Protection of Synchronous Generators
Protection of Synchronous Generators
SYNCHRONOUS GENERATORS
Sture Lindahl
Preface
Generally, the power stations represent about 50% of the capital cost in a
power supply system. The power generator itself plays an important role in
the energy conversion process in the power station. A generator has more
failure modes than any other component in the power system. The
generator protection system must detect the faults rapidly. Otherwise, there
is a risk that the power generating unit will suffer a protracted forced
outage. In some nuclear power stations, there are a spare rotor, a spare
stator or both. Usually, there is no spare generator. This means that a
generator failure will cause a forced outage of the entire power generating
unit. Such outages will cause a substantial increase of the costs for power
generation.
The ambition, to protect the generator against all faults, results in ad-
vanced protection and monitoring systems. There is, however, considerable
divergence in opinion on the extent of generator protection systems. It is
important that the protection system detects fault that may hurt humans and
damage equipment. Most power systems tolerate the disconnection of one
generating unit without running into serious problems. A fault on another
power system component may cause the generator protection system to op-
erate non-selectively. Such an unwanted operation may cause a blackout of
the power system or the disconnection of customers.
In this document, we discuss generator faults and abnormal
conditions. We also describe several aspects of the generator protection
system.
My intent has been to compile a document that can serve as an intro-
duction and a background to further studies. I have presupposed that the
reader has some knowledge in power system engineering. I plan to use the
document in further education courses. The intended readers are power sys-
tem operators and protection engineers. I hope that design engineers in the
power industry will find the document useful as a background.
As a former teacher in automatic control, I am aware of the
importance of feedback. I encourage all readers to let me know of errors,
misunderstandings and suggestions for improvement.
Contents
1. Introduction
2. Synchronous Machines
3. Generator Faults
4. Fault Statistics
5. Background
6. Differential Protection
7. Underimpedance Protection
8. Overcurrent Protection
9. Interturn Fault Protection
10. Protection Against Open Circuits
11. Stator Earth-Fault Protection
12. Field Earth-Fault Protection
13. Underexcitation Protection
14. Overvoltage Protection
15. Reverse Power Protection
16. Unbalance Protection
17. Out of Step Protection
18. Abnormal Frequency Protection
19. Inadvertent Energising Protection
20. Bearing Current Protection
21. Breaker Failure Protection
22. Operational Experience
1. INTRODUCTION
Generally, the power stations represent about 50% of the capital cost in a
power supply system. The power generator itself plays an important role in
the energy conversion process in the power station. A generator has more
failure modes than any other component in the power system. The
generator protection system must detect the faults rapidly. Otherwise, there
is a risk that the power generating unit will suffer a protracted forced
outage. In some nuclear power stations, there are a spare rotor, a spare
stator or both. Usually, there is no spare generator. This means that a
generator failure will cause a forced outage of the entire power generating
unit. Such outages will cause a substantial increase of the costs for power
generation. It is very important that the protection system detects all faults
that may hurt humans and damage equipment. This means that the
generator protection system must have a high degree of dependability. It is
high if the probability of not having a failure to operate is high.
Most power systems tolerate the disconnection of one generating
unit, one power transformer, one power line or one busbar section without
running into serious problems. A fault on adjacent power system
component may cause the generator protection system to operate non-
selectively. Such an unwanted operation may cause a blackout of the power
system or the disconnection of customers. The generator protection system
must have a high degree of security. It is high if the ability of not having
an unwanted operation is high.
All protection systems must have a high degree of dependability and
a high degree of security. We say that a protection system has a high degree
of reliability if the ability of not having an incorrect operation is high. The
reliability is the combined ability of not having a failure to operate and of
not having an unwanted operation.
The ambition to protect the generator against all faults results in
advanced protection and monitoring systems. There is, however,
considerable divergence in opinion on the extent of generator protection
systems.
To reduce the operating costs for the power generation, utilities
reduced their staff and many power stations are unmanned. To avoid
increased risks for damage to such unmanned power station it is necessary
to equip these power stations with advanced protection systems and remote
control systems. Depending on the size (cost) and importance for the power
supply we place different demands on the protection system. In hydro
power stations with only one generating unit and in nuclear power stations,
the protection systems have to meet the most stringent requirements. In
hydro power stations with several small generating units, we may simplify
the protection systems. Such protection systems have to satisfy the legal
requirements but no other requirements.
Protection systems in pumped storage hydro plants require many
special considerations because of the many modes of operation. They
include (1) generation, (2) pumping, (3) synchronous compensation
prepared for generation and (4) synchronous compensation prepared for
pumping. One special problem is to maintain the correct current direction
in reversible pumped storage units.
In the mid 1960's, many utilities introduced electronic control
equipment in power stations. After accumulating sufficient experience
concerning reliability, maintainability and disturbance immunity, they also
introduced static protection equipment. Electronic protection equipment has
shorter operate times, better earthquake safety and does not need as much
panel space as older electromechanical protection equipment. The
introduction of electronic protection equipment made it possible to
introduce more sophisticated protection functions. Now, we seldom install
new electromechanical protections.
Microcomputer based measurement and control equipment has been
used for several years. In the early 1980's, computer based protections
became available. In the late 1980's, complete integrated protection system
using digital signal processing techniques become commercially available.
2. SYNCHRONOUS MACHINES
A synchronous machine is not a simple device. The armature, or stator,
winding is arranged in three symmetrical phase belts in slots in the stator
surface. The magnetic field intensity can be controlled via the DC current
in the rotor, or field, winding. A synchronous machine can operate as a
generator or as a motor. In our case, generator operation is the most
common operating mode. When the synchronous machine operates as a
generator, a prime mover drives the rotor. The prime mover can be a
diesel engine, a gas turbine, a hydro turbine or a steam turbine. A
synchronous generator may operate alone with a single load or in parallel
with other generators on a large power system.
np (1)
f =
60
where
n = the rotational speed in revolutions per minute [rpm], and
p = the number of pole pairs.
S ≈ n D2 LBA (2)
where
n = the rotational speed [rpm],
D = the diameter of the rotor [m],
L = the length of the rotor [m],
B = the magnetic flux density in the air-gap [T], and
A = the linear current density on the rotor [A/m].
HYDRO-GENERATORS IN SWEDEN
400 Juktan G1
Ritsem G1
300 Porjus G11
Seitevare G1
200 Stornorrfors G1
Harsprånget G1
Hjälta G1
100 Torpshammar G1
Hojum G1
Stadsforsen G1
0
1900 1920 1940 1960 1980 2000
Year
1640
MVA
1500
1200
850
1000
500
200
0
Air Hydrogen Water/Hydrogen Water
1250
*)
Net active power [MW]
0
1900 1920 1940 1960 1980 2000
Year
*) Increase of maximum capacity in existing power plants
bines. This means that the unit has two generators with a rated capacity of
25.3 MVA and two generators with a rated capacity of 68.8 MVA. The
total rated capacity is 188.2 MVA. In 1985, Oskarshamns Kraftgrupp AB
commissioned the nuclear unit Oskarshamn 3 with one turbo-generator. It
has a rated capacity of 1 294 MVA. During these 26 years, the average rate
of increase is about 12% per year.
power generated. Slip frequency current will flow in several paths in the ro-
tor. The field winding may form such a path. Another path is the damper
winding of a salient pole machine. The current will also flow in slot wedges
and the solid rotor body.
When the machine operates as an induction generator, the external
power network will provide the necessary excitation. This means that the
machine will absorb much reactive power. The reactive current may ap-
proach or even exceed the rated current of the machine.
