VRV Iiis Minivrv Sibe34 802
VRV Iiis Minivrv Sibe34 802
VRV Iiis Minivrv Sibe34 802
Service
Manual
RXYSQ4-5-6PA7Y1B, PA7V1B
R-410A
HEAT Pump 50Hz
SiENBE34-802
R-410A
Heat Pump
50Hz
1. Introduction ........................................................................................... vi
1.1 Safety Cautions ....................................................................................... vi
1.2 PREFACE ................................................................................................x
Part 5 Function............................................................................ 47
1. Operation Mode.......................................................................................48
2. Basic Control ...................................................................................................49
2.1 Normal Operation ...................................................................................49
2.2 Compressor PI Control...........................................................................50
2.3 Electronic Expansion Valve PI Control...................................................51
2.4 Cooling Operation Fan Control...............................................................52
3. Special Control ................................................................................................53
3.1 Startup Control .......................................................................................53
3.2 Oil Return Operation ..............................................................................54
3.3 Defrosting Operation ..............................................................................56
3.4 Pump-down Residual Operation ............................................................57
Table of Contents i
SiENBE34-802
ii Table of Contents
SiENBE34-802
3.11 “C4” Indoor Unit: Malfunction of Thermistor (R2T) for Heat Exchanger 156
3.12 “C5” Indoor Unit: Malfunction of Thermistor (R3T) for Gas Pipes .........157
3.13 “C6” Indoor Unit: Failure of Combination
(Between Indoor unit PC Board and Fan PC Board)............................158
3.14 “C9” Indoor Unit: Malfunction of Thermistor (R1T) for Suction Air ........159
3.15 “CA” Indoor Unit: Malfunction of Thermistor for Discharge Air ..............160
3.16 “CC” Indoor Unit: Malfunction of Humidity Sensor System ....................161
3.17 “CJ” Indoor Unit: Malfunction of Thermostat Sensor in Remote Control ....162
3.18 “E1” Outdoor Unit: PC Board Defect......................................................163
3.19 “E3” Outdoor Unit: Actuation of High Pressure Switch..........................164
3.20 “E4” Outdoor Unit: Actuation of Low Pressure Sensor .........................166
3.21 “E5” Inverter Compressor Motor Lock...................................................168
3.22 “E7” Malfunction of Outdoor Unit Fan Motor .........................................169
3.23 “E9” Outdoor Unit: Malfunction of Moving Part of Electronic
Expansion Valve (Y1E, Y3E)................................................................170
3.24 “F3” Outdoor Unit: Abnormal Discharge Pipe Temperature..................172
3.25 “F6” Outdoor Unit: Refrigerant Overcharged ........................................173
3.26 “H9” Outdoor Unit: Malfunction of Thermistor (R1T) for Outdoor Air ....174
3.27 “J3” Outdoor Unit: Malfunction of Discharge Pipe Thermistor (R2T)....175
3.28 “J5” Outdoor Unit: Malfunction of Thermistor (R3T, R5T)
for Suction Pipe 1, 2 .............................................................................176
3.29 “J6” Outdoor Unit: Malfunction of Thermistor (R6T).............................177
3.30 “J7” Outdoor Unit: Malfunction of Thermistor (R7T) for
Outdoor Unit Liquid Pipe ......................................................................178
3.31 “J9” Outdoor Unit: Malfunction of Thermistor (R4T).............................179
3.32 “JA” Outdoor Unit: Malfunction of High Pressure Sensor .....................180
3.33 “JC” Outdoor Unit: Malfunction of Low Pressure Sensor ......................181
3.34 “L1” Outdoor Unit: Malfunction of PC Board ..........................................182
3.35 “L4” Outdoor Unit: Malfunction of Inverter Radiating Fin Temperature Rise 183
3.36 “L5” Outdoor Unit: Inverter Compressor Abnormal...............................184
3.37 “L8” Outdoor Unit: Inverter Current Abnormal ......................................185
3.38 “L9” Outdoor Unit: Inverter Start up Error .............................................186
3.39 “LC” Outdoor Unit: Malfunction of Transmission between Inverter
and Control PC Board ..........................................................................187
3.40 “P1” Outdoor Unit: High Voltage of Capacitor in Main Inverter Circuit...188
3.41 “U0” Low Pressure Drop Due to Refrigerant Shortage or
Electronic Expansion Valve Failure......................................................189
3.42 “U2” Power Supply Insufficient or Instantaneous Failure......................191
3.43 “U3” Check Operation not Executed .....................................................193
3.44 “U4” Malfunction of Transmission between Indoor Units and Outdoor Units 194
3.45 “U5” Malfunction of Transmission between Remote Control and Indoor Unit 196
3.46 “U8” Malfunction of Transmission between Main and Sub Remote Controls 197
3.47 “U9” Malfunction of Transmission between Indoor and Outdoor
Units in the Same System ....................................................................198
3.48 “UA” Excessive Number of Indoor Units................................................200
3.49 “UC” Address Duplication of Central Remote Control ...........................201
3.50 “UE” Malfunction of Transmission between Central Remote Control
and Indoor Unit.....................................................................................202
3.51 “UF” System is not Set yet ....................................................................203
3.52 “UH” Malfunction of System, Refrigerant System Address Undefined ..204
Index ............................................................................................. i
iv Table of Contents
Introduction SiENBE34-802
1. Introduction
1.1 Safety Cautions
Cautions and Be sure to read the following safety cautions before conducting repair work.
Warnings The caution items are classified into “ Warning” and “ Caution”. The “ Warning”
items are especially important since they can lead to death or serious injury if they are not
followed closely. The “ Caution” items can also lead to serious accidents under some
conditions if they are not followed. Therefore, be sure to observe all the safety caution items
described below.
About the pictograms
This symbol indicates an item for which caution must be exercised.
The pictogram shows the item to which attention must be paid.
This symbol indicates a prohibited action.
The prohibited item or action is shown inside or near the symbol.
This symbol indicates an action that must be taken, or an instruction.
The instruction is shown inside or near the symbol.
After the repair work is complete, be sure to conduct a test operation to ensure that the
equipment operates normally, and explain the cautions for operating the product to the
customer
1.1.1 Caution in Repair
Warning
Be sure to disconnect the power cable plug from the plug socket before
disassembling the equipment for a repair.
Working on the equipment that is connected to a power supply can cause an
electrical shook.
If it is necessary to supply power to the equipment to conduct the repair or
inspecting the circuits, do not touch any electrically charged sections of the
equipment.
If the refrigerant gas discharges during the repair work, do not touch the
discharging refrigerant gas.
The refrigerant gas can cause frostbite.
Do not start or stop the air conditioner operation by plugging or unplugging the
power cable plug.
Plugging or unplugging the power cable plug to operate the equipment can
cause an electrical shock or fire.
vi
SiENBE34-802 Introduction
Caution
Do not repair the electrical components with wet hands.
Working on the equipment with wet hands can cause an electrical shock.
Be sure to turn off the power switch and unplug the power cable when cleaning
the equipment.
The internal fan rotates at a high speed, and cause injury.
Be sure to check that the refrigerating cycle section has cooled down
sufficiently before conducting repair work.
Working on the unit when the refrigerating cycle section is hot can cause burns.
Use the welder in a well-ventilated place.
Using the welder in an enclosed room can cause oxygen deficiency.
vii
Introduction SiENBE34-802
Warning
Be sure to use the specified cable to connect between the indoor and outdoor
units. Make the connections securely and route the cable properly so that there
is no force pulling the cable at the connection terminals.
Improper connections can cause excessive heat generation or fire.
When connecting the cable between the indoor and outdoor units, make sure
that the terminal cover does not lift off or dismount because of the cable.
If the cover is not mounted properly, the terminal connection section can cause
an electrical shock, excessive heat generation or fire.
