IT COOLING

DATA CENTER COOLING

THE MILESTONE OF GREEN DATA CENTER


COOLING TECHNOLOGY
Climaveneta approach for
perfect data center cooling

THE FUTURE OF DATA CENTERS STRUCTURAL LIMITS RESULT


BRINGS BOTH ADVANCED IN HIGHER AND HIGHER POWER
TECHNOLOGIES AND EXPONENTIAL DENSITIES AFFECTING THE
DATA EXCHANGE THAT STRONGLY DEVELOPMENT AND DESIGN
INCREASES HEAT LOADS PER OF SERVER ROOMS.
SQUARE METER.

KEY FEATURES OF MODERN DATA CENTERS:

HIGH FLEXIBILITY GREAT SCALABILITY

Data centers require scalable design to: Data center design changes rapidly in terms of:

a Manage different heat loads for different areas a Shape & architecture
a Manage an increasing heat load over time a Computing capacity
a Accomodate new areas to be cooled a New technologies, always adopting the latest rack
and server solutions
a Heat dissipation

02/03
02/03

Energy efficiency is crucial in data centers that require the 40kW in less than one square meter (or 10 square feet).
latest cooling technologies to ensure the reliability and high Cooling such loads is a serious challenge for the air
performance of these critical applications. conditioning industry and only solid technological innovations
backed by R&D and experienced staff can provide the right
Server usage in both upgraded and newly designed data solutions.
centers will, over time, lead to increasingly higher performance
that will eventually result in higher density power loads. The answers lie in the use and combination of the most
sophisticated technologies such as MAGNETIC LEVITATION
The data center environment is critical and requires a and FULL ELECTRONIC MODULATION cooling equipment.
guarantee of reliability, device safety, and modularity.
As a race car needs an experienced driver, high tech
Preparing for the modular infrastructure evolution, components require superb design capacities as well
the IT room has several standards, classifications, as a deep understanding of the application’s requirements.
and certifications to comply with.
Climaveneta range of IT COOLING solutions includes state
The key factor that must be continuously improved is energy of the art, efficient, and reliable cooling technologies for ICT
efficiency to cope with more demanding OPEX requirements, environments.
and the global footprint, which greatly affects CAPEX.

Virtualisation, Cloud Computing, and Internal Redundancy


also greatly contribute to server room development with many
powerful and concentrated servers creating racks exceeding

INCREASING HEAT LOADS RELIABLE OPERATION

The growth of microprocessor performance leads to Redundancy is the typical way to increase uptime.
the growth of power generated density. In facing the cooling problems only smart solutions can
avoid the disaster of shut-down while limiting CAPEX
Besides this, progressive diffusion of incoming and OPEX. Reliability must look at a full 360° view.
virtualisation and blade servers characterised by
increasing power in limited volumes, leads to the
unrelenting growth of loads which consequently
increases thermal power per m2.
BUILDING AN ENHANCED
MODEL FOR TOP DATA CENTER
EFFICIENCY
Built on the profound experience of both the Climaveneta and RC, the
new Climaveneta IT Cooling solutions merge the best technologies of
the two brands with the top quality approach of Mitsubishi Electric to
ensure:

HIGH
Density Zone
> 25 kW/rack
MEDIUM
Density Zone
10 - 20 kW/rack

LOW
Density Zone
< 5 kW/rack

CLIMAVENETA IT COOLING Optimised air


BEST PRACTICES Hot and cold aisles
flow management
Extensive research in this Optimised air flow design, directing Hot & cold aisles address layout
application has resulted in some cold air through the raised floor air-flow to the servers to ensure
best practices, which are a must to form cold aisles in front of the a constant temperature. Working
for an efficient data center. rack air intake. conditions become more stable
and the efficiency of the whole
Climaveneta for IT COOLING cooling system increases.
solutions are designed to
perfectly fit with this
approach.

04/05
04/05

HIGHEST EFFICIENCY AND REDUCED OPERATING COSTS


The growing energy demand in modern data centers implies that every energy improvement allows
for a significant reduction in OPEX (operating costs). In infrastructures working 24 hours per day, 365
days per year, over an average of 10 years, this accounts for the largest proportion of overall costs.

Climaveneta IT Cooling solutions put great efforts on the use of high quality components such as the EC
PUL (polymeric ultralight) fans and the full DC inverter technology applied both on the compressors and
fans.