In [ 1 ], Mason and co-authors describe a series of asynchronous
running tests. The test object was a 588 MVA turbo-generator equipped
with special temperature-measuring devices on both the stator and rotor.
Below, we reproduce some results presented in [ 1 ].
ASYNCHRONOUS OPERATION
0.6
0.5
0.2
0.1
0.0
0.0 0.2 0.4 0.6 0.8 1.0
Active Power, P/S [pu]
ASYNCHRONOUS OPERATION
1.2
Quadrature Coponent of
Stator Current [pu]
1.0
0.8
0.6
0.4
0.2
0.0
0.0 0.2 0.4 0.6 0.8 1.0
In-Phase Component of Stator Current [pu]
Reference
3. GENERATOR FAULTS
The protection of synchronous generators involves the consideration of
more possible faults and abnormal conditions than the protection of any
other power system component. When designing the protection system we
have to consider (1) stator faults, (2) rotor faults and (3) abnormal
operating conditions.
Pohl has investigated how the earth-fault current damages the sheets of a
synchronous machine. In [ 2 ], he describes the result of tests with three
different insulating materials between the stator sheets, two different values
of the earth-fault current and four values of the fault clearance times.
Figure 1 shows the number of stator sheets that melt together because of an
earth-fault. We can see how the damage caused by the earth fault current
may increase with the fault clearance time. Table 1 shows how to interpret
the legend in the figure.
Legend
# SM 2 A
SM 5 A
100
CM 2 A
CM 5 A
M 2A
50 M 5A
0
4 sec 1 min 10 min 60 min
Fault Clearance Time
negative sequence currents that flow during these unbalanced faults induce
voltages in the rotor of the generator. The frequency of these voltages is 2fn
where fn is the power frequency. The induced voltages cause rotor currents
that tend to flow on the surface of the rotor forging and in the non-magnetic
rotor wedges and retaining rings. The resulting losses quickly raise the
temperature. If the abnormal condition persists, the metal will melt,
damaging the rotor structure.
There are [ 1 ] four potential sources of shaft voltages on generator
shafts (1) the generation of a shaft voltage by an asymmetrical generator
airgap or stator field which links with the rotor shaft, (2) the capacitive cou-
pling of the excitation control system with the shaft, (3) the shaft voltages
generated by charge separation in the latter stages of the steam turbine and
(4) the stresses of the turbine stationary and rotating blades/nozzles or
buckets cause the blades to become magnetised by magnetostriction, which
on rotation, generates a small AC voltage across the turbine. It is common
practice to earth the shaft at one location. The contact between the hydro
turbine and the water column prevents charging of the shaft. Usually,
turbo-generators have earthing brushes at the turbine end of the generator.
It is common practice to earth the shaft at only one point to avoid
circulating currents. The remote bearings are insulated from earth. If this
insulation deteriorates, induced shaft voltages may be high enough to
penetrate the oil film in the bearing and some current starts to flow. The
current causes pitting of the bearing surfaces. Essentially, pitting continues
until the bearing loses its low coefficient of friction, the friction losses
increase, the bearing surface breaks up and the surface is wiped. Generally,
a bearing will be damaged within second if the shaft current is higher than
2 A.
References
4. FAULT STATISTICS
It is an advantage to know the failure rate, the type of failures and the
causes of failures when we design the protection system for a power
system. Sometimes, it is a necessary condition for the design of a cost-
effective protection system to have such fault statistics available. There is,
however, limited information on generator faults.
This section contains a review of the available sources. It also con-
tains a compilation of failure rates for synchronous machines. The rate of
external faults and system abnormalities depends on the power system. We
do not have the ambition to discuss these rates here. It is believed that the
material allows us to carry out simple probabilistic risk analyses. We have
to be careful when using the results of the analysis. One should not assume
that the calculated results have better accuracy than a factor of two.
ability concepts and methods. There are also some examples of reliability
data in the Application Guide [ 2 ]. These data do, however, not allow us to
estimate the failure rate of synchronous generators and, especially not, how
often generator protection systems have to operate.
40
30
Hours*1000
20
10
0
Canada France India Sweden UK USA
4.2.2 BBC
Kramer and Reinhard [ 3 ] describe the system that BBC used to collect
fault data for steam turbines and turbo-generators. The paper contains only
limited information on failure rates for turbo-generators. Table 2 gives the
availability and forced outage rate (FOR) for turbo-generators. The data
represents five calendar years, 1968-72.
4.2.3 Sweden
operating close to the voltage collapse limit. These facts and the high rela-
tive failure rate underline the importance of protection against loss-of-field.
35.7
40
28.6
30
14.3
14.3
20
7.1
10
0
S. short-c. S. earth-f. R. short-c. R. earth-f. Loss-of-f.
References [ 4 ] and [ 5 ] contain data that are useful when analysing the
risks associated with turbo-generator faults. The author presented the mate-
rial at two forums in München arranged by the insurance company Allianz
Versicherungs-AG.
Unfortunately, references [ 4 ] and [ 5 ] contain any data on absolute
failure rates. According to [ 4 ] the number of rotor faults is 80% higher
than the number of stator faults. The costs associated with rotor damages
are 70% higher than the costs associated with stator damages.
Figure 3 shows a breakdown [ 5 ] of the stator damages according to
the cause and the type of faults. The hatched bars show the percentage of
the costs associated with the fault type. The full bars show the percentage
of the number of stator damages.
Figure 3 shows that the costs associated with electrical faults on the
stator winding are considerably larger than the relative number of faults.
Reference [ 5 ] does not give the distribution of earth-faults and interturn
faults. The data show the importance of fast and reliable protection against
stator earth-faults and stator short-circuits.
Stator Damages
60 Allianz Versicherungs-AG, 1969-75
%
Legend
50
Cost
40 Number
30
20
10
0
A B C D
Rotor Damages
60 Allianz Versicherungs-AG, 1969-1975
%
50
Legend
40 Cost
Number
30
20
10
0
A B C D
Figure 4 shows that the costs associated with electrical faults are consider-
able higher than the relative number of faults. It is not very surprising that
the retaining rings and the end regions of the rotor represent a considerable
share of the costs associated with the rotor damages. The data emphasises
the importance of fast and reliable rotor earth-fault protections and loss-of-
excitation protections.
From these data we can estimate the failure rate at 60 faults/(100 genera-
tors, year).
Table 7 shows the distribution of number of faults by components.
4.3.2 Nordel
Hydro-Power Generators
50
Nordel 1982-91 ( S > 5 MVA )
35.6
40
Faults/(100 gen., year)
30
18.3
15.1
20
5.7
10
0
Finland Norway Sweden Nordel
We can see that the failure rate corresponds to a mean time between
failures of 5 years. There is considerable variation in the failure rate from
one country to another. Figure 6 shows the cause to the failures of the
hydro-generators mentioned above.
Hydro-Power Generators
60
Nordel 1982-91 ( S > 5 MVA )
%
45
40
26
21
20
6
2
1
0
Ligthning Nature Sabotage Staff Equipment Other
We can see that failure of the technical equipment is the most common
cause. It is also obvious that the power houses provide ample protection of
the hydro-generators against lightning, nature and third party.
