INSTALLATION, OPERATION & MAINTENANCE MANUAL

Air Cooled Chiller Heat Pump


Models: MAC070/100/120C(R)

Contents

MAC0807-V2 Part No.: M08019320008

1. Introduction
Introduction3

Nomenclature

2. Features
General Specification6 Parameter7

Technical Data 9

Outlines And Dimensions 10

3. Installation
Operation Limit 13

Unit Installation 13

Water System Installation 16

Power Connection 19

4. Servicing and Maintenance


Servicing and Maintenance 20

Troubleshooting 21
2008McQuay

Troubleshooting with Microprocessor 22

Schematic Diagram 23

5. Notice
Notice 26

Caution

Installation and maintenance are to be performed only by qualified personnel who are familiar with local codes and regulations, and experienced with this type of equipment. McQuay is not responsible for any unit damage, personal injury or death due to not complying with these requirements.

Warning

Sharp edges and coil surfaces are a potential injury hazard. Avoid contact with them.

Warning

It is not allowed to install the unit in public area.

Warning

A fit Air-switch should be installed in the main electrical wire when the unit connects with electric net system. Moving machinery and electrical power is hazardous. It may cause severe personal injury or death. Disconnect and lock off the Air-switch or power before servicing equipment.

2008McQuay

"McQuay" is a registered trademark of McQuay International. All rights reserved throughout the world. 2008 McQuay International
"Bulletin illustrations cover the general appearance of McQuay International products at the time of publication and we reserve the right to make changes in design and construction at any time without notice."

1 Introduction
Introduction
For years, McQuay international has earned a reputation for providing the industry with various highest quality and most technologically advanced air conditioning systems. Now Shenzhen McQuay is proud to introduce the new generation air-cooled chiller-MAC C series. Inherited from the advantage of the earlier product experiences and introduced the most up-to-date technology, the new MAC C series is designed with the always-in-mind concept - to satisfy customers high efficiency, comfort, safety, intelligence requirements to maximum extent. The unit can be flexibly coupled with multi fan coil units, easily operated with artificial intelligence, additionally combined with indoor top level decoration, these altogether bring you to enjoy the nobility coming from central air conditioning.

Nomenclature

MAC 070 C R - P AB U
U for America Market E for Other Location Description of the unit Power supply feature P for 208-230V/3 /60Hz R for Heat Pump Default for Cooling Only Design series Cooling capacity Air Cooled Chiller(Heat Pump) Mcquay

2008McQuay

2 Features
Superior Performance Extensive research work coupled with world leading manufacturing technology has resulted the new design with superb performance and high efficiency. Stringent quality control and component selection ensure performance and reliability. Major components are rigorously tested and qualified prior to usage in the machine. Every machine design has passed many hours of rigorous testing to ensure the machine reliability, durability and quality. Scroll compressor brings much higher energy efficiency. High efficiency heat exchanger ensures strenuous exertion of equipment capacity. Water pump particularly designed for air conditioning engineering is operating steadily with minimum vibration and noise. These units are designed with double independent refrigerating system, greater energy saving is achieved by only one compressor on duty under part load condition. Robust Construction With Slim Outlook Detailed engineering work coupled with extensive market research has resulted the new MAC model come in new mono-block design to yield a compact and robust structure while maintaining the slim outlook. The smaller capacity models MAC070C(R) are having side discharge design, while the larger capacity models MAC100/120C(R) are having top discharge design. Simple To Operate The machine is complete with intelligent microprocessor controller and temperature sensor to automatically control the operation to its optimum condition, making it very simple to operate. All temperature settings are finished before shipment. The only thing for user to do is to start the unit by pressing the ON/OFF button after ensuring unit proper function, then every operation can be automatically performed by the unit itself. Either wireless remote controller or wired remote controller is ready for choosing to meet satisfactory indoor unit control, both compatible with the unit. Friendly Installation The machine has been designed with installation friendly in mind such that no refrigeration charging or copper pipe brazing is required on site. Threaded fitting is provided for easy water piping connection on site. Water inlet and outlet are provided on both sides of the machine such that piping can be connected on
2008McQuay