INCREASED kW/SQUARE METER


It is well-known that set loads in technological applications are rapidly increasing.
The expansion in data exchange in generating heat loads that are usually localized
in specific areas called hot spots.

This means that air conditioning systems are required to be more and more performing,
even if space available is still the same. In this sense, Climaveneta for IT COOLING range
ensures
the best power/footprint ratio in the market.

COMPLETE COOLING PACKAGE

Climaveneta for IT COOLING range features 360° versatility, both a s concerns capacities, as well as
configurations. Perimeter air conditioners, together with close-coupled solutions ensure effective cooling
for low-medium and high density areas. Data center infrastructures and PDU solutions complete the range
provinding customers a complete cooling package for your data center.

UNITS FOR HIGH TEMPERATURE ENVIRONMENTS


The need for higher efficiency levels and reduced TCO values have led to
increasing temperatures (up to 27°C) of intake airflows directed to the IT
equipment (ASHRAE, ‘Thermal Guidelines for Data Processing Environments’),
thus increasing supply air temperatures.

Climaveneta Close control units have been designed to manage such air suction
temperature up to 40°C. Available both as Dual Fluid (DF) and Free Cooling (FC)
versions, NEXT air conditioners optimize the primary water circuit performance
even with high temperature fluids.
UP TO
The chiller’s efficiency and the free cooling operation are therefore maximized 18-27°C 40°C
also when outdoor temperatures are high.

TOTAL RELIABILITY AND EXTENDED LIFE CYCLE


Reliability is key when it comes to IT infrastructures.
In all these applications, an interruption in the cooling supply may seriously compromise the technical
equipment operation, causing unexpected shutdowns.

Climaveneta’s approach to cooling dependability goes beyond the unit’s accurate and sturdy design.
It also involves several devices and functions that maximise unit’s uptime in case of emergency
circumstances such as power supply outage.

Highest efficiency with


Localised cooling water cooled systems
Dedicated localised cooling Optimised hydronic solutions for
directly targets hot spots HPAC combine energy efficiency
as well as integrating the with flexible performance and
hot & cold aisle. utmost reliability.
MEASURING EFFICIENCY
TO IMPROVE IT
The awareness of data center All Climaveneta IT Cooling solutions are
requirements and the commitment to developed to optimise these metrics,
improve their energy efficiency has allowing for a transparent evaluation of
led to the development of dedicated the real benefits offered by our approach
indices for these applications. to HD.

DATA CENTER COOLING &


POWER LOAD CONSUMPTION

Power and cooling represent the lion’s


share of the energy consumed in a data 55%
45%
center, although they are not directly
linked with the value adding operations Power and
of the data center. cooling
IT load
Accurate measurements of heat loads
are the essential base for highly efficient
green data center design.

DATA CENTER POWER


CONSUMPTION BY APPARATUS

Data center power consumption by apparatus


50%
Chiller
Chiller
45%

40% 7% IT IT equipment
equipment
35%
6% Power
Power distrib.
distrib. units units
30%
30%
CRAC
CRAC
25%
Humidification
Humidification
20% 18%
15% UPS
UPS
10% 32% Lighting
Lighting
5%
5%
1% 1% Switchgear/generator
Switchgear/generator
0%

06/07
06/07

CAPEX
Capital Expenditure

A data center is a valuable asset for a company. All expenses


relating to the infrastructure, especially high-tech solutions,
remain within the company by adding value and extending the
life span of the data center.

OPEX
Operating Expenditure

Running costs of a data center operating 24 hours a day,


365 days a year for an average of 10 years, are crucial for
those who must manage it. Even a small saving becomes
very significant over time. This justifies even very high initial
investments and justifies an anticipated system refurbishment,
aimed at improving their efficiency.

PUE Percentage of effectiveness =


Total Facility Power / Equipment Power

PUE considers the overall energy efficiency of the data center,


measured as the ratio between total absorbed power and the
power needed by the servers. As only energy used to transfer
data creates value for the data center, a ratio close to 1 would
represent the condition of optimum efficiency. Most data
centers have a PUE between 2 and 3, excellent values are
between 1,2 and 1,5.

