DF-60334:A6 • A1-100

MS-9600LS(E)/MS-9600UDLS(E)
Intelligent Addressable FACP
with Optional Second Loop
Addressable Control Panels

General
Fire•Lite’s MS-9600LS(E) and MS-9600UDLS(E) are compact, cost
effective, intelligent addressable FACPs (Fire Alarm Control Panels)
with an extensive list of powerful features. The combination of
Fire•Lite’s newer series devices and legacy 300 Series devices,
along with the MS-9600LS(E) or MS-9600UDLS(E) FACP, offer the
latest in fire protection technology. LiteSpeed™ is a patented tech-
nology that polls 10 devices at a time looking for new or different
information. When new information is found at a specific address,
the system polls that device several times for any new data. This
improvement allows a fully loaded panel with up to 636 devices to
report an incident and activate the notification circuits in under 10
seconds. With this polling scheme, devices can be wired on stan-
dard twisted, unshielded wire up to a distance of 10,000 feet per
loop. Each Signaling Line Circuit (SLC) loop supports up to 159
addressable detectors including photoelectric, photoelectric with
heat, beam, ionization, photoelectric duct, fixed heat, fixed heat with
rate-of-rise, and fixed high-heat detectors. It also supports up to 159
addressable modules including monitor (two-wire detector, normally
open devices), dual-monitor functions (two monitor circuits from one
module, two addresses used), multi-monitor (multiple monitor cir-
cuits from one module, multiple addresses used), control (for Notifi-
cation Appliance Circuits), and relay (two Form-C) modules.
The FLPS-7 power supply is a separate board while all other elec-
tronics are contained on a single main circuit board. Both boards are
mounted to a quick-removable chassis and housed in a metal cabi-
net. The backbox can be installed allowing field wiring to be pulled. MEMBRANE SWITCH CONTROLS
When construction is completed, the chassis with the electronics
• ACKNOWLEDGE/STEP
can be quickly installed with two bolts.
• ALARM SILENCE
The MS-9600UDLS(E) includes a factory-installed 2 Digital Alarm
• DRILL
Communicator Transmitter. The DACT transmits system status
(alarm, troubles, AC loss, etc.) to a Central Station via internet • SYSTEM RESET (lamp test)
(optional IPDACT installed) or the public switched telephone net- • 12-key pad with full alphabet
work. • 4 cursor keys
Optional modules, which plug into the main circuit board, are avail- • ENTER
able for special functions. Available accessories include LED,
graphic and LCD annunciators, reverse polarity/city box transmitter, Special Features
digital alarm communicator/transmitter, SLC expansion module,
• Easy mount chassis.
local and remote upload/download software and remote power
expansion. • 7 amp switching power supply.
FM APPROVED to UL ANSI 864. • Large enclosure allows 18 amp-hour batteries
• 2 plug-in communicator standard with MS-9600UDLS/E.
NOTE: Unless otherwise specified, the term MS-9600LS is used in this
document to refer to the MS-9600LS, MS-9600UDLS, MS-9600LSE, and • Optional IPDACT Internet Protocol Digital Alarm Communicator/
MS-9600UDLSE FACPs (Fire Alarm Control Panels). Transmitter
• Four Style Y (Class B) or two Style Z (Class A)
Controls And Indicators NAC circuits.
• Selectable strobe synchronization per NAC for
LED INDICATORS System Sensor, Wheelock, and Gentex devices.
• AC POWER (green) • Certified for seismic applications when used with the appropriate
• FIRE ALARM (red) seismic mounting kit
• SUPERVISORY (yellow) • Seamless integration between fire and mass notification with the
• ALARM SILENCED (yellow) ECC-50/100 Emergency Command Center via ANN-BUS con-
• SYSTEM TROUBLE (yellow) nections.
• MAINTENANCE/PRESIGNAL (yellow) • ECC-FFT Firefighter Telephone Option
• DISABLED (yellow) • ANN-BUS for connection to following optional modules
• BATTERY FAULT (yellow) Note: cannot be used if ACS annunciators are used.
• GROUND FAULT (yellow) – ANN-80(-W) Remote LCD Annunciator
– ANN-I/O LED Driver Module
– ANN-S/PG Serial/Parallel Printer Module

