the top part flashing effect
"End position of chamber is in furnace position.
furnace"
1
4 Toggle switch Flip the switch to position "Open" to
"Open/Close" move the top part of chamber to the
2
parking position.
Flip the switch to position "Close" to
move the top part of chamber to the 3
furnace position.
5 Two-hand buttons Switches to activate the movement Figure 34: "Messages and warnings" signal unit
unit. Both buttons must be pressed by
the operator to move the top part of
chamber. Table 7-4: "Messages and warnings" signal unit
7.2 Main Switches at the Furnace System 3 Close the control cabinet and set he main switch on position “ON”.
This chapter describes the main switches at the furnace and the
functionality of said. In detail: How to start, set up and stop the
system.
4 Open the control unit and check if the UPS is switched on. If the
The safe and reliable operation of the furnace system is ensured by UPS is switched off, press the power button (see Figure 37).
using an uninterruptible power supply (UPS). Before starting a
process run, make sure that the UPS is switched on. 1 Power button
First Start When you START the system for the first time or after maintenance
1
activity, proceed as described below:
1 Open the control cabinet.
2 Turn the bypass-switch to the position “Mains” (see Figure 35).
1 Bypass switch
1
Figure 37: Power button for UPS
Figure 35: Bypass-switch on position “Mains”
5 Turn the bypass-switch (Figure 35) to the position “UPS”.
6 Close the control cabinet.
The program structure covers the following clearance levels that are
embedded in a clear hierarchical structure:
Viewer Without a password only display windows for values can be opened.
User Users may conduct additional tests in fully automatic mode.
2 Log into the system as a “user” (see chapter 0, page 118). Wear safety helmet, protective suit, eye protection, protective
gloves and safety boots!
o The operator is registered in the system as a user (1) and he
can start operating the furnace system.
1 Registered Level
• Only fill the melting crucible up to the default filling height. Use a
gauge to check the correct height
• Take care that you have still sufficient space between the highest
pieces of silicon and the top part of chamber when the top part of
chamber is closed
• Observe the maximum filling weight during charging
• Avoid any contamination of the crucible from acids and bases.
Hence, take measures of all given actions during crucible
handling and charging
Please observe the following points: 3 Load the melting crucible with caution
• Only trained personnel is allowed to load the melting crucible o Make sure the melting crucible is not damaged during loading
• Overloading the melting crucible has to be approved by of the o Only fill the melting crucible up to the default filling height. Use a
plants owner/operator gauge to check the correct height
• Only use the melting crucible in combination with a suitable o Take care that you have still sufficient space between the upper
support crucible edge of silicon and the top part of chamber when the top part of
chamber is closed
• Do not use unqualified or damaged crucibles
o Only use silicon nitride coated crucibles
• Use a gauge to check the filling height
o Recommended crucibles by centrotherm SiTec GmbH:
o Ceradyne 36040 C, “RTU” ready to use
1 Check the specified melting crucible for damage
o Vesuvius X712880, “RTU” ready to use
o Do not use damaged melting crucibles
1 Melting crucible 1 3
2 Place the melting crucible on the bottom plate of the support 2 Cropped bricks
1 Melting crucible 3 Chunks
2
2 Bottom plate
8.2 Open Chamber before Process 8.3 Loading the Crucible into the Bottom Part of
1 To open the chamber the operator has to activate the two-hand Chamber
control unit. The operator has to put the “Drive demand" at the Necessary Conditions • The top part of chamber is in parking position.
control cabinet to position “1”. The audio-visual signal confirms the
activation of the control unit • Prior to first start, after maintenance or exchange of inner parts
make sure that the equipment has no leakage and burn out /
2 The operator has to betaken to the platform where the two-hand cleaning procedure was done. The inner process chamber has to
control unit is placed on its parking rack be free of any particles .
3 Put the “Open/close toggle switch” at the two-hand control to
position “Open”
Please observe the following points:
4 The operator has to hold the two-hand buttons pushed to move
• Only use specified lifting gear
the carriage to position 1 of the opening process. When the
carriage has reached position 1, the LED 2 ("End position furnace" • The crane used must be designed for smooth motion, particularly
indicator light) gets on for smooth starting and stopping.
5 The operator has to release the action, the two hand buttons. LED • Travel the last 100 mm before the support crucible touches the
2 gets off bottom part of chamber at a reduced speed of 20 mm/s maximum.
6 The operator has to hold the two-hand buttons pushed again to
start the lowering process. When the carriage has reached 1 Use the crane to move the handling tool the supply area for the
position 2, the LED 2 ("End position furnace" indicator light) gets charged crucibles. The operator has to position the handling tool
on above the crucible.
7 The operator has to release the action, the two hand buttons. LED 1 Handling tool
2 gets off
2 Brackets
8 The operator has to hold the two-hand buttons pushed for a thirt
time to move the carriage to the final position of the opening
process. When the carriage has reached the end position, LED 1
("End position assembly" indicator light) gets on
9 The operator has to release the action, the two hand buttons. LED
1 gets off
10 The operator has to put the two-hand control back onto the
parking position of the rack
11 The operator has to betaken to the ground floor. At the cabinet the
operator has to put the "Drive demand" key switch back to position 1
“0”
2
12 Beware of hot quartz and silicon parts sprinkling around in case of
ingot or crucible breaking.
13 Move down the top part of chamber into its parking position. The Figure 43: Handling tool
chamber is open. The crucible and ingot can be removed now.