DCiE = 1/PUE x 100

Reciprocal of PUE, DCiE shows the % of power absorbed


by IT infrastructure, compared to the overall data center
consumption.
Values close to 33% are usual for traditional data centers.
DCiE of 66% reflects a very high energy efficiency.
DEDICATED APPROACH
FOR HIGHLY EFFICIENT
DATA CENTERS
Climaveneta IT Cooling solutions are adaptive cooling systems based on actual
data center heat load requirements (kW/rack).

Designed to achieve unparalleled efficiency perfomance and total reliability,


the wide range of high precision solutions provides customers with
the answer for every kind of data center.

LOW MEDIUM
Density Zone Density Zone
< 5 kW/rack 10 - 20 kW/rack

Aisle Containment
AISLE CONTAINMENT prevents the
HOT & COLD air from mixing in the
upper section of the racks,
guaranteeing homogeneous air flow.

Hot/Cold aisle
a No mixing between Hot & Cold air
An easy, fast and long-lasting solution; streams in order to avoid energy
the hot & cold aisle is the basic and waste.
essential concept that drives the layout
of all data denters. a Additional 15% energy saving
depending on the data center
layout.
a Through the raised floor, air can
be easily delivered exactly where
required (in front of the rack)
allowing easy management of
redundant cooling units.

a Flexible design, providing maximum


freedom in accommodating new
rack distribution or even major
infrastructure changes.

a Lowest CAPEX allows more


investment in more productive
equipment.

08/09
08/09

HIGH
Density Zone
> 25 kW/rack

Aisle Containment +
Localised Cooling to
manage hot spots
CCD (Climaveneta for IT COOLING
Door) & CCV (Climaveneta for IT
COOLING Rack Cooler) guarantee
ideal integration to manage HOT
SPOTS caused by new blade servers,
providing extra local cooling exactly
where it is needed.
a Quick and easy solution with low
initial investments. a Extra cooling only where a Modulating Air flow thanks
required. to EC high efficiency fans.
a Complete integration with The fans adapt to the thermal
existing perimeter CRAC units. a Direct expansion inverter load detected by sensors
type or Chilled water system positioned in the hot and cold
a Immediate energy benefits. for complete cooling system aisle. This increases efficiency
flexibility. and reduces air stratification.

a Perfectly compatible with most


racks and ready for extension
of the cooling system.
LOW
HOT/COLD AISLE
Density Zone
< 5 kW/rack
Data centers are specifically designed to create hot
and cold aisles. Cold air is delivered through the
floor or ducts exactly where it is needed and hot
air returns to the HPAC units, thus improving the set
point and the overall energy efficiency of the system.

THIS SYSTEM ALLOWS:

a High efficiency
a Perfect redundancy
a Quick and easy expansion
a Low initial investment

HOT AND COLD AISLE CONFIGURATION

The hot and cold aisle solution overcomes the limits of a traditional
approach where cooling aims to maintain stable room conditions,
forgetting to focus on the racks requirements.

In the last decade the data center design has dramatically The arrangement of rack servers according to
changed. Years ago data center design was not driven by heat this logic allows delivery of cold air-flow exactly where it is
loads, so server distribution in the room was driven by other needed - i.e. typically in front of the racks, greatly reducing
needs leading to only one reference room temperature. This the chances of cold and hot air mixing. This system increases
used to be from 18°C to 24°C and it was an accepted standard the efficiency of the cooling system by 20% if compared to
throughout the world. As soon as server heat generation traditional layouts.
increased, it became clear a more rational distribution of heat
was necessary; this resulted in the Hot & Cold Aisle concept. On the other hand, this new concept requires two levels of
temperatures to be properly defined.The optimisation of these
temperatures leads to greatly improved working conditions.

10/11
10/11

CLOSE CONTROL AIR CONDITIONERS


Constant air flow and pressure management systems

ACCURATE LEGACY air conditioners are located along the walls.

This essential concept drives the layout of the majority of data centers.

Through theraised floor, air can be easily delivered exactly where


required, creating hot and cold aisles within the data center.

- ACCURATE LEGACY Direct expansion air conditioners


- w-ACCURATE LEGACY Chilled water close control units air conditioners
- i-ACCURATE LEGACY Direct expansion air conditioners with full DC inverter technology.

