ENGM041 Unit 4
ENGM041 Unit 4
Two types of important reinforced concrete structural frames, braced and unbraced, are
examined. Design stresses depend on which type of structure is being built and it is
helpful at the outset of a design to be aware of the influence the „type‟ of structure has on
the stresses.
Braced Frames.
The deflections of the frame are relatively small (shown exaggerated in diagram) as the
frame relies on a stiff core or „shear wall‟ as a bracing element to carry lateral loads. The
floors transmit lateral forces to the bracing or shear wall which is much stiffer than the
columns.
Wind load
Braced Frame
Deflected frame Bracing wall
Unbraced frame.
Frame displacements are relatively large because the frame has to rely solely on the
stiffness of the columns to resist lateral forces.
Wind load
Deflected frame
Large deflection
Unbraced Frame
Original frame
Unbraced frame
Unbraced frame
– partly clad
Braced structure.
Braced frame
Horizontal forces
transmitted to the central
core via the core.
Analysis of structures.
1. The overall structure is examined for stability. The loads which produce the worst
possible situation for toppling or sliding of the structure are placed on the floors and
walls of the structure and its overall stability is assessed. Characteristic loads and partial
factors are included. In this process, it must be assumed that the structure acts as a single
element (usually) and is sufficiently strong to be rigid. The overall stability is checked.
It is usual to check before the complete design is undertaken making assumptions about
imposed loads and element sizes. It may be prudent to check the stability again after the
design. Partial factors from Table NA.A1.2(A) are used.
To give some guidance of how the code considers analysis, the general introduction to
the section on structural analysis is attached.
(1)P The purpose of structural analysis is to establish the distribution of either internal
forces and moments, or stresses, strains and displacements, over the whole or part of a
structure. Additional local analysis shall be carried out where necessary.
Note: In most normal cases analysis will be used to establish the distribution of internal forces and
moments, and the complete verification or demonstration of resistance of cross sections is based on these
action effects; however, for certain particular elements, the methods of analysis used (e.g. finite element
analysis) give stresses, strains and displacements rather than internal forces and moments. Special methods
are required to use these results to obtain appropriate verification.
(2) Local analyses may be necessary where the assumption of linear strain distribution is
not valid, e.g.:
- in the vicinity of supports
- local to concentrated loads
- in beam-column intersections
- in anchorage zones
- at changes in cross section.
(3) For in-plane stress fields a simplified method for determining reinforcement may be
used.
Note: A simplified method is given in Annex F.
(4)P Analyses shall be carried out using idealisations of both the geometry and the
behaviour of the structure. The idealisations selected shall be appropriate to the problem
being considered.
(5)P The effect of the geometry and properties of the structure on its behaviour at
each stage of construction shall be considered in the design
(7) In buildings, the effects of shear and axial forces on the deformations of linear
elements and slabs may be ignored where these are likely to be less than 10% of those
due to bending.
Although concrete structures only behave elastically under small loads, while the sections
remain un-cracked, a linear elastic analysis may still be used for both the serviceability
and ultimate limit states to determine the internal forces and moments, provided the
structure has sufficient ductility to distribute moments from highly stressed regions to
less highly stressed regions.
Sections 5.4 and 5.5 are included and give the rules for using linear elastic and linear
elastic analysis with limited redistribution of moments. Only these aspects of the analysis
of concrete structures are considered.
(2) For the determination of the action effects, linear analysis may be carried out
assuming:
i) uncracked cross sections,
ii) linear stress-strain relationships and
iii) mean value of the modulus of elasticity.
(3) For thermal deformation, settlement and shrinkage effects at the ultimate limit state
(ULS), a reduced stiffness corresponding to the cracked sections, neglecting tension
stiffening but including the effects of creep, may be assumed. For the serviceability limit
state (SLS) a gradual evolution of cracking should be considered.
This clause is included later in this document in the section associated with moment re-
distribution.
This module does not attempt to cover structural analysis in great detail but in the
following sections and techniques for modelling structures are presented.
Modelling structures.
Analysing the complete three dimensional structure. This is not often undertaken
and is a lengthy and complex process but sometimes has to be undertaken. Finite
elements is the usual method used.
Dividing the structure into two dimensional frames. These are much simpler to
analyse and very often due to repetition, only relatively few frames need to be
analysed.
Dividing two dimensional frames into sub frames. A sub frame consists of the
beams at one level together with the columns above and below.
This latter method, is used extensively because repetition of sub-frames is likely and the
analysis is sufficiently simple so that hand methods (Moment Distribution) can be
employed. It can be used for both braced and unbraced frames but because unbraced sub
frames have to consider the effects of horizontal loads, the method has no great
advantage over a full frame analysis in which case a more sophisticated technique of
analysis is recommended.
The following sections consider how braced frames can be subdivided into sub
frames.
2. Reduce this to form a full sub-frame. The ends of the columns remote from the beams
are generally assumed to be fixed, unless for some reason the assumption they are pinned
is more rational as may be the case at the base.
Stiffness halved
Stiffness
halved
In the partial sub-frame and single column cases, the assumption of fixed ends to the
outer beams over estimates the stiffness. These values are therefore halved to allow for
the flexibility resulting from continuity
Load combinations.
Details of how to combine loads are given in unit 3. Debate over what factors should
be used is on going but factors acceptable to the UK have nevertheless been
recommended and are in the following Table
Example of Load combinations and partial factors for the ultimate limit state.