Do not damage or modify the power cable.
Damaged or modified power cable can cause an electrical shock or fire.
Placing heavy items on the power cable, and heating or pulling the power cable
can damage the cable.
Do not mix air or gas other than the specified refrigerant (R-410A) in the
refrigerant system.
If air enters the refrigerating system, an excessively high pressure results,
causing equipment damage and injury.
If the refrigerant gas leaks, be sure to locate the leak and repair it before
charging the refrigerant. After charging refrigerant, make sure that there is no
refrigerant leak.
If the leak cannot be located and the repair work must be stopped, be sure to
perform pump-down and close the service valve, to prevent the refrigerant gas
from leaking into the room. The refrigerant gas itself is harmless, but it can
generate toxic gases when it contacts flames, such as fan and other heaters,
stoves and ranges.
When replacing the coin battery in the Remote Control, be sure to disposed of
the old battery to prevent children from swallowing it.
If a child swallows the coin battery, see a doctor immediately.
Caution
Installation of a leakage breaker is necessary in some cases depending on the
conditions of the installation site, to prevent electrical shocks.
Do not install the equipment in a place where there is a possibility of
combustible gas leaks.
If a combustible gas leaks and remains around the unit, it can cause a fire.
Be sure to install the packing and seal on the installation frame properly. For integral units
If the packing and seal are not installed properly, water can enter the room and only
wet the furniture and floor.
If the power cable and lead wires have scratches or deteriorated, be sure to
replace them.
Damaged cable and wires can cause an electrical shock, excessive heat
generation or fire.
Do not use a joined power cable or extension cable, or share the same power
outlet with other electrical appliances, since it can cause an electrical shock,
excessive heat generation or fire.
viii
SiENBE34-802 Introduction
Caution
Check to see if the parts and wires are mounted and connected properly, and
if the connections at the soldered or crimped terminals are secure.
Improper installation and connections can cause excessive heat generation,
fire or an electrical shock.
If the installation platform or frame has corroded, replace it.
Corroded installation platform or frame can cause the unit to fall, resulting in
injury.
Check the grounding, and repair it if the equipment is not properly grounded.
Improper grounding can cause an electrical shock.
Be sure to measure the insulation resistance after the repair, and make sure
that the resistance is 1 Mohm or higher.
Faulty insulation can cause an electrical shock.
Be sure to check the drainage of the indoor unit after the repair.
Faulty drainage can cause the water to enter the room and wet the furniture
and floor.
Caution A “caution” is used when there is danger that the reader, through
incorrect manipulation, may damage equipment, loose data, get
Caution an unexpected result or has to restart (part of) a procedure.
ix
Introduction SiENBE34-802
1.2 PREFACE
Thank you for your continued patronage of Daikin products.
This is the new service manual for Daikin's Year 2008 VRVIII-S series Heat Pump System.
Daikin offers a wide range of models to respond to building and office air conditioning needs.
We are confident that customers will be able to find the models that best suit their needs.
This service manual contains information regarding the servicing of VRVIII-S series R-410A
Heat Pump System.
July, 2008
x
SiENBE34-802
Part 1
General Information
General Information 1
Model Names of Indoor/Outdoor Units SiENBE34-802
Ceiling Suspended
Cassette Type FXUQ — — — — — — 71MA 100MA 125MA V1
BEVQ-
Connection Unit — — — — — — 71MA 100MA 125MA VE
M(A)
Note: BEV unit is required for FXUQ only.
VE :1φ, 220~240V, 50Hz, 1φ, 220V, 60Hz
V1 :1φ, 220~240V, 50Hz
V3 :1φ, 230V, 50Hz
Outdoor Units
Series Model Name Power Supply
2 General Information
SiENBE34-802 External Appearance
2. External Appearance
2.1 Indoor Units
Ceiling Mounted Cassette Type (Double Flow) Ceiling Mounted Duct Type
FXCQ20M8 FXMQ40P
FXCQ25M8 FXMQ50P
FXCQ32M8 FXMQ63P
FXCQ40M8 FXMQ80P
FXCQ50M8 FXMQ100P
FXCQ63M8 FXMQ125P
FXCQ80M8
FXCQ125M8
Ceiling Mounted Cassette Type (Round Flow) Ceiling Suspended Type
FXFQ20P7 FXHQ32MA
FXFQ25P7 FXHQ63MA
FXFQ32P7 FXHQ100MA
FXFQ40P7
FXFQ50P7
FXFQ63P7
FXFQ80P7
FXFQ100P7
FXFQ125P7
600×600 Ceiling Mounted Wall Mounted Type
Cassette Type (Multi Flow)
FXAQ20MA
FXZQ20M8 FXAQ25MA
FXZQ25M8 FXAQ32MA
FXZQ32M8 FXAQ40MA
FXZQ40M8 FXAQ50MA
FXZQ50M8 FXAQ63MA
Connection Unit
Ceiling Mounted Built-In Type
FXSQ20M
FXSQ25M
FXSQ32M
FXSQ40M
FXSQ50M
FXSQ63M
FXSQ80M
FXSQ100M
FXSQ125M
General Information 3
Capacity Range SiENBE34-802
3. Capacity Range
Outdoor Units
Capacity Range 4HP 5HP 6HP
RXYSQ 4PA 5PA 6PA
No of Indoor
Units to be 6 8 9
Connected
Total Capacity
Index of Indoor 50~130 62.5~162.5 70~182
Units to be
Connected
Indoor Units
Capacity Range 0.8HP 1HP 1.25HP 1.6HP 2HP 2.5HP 3.2HP 4HP 5HP
Capacity Index 20 25 31.25 40 50 62.5 80 100 125
Ceiling Mounted
Cassette Type FXCQ 20M 25M 32M 40M 50M 63M 80M — 125M
(Double Flow)
Ceiling Mounted
Cassette Type FXFQ 20P 25P 32P 40P 50P 63P 80P 100P 125P
(Round Flow)
600×600 Ceiling
Mounted Cassette FXZQ 20M 25M 32M 40M 50M — — — —
Type (Multi Flow)
Ceiling Mounted
Cassette Corner Type FXKQ — 25MA 32MA 40MA — 63MA — — —
Ceiling Mounted
Built-In Type FXSQ 20M 25M 32M 40M 50M 63M 80M 100M 125M
Ceiling Mounted
Duct Type FXMQ — — — 40P 50P 63P 80P 100P 125P
Ceiling Suspended
Type FXHQ — — 32MA — — 63MA — 100MA —
Wall Mounted Type FXAQ 20MA 25MA 32MA 40MA 50MA 63MA — — —
Floor Standing Type FXLQ 20MA 25MA 32MA 40MA 50MA 63MA — — —
Concealed Floor
Standing Type FXNQ 20MA 25MA 32MA 40MA 50MA 63MA — — —
Ceiling Suspended
Cassette Type FXUQ — — — — — — 71MA 100MA 125MA
4 General Information
SiENBE34-802
Part 2
Specifications
1. Specifications ..........................................................................................6