DF-60334:A6 • 2/20/2019 — Page 1 of 6


– ANN-RLY Relay Module • Local piezo sounder.
– ANN-LED Annunciator Module • Waterflow (non-silenceable) selection per monitor point.
– ANN-RLED Annunciator Module (alarms only) • System alarm verification selection per detector point.
• Compatible with SWIFT® wireless devices • PAS (Positive Alarm Sequence) and presignal delay per point
(NFPA 72 compliant).
Standard Features • Optional 4XTMF module (conventional reverse polarity/city box
transmitter).
SLC LOOP
• SLC can be configured for NFPA Style 4, 6, or 7 operation. Field-programming Features
• SLC supports up to 318 addressable devices per loop (159 Off-line Programming: Create the entire program in your office
detectors and 159 monitor, control, or relay modules). using a Windows®-based software package (download PS-Tools
• SLC loop maximum length 10,000 ft. (3,048 m) @ 12 AWG (3.1 from www.firelite.com). Upload/download system programming
mm²) using twisted, unshielded wire (see Wire Table on page 5). locally to the MS-9600LS in less than one minute.
NOTIFICATION APPLIANCE CIRCUITS (NACS): Autoprogramming: Command the MS-9600LS to program itself
(takes less than 30 seconds). In the Auto-Program mode, the MS-
• Four onboard NACs with additional NAC capability using output
9600LS scans for all possible devices at all addresses, stores the
control modules (CMF-300 or CMF-300-6). The four Class B
device types, and addresses found, and then loads default values
NACs can be converted to two Class A NACs with the NACKEY
for all options (General Alarm). It also checks for two or more
(included).
devices set to the same address.
• Silence Inhibit and Auto Silence timer options.
Online Editing: While still providing fire protection, the MS-9600LS/
• Continuous, March Time, Temporal or California code for main E may be programmed from the front panel. Simple menu trees dis-
circuit board NACs with two-stage capability. played on the LCD allow the trained user to perform all functions
• Selectable strobe synchronization per NAC. without referring back to the programming manual.
• 3.0 amps special application, 300mA regulated maximum per English Label Library: Quickly select labels from a standard library
each NAC circuit of more than 50 adjectives/nouns, such as “FLR 3 HALLWAY,” or
Note: Maximum 24 VDC system power output is shared among enter custom labels letter-by-letter. Use recall function to repeat pre-
all NAC circuits and 24 VDC special application auxiliary power viously used label.
outputs. Total available output is 7.0 amps.
Program Check: Automatically catch common errors, such as con-
ADVANCED FIRE TECHNOLOGY: trol modules not linked to any zone or input point.
• Sensitivity testing with printable results, on-site or off-site.
• Automatic drift compensation. Maintenance Alert
The MS-9600LS(E) continuously monitors each smoke detector and
PROGRAMMING AND SOFTWARE: is capable of reporting maintenance conditions. This reduces the
• Autoprogramming (learn mode) reduces installation time. risk of false alarms due to dust accumulation. Refer to the control
• Fully programmable from local keypad, local PS/2 keyboard or panel installation manual for more information.
PC (using the standard PS-Tools Windows® utility).
• Two-level user-programmable passwords. Automatic Test Operation
• Custom English labels (per point) may be manually entered or The MS-9600LS(E) performs an automatic test of each detector
selected from an internal library file. every two hours. Failure to meet the test limits causes an AUTO
• Three Form-C relay outputs (two programmable). TEST FAIL trouble type. System Reset clears this trouble.
• 99 software zones.
Terminal Blocks
USER INTERFACE:
AC Power – TB1: 120 VAC, 60 Hz, 3.0 amps or 240 VAC, 50 Hz,
• Optional plug-in 2 communicator (standard with MS- 1.5 amps. Wire size: minimum 14 AWG (2.00 mm²) with 600 V insu-
9600UDLS(E) with USB port for local upload/download. lation.
• Remote Acknowledge, Silence, Reset and Drill via addressable
Battery (lead acid only) – TB2: Maximum charging circuit: Normal
monitor modules, ACS Series annunciators, LCD-80F remote
float charge 27.6 VDC @ 1.0 amp. Maximum battery charger capac-
annunciator, or ANN-80 Series Annunciators.
ity: 26 AH. Minimum battery 12 AH. MS-9600LS cabinet holds maxi-
• EIA-232 printer/PC interface (variable baud rate) on main circuit mum of two 18 AH batteries. For 26 – 120 AH batteries, use the
board. CHG-120F or CHG-75 Battery Charger and BB-55F Battery Box.
• Integral 80-character LCD display with backlighting. NOTE: Jumper JP3, on the FACP main circuit board, must be cut to dis-
• Real-time clock/calendar with automatic daylight savings adjust- able the FACP battery charger when using the CHG-120F or CHG-75.
ments.
Communication Loop – (standard) TB8: 24 VDC nominal, 27.6
• History file with 1,000-event capacity. VDC maximum. Maximum length: 10,000 ft. (3048 m) total twisted,
• EIA-485/ANN-BUS supporting up to 8 ANN Series Annunciators unshielded pair length. Maximum loop current: 400 mA (short circuit)
or 32 ACS Series annunciators. or 100 mA (normal). Maximum loop resistance: 40 ohms. Super-
• EIA-485 supporting up to 32 ACS annunciators. vised and power-limited.
• Maintenance alert warns when smoke detector dust accumula- Notification Appliance Circuits – TB4: Power-limited circuitry.
tion is excessive. Nominal operating voltage: 24 VDC. Current limit: fuseless, elec-
• Automatic device type-code verification. tronic, power-limited circuitry. Maximum signaling current per circuit:
3.0 amps special application, 300mA regulated. End-of-Line Resis-
• One person audible or silent walk test with walk-test log and print- tor: 4.7K ohm, 1/2 watt (P/N 71252 UL listed) for NACs. Refer to
out. Fire•Lite Device Compatibility Document for listed compatible
• Point trouble identification. devices.