either side of the machine. Rust resistant PP-R composite water pipe with good insulation property and high durability is standard parts in the machine. Stainless steel taper threaded fittings target convenient disassembly or assembly. Expansion chamber, water pump and water flow switch are already equipped in this compact packaged unit with top air discharge. In addition, McQuay provide accessory hydraulic kit with water storage tank, auto water fill valve, auto air vent valve, auto pressure relief valve and strainer integrated in, aiming at ensuring high efficiency and safe operation. Safety Control Protection devices such as dual pressure protection and overload protection etc. is provided to ensure unit operating within safety condition range. The microprocessor-based controller automatically directs system on or off by processing the water temperature feedback. If the water temperature falls to unacceptable low point, the controller automatically shut off the system to prevent hydraulic system internal freeze for unit safety operation. Meanwhile, the microprocessor-based controller automatically monitors every component operating status and malfunction, and feedback it to indoor controller to greatly ease the work of status monitor and troubleshooting. All Weather The cabinet is made of electro galvanized mild steel sheet, coated with baked polyester power to ensure the units extra durability in all climates against sun, rain, wind corrosion. Space saving (small footprint) design of the machine eliminates large installation area requirement, no need for equipment room. The machine uses high quality parts to ensure durability in various climate conditions. Simple To Maintain The simple design of the machine allows for maximum serviceability. All components are with reach of the maintenance personnel upon open up of the servicing panel. If emergency shutoff occurs, the microprocessor-based controller will indicates the fault cause to quicken and ease troubleshooting.

2008McQuay

General Specification
Compressor McQuay Mini Chillers are equipped with two highly efficient, reliable and silence scroll compressors for MAC070 C(R) to MAC120 C(R). Air-Cooler Condenser The air-cooled condenser coil consists of staggered rows of 3/8 OD seamless copper tube, mechanically expanded into die formed aluminum fins to ensure optimum heat exchange capability. Condenser Fan Motor To achieve the high air change requirement, the unit is equip with the high air flow propeller fan which is made of acryl styrene resin. The fan is direct driven by weather proof single phase motor to ensure reliable continuos operation. Evaporator The heat exchanger is made of stainless steel plates closely arranged and brazed together to ensure high heat exchange efficiency. The complete heat exchanger is insulated with thermal closed cell nitric rubber foam to give optimum thermal insulation. Refrigerant Circuit The refrigerant circuit is factory brazed and evacuated before accurately charged with R22 to ensure optimum operating requirement. To ensure flawless continuous operation, each refrigerant circuit is equipped with a carefully sized capillary tube. Additional Safety Protection The units are equipped with intelligently designed safety control to ensure continuous safe operation. High and low pressure switch is provided to prevent the compressor damage, resulting from both abnormally high discharge pressure and low pressure due to insufficient gas. The compressors of the whole range are provided with crank case heater to prevent liquid migration during the off cycle and also to ease the start up of the unit. The standard electronic controller provides accurate water temperature control in the circuit by closely monitoring and reacting to the input from the water entering temperature, water leaving temperature and ambient air temperature. Flow switch is provided in the unit to protect against damage to the water pump. During abnormal condition, the electronic controller will turn the unit off and the then display the faulty of operation. (Refer to Troubleshooting sheet)
2008McQuay

Parameter
MODEL RATED COOLING CAPACITY RATED HEATING CAPACITY POWER SUPPLY REFRIGERANT TYPE RATED COOLING POWER INPUT RATED HEATING POWER INPUT RATED COOLING CURRENT RATED HEATING CURRENT TYPE/DRIVE FAN MOTOR RATED POWER INPUT RATED CURRENT TYPE PUMP RATED POWER INPUT RATED CURRENT AVAILABLE HEAD WATER FLOW RATE UNIT WATER PRESSURE DROP HEIGHT(H) TOTAL UNIT DIMENSION WIDTH (W) DEPTH (D) INSTALLATION WATER PIPE CONNECTION CONDENSER TYPE EVAPORATOR TYPE SOUND LEVEL NET WEIGHT dB(A) kg mm W A m m /h kPa
3

MAC070C W W 17500 --

MAC100C 27000 -208-230V/3/60Hz R22

MAC120C 33000 --

W W A A

6690 -20.1 --

9240 -30.8 -Propeller/Direct

11370 -37.2 --

W A

350 1.5

260 x 2 0.9 x 2

445 x 2 1.1 x 2

Horizontal Multistage End-Suction 1410 3.4 18.6 3.0 102 1700 1212 502 Rc 1 1410 4.1 25.2 4.7 150 1260 1500 900 Rc 1 1/4 2380 7.8 35.3 5.7 110 1260 1800 1150