1.1 Outdoor Units ...........................................................................................6
1.2 Indoor Units ............................................................................................10
Specifications 5
Specifications SiENBE34-802
1. Specifications
1.1 Outdoor Units
Heat Pump 50Hz <RXYSQ-PA7Y1B>
1-1 TECHNICAL SPECIFICATIONS RXYSQ4PA7Y1B RXYSQ5PA7Y1B RXYSQ6PA7Y1B
Cooling kW 11.2 14.0 15.5
Capacity
Heating kW 12.5 16.0 18.0
Cooling 3.88 3.88 3.33
COP
Heating 4.43 4.03 3.83
Capacity range HP 4 5 6
PED category Category I
Max n° of indoor units to be connected 6 8 9
Indoor index Minimum 50 62.5 70
connection Maximum 130 162.5 182
Colour Daikin White
Casing
Material Painted galvanised steel
Height mm 1,524
Packing Width mm 980 980 980
Depth mm 420 420 420
Dimensions
Height mm 1,345
Unit Width mm 900 900 900
Depth mm 320 320 320
Unit kg 120 120 120
Weight
Packed Unit kg 130 130 130
Material Carton, wood + EPS
Packing
Weight kg 8 8 8
Length mm 857 857 857
Nr of Rows 2 2 2
Fin Pitch mm 2 2 2
Dimensions
Nr of Passes 10 10 10
Heat Face Area m² 1,131
Exchanger
Nr of Stages 60 60 60
Tube type Hi-XSS (8)
Fin type Non-symmetric waffle louvre
Fin
Treatment Corrosion resistant
Type Propeller
Quantity 2 2 2
Air Flow Rate Cooling m³/min 106 106 106
Fan (nominal at 230V) Heating m³/min 102 105 105
Discharge direction Horizontal
Quantity 2 2 2
Motor
Model Brushless DC motor
Speed Cooling rpm 850/815
Motor
(nominal) Heating rpm 820/785 840/805 840/805
Drive Direct drive
Fan Motor
Output motor W 70 70 70
Quantity 1 1 1
Quantity 1 1 1
Model JT100G-VDLYR
Type Hermetically sealed scroll compressor
Compressor Speed rpm 6,480
Motor
Motor Output kW 2.5 3.0 3.5
Starting Method Direct on line
Crankcase W
33 33 33
Heater
Cooling Standard Min °CDB -5 -5 -5
Cooling Max °CDB 46 46 46
Operation
Range Min °CWB -20 -20 -20
Heating
Max °CWB 15.5 15.5 15.5
6 Specifications
SiENBE34-802 Specifications
Specifications 7
Specifications SiENBE34-802
8 Specifications
SiENBE34-802 Specifications
Specifications 9
Specifications SiENBE34-802
10 Specifications
SiENBE34-802 Specifications
Specifications 11
Specifications SiENBE34-802
Screws for fixing the paper pattern for installation, Washer for hanging bracket, Clamps, Installation and operation manual,
Standard Accessories
Paper pattern for installation, Insulation for fitting, Drain hose
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB,
equivalent refrigerant piping : 8m, level difference : 0m.
Notes Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB,
equivalent refrigerant piping : 8m, level difference : 0m.
Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
12 Specifications
SiENBE34-802 Specifications
Specifications 13
Specifications SiENBE34-802
14 Specifications
SiENBE34-802 Specifications
Specifications 15
Specifications SiENBE34-802
16 Specifications
SiENBE34-802 Specifications
Specifications 17
Specifications SiENBE34-802
18 Specifications
SiENBE34-802 Specifications
Specifications 19
Specifications SiENBE34-802
20 Specifications
SiENBE34-802 Specifications
Specifications 21
Specifications SiENBE34-802
22 Specifications
SiENBE34-802 Specifications
Specifications 23
Specifications SiENBE34-802
24 Specifications
SiENBE34-802 Specifications
Specifications 25
Specifications SiENBE34-802
26 Specifications
SiENBE34-802 Specifications
BEV Units
11-1-1Technical Specifications BEVQ71MAVE BEVQ100MAVE BEVQ125MAVE
Power input Cooling kW 0.189 0.298 0.298
(Nominal) Heating kW 0.169 0.278 0.278
Casing Material Galvanised steel plate
Height mm 100 100 100
Dimensions Packing Width mm 350 350 350
Depth mm 225 225 225
Sound absorbing thermal insulation material Flame and heat resistant foamed polyetherene
Weight Unit kg 3.0 3.0 3.5
Type Flare connection
Liquid (OD)
Diameter mm 9.5 9.5 9.5
Indoor Units
Type Flare connection
Gas
Diameter mm 15.9 15.9 15.9
Type Flare connection
Liquid (OD)
Diameter mm 9.5 9.5 9.5
Outdoor Unit
Suction gas Type Flare connection
(OD) Diameter mm 15.9 15.9 15.9
Standard
Item Installation manual, Gas piping connections, Insulation for fitting, Sealing material, Clamps
Accessories
Specifications 27
Specifications SiENBE34-802
28 Specifications
SiENBE34-802
Part 3
List of Electrical and
Functional Parts
RXYSQ4 / 5 / 6PA7V1B
Model Remark
Item Name Symbol
4HP 5HP 6HP (PCB terminal)
Type JT100G-VDL Relay
Inverter M1C
Compressor Output 2.5kW 3.0kW 3.5kW A1P
Crankcase heater (INV) E1HC 33W A1P X28A
Motor M1F·M2F 0.07kW —
Fan motor
Over-current relay — 3.2A —
Electronic expansion Cooling 480pls
Y1E A1P X21A
valve (Main) Heating PI control
Electronic expansion Cooling PI control
Functional Y3E A1P X22A
valve (Subcool) Heating PI control
parts
4 way valve Y1S STF-0404G A1P X25A
Solenoid valve (Hot gas) Y2S TEV1620DQ2 A1P X26A
Solenoid valve (Unload circuit) Y3S TEV1620DQ2 A1P X27A
ACB-4UB10
Pressure switch (INV) S1PH A1P X32A
Pressure- OFF: 4.0+0/-0.15MPa ON: 3.0±0.15MPa
related parts Pressure sensor (HP) S1NPH PS8051A 0~4.15MPa A1P X17A
Pressure sensor (LP) S1NPL PS8051A –0.05~1.7MPa A1P X18A
For outdoor air R1T 3.5~360kΩ A1P X11A
For discharge pipe R2T 5.0~640kΩ A1P X12A 1-2Pin
For suction pipe 1 R3T 3.5~360kΩ A1P X12A 3-4Pin
For heat exchanger R4T 3.5~360kΩ A1P X12A 5-6Pin
Main
Thermistor PCB For suction pipe 2 R5T 3.5~360kΩ A1P X12A 7-8Pin
For subcooling heat R6T 3.5~360kΩ A1P X13A 1-2Pin
exchanger
For liquid pipe 1 R7T 3.5~360kΩ A1P X13A 3-4Pin
For liquid pipe 2 R8T 3.5~360kΩ A1P X13A 5-6Pin
Others Fuse (A1P) F1U AC250V 6.3A Time lag fuse —
Model
Parts Name Symbol FXCQ FXCQ FXCQ FXCQ FXCQ FXCQ FXCQ FXCQ Remark
125
20MV3 25MV3 32MV3 40MV3 50MV3 63MV3 80MV3 MV3
Wired Remote Control BRC1D52
Remote
Control Infrared remote Option
control BRC7C62
AC 220~240V 50Hz
1φ10W 1φ15W 1φ20W 1φ30W 1φ50W 1φ85W
Fan Motor M1F
Thermal protector 135°C : OFF
Thermal Fuse 152°C — 87°C : ON
Motors
AC220-240V (50Hz) AC220V (60Hz)
Drain Pump M1P PLD-12230DM
Thermal Fuse 145°C
MT8-L[3PA07509-1]
Swing Motor M1S
AC200~240V
ST8601-6 φ4 L1250