Page 2 of 6 — DF-60334:A6 • 2/20/2019


Programmable and Trouble Output Relays – TB5: Contact rating: CHG-120F: Remote battery charging system for lead-acid batteries
2.0 amps @ 30 VDC (resistive), 0.5 amps @ 30 VAC (resistive). with a rating of 25 to 120 AH. CHG-120F or CHG-75 required for
Form-C relays. charging greater than 25 AH batteries.
Four-Wire Resettable Smoke Detector Power CHG-75: Battery charger for lead-acid batteries with a rating of 25 to
(24 VDC nominal) – TB3, Terminals 1(+) & 2(–): 75 AH. CHG-120F or CHG-75 required for charging greater than 25
Maximum ripple voltage: 10 mVRMS. Up to 1.5 amps for powering AH batteries.
four-wire smoke detectors. Power-limited circuit. Refer to Fire•Lit- BAT Series: Batteries, see data sheet DF-52397.
eDevice Compatibility Document for listed compatible devices.
PRN Series: UL listed compatible event printer which uses tractor-
Nonresettable Power #1 (24 VDC Nominal) –TB3, Terminals 3 (+) fed paper.
& 4 (–): Maximum ripple voltage: 10 mVRMS. Up to 1.5 amps total
DC current available from each output. Power-limited circuit. TB3, SEISKIT-COMMENC: Seismic kit for the MS-9600UDLS backbox.
Terminals 5 (+) & 6 (–): non-resettable power #2. Includes battery bracket for two 7, 12, or 18 AH batteries.
Nonresettable Special Application Power #2 (24 VDC Nominal) -
TB3, Terminals 5 (+) & 6 (-): Maximum ripple voltage: 10mVRMS. Compatible Addressable Devices
Total DC current available from each output is up to 1.5 amps. All feature a polling LED and rotary switches for addressing.
Power-limited circuit, non-supervised.
AD355/AD365(-IV): Low-profile, intelligent, “Adapt” multi-sensor
EIA-485 (ACS/ANN) – TB6: Annunciator connector, programmable detector; B350LP base included.
for type ANN or ACS. Terminal 1 (+) and Terminal 2 (–).
BEAM355: Intelligent beam smoke detector.
EIA-485 (TERM) – TB7: Terminal mode annunciator connector, Ter-
minal 1 (Out +), 2 (In +), 3 (Out –), 4 (In –). BEAM355S: Intelligent beam smoke detector with integral sensitiv-
ity test.
EIA-232 – TB8: PC/printer connector, Terminal 1 (Transmit), 2
(Receive), 3 (DTR), 4 (Ground). CP355: Addressable low-profile ionization smoke detector.
D355PL: Photoelectric low-flow duct smoke detector, SD355R
Ordering Options included.

