FLUIDWELL

GENERAL
MODBUS COMMUNICATION
PROTOCOL

PROG
1 2 3 4 5 START
ENTER

6 7 8 9 0 HOLD RESET
RATE TOTAL COUNT PRINT
Page 2

SAFETY RULES AND PRECAUTIONARY MEASURES

Warning: Any responsibility is lapsed if the instructions and procedures as described in this
manual are not followed.

LIFE SUPPORT APPLICATIONS:


The Fluidwell products are not designed for use in life support appliances, devices, or systems
where malfunction of the product can reasonably be expected to result in a personal injury.
Customers using or selling these products for use in such applications do so at their own risk and
agree to fully indemnify the manufacturer and supplier for any damages resulting from such
improper use or sale.

Manual : Modbus_Protocol_v1303
© Copyright 2015 : Fluidwell bv - The Netherlands.

Information in this manual is subject to change without prior notice. The


manufacturer is not responsible for mistakes in this material or for incidental
damage caused as a direct or indirect result of the delivery, performance or
use of this material.

© All rights reserved. No parts of this publication may be reproduced or used


in any form or by any means without written permission of your supplier.

Modbus_Protocol_v1303
Page 3

CONTENTS

Safety rules and precautionary measures............................................................................................. 2


Contents ............................................................................................................................................... 3
1. Introduction ............................................................................................................................ 4
1.1. General ..................................................................................................................... 4
1.2 Design choices in perspective to MODBUS specification......................................... 4
2. Ascii record structure ............................................................................................................. 5
2.1. General ..................................................................................................................... 5
2.2. Lrc - checksum .......................................................................................................... 5
3. Rtu record structure ............................................................................................................... 6
3.1. General ..................................................................................................................... 6
3.2. Crc-error check ......................................................................................................... 7
4. Function codes ....................................................................................................................... 8
4.1. General ..................................................................................................................... 8
5. Explanation function codes .................................................................................................... 9
5.1. General ..................................................................................................................... 9
5.2. Read table data ......................................................................................................... 9
5.3. Write table data ....................................................................................................... 10
5.4 Error response codes .............................................................................................. 11
6. Standard begin-table fluidwell products ............................................................................... 13
6.1. General ................................................................................................................... 13
6.2. Indexed variables .................................................................................................... 15
7. General remarks .................................................................................................................. 16
7.1. General ................................................................................................................... 16
INDEX ............................................................................................................................................. 17
Notes ............................................................................................................................................. 18
Notes ............................................................................................................................................. 19

Modbus_Protocol_v1303
Page 4

1. INTRODUCTION
1.1. GENERAL

Fluidwell's communication protocol is compatible with MODBUS, used for Modicon Plc's e.g.. This
protocol is described in "Protocol Reference Guide" (Modicon doc-nr. PI-MBUS-300 rev. C).

Fluidwell supports both modes of the above mentioned protocol: ASCII-mode and RTU-mode.
These modes are described in chapter 2. and chapter 3. The selection between both modes is done
at SETUP-level or Parameter-level (300-series), just as setting the baud-rate, bus address and delay
time.

The baudrate is selectable through values 1200, 2400, 4800, 9600. The bus address can be set
from 1 up to and including 255.
Fluidwell equipment uses eight databits, no parity, a startbit and one stopbit. The least significant bit
of every byte is send first.

This manual describes the general MODbus protocol implementation for all products. The product
specific variables are described in the appendix of the operation manual.

1.2 DESIGN CHOICES IN PERSPECTIVE TO MODBUS SPECIFICATION

This communication package supports MODBUS functions “read holding registers” (03) and “preset
multiple registers” (16). It should be noted that for these functions MODBUS specifies a register as
being two bytes. Since some of the variables have a length which exceeds two bytes, a variable
might need to be represented in more than one register. Therefore for reading or writing a variable
its number (register number) and its length (number of registers) need to be supplied. The internal
variable table may be visualised as a collection of small groups of registers, with each group
representing a unique variable. This leads to the implication that it is not possible to read/write
multiple variables in one request. Refer to chapter 5 for exact description of implemented MODBUS
functions.

Modbus_Protocol_v1303
Page 5

2. ASCII RECORD STRUCTURE


2.1. GENERAL

In ASCII-mode the databytes are ASCII-coded. This means that each (hexadecimal) databyte is split
up into two nibbles; each nibble is send as its ASCII code afterwards. In this way every databyte is
transferred as two ASCII-bytes.