Load Permanent load Wind
combination Unfavourable Favourable Unfavourable Favourable
1. Permanent 1.35 1.0 1.5 0.0 -
+ variable
2. Permanent 1.35 1.0 - - 1.5
and wind
3. Permanent 1.35 1.0 1.5 0.0 0.75
+ variable +
wind
4. Permanent 1.35 1.0 1.05 0.0 1.5
+ variable and
wind
Notes. 3. Wind is the secondary variable load = 1.5 x 0.5 = 0.75 {1.5 x ψo (wind)}
4. Variable load is the secondary “variable” load = 1.5 x 0.7(non-storage)
= 1.05 {1.5 x ψo (office say)}
Loading arrangements.
Patterns of load are chosen to produce the worst effects on the structure. In the
following, the effect of vertical load on a sub structure is examined. In the frame
considered, no columns are assumed to exist above the beam.
In general, to maximise the moment in a span, that span must carry the maximum load,
adjacent spans the minimum, and the spans next to those, the maximum. This produces
two patterns of loading, generally called load cases.
Load case 1
Mmax Mmax
Load case 2
maximum minimum maximum minimum maximum
In general, to maximise the support moments, the adjacent spans must carry the
maximum load and the next spans must alternate with minimum and maximum load.
This produces (n-1) load cases where n is the number of spans. The maximum moment
at the end supports is produced by the alternate loading arrangement described
previously.
The code, however, suggests that the maximum support moments are calculated from two
adjacent spans carrying the maximum load and all other spans carrying the minimum
load so the load cases will look like. With the two load cases to produce the maximum
span moments, this gives (n + 1) load cases.
Load case 1
minimum minimum minimum maximum maximum
Mmax
Load case 2
minimum minimum maximum maximum minimum
Mmax
Load case 3
minimum maximum maximum minimum minimum
Mmax
Load case 4
maximum maximum minimum minimum minimum
Mmax
(a) alternate spans carrying the design variable and permanent load (γ Q + γ G + P ), other spans carrying
Q k G k m
(b) any two adjacent spans carrying the design variable and permanent loads ( γ Q + γ G + P ). All other
Q k G k m
Examination of the table above indicates the UK permits a single load case of all spans
loaded to determine the maximum support moments provided that the resulting moments,
except those at the supports of cantilevers are reduced by 20% with a consequential
increase in the span moments. (See also moment re-distribution)
In a one way spanning slab, the area of each bay exceeds 30m2.
Ratio of the variable load Qk to the permanent load Gk does not exceed 1.25
The variable Qk does not exceed 5kN/m2.
UK additional situation
maximum maximum maximum maximum maximum
Loading arrangements.
Loading patterns or cases show us where to apply the maximum and minimum loads but
not what the values of these loads are. If Gk is the characteristic permanent load and Qk
the characteristic imposed load, then the maximum and minimum loads likely are :
The table entitled, Example of Load combinations and partial factors for the ultimate
limit state on page 4.9 has been used to derive the above.
Note. In b2) of Table NA.1 it is noted that the same value of γG should be used
throughout the structure. This would usually be taken as 1.35.
Forms of loading.
Consider the two, one way spanning slabs CABD and ABFE, supported along CD, AB
and EF.
This could be produced by a one way spanning slab or as direct loading on a beam say by
a wall and beam self weight. In our example, if w is the slab design load per square
metre then, UDL along AB = wa kN/m
a C b
This is the reaction of a secondary beam spanning onto a main beam, or column
supported by a beam or a direct load. A point load will exist at A and B, the value as
indicated in the diagram above.
These are produced by a two way spanning slab. The area of load apportioned to each
beam is calculated by projecting lines which bisect the corner angles as shown.
Moment distribution
Member stiffness.
The greater the stiffness of a member, the more moment it will attract.
The stiffness of a member also depends on the degree of fixity at the ends.
k = EI/L k = 0.75EI/L
k=EI/l
Distribution Factors.
Using the member stiffnesses we calculate the proportion of the total stiffness at a
connection that each member provides. Distribution factors enable the proportioning of
the stiffness.
k2 f2
k1 k3 f1 f3
k4 f4
Total stiffness at a connection is – f1 = k1/kt f2 = k2/ft
k1 + k2 + k3 + k4 = kt f3 = k3/ft f4 = k4/ft
f1 + f2 + f3 + f4 = 1.0
Fixed end moments.
These are the moments at the fixed ends of a member due to a given vertical load. The
values for a uniformly distributed load (UDL) acting on the whole of a span and a point
load are shown. The formulae for other loading situation can be found in many reference
books.
Ma = Wab2/L2 Mb = Wa2b/L2
Sign convention.
A three span beam has fixed ends. The outer spans are 5.33m in length, and the inner
span 8.0m long. The beam is of the same section throughout and so EI is a constant
hence we only require relative stiffnesses. For this purpose assume EI = 100, say (EI
cancels out through all the terms so 100 is chosen simply for convenience). There is a
uniformly distributed load of 36k N/m over the beam.
Distribution factors.
Step 3.
Out of balance moment = - (213.35 – 85.23) = -128.12
Distribution to left of support = 128.12 x 0.4 = -51.25
Step 1. Distribution to right of support = -128.12 x 0.6 = -76.87
Distributed moment Carry over to left = 0.5 x -51.25 = -25.62
= - 85.23 x 0 = 0 Carry over to right = 0.5 x -76.87 = -38.43
Step 2.