Thermistor (Suction Air) R1T 20kΩ (25°C)
Model
Parts Name Symbol FXZQ FXZQ FXZQ FXZQ FXZQ Remark
20MV1 25MV1 32MV1 40MV1 50MV1
Wired Remote Control BRC1D52
Remote
Control Infrared remote Option
BRC7E530
control
AC 220~240V 50Hz
Fan Motor M1F 1φ55W 4P
Thermal Fuse OFF : 130±5 / ON : 80±20
Capacitor, fan motor C1 4.0μ F 400VAC
Motors
AC220-240V (50Hz)
Drain Pump M1P PLD-12230DM
Thermal Fuse 145°C
MP35HCA [3P080801-1]
Swing Motor M1S
AC200~240V
ST8601A-1 φ4 L250
Thermistor (Suction Air) R1T 20kΩ (25°C)
Thermistor (for Heat
Thermistors Exchanger High Temp.) R3T ST8605-3 φ8 L630
20kΩ (25°C)
Thermistor (Heat ST8602A-3 φ6 L630
R2T
Exchanger) 20kΩ (25°C)
Float Switch S1L FS-0211
Others Fuse F1U 250V 5A φ5.2
Transformer T1R TR22H21R8
Model
Parts Name Symbol FXKQ FXKQ FXKQ FXKQ Remark
25MAVE 32MAVE 40MAVE 63MAVE
Wired Remote Control BRC1D52 Option
Remote
Control Infrared remote BRC4C61
control
AC 220~240V 50Hz
Model
Parts Name Symbol FXDQ FXDQ FXDQ FXDQ FXDQ FXDQ Remark
20 PVE 25PVE 32PVE 40NAVE 50NAVE 63NAVE
Wired Remote Control BRC1D52
Remote
Infrared remote Option
Control BRC4C62
control
AC 220~240V 50Hz
Model
Parts Name Symbol FXDQ FXDQ Remark
20M8V3B 25M8V3B
Wired Remote Control BRC1D52
Remote
Infrared remote Option
Control BRC4C62
control
AC 200~240V 50/60Hz
1φ10W4P
Motors Fan Motor M1F
Thermal protector
135°C: OFF, 87°C: ON
ST8601-4 φ4 L=800
Thermistor (Suction Air) R1T
20kΩ (25°C)
Model
Parts Name Symbol FXSQ FXSQ FXSQ FXSQ FXSQ FXSQ FXSQ FXSQ FXSQ Remark
20 25 32 40 50 63 80 100 125
MV3 MV3 MV3 MV3 MV3 MV3 MV3 MV3 MV3
Wired Remote Control BRC1D52
Remote Option
Control Infrared remote
control BRC4C62
AC 220~240V 50Hz
1φ125
Fan Motor M1F 1φ50W 1φ65W 1φ85W W 1φ225W
Model
Parts Name Symbol FXMQ FXMQ FXMQ FXMQ FXMQ FXMQ Remark
40PVE 50PVE 63PVE 80PVE 100PVE 125PVE
Wired Remote Control BRC1C62
Remote
Control Infrared remote
control BRC4C65
Model
Parts Name Symbol FXHQ FXHQ FXHQ Remark
32MAVE 63MAVE 100MAVE
Remote Wired Remote Control BRC1D52 Option
Control Wireless Control BRC7E63W
AC 220~240V/220V 50Hz/60Hz
Fan Motor M1F 1φ63W 1φ130W
Model
Parts Name Symbol FXAQ FXAQ FXAQ FXAQ FXAQ FXAQ Remark
20MAVE 25MAVE 32MAVE 40MAVE 50MAVE 63MAVE
Wired Remote Control BRC1D52
Remote
Infrared remote Option
Control BRC7E618
control
AC 220~240V 50Hz
Fan Motor M1F 1φ40W 1φ43W
Motors Thermal protector 130°C : OFF 80°C : ON
Model
Parts Name Symbol FXLQ FXLQ FXLQ FXLQ FXLQ FXLQ Remark
20MAVE 25MAVE 32MAVE 40MAVE 50MAVE 63MAVE
Wired Remote Control BRC1D52
Remote Option
Control Infrared remote
control BRC4C62
AC 220~240V 50Hz
Fan Motor M1F 1φ15W 1φ25W 1φ35W
Motors
Thermal protector 135°C : OFF 120°C : ON
Capacitor for Fan Motor C1R 1.0μF-400V 0.5μF-400V 1.0μF-400V 1.5μF-400V 2.0μF-400V
Model
Parts Name Symbol FXNQ FXNQ FXNQ FXNQ FXNQ FXNQ Remark
20MAVE 25MAVE 32MAVE 40MAVE 50MAVE 63MAVE
Wired Remote Control BRC1D52
Remote
Infrared remote Option
Control BRC4C62
control
AC 220~240V 50Hz
Fan Motor M1F 1φ15W 1φ25W 1φ35W
Motors
Thermal protector 135°C : OFF 120°C : ON
Capacitor for Fan Motor C1R 1.0μF-400V 0.5μF-400V 1.0μF-400V 1.5μF-400V 2.0μF-400V
ST8601-6 φ4 L1250
Thermistor (Suction Air) R1T
20kΩ (25°C)
Thermistor (for Heat ST8605-9 φ8 L2500
Thermistors Exchanger High Temp.) R3T
20kΩ (25°C)
Thermistor (for Heat ST8602A-9 φ6 L2500
R2T
Exchanger) 20kΩ (25°C)
Fuse F1U AC250V 5A
Others
Transformer T1R TR22H21R8
Model
Parts Name Symbol Remark
FXUQ71MAV1 FXUQ100MAV1 FXUQ125MAV1
Wired Remote Control BRC1C62
Remote Option
Control Infrared remote
control BRC7C528W
AC 220~240V 50Hz
Fan Motor M1F 1φ45W 1φ90W
Thermal protector 130°C Thermal protector 130°C : OFF 83°C : ON
Motors
AC220-240V (50Hz) AC220V (60Hz)
Drain Pump M1P
PJV-1426
MT8-L[3PA07572-1]
Swing Motor M1S AC200~240V
Part 4
Refrigerant Circuit
Refrigerant Circuit 39
Refrigerant Circuit SiENBE34-802
1. Refrigerant Circuit
1.1 Outdoor Unit
RXYSQ4 / 5 / 6PA7Y1B
No. in
refrigerant Symbol Name Major Function
system
diagram
Inverter compressor is operated on frequencies between 36 Hz and 195 Hz by using
A M1C Inverter compressor (INV) the inverter.
31 steps
D M1F Inverter fan Since the system is of air heat exchanging type, the fan is operated at 8-step rotation
M2F speed by using the inverter.
Electronic expansion valve While in heating operation, PI control is applied to keep the outlet superheated degree
E Y1E
(Main: EV1) of air heat exchanger constant.
Electronic expansion valve Pl control is applied to keep the outlet superheated degree of subcooling heat
F Y3E (Subcool: EV3) exchanger constant.
G Y2S Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
Solenoid valve (Unload circuit
H Y3S SVUL) Used to the unloading operation of compressor.
M Y1S Four way valve Used to switch the operation mode between cooling and heating.
N S1NPH High pressure sensor Used to detect high pressure.
O S1NPL Low pressure sensor Used to detect low pressure.
HP pressure switch (For INV In order to prevent the increase of high pressure when a malfunction occurs, this
P S1PH switch is activated at high pressure of 4.0 MPa or more to stop the compressor
compressor) operation.
Pressure regulating valve 1 This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
T — resulting in no damage of functional parts due to the increase of pressure in
(Receiver to discharge pipe) transportation or storage.
1 R1T Thermistor (Outdoor air: Ta) Used to detect outdoor temperature, correct discharge pipe temperature, and others.
Thermistor (INV discharge used to detect discharge pipe temperature, make the temperature protection control of
2 R2T pipe: Tdi) compressor, and others.
3 R3T Thermistor used to detect suction pipe temperature, keep the suction superheated degree
(Suction pipe1: Ts1) constant in heating operation, and others.
Thermistor (Subcooling heat
4 R4T Used to control of subcooling electronic expansion valve.
exchanger gas pipe: Tsh)
Thermistor
5 R5T (Suction pipe2: Ts2) Used to the calculation of an internal temperature of compressor etc.
6 R6T Thermistor (Heat exchanger Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
deicer: Tb) operation, and others.