Cross Aluminum Finned Seamless Copper Tubes Stainless Steel Brazed Plate Heat Exchanger 64 235 64 350 67 470

Notes: 1) All specifications are subjected to change by manufacturer without prior notice. 2) Nominal cooling values are based on entering / leaving water temperature 12 / 7 and ambient temperature 35. 3) Nominal heating values are based on entering / leaving water temperature 40 / 45 and ambient temperature 7. 4) Rated cooling / heating power input doesnt include the pump consumption. 5) Actual performance can be determined by conducting correction after looking up the following charts. 2008McQuay

8 Based on the ambient temperature and desired return water temperature, we can locate the corresponding performance factor in these charts, then the corresponding actual cooling (heating) capacity and power input can be determined by using the following formula. Actual cooling (heating) capacity = nominal cooling (heating) capacity * cooling (heating) performance correction factor Actual power input = nominal power input * power input correction factor.

All specifications above are subjected to change by manufacturer without prior notice.

MODEL RATED COOLING CAPACITY RATED HEATING CAPACITY POWER SUPPLY REFRIGERANT TYPE RATED COOLING POWER INPUT RATED HEATING POWER INPUT RATED COOLING CURRENT RATED HEATING CURRENT TYPE/DRIVE FAN MOTOR RATED POWER INPUT RATED CURRENT TYPE PUMP RATED POWER INPUT RATED CURRENT AVAILABLE HEAD (C/H) WATER FLOW RATE (C/H) UNIT WATER PRESSURE DROP (C/H) HEIGHT(H) TOTAL UNIT DIMENSION WIDTH (W) DEPTH (D) INSTALLATION WATER PIPE CONNECTION CONDENSER TYPE EVAPORATOR TYPE SOUND LEVEL NET WEIGHT dB(A) kg mm W A m m /h kPa
3

MAC070CR W W 17500 18500

MAC100CR 27000 28500 208-230V/3/60Hz R22

MAC120CR 33000 35000

W W A A

6700 6500 21.4 21.0

10120 10320 33.5 33.2 Propeller/Direct

11540 11760 37.8 39.5

W A

350 1.5

260X2 0.9x2 Horizontal Multistage End-Suction

445X2 1.1x2

1410 3.4 18.6/18.0 3.0/3.2 102/103 1700 1212 502 Rc 1

1410 4.1 25.2/20.6 4.7/4.9 150/190 1260 1500 900 Rc 1 1/4

2380 7.8 35.3/30 5.7/6.0 110/157 1260 1800 1150

Cross Aluminum Finned Seamless Copper Tubes Stainless Steel Brazed Plate Heat Exchanger 64 245 64 360 67 480

Notes: 1) All specifications are subjected to change by manufacturer without prior notice. 2) Nominal cooling values are based on entering / leaving water temperature 12 / 7 and ambient temperature 35. 3) Nominal heating values are based on entering / leaving water temperature 40 / 45 and ambient temperature 7. 4) Rated cooling / heating power input doesnt include the pump consumption. 5) Actual performance can be determined by conducting correction after looking up the following charts. 2008McQuay

9 Based on the ambient temperature and desired return water temperature, we can locate the corresponding performance factor in these charts, then the corresponding actual cooling (heating) capacity and power input can be determined by using the following formula. Actual cooling (heating) capacity = nominal cooling (heating) capacity * cooling (heating) performance correction factor Actual power input = nominal power input * power input correction factor.

All specifications above are subjected to change by manufacturer without prior notice.

Technical Data
Cooling Performance Characteristic Chart

Cooling Performance Chart 1.30

1.20 Correction Factor of Capacity

1.10

1.00
9 8 7 6 5 4

0.90

0.80

0.70 10 15 20 25 30 35 40 45 50 Ambinet T emperature( )

Heating Performance Characteristic Chart

Heating Performance Chart


1.40 Correction Factor of Capacity 1.30 1.20 1.10 1.00 0.90 0.80 0.70

Output Temperature of Cooled Water

40 45 50 55

Output Temperature of Cooled Water

2008McQuay

10

Outlines And Dimensions


Model: MAC 070 C(R)

4-10X20 E A D B

2-Rc1

I J

2008McQuay

11

UNIT: mm

Model MAC070C(R)