4.3.3 Sweden
4.3.4 Norway
4.4 Summary
The probability of an electrical failure of a given synchronous generator is
low. One can relate the failure rate of a synchronous generator to the failure
rate of 400 kV overhead line. Let us assume that the failure rate of 400 kV
overhead lines is 0.5 faults/(100 km, year). We assume that the failure rate
of a synchronous machine is 15 faults/(100 generators, year). The failure
rate of the synchronous machine then corresponds to the failure rate of a
15/0.5 = 30 km long 400 kV overhead line. It is common practice to use
GENPC040.DOC 2007-05-22 15.25
4.12 Fault Statistics
References
5. BACKGROUND
This section contains a short historical background to the protection of syn-
chronous generators. This section is entirely based on [ 1 ]. Electrical ma-
chines for use in power systems were being produced in the final decades
of the last century. Then, the only electrical protective devices available
were fuses. They were suitable for use with some small motors. Apparently
fuses could not provide adequate protection of generators. They were
particularly unsuitable for use with three-phase machines because the
operation of a single fuse in case of a phase-to-earth fault on a machine
would have caused it to carry unacceptably high negative sequence
currents. In addition the operation of fuses in the three-phase circuits could
not have initiated the opening of field-winding circuits.
In 1902 H.W. Clothier stated in a paper that he presented to the IEE
that for large AC generators it is feasible to do without fuses or other
automatic devices. This view was also expressed by W.B. Woodhouse
during a paper by H.L. Riesley that he presented to the IEE in 1903.
In spite of these views, there were those who felt that protection re-
lays should be used. Reverse-current relays were referred to in a paper by
C.H. Merz and McLellan entitled "Power station design" that was presented
to the IEE in 1904. These relays were directional relays and their task was
to detect current fed from the busbars into faulted machines. The authors
stated that these relays would not detect short circuits within machines be-
cause the voltages would be too low for the relays to function correctly.
The authors nevertheless felt that automatic protective devices were
required. In the discussion on this paper L. Andrew stated that he had
demonstrated a reverse-current device in 1898 but recognised that it still
was not entirely satisfactory. Reverse-current relays, developed by Brown
Boveri, were referred to in a paper that was presented to the British
Association in 1903. Five years later C.C. Garrard referred to the use of
reverse-current relays with 0.5 s time lags to allow for transient effects in a
paper presented to the IEE. Clearly most machines were operating
without effective protective equipment thus far.
In 1910 K. Faye-Hansen and G Harlow presented a paper "Merz-
Price protective gear and other discriminative apparatus for alternating-cur-
rent circuits" to the IEE. They advocated the use of circulating-current
protective schemes (differential relays) on alternators and showed ar-
rangements suitable for delta- and star-connected machines. Even then sev-
eral speakers in the following discussion expressed the view that such
schemes were unreliable and not suitable for applications to alternators.
One speaker, A.E. McKenzie, stated that two 4 MW, three-phase machines
GENPC050.DOC 2007-05-22 15.25
5.2 Background
References
6. DIFFERENTIAL PROTECTION
A short-circuit between two (or three) phases in a synchronous machine is a
very severe fault. Within a short time, such a fault may cause much
damage. There is a risk that a short-circuit that is not cleared properly may
cause a fire in the power house. All generators must have a short-circuit
protection that detects internal short-circuits quickly, immediately trips the
HV unit circuit-breaker (or the MV generator circuit-breaker), the field
circuit-breaker, and de-energises the fault location. The short-circuit
protection should also shut down the prime mover, turn on CO2 if provided
and give an alarm. The short-circuit protection may also initiate the transfer
of station auxiliaries from the normal supply from the generator terminals
to the reserve supply from the network.
According to Mason [ 3 ], it is the standardised practice of manufac-
tures to recommend differential protection for generators rated at 1 MVA or
higher. In 1948, Harder and Marter [ 2 ] stated that most of the generators
have such differential protection. Above 10 MVA, it is almost universally
the practice to use differential relays [ 5 ].
A rotating machine provides a classical application of differential
protection. Usually, all equipment, the CTs and the circuit-breakers are near
each other. This minimises the possible error due to long cable runs. In ad-
dition, there is only one voltage level involved. This means that the CT
ratio and types can be the same. The CTs may have matched characteristics.
A generator differential protection should have dedicated CT cores and cir-
cuits. Such cores should not be used with any other protections, metres, in-
struments or auxiliary transformers without a careful check on the effect on
CT performance.
The CTs used for the generator differential protections is almost in-
variably located in the buses and leads immediately next to the generator
winding. This is done to limit the zone of protection so a fault in the
generator is immediately identifiable for quick assessment of damage,
repair and restoration of service. The generator buswork is usually included
in some overall differential protection.
It is very important the differential protection does not operate in
case of external short-circuits. This is important in power stations with
several large generating units. Most power systems are not designed to
withstand a line fault and a simultaneous loss of a generating unit (several
generating units). There is a risk that the generator differential protection
maloperates if a CT saturates. Close to power stations, the time constant, of
the DC component of the short-circuit current, may be very long and in the
order of 100 to 150 ms. External short-circuits with fully developed DC
GENPC060.DOC 2007-05-22 15.26
6.2 Differential Protection
References
[1] Andersson, B., Broman, H., Eriksson, P.- A., Fredriksson, S. &
Lohage, L.: "Generatorskydd i Vattenkraftstationer", Rapport,
Vattenfall, November, 1982.
[2] Harder, E.L. & Marter, W.E.: "Principles and Practices of Relay-
ing in the United States", AIEE Trans., vol. 67, pp. 1075-1081,
1948.
[3] Mason, C.R.: "The Art and Science of Protective Relaying",
John Wiley and Sons, New York, 1956.
[4] Walker, C.W.: "Relay Protection in Hydro-Electric Power
Stations of the Snowy Mountains Authority", The Institution of
Engineers, Australia, Electrical Engineering Transactions, vol.
EET-5, no. 2, pp. 311-316, September, 1969.
[5] "Relay Protection of A-C Generators", AIEE Committee Report,
AIEE Trans., vol. 70, pt. I, pp. 275-282, 1951.
7. UNDERIMPEDANCE PROTECTION
The line protections shall detect all shunt faults on the transmission
network and to trip associated circuit-breakers. The back-up protection
system must operate when a line protection fails to operate or when a
circuit-breaker fails to interrupt the fault current. Often, the generator
underimpedance protection is one part of this back-up protection system.
Sometimes, there is no overall differential protection and we need another
type of back-up protection when the main protection fails to operate.
Table 1 shows the steady-state short-circuit currents from generators
at a three-phase short circuit on the generator terminals. We assume that the
excitation voltage is constant.
References
[1] Andersson, B., Broman, H., Eriksson, P.- A., Fredriksson, S. &
Lohage, L.: "Generatorskydd i Vattenkraftstationer", Rapport,
Vattenfall, November, 1982.
8. OVERCURRENT PROTECTION
The Swedish electrical safety regulations demand that all generators have
an overcurrent protection in each phase. These regulations also demand that
all generators have switching devices that disconnect all phases of the
generator from the rest of the power system. A unit connected generator
and transformer may use common protection and switching devices.
Many old synchronous generators have rotating exciters. Often, these
generators have simple overcurrent protections [ 1 ]. The task of this over-
current protection is to provide back-up protection for internal short-
circuits and for external shunt faults. Generally, the setting is 1.5 In where In
is the rated current of the generator. Often, the time delay is 1.5 seconds.
The introduction of static exciters made it necessary to replace the
overcurrent protections by underimpedance protections. Short-circuits close
to the power station may reduce the generator terminal voltage. The
reduced terminal voltage reduces the excitation current. The fault current
may fall below the rated current of the generator and the overcurrent
protection may fail to operate. Underimpedance protections may operate
even if the fault current is lower than the rated current of the generator.