Thermistor
7 R7T Used to detect refrigerant over charge in check operation, and others.
(Liquid pipe1: Tl1)
Thermistor
8 R8T (Liquid pipe2: Tl2) Used to detect refrigerant over charge in check operation, and others.
40 Refrigerant Circuit
SiENBE34-802
Refrigerant Circuit
Double pipe Electronic
heat exchanger expansion valve 8
F Filter
Subcooling heat E
exchanger
7 T
Heat exchanger
6
Pressure regulating valve
4 1
Filter 3 Service port
D D
Four way
valve
M
5 Solenoid valve
Filter Capillary tube Filter
2
Compressor G
A Solenoid valve
Capillary tube
High pressure
switch P
Accumulator
Stop valve (With service port on field piping side ø 7.9 mm flare connection)
C : 3D052628
41
Refrigerant Circuit
Refrigerant Circuit SiENBE34-802
RXYSQ4 / 5 / 6PA7V1B
No. in
refrigerant
system Symbol Name Major Function
diagram
Inverter compressor is operated on frequencies between 36 Hz and 195 Hz by using
A M1C Inverter compressor (INV) the inverter.
31 steps
M1F Since the system is of air heat exchanging type, the fan is operated at 8-step rotation
D M2F Inverter fan speed by using the inverter.
E Y1E Electronic expansion valve While in heating operation, PI control is applied to keep the outlet superheated degree
(Main: EV1) of air heat exchanger constant.
Electronic expansion valve Pl control is applied to keep the outlet superheated degree of subcooling heat
F Y3E
(Subcool: EV3) exchanger constant.
G Y2S Solenoid valve (Hot gas: SVP) Used to prevent the low pressure from transient falling.
Solenoid valve (Unload circuit
H Y3S Used to the unloading operation of compressor.
SVUL)
M Y1S Four way valve Used to switch the operation mode between cooling and heating.
N S1NPH High pressure sensor Used to detect high pressure.
O S1NPL Low pressure sensor Used to detect low pressure.
In order to prevent the increase of high pressure when a malfunction occurs, this
P S1PH HP pressure switch (For INV switch is activated at high pressure of 4.0 MPa or more to stop the compressor
compressor)
operation.
This valve opens at a pressure of 4.0 MPa for prevention of pressure increase, thus
T — Pressure regulating valve 1 resulting in no damage of functional parts due to the increase of pressure in
(Receiver to discharge pipe)
transportation or storage.
1 R1T Thermistor (Outdoor air: Ta) Used to detect outdoor temperature, correct discharge pipe temperature, and others.
Thermistor (INV discharge used to detect discharge pipe temperature, make the temperature protection control of
2 R2T
pipe: Tdi) compressor, and others.
Thermistor used to detect suction pipe temperature, keep the suction superheated degree
3 R3T (Suction pipe1: Ts1) constant in heating operation, and others.
4 R4T Thermistor (Heat exchanger Used to detect liquid pipe temperature of air heat exchanger, determine defrosting
deicer: Tb) operation, and others.
Thermistor
5 R5T Used to the calculation of an internal temperature of compressor etc.
(Suction pipe2: Ts2)
Thermistor (Subcooling heat
6 R6T exchanger gas pipe: Tsh) Used to control of subcooling electronic expansion valve.
7 R7T Thermistor Used to detect refrigerant over charge in check operation, and others.
(Liquid pipe1: Tl1)
Thermistor
8 R8T Used to detect refrigerant over charge in check operation, and others.
(Liquid pipe2: Tl2)
42 Refrigerant Circuit
SiENBE34-802
Refrigerant Circuit
Double pipe
Electronic
heat exchanger expansion valve
Subcooling heat Filter
exchanger
Heat exchanger
Pressure regulating valve
Four way
valve
Solenoid valve
Filter Capillary tube
Filter
Compressor
Capillary tube Solenoid valve
High pressure
switch
Accumulator
Stop valve (With service port on field piping side ø 7.9 mm flare connection)
C : 3D052712
43
Refrigerant Circuit
Functional Parts Layout SiENBE34-802
THERMISTOR (DISCHARGE)
R2T Y1E ELECTRONIC EXPANSION VALVE
(CONNECTOR COLOR : WHITE)
44 Refrigerant Circuit
SiENBE34-802 Functional Parts Layout
Refrigerant Circuit 45
Functional Parts Layout SiENBE34-802
Back view
46 Refrigerant Circuit
SiENBE34-802
Part 5
Function
1. Operation Mode ....................................................................................48
2. Basic Control.........................................................................................49
2.1 Normal Operation ...................................................................................49
2.2 Compressor PI Control...........................................................................50
2.3 Electronic Expansion Valve PI Control...................................................51
2.4 Cooling Operation Fan Control...............................................................52
3. Special Control......................................................................................53
3.1 Startup Control .......................................................................................53
3.2 Oil Return Operation ..............................................................................54
3.3 Defrosting Operation ..............................................................................56
3.4 Pump-down Residual Operation ............................................................57
3.5 Restart Standby......................................................................................58
3.6 Stopping Operation ................................................................................59
4. Protection Control .................................................................................60
4.1 High Pressure Protection Control...........................................................60
4.2 Low Pressure Protection Control............................................................61
4.3 Discharge Pipe Protection Control .........................................................62
4.4 Inverter Protection Control .....................................................................63
5. Other Control.........................................................................................64
5.1 Demand Operation .................................................................................64
5.2 Heating Operation Prohibition ................................................................64
6. Outline of Control (Indoor Unit) .............................................................65
6.1 Drain Pump Control................................................................................65
6.2 Louver Control for Preventing Ceiling Dirt..............................................67
6.3 Thermostat Sensor in Remote Control...................................................68
6.4 Freeze Prevention ..................................................................................70
6.5 View of Operations of Swing Flaps ........................................................71
6.6 Electronic Expansion Valve Control .......................................................72
6.7 Hot Start Control (In Heating Operation Only)........................................72
Function 47
Operation Mode SiENBE34-802
1. Operation Mode
Operation in
stop mode
Malfunction /
Standby
Indoor unit stop or
Startup control thermostat OFF
• Cooling startup Pump-down
control residual
• Heating startup Indoor unit thermostat ON
operation
control
Malfunction/Standby
Cooling or heating
operation
Malfunction /
Standby
No
Defrost IN Yes
conditions are met. Defrosting operation
No
Operation Yes
mode change
No Note:
In the event indoor unit stops or the thermostat
turns OFF while in oil return operation or
defrosting operation, pump-down residual
operation is performed on completion of the oil
return operation or defrosting operation.
(V3152)
48 Function
SiENBE34-802 Basic Control
2. Basic Control
2.1 Normal Operation
Cooling Operation
Actuator Operation Remarks
Used for high pressure protection control, low
pressure protection control, discharge pipe
Compressor Compressor PI control temperature protection control, and compressor
operating frequency upper limit control with
inverter protection control.
Outdoor unit fan Cooling fan control ⎯
Four way valve OFF ⎯
Main electronic expansion valve (EV1) 480 pls ⎯
Subcooling electronic expansion valve PI control ⎯
(EV3)
This valve turns on with low pressure protection
Hot gas bypass valve (SVP) OFF control.
Heating Operation
Actuator Operation Remarks
Used for high pressure protection control, low
pressure protection control, discharge pipe
Compressor Compressor PI control temperature protection control, and compressor
operating frequency upper limit control with
inverter protection control.
Outdoor unit fan STEP 7 or 8 ⎯
Four way valve ON ⎯
Main electronic expansion valve (EV1) PI control ⎯
Subcooling electronic expansion valve PI control ⎯
(EV3)
This valve turns on with low pressure protection
Hot gas bypass valve (SVP) OFF control.