Out of balance moment = - (85.23 – 192.0) = 106.77
Distribution to left of support = 106.77 x 0.6 = 64.06
Distribution to right of support = 107.77 x 0.4 = 42.71 Step 4.
Carry over to left = 0.5 x 64.06 = 32.03 Distributed moment
Carry over to right = 0.5 x 42.71 = 21.35 = 85.23 x 0 = 0
Boxed numbers below the beam only indicate the method and are to be omitted.
The diagram above indicates the first iteration of the moment distribution process. The
bold unboxed numbers are the moments at the fixed ends and either side of the supports
after the first distribution. This process is repeated until the out of balance moments are
small.
Step 3.
Out of balance moment = - (165.95 – 162.10) = -3.85
Distribution to left of support = 3.85 x 0.4 = -1.54
Step 1. Distribution to right of support = 3.85 x 0.6 = -2.31
Distributed moment Carry over to left = 0.5 x 1.54 = -0.77
= - 53.02 x 0 = 0 Carry over to right = 0.5 x 2.31 = -1.12
Step 2.
Out of balance moment = - (149.29 – 174.91) = 25.62
Distribution to left of support = 25.62 x 0.6 = 15.37
Distribution to right of support = 25.62 x 0.4 = 10.25 Step 4.
Carry over to left = 0.5 x15.37 = 7.69 Distributed moment
Carry over to right = 0.5 x 7.69 = 3.85 = 46.80 x 0 = 0
Boxed numbers below the beam only indicate the method and are to be omitted.
The diagram above indicates the second iteration of the moment distribution process.
The bold italicised numbers are the moments at the fixed ends and either side of the
supports after the second iteration. It can be seen that the out of balance moments are
already small.
The process is repeated until the out of balance moments are sufficiently small to be
ignored.
At this stage all that is known are the support moments. To obtain the actual moments in
the beam the free bending moments from loads between supports are superimposed on
the beam end moments.
165.32 165.32
45.18
45.18
The shear force along a beam is the summation of the individual effects of end moments
and loads.
73.4
Combining the two diagrams gives for
the end span : 95.9 - 22.5 = 73.4kN -118.4
and -95.9 - 22.5 = - 118.4kN
144
Combining the two diagrams gives for
the centre span : 144 - 0.0 = 144kN -144
and -144 - 0.0 = - 144kN
The above information now enables us to assemble the final shear force diagram for the
beam.
C
73.4
144 D
118.4
95.9
-22.5
118.4
144
A
B
Using virtual work or similar analytical methods, the reactions at A, B, C and D can be
found. They would be the same as the sum of the shear forces at the ends of the beams
spanning onto the support :
Reaction at A = 73.4kN
Reaction at B = 144 + 118.4 = 262.4kN
Reaction at C = 118.4 + 144 = 262.4kN
Reaction at D = 73.4Kn
Determine the shear force diagram if a = 4m, b - 2.5m and W = 260kN in the beam
shown.
W
a b
a b
Wb/L
-Wa/L
In most practices analysis of all elements is undertaken using some form of computer
package. To undertake the moment distribution of the sub frames in a 10 storey building
would be most unusual these days. With computer software, errors are reduced although
it is important to always check the moments using wL2/8, or wL2/12 depending on the
fixity to ensure you are not an order of 10 out. Engineers call this “having a feel” for the
structure. In reality it is unlikely that any project which is big would not be checked at
least four or five times.
Further if there are a number of load cases it can be seen that the number of computations
rapidly expands.
Coefficients are given in unit 9 for 1 and 2 way spanning slabs with a variety of edge
conditions. Alternatively Tables 15.2 and 15.3 of the Concise Eurocode may be used, the
latter table being relevant to beams..
Geometric imperfections.
The need to allow for geometric imperfections is covered in Clause 5.2 of the code the
text of which follows. Imperfection calculations refer only to column design.
(1)P The unfavourable effects of possible deviations in the geometry of the structure and
the position of loads shall be taken into account in the analysis of members and
structures.
Note: Deviations in cross section dimensions are normally taken into account in the material safety factors.
These should not be included in structural analysis. A minimum eccentricity for cross section design is
given in 6.1 (4).
(2)P Imperfections shall be taken into account in ultimate limit states in persistent and
accidental design situations.
(4) The following provisions apply for members with axial compression and structures
with vertical load, mainly buildings. Numerical values are related to normal execution
deviations (Class 1 in ENV 13670). With the use of other deviations (e.g. Class 2), values
should be adjusted accordingly.
where :
θo is the basic value:
αh is the reduction factor for length or height: αh = 2/ √l ; 2/3 ≤ αh ≤ 1.
There will be no reduction for members up to 4.0m. Members in excess of
9.0m get no further benefits.
αm is the reduction factor for the number of members: αm = (0,5(1+1/m))0.5
Note for 1 member, αm = 1.0.
l is the length or height [m], see (6)
m is the number of vertical members contributing to the total effect
Note: The value of θ0 for use in a Country may be found in its National Annex. The recommended value is
1/200
(6) In Expression (5.1), the definition of l and m depends on the effect considered, for
which three main cases can be distinguished (see also Figure 5.1):
(7) For isolated members (see 5.8.1), the effect of imperfections may be taken into
account in two alternative ways a) or b):
Note: Eccentricity is suitable for statically determinate members, whereas transverse load can be used for
both determinate and indeterminate members. The force Hi may be substituted by some other equivalent
transverse action.