2 By using the special alignment gauge the operator can align the
14 Do not keep the chamber open for a long time and close it crucible into a clear position in the handling tool. Turn the brackets
immediately as soon as possible. of the lifting device into the opening of the bottom plate by using
15 Avoid dust, high humidity and condensing air condition while the the hand-wheel.
chamber is open.
Cooling Water The cooling water supply is equipped with two redundant filters. The
1 operator can switch between both filters. This safety feature secures
the cooling water supply at any time.
1 Make sure, the manual ball valve of cooling water reflow side is
2 open.
2 Make sure, the manual ball valve of cooling water supply side is
open.
3 Check pressures before and after filters F204 and F205:
Pressure at the pressure gauge drain side must be 5 bar. If
pressure difference supply and drain side is >1 bar, the filter has
Figure 45: Lowering the charged crucible into the hot zone to be cleaned or flushed.
6 When the charged crucible is placed on the bottom plate of the 1 Pressure gauge drain
furnace, the operator has to use the hand-wheel again. By turning side of the filter 1
the brackets into position “open” the handling tool gets free. Make
2 Manual ball valve for
sure that brackets are moved out of the openings completely. 10
cooling water reflow 2
7 Use the crane to lift the handling tool out of the guide sleeves and (V201)
place it at its parking position.
3 Manual ball valve for
cooling water reflow
(V203) 9
4 Pressure gauge drain 3
side of the filter
5 Filter F205
8
6 Manual ball valve for
cooling water supply 4
(V202) 7
7 Pressure gauge feed
side of the filter
6
8 Filter F204
5
9 Manual ball valve for
cooling water supply
(V200)
10 Pressure gauge feed Figure 46: Cooling water supply
side of the filter
4 The operator has to check flow rate at Flow meter F101: flow must Compressed Air To ensure the operation of the SiHIDry-pump the operator has to
3
be between 240 and 280 m /h check the pressure of compressed air. Default value for the air
5 The operator has to check pressure at gauge P303: pressure must pressure has to be at 7 bar. The operator can adjust the pressure
be between 1.5 and 2.5 bar. Tuning of the pressure can be done value at the pressure reducer that is located next to the interface to
the facility.
at valve V303.
Argon Check Argon pressure at gauge P306. Pressure must be at 5 bar. Set 8.5 Checking Furnace for Any Damage
Argon pressure at valve V305.
Following the media check the operator has to test the furnace system
with respect to water leakage or damaged parts. The operator has to
keep records on the conditions. Furthermore, the operator is
Argon pressure can only be set when the process is running. Hence, responsible to take actions to get the damaged parts repaired.
argon pressure must be controlled on a regular basis. In case of fall or • Damaged or defective parts has to be replaced or repaired by
increase, the Argon flow has to be adjusted. qualified personnel
• Water leakage has to be stop by qualified personnel
• Visual check of the entire system on safety critical conditions
• Listen to abnormal audible indications (e.g. pumps)
1 Flow Meter F751 • Replace broken, loosen or damaged parts
2 Pressure Gauge P305
3 Pressure Reducer V305 All damaged or defect parts must be replaced immediately. Don’t use
the furnace if you are aware of defects and damaged parts at the
4 Pressure Gauge P306 5 1 furnace.
5 Flow Meter F750
• Prior to every motion of the top part of chamber, make sure no 10 Stop pressing both two hand buttons. LED 2 turns off.
person stays in the danger area. 11 The operator has to put the two hand control back on its parking
• Only the operator using the two-hand control is allowed on the position.
platform while the top part of chamber is moving. 12 The operator has to go to the ground floor and has to switch the
• The operator with the two-hand control must be able to "Drive demand" key at the control cabinet to position “0”.
overlook the entire danger zone of movement. 13 The close chamber process is completed.
1 To log into the system the operator has to press the operator 3 Open the process data window by pressing the “Process Data”
button (1). The system login (2) pops up. button (1) on the overview screen.
1 Operator Button
2 System Login 1 Process Data Button
1
2
The operator has to check, if the process status and the program
Figure 52: Recipe with break points status are equal. If so, the operator has to confirm the status.
Molten Silicon For example: The melting breakpoint can be checked on the process
Breakpoints in recipe Breakpoints are defined process events in the process flow. At this side by looking through the inspection glass at the top part of the
point, the operator has to confirm the status of the process. process chamber.
e.g. Breakpoint 1: The feedstock is completely melted The operator can check the status of the silicon by visual inspection.
There is a clear visible indication for molten silicon.
e.g. Breakpoint 2: The melt is completely crystallized
By looking through the inspection glass of the top chamber the
The above screen shot shows such a recipe with two breakpoints. operator has a look onto the silicon.
In case of visible travelling waves at the surface of the feedstock the
material is molten.
7 The operator has to set the process number, the start time for the
run and the Silicon weight of the charged crucible in the recipe.
1 Process number
2 Charged weight 4
1
3 Start time
4 Date 2
5 Date acceptance
Figure 54: Molten Silicon, a look through the inspection glass 6 End date & time 3
If the feedstock is molten, the operator can confirm the status by Process total duration
pressing the confirm button.
The process cycle continues by starting the next step of the recipe. 5 6
CAUTION o Open the menu “Process number” (1) and set the process
The radiation of the Silicon can harm your eyes. number.
o Open “Silicon weight [kg]” menu (2) and set the weight – one
Wear appropriate safety equipment to protect your eyes..
digit after the point - of the Silicon.
o Open the menu “Start date & time” (3).
o The calendar menu (4) opens.
o Select the date and time for the run. Confirm the selection by
pressing “Accept” (5)
o For operators reference, “End date & time” as well as “Process
total duration” (6) are displayed.