Large generators are often equipped with differential protection that
serves as main short-circuit protection. It is good engineering practice to
equip the generator with short-circuit back-up protection. The overall
differential protection is the best back-up protection. All generators do not
have such back-up protections. Generators without overall differential
protection must have underimpedance protection or overcurrent protection
as back-up protection.
When the excitation current depends on the generator terminal volt-
age, a simple overcurrent protection may not be reliable enough. As de-
scribed in Section 7, underimpedance protections may provide reliable
back-up protection. The combination of overcurrent and undervoltage
relays may provide better short-circuit back-up protection than simple
overcurrent protections. We can use voltage-controlled overcurrent
protections where the overcurrent relay is disabled until the generator
terminal voltage drops below the set level of the undervoltage relay. We
can also use voltage-restrained overcurrent protections where the pickup
value of the overcurrent relay is proportional to the generator terminal
voltage.
Persisting overcurrents in the interval [1.0In,1.4In], where In is the
rated current of the generator, are not detected by overcurrent protections or
by underimpedance protections. Such overload must be detected by dedi-
cated thermal overload protections or by over-temperature sensors. Modern
overload protections may have an adjustable time constant that can be ad-
justed to the thermal properties of the generator.
References
[1] Andersson, B., Broman, H., Eriksson, P.- A., Fredriksson, S. &
Lohage, L.: "Generatorskydd i Vattenkraftstationer", Rapport,
Vattenfall, November, 1982.
INTERTURN FAULT
Phase Windings
A
N B
Interturn faults are quite rare but they have occurred and will continue to
occur. Buttrey, Hay and Weatherhall [ 1 ] have provided some information
concerning the failure rate of interturn faults. They point out that it is diffi-
cult to identify faults that were initiated by interturn faults. Usually, the
source of initiation of a stator winding fault is destroyed by the subsequent
damage. During the period 1970-74, thirteen major dielectric breakdowns
have occurred on stator windings of machines rated at 200 MW or above.
The number of exposed generators are not given. We have estimated the
number of exposed generators at 50. This means that the failure rate of
interturn fault may be in the order of 5.2 interturn faults/(100 generators,
year).
Buttrey, Hay and Weatherhall [ 1 ] have also provided some informa-
tion concerning the magnitude of the fault current. They state that it may be
in the order of 100 kA on a 500 MW generator. Let us assume that the
power factor (cos(ϕ)) is 0.8 and that the rated voltage of the generator is
20 kV. Then, the fault current is about 5 per unit. Such high local fault cur-
rents can cause severe damage to the iron core. The fault clearance time
must be as short as possible.
R R R
A B C
the line end of each winding. One must connect the other primary terminal
of the voltage transformers to the neutral point of the generator. The
protection measures the zero sequence voltage across the machine.
Normally, no zero sequence voltage should exist but a short circuit of one
or more turns on one phase will cause the generated EMF to contain such a
component. Figure 3 shows such a zero sequence protection.
A B C
most of the harmonic content in the secondary voltage from the broken-
delta connected winding. We can also provide a filter to extract the third
harmonic component from the broken-delta connected winding and apply it
as a relay bias [51].
References
One current transformer can replace the two cross-connected current trans-
formers if the neutral point is unearthed. This single current transformer
measures the current that flows between the two neutral points. Figure 2
shows such a neutral current unbalance protection.
line end there are four current transformers per phase. To detect phase-to-
phase short circuits, there are four three-phase differential protections.
References
1 (1)
RN =
3ω (C w + Cb + C a + Ct )
where
Cw = the capacitance of the generator winding [F/phase],
Cb = the capacitance of the buswork [F/phase],
Ca = the capacitance of the auxiliary transformers [F/phase],
Ct = the capacitance of the step-up transformer [F/phase].
High earth fault currents may damage the iron core if the fault clearance
time is long. The risk for damage is small if the earth fault current is lower
than 15 A when there is an earth fault on one generator phase terminal.
According to Walker [ 7 ], the safe limit is 5 A.
Below, we will discuss only generators with high-impedance earthed
neutral. We describe earth fault protection systems for generators and trans-
formers connected to a unit. Figure 4 in Section 2 shows the single-line dia-
gram for such a power plant with generating units without a generator
breaker. Figure 5 in Section 2 shows the single-line diagram for generators
with a generator breaker. One can use similar earth fault protection systems
in power plants where two or more generators share a the same step-up
transformer. Figure 6 in Section 2 shows the single-line diagram for such a
power plant. Finally, we will describe earth fault protection systems for
generators connected to a common busbar. Figure 7 in Section 2 shows the
single line diagram for such a power plant.
A
N
B
C
Line End Earth
Fault Protection
Neutral End Earth
Fault Protection
Combined Earth
Fault Protection
Total Earth
Fault Protection
The line end earth fault protections can detect earth faults on almost the
entire generator winding but have a blind zone close to the neutral point.
The size of the blind zone may be 5-20%. The main task of the neutral end
earth fault protection is to detect an earth fault close to the neutral point.
Such protections may cover 20-40% of the winding. Sometimes these
protections can detect earth faults close to the line terminals. To cover the
entire winding, one can use a combined earth fault protection that com-
prises line end earth fault protection and a neutral end earth fault
protection. There are finally total earth fault protections based on a
method that makes it possible to detect earth faults anywhere along the
entire generator winding.
GENPC110.DOC 2007-05-22 15.27
11.4 Interturn Fault Protection
A B C
N
U>
A B C
I>
Generally, large hydro power units with generator breakers have one
neutral point overvoltage protection and one zero sequence overvoltage
protection. The neutral point overvoltage protection must cover at least
95% of the stator winding. In new plants a combined earth fault protection
that can detect earth faults anywhere along the generator winding replaces
the neutral point overvoltage protection. The delay for this sensitive
protection is usually 1.2 second. Often, the zero sequence overvoltage
protection covers about 80% of the generator winding. Normally, the delay
is 0.4 second.
U>
The earth fault protections described above cannot detect earth faults on the
primary winding of the step-up transformer while the generator breaker is
open. To detect such faults, one may use a zero sequence overvoltage pro-
tection. It is connected to the primary winding of the step-up transformer.
The sensitivity is about 80% and the delay is equal to 0.8 second.
determines the maximum size of the resistor connected to the neutral point
of the generator. When all generators with such resistors are in service, the
total earth fault current may become too high.
Some busbars may have a bay for an earthing transformer with a neu-
tral point resistor. In such cases, the system has a high-impedance earthed
neutral. Sydkraft uses a combined earthing transformer and station
auxiliary transformer. Some plants may have only a step-up transformer
with a Y- or Z-connected winding connected to the busbar. One can use
this neutral point to connect a neutral point resistor. It is not necessary to
install neutral point resistors at each generator if there is an earthing
transformer with a neutral point resistor of if the step-up transformer has a
neutral point resistor. It is also possible to avoid using neutral point
disconnecters otherwise necessary to limit the earth fault current.
Neutral point overvoltage protections, neutral point overcurrent pro-
tections and zero sequence overvoltage protections cannot select the faulty
generator if several generators are connected to one common busbar.
Figure 5 shows a residual differential protection that can select the
faulty generator when several generators are connected to a common
busbar.