Function 49
Basic Control SiENBE34-802
[Cooling operation]
Controls compressor capacity to adjust Te to Te : Low pressure equivalent saturation temperature
achieve target value (TeS). (°C)
Te setting (Set in Set-up mode 2) TeS : Target Te value
(Varies depending on Te setting, operating
L M (Normal) H frequency, etc.)
(factory
setting)
3 6 9
[Heating operation]
Controls compressor capacity to adjust Tc to Tc : High pressure equivalent saturation temperature
achieve target value (TcS). (°C)
Tc setting TcS : Target Tc value
(Varies depending on Tc setting, operating
L M (Normal) H frequency, etc.)
(factory
setting)
43 46 49
RXYSQ4 · 5 · 6PA
STn INV(Fullload) INV(Unload) STn INV(Fullload) INV(Unload) STn INV(Fullload) INV(Unload)
1 36.0Hz 11 80.0Hz 21 140.0Hz
2 39.0Hz 12 86.0Hz 22 146.0Hz
3 43.0Hz 13 92.0Hz 23 152.0Hz
4 47.0Hz 14 98.0Hz 24 158.0Hz
5 52.0Hz 15 104.0Hz 25 164.0Hz
6 52.0Hz 57.0Hz 16 110.0Hz 26 170.0Hz
7 57.0Hz 64.0Hz 17 116.0Hz 27 175.0Hz
8 62.0Hz 71.0Hz 18 122.0Hz 28 180.0Hz
9 68.0Hz 78.0Hz 19 128.0Hz 29 185.0Hz
10 74.0Hz 20 134.0Hz 30 190.0Hz
31 195.0Hz
∗ Compressors may operate in a pattern other than those listed in above tables subject to the operating conditions.
Selection of full load operation to/from unload operation is made with the unload circuit solenoid valve
(Y3S=SVUL). The full load operation is performed with the SVUL set to OFF, while the unload operation is
performed with the SVUL set to ON.
50 Function
SiENBE34-802 Basic Control
Function 51
Basic Control SiENBE34-802
Pc<2.75MPa Pc>3.24MPa
PI control
Lapse of 20 sec.
PI control
-1 step on Hold the +1 step on
current step on
outdoor unit fan outdoor unit fan outdoor unit fan
PI control Lapse of 20 sec.
Fan Steps
52 Function
SiENBE34-802 Special Control
3. Special Control
3.1 Startup Control
This control is used to equalize the pressure in the front and back of the compressor prior to the startup of the
compressor, thus reducing startup loads. Furthermore, the inverter is turned ON to charge the capacitor.
In addition, to avoid stresses to the compressor due to oil return or else after the startup, the following control is made
and the position of the four way valve is also determined. To position the four way valve, the master and slave units
simultaneously start up.
3.1.1 Startup Control in Cooling Operation
Thermostat ON
Function 53
Special Control SiENBE34-802
Take the current step as the 52 Hz Full load Same as the “oil return
Compressor (→ Low pressure constant operation” mode.
upper limit. control)
Outdoor unit fan Fan control (Normal cooling) Fan control (Normal cooling) Fan control (Normal cooling)
Four way valve OFF OFF OFF
Main electronic expansion valve 480 pls 480 pls 480 pls
(EV1)
Subcooling electronic expansion SH control 0 pls 0 pls
valve (EV3)
Hot gas bypass valve (SVP) OFF OFF OFF
• 3 min. • 3 min.
Ending conditions 20 sec. or • Ts - Te<5°C or • Pe<0.6MPa
• HTdi>110°C
54 Function
SiENBE34-802 Special Control
* From the preparing oil-returning operation to the oil-returning operation, and from the oil-
returning operation to the operation after oil-returning, the compressor stops for 1 minute to
reduce noise on changing of the four way valve.
Function 55
Special Control SiENBE34-802
* From the preparing operation to the defrost operation, and from the defrost operation to the
operation after defrost, the compressor stops for 1 minute to reduce noise on changing of the
four way valve.
56 Function
SiENBE34-802 Special Control
Function 57
Special Control SiENBE34-802
58 Function
SiENBE34-802 Special Control
Function 59
Protection Control SiENBE34-802
4. Protection Control
4.1 High Pressure Protection Control
This high pressure protection control is used to prevent the activation of protection devices due
to abnormal increase of high pressure and to protect compressors against the transient
increase of high pressure.
Pc>3.64MPa
When occurring 10 times within 60
High pressure minutes, HPS is activated without high
standby pressure standby, thus outputting the
malfunction code "E3".
[In heating operation]
High-pressure drop
Pc>3.04MPa
High pressure not limited
Pc: HP pressure sensor detection value
Pc<2.89MPa
Pc>3.64MPa
When occurring 10 times within 60
High pressure minutes, HPS is activated without
standby high pressure standby, thus
outputting the malfunction code "E3".
60 Function
SiENBE34-802 Protection Control
Low pressure
Hot gas SVP = OFF
limited
Pe<0.15MPa Pe>0.30MPa
36Hz Unload
Pe<0.07MPa
Pe<0.17MPa
Low pressure not limited
• Pe>0.09MPa
or • Ts-Teg<8deg
&
• Pe>0.06MPa
Pe< 0.07MPa
Function 61
Protection Control SiENBE34-802
[INV compressor]
or HTdi>135°C
36 Hz Unload HTdi>120°C for 10 min. or more.
62 Function
SiENBE34-802 Protection Control
Not limited
Limited
Status quo
Not limited
Limited
Tfin ⱕ 76°C
Without conditions
continues for 3 min.
INV upper limit frequency:
1-step up from current
compressor frequency
Tfin ⱖ 84°C
Function 63
Other Control SiENBE34-802
5. Other Control
5.1 Demand Operation
In order to save the power consumption, the capacity of outdoor unit is saved with control
forcibly by using “Demand 1 Setting”.
To operate the unit with this mode, additional setting of “Continuous Demand Setting”.
[Demand 1 setting]
Setting Standard for upper limit of power consumption
Demand 1 setting 1 Approx. 60%
Demand 1 setting 2 (factory setting) Approx. 70%
Demand 1 setting 3 Approx. 80%
H Other protection control functions have precedence over the above operation.
64 Function
SiENBE34-802 Outline of Control (Indoor Unit)
6.1.1 When the Float Switch is Tripped while the Cooling Thermostat is
ON:
Remote control “A3” flashing
malfunction stop
ON
Thermostat
(running) OFF
ON
Float switch
OFF
ON
Drain pump
OFF
(VL008)
5 min. 5 min. 5 sec.
*1) Residual operation Malfunction residual
∗ 1. The objective of residual operation is to completely drain any moisture adhering to the fin of
the indoor unit heat exchanger when the thermostat goes off during cooling operation.
6.1.2 When the Float Switch is Tripped while the Cooling Thermostat is
OFF:
Enters malfunction treatment if the float switch is not reset within 5 minutes.
ON
Float switch
OFF
ON
Drain pump
OFF
Function 65
Outline of Control (Indoor Unit) SiENBE34-802
ON
Humidifier
OFF
ON Reset
Float switch
OFF
ON
Drain pump
OFF
During heating operation, if the float switch is not reset even after the 5 minutes operation, 5
seconds stop, 5 minutes operation cycle ends, operation continues until the switch is reset.
6.1.4 When the Float Switch is Tripped and “AF” is Displayed on the
Remote Control:
Enters malfunction treatment
if the float switch is not reset
within 5 minutes.
“AF” display (running) Remote control “A3” flashing
Remote control malfunction stop
display
ON
Float switch
OFF
1st time 2nd time 3rd time 4th time 5th time
ON
Drain pump
OFF
*1 = 5 min. *1 *1 *1 *1 *1 *1 *1 (VL011)
Note: If the float switch is tripped five times in succession, a drain malfunction is determined to have
occurred. “AF” is then displayed as operation continues.