8 Followed by the parameter (process number, weight and start If the recipe is without fault, message box “Import into CPU” (2) pops
time) the operator has to start a “Plausibility check” (1). The up.
plausibility check is an interactive safety function. The operator
To proceed in the process flow the operator has to confirm the
gets the information on the process plausibility. Information can be
message by pressing the “OK” button
either the accuracy of the recipe or details on recipe failures in
form of warnings and alarms. 1 “Write into CPU” button
1 Plausibility check 2 Message box
“Import into CPU”
2 Message Box
3 “OK” button
“Warnings and Alarms
3
1
After revision of the recipe the operator has to load the revised recipe
by repeating step 7 and step 8.
After loading the recipe into the CPU, the furnace is ready for the
process. The operator gets additional information on the process step by the
11 The operator has to load the processes window by pressing the “status information” (5) displayed message.
“Processes” button (1) in the menu bar. The status can be the following:
o The processes window opens.
• Pass
• Fail
1 “Processes” button • Finished
7
2 Process step “Information” 1 • Running
box
2
3 Connection arrow By pressing the “Process to continue” button (6) the operator has the
6
4 “Lock” symbol possibility for a stepwise approval the process steps either to verify
3 the process step or, in case of a fixed process interruption, to start a
5 “Status information” on re-entry.
process step
6 “Process to continue” 4
button 5 12 To set the process on the start the operator has to push the
7 “Process start” button "Process start" (7) button.
13 As result of the “Process start” the message box “Process start /
cancel” (1) pops up. The operator has to set the status on “On”.
Therefore, the operator has to push the “Process “start / cancel”
button (2) distinguishable by the three dots. A further submenu,
the extended process window with message box start/cancel,
opens.
14 The operator has to set the status on “On” by pressing the “Status A third indication for the successful start of the process is the progress
On” button (1) in the command section of the message box. The bar “Remaining” (4). The following information gets visible:
selection has to be confirmed by pressing the “Ok” button (2) in
the execution section of the message box. • Colour of the box changes to green
• The remaining time of the process step
o The process starts.
• The shifting of the bar versus time. The shorter the remaining
process step time the shorter the length of the bar.
1 “Status On” button 1 “Process stop” button
2
2 Confirmation “Ok” button 3 2 Process step “Information”
box 2 3
3 “Close” button
3 “Status information” on the 4
process step
4 Progress bar “Remaining” 5
1 5 “Lock” symbol
6
6 Submenu “Not worked
through” conditions”
7 “Close” button 6
8 Process step “VII Process
2 terminated”
Figure 60: Extended process window with message box Figure 61: Running process and pop-up with start conditions
start/cancel
If a “Lock” symbol (5) is attached to the connection arrow the step
below cannot be started by the program sequence. Hence, the
operator has to debug the faulty conditions. Therefore, the operator
15 The operator has to close the message box pushing the “Close” has to open the sub-menu “Not worked through” conditions (6) by
button (3) distinguishable by the x. pressing the “Lock” symbol. To highlight the faulty information the
faults are marked red.
After the operator has started the process the message of the After debugging the faulty conditions, the operator has to close the
“Process start” button changes both the message “Process stop” (1) message box by pressing the “Close” button (7), distinguishable by
and the colour “green”. By pressing the button, the operator could stop the x.
the process. If the process has successfully reached and finished process step
The successful start of the process gets visible by the colour change number VII the information box “VII Process terminated” (8) changes
of the “Information” box (2) of process step number #1. The colour its colour to green.
changes to green. In addition to the change of box colour the “Status
information” (3) changes to running. If the operator cannot debug the faulty conditions, the operator has to
inform the administrator.
Furnace Approvals After the set up of the furnace the following approval status needs to
be confirmed:
Final Approvals After all process steps have been carried out successfully, the final
No. Test Description approval procedure starts. The test proceeding ensures the thightness
of the chamber during the process.
1 Sensor Functionality tests of all sensors
approval e.g. safe test probes, thermo couples,
pyrometers. No Test Description
2 Cooling Overall testing of functionality and pressure 1 Evacuation The chamber has to be evacuated to a
Circuit conditions of the cooling circuit approval minimum value, the set point pressure
approval
2 Leak Test The leak-tightness of the process chamber
3 Evacuation The chamber has to be evacuated to a approval has to be approved by a leak test. The drop
approval minimum value, the set point pressure of pressure has to stay below the set point
value
4 Leak Test The leak-tightness of the process chamber
approval has to be approved by a leak test. The drop of
pressure has to stay below the set point value End of Process The successful completion of the final approvals marks the end of the
5 process. The camber can be flooded.
Heater Test Functionality test of the two independent
approval heating circuits. The test approves both, the
system function and the inexistence of short-
circuits
6 Process Only if all test approvals show the status “Ok”
Release the process can be started. In case of any
approval failure the operator has either to debug the
failure or repeat the approval proceeding.
Process Steps The preheating of the furnace system excluded the operator can set
40 process steps within 7 main process steps. The 7 main process
steps are the following:
No Process step Description
1 Heat-up Controlled heating to remove the humidity
and the low temperature chemical bound
Oxygen in the process chamber
2 Melting Controlled heating to change the state of
the Silicon, from solid to liquid
3 Operator Interactive step. The operator has to
Intervention confirm the current status and to clear the
next process step
4 Crystallization Controlled cooling to change the state of
the Silicon, from liquid to solid
5 Operator Interactive step. The operator has to
Intervention confirm the current status and to clear the
next process step
6 Tempering Controlled cooling to reduce the stress in
the solid and hence, crystallized Silicon.