Example:
The databyte 4Ah is transferred as 34h (= '4') and 41h (='A').

The advantage of this protocol-mode is that an ASCII-terminal can be used to "overhear" the
dataline during debugging. A disadvantage is the quantity of data almost doubles.

The most significant nibble is send first.


msn : most significant nibble ASCII coded
lsn : least significant nibble ASCII coded

Following the example: msn = 34h and lsn = 41h.

ASCII DATA Contents: Meaning:


BYTE-NR BYTE-NR
00 00 ":" (3Ah) Start of record marker
01 01 address msn Bus address product
02 01 address lsn Bus address product
03 02 function msn Function to be executed
04 02 function lsn Function to be executed
05 03 msg-byte 0 msn Data for/from the function
06 03 msg-byte 0 lsn Data for/from the function
07 04 msg-byte 1 msn Next byte
08 04 msg-byte 1 lsn Next byte

// // etc. //

05+2*x 03+x msg-byte x msn Last function data byte


06+2*x 03+x msg-byte x lsn Last function data byte
07+2*x 04+x ERROR CHECK msn LRC: LongitudinalRedundancy
08+2*x 04+x ERROR CHECK lsn Check: see below
09+2*x 05+x CR (0Dh) End of record marker 1
10+2*x 06+x LF (0Ah) End of record marker 2
Table 1: ASCII-mode.

Since each databyte is now represented as two ASCII-bytes, numbering of data-bytes in the record
does not count up synchronously with the real number of bytes transferred over the line.

2.2. LRC - CHECKSUM

The checksum is calculated by adding all databytes in the record together from bus-address (data-
byte 01) up to and including the last function data-byte (03+x) and take the two’s complement of the
least significant byte, which means inverting the byte and adding 1. The calculated LRC-byte is now
added to the record as its ASCII-coded 2-byte value.

The receiver must use the same kind of calculation and compare the result with the received
checksum. A less complicated procedure is to calculate from the bus address up to AND
INCLUDING the checksum (this means databytes 1 up to and including 04+x). If the record is not
mutilated after receiving, the result must be 00.

All characters different as CR, LF, '0' - '9', ':', 'A' - 'F' point out a mutilated message.

Modbus_Protocol_v1303
Page 6

3. RTU RECORD STRUCTURE


3.1. GENERAL

RTU DATA Contents: Meaning:


BYTE-NR BYTE-NR

A time of at least 0.11 seconds between records is used as record


separator!

01 01 address Bus address product


02 02 function Function to be executed
03 03 msg-byte 0 Data for/from the function
04 04 msg-byte 1 Next byte

// // etc. //

05+x 05+x msg-byte x Last function data byte


06+x 06+x ERROR CHECK lsb CRC: Cyclic Redundancy Check
07+x 07+x ERROR CHECK msb CRC: Cyclic Redundancy Check

A time of at least 0.11 seconds between records is used as record


separator!

Table 2: RTU-mode.

In the table above, databyte-number 0 is NOT used by purpose to express the similarity with the
ASCII-mode.

RTU-mode sends all databytes without conversion; time outs are used as record separators. Please
notice that the time between two databytes WITHIN a record may not exceed 0.11 seconds! This
time-to-wait is enlarged to two "PC-clockticks" (2/18.2 sec) compared with the original MODBUS
specification, to get a more reliable and simplified time-out detection.

In RTU-mode the databyte-numbers in the record do count up synchronously with the real number of
bytes transferred over the line, since each byte is transferred in its original form.

Modbus_Protocol_v1303
Page 7

3.2. CRC-ERROR CHECK

The CRC-error check method uses the following polynomial:

X16 + X15 + X2 + X0

Description applied procedure:


1 Initialise a 16 bit-register with 0FFFFh (sixteen ones).
2 Put pointer to first byte (databyte no. 1 (address)).
3 Initialise a bit-counter to 8.
4 Put EXOR from LSbyte 16 bits-reg and pointed byte in LSbyte 16 bits-reg.
5 Shift the 16 bits-reg one position to the right; shift in a zero at the left side,
save the shifted-out bit (LSbit).
6 Is the shifted-out bit "1", then EXOR the 16 bits-reg with A001h.
7 Is the shifted-out bit "0", then don't do anything at all.
8 Decrement bit-counter; if not all bits done, return to step 5.
9 Increment pointer to next byte, if not all bytes done, return to step 3.
10 Now, the sender adds the contents of the 16 bits register to the end of the
message to be send.

