MACX MCR voltage transducers for DC voltages of 0... (+/-) 20 V DC to 0.. .(+/-) 660 V DC, output signal (+/-)
10 V/ (+/-)20 mA
Your advantages
Adjustable voltage ranges
Bidirectional output signals
3-way isolation
ZERO/SPAN adjustment ±20%
Tool-free parameterization of measured values
Teach-in configuration of the measured value range
Key Commercial Data
Packing unit 1 pc
GTIN
GTIN 4055626050928
Weight per Piece (excluding packing) 226.500 g
Custom tariff number 85437090
Country of origin Germany
Technical data
Note
EMC: class A product, see manufacturer's declaration in the download
Utilization restriction
area
Dimensions
Width 22.5 mm
Height 99 mm
Depth 114.5 mm
Ambient conditions
08/08/2019 Page 1 / 5
https://www.phoenixcontact.com/gb/products/2906242
Voltage measuring transducers - MACX MCR-VDC - 2906242
Technical data
Ambient conditions
Ambient temperature (operation) -25 °C ... 60 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C (non-condensing)
Maximum altitude ≤ 2000 m
Permissible humidity (operation) 10 % ... 95 % (non-condensing)
Degree of protection IP20
EN 61000-6-2 When being exposed to interference, there may be
Noise immunity
minimal deviations.
Input data
Input voltage range -550 V DC ... 550 V DC
Input resistance 5500 kΩ
Input voltage range -370 V DC ... 370 V DC
Input resistance 3700 kΩ
Input voltage range -250 V DC ... 250 V DC
Input resistance 2500 kΩ
Input voltage range -170 V DC ... 170 V DC
Input resistance 1700 kΩ
Input voltage range -120 V DC ... 120 V DC
Input resistance 1200 kΩ
Input voltage range -80 V DC ... 80 V DC
Input resistance 800 kΩ
Input voltage range -54 V DC ... 54 V DC
Input resistance 800 kΩ
Input voltage range -36 V DC ... 36 V DC
Input resistance 800 kΩ
Input voltage range -24 V DC ... 24 V DC
Input resistance 240 kΩ
Nom. voltage ± 660 V DC
Output data
Output name Voltage output
Voltage output signal -10 V ... 10 V
Max. output voltage ≤ 11 V
Load/output load voltage output > 10 kΩ
Ripple 50 mV
Output name Current output
Current output signal -20 mA ... 20 mA
Max. output current ≤ 22 mA
Load/output load current output < 500 Ω
Power supply
Nominal supply voltage 24 V DC (-20 % ... +25 %)
Supply voltage range 19.2 V DC ... 30 V DC
08/08/2019 Page 2 / 5
https://www.phoenixcontact.com/gb/products/2906242
Voltage measuring transducers - MACX MCR-VDC - 2906242
Technical data
Power supply
Max. current consumption < 60 mA
Connection data
Connection method Pluggable screw connection
Connection technology Screw connection
Stripping length 8 mm
Screw thread M3
Conductor cross section solid 0.2 mm² ... 2.5 mm²
Conductor cross section flexible 0.2 mm² ... 2.5 mm²
Conductor cross section AWG 24 ... 14
General
Maximum transmission error < 1 % (of measuring range end value)
Maximum temperature coefficient < 0.015 %/K
Alignment zero ± 20 %
Alignment span ± 20 %
Step response (10-90%) < 16 ms
Test voltage 5.3 kV AC (50 Hz, 1 min.)
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
EN 61000-6-2 When being exposed to interference, there may be
Noise immunity
minimal deviations.
Color gray
Mounting position any
Assembly instructions Can be aligned with spacing = 10 mm
Conformance CE-compliant
UL, USA/Canada UL 61010 Listed
Standards and Regulations
Electromagnetic compatibility Conformance with EMC directive
Noise emission EN 61000-6-4
Standards/regulations IEC 61010-1
IEC 61010-2-030
Degree of pollution 2
Low Voltage Directive Conformance with Low Voltage Directive
Conformance CE-compliant
UL, USA/Canada UL 61010 Listed
Environmental Product Compliance
REACh SVHC Lead 7439-92-1
China RoHS Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
08/08/2019 Page 3 / 5
https://www.phoenixcontact.com/gb/products/2906242
Voltage measuring transducers - MACX MCR-VDC - 2906242
Classifications
eCl@ss
eCl@ss 5.0 27210190
eCl@ss 5.1 27200300
eCl@ss 6.0 27210100
eCl@ss 7.0 27210125
eCl@ss 8.0 27210125
eCl@ss 9.0 27210125
ETIM
ETIM 4.0 EC002477
ETIM 5.0 EC002477
ETIM 6.0 EC002477
ETIM 7.0 EC002477
Approvals
Approvals
Approvals
UL Listed / cUL Listed / EAC / cULus Listed
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 330267
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 330267
RU C-
EAC
DE.A*30.B.01082
cULus Listed
08/08/2019 Page 4 / 5
https://www.phoenixcontact.com/gb/products/2906242
Phoenix Contact 2019 © - all rights reserved
http://www.phoenixcontact.com
08/08/2019 Page 5 / 5