(8) For structures, the effect of the inclination θi may be represented by transverse forces,
to be included in the analysis together with other actions.
Hi = θi . Na (5.6)
(9) As a simplified alternative for walls and isolated columns in braced systems, an
eccentricity ei = lo/400 may be used to cover imperfections related to normal execution
deviations (see 5.2(7)).
Redistribution of moments.
(1)P The influence of any redistribution of the moments on all aspects of the design shall
be considered.
(2) Linear analysis with limited redistribution may be applied to the analysis of structural
members for the verification of ULS.
(3) The moments at ULS calculated using a linear elastic analysis may be redistributed,
provided that the resulting distribution of moments remains in equilibrium with the
applied loads.
Where:
Note: The values of k1, k2, k3 , k4, k5 and k6 for use in a Country may be found in its
National Annex. The recommended value for k1 is 0,44, for k2 is 1,25(0,6+0,0014/εcu2),
for k3 = 0,54, for k4 = 1,25(0,6+0,0014/εcu2), for k5 = 0,7 and k6 = 0,8.
εcu2 is the ultimate strain according to Table 3.1. In table 3.1 εcu2 = εcu3 so this
information also refers to the rectangular stress block. Values from the UK National
Annex follow.
(5) Redistribution should not be carried out in circumstances where the rotation capacity
cannot be defined with confidence (e.g. in the corners of prestressed frames).
(6) For the design of columns the elastic moments from frame action should be used
without any redistribution.
εcu2 = εcu3
Practical outworking.
Interior span of a continuous Same beam but with ends Same beam but simply
rectangular beam of length L fully fixed supported.
and subject to a uniform load
of w/m per metre
wL2/8
2
wL /8
wL2/8
wL2/12
wL2/16
The overall value of moment between span and supports remains the same, it‟s just
the distribution of the moment that changes.
The most important conditions which can be gleaned from the code clauses are :
When =1.0, x/d = 0.6, and when =0.7, x/d = 0.3. The Concrete Centre and Mosley,
Bungey and Hulse, recommend limiting x/d to 0.45. Based on this the following table
can be derived.
δ x/d theoretical x/d as used in code
1.0 0.6 0.45
0.95 0.55 0.45
0.9 0.5 0.45
0.85 0.45 0.45
0.8 0.4 0.4
0.75 0.35 0.35
0.7 0.3 0.3
A three span continuous beam is analysed using conventional elastic analysis. Three load
cases are assessed and these are given in the Figure below. Spans are not equal
The load case which produces the maximum support moments of 452 and 550kNm does
not produce the maximum span moment of 375kNm. If the maximum support moments
were reduced to the maximum support moments produced by the maximum span moment
case, namely 358 and 349kNm, we would produce an identical moment diagram because
both load cases have maximum loading on the span. Identical in this context means of
the same shape and overall value, but obviously in different vertical positions. Therefore
we can reduce the maximum support moments without increasing the maximum span
moment. The bending moments from each load case are given in the figure below.
550
452
349
358 240
max max max
144
min max min
375
Redistribution in accordance with the code.
For high ductility steel the code permits a 70% reduction in moment thus :
However there is no advantage in reducing 452 below 358 as this is the value of the
support moment for the min max min case. Consequently we are only able to reduce
moments by 21% in this case.
If we then superimpose the free bending moment from this load case on support moments
of 358 and 385, the diagram shown below is obtained.
Redistributed moment
diagram 550
452
349
358 240
144
375
At first sight it seems as if we have gained something for nothing and to some extent this
is true. In practice sufficient plasticity over the supports to ensure moment re-distribution
can occur must be ensured. This achieved by limiting the depth to the neutral axis and is
covered in more detail in unit 5.
This is obtained by selecting the greatest positive (span) moments and negative (support)
moments at each section along the beam, bearing in mind that we select 70% of the
support moments (or moments which will influence the amount of top steel in the beam)
and that in certain regions of the beam 70% reduction may not be appropriate as at the
left of the above span.
Envelope representing 70% of
maximum ultimate moments 550 385
452 349
358 240
144
375
FINAL BENDING MOMENT ENVELOPE AFTER RE-DISTRIBUTION
The span above has been considered in isolation to explain the process of re-distribution
and to satisfy the conditions given in the code.
In practice, we have to consider the effects of moment re-distribution on all spans, for
example reducing a support moment for a given load case, not only increases the span
moment in this span but also in the adjacent span.
Consider a beam, where the flexural resistance is equal at the centre and supports and
with uniformly distributed load. Ultimate moments according to elastic theory give a
central moment of half the support moments.
Loading diagram
Wl2/12
Ultimate moments
2
Wl /24
As the load is increased the beam continues to behave elastically until the plastic moment
of one or more critical sections is reached. In this example this will occur at the supports.
If this load is wkN/m, then :-
Further loading of the beam will cause the plastic hinges to rotate although they will still
sustain their moment. The extra moment required to balance the load is carried by other
parts of the beam. This continues until the mid section of the beam reaches its plastic
moment at which point the beam becomes a mechanism and collapses.
Three plastic hinges resulting in a
mechanism
Collapse mechanism
At collapse, wL2/12 (at the centre) = wL2/24 + waL2/8, assuming wa is the additional load
required to cause final collapse. wa = w/3.