MS-9600LS(E): 318-point addressable Fire Alarm Control Panel, H355/H365: Fast-response, low-profile heat detector.
one SLC loop. Includes 80-character LCD display, single printed cir- H355R/H365R(-IV): Fast-response, low-profile heat detector with
cuit board, and cabinet. rate-of-rise option.
MS-9600UDLS(E): 318-point addressable Fire Alarm Control Panel, H355HT/H365HT(-IV): Fast-response, low-profile heat detector that
one SLC loop. Includes 2, 80-character LCD display, single printed activates at190° F (88°C).
circuit board, and cabinet.
OSI-RI-FL: Addressable long range projected beam smoke detector
DACT-UD2: Optional communicator for remote monitoring (standard designed to provide open area protection
with MS-9600UDLS).
SD355/SD365(-IV): Addressable low-profile photoelectric smoke
SLC-2LS: Optional expander module, enables second SLC loop. detector
4XTMF: Optional Transmitter Module provides a supervised output SD355T/SD365T(-IV): Addressable low-profile photoelectric smoke
for local energy municipal box transmitter, alarm and trouble reverse detector with thermal sensor
polarity. It includes a disable switch and disable trouble.
CDRM-300: Dual relay Monitor Module
IPDACT-2/2UD, IPDACT Internet Monitoring Module: Mounts in
CMF-300: Addressable Control Module for one Style Y/Z (Class B/
bottom of enclosure with optional mounting kit (P/N: IPBRKT). Con-
A) zone of supervised polarized Notification Appliances. Mounts
nects to primary and secondary DACT telephone output ports for
directly to a 4.0" (10.16 cm.) electrical box. Notification Appliance
internet communications over customer provided ethernet internet
Circuit option requires external 24 VDC to power notification appli-
connection. Requires compatible Teldat VisorALARM Central Sta-
ances.
tion Receiver. Can use DHCP or static IP. (See data sheet DF-60407
or DF-52424 for additional information. CRF-300: Addressable relay module containing two isolated sets of
Form-C contacts, which operate as a DPDT switch. Mounts directly
IPBRKT: Optional mounting bracket kit consisting of screws and
to a 4.0" (10.16 cm.) box, surface mount using the SMB500.
battery shield with standoffs required when mounting the IPDACT in
lower enclosure section of FACP. MDF-300: Dual Monitor Module. Same as MMF-300 except it pro-
vides two Style B (Class B) only IDCs
IPSPLT: Optional Y-Adaptor which allows connection of both panel
dialer outputs to one cable input to IPDACT (sold separately). MMF-300: Addressable Monitor Module for one zone of normally-
open dry-contact initiating devices. Mounts in standard 4.0" (10.16
ACM-8RF: Optional plug-in relay module provides 8 Form-C 5.0
cm.) box. Includes plastic cover plate and end-of-line resistor. Mod-
amp relays.
ule may be configured for either a Style B (Class B) or Style D (Class
PS-Tools: Programming software for Windows®-based PC com- A) IDC.
puter (cable not included). Available for download at www.fire-
MMF-301: Miniature version of MMF-300. Excludes LED and Style
lite.com.
D option. Connects with wire pigtails. May mount in device backbox.
PRT/PK-CABLE: Cable printer/personal computer interface cable.
MMF-302: Similar to MMF-300, but may monitor up to 20 conven-
DP-9692: Optional dress panel for MS-9600LS(E). tional two-wire detectors. Requires resettable 24 VDC power. Con-
TR-CE: Optional Trim Ring for semi-flush mounting. sult factory for compatible smoke detectors.