One only needs three-phase current transformer if the neutral point of
the generator is unearthed. Unavoidable amplitude errors and phase errors
limit the sensitivity of the earth fault protection. On external short-circuits,
the fault current from the generator may be very high and may contain a
substantial DC component. The fault currents may cause a false secondary
zero sequence current. There is a risk that this false current will cause un-
wanted operation of the earth fault protection. To avoid such unwanted op-
erations, the short circuit protection may block the earth fault protection on
external short-circuits. The closing of the generator breaker may cause tran-
sient residual currents. These currents may limit the sensitivity of the resid-
ual differential protection.
Let us now assume that each generator has a neutral point resistor.
To obtain selective clearance of earth faults, it is necessary to use a residual
differential protection. Figure 5 shows such a protection that is energised
from three-phase current transformers and one neutral point current
transformer.
Generally, it is necessary to clear earth faults on the buswork and on
the primary winding of the step-up transformers. To detect such faults, one
may use a zero sequence overvoltage protection. Three single-phase
voltage transformers connected to the primary winding of the step-up
transformer may energise the zero sequence overvoltage protection.
A B C
R
There are schemes that inject a subharmonic voltage into the pro-
tected plant. An overcurrent relay monitors the subharmonic current that
flows to the protected plant. An earth fault anywhere on the stator winding
will increase the subharmonic current. This scheme provides total coverage
of the entire stator winding. However, the cost of the implementation tends
to be high due to the cost of the injection equipment.
References
[1] Andersson, B., Broman, H., Eriksson, P.- A., Fredriksson, S. &
Lohage, L.: "Generatorskydd i Vattenkraftstationer", Rapport,
Vattenfall, November, 1982.
[2] Diesendorf, W. & Groß, E.: "Zur Theorie der Pohl'schen
Nullpunktsverlagerung für vollständigen Gehäuseschlußschutz",
E und M, vol. 54, no 22, pp. 253-256, 31 May, 1936.
[3] Evenson, O.: "Reläteknik för högspänningsanläggningar", Kom-
pendium, Lidingö, 1961.
[4] Griffin, C.H. & Pope, J. W: "Generator Ground Fault Protection
Using Overcurrent, Overvoltage, and Undervoltage Relays",
IEEE Trans. on Power Apparatus and Systems, vol. PAS-101,
no. 12, pp. 4490-4501, December, 1982.
[5] Schlake, R.L., Buckley, G.W. & McPherson, G.: "Performance
of Third Harmonic Ground Fault Protection Schemes for
Generator Stator Windings", IEEE Trans. on Power Apparatus
and Systems, vol. PAS-100, no. 7, pp. 3195-3202, July, 1981.
[6] Tideström, S. H:son (ed): "Ingenjörshandboken/Allmän Elektro-
teknik", 3rd ed., Nordisk Rotogravyr, Stockholm, 1959.
[7] Walker, C.W.: "Relay Protection in Hydro-Electric Power
Stations of the Snowy Mountains Authority", The Institution of
Engineers, Australia, Electrical Engineering Transactions, vol.
EET-5, no. 2, pp. 311-316, September, 1969.
[8] Wilheim, R. & Waters, M.: "Neutral Grounding in High Voltage
Transmission", Elsevier Publishing Co., New York, 1956.
References
[1] Andersson, B., Broman, H., Eriksson, P.- A., Fredriksson, S. &
Lohage, L.: "Generatorskydd i Vattenkraftstationer", Rapport,
Vattenfall, November, 1982.
[2] Blackburn, J.L.: "Protective Relaying, Principles and Applica-
tions", Marcel Dekker, New York, 1987.
[3] Bär, G., Grau, H.-W. & Kienast, L.: "Der Generatorschutz in
elektronischer Bauweise im Pumpspeicherwerk Wehr", Elektriz-
itätswirtschaft, vol. 78, no. 5, pp. 147-154, 1979.
[4] Henninger, K., Knütter, E.-F. & Schmiedel, K.: "Two-Step Rotor
Earth-Fault Protection of High Sensitivity for Synchronous Ma-
chines", Siemens Power Engineering, vol. 2, no. 1, pp. 13-17,
January, 1980.
[5] Horowitz, S.H. & Phadke, A.G.: "Power System Relaying", Re-
search Studies Press and John Wiley & Sons, Taunton and New
York..., 1992.
[6] Mason, C.R.: "The Art and Science of Protective Relaying",
John Wiley and Sons, New York, 1956.
[7] Tideström, S. H:son (ed): "Ingenjörshandboken/Allmän Elektro-
teknik", 3rd ed., Nordisk Rotogravyr, Stockholm, 1959.
CAPABILITY DIAGRAM
We have plotted the active power, P [MW] along the horizontal axis and
the reactive power, Q [Mvar] along the vertical axis. Here, we have
assumed that the terminal voltage is equal to the rated voltage. Many
capability diagrams have axes scaled in per unit, i.e., P/Sn and Q/Sn where
Sn [MVA] is the rated apparent power of the synchronous machine. The
rated apparent power, Sn, the rated voltage, Un, the synchronous reactance,
Xs, and the power factor (cosϕ) define the acceptable reactive limits in the
simplified capability diagram.
The rated apparent power and the rated voltage determine the rated
stator current. The stator current may only temporarily exceed the rated
current. During steady state, the synchronous machine must not operate
outside a circle with a radius equal to 1 per unit.
Let us assume that the active power P is zero. Now, it is not possible
to increase the reactive power to the rated apparent power. One cannot
reach the limit Q = Sn, because the excitation current becomes too high. It
must, however, be possible to operate the machine at P = Sncos(ϕ) and
Q = Snsin(ϕ). This determines the requirement on the excitation system and
the thermal design of the rotor. The reactive limit given by the highest exci-
tation current is also a circle. It passes the point ( P = Sncos(ϕ),
Q = Snsin(ϕ)) and has its centre on the negative reactive axes, theoretically
at Q/Sn = -1/Xs
UNDEREXCITATION PROTECTION
Q/U
P/U
An AIEE working group has prepared and sent out a questionnaire about
practice and experience of underexcitation protection. The group has ana-
lysed and documented [ 9 ] answers from 63 utilities in the US, Canada and
Mexico. The answers represented 309 generators rated at 60 MW or more,
installed since 1949. Already 1958, 72% of these generators had underexci-
tation protection. Of all utilities, 86% reported that their new generators
had underexcitation protection. Most of the underexcitation protections
tripped the generator.
The underexcitation relay tripped many generators during the North-
east Power Interruption on the 9 November 1965 and during the PJM Sys-
tem Disturbance on the 5 June 1967. Many questions were raised concern-
ing the correctness of these relay operations and whether they caused or
aided the disturbance. The IEEE Power System Relay Committee formed a
Tripping Chatacteristic
References
[1] Andersson, B., Broman, H., Eriksson, P.- A., Fredriksson, S. &
Lohage, L.: "Generatorskydd i Vattenkraftstationer", Rapport,
Vattenfall, November, 1982.
[2] Born, E. & Fischer, A.: "Elektronischer Untererregungsschutz",
Siemens-Zeitschrift, vol. 46, no. 12, pp. 912-915, December,
1972.
[3] Bär, G., Grau, H.-W. & Kienast, L.: "Der Generatorschutz in
elektronischer Bauweise im Pumpspeicherwerk Wehr", Elektriz-
itätswirtschaft, vol. 78, no. 5, pp. 147-154, 1979.
[4] Glebov, I.A., Danilevich, J.B. & Mamikoniants, L.G.:
"Abnormal Operation Conditions of Large Synchronous
Generators and their Influence on Design and Performance in a
Power System", Report 11-07, CIGRE-Session, Paris, 1976.