66 Function
SiENBE34-802 Outline of Control (Indoor Unit)
Existing position
P0
P1
P2
P3
P4
P1 P1
P0' P2
P2
P3 P1' P4 P0''
P4 P1''
P4 P2'
P2''
P3' P3''
P4' P4''
Draft
prevention P0 P1 P2 P3 P4 Same as existing position
position
Range of direction adjustment
Function 67
Outline of Control (Indoor Unit) SiENBE34-802
Cooling If there is a significant difference in the preset temperature and the suction temperature, fine
adjustment control is carried out using a body thermostat sensor, or using the sensor in the
Remote Control near the position of the user when the suction temperature is near the preset
temperature.
Preset temperature
(Ts)
And, assuming suction temperature has changed from 30°C to 18°C (F → A):
Body thermostat sensor is used for temperatures from 30°C to 25°C (F → D).
Remote Control thermostat sensor is used for temperatures from 25°C to 21°C (D → B).
Body thermostat sensor is used for temperatures from 21°C to 18°C (B → A).
68 Function
SiENBE34-802 Outline of Control (Indoor Unit)
Heating When heating, the hot air rises to the top of the room, resulting in the temperature being lower
near the floor where the occupants are. When controlling by body thermostat sensor only, the
unit may therefore be turned off by the thermostat before the lower part of the room reaches the
preset temperature. The temperature can be controlled so the lower part of the room where the
occupants are doesn’t become cold by widening the range in which thermostat sensor in
Remote Control can be used so that suction temperature is higher than the preset temperature.
Preset temperature
(Ts)
And, assuming suction temperature has changed from 28°C to 18°C (D → A):
Remote Control thermostat sensor is used for temperatures from 28°C to 23°C (D → B).
Body thermostat sensor is used for temperatures from 23°C to 18°C (B → A).
Function 69
Outline of Control (Indoor Unit) SiENBE34-802
10 min.
+ 7 °C
+ 0 °C
- 5 °C
(VG005)
70 Function
SiENBE34-802 Outline of Control (Indoor Unit)
Function 71
Outline of Control (Indoor Unit) SiENBE34-802
setting
Po (Horizontal)
72 Function
SiENBE34-802
Part 6
Test Operation
Test Operation 73
Test Operation SiENBE34-802
1. Test Operation
1.1 Procedure and Outline
Follow the following procedure to conduct the initial test operation after installation.
Check on refrigerant piping Is pipe size proper? (The design pressure of this product is
4.0MPa.)
Are pipe insulation materials installed securely?
Liquid and gas pipes need to be insulated. (Otherwise causes
water leak.)
Are respective stop valves on liquid and gas line securely open?
74 Test Operation
SiENBE34-802 Test Operation
Outdoor unit
Tank
Fig. 6
Test Operation 75
Test Operation SiENBE34-802
To avoid compressor breakdown. Do not charge the refrigerant more than the specified
amount.
This outdoor unit is factory charged with refrigerant and depending on pipe sizes and pipe
lengths some systems require additional charging of refrigerant. See "How to calculate the
additional refrigerant to be charged" on page 249.
In case re-charge is required, refer to the nameplate of the unit. The nameplate states the
type of refrigerant and necessary amount.
Since this refrigerant is a mixed refrigerant, adding it in gas form may cause the refrigerant
composition to change, preventing normal operation.
Before charging, check whether the refrigerant cylinder is equipped with a siphon tube or
not.
Charge the liquid Charge the liquid
refrigerant with the cylinder refrigerant with the cylinder
in upright position. in up-side-down position.
The filled out label must be adhered in the proximity of the product charging port (e.g. onto the
inside of the service cover).
Contains fluorinated greenhouse gases covered by the Kyoto Protocol Contains fluorinated greenhouse gases
covered by the Kyoto Protocol
factory refrigerant charge of the product:
see unit name plate
additional refrigerant amount charged
in the field
outdoor unit
76 Test Operation
SiENBE34-802 Test Operation
Valve A
When the refrigerant tank is connected and the specified operation is performed, the
appropriate amount of refrigerant will be charged into the system. After charging, the system will
stop automatically. The refrigerant must be charged according to the procedure described
below.
Caution Make sure to turn ON the power 6 hours before starting the operation. This is necessary to
warm the crankcase by the electric heater.
Automatic charging is able to charge 6 kg/hour refrigerant at an outside temperature of 0°C
to 24 kg/hour refrigerant at an outside temperature of 35°C.
The charging time depends on the amount of charged refrigerant and on the outside
temperature.
Automatic refrigerant charging is NOT possible if the following restrictions are exceeded:
Outside temperature: 0°C DB~43°C DB
Indoor temperature: 0°C DB~32°C DB
Indoor unit connection capacity: 50%~130%
Note When an indoor unit is connected to the refrigerant system and the indoor unit is turned off,
automatic charging will fail.
3. Make sure that the led on the PCB on the outdoor unit are as shown in the table below. This
indicates that the system is operating normally.
Test/HWL
Demand
L.N.O.P.
Master
Mode
Slave
Ind
Test Operation 77
Test Operation SiENBE34-802
Led state
Throughout the manual the state of the leds is indicated as follows:
h OFF
i ON
j blinking
* ON or OFF
If H2P is lit up, check the type of error based on the error code in the remote control and correct
the error in accordance with “1.1.5 Check Operation” on page 82.
Warning Do not touch anything else than the push-buttons (BS1~5) on the PCB when making
the settings. These settings must be done with the power on
4.2 Press BS4 TEST for 5 seconds. The unit will start running.
H1P H2P H3P H4P H5P H6P H7P
* *
If the led display below appears, the automatic refrigerant charging restriction has been
exceeded. Additional refrigerant must be charged by calculating the additional refrigerant
charging amount.
H1P H2P H3P H4P H5P H6P H7P Description of error
Inappropriate outdoor
temperature
or
H1P H2P H3P H4P H5P H6P H7P Description of error
Inappropriate indoor
temperature
If the led display below appears, check the indoor unit connection capacity.
H1P H2P H3P H4P H5P H6P H7P Description of error
If the led display below appears, the liquid and gas side stop valves may be closed.
H1P H2P H3P H4P H5P H6P H7P Description of error
* * * * *
Stop valve is closed
Note If you want to repeat the automatic refrigerant charging operation from step 4.1, fully open the
liquid and gas side stop valves and press the BS1 MODE button once.
4.3 When the led indication becomes as shown in the table below in about 15 to 30 minutes
after start of operation, open valve A at once to start charging of the refrigerant.
Immediately after starting charging of the refrigerant by opening valve A, press BS4 TEST
once. When BS4 TEST is not pressed within 10 minutes after the led indication is shown,
charging is stopped.
H1P H2P H3P H4P H5P H6P H7P Code on remote control
PA
78 Test Operation
SiENBE34-802 Test Operation
4.4 The led indication becomes as shown in the table below during automatic refrigerant
charging.
During automatic refrigerant charging, the remote control indicates TEST (test operation)
and (external control).
H1P H2P H3P H4P H5P H6P H7P
* * * * *
Note If the led display below appears, the refrigerant tank is empty. Replace the refrigerant tank,
open valve A and re-charge.
H1P H2P H3P H4P H5P H6P H7P Code on remote control
PA
The led indication becomes as shown in the table below when automatic refrigerant charging is
about to end. Prepare to close the valve on the refrigerant tank.
H1P H2P H3P H4P H5P H6P H7P Code on remote control
PE
Note It is possible that the code PE is not shown on the remote control but this does not indicate a
malfunction. The led indication can immediately shift to the situation as shown in "Case 1:
Charging complete" on page 79.