WARNING: The CRC checksum bytes are in LSB-MSB order! (Contrary to the other words in
the message which are in MSB-LSB order)

This CRC must be calculated from the bus-address (data-byte 01) up to and including the last data-
byte (05+x).
The receiver can determine the CRC by following the same procedure, but now up to and including
both checksum bytes (06+x/07+x). The now calculated checksum must equate zero, otherwise a
mutilated message was received.
Extending the procedure to including the checksum bytes avoids the need for a compare of received
and newly calculated checksum.

Modbus_Protocol_v1303
Page 8

4. FUNCTION CODES
4.1. GENERAL

The table below contains an overview of the communication-functions. The second column contains
the standard MODBUS description.
To be compatible with the several MODBUS-implementations in software-programs as SCADA e.g.,
only the Read en Write holding registers functions are used.
The third column shows the Fluidwell name. The last column indicates the paragraph which contains
more detailed explanation of the function.

Due to the standard table-begin for all the Fluidwell equipment (see chapter 6), it is possible to
detect the type of product, software-version etc. of each product present on the communication bus.

MODICON FUNCTION CODES FLUIDWELL IMPLEMENTATION PAR.

00 Not defined
01 Read Coil(s) status
02 Read input(s) status
03 Read holding registers Read table data 5.2
04 Read input registers
05 Force single Coil
06 Preset single register
07 Read exception status
08 Loopback diagnostic test
09 Program (484 only)
10 Poll prog. complete (484)
11 Fetch event count.comm.
12 Fetch comm. event log
13 Program (184,384,484,584)
14 Poll prog. (see 13)
15 Force multiple coils
16 Preset multiple reg's. Write table data 5.3
17 Report slave id.
18 Program 884 & micro 84
19 Reset comm. link
20 Read general ref. (584)
21 Write general ref. (584)
22-64 Reserv.f. exp. funct.
65-72 Reserv.f. user funct.
73-119 Illegal functions
120-127 Reserv.f. intern. use
128-255 Exception responses Error response 5.4
Table 4: Function codes.

Modbus_Protocol_v1303
Page 9

5. EXPLANATION FUNCTION CODES


5.1. GENERAL

In the diagrams below, following lay-out is used:

The upper line indicates the sequence number of each byte. These sequence numbers correspond
with the databyte-numbers in chapter 2 and chapter 3.

The byte(s) ‘CS’ contains the CheckSum. In ASCII-mode this is a one-byte LRC (which will be
represented in two bytes, just like all databytes in an ASCII record) and for RTU-mode this is a two
byte CRC.

5.2. READ TABLE DATA

This function complies with the MODBUS specified function “Read holding registers” (03). It is used
to read variables from the system. The system will respond to this type of message by sending
either an acknowledge or an error response. Below you will find the record structures that are used
to request and acknowledge this function.

The read request record looks like:

A read response record looks like:

Address refers to the bus-address of the slave module that needs to execute the function. Function
holds the MODBUS function code. Variable number tells the system which variable to read, a
complete table of variable numbers can be found in chapter 6 and Appendix A.
These tables also show the number of bytes that need to be read to get the complete value. It is by
no means possible to read more bytes than the real length of the variable as mentioned in this table.
When such a request is made though, the system will respond with an error. This implies it is only
possible to read one variable per request.

It should be noted that the read request record supplies the system with the number of words
instead of the number of bytes to read. When variables with an odd number of bytes need to be read
the number of words is rounded up (e.g. to read 1-byte bus address -> requested number of words
is 1). This will result in an response which holds one extra byte, which will always be 0. The result is
valid though, because this extra byte will always be the MS-byte of the returned data.

In contrary to reading too much bytes, it is possible to read a variable partially. When a request is
made to read less bytes than the complete length of the variable, the system will return the
requested number of bytes from the least significant part of the variable (e.g. datetime holds 6 bytes
YMDHMS, when you request 2 words DHMS will be returned).

Modbus_Protocol_v1303
Page 10

When the read request record is correctly received by the system and all data-members turn out to
be valid, the system will return the read response record as mentioned above. The address and
function bytes are an exact copy of the ones in the read request record, bytecount shows the
number of bytes of data that the record holds. Of course as many bytes as requested are returned,
so this number always equates 2*number_of_words.