[5] Mason, C.R.: "A New Loss-of-Excitation Relay for Synchronous
Generators", AIEE Trans., vol. 68, pt. II, pp. 1240-1245, 1949.
[6] Mason, C.R.: "The Art and Science of Protective Relaying",
John Wiley and Sons, New York, 1956.
[7] Sarma, M.S.: "Synchronous Machines (Their Theory, Stability,
and Excitation Systems)", Gordon and Breach, New York, 1979.
[8] Walker, C.W.: "Relay Protection in Hydro-Electric Power
Stations of the Snowy Mountains Authority", The Institution of
Engineers, Australia, Electrical Engineering Transactions, vol.
EET-5, no. 2, pp. 311-316, September, 1969.
[9] "A Partial Survey of Relay Protection of Steam-Driven A-C
Generators", AIEE Committee Report, AIEE Trans., vol. 81, pt.
III (Power Apparatus and Systems), pp. 954-957, February,
1962.
[ 10 ] "Loss-of-Field Operation During System Disturbances", IEEE
Committee Report, IEEE Trans. on Power Apparatus and Sys-
tems, vol. PAS-94, no. 5, pp. 1464-1472, September/October,
1975.#
the hydro-generator may approach the runaway speed of the hydro turbine.
The runaway speed of a Francis turbine is about 150 to 200% of nominal
speed. For a Kaplan turbine, the runaway speed is about 200 to 300%. One
has to remember that the induced EMF is proportional to the product of the
rotational speed and airgap flux. The flux is approximately proportional to
the excitation current.
In EHV transmission systems, a load rejection at the receiving end of
a long transmission line may cause too high voltages even if the AVR and
the turbine governor at the sending end operate correctly.
The core material in modern power transformers will saturate if the
applied voltage is higher than 110 to 125% at rated frequency. A saturating
transformer will reduce the overvoltage because the excitation current to
the transformer will increase. The saturated magnetisation impedance may
decrease to 0.1% of the unsaturated value. Unfortunately, the flux in a
saturated transformer may reach magnetic objects outside the iron core.
Eddy current losses may very rapidly increase the temperature of such
objects. Such hot objects may also increase the temperature of the oil in the
transformer tank and increase the risk for dielectric failures. Such a
situation may occur during start-up and shutdown of unit-connected
generators. There is a risk that the operator switches over to automatic
voltage regulation before the rotational speed has reached 90% of rated
speed. He may also forget to switch over to manual excitation control
during a shutdown of the unit.
Tideström recommends [ 4 ] a dependent time overvoltage relay for
overvoltage protection. Such a relay has a short delay if the overvoltage is
very high. The delay increases with decreasing overvoltage.
The overvoltage protection system for the generators in the Snowy
Mountain Complex comprises, according to Walker [ 5 ] an overvoltage
relay and a timer. The overvoltage relay picks up if the voltage is higher
than 130% of rated voltage. The time delay is 2 s.
The overvoltage protection system should, according to Sarma [ 3 ],
have two steps if the generator does not have an AVR. In thermal power
plants the first step should pick up if the voltage exceeds 125%. For hydro
power plants, the corresponding figure is 140%. The first step should trip
without delay. The second step should pick up if the voltage is higher than
110% and should have a dependant time characteristic.
The synchronous machines in the pumped storage plant Wehr have,
according to Bär, Grau and Kienast [ 2 ], an overvoltage protection system
comprising a frequency compensated overvoltage relay and a timer. The
overvoltage relay picks up if the voltage is higher than 120% of rated
power. The time delay is 3 s.
References
[1] Andersson, B., Broman, H., Eriksson, P.- A., Fredriksson, S. &
Lohage, L.: "Generatorskydd i Vattenkraftstationer", Rapport,
Vattenfall, November, 1982.
[2] Bär, G., Grau, H.-W. & Kienast, L.: "Der Generatorschutz in
elektronischer Bauweise im Pumpspeicherwerk Wehr", Elektriz-
itätswirtschaft, vol. 78, no. 5, pp. 147-154, 1979.
[3] Sarma, M.S.: "Synchronous Machines (Their Theory, Stability,
and Excitation Systems)", Gordon and Breach, New York, 1979.
[4] Tideström, S. H:son (ed): "Ingenjörshandboken/Allmän Elektro-
teknik", 3rd ed., Nordisk Rotogravyr, Stockholm, 1959.
[5] Walker, C.W.: "Relay Protection in Hydro-Electric Power
Stations of the Snowy Mountains Authority", The Institution of
Engineers, Australia, Electrical Engineering Transactions, vol.
EET-5, no. 2, pp. 311-316, September, 1969.
will soon become overheated and damaged. The turbine overheats within
minutes if the turbine loses the vacuum. Steam turbines may eventually,
according to Mason [ 2 ], become overheated if the steam flow is so low
that the electrical power generation falls below 10%.
The critical time to overheating of a steam turbine varies, according
to Mason [ 2 ], from about 0.5 to 30 minutes depending on the type of
turbine. A high pressure turbine with small and thin blades will become
overheated more easily than a low pressure turbine with long and heavy
blades. The conditions vary from turbine to turbine and it is necessary to
ask the turbine manufacturer in each case. It is also prudent to measure the
reverse power during commissioning of new units.
Power to the power plant auxiliaries may come from a station service
transformer connected to the primary side of the step-up transformer.
Power may also come from a start-up service transformer connected to the
external network. One has to design the reverse power protection so that it
can detect reverse power independent of the flow of power to the power
plant auxiliaries.
Hydro turbines tolerate reverse power much better than steam tur-
bines do. According to Lohage and co-workers [ 1 ], only Kaplan turbine
and bulb turbines may suffer from reverse power. There is a risk that the
turbine runner moves axially and touches stationary parts. They are not al-
ways strong enough to withstand the associated stresses.
Ice and snow may block the intake when the outdoor temperature
falls far below zero. Branches and leaves may also block the trash gates. A
complete blockage of the intake may, according to Mason [ 2 ] cause
cavitation. The risk for damages to hydro turbines can justify reverse power
protection in unattended plants. According to GEC [ 7 ], geared units may
require reverse power protection. This is because the design of the gears is
for driving in one direction only.
A hydro turbine that rotates in water with closed wicket gates will
draw electric power from the rest of the power system. This power will be
about 10% of the rated power. If there is only air in the hydro turbine, the
power demand will fall to about 3%. It is prudent to measure these values
during the commissioning.
Diesel engines should, according to Mason [ 2 ] have reverse power
protection. The generator will take about 15% of its rated power or more
from the system. According to GEC [ 7 ], a stiff engine may require
perhaps 25% of the rated power to motor it. An engine that is well run in
might need no more than 5%. According to Sarma [ 4 ], diesel engine units
usually require reverse power protection with a setting of 15 to 25%. It is
Q Q
Operate Operate
Line Line
Margin Margin
P P
There is a risk that the generator breaker does not open on command from
the reverse power relay. Now, we are in danger. It is futile to start the
breaker failure protection from the reverse power relay. The operate value
of the breaker failure protection is usually higher than the operate value of
the reverse power relay. There is only a remote possibility that the breaker
failure relay will detect that the generator breaker has failed to open.
Let us consider a unit with a generator breaker on the primary side of
the step-up transformer. It has a unit breaker on the secondary side of the
step-up transformer. We can increase the dependability of the reverse
power protection by installing two reverse power relays. Two different sets
of instrument transformers should energise the reverse power relays. The
two reverse power relays should have approximately the same pick up
value. One reverse power relay should have a shorter delay than the other.