7 Cooling Controlled cooling step to reduce the
temperature in the camber below the critical
value to open the chamber
8.8 Opening of the Furnace after the Process 8.9 Unloading of the Furnace
To unload the furnace the operator has to open the process chamber.
Opening chamber sequence The operator has to proceed as follows:
1 The operator has to activate the two hand control. Therefore, he DANGER All part of the furnace as well as the crystallized ingot including
has to switch the "Drive demand" key at the control cabinet to both crucibles might have a temperature above 50 °C.
position “1”. If the two hand control is active an audio visual Risk of burns!
indication – acoustic signal and yellow flashing light – shows the
status. Wear appropriate safety equipment!
2 The operator has to go on the platform and take the two hand
control out of its parking position. Necessary conditions • The crystallization process is finished.
3 To start the opening sequence the operator has to switch the • The top part of chamber is moved to the parking position.
“Open/close toggle switch” at the two hand control to position
“Open”. • The main power switch of the furnace is switched off.
4 The operator has to hold the two hand buttons pressed to move 1 The operator has to wear the appropriate safety equipment.
the carriage towards the first position of the opening process.
When the carriage has reached the first position, LED 2 ("End 2 To unload the crucible the operator has to move the handling tool
position furnace" indicator light) lights up. above the furnace
5 Stop pressing both two hand buttons. LED 2 turns off. 3 During the lowering the operator has to take care that the guiding
pins fits into the guiding sleeves. Furthermore, the operator has to
6 To move the carriage towards the parking position the operator take care that the adjustment rings (3) are positioned at the
has to hold both two hand buttons pressed again. When the correct level.
carriage has reached the second position, LED 2 ("End position
furnace" indicator light) lights up.
7 Stop pressing both two hand buttons. LED 2 turns off.
8 The operator has to hold both two hand buttons pressed again, to Wear appropriate safety equipment.
move the carriage down to the end position of the opening Take care not to damage the graphite parts of the hot zone
process. When the carriage has reached the end position, LED 1
("End position assembly" indicator light) lights up.
9 Stop pressing both two hand buttons. LED 1 turns off.
4 The operator has to lower the handling tool carefully into the hot
10 The operator has to put the two hand control back on its parking zone so that the guiding pins fit into the guide sleeves.
position.
1 Guiding Pin
11 The operator has to wear the appropriate safety equipment as hot
and sharp particles could work loose. 2 Guide Sleeve
3 Ring to adjust the vertical
positioning
CAUTION
Caution, the loosening of hot and sharp particles from either the ingot
or the crucible is possible. 3
Wear appropriate safety equipment.
12 The operator has to go down to the ground floor and has to switch
the "Drive demand" key at the control cabinet to position “0”. 1
13 The opened chamber is now ready for the unloading step
2
5 When the handling tool is positioned, the operator has to use the 8.10.2 Switch off during the Process
hand wheel to turn the brackets to position “Close”. To avoid
In case of a switch off during the process critical situations might
damaging of the graphite the operator has to make sure that the
happen.
brackets fits into the openings.
To avoid these situations and to safeguard a controlled shut down of
6 By the handling tool, the operator has to lift the bottom plate with
the system the operator has to use the “Emergency Stop”
the crucibles and the ingot out of the furnace.
7 The operator has to move the goods to the assembly area and
place them carefully onto the assembly carriage.
CAUTION Only use the Emergency-Stop button to switch of the furnace
during a process run!
If the furnace is switched off during process, the following situations
can happen:
o Process control failure
o Safety equipment failure
o Voltage supply failure
o Cooling water supply failure
o Process gas supply failure.
9 User Interface of the Control Panel 9.1 Structure of the User Interface Window
9.1.1 Areas of the user interface window
CAUTION Manual interventions are not checked on plausibility! The furnace system provides a user interface window for an
interactive-dialog between the operator and the process flow.
Not all functions are locked against faulty inputs.
This user interface window is segmented into four main areas:
Faulty inputs can result into critical situations.
• Area 1: Overview area
• Area 2: Work area
• Area 3: Main Process Value Area
WARNING Risk of damage to the furnace! • Area 4: Button area
• "Manual" operating mode is only allowed during maintenance and
start-up. 1 Overview Area
• "Manual" operating mode is not allowed for standard processes. 2 Work Area 1
• Only qualified and instructed experts may run the furnace in 3 Main Process Value Area
the "Manual" operating mode.
4 Button Area
3
4
Figure 64: Areas of user interface
Main Process Value Area The main process value area displays the following detailed
information:
9.1.4 Overview area
• Status of the audio visual signal unit
• Process name The overview area is segmented by the following functionality:
• Recipe step number • Selection buttons
• Remaining time bar function and time display • Message box
• Temperatures • Shortcut Icons
• Pressures By using the functionality of the overview area the operator can
navigate through the information system of the furnace system.