EVAPORATIVE COOLING SYSTEM

a Variable air flow and cooling capacity


a Fully aluminium structure (20 years warranty against corrosion)
a Low pPue index: 1,025
a Modular units
MEDIUM
AISLE CONTAINMENT
Density Zone
10 - 20 kW/rack
When hot and cold aisles are not enough to
prevent air mixing, Aisle Containment ensures
a perfect and homogeneous airflow to the
server inlet.

THIS SYSTEM ALLOWS:

a significant improvement in efficiency


a tight control of conditioned air
feeding the servers
a the addition of more servers in less
volume

AISLE CONTAINMENT

In medium/high density applications the presence of hot and


cold aisles is not enough to prevent the mix of supply and
return air.

This mix results in air flow with a temperature that reduces the
performance of the data center. If such air goes to the servers
and it is warmer than expected the servers may stop working
due to overheating.

If mixed air goes to the cooling system and it is cooler than air
coming out from the servers, heat exchange is reduced and
then global efficiency is affected.

Therefore it is necessary to provide a physical separation for


the two airflows.This is achieved by using aisle containment,
which is a simple and cost effective solution: it guarantees the
servers are fed with the cold air and the cooling system is more
efficient.

The image above shows an excellent example of the


advantages in terms of hot and cold flow separation
obtained through aisle containment.

12/13
12/13

CLIMAVENETA for IT COOLING AISLE CONTAINMENT

COLD AISLE containment


The decision regarding the use of aisle containment needs
to be analyzed on project to project basis as it is affected by
different factors such as: room dimensions, shape, heat load
and density, cooling technology, redundancy provisions and
more.

In practice Climaveneta for IT COOLING package provides two


methods for aisle containment:

1 Cold Aisle Containment, which provides tight control


to the cold air feeding the servers.

2 Hot Aisle Containment, which confines hot discharge


air from servers to one zone.

Both the Hot and Cold Aisle Containment Systems provided


by Climaveneta for IT COOLING represent the perfect
solution to: HOT AISLE containment

a Increase energy efficency thanks to a complete separation


of hot and cold air streams
a Easily expand your data center if required by the layout
of the environment
a Perfectly integrate with different cooling technologies:
- Inverter
- In row units / Enclosure units
- Cooling door units
a Optimise the available space
a Adapt easily with or without raised floor design
HIGH
AISLE CONTAINMENT + LOCALISED COOLING
Density Zone
> 25 kW/rack This solution must accomodate the most critical
heat load densities. Here hot-spots cannot be
avoided without Climaveneta for IT COOLING’s
localised air conditioners which are the best
answer for dealing with hot spot management,
providing extra local cooling exactly where it is
needed.

THIS SYSTEM ALLOWS:

a Maximisation of the internal capacity


of the infrastructure
a Elimination of hot spots
a Minimum floorspace occupancy

CLOSE-COUPLED SOLUTIONS FOR HIGH DENSITY RACKS

CCD LEGACY
Close-Coupled Solution For High Density Racks

a Additional cooling capacity thanks to


chilled water coil available in both single
& double circuit

a Zero footprint

a Adaptable for almost all racks

a Top energy efficiency with electronically


controlled fans modulated to actual
needs

a Dynamic air stratification management


Tight control of the rack temperatures
thanks to 8 independent sensors

a Flexible connections From the top


and from the bottom depending on the
customer’s choice and on raised floor
availability

a Ready to operate with latest generation


32 - 36 °C 43 - 50 °C 20 - 25 °C chillers featuring magnetic levitation and
free-cooling technologies.

14/15
14/15

CRC LEGACY
Rack Cooling Solutions

a Large savings due to the limited


air volume, scalability &
modularity
a Optimal solution for single rack
a 100% redundancy

CRCX: Direct Expansion CRCD: Dual Fluid CRCX ROW: Direct Expansion
with integrated compressor
a DC inverter compressor a DC inverter compressor
a New generation EC brushless fans a Double coil a Installation within the row; do not
a Capacity from 4,7 to 68,3 kW a Capacity from 4,5 to 16,7 Kw require underfloor plenum, ducts or
false-ceilings
a DC inverter compressor integrated
CRCF: Free Cooling within the air conditioner
CRCC: Chilled Water
a Capacity from 14 to 39 kW
a New generation EC brushless fans a DC inverter compressor
a 3-way modulating valve a New-generation EC brushless fans
a Capacity from 16 to 74,7 kW a Capacity from 4,6 to 17,5 kW
a 60% of the year in the free cooling
Mode
ADVANCED TECHNOLOGIES
FOR EFFICIENT DATA CENTERS
Climaveneta IT Cooling leadership in data center cooling systems is
backed by 50 years of experience in the smart integration of premium
technologies for complex IT cooling projects.