The first reverse power relay should trip the generator breaker and the
second relay should trip the unit breaker. With this, we can avoid necessary
interruption of the supply of auxiliary power through the step-up
transformer.
The demands on the reverse power protection are increasing. An
AIEE report [ 8 ] says that the reverse power relays may only give an alarm
immediately when power flows from the network to the generator. The re-
verse power relay should trip if the power reversal persists long enough to
cause damage to the turbine from overheating. A delay of at least one
minute will be permissible between the time when the power reversal starts
and tripping should occur.
An IEEE report [ 8 ] does not recommend any dedicated reverse
power protection. The interlocking system can provide certain reverse
power protection.
GEC points out [ 7 ] that the reverse power relay must detect active
power. The reactive power will not change very much when the active
power reverses. The reactive power seldom exceeds 60% of rated power.
This means that the phase angle between current and voltage may be as
high as 85o and may be either inductive or capacitive. This illustrates the
difficulties when designing a suitable reverse power relay. GEC also
mentions that there are sensitive three-phase power relays with a sensitivity
of about 0.5%.
According to Lohage and co-workers [ 1 ] the reverse power relay
must pick up if the active power from the network to the generator exceeds
2% of the rated power. They say that, the delay of should be from five to 10
seconds, depending on the type of turbine.
References
[1] Andersson, B., Broman, H., Eriksson, P.- A., Fredriksson, S. &
Lohage, L.: "Generatorskydd i Vattenkraftstationer", Rapport,
Vattenfall, November, 1982.
[2] Mason, C.R.: "The Art and Science of Protective Relaying",
John Wiley and Sons, New York, 1956.
[3] Neugebauer, H.: "Selektivschutz", Springer-Verlag, Berlin,
1955.
[4] Sarma, M.S.: "Synchronous Machines (Their Theory, Stability,
and Excitation Systems)", Gordon and Breach, New York, 1979.
[5] "Minimum Recommended Protection, Interlocking and Control
for Fossil Fuel Unit-Connected Steam Station. I - Overall
Protection", IEEE Committee Report, IEEE Trans. on Power
Apparatus and Systems, vol. PAS-92, no. 1, pp. 374-380,
January/February, 1973.
[6] "Power System Protection", vol. 1, 2 and 3, Application, Edited
by the Electricity Council, Peter Peregrinus, Stevenage, 1981.
[7] "Protective Relays Application Guide", 2nd ed., GEC Measure-
ment, 1975, 5th printing, October, 1983.
[8] "Relay Protection of A-C Generators", AIEE Committee Report,
AIEE Trans., vol. 70, pt. I, pp. 275-282, 1951.
0π (1)
I a = I sin (2πf - )
3
2π
I b = I sin (2πf - )
3
4π
I c = I sin(2πf - )
3
0π (2)
V a = V sin (2πf - + ϕ)
3
2π
V b = V sin (2πf - + ϕ)
3
4π
V c = V sin (2πf - + ϕ)
3
I a + a2 I b + a I c (3)
I2 =
3
and In is the rated stator current of the machine. The relative negative se-
quence current is therefore well defined and one can measure it.
Unbalanced loading may produce more severe heating than balanced three-
phase operation. Series faults close to the generator will cause negative se-
quence currents. Unsymmetrical faults may produce more severe heating in
three-phase synchronous machines than symmetrical faults. Typical condi-
tions and incidents that can cause unbalanced loading are:
• Single-phase loads close to the power plant.
• Untransposed transmission circuits.
• Unbalanced step-up transformers.
• Series faults in the transmission network.
• Series faults on the secondary side of the step-up transformer.
• Series faults on the primary side of the step-up transformer.
• Pole discrepancy in the generator breaker.
• Unbalanced shunt faults close to the power plant.
• Unbalanced shunt faults on the generator buswork.
16.1.3 Turbo-Generators
Generators without damper winding do not have well-defined paths for the
induced double frequency currents. The electromagnetic and thermal
GENPC160.DOC 2007-05-22 15.30
Unbalance Protection 16.3
utilisation increases steadily. This is especially true for the rotors in turbo-
generators. This means that the turbo-generators are very sensitive for
unbalanced loading. Much development work has been done and will be
done to improve the unbalance loading capability. One has to pay special
attention to the material of the slot wedges. When the conductivity of the
slot wedges is higher than the conductivity of the rotor body, most of the
induced double frequency currents will flow in the slot wedges. In several
modern generators, the slot wedges do not have electrical contact with each
other. This means that the current will flow from slot wedges to the rotor
and back again. This will cause severe local heating. The general opinion is
that it is important to secure good electrical contact between the slot
wedges and the rotor body.
16.1.4 Hydro-Generators
where:
i22(t) = the instantaneous negative sequence current as a
function of time; the current is expressed in per unit
based and
K = a constant.
where
In = the rated current of the generator [A] and
K = a constant [s] that is typical for the type of generator.
The constant K tells us how many seconds the machine can withstand a
negative sequence current equal to the rated current of the generator. The
constant K depends on the size of the generator and the method of cooling.
For most generators the value is from 5 to 30 s, but for some hydro-genera-
tor it may be as high as 60 s.
There are industry standards that determine the permissible
unbalance to which a generator is designed [ 4 ]. For turbo-generators with
Sn ≤ 800 MVA the requirement is:
K ≥ 10 (6)
K ≥ 10 - 0.00625(800 - Sn ) (7)
K [s]
10
K = 10 - 0.00625*( S - 800 )
0
0 500 1000 1500 2000
Rated Apparent Power, S [MVA]
High I2max
Maximum Time [ s ]
1000
100 High K
10
Low K
1
0.01 0.10 1.00 10.0
Negative Sequence Current [ pu ]
References
[1] Andersson, B., Broman, H., Eriksson, P.- A., Fredriksson, S. &
Lohage, L.: "Generatorskydd i Vattenkraftstationer", Rapport,
Vattenfall, November, 1982.
[2] Barkle, J.E. & Glassburn, W.E.: "Protection of Generators
Against Unbalanced Currents", AIEE Trans., vol. 72, pt. III
(Power Apparatus and Systems), pp. 282-286, April, 1953.
[3] Glebov, I.A., Danilevich, J.B. & Mamikoniants, L.G.:
"Abnormal Operation Conditions of Large Synchronous
Generators and their Influence on Design and Performance in a
Power System", Report 11-07, CIGRÉ-Session, Paris, 1976.
[4] Horowitz, S.H. & Phadke, A.G.: "Power System Relaying", Re-
search Studies Press and John Wiley & Sons, Taunton and New
York..., 1992.
[5] Mason, C.R.: "The Art and Science of Protective Relaying",
John Wiley and Sons, New York, 1956.
[6] "A Partial Survey of Relay Protection of Steam-Driven A-C
Generators", AIEE Committee Report, AIEE Trans., vol. 81, pt.
III (Power Apparatus and Systems), pp. 954-957, February,
1962.
[7] "Protective Relays Application Guide", 2nd ed., GEC Measure-
ment, 1975, 5th printing, October, 1983.
Often, the utilities do not tolerate loss of synchronism because of such con-
tingencies. Sometimes a utility may decide to delay investments and tempo-
rarily deviate from the reliability principles.
Severe stresses may result when a generator loses the synchronism
without having lost the excitation. Pole slipping is associated with high cur-
rent pulses and violent oscillations of the air gap torque in the generator.