• Cooling energy
Furthermore, he can trace back into the process history to analyze
Button Area The button area supports the operator by navigating through the parameters or look into the future to plan maintenance or service
windows. The functionality of the icons is comparable to the windows work.
icons. The operator handle the operational procedures like saving or
loading and displaying or hiding. Navigation The operator can navigate through the information system by
selecting the corresponding “Selection Button” (1). The information on
9.1.3 Cursor shapes during the process the selected button is displayed in the work area.
Message The operator gets the breaking news on the process by the written
Shape of the cursor The operator can use the cursor to select command buttons or icons
in the following three areas: information in the “Message box” (2).
If you click on an area selection button, the corresponding process
picture of the highest picture hierarchy level is displayed in the work
• Area 1: Overview area area.
• Area 2: Work area
• Area 4: Button area 1 Selection button
2 Message box 3 2
1
The operator has to move the cursor onto the command button or 3 Shortcut icons
icon. To activate the corresponding function the operator has to select Figure 67: Overview area
the command button or icon by pressing the left mouse button.
The operator can get control on the function if the cursor changes its
shape from a standard arrow shape into the control cursor shape.
Icons The "Shortcut icons" (3) can be clusters into three different classes:
• Message system
Figure 65: Control cursor • Graphic system
• System function
The functionality and the classification of the selectable icons are the
The operator can use the cursor in a input box, if the cursor changes following:
its shape into the text cursor shape.
The operator cannot get control on the function or on the input box if
the shape of the cursor does not change.
In case of a message on the process the icon pops up The operator can select between two predefined button sets to control
next to the linked selection button. The colours give an the furnace system.
indication on the status of the message: Set 1 is obligatory when the operator starts the process. By pressing
A: Excess of the alarm limit the operator buttons (green triangle) the operator can switching back
W: Excess of the warning limit Graphic system and force between the two sets
S Process control error
O Operator prompt 1
X One or more messages are locked 1 Operator button
Pressing the icon generates a screen shot. The screen Figure 69: Button Set 1 (top)
shot is saved as temporary file and printed out at the System function
connected printer.
Figure 70: Button Set 2 (bottom)
Pressing the icon displays the "System Log in". The
operator can log in or log out to the various levels by System function
selecting the level followed by the password
Button colour scheme Buttons can be either active or blocked.
By the colour index the operator can direct read the status.
9.1.5 Work area • Gray:
The operator can get in-depth information by the system navigation The button is blocked. Either as the permission of the level is
Display of process pictures
system. By the selection of the information of interest, either a flow missing or as the related process picture I not active
chart a diagram a list of data or a combination of all pops up in the • Coloured:
work area. The button is active and hence, can be used by the operator
The operator has various possibilities to load the process picture of
the information of interest into the work area. For example:
Switching between the button sets By pressing the switch button(s) (green triangle) the operator can
• Selection button in the overview area switching back and force between the two sets.
• Shortcut icon in the overview area
• Icons in the button area
Note on the operator buttons To get the information on the function of the operator button move the
cursor onto the button.
9.1.6 Main process value area
If the operator clicks on the button the corresponding action starts.
The main process value area is divided into 2 segments. The
summary box (1) and the audio visual signal unit (2), (3).
The summary box (1) provides all major information on the process. Button set 1 Table 9-2 gives an explanation of the icon and defines the
He temperatures, the cooling energy the pressures as well as the functionality of the various buttons of button set 1 and set 2.
remaining time of the process step.
The audio visual signal (2), (3) unit of the main process value area is a
mirror image to the signal unit at the furnace system. Controlled by the
software the indication is the same as at the furnace.
3 2
1 Summary box
2 Visual signal unit Figure 68: Main process value area 1
3 Audio signal unit
Go up
Displays the process picture above to the current process picture 9.2 Start Screen
Go down Besides the overview area and the button area the Start screen shows
Displays the process picture below to the current process picture the logo of centrothem and the version of installed software (1).
Go right
Displays the process picture right to the current process picture 1 Overview area
2 Button area
Back
Displays the previous process picture 3 Centrotherm logo
1
Forward 3
Displays the next process picture
Load
Loads a saved screen composition
Save
Saves a screen composition
Delete
Deletes a screen composition
Information 2
Opens a dialog box that provides information on the current process picture
9.3 Log In
Pressing the “Operator button” (1), the operator get access to the 9.4 “Overview” function
“Login” message box (2). Pressing the “Overview” button (A) in the overview area, the operator
The operator can select his permission level by writing the relevant gets access to the “Overview window” in the work area.
level name in the login line. Writing the password in the operator gets The overview function displays the piping and instrumentation diagram
access to the system permission level of choice. (PID) in the work area.
1 Operator button
2 “Login” message box
1
1 14
A
2 3
15
6
Table 9-3: Login
8
Pos. Control Element Explanation
1 Operator button Operator button displays the login permission level 16
Clicking on the button opens the “Login” message box
2 “Login” message box Gives access to the system permission level of choice 19 18 20 17 13 12 11 10 2
Login: Type user name in → linked to the system permission
Figure 73: Overview function – PID diagram
Password: Type password in
OK: Confirmation of the input data, get access to the system
Cancel: Cancel input data Table 9-4: Overview function - PID diagram
Logout: Logout of the system
Locking of all operator controls Pos. Control Element Explanation / functionality
Closing of process mode
1 V-5 Cooling vent
Switch to guide the gas flow through the heat exchanger
2 V-6 Chamber vent
Control valve for process pressure control
3 Roots pump value box Recording roots pump values
Switch between automatic and manual mode
9
5
10
11
12
5 Controller difference Delta of vertical (angular) displacement of axis • The visualisation of the position of the temperature sensors
Displays the displacement of the two axis • The current values
• The redundancy and verification of the measurement results
6 Drive Drive parameter display
Displays current speed and position of the movement
7 Hub Drive Parameter setting
“Normal” furnace opening Displays the valid end positions for the furnace opening and closing A
process
2
8 Hub Drive Parameter setting
“Hot Zone removing” Displays the valid end positions for the maintenance work on the hot
zone
9 Step sequence opening Process flow chart 3
Displays both, the process flow and the current valid sequence of
the process (box change to orange colour) 1 4
10 Moving menu Selection menu
Menu to select the necessary process “Closing” or “Opening”
5
11 Message box Message display
Displays both the current message(s) as well as the status of each
message (colour indication)
12 Sensors Status of limit switch overview
Displays the current status of each limit switch by its colouring
Green: End position reached
Grey: End position not reached
4 13
5 14
15
6
16
7 7
17
8
18
3
19
20
2
3
2 4
4
7
5 8
4 13
5 14
15
EMERGENCY OFF In case of an EMERGENCY STOPP, the signal lamp "Acknowledge The furnace system is ready for operation again.