A 1212

B 502

C 1700

D 1135

E 1162

F 132

G 254

H 235

I 80

J 604.5

Model: MAC 100/120 C(R)

100

HP Gauge (SYS2) LP Gauge (SYS2) D C Cable Port(OUT) Cable Port (IN) Chilled Water Out Rc 1 1/4 Chilled Water In Rc 1 1/4

27

253.5

128

F B

UNIT mm
2008McQuay

12

Model Dimension A B C D E F(Mounting hole) G(Mounting hole)

MAC100C(R) 1500 900 1260 1190 297.5 307.5 1446

MAC120C(R) 1800 1150 1260 1190 367 416 1746

Accessory Hydraulic Kit Accessory hydraulic kit consists of 40L capacity stainless steel water storage tank, 8L volume water expansion chamber, safety valve, dirt drainage valve, and auto air vent valve etc.

N MAC-S1U R1 MAC-S2U R1 1/4

680 816

4-10x20 400

448

Chilled Water Inlet N 500 302 Chilled Water Outlet N Dirt Drainage Port R1/2 87 48

151 61

Water Drainage Port DN25

2008McQuay

13

3 Installation
Operation Limit

Cooling mode
5 48 40 35 30 25 20 15 5 7.5 10 12.5 15 leaving water temperature operating limit Ambient temperature 7.5 10 12.5 15 48 40 35 30 25 20 15 26 21 15 10 Ambient temperature 30

Heating mode
35 40 45 50 26 21 15 10 operating limit 5 0 -5 -10 30 35 40 45 50 leaving water temperature 5 0 -5 -10

Notes: The charts above show the unit performance change characteristic in relationship with variable ambient temperature and supply water temperature. Please notice that there are some little differences between the performance of actual manufactured unit and that obtained using these charts.

Unit Installation
The chiller must be installed by qualified dealer or personnel authorized by MCQuay, and the installation must satisfy all the following requirements. Location Air Discharge Air Intake In order to achieve maximum capacity, the location selection should fulfill the following requirements: Air Intake 1) The location must be well ventilated, so that air can be drawn in and discharge out efficiently.
Air Intake Air Intake
Air discharge

Air Discharge Air Intake

2008McQuay
Air Intake

14

2) Install the unit in such a way that the hot air discharge cannot be drawn in again by itself or other units.

3) Ensure that there is no obstruction to air flow into or out of the unit. Remove obstacles which blocking intake or discharge air if exist.
Obstacles Blocking Air Intake

Obstacles Block Air Intake

Obstacles Block Air Discharge


Obstacles Blocking Servicing Access

4) If good ventilation cannot be guaranteed when unit being installed indoors, it is advisable to induce discharge air from air outlet to outdoors by installing duct which is as short as possible. 5) Support unit base up to create a space above foundation for ensuring free water drainage, and the stable foundation with level surface must be sufficiently durable against the unit weight.

Unit Unit Supporter Drain Ditch

6) The location must not be susceptible to dust or oil to avoid condenser coil being choked by the contaminant. As the general safety precaution, it is advised that no flammable danger gas should be located near to the unit. 7) It is advised to have sufficient clearance around the unit for proper condenser air flow and to facilitate access for maintenance.( see clearance shown in figure below)

900

350

350

900

2000

2008McQuay

15

Delivery and Lifting When transporting the unit, it is advisable to use forklift or crane to do this work. Only the wooden skid base is allowed to be served as the weight-supporter.

When hoisting, please keep the unit stable and without slope, meanwhile, be sure to avoid lifting ropes contact with side heat exchanger, panel and units top part.
Lifting Hook

Lifting Cable

Backing Angle

After deciding the mounting location, remove the skid base by unfastening the bolts. Mounting When mounting, please use foundation bolts or expansion bolts to fasten the unit with foundation supporting legs. When installing indoors, it is advisable to pad the unit bottom against foundation by using vibration absorption rubber.