BB-55F: Battery box, required to house two 25 AH batteries and BG-12LX: Addressable manual pull station with interface module
one CHG-120F battery charger. For batteries greater than 25 AH, mounted inside
consult factory for housing/mounting arrangements. I300: This module isolates the SLC loop from short circuit conditions
BB-26: Battery backbox, holds up to two 25 AH batteries. (required for Style 6 or 7 operation).

DF-60334:A6 • 2/20/2019 — Page 3 of 6


Audio Control for ECC-50/100 Emergency Command Center

MS-9600LS
ADDRESSABLE
FIRE ALARM CONTROL PANEL
SMOKE
DETECTORS
SD355/T, SD365/T, CP355

by Honeywell

EIA-485
ACS/ANN-BUS
ANNUNCIATORS HEAT
(2-data wires, DETECTORS
2-power wires) H355/R, H365/R
S
A CK

TE 8 FORM-C, 5-AMP RELAYS


P

A LARM

TROUBLE
(optional, order ACM-8RF)
FIRE ALARM ANNUNCIATOR

ANN-80 NACs (Notification


Appliance Circuits) DUCT DETECTORS
BELLS, SIGNALS, STROBES D355PL

EIA-232 DACT-UD2
INTERFACE for Central Station reporting

INTELLIGENT
BEAM DETECTORS
PRINTER Optional BEAM355, BEAM355S
REVERSE OSI-RI-FL
POLARITY/
CITY BOX
OUTPUT
(4XTMF)
ON A B
C D

CN1

MONITOR/CONTROL
A

MMF-300, MDF-300,
MMF-302, CMF-300,
CRF-300, I300, CDRM-300
CN2

4XTMF
PSTN PHONE TO AP FROM AP OUT 2 OUT 1 INPUT 2 INPUT 1 TAMPER GND +24V

Reverse Polarity Module IPDACT


Internet Protocol DACT

WIRELESS MINI MONITOR


Wireless GATEWAY MMF-301
Monitor W-GATE
Module
ADDRESSABLE
W-MMF MULTI-MODULES
Wireless MMF-300-10,
Relay MMF-302-6,
Module CMF-300-6,
CRF-300-6,
W-CRF ISO-6
Wireless
Photo
Detector
W-SD355
Wireless Pull Station
W-BG12LX PULL STATION
BG-12LX

Page 4 of 6 — DF-60334:A6 • 2/20/2019


ISO-6: Six-fault Isolator Module. Mount one or two modules in a BB- NOTE: For more information on Compatible Annunciators for use with
2F cabinet (optional). Mount up to six modules on a CHS-6 chassis the MS-9600LS(E), see the following data sheets (document numbers)
in a BB-6F. ACM-8RF (DF-51555), ACS/ACM Series (DF-52378), LDM Series (DF-
51384), LCD-80F (DF-52185).
SMB500: Used to mount all modules except the MMF-301 and
M301
Wiring Requirements
MMF-300-10: Ten-input monitor module. Mount one or two modules
in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6 While shielded wire is not required, it is recommended that all SLC
chassis in a BB-6F wiring be twisted-pair to minimize the effects of electrical interfer-
ence. Refer to the panel manual for wiring details.
MMF-302-6: Six-zone interface module. Mount one or two modules
in a BB-2F cabinet (optional). Mount up to six modules on a CHS-6
chassis in a BB-6F
CMF-300-6: Six-circuit supervised control module. Mount one or two
modules in a BB-2F cabinet (optional). Mount up to six modules on a
CHS-6 chassis in a BB-6F
CRF-300-6: Six Form-C relay control module. Mount one or two
modules in a BB-2F cabinet (optional). Mount up to six modules on a
CHS-6 chassis in a BB-6F
W-GATE: SWIFT Wireless Gateway
W-DIS-D: LCD user interface for use with the W-GATE wireless
gateway and an ANN-80-W Remote Annunciator
W-SD355: Intelligent, wireless photo detector
W-H355R: Intelligent wireless rate of rise (135°) heat detector
W-SD355T: Intelligent wireless photo/heat detector
W-H355: Intelligent wireless fixed-temperature (135°) heat detector
W-MMF: Intelligent wireless monitor module
W-CRF: Intelligent wireless relay module
W-BG12LX: Intelligent wireless pullstation
WAV-CRL/WAV-CWL: Intelligent wireless AV bases
W-SYNC: Intelligent wireless sync module.
W-USB: Wireless USB radio/antenna dongle that plugs into the
USB port of a PC running SWIFT Tools
SWIFT Tools: Programming and diagnostic utility for the Wireless
Gateway and devices. Available for download from firelite.com.