Mason says [ 3 ] that it is not likely to lose synchronism with other
generators in the same station unless it loses excitation. Many units have
underexcitation protection. He concluded that it is not the usual practice to
provide out of step protection.
Synchronism can, according to GEC [ 4 ], be regained if the load is
sufficiently reduced, but if this does not occur within a few seconds it is
necessary to isolate the generator and then re-synchronise.
During the planning of the power plant Abwinden-Asten on the
River Danube, it was necessary to consider the long fault clearance time in
the connecting network. Each generating unit has a bulb turbine and the
turbine generator units have a low inertia constant. The low inertia
constants and the long fault clearance times made it necessary to install an
out of step protection. ELIN has, according to Dorfmeister [ 2 ], developed
an out of step protection. He does, however, not describe the method for
detection of pole slipping clearly. Static and dynamic estimation of the
rotor angel is a key task of the protection.
Hydro-generators owned by Vattenfall must not have out of step pro-
tection [ 1 ]. Some nuclear units in Sweden have a simple out of step pro-
tection. It comprises an overcurrent relay and some associated logic. After
three consecutive overcurrent pulses, it trips the unit.
References
[1] Andersson, B., Broman, H., Eriksson, P.- A., Fredriksson, S. &
Lohage, L.: "Generatorskydd i Vattenkraftstationer", Rapport,
Vattenfall, November, 1982.
[2] Dorfmeister, K.: "Betrieb und Erfahrung mit einem neuartigen
Stabilitätsschutz in der Mikroprozessortechnik", ELIN-
Zeitschrift, vol. 34, no. 3/4, pp. 58-61, 1982.
[3] Mason, C.R.: "The Art and Science of Protective Relaying",
John Wiley and Sons, New York, 1956.
[4] "Protective Relays Application Guide", 2nd ed., GEC Measure-
ment, 1975, 5th printing, October, 1983.
Breaker Head Flashover: The extreme dielectric stress in breakers and the
small contact gap spacing associated with their high-speed interrupting re-
quirement can lead to contact flashover. The risk of a flashover is higher
just before synchronisation or just after the unit is removed from service.
arcing between them and the rotor iron. The arc heating begins to melt the
metals.
Hydro Unit Damage: Heating of the damper windings and the rotor mate-
rial, combined with the lack of proper ventilation, will create damage
quickly.
Distance Relays: This scheme uses a distance relay located in the high-
voltage switchyard that is set to look into the machine. The relay should be
set to detect the sum of the generator step-up transformer and machine
transient reactance with an appropriate margin.
19.6 Conclusion
American utilities have observed that inadvertent energising of large
generators has significantly increased in recent years as generating stations
have become more complex. Operating errors, breaker head flashover,
control circuit malfunctions or a combination of these causes have resulted
in generators becoming accidentally energized. Major US turbine-generator
manufacturers have recommended, and many utilities are installing,
dedicated inadvertent energising protection systems.
References
Axial Shaft Flux: This source is due to the possibility that the turbine
cylinder/shell combination acts like a permanent magnetic generator. Both
the stationary and rotating turbine blades/buckets can be magnetised by
magnetostriction and can form an additional source of voltage. This is an
AC source rich of harmonics, but it is also a weak source. It is not very
important in turbine generators, although it is very important in high-speed
axial-flow compressors used in the petrochemical industry.
age waveform. This source is also weak and incapable of driving large cur-
rents, but again it can cause a breakthrough in the oil film.
References
[1] Ammann, C., Reicher, K., Joho, R. & Posedel, Z.: "Shaft
Voltages in Generators with Static Excitation Systems -
Problems and Solutions", IEEE Trans. on Energy Conversion,
vol. 3, no. 2, pp. 409-419, June, 1988.
[2] Andersson, B., Broman, H., Eriksson, P.- A., Fredriksson, S. &
Lohage, L.: "Generatorskydd i Vattenkraftstationer", Rapport,
Vattenfall, November, 1982.
[3] Buckley, G.W., Corkins, R.J. & Stephens, R.N.: "The
Importance of Grounding Brushes to the Safe Operation of Large
Turbine Generators", IEEE Trans. on Energy Conversion, vol. 3,
no. 3, pp. 607-612, September, 1988.
[4] "Relay Protection of A-C Generators", AIEE Committee Report,
AIEE Trans., vol. 70, pt. I, pp. 275-282, 1951.
A local back-up protection system has the advantage that it is the cir-
cuit breaker in the same station that carries out the back-up protection. This
is an advantage for the system operators.
An AIEE report [ 3 ] documents contemporary practice for back-up
protection in thermal power plants. Then, it was obvious that the big invest-
ments in the power plants motivate the existence of a back-up protection
system. Then, the equipment was more sturdy and the fault currents were
lower. It is not a surprise that the utilities then accepted remote back-up
protection systems.
An AIEE working group has prepared and sent out a questionnaire
about practice and experience of underexcitation protection. The group has
analysed and documented [ 2 ] answers from 63 utilities in the US, Canada
and Mexico. The answers represented 309 generators rated at 60 MW or
more, installed since 1949. In 1958, 19 utilities said that they had no back-
up protection for short circuits in the generator. On the other hand, 18 utili-
ties required back-up protection for short circuits in the generator, 15 utili-
ties required breaker back-up for short circuits in the generator, 20 utilities
required back up protection for the high voltage busbar, 14 utilities
required a breaker back up for short-circuits on the busbar, 29 utilities
required the tripping of the generator when the line protection failed to
operate. The working group recommended installation of back-up
protection to obtain the same level of reliability for generator faults as for
line faults.
The unit breaker and the generator breaker (if it exists) for hydro-
generators owned by Vattenfall shall, according to Lohage and co-workers
[ 1 ], have breaker failure protection using three or four current relays.
References
[1] Andersson, B., Broman, H., Eriksson, P.- A., Fredriksson, S. &
Lohage, L.: "Generatorskydd i Vattenkraftstationer", Rapport,
Vattenfall, November, 1982.
[2] "A Partial Survey of Relay Protection of Steam-Driven A-C
Generators", AIEE Committee Report, AIEE Trans., vol. 81, pt.
III (Power Apparatus and Systems), pp. 954-957, February,
1962.
[3] "Relay Protection of A-C Generators", AIEE Committee Report,
AIEE Trans., vol. 70, pt. I, pp. 275-282, 1951.
22.4 Conclusions
The two blackouts described above show the importance of co-ordinating
control system functions and protection system functions. It is not good
enough to co-ordinate the protection for the generator and the step-up trans-
former. In the setting of rotor current limiters and overcurrent protection it
is important not to restrict the capability of the unit by selecting typical set-
tings.
The IEEE survey shows that utilities in the US prefer to use distance
protection as phase back-up protection in favour of overcurrent protection.
It also shows that the neutral point overcurrent relay performs well as
backup protection. Another result is that it is difficult to achieve the desired
level of security. When a back-up protection maloperates during a power
system disturbance, there is a risk that it disconnects several units and
causes a very severe contingency. Few transmission systems can withstand
such contingencies.
References
[1] Van den Damme, R.: "The incident of August 4th 1982 of the
Belgian electricity system", Intercom, 12 September, 1983.
[2] "A survey of generator back-up protection practices", IEEE
Committee Report, IEEE Trans. on Power Delivery, vol. 5, no.
2, pp. 575-584, April, 1990.
[3] "Die Störung vom 12. Januar 1987, 11.42 Uhr", Unpublished
translation of an internal report from EdF, Mouvements
d'Energie, 2 February, 1987.