collective default / default" lights up on the control panel.
Display on the control panel The following table lists the basic structure on how to proceed in case
of defaults and warning.
Table 10-1: Default displays on the control panel – measures (PLC collective messages)
3 4 3
Indicated inspection intervals are based on empirical values of the
Figure 90: Maintenance access points on the front rack
manufacturer, proper handling of the processes and the use of the
specified auxiliary and feedstock materials. Minor changes of the set-
11.1.4 System Parts Requiring Recording
up may influence the intervals.
In accordance with Industrial Safety Ordinance (BetrSichV), systems Frequently record the lifetime of the furnace components according to
and their parts requiring recording must be inspected on regular your process set-up and adjust inspection intervals to the furnace
intervals. The inspection has to be done by an approved inspection conditions.
authority to ensure that they are in perfect working order as regards
operating safety. Centrotherm SiTec GmbH recommend to use a maintenance logbook
Safety accessories (pressure With regard to a safety function the following accessories parts must
limitation valves) be proofed according to the Pressure Equipment Directive.
The following abbreviations are used in the maintenance list: Table 11-3: Maintenance Table
A After maintenance or retrofitting Entire chamber Perform visual inspection of Check for leaks and visible
tensioning elements and all damages.
I Prior to integration into the furnace connection points on leaks M IM
All damages have to
C Included in commissioning by manufacturer remedied immediately
The following abbreviations are used in the "By" column: Check gas filling and Performed with a test and
suction pressure (negative ¼Y EP filling device
IP Instructed person pressure)
EP Expert Check if the chamber jacket
is free from cracks, damage
ESP Electrically skilled person
and leaks
Chamber jacket Visual inspection P IP
IM Industrial mechanic In case of any damage to the
chamber jacket, it has to be
repaired immediately
Top part and bottom part of Chamber functions:
chamber Check pyrometer.
Temperature measurement
¼Y If necessary, adjust pressure
Check sealing surface on
by the associated pressure
flange
gauge.
Heat exchanger connection
Clean the inspection glasses
Inspection glasses Cleaning ½Y IP
with isopropanol.
Cleaning ½Y IP
Chamber interior
Visual inspection P IP
Hot zone Clean foundation plate daily
before the start of work and
D EP
check the bearing surface
for the crucible for damage.
Check protective walls. M IP
Check bearing surfaces for
M IP
wear and tear.
Component Maintenance Activity Interval By Further Information Component Maintenance Activity Interval By Further Information
Check sealing surfaces for Check in perfect working
M IP 4Y ESP
wear and tear. order.
Hot zone integrated safety Repeated inspection as per
Visual inspection ½Y IP
barrier VDE 0113 / DIN EN 60204 4Y ESP
Pt. 19 / BGV A2
Visual inspection IP
melting crucible I Main switch Functional test Y, A, C ESP
Measurement IM
Emergency stop system Functional test A, C ESP
Visual inspection
support crucible I, P IP Visual inspection ½ Y, A
Cleaning Protective circuit ESP
Measurement C
Cooling water components Clean contaminated parts Proceeding like this,
Wipe up spilt water with a D IP improves detection of Covers of the power Cleaning
leakage ½Y ESP
cloth immediately supplies Visual inspection
Cooling water lines, cooling Inspect all cables, hoses Cleaning ½Y
water hoses and couplings for leaks and Warning devices ESP
externally detectable Functional test C, P
damage. Cleaning ½Y
W IP Warning and information
Have all damage remedied IP
labels and inscriptions Visual inspection W, P
immediately.
Spurting water can result in Safety valve cooling circuit Functional test M EP See supplier documentation.
injuries.