From the design point of view, the collapse moment is 1.33 x the elastic capacity, this
being achieved by plastic behaviour at the supports, brought about by re-distribution.
The percentage by which a moment is reduced from the elastic value is a measure of the
rotation of the hinge. Design can therefore be undertaken by applying a limited amount
of re-distribution to the elastic analysis. This is limited to 30% for high ductility steel to
restrict the rotation of the hinge.
The design of the critical sections must then be such that they can sustain the rotations
implied by the re-distribution. This is achieved in practice by limiting neutral axis depth.
See Clause 5.5(4)
Re-distributed
moment diagram
Re-distributed
moment diagram
The bending moment diagram for service loading, gives a region „x‟ where no
reinforcement (in the top of the beam) is required for the ultimate load condition. Wide
cracking could occur in this region but supplying reinforcement to carry at least 70% of
the maximum moment at any section means that the behaviour will remain roughly
elastic at loads equal to or less than 70% of total ultimate load.
The loading corresponding to serviceability limit state is always less than this, and thus
the possibility of wide cracking is eliminated.
Shear force diagrams must therefore be calculated after re-distributing the bending
moments. This may increase or reduce the shear values.
It is therefore considered prudent to use the worst of the re-distributed and un-distributed
shear forces as the design values.
Shear walls.
Introduction.
In reinforced concrete framed structures, the effect of wind forces and earthquake actions
increase in significance as the structure increases in height. Codes of practice impose
limits on horizontal movement or sway. One way to limit the sway and reduce horizontal
movement is to increase the section sizes to create a more rigid frame with greater
horizontal resistance but doing this increases column and beam sizes and the overall cost
of a building. This technique is rarely used in structures beyond 7 - 8 storeys. Another
way of stabilising a building is to provide stiff shear resisting walls linked to a flexible
frame. The wall can be external or internal such as the walls around the lift and service
shafts. With some oversimplification, the stiff walls called „shear walls‟ resist the lateral
forces whilst the frame supports the vertical loads.
Framed structure.
Typical Examples.
Shear walls are at either side of the building with splayed columns at the base.
Shear walls exist either side. A lift shaft near one end provides additional lateral support.
This building is curved in plan and includes shear walls at either end. These are at 90o to
each other providing good lateral resistance to the building. In addition each shear wall is
flanged in section to provide additional support.
Monolithic shear walls are classified as short, squat or cantilever according to their
height/depth ratio.
1. Plane in section.
2. Flanged in section
3. Channel in section. Lift cores.
These are two walls coupled by beams or slabs, usually because there are openings in the
wall (e.g. lift opening). With coupled shear walls the stiffness of the connecting beam or
slab will determine how effective the shear wall is as a whole.
Connecting beams
Connecting slabs
1. If a building is to have two shear walls the best position for them is at the centre of
each half of the building i.e. at the quarter points.
The shear walls provide lateral stiffness in the direction of the arrow although in reality
this would be a udl across the building. Stiffness in this example in the other direction is
supplied by the columns.
Shear walls –
shown grey
The lift shaft provides lateral resistance in both directions, but as it is eccentric, the
building as a whole will be subject to torsional effects and needs to be designed for these.
If at all possible, symmetrical arrangements are preferred.
1. Rigid frames and short shear walls subjected to horizontal forces, deflect in a near
pure shear form.
2. Cantilever shear walls (tall walls) deflect in a flexural manner.
3. Squat and coupled shear walls deform in a manner intermediate between shear
and beam flexure.
4. A symmetrical form of structure implies all elements deform in the same way and
in the direction of the horizontal force.
5. The high stiffness of the floors also ensures all elements achieve identical
deflection profiles provided the structure is symmetrical.
6. Frames and walls do not attract the same proportion of load throughout their
height. The shape of the deflection curves indicate that a rigid frame attracts a
higher proportions of the load near the top whereas a shear wall tends to attract
more of the horizontal force near its base.
A coupled shear wall consists of two or more shear walls in the same plane joined by
beams or slabs at each floor level. Usually coupled walls are a single wall with openings.
If the stiffness of the linking beams or slabs is low compared to the walls or if the joint
between the beam and wall is inadequate allowing hinge like behaviour, then the shear
wall will in effect need to be designed as two walls linked by the beam or floor elements
which only transmit axial (horizontal) loads. The two walls will have the same deflection
profile but in reality the forces in the connecting beams will vary with height and this will
alter the deflections slightly. In many practical instances the joint between connecting
beam and shear wall is rigid and the connectors are relatively stiff.
1. Flexural failure
2. Horizontal shear failure
3. Vertical shear failure.
Shear
tension
crack
Yielding Crushing
With symmetrical shear forces, there is no torsional effect so only direct forces need be
considered.
0.3m 0.3m
29.7m
0.3m
0.3m 0.3m
D
A
19.4m
C
B
12m
0.3m
5m 20m 5m
15m 15m
100kN
Consider the forces in one direction at a time. Ignore the resistance of shear walls
orthogonal to the direction of force. The diagram below illustrates the principle.
E
Basic principle 2 - Applied forces
Typical shear C
A c provide a rotating moment to the
wall c building which acts about the
centre of rotation of the building.