SMART THERMAL
ACTIVE REDUNDANCY
ENERGY MANAGEMENT

A real active redundancy achieved through An innovative heat recovery system which
the adoption of innovative EC PUL fans allows Climaveneta for IT COOLING units
together with Inverter DC brushless to synergistically match both the cooling
compressors (on direct expansion units) and sources of the data center with the heating
an advanced algorithm for balancing the heat requirements inside the building, by moving
loads among the units (including those units the heat from the data center to other areas
that usually remain in stand-by). inside the building.

16/17
16/17

1 / MAGNETIC LEVITATION 2 / ACTIVE FREE COOLING

An extended range of chillers with magnetic levitation An advanced free cooling system available both
centrifugal compressors from 200kW, both air source as direct and indirect free cooling (no glycol),
and water source, available also in free cooling and to exploit the outdoor air to cool the data center.
evaporative free cooling versions, to deliver the highest
effiency in every application.

3 / GREEN HFO REFRIGERANTS 4 / ADAPTIVE SET POINT

Following the vast experience in using green refrigerants, An advanced algorithm instantaneously detects the
Climaveneta IT Cooling has already employed extensively real thermal loads of indoor units and conveys this
green HFO refrigerants such as HFO1234ze in many information to chiller, to select the most efficient
ranges, in order to continue to be at the forefront of green operating mode.
best practices.

5 / EVAPORATIVE 6 / X-TYPE 7 / SHR=1 8 / AISLE


COOLING SYSTEM CONTAINMENT

The latest AHR solution with The revolutionary double stage Additional full sensible A significant improvement
2-stage indirect adiabatic design applied to the heat cooling capacity in efficiency thanks to a tight
free-cooling section. exchangers in order to achieve control of the conditioned
pPUE down to 1,025. top level efficiency and pPUE air feeding the servers and
levels down to 1,07. to the addition of more
servers in less volume.

9 / ELECTRONIC EXPANSION VALVE 10 / EC FANS 11 / ELECTRONIC INVERTER


DRIVEN COMPRESSOR
The Electronic Expansion Valve allows NEW GENERATION EC FANS
ultimate compressor working conditions The high efficiency EC fan reduces Modulating the cooling capacity results
in order to achieve the most efficient both noise levels as well as energy in a major increase of energy efficiency:
performances and to avoid dangerous consumption, and assures a variable EER can rise from the typical 2,7 to 5,2
downtimes. air flow at part loads. Operational costs and more!
are reduced by -15% if compared
to traditional EC-Fans, and 25% if Redundant unit will not be a dead
compared to plug fans. investment as it will be on duty at
extremely partialised loads thus granting
EC FANS ALSO IN THE REMOTE cooling capacity with greater efficiency.
CONDENSERS
The use of EC technology even on the i-ACCURATE LEGACY represents
remote condenser fans assures a further the ultimate MILESTONE in data
average reduction of noise levels by center cooling, providing a FULLY
10%, together with a strong energy ELECTRONICALLY CONTROLLED
consumption reduction by 45% when air conditioners.
compared with traditional condensers
with AC technology.
CLIMAVENETA IT COOLING RANGE
A complete cooling package to make your ICT
environment run at peak efficiency
CLOSE CONTROL AIR CONDITIONERS