Cleaning ½Y
Replace water hoses 3Y IM
Visual inspection Y
Cooling water connection Electrical components ESP
Discharge collected water Functional test Y, A, C
under operator terminal and M EP
cooling water supply Clean surfaces
Measurement C, 4 Y
Cooling water Measurement Y EP Visual inspection ½Y
High-voltage lines ESP
Filter device Ball valves on the filters: Functional test C
Check function of the valves W EP Cleaning M
and smoothness of Measuring equipment EP
operation of the ball valves. Functional test Y, A
Filter screens Cleaning M IP Visual inspection W
Control elements IP
Water filter Replace filter candles Increased flow resistance Functional test M
cooling filter circuit and results in reduced cooling
supply power Control panel Clean operator panel with a
½Y M IP
damp cloth (water only)
(or as IP The exchange cycle must be
required) determined according to the Check function of signal If necessary, have the faulty
contamination level of the lamps lamps replaced
M ESP
cooling water Replacement only by
Electrical equipment (and Check function of all Check whether connection electrician!
operating material) electrical contacts. cables and electrical wires Cleaning P
are damaged (cracks, Guide rail IP
½Y abrasion marks, cuts, etc.) Visual inspection ½Y
(or as ESP Check filter mats in fans Cleaning P
required) Guide rods of the handling
IP
Check connectors are tool Visual inspection ½Y
fastened securely
Replace defective parts Cleaning and lubrication of
Screw jack Y EP See supplier documentation.
screw
Lubrication of jack at nipple Y
Component Maintenance Activity Interval By Further Information Component Maintenance Activity Interval By Further Information
Removal, cleaning and re- Check geared motor for
5J
filling jack with grease unusual noise, vibration and D
changes
Visual inspection for wear Y
Check of housing
Argon pressure pumps Repeated tests EP Installation site M
temperature
Argon piping Functional test Y EP
Check of oil level M
Graphite and CFC Check of oil level sensor M
Visual inspection I, P IP
components EP
Check of oil quality ½Y
Current feed through Visual inspection Y, I, C ESP
Gearbox First oil change after See supplier documentation.
C, A, –
Measurement ESP commissioning
½Y
Further oil changes 2J
Replacement of bottom
Y EP
Heaters heater Check of gearbox for leaks M
Replacement of side heater ½Y EP
Cleaning of gearbox vent ½Y
Replacement of both
2J EP Cleaning ½Y
heaters
Check of level in cooling Check of slipping clutch 500 h, Y
–
jacket
Check of clutch 3M
Vacuum pump check of sieve for soiling – EP See supplier documentation.
Complete check of geared
Y
cleaning of delivery motor
– EP
chamber
after 3 h;
Check of mounting screws
Visual inspection Y M
Gearbox See supplier documentation.
Transformer Cleaning Y ESP See supplier documentation. Change of roller bearing
2J
grease
Retightening of fittings Y
Check of rubber buffer of
Initial inspection ½Y ½Y
stator
Lubricate bearings 5Y Leak test –
Heat exchanger EP See supplier documentation.
Cleaning – Functional test –
Three-phase motors EP See supplier documentation.
Main inspection 2J Check of heat exchanger
Draining of condensed for ambient air and cleaning 3M
water if necessary
Check of condensed water
3M
Control cabinet cooler discharge EP See supplier documentation.
Check of fans for possible
overheating or excessive Y
vibration
Cleaning –
Pyrometer Cleaning of lens – EP See supplier documentation.
11.3.2 Checking the Function of the Main Switch Cleaning Clean the outside surfaces of the signal towers.
Switch on the main switch. Check if the furnace is supplied by power. 11.3.7 Maintaining Warning Labels and Inscriptions
Switch off the main switch. Check if the furnace is completely
Visual Inspection Check all warning and information labels as well as all inscriptions of
disconnected to power supply.
the control elements for legibility and completeness.
11.3.3 Checking the Function of the Emergency Stop System Have illegible and incomplete labels or inscriptions replaced.
Check EMERGENCY OFF switch and EMERGENCY OFF devices for Cleaning Clean all warning and information labels as well as all inscriptions with
trouble-free function. a damp cloth.
Perform the following steps: 11.3.8 Maintaining Electrical Components
1 Put the furnace into service.
Functional Test Check all electrical components for proper function.
2 Push the emergency stop buttons.
In case an electrical component does not work, replace it.
o Check if all hazardous movements have been stopped safely
Visual Inspection Carry out the following checks for all electrical components:
o Check if the heaters have been switched off
• Make sure the electrical equipment confirms with the technical
o Check if voltage supply of the drives was switched off
documentation.
o Check if the argon supply valves have been closed by the
• Check all connections for tight fit.
control
o If one of the above points does not apply, take the furnace out • Fix all screws and terminals.
of operation and have the emergency stop system repaired • Check wires for tight fit.
immediately • Check wirings for cracks, abrasion or erosion.
3 Repeat this check for all emergency stop buttons on the furnace • Check covers and insulations for damage.
Immediately replace damaged electrical components.
11.3.4 Maintaining the Protective Circuit
Measurement Carry out the following measurements for all electrical components:
Visual Inspection Check all connections of the protective circuit in the control cabinet
and on the furnace for tight connection. If required, fix the • Check the protective circuit on continuous connection.
connections. • Check insulation resistance.
Measurement Check the protective circuit for continuous connection. • Check voltages.
In case of interruptions, safeguard a continuous connection. • Check protection against residual voltages.
Cleaning Visual Inspection Check the guide rods of the handling tool for damage such as cracks
or fatigue.
Engage expert companies or especially trained personnel when Should the guide rods of the handling tool be damaged, have them
cleaning inside electrical components is to be carried out (e.g. of fans repaired or replaced.
of electric motors, control cabinet interior). Cleaning Clean the guide rods of the handling tool with a dry cloth.
Should any sheathing be damaged, replace the related cable. Should the melting crucible be damaged, replace it.
Functional Test Check the contact points for tight installation. Measurement Prior to integration into the furnace, carry out an inspection of each
melting crucible (100-% inspection). Check and record the
If required, fix the contact points. dimensional consistency of the melting crucibles.
Functional Test Check all measuring equipment for proper function according to the • width: 880 + 2 mm x 880 + 2 mm
component operation manuals. • height: 420 mm
If required, readjust, maintain or replace the equipment.