Centre of rotation (cr).
xc
Shear centre
H
rcx
x(cr)
t e
D
yc Shear walls
B shown hatched
b
F
X
x – usually L/2 Fy – Horizontal force on building
usually due to wind but possibly
Basic principle 1 - Applied earthquake forces
forces on a building act at the
mid point of the length
Non-symmetric
shear walls
Y xc y
E
C
A x x y
Shear centre
xcr D yc
Centre of rotation
ycr
B F
X
( k x x ) ( k y y )
x( cr ) y( cr )
k x k y
Y
C
E
A
e = L/2 - xcr D
Centre of rotation
B F
X
Fy
L/2 L/2
My = Fy e
Pc Pdirect Ptorsional
Pc – Force acting on wall c
Pdirect – Direct force acting on wall c {Determine as before}
Ptorsional – Force due to torsional moment acting on c
k cx k cx rcx
Fy My
Pc
k x
k x rx2
Direct component Torsional component
Notation
• kcx – stiffness of wall c in x direction (about y axis).
• Σkx – Sum of the stiffnesses of all shear walls in x direction (about y axis).
• rcx – distance of centre of gravity of wall C from centre of rotation (cr) of building
perpendicular to Fy
• Σ(kx rx2) - Sum of the stiffnesses of individual walls in the x direction (about x
axis) multiplied by the square of the distance between the centre of gravity of the
wall and the centre of rotation of the building in a direction perpendicular to Fy
The following derivation applies to walls bending about the x-x axis.
Where :
M - resisting moment due to torsional effects
Fix – Force I wall I in x direction. i.e. Force is orthogonal to x – x
rix – Distance of wall i from shear centre in a direction parallel to x – x.
Where :
Mix Resisting moment of wall i in x direction due to torsional effects
So K = M/(Σkix rix2)
M
And so Fix k ix rix
k ix rix
2
M
Fcx k cx rcx
k ix rix
2
Example.
A wind load of 100 kN acts on the south face of a building. Determine the force the
shear walls A, B, C and D each carry as a result of the wind force Fy.
Y 40.15m
0.3m 14.55m 0.3m 0.3m
A
10m
C
Centre of rotation (cr). D
Shear centre
20m
rcx
x(cr)
0.3m e
yc Shear walls
B shown hatched
5m
b
F
10m X
Fy – Horizontal force on building
usually due to wind but possibly
20m earthquake forces. Assumed to
act 20.0m from Y axis
A 0.3 20 200
B 0.3 5 3.125
C 0.3 10 25.0
D 0.3 20 200
k cx k r
For typical wall C : Pc Fy M y cx cx2
k x
k x rx
1. Shear walls are designed as storey high panels which are restrained laterally at
each floor level.
2. Panels are designed to resist axial compressive forces, in plane moments MZ and
sometimes transverse moments My.
N
My Mz
Hw
x
z
y Lw
Total section in
compression :
Mz/N≤Lw
Tensile forces in
section Mz/N≥Lw
Design Procedure.
Where Hw/Lw >1, flexure will govern the failure but when Hw/Lw is small shear
failure will occur.
Example.
Consider a shear wall 5m long and 150mm thick which is subject to a factored axial load
of 6000kN, Mz = 3625kNm and My = 290kNm. Find the maximum compressive stress in
the wall due to N and Mz. Assume horizontal transverse restraint every 3.5m (floor
level).
Divide the wall into sections, say 500mm long and design each as a column subject to an
axial load and a moment. Start with the most heavily loaded section at the end of the
wall.
This problem now becomes :- Design a column which is 500mm long and 150mm wide.
The column is subject to factored axial loads and transverse moments of 991kN and
29kNm.
Only the most highly stressed sections of the wall need be considered and Mz is usually
considered reversible. Different areas of reinforcement are required (at the extreme
fibres) in each of the sections, but in most cases the reinforcement required in the end
section is provided across the whole wall.
150
Design each end zone as a column subject to axial load of 805.5 + 600 = 1405kN and a
moment of 29kNm (290 x 500/5000)
Design the middle zones as columns subject to an axial load of 600kN and a moment of
29kNm.
There is no method in the code for checking the in-plane shear force. However, the
following assumptions are suggested as being reasonable.
The critical section for shear is taken at a distance from the base of the wall as the lesser
of 0.5Lw and 0.5Hw, where…..
The shear resistance of the section without shear, VRd,ct is taken to be the minimum
design shear resistance of the concrete, thus ……..
Where :-
vmin = 0.0035k1.5fck0.5
K = 1 + (200/d)0.5
ζcp = NEd/Lwt
Leff = αLw with say α = 0.8 – 0.9
Detailing requirements.
Typical details.
1. Determine the final bending moment and shear force diagrams and the reactions
for the beam in Figure 1. All beams have the same stiffness, I.
80kN D
A B C 18kN/m
2. Determine the final bending moment and shear force diagram and reactions for
the beam in Figure 2.
50kN 100kN
A B 10kN/ D
C
m
2.5m
5.0m 5.0m 5.0m 5.0m
FIGURE 2
3. Find the bending moment diagram for the frame shown in Figure 3. Also
evaluate the propping force P.
13.5kN/m
Prop P
B I=2 C
3.33m
I=1
I=1
5.0m
A FIGURE 3
3.33m
4. Determine the bending moment and shear force diagrams and the reactions. for
the beam shown in Figure 4. EI is constant.
65kN/m
32.0kN/m
A B C
FIGURE 4
3.0m 3.6m
5. How would you determine the moments (and shears) in a braced as opposed to an
un-braced frame.