In case any data-members in the read request record turn out to be invalid, the system will return an
error response record. Paragraph 5.4 holds an exact description of all possible error records with an
explanation of the possible causes. When the system does not return any record at all the cause
might be found in a wrong bus-address, wrong checksum or a distortion in the communication
process.

5.3. WRITE TABLE DATA

This function complies with the MODBUS specified function “Preset multiple registers” (16). It is
used to write variables in the system. The system will respond to this type of message by sending
either an acknowledge or an error response. Below you will find the record structures that are used
to request and acknowledge this function.

It is not always possible to write a variable. Some variables are never writeable (e.g. serial number)
and some others can become temporarily unavailable for writing (e.g. baudrate). The standard table
for Fluidwell products (chapter 6) contains a column which shows the writeability of a variable. For
the product specific variables mentioned in Appendix A goes that the ones that are also
programmable on the unit itself (configuration variables) are unavailable for writing during local
programming, to avoid conflicts between local and remote programming. Other, non-programmable,
product specific variables are never writeable unless mentioned otherwise.

The write request record looks like:

A write response record looks like:

Address, function, variable number and number of words are used the same way as with the read
request record which was explained in the previous paragraph. Furthermore the bytecount should
hold the number of bytes that need to be written to the given variable. The system will only accept a
write request record when the bytecount equates the doubled value of the number of words
(bytecount=2*number_of_words).

The number of words may never exceed the true length of the variable as given in the variable table.
When variables with an odd number of bytes need to be written the number of words is rounded up
(e.g. to write 1-byte bus address -> number of words is 1). This implies that the bytecount should
always be an even number and therefore a dummy-byte needs to be added when variables of odd
length are written. This dummy-byte should always be zero and must be added as the most
significant byte in the data to write.

Modbus_Protocol_v1303
Page 11

Example
We want to change the communication mode of the system. In the standard begin table for
Fluidwell products we find that the variable number is 11 (0Bh). We also find that this variable
is only one byte in length. Furthermore The MODBUS function code for writing is 16 (10h) and
we assume the bus-address as being 01 for the system in question. We are willing to write the
byte XX to this variable. The write request record should look like this:

01 10 00 0B 00 01 02 00 XX CS

The highlighted part shows we request 1 word, which leads to a bytecount of 2 and we add an
extra ‘0’-dummy-byte at the most significant part of the data to write.

In contrary to writing too much bytes, it is possible to write a variable partially. When a request is
made to write less bytes than the complete length of the variable, the system will overwrite the least
significant part of the variable in question.

When the write request record is correctly received by the system and all data-members turn out to
be valid, the system will return the write response record as mentioned above. This response record
is an exact copy of the request record, only without the bytecount and the written databytes.

In case any data-members in the write request record turn out to be invalid, the system will return an
error response record. Paragraph 5.4 holds an exact description of all possible error records with an
explanation of the possible causes. When trying to write a variable from the “standard begin-table for
Fluidwell products” that is not implemented on the system in question the write request will be
confirmed, but of course this has no influence on the system whatsoever.
When the system does not return any record at all the cause might be found in a wrong bus-
address, wrong checksum or a distortion in the communication process.

5.4 ERROR RESPONSE CODES

When a request is made and the system finds one of the data-members in the record to be invalid it
will make this not acknowledge clear by sending an error response record.

To let the master system know this is an error record the MODBUS function code will be changed.
While the ms-bit of this code is normally always 0 it will be set to 1 (=OR 0x80). The master system
can determine what went wrong by reading the error code on the third position of the error response
record. In the table below you can find these error codes with an explanation of its meaning and the
possible cause(s).

Error code 0 = reserved for future use

Error code 1 = ILLEGAL FUNCTION


Meaning: The function code received by the system does not represent an executable function.
Possible causes:
1. Requested function is not implemented on this system.
2. Function code does not represent a valid MODBUS function.

Modbus_Protocol_v1303
Page 12

Error code 2 = ILLEGAL DATA ADDRESS


Meaning: The received data cannot be linked to a variable in the system
Possible causes:
1. Variable number does not represent a valid variable on this system.
2. Length of record does not comply with the expected length.
3. Number of words exceeds the real length of the variable.