2008McQuay

16

Water System Installation


Chilled Water Piping Chilled water piping must be insulated and waterproof to avoid performance loss and moisture condensing on it. To guarantee the chilled water quality, the water strainer shipped with unit must be installed on the chilled water in pipe. Both chilled water inlet and outlet port are met the needs.(refer to the Parameter table) When performing water pipe connection, use gripping pliers to fix the unit connections to avoid the reserved connections on unit being directly suffered from revolving torque when fastening. The accessory water pipe components shipped with unit include water pump and water flow switch. Please install them on pipe in accordance with the chilled water system installation schematic diagram. Air vent valve should be installed at highest points on chilled water piping system, see detailed information in chilled water system installation schematic diagram. After completing chilled water piping, carry out leak detection and 0.4MPa pressure test to ensure having no fault, then fully fill water in system, open air vent valve, purge all the air trapped in the piping system, after that shut off the air vent valve. Water drainage valve should be installed at lowest points on chilled water piping system. In order to achieve the unit long-life operation, it is recommended to give first priority to new type plastic water pipe such as PP-R, PVC, never use galvanized steel pipe when choosing the material of water pipe.

Caution

The accessory strainer shipped with unit must be installed on water in pipe, otherwise failure of the unit may be caused. The unit should be connected with the water supply system through the automatic feeder that is the unit accessory. The pressure of the water supply system must be more than 1.5 bar and less than 6 bar.

Caution

If the chiller is operated with very oily, salty or acidic water, these substances may lead to capacity drop. Be sure to use clean water when filling in the water circuit to avoid heavy corrosion and choking of the system.

Caution

Dont use the water pump equipped in unit to clean piping. If using the pump to clean is required, you can fill clean water in system at water in side, meanwhile make the pump running, please conduct 30-minute pump operation, then clean the strainer. Hydraulic system installation schematic diagram

2008McQuay

17

Limit to the water volume of the chiller

! Caution
If the system water volume is less than required water volume(Vmin) while the chiller is operating, it will result in frequent ON/OFF.

Vmin is referred to the below table Item Model Setting EWT() 14 13 12 11 10 14 13 12 11 10 14 13 12 11 10 Vmin(l) 95 109 129 158 203 77 89 106 129 166 165 206 275 413 826

MAC070C/CR

MAC100C/CR

MAC120C/CR

Notice 1. The total water volume of the entire hydraulic system includes the water in main pipe, water tank and terminal equipments,in which the 2-way valve is open. 2. If the water volume (V) while the unit is running is less than Vmin, it's recommended to install a water tank of (Vmin-V)L, or it will cause the unit frequent ON/OFF 3. The Vmin in the table is calculated based on nominal cooling water flow and 5 anti-freeze. If the water flow and anti-freeze temperature change, related Vmin will change. 4. The table is applied for the water volume selection of normal chiller, not for the chiller under low leaving water temperature with glycol.

2008McQuay

18

Hydraulic System When installing the MAC unit, using closed water system is strongly recommended by McQuay, and please refer to the schematic diagram above. In order to ensure energy saving and system safe operation, McQuay has provided hydraulic system accessories, including insulated stainless steel water storage tank, safety valve, dirt drainage valve, auto air vent valve, Y-shaped strainer and automatic water fill valve etc. Auxiliary heater in the diagram below is available for option, please choose either type of auxiliary electric heater or auxiliary gas heater. If you have the demand, please contact with local McQuay sales representation, and install it according to below diagram ; if you have no need of this option, the components in dotted line box can be omitted.

Air Vent Valve Two Way Valve


T

FCU

Two Way Valve


T

FCU

Two Way Valve


T

FCU

Water Gauge

Two Way Valve Globe Valve


T

FCU Flexible Joint Shutoff Valve

Flexible Joint Shutoff Valve

Heater

Water Fill Valve

Shutoff Valve

Thermometer
T

Check Valve
T

Accessory Hydraulic Kit (optional) Y Strainer

Shutoff Valve

Dirt Drainage Valve Flexible Joint

Unit

Notes
The design, construction and acceptance check of the hydraulic system should respectively refer to and comply with the corresponding manual, code and standard.
2008McQuay

19

Power Connection
Laws and regulations concerning electrical wiring work vary by country. Therefore, work should basically be performed according to the regulations of each country. Before power connection, make sure that your local power supply type accords with the unit nameplate. Please use suitable size dedicated wire to power this unit. The connections must be made secured without tension the terminals. All electric work must be performed by licensed technician according to local regulations and the instructions given in this catalogue. The unit must be properly earth connected. Do not connect the earth wire to gas pipe, city water pipe or telephone wire, improper earth connection may cause electrical shock. Please mount electric leak protection breaker to avoid electric shock. Please ensure correct phase sequence, make L1, L2, L3 correspond with R, S, T on terminal block respectively, otherwise the system cannot be started and the controller has no display. Every wire should be firmly connected without tension to the cables and terminals. All cables should not contact with refrigerating piping and moveable components such as compressor and fan motor etc.