6. What are the benefits of moment re-distribution and to what extent can it be
undertaken in a beam.
i. Determine the design axial force on the top of the foundations below X.
You may assume half the slab loads are shed to the beams either side,
and half the beam load are shed to the columns (or shear walls) either
end.
[4 marks]
ii. Determine the end (top and bottom) moments on column X between the
first and second storey about axis VV. Assume column moments result
from the beams entering the column only and that the columns above
and below do not affect the moments. Assume the ends of the beam at
W and Y are fully fixed.
[8 marks]
iii. Determine the bending moment diagram for the beam WXY.
[3 marks]
.
i. The axial force on section AC of the wall due to slab and self weigh
effects.
[4 marks]
ii. The axial force on section AC due to the building being subject to a
wind load in the direction of F of 0.5kN/m2.
[6 marks]
A U
5.0m 5.0m 5.0m 100mm
Indicates direction of
span of simply supported
C W precast slabs
1000mm
6.0m
Shear walls
V X V
6.0m
B Y
U
F
Seventh floor
24 000mm
Second floor
First floor
Ground bearing slab
Ground floor
2000mm
FIGURE Q7
Learning outcomes.
Question 1.
Determine the final bending moment and shear force diagrams and the reactions for the
beam in Figure 1. All beams have the same stiffness, I.
80kN D
A B C 18kN/m
Stiffness of beam I I I
Stiffness Factor
Question 2.
Determine the final bending moment and shear force diagram and reactions for the beam
in Figure 2.
50kN 100kN
A B 10kN/ D
m C
2.5m
5.0m 5.0m 5.0m 5.0m
FIGURE 2
Stiffness of beam I 2I 3I
Stiffness Factor
ModStiff Factor
Distribution factors
Question 3.
Find the bending moment diagram for the frame shown in Figure 3. Also evaluate the
propping force P.
13.5kN/m
Prop P
B I=2 C
3.33m
I=1
I=1
5.0m
A FIGURE 3
3.33m
Question 4.
Determine the bending moment and shear force diagrams and the reactions. for the beam
shown in Figure 4. EI is constant.
65kN/m
32.0kN/m
A B C
3.0m 3.6m
SOLUTIONS
Question 1 - Solution. Determine the bending moment and shear force diagrams and the
reactions for the beam in Figure 1. All beams have the same stiffness, I.
80kN
18kN/m
Stiffness of beam I I I
Support A B C D
Dist factor 0.5 0.5 0.57 0.43
FEM 0 0 -100 +100 -150 +150
Release 50 50 28.5 21.5 -150
Carry over 25 14.3 25 -75
Release -7.2 -7.2 28.5 21.5
Carry over -3.6 14.3 -3.6
Release -7.2 -7.2 2.1 1.5
Carry over -3.6 1.0 -3.6
Release -0.5 -0.5 2.1 1.5
Carry over -0.2 1.0 -0.2
Release -0.5 -0.5 0.1 0.1
TOTAL 17.6 34.6 34.8 178.9 -179.9 0
SUPPORT MOMENTS
179
34.6
17.6
M = wL2/8 = 18 x 102/8 =
M = WL/4 = 80 x 10/4 = 200kNm 225kNm
FINAL BM
DIAGRAM
179
34.6 200
225
17.6
Span AB.
Shear force due to end moments = [(-17.6 –34.6)]/10 = -5.22kN
Shear force due to applications = 0
SPAB BC
Shear force due to end moments = (34.6 – 179)/10 = -14.44
Shear force due to point load = 80/2 = 40kN (rectangular0
Span CD
Shear due to end moments = (179 – 0)/10 = 17.9kN
Shear due to UDL = 18 x 10/2 = 90kN
90 + 17.9 = 107.9kN
40 – 14.44 = 25.56
5.22kN
40 + 14.44 = 54.44kN
90 - 17.9 = 72.1kN
Reactions.
R(A) = -5.22
R(B) = 5.22 + 25.56 = 30.78kN
R(C) = 54.44 + 107.9 = 162 34kN
R(D) = 72.1kN
Question 2 – Solution
Determine the final bending moment and shear force diagram and reactions for the beam
in Figure 2.
.
50kN 100kN
A B 10kN/ D
C
m
2.5m
5.0m 5.0m 5.0m 5.0m
Stiffness of beam I 2I 3I
Stiffness Factor
ModStiff Factor
Distribution factors
Support A B C D
Orig SF I/5 2I/5 3I/10
Mod SF I/5 2I/5 (3/4)3I/10
Dist factor 0.33 0.67 0.64 0.36
FEM -31.25 31.25 -20.8 20.8 -125 +125
Release -3.5 -7 66.7 37.5 -125
Carry over -1.8 33.4 -3.6 -62.5
Release -11 -22.4 42.3 23.8
Carry over -5.5 21.2 -11.2
Release -7.0 -14.2 7.2 4.0
Carry over -3.5 3.6 -7.1
Release -1.2 -2.4 4.5 2.6
TOTAL -42.1 8.6 -8.6 119.6 -119.6 0
SUPPORT MOMENTS
119.6
42.1
8.6
31.25kNm
M = WL/4 = 50 x 5/4 = 62.5kNm 250kNm
32.15kNm 119.6
42.1
8.6
62.5kNm
250kNm
FINAL BENDING
MOMENT DIAGRAM
Span AB.