Compatible Annunciators
ANN-80(-W): Remote LCD annunciator that mimics the information
displayed on the FACP’s LCD display. Recommended wire type is
unshielded. (Basic model is red; order -W version for white; see DF-
52417).
ANN-LED: Annunciator Module provides three LEDs for each zone:
Alarm, Trouble and Supervisory. Ships with red enclosure (see DF-
60241).
ANN-RLED: Provides alarm (red) indicators for up to 30 input zones
or addressable points (see DF-60241).
ANN-RLY: Relay Module, which can be mounted inside the cabinet,
provides 10 programmable Form-C relays (see DF-52431).
ANN-S/PG: Serial/Parallel Printer Gateway module provides a con-
nection for a Serial or Parallel printer (see DF-52429).
ANN-I/O: I/O Driver Module provides connections to a user supplied
graphic annunciator (see DF-52430).
ACS-LED Zone Series: LED-type fire annunciators capable of pro-
viding up to 99 software zones of annunciation. Available in incre-
ments of 16 or 32 points to meet a variety of applications.
ACS-LDM Graphic Series: Lamp Driver Module series for use with
custom graphic annunciators.
LCD-80F Annunciator: 80-character, backlit LCD-type fire annunci-
ators capable of displaying English-language text. Up to 32 LCD-
80F annunciators may be connected to the EIA-485 terminal mode
serial interface on the MS-9600LS(E) motherboard.