ACCURATE LEGACY Direct expansion close control air conditioners

a High efficiency a Quick and Easy expansion of the cooling system


a Active Redundancy system

ON / OFF INVERTER

b-AV DX /t-AV DX i-AV DX


Air cooled direct expansion air conditioners Air cooled direct expansion air conditioners with full DC inverter technology
From 6 to 143 kW From 9 to 129 kW
t-AV DF DX i-AV DF DX
Air cooled direct expansion air conditioners Air cooled direct expansion air conditioners with Dual Fluid system
with Dual Fluid system - From 10,3 to 149 kW with full DC inverter technology - From 9 to 141 kW
b-AV DW /t-AV DW i-AV DW
Water cooled direct expansion air conditioners Water cooled direct expansion air conditioners with full DC inverter
From 7,8 to 156 kW technology - From 9,7 to 141 kW
t-AV DF DW i-AV DF DW
Water cooled direct expansion air conditioners Water cooled direct expansion air conditioners with Dual Fluid
with Dual Fluid system - From 7,8 to 156 kW system with full DC inverter technology - From 9,7 to 150 kW
t-AV FC DW i-AV FC DW
Water cooled direct expansion air conditioners Water cooled direct expansion air conditioners with Free Cooling
with Free Cooling system - From 7,8 to 157 kW system with full DC inverter technology - From 9,7 to 141 kW

ACCURATE LEGACY Direct expansion close control air conditioners for laboratories

i-AX PRECISE
Direct expansion air conditioners with inverter technology - From 11 to 16,6 kW

w-ACCURATE LEGACY Chilled water close control units

w-AV S w-AV DF
Chilled water air conditioners - From 6,7 to 213 kW Chilled water air conditioners with double chilled water coil
From 13,3 to 163 kW
w-AV 2 S/K
2-Section chilled water air conditioners - From 57,8 to 227 kW w-AV 2DF
2-Section chilled water air conditioners with double chilled water coil
w-AV HD S/K
From 63,5 to 243 kW
Chilled water air conditioners for high density
From 15,3 to 183 kW

ACCURATE LEGACY close control air conditioners for high temperatures, high delta T

AV-XT
Chilled water air conditioners with X-type coil technology - From 49,3 to 173 kW

Close Control Units with Displacement Air Delivery

t-AV DL DX
Air cooled direct expansion air conditioners
From 7,6 to 42,6 kW
i-AV DL DX w-AV DL DX
Air cooled direct expansion air conditioners with Chilled water air conditionerstechnology
full DC inverter technology - From 16,2 to 40,5 kW From 11,6 to 41,3 kW

18/19
18/19

AIR CONDITIONERS FOR HIGH DENSITY RACKS AND BLADE SERVERS

Close-coupled air conditioners

a Maximalization of the internal capacity of the infrastructures a Minimum floorspace occupancy


a Elimination if hot spots

CRCX CRCD
Direct Expansion Rack Cooler unit Dual Fluid Rack Cooler unit
From 4,7 to 68,3 kW From 4,5 to 16,7kW

CRCC CRCF
Chilled Water Rack Cooler unit Free Cooling Rack Cooler unit
From 16 to 74,7 kW From 4,6 to 17,5 kW

CRCX ROW
Direct Expansion Rack Cooler unit with integrated compressor
From 14 to 39 kW

REMOTE CONDENSERS AND DRY COOLER

a Optimised to be combined with close control air conditioners


a High capacity sensitive cooling

Air cooled remote condenser


Motocondensing unit with inverter compressors
Dry cooler
Moto drycooling unit with inverter compressors

2-STAGE INDIRECT EVAPORATIVE


COOLING SYSTEM FOR LARGE DATA CENTERS

a Variable air flow and cooling capacity a Low pPUE index: 1,025
a Fully aluminium structure (20-year warrenty against corrosion) a Modular units

DATA CENTER INFRASTRUCTURE

a RACKS a Aisle Containment a PDUs a Raised Floors


High quality cabinets Aisle Containment Premium Rack Power Raised floor solutions for
for the protection and solutions for high density Technology high efficiency data
housing of servers applications centers
CHILLERS
a Reduced pPUE
a Optimized for High Delta T operation
a Reduced pump costs
a ADAPTIVE SET POINT: Smart communication between indoor and outdoor units
a Compliant with the strictest best practice in data center design

Sturdy and resilient

Optimised for set point 20°C

Active redundancy function available

Air Cooled Chillers R


SCROLL
NX-Z i-FX (1+i)-Z
Chillers with scroll compressors Chillers with screw compressors and inverter technology
From 39 to 885 kW From 567 to 1273 kW

2,/)5((
i-NX-Z TECS2-Z
Chillers with screw compressors and inverter technology Chillers with oil-free inverter compressors
From 32 to 129 kW From 220 to 1324 kW