Shear force due to end moments = [(42.1 – 8.6)]/5 = 6.7kN
Shear force due to applications = 25kN rectangular.
SPAB BC
Shear force due to end moments = (8.6 – 119.6)/5 = -22.22kN
Shear force due to udl load = 50/2 = 25kN (triangular)
Span CD
Shear due to end moments = (119.6 – 0)/10 = 11.96kN
Shear due to point load = 100 x 10/2 = 50kN (rectangular)
25kN
50 + 11.96 = 61.96kN
25 – 22.22 = 2.78kN
22.22 + 25 = 47.22kN
6.7kN
25 – 6.7 = 18.3kN
50 – 11.96 = 38.04kN
Reactions
RA = 31.7kN
RB = 21.08kN
RC = 109.18kN
RD = 38.04kN
Question 3.
Find the bending moment diagram for the frame shown in Figure 3. Also evaluate the
propping force P.
13.5kN/m
Prop P
B I=2 C
3.33m
I=1
I=1
5.0m
3.33m
FIGURE 3
A
With two dimensional problems no problems exist except the layout of the table. Initially
assume there is no sway.
4.73 6.474
B C
3.266 M = wL2/8 =
13.5 x 3.332/8 =
18.71kNm
A
2.375
4.73 6.474
B 18.71kNm, C
FINAL BENDING
MOMENT DIAGRAM
D
3.266
2.375
4.73 6.474
3.266
D
2.375 HD
A HA
Question 4.
Determine the bending moment and shear force diagrams and the reactions. for the beam
shown in Figure 4. EI is constant.
65kN/m
32.0kN/m
A B C
3.0m 3.6m
A B C
Dist factors 0.545 0.455
FEM‟s -48.75 48.75 -34.56 34.56
Release -7.73 -6.46
Carry over -3.87 -3.23
Totals -52.62 41.02 -41.02 31.33
No further releases are possible.
SUPPORT MOMENTS
M = 32 x 3.62/8 = 51.84kNm
M = 65 x 32/8 = 73.13kNm
52.62
73.13kNm 41.02 51.84kNm 31.33
Span AB.
Shear force due to end moments = [52.62 – 41.02)]/3 = 3.87kN
Shear force due to applications = 97.5kN (Triangular).
SPAB BC
Shear force due to end moments = (41.02 – 31.33)/3.6 = 2.69kN
Shear force due to udl load = 57.6kN(triangular)
57.6 + 2.69 = 60.29kN
97.5 + 3.87 = 101.37kN
B C
A
Reactions
RA = 101.37kN RB = 153.92kN RC = 54.91kN
RA + RB + RC = 310.2kN
Question 7.
Figure Q7 indicates a plan and elevation of a 7 storey building. Shear walls are
positioned as shown on the figure. The characteristic permanent loading on each floor
and the roof is 6.0kN/m2 and the transient loads are 4.0kN/m2. Columns are 400 x
400mm beams are 300 x 600 mm deep and assume E for the beams and columns to be
constant. Take the column height as 4.0 m.
i. Determine the design axial force on the top of the foundations below X. You
may assume half the slab loads are shed to the beams either side, and half the
beam load are shed to the columns (or shear walls) either end.
[4 marks]
ii. Determine the end (top and bottom) moments on column X between the first
and second storey about axis VV. Assume the ends of the beam at W and Y
are fully fixed.
[8 marks]
iii. Determine the bending moment diagram for the beam WXY.
[3 marks]
.
b. Shear wall AB is 200 mm thick. Consider a 1000 mm length of this wall
denoted AC. If the building is subject to a wind load of 0.45 kN/m2 in the
direction of F, determine using the worst possible load case,
i. The axial force on section AC of the wall due to slab and self weigh
effects.
[4 marks]
ii. The axial force on section AC due to the building being subject to a wind
load in the direction of F of 0.45 kN/m2.
[6 marks]
A U
5.0m 5.0m 5.0m 100mm
Indicates direction of
span of simply supported
C W precast slabs
1000mm
6.0m
Shear walls
V X V
6.0m
B Y
U
F
Seventh floor
24 000mm
Second floor
First floor
Ground bearing slab
Ground floor
2000mm
FIGURE Q7
Solution.
6.0m 6.0m
To carry out this analysis, use the fact that we from a substitute frame which includes
beams WX ansd XY and the columns above and below the point X. Also, we assume
that the stiffness of beams WX and XY are halved because in the substitute frame we
have built in the ends at W and Y an actually there will be some rotation there so :
0.4 0.4 3
Column stiffness k col 0.71 10 3
12.0 3.0
Fixed end moments for beam WX = +/- 70.5 x 62/12 = +/-211.5 kNm
Fixed end moments fro beam XY = +/- 30 x 62/12 = - 90 Knm
7aiii).
Final BM 150.75
59.62
241.88
diagram
WXY
120.9 29.82kNm
7bi). Axial load per m of shear wall assuming full loads are acting
From slab loads = 1.35 x 6 x 2.5 + 1.5 x 4 x 2.5 = 20.25 + 15 = 35.25 kN/m
Total load from slabs = 35.25 x 8 = 282 kN/m
Force at base of wall due to self weight = 0.2 x 1 x 25 x 1.35 x 26 = 175.5 kN/m
Force on AC = 282 + 175.5 = 457.5 kN
Force over 1.0m end length = [0.28 x 5.6/6.1]x[1000 x 200] x 10-3 = 51.4 kN