DF-60334:A6 • 2/20/2019 — Page 5 of 6


SYSTEM SPECIFICATIONS
System Capacity Shipping Specifications
• Intelligent Signaling Line Circuits.....................1 expandable to 2 Dimensions: 20.00” (50.80 cm) high, 22.5” (57.15 cm) wide, 8.5”
• Intelligent detectors ................................................. 159 per loop (21.59 cm) deep. Weight: 27.3 lbs (12.38 kg).
• Addressable monitor/control modules ..................... 159 per loop
• Programmable software zones ................................................ 99
Temperature and Humidity Ranges
• ANN-BUS devices ..................................................................... 8 This system meets NFPA requirements for operation at 0 – 49°C/32
– 120°F and at a relative humidity 93% ± 2% RH (noncondensing) at
• ACS Annunciators ................................................................... 32
32°C ± 2°C (90°F ± 3°F). However, the useful life of the system's
• LCD Annunciators.................................................................... 32 standby batteries and the electronic components may be adversely
affected by extreme temperature ranges and humidity. Therefore, it
Electrical Specifications is recommended that this system and its peripherals be installed in
an environment with a normal room temperature of 15 – 27°C/60 –
• Primary input power:
80°F.
120 VAC, 50/60 Hz, 3.0 A.
240 VAC, 50 Hz, 1.5 A.
• Battery: 27.6 VDC @ 1.0 A (max).
Agency Listings and Approvals
Maximum battery charger capacity: 26 AH. The listings and approvals below apply to the MS-9600LS(E) and
Minimum battery: 12 AH. MS-9600UDLS(E) control panels. In some cases, certain modules
MS-9600LS cabinet holds maximum of two 18 AH batteries. may not be listed by certain approval agencies, or listing may be in
• Communication Loop: 24 VDC nominal, supervised and power- process. Consult factory for latest listing status.
limited. • ULC: S624 (MS-9600LSC only; see DF-60438)
• Notification Appliance Circuits: terminal block provides connec- • FM APPROVED: to UL ANSI 864
tions for four Style Y (Class B) or two Style Z (Class A) NACs. • CSFM: 7170-0075:217
Maximum signaling current per circuit: 3.0 amps special applica-
tion, 300mA regulated. • MEA: 87-08-E
End-of-Line Resistor: 4.7 K ohms, ½ watt (P/N 71252 UL listed) • IBC 2012, IBC 2009, IBC 2006, IBC 2003, IBC 2000 (Seismic).
for Style Y (Class B) NAC. • CBC 2007 (Seismic)
Supervised and power-limited.
Refer to panel documentation and Fire-Lite Device Compatibility
Document for listed compatible devices.
NFPA Standards
• Two Programmable Form-C Relays and One Fixed Trouble The MS-9600LS(E) and MS-9600UDLS(E) control panels comply
Form-C Relay: Contact rating: 2.0 A @ 30 VDC (resistive) with the following NFPA 72 Fire Alarm Systems requirements:
0.5 A @ 30 VAC (resistive). – LOCAL (Automatic, Manual, Waterflow and Sprinkler Supervi-
• Four-wire Resettable Special Application Power (24 VDC nomi- sory).
nal): Up to 1.5 A for powering four-wire smoke detectors. Power- – AUXILIARY (Automatic, Manual and Waterflow) (requires
Limited, non-supervised. 4XTMF).
Refer to Fire-Lite Device Compatibility Document for listed com- – REMOTE STATION (Automatic, Manual and Waterflow)
patible devices. (Requires 4XTMF where DACT-UD2 is not accepted.)
• Non-resettable Special Application Power #1 (24VDC nominal) – PROPRIETARY (Automatic, Manual and Waterflow).
TB3, Terminals 3 (+) & 4 (-):
Maximum ripple voltage: 10 mVRMS – CENTRAL STATION (Automatic, Manual and Waterflow, and
Total DC current available from each output is up to 1.5 A. Sprinkler Supervised).
Power-limited, non-supervised. – OT (Other Technologies-PSDN) For use with IPDACT.
• Non-resettable Special Application Power #2 (24VDC nominal)
TB3, Terminals 5 (+) & 6 (-):
Maximum ripple voltage: 10 mVRMS
Total DC current available from each output is up to 1.5 A.
Power-limited, non-supervised.
NOTE: Although each Special Application power output can deliver 1.5
A individually, the total power output from these circuits cannot exceed
1.5 A in standby. The total Alarm output for all Special Application power
and NAC circuits cannot exceed 7 A.

Cabinet Specifications
LiteSpeed™ is a trademark; and FireLite® Alarms and SWIFT® are registered
Door: 19.26" (48.92 cm.) high x 16.82" (42.73 cm.) wide x 0.67" trademarks of Honeywell International Inc. Windows® is a trademark of the
(1.70 cm.) deep. Backbox: 19.00" (48.26 cm.) high x 16.65" (42.29 Microsoft Corporation.
cm.) wide x 5.21" (13.23 cm.) deep. Trim Ring (TR-CE): 22.00" ©2019 by Honeywell International Inc. All rights reserved. Unauthorized use of this
(55.88 cm.) high x 19.65" (49.91 cm.) wide. document is strictly prohibited.

This document is not intended to be used for installation purposes.


We try to keep our product information up-to-date and accurate.
We cannot cover all specific applications or anticipate all requirements.
All specifications are subject to change without notice.

For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. Country of Origin: USA
www.firelite.com

Page 6 of 6 — DF-60334:A6 • 2/20/2019