R 2,/)5((
FX-Z TECS2 HFO-Z
Chillers with screw compressors Chillers with oil-free inverter compressors and HFO refrigerant
From 145 to 1710 kW From 339 to 1017 kW

High efficiency

Widest cooling capacity range

Active redundancy function available

Water Cooled Chillers R

2,/)5((
NX-W-Z FOCS3-W-Z
Chillers with scroll compressors Chillers with oil-free inverter compressors
From 38 to 398 kW From 241 to 1949 kW

R 2,/)5((
FX-W-Z TECS2 HFO-Z
Chillers with screw compressors Chillers with oil-free inverter compressors and HFO refrigerant
From 124 to 1693 kW From 340 to 1364 kW

2,/)5((
i-FX-W (1+i)-Z TX-W-Z
Chillers with screw compressors and inverter technology Chillers with oil-free inverter compressors
From 468 to 1637 kW From 246 to 4191 kW

20/21
20/21

FROM THE PROFOUND EXPERIENCE OF BOTH THE RC AND CLIMAVENETA


BRANDS, TOGETHER WITH THE TOP-QUALITY STANDARDS OF MITSUBISHI
ELECTRIC, A COMPLETE LINE OF CHILLERS SPECIFICALLY DESIGNED FOR
IT COOLING EVIRONMENTS.

UTMOST RELIABILITY

100% FREE COOLING at 12°C

ADAPTIVE SET POINT

Air Cooled Chillers

NECS-FC-Z FX-EFC-Z
Chillers with scroll compressors and free-cooling technology Chillers with screw compressors and evaporative free-cooling
From 41 to 477 kW technology
From 329 to 1441 kW

FX-FC-Z 2,/)5((
Chillers with screw compressors and free-cooling technology
From 332 to 1450 kW TECS-EFC-Z
Chillers with oil-free compressors and evaporative free-cooling
technology
2,/)5(( From 300 to 1682 kW
TECS-FC-Z
Chillers with oil-free compressors and free-cooling technology
From 302 to 1693 kW

CONTROL, SUPERVISION AND OPTIMISATION SYSTEMS

a Supervision and Monitoring a Optimisation systems


Systems a ClimaPRO_DCO
The ultimate solutions for Data Center Optimisationsystem
supervision, remote monitoring, Data Center IT COOLING
service, and preventive maintenance system
optimiser for real time, smart
a FWS3 / FWS3000 management of energy indeces
remote monitoring systems for the single units and the entire
a Climaveneta Cloud - Cloud based plant room.
remote monitoring system
a WS3000 a Human Machine Interfaces
Remote monitoring system for
service and proactive maintenance a KIPlink
Control interface for smart
phones and tablets
a Control Systems
a DATA MANAGER 3000
Specialized group control for
Data Center air conditioners
“EXPERIENCE IS BY FAR
THE BEST PROOF”
Sir Francis Bacon
British Philosopher (1561-1626)

proRZ
Munich, Germany
proRZ is one of the main German general
contractors, which realizes and optimizes
data centers of any size, focusing
on the fulfilment of individual requirements.

Cooling Capacity:
1800 kW
Installed machines:
2x High-efficiency free cooling
Air cooled unit with magnetic
levitation centrifugal compressors
14x Chilled water air conditioners

WIIT Tier IV
2014 Milan, Italy
WIIT is an italian company focused on Private
and Hybrid continuative services, it is one of the
main players in Europe and Worldwide among the
most specialized players in application management
and critical application as disaster recovery and
business continuity.

Cooling Capacity:
700kW
Installed machines:
12X Close Control Air Conditioners
with downflow air delivery equipped
with BLDC scroll compressors
18x Remote condensers

22/23
22/23

FastWeb Tier IV
2014 Milan, Italy
Fastweb, a telecommunications operator,
decided to build a new data center offering
the highest level of security possible to its clients.

Cooling Capacity:
2800 kW
Installed machines:
4x High-efficiency Air cooled unit
with magnetic levitation centrifugal
compressors.

Unipol Tier IV
2015-2016 Bologna, Italy
Unipol is the second largest insurance group on
the italian market and the first in Non-Life business,
classified among the top ten in Europe.

Cooling Capacity:
2300 kW
Installed machines:
4x High-efficiency Air cooled unit
with magnetic levitation centrifugal
compressors
CLIMAVENETA for IT COOLING_05-2018_ENG