Caution

At emergency (if you smell something burning), stop operation and turn the power source switch off, ask for your dealers instruction. Continuing the operation without eliminating the emergency state may cause a machine trouble, fire, or electrical shock. Dont extend your fingers or other foreign pieces such as stick into unit air outlet, otherwise the unit could be damaged or you could be injured. ELECTRICAL DATA
MODEL POWER SUPPLY MAX. INPUTW MAX. CURRENTA POWER CABLE CROSS SECTION AREA (mm) Q.T.Y 9350 27.2 6 MAC070C(R) MAC100C(R) 208-230V/3~/60Hz 15000 45.0 10 4 16400 49.5 10 MAC120C(R)

ELECTRICAL CONNECTION OF AUXILIARY ELECTRIC HEATER If auxiliary electric heater or auxiliary gas heater installation is required, please do installation after thoroughly reading corresponding manual. Carry out the electrical connection according to the circuit diagram in unit electrical box so that achieve their automatic on/off governed by the unit controller. In addition, contact with local McQuay service representative for performing trail startup.
2008McQuay

20

4 Servicing and Maintenance


Servicing
Service and maintenance are to be performed only by qualified personnel who are well trained with refrigeration engineering. Before restart the unit, do a thorough check and analysis of the unit safety control component. The optimum design of the refrigerating system eliminates the possibility of problems being occurred during normal operation. There is no need to conduct any maintenance to refrigerant piping if the unit is under normal running. McQuay designers have given full consideration to make servicing convenient during unit development. After opening service panel, both servicing and maintenance can be easily carried out. Under normal environment, the only work needed is checking the return air way and cleaning the heat exchange surface regularly at month or season interval decided on operating condition. If the surrounding is very dirty or oily, for maintaining superior performance and sufficient capacity, please ask specialized personnel to do regular cleaning of heat exchanger.

Maintenance
For keeping consistent performance and durability with safe, effective and long-life operation, always conduct proper and regular maintenance to the unit. For long period of operation time, the heat exchanger will become dirty impairing its effectiveness and reducing the performance of the air conditioner. Consult your local dealer on the cleaning of the heat exchanger. No main maintenance or servicing needed for the internal water circuit except the water pump failure. It is advised that regular check on the strainer should be conducted and replace the water strainer if the strainer is dirty or clogged. Always check the water level in the system, for the target of protecting the moving components in the hydraulic kit from overheating, excessive wearing and water freeze. All the chilled water in the hydraulic system must be drained out completely during unit shutdown in winter, to avoid water piping damage due to freeze.

2008McQuay

21

Troubleshooting
When any malfunction is occurred, immediately turn the switch off and shut down operation, then contact with your dealer for resolution. For some frequently occurred failure, you can conduct some handling referring to the simple trouble shooting tips given below. SYMPTOMS 1. Compressor does not start POSSIBLE CAUSES No power supply. Fuses blown or automatic circuit breakdown open. REMEDIAL ACTION Check power supply. Look for short circuit or grounded wires in motor windings. Replace fuses and reset circuit breakers when the fault has been corrected. Check tightness and soundness of all electrical connections. Determine the type of safety shut down and correct the default before the unit is restarted. Check wire connections and tighten terminal screws. Contact local dealer. Check power supply. Contact local dealer. Reset thermostat Contact local dealer. Remove the obstacle. Contact local dealer. Contact local dealer. Contact local dealer.

Unit is stopped because a safety has tripped.

Loose wires. Compressor faulty. 2. Fan does not work 3. Air conditioner does work, but insufficient cooling. No power supply. Fan motor faulty. Thermostat setting too high. Condenser coil dirty. Obstacle blocking air inlet or outlet of the unit. Insufficient refrigerant in the system. Improper water flow rate. Water in the system is contaminated.