Error code 3 = ILLEGAL DATA VALUE


Meaning: The data is not valid with this variable
Possible causes:
1. Value is not valid for this variable. It exceeds the value range of this variable (too low/high).
2. Dummy byte does not equate zero when writing an odd number of bytes.

Error code 4 = FAILURE IN ASSOCIATED DEVICE


Meaning: the message contains an illegal request, so it can not be processed
Possible causes:
1. The communication index is out of range when trying to access an indexed variable.

Error code 5: reserved for future use.

Error code 6 = SLAVE DEVICE BUSY


Meaning: The variable is not available for remote access
Possible causes:
1. Writing to a read-only variable.
2. System is currently being used in program-mode, so remote access is temporarily disabled for
the variable that is being programmed.

When a function is requested and no response frame comes back within a short time (with regards
to the Comdelay value!) the possible causes might be:
1. communication protocol is set to off,
2. message was mutilated due to a distortion on the line,
3. a hardware problem,
4. wrong bus-address,
5. baudrate of communicating devices differs (2400 <-> 9600),
6. communication mode of communicating devices differs (RTU <-> ASCII),
7. startbit, stopbit or number of databits of communicating devices differs,
8. wrong checksum.

Modbus_Protocol_v1303
Page 13

6. STANDARD BEGIN-TABLE FLUIDWELL PRODUCTS


6.1. GENERAL

Not all functions are implemented in every Fluidwell product. This may vary per device and
product-family. It is even possible that a product with the same product-number has different
software and/or hardware.
The function-codes 3 and 16 (read and write table data) are implemented in every Fluidwell-product.
To make it possible to access any product (also future products) via this protocol, the table-begin as
described below is mandatory. With this standard begin, communication software can conclude
which other functions are implemented.

Nr. VARIABLE NAME LENGTH NOT WRITABLE


00 Kind of product 2 bytes never writeable
01 Model number 2 bytes never writeable
02 Serial number product 4 bytes never writeable
03 Hardware options 2 bytes never writeable
04 Software options 2 bytes never writeable
05 Protocol options 2 bytes never writeable
06 Software version 2 bytes never writeable
07 Protocol version 2 bytes never writeable
08 Display languages 2 bytes never writeable
09 Bus address 1 byte during local programming
10 Baud rate 2 bytes during local programming
11 Communication mode 1 byte during local programming
12 Comm. index use 2 bytes always writeable
13 Comm. index 1 byte always writeable
14 Comdelay 2 bytes
15 general status 2 bytes never writeable
16 indexed status 1 byte never writeable
17 reserved
18 reserved
19 reserved
20 Inputs never writeable
21 Outputs never writeable
22 Beep command 1 byte always
23 Time and date 6 bytes during local programming
24 Print command not implemented
25 Reboot 2 bytes always writeable
26 reserved
27 reserved
28 reserved
29 reserved
30……...Further product dependant variables only!!

Table 5: Standard begin-table Fluidwell products.

Modbus_Protocol_v1303
Page 14

Nr. VARIABLE EXPLANATION

00 Kind of product Batch controller, PC, printer etc.


01 Model number Type of product
02 Serial number Serial number binary coded
03 Hardware options Extra hardware mounted, inputs / outputs e.g.
04 Software options Extra software functionality, temperature compensation e.g.
05 Protocol options Protocol extensions, also other protocol implementation e.g.
06 Software version Product software version
07 Protocol version Communication software version
08 Display languages Code for the display languages available
09 Bus address The communication address
10 Baud rate Communication speed 1200=0, 2400=1, 4800=3, 9600=4
11 Communication mode BUS_ASCII=0, BUS_RTU=1, OFF=2 Warning: can not be
enabled remotely
12 Comm. index use User options of the comm. index:
00 : no features
01 : auto increment after each usage
02 : auto decrement after each usage
04 : auto functions also during broadcast access
13 Comm. index Pointer for indexed values
14 Comdelay { 0..9999 } In milliseconds!!
15 General status Device status, general alarm etc.
Meaning of bits [msb…lsb] for 100-series:
0x0001: PCF error
0x0002: EEPROM error
0x0004: data corrupted (communication)
0x0008: receive buffer full (communication)
16 Indexed status status per liquid; busy, overrun, pause etc, new data
17 Reserved
18 Reserved
19 Reserved
20 Inputs See device description
21 Outputs See device description
22 Beep command One byte in units of 0.1 seconds.
23 Date time Order used: year,month,day,hour,minutes,seconds
All bytes binary coded.
24 Print command Not implemented yet
25 Reboot 0xA50F (warm reboot) or 0x5AF0 (cold reboot).
A warm reboot resets the unit, but all programmed variables are
stored.
A cold reboot resets the unit and all of its programmed
variables. Note that also the accumulated total will be lost!
26 Reserved
27 Reserved
28 Reserved
29 Reserved
30……...Further product dependant variables only!!