11.3.15 Inspecting the Support Crucible
Visual Inspection Carry out a visual inspection of the support crucible. Check if the
Record the results of the functional tests support crucible is free from cracks and damage.
Centrotherm SiTec GmbH recommends to take measures to detect Should the support crucible be damaged, replace it.
trends to adjust inspection intervals.
Cleaning Clean the underside of the crucible and check for damage to the
Should a sensor indicate unrealistic values, check its function and bearing surface.
replace it if required. Check sealing surface on the flange for correct positioning and
damage.
Clean hot zone components daily before the start of work and check
Cleaning Clean the quartz glasses of the pyrometers with iospropanol.
the bearing surface for the crucible for damage.
11.3.11 Maintaining Control Elements
11.3.16 Inspecting the Hot Zone Integrated Safety Barrier
Functional Test Test the function of all control elements.
Visual Inspection Carry out a visual inspection of the hot zone integrated safety barrier.
Should any control element not work, have it replaced by an Check if the hot zone integrated safety barrier is free from cracks and
electrically skilled person. damage.
Visual Inspection Check all control elements on damage and signs of wear. Should the hot zone integrated safety barrier be damaged, have it
Should any control element be damaged, have it replaced by an repaired or replaced.
electrically skilled person. Cleaning Clean hot zone components daily before the start of work and check
the bearing surface for the crucible for damage.
11.3.12 Maintaining Guide Rails
11.3.17 Inspecting Graphite and CFC Components
Visual Inspection Check the guide rails for damage such as cracks or fatigue.
Should the guide rails be damaged, have them repaired or replaced. Check the graphite and CFC components on damage such as cracks
or aging.
Cleaning Clean the running surfaces of the guide rail of the carriage with a dry
cloth. Should the graphite or CFC components be damaged, have them
repaired or replaced.
11.3.18 Inspecting the Current Feed Through 11.3.23 Cleaning the Touch Panel
After every heater change, however no later than within the indicated The touch panel has a cleaning mode you can use for cleaning.
inspection intervals, carry out an inspection of the clamped terminal With the "Cleaning picture" button, switch to that mode before
connection between current feed through and electrode. Check if the cleaning the touch panel with a dry cloth. Proceeding like mentioned
insulating washer between current feed through and electrode is
you avoid that any settings can be accidentally changed.
intact.
Only use rinsing agents or foaming monitor cleaners for cleaning.
Should the insulating washer be damaged, replace it immediately.
C. Quartz crucible failure: 1 In any case contact the responsible supervisor and line manager D. Argon flow failure: 1 In case of a failure in the Argon supply for more than 3 minutes,
C-I. Determination of molten immediately. the operator has to close the valve for top axial argon flow
silicon leakage: 2 Periodic leakage of molten silicon may occur at the beginning of 2 The personnel have to detect the reason of Argon flow failure and
the silicon melting – 6 to 9 hours after the process start. solve the problem as quick as possible.
Most probable reason may be the usage of a damage crucible. 3 In case the Argon flow has been repaired the operator has to open
3 Intensive leakage of molten silicon may occur at the ending of the the valve for top axial argon flow very slowly. The increase should
silicon melting process – 10 to 12 hours after the process start. be done stepwise up to 20–30 l/min. One step per minute by
The situation may happen as a consequence of an emergency setting 2 to 3 l/min per step.
situation. 4 The second operator should control the cooling water temperature
4 Leakage of molten silicon during crystallization is even less especially in the heat exchanger and bottom part of chamber in
probable as the bottom of the crucible may be covered by solid order to determine silicon leakage.
silicon. The situation may happen as a consequence of an 5 Contact the responsible supervisor and line manager immediately.
emergency situation.
5 Low intensive periodical leakage during melting can be
determined by periodical decreasing of the bottom heater power
E. Out of Control: Most critical situation may happen in case of a strong software or
below the limits. In case, the heart power may fall.
hardware failure.
6 Intensive leakage during melting can be determined by a sharp
1 If the process gets out of control the operator has to switch off the
increasing of cooling water temperature, especially in the bottom
power by pressing the Emergency Stop button
cooling cycle. In case, the heart power may fall.
2 All personnel have to leave the building immediately. Stay out of
7 Intensive leakage during crystallization can be determined by
the building for a minimum of 3 to 6 hours. Time depends on the
sharp increasing of cooling water temperature, especially in the
process step.
bottom cooling cycle. In case, the heart power may fall.
3 Contact the supervisor and the line manager immediately.
C-II. Operators activity to 1 In any case contact the responsible supervisor and line manager
minimize damages: immediately.
2 During silicon charge melting – 6 to 12 hours after the process
start – the shift operators has to control bottom heater power
every 10 minutes.
3 Alarms get active on sharp increasing of cooling water
temperature in the heat exchanger and bottom part of chamber.
For example in case of a silicon leakage.
4 In case the bottom heater power has 2 times dropped below 50
kW during the melting process – 6 to 9 hours after the process
start - the operator has to switch the process to the first cooling
step.
5 In case the bottom heater power drops at the ending of melting
process – 10 to 12 hours after the process start – the operator
has to switch the process to the first crystallization step.
6 The operator has to control cooling water temperature during
crystallization in the heat exchanger. In case of an increase above
70 °C the operator has to switch the process to the first cooling
step.
7 In case of uncontrollable situations, the operator standing at the
control unit has to give command to evacuate the building