2008McQuay

22

Troubleshooting With Microprocessor


Error Code E1 E2 E3 E4 E7 E8 EA EC ED EE EF Possible Causes Return water sensor contact loose/short Supply water sensor contact loose/short Return air sensor contact loose/short System 1 defrosting sensor contact loose/short Insufficient water flow Water pump overload Compressor 1 overload Compressor 1 high pressure cutout Compressor 1 low pressure cutout RAM access failure Solutions Contact with the dealer, check and rewire it Contact with the dealer, check and rewire it Contact with the dealer, check and rewire it Contact with the dealer, check and rewire it Adjust water flow rate, check and clean strainer Contact with the dealer Contact with the dealer Contact with the dealer Contact with the dealer Contact with the dealer

Too low supply water temperature when Contact with the dealer cooling

When other code is displayed, please consult specialized personnel. See detailed indoor controller operation in corresponding instruction manual.

2008McQuay

23

Schematic Diagram
MAC070C
2

5 Chilled Water In 6 Chilled Water Out 4

LEGEND Refrigerant Fow Direction 1.Compressor 4.Bphe 7.Accumulator 2.Heat Exchanger Fan 5.Water Pump 3.Throttle Device 6.Difference Pressure Switch

MAC070CR

5 2 6 4 8 8 1 W a ter In 9 3 W a ter O ut 10 12 7

11

LE G E ND R e frigeran t F lo w D ire ctio n Wh en C oo ling R e frigeran t F lo w D ire ctio n Wh en H ea tin g 1 Com pressor 2 F ou r W a y V alve 3 A ccu mu lato r 7 Thro ttle Device 1 1 W a te r P u mp 4 C opper T ube Alum inium Fin H ea t E x ch an ge r 8 C he ck V a lve 1 2 Diffe re n tia l P re ssure S w itch

5 Hea t E x cha nger F an 6 T hrottle De vice 9 Rece ive r 1 0 B PH E

2008McQuay

24

MAC100C/120C

Water In

Water Out

LEGEND Refrigerant Flow Direction 1 Compressor 4 BPHE 2 Heat Exchanger Fan 5 Water Pump 3 Throttle Device 6 Differential Pressure Switch 7 Accumulator

2008McQuay

25

MAC100CR/120CR

Water In

Water Out

LEGEND Refrigerant Flow Direction When Cooling Refrigerant Flow Direction When Heating 1 Compressor 2 Four Way Valve 3 Accumulator 7 Throttle Device 11 Water Pump 4 Copper Tube Aluminium Fin Heat Exchanger 8 Check Valve 12 Differential Pressure Switch

5 Heat Exchanger Fan 6 Throttle Device 9 Receiver 10 BPHE

2008McQuay

26

5 Notice
Inspection
As soon as the unit is received, it should be inspected for any damage that may have occurred in transit. If damage is evident, it should be noted on the carriers freight bill. A separate request for inspection by the carriers agent should be made in writing at once. Concealed damage must be reported within 15 days of receipt of shipment. Check shipment against the bill of lading to verify that all items were delivered. Any shortages should be noted on the delivery receipt, and a claim filed immediately.

Instruction for use


1) Suitable room temperature setting It is advisable to comfort every one in the conditioned space, so the temperature setting shouldnt be too high or too low. It is recommended that the setting should be within the range of from 26 to 28 when cooling, from 18 to 23 when heating. 2) Winter anti-freeze of chilled water circulating in the hydraulic system All the chilled water in the hydraulic system must be drained out completely during unit shutdown in winter, to avoid water piping damage due to freeze. 3) Make sure the air side ventilation is good. These obstacles may cause performance deficiency or shutdown of the air conditioner. 4) Antirust Please take antirust measures and regularly remove rust when using water pipe vulnerable to rust to connect chilled water system 5) Conducting regular chilled water maintenance, this contributes to ensure safe, high efficiency and consistent operation. 6) Only clean water is suitable to fill in system, in addition, install the high efficiency water strainer, which is provided by McQuay, on the upstream pipe to unit water inlet 7) Special attention to winter antifreeze During long period shutdown in winter, the water in system must be completely drained out. Please refer to the diagram below and the labels stuck on unit. Add proper quantity anti-freezer such as ethylene glycol into the hydraulic system if the unit is not on duty for short time.

2008McQuay

27

While utmost care is taken in ensuring that all details in the publication are correct at the time of going to press, we are constantly striving for improvement and therefore reserve the right to alter model specifications and equipment without notice. Details of specifications and equipment are also subject to change to suit local conditions and requirements and not all models are available in every market.