Table 6: Variable description.

Modbus_Protocol_v1303
Page 15

6.2. INDEXED VARIABLES

Some Fluidwell products use an array of multiple variables, for example a linearisation table which
holds multiple frequency-correction pairs or an array of multiple batch sizes. To make easy use of
such an array, a communication index needs to be used.
The variable that will be returned depends of the value of this index. When a larger part of the array
needs to be read or written it is possible to auto-increment or decrement the index, meaning that
after each successful read/write the index will point to the next or previous variable in the array. This
way complete arrays can be accessed fairly easily.
Note that if index=0 the first array member will be returned, so an array of 5 variables uses indices 0
through 4. Be aware that this index can only be used for variables which are marked as indexed in
this manual, it is never possible to use the index to read/write multiple un-indexed variables!

Example
Assume we are communicating with a unit that uses linearisation and has a bus-address of
01. We are willing to read the complete linearisation table from it. Of course we can initialise
the index, read the variable, increment the index, write the new index, read again and repeat
this procedure until the whole table is read, however it is more easily to use the next steps:
1. Initialise the communication index to the first array-member, we need to write:
01 10 00 0D 00 01 02 00 00 DF (LRC checksum! ASCII-mode only!)
2. Set the communication index use to auto-increment, we need to write:
01 10 00 0C 00 01 02 00 01 DF
3. Now we are ready to read the first array-member, for our example the linearisation table
start at address 0400h and each entry contains 6 bytes:
01 03 04 00 00 03 F5
4. The index is now auto-incremented to 01, so now we only need to repeat step 3. until the
whole table is read!

For safety reasons the auto-increment/decrement function is disabled for Fluidwell products which
are used in broadcast-mode (e.g. FW/0300 series), but can still be enabled if desired (see standard
begin-table Fluidwell products, variable 12)

Modbus_Protocol_v1303
Page 16

7. GENERAL REMARKS
7.1. GENERAL

All numeric variables are binary coded. There are variables with different lengths:

byte : 8 bits
word : 16 bits
double word : 32 bits

When transmitting multibyte variables, the msb is transmitted first.


In tables, the length of variables is given in bytes.
Several on/off variables use "0" for off-position. A value unequal "0" indicates that the concerning
variable is "on".

Variables that indicate a decimal position contain as value the number of digits behind the decimal
point. This corresponds with the negative value of the exponent from 10 from the number to be
multiplied with the concerning variable.

Example:
K-factor = 1031, decimal position K-factor = 2.
This means that the K-factor has two digits behind the decimal point; the K-factor is 10.31
This corresponds with the multiplying with 0.01 = 10E-2. The last 2 corresponds (but without
minus sign) with decimal position 2.

Time variables - if no other time unit indicated - use a time base of 0.1 second.
If the programmed overrun-time in a batch controller is 6.5 seconds for example, then the
"communication-value" will be 65.

Some variables are always write protected such as the product and serial number. It is always
allowed to read a variable.

Modbus_Protocol_v1303
Page 17

INDEX
ASCII-mode 5 multiple variables 4
communication-functions 8 Notes 21, 22
Contents 2 numeric variables 18
CRC-ERROR CHECK 7 Read table data 10
ERROR RESPONSE CODES12 Rtu record structure 7
Function codes 8 RTU-mode 7
Indexed variables 18 Standard begin-table fluidwell15
LRC - CHECKSUM 5 Write table data 11

Modbus_Protocol_v1303
Page 18

NOTES

Modbus_Protocol_v1303
Page 19

NOTES

Modbus_Protocol_v1303
Page 20

Fluidwell bv Modbus_Protocol_v1303
PO box 6 Voltaweg 23 Website: www.fluidwell.com
5460 AA Veghel 5466 AZ Veghel Find your nearest representative: www.fluidwell.com/representatives
The Netherlands The Netherlands Copyright Fluidwell bv - 2015 - Modbus_Protocol_v1303