4.5 When the led indication becomes as shown in the table below, quickly close valve A and
follow instructions as described below.
Caution When adding refrigerant is done or when pausing, close the valve on the refrigerant tank
immediately.
More refrigerant might be charged by any remaining pressure after the machine is stopped.
The outdoor fan may keep rotating a little bit more, but this does not indicate a malfunction.
Charging of the refrigerant is complete. Press BS1 MODE button once and go to step 5.
Press BS1 MODE button once and perform automatic refrigerant charging again starting from
Step 4.1.
After correcting the problem, press BS1 MODE button once and perform automatic refrigerant
charging again starting from step 4.1.
Test Operation 79
Test Operation SiENBE34-802
Case 4: Failure
After correcting the problem, press BS1 MODE button once and perform automatic refrigerant
charging again starting from step 4.1.
5. When charging is complete, determine the weight of refrigerant that was added and fill in the
amount in the "Additional refrigerant charge label" attached to service precautions plate on
the unit.
6. After adding the refrigerant, do not forget to close the lid of the service port. The tightening
torque for the lid is 11.5~13.9 N•m.
V1 Y1
2. After the vacuum drying is finished, open valve A and charge the additional refrigerant in its
liquid state through the service port on the liquid stop valve taking into account following
instructions:
- Turn on the power of the outdoor unit and indoor units.
- Check that gas and liquid stop valves are closed.
- Stop the compressor and charge the specified weight of refrigerant.
80 Test Operation
SiENBE34-802 Test Operation
To avoid compressor breakdown. Do not charge the refrigerant more than the specified
amount.
If the total refrigerant cannot be charged while the outdoor unit is at a standstill, it is possible
to charge the refrigerant by operating the outdoor unit using the refrigerant charge function
(refer to “Setting mode 2” on page 108) and follow "Procedure 3: Charging while the outdoor
unit is operating" on page 81.
1. Completely open the gas side stop valve and liquid side stop valve. Valve A must be left fully
closed.
2. Close the front panel and turn on the power to all indoor units and the outdoor unit.
3. Open valve A immediately after starting of the compressor.
4. Charge the additional refrigerant in its liquid state through the service port of the liquid line
stop valve.
5. While the unit is at a standstill and under setting mode 2 (refer to Checks before initial start-
up, "Setting mode 2" on page 108), set the required function A (additional refrigerant
charging operation) to ON (ON). Then operation starts. The blinking H2P led indicates test
operation and the remote control indicates TEST (test operation) and (external
control).
6. When the specified amount of refrigerant is charged, push the BS3 RETURN button. Then
operation stops.
The operation automatically stops within 30 minutes.
If the refrigerant charge cannot be finished within 30 minutes, repeat step 5.
If the operation stops immediately after restart, there is a possibility that the system is
overcharged.
The refrigerant cannot be charged more than this amount.
7. After the refrigerant charge hose is removed, make sure to close valve A.
Test Operation 81
Test Operation SiENBE34-802
Press and hold the TEST The test operation is started automatically.
OPERATION button (BS4) on The following judgements are conducted within 15 minutes(about 30
outdoor unit PC board for 5 minutes at the maximum).
seconds. 2“Check for wrong wiring”
2“Check stop valve for not open”
2“Check of refrigerant charge”
2“Pipe length automatic judgement”
The following indications are conducted while in test operation.
2LED lamp on outdoor unit PC board H2P flickers (test operation)
2Remote control Indicates “UNDER CENTRALIZED
CONTROL” on upper right.
Check on operation Indicates “TEST OPERATION” on lower left.
(V3057)
On completion of test operation, LED on outdoor unit PC board displays the following.
H3P ON: Normal completion
H2P ON: Abnormal completion →Check the indoor unit remote control for
abnormal display and correct it.
82 Test Operation
SiENBE34-802 Test Operation
Malfunction code
In case of an alarm code displayed on remote control:
Malfunction
Nonconformity during installation Remedial action
code
The shutoff valve of an outdoor unit is left Open the gas-side shutoff valve and the liquid-side shutoff valve.
closed.
E3 Recalculate the required amount of refrigerant from the piping
Refrigerant overcharge. length and correct the refrigerant charge level by recovering any
excessive refrigerant with a refrigerant recovery machine.
The shutoff valve of an outdoor unit is left Open the gas-side shutoff valve and the liquid-side shutoff valve.
closed.
Check if the additional refrigerant charge has been finished
E4 correctly.
Insufficient refrigerant.
Recalculate the required amount of refrigerant from the piping
length and add an adequate amount of refrigerant.
Recalculate the required amount of refrigerant from the piping
Refrigerant overcharge. length and correct the refrigerant charge level by recovering any
excessive refrigerant with a refrigerant recovery machine.
The shutoff valve of an outdoor unit is left Open the gas-side shutoff valve and the liquid-side shutoff valve.
F3 closed.
Check if the additional refrigerant charge has been finished
correctly.
Insufficient refrigerant.
Recalculate the required amount of refrigerant from the piping
length and add an adequate amount of refrigerant.
Recalculate the required amount of refrigerant from the piping
F6 Refrigerant overcharge length and correct the refrigerant charge level by recovering any
excessive refrigerant with a refrigerant recovery machine.
Power supply cables are connected in the Connect the power supply cables in normal phase. Change any
U1 reverse phase instead of the normal phase. two of the three power supply cables (L1, L2, L3) to correct phase.
U2 Insufficient supply voltage Check to see if the supply voltage is supplied properly.
If a check operation has not been
U3 Perform a check operation.
performed.
U4 No power is supplied to an outdoor unit. Turn the power on for the outdoor unit.
Check the indoor unit. If it is not a dedicated unit, replace the
UA If no dedicated indoor unit is being used. indoor unit.
The shutoff valve of an outdoor unit is left Open the gas-side shutoff valve and the liquid-side shutoff valve.
closed.
UF
If the right indoor unit piping and wiring are Make sure that the right indoor unit piping and wiring are properly
not properly connected to the outdoor unit. connected to the outdoor unit.
If the interunit wiring has not be connected Make sure the interunit wiring is correctly attached to terminals
UH or it has shorted. (X2M) F1/F2 (TO IN/D UNIT) on the outdoor unit circuit board.
Test Operation 83
Test Operation SiENBE34-802
84 Test Operation
SiENBE34-802 Test Operation
Indoor unit If ON button is pushed during operation described above, the “UH”
malfunction indicator blinks.
(Returns to normal when automatic setting is complete.)
Indoor unit If ON button is pushed during operation described above, the operation lamp
lights but the compressor does not operate. (Returns to normal when
automatic setting is complete.)
1.2.3 When an Indoor Unit or Outdoor Unit has been Added, or Indoor or
Outdoor Unit PC Board has been Changed
Be sure to push and hold the RESET button for 5 seconds. If not, the addition cannot be
recognized. In this case, the unit cannot be run for up to 12 minutes to automatically set the
address (indoor-outdoor address, etc.)
Status
Outdoor unit Test lamp H2P .... ON
Can also be set during operation described above.
Indoor unit If ON button is pushed during operation described above, the “UH” or “U4”
malfunction indicator blinks. (Returns to normal when automatic setting is
complete.)
Test Operation 85
Outdoor Unit PC Board Layout SiENBE34-802
A2P
X1M X2M
RXYSQ4 / 5 / 6PA7V1B
A3P
A2P
A4P
X2M
Changeover between
X1M Test cooling and heating Low
Page
Error Individual Batch
(master)
Batch
(slave) noise Demand
DIP switches
(DS1-1 and DS1-2)
ON
MODE SET RETURN TEST RESET OFF
86 Test Operation
SiENBE34-802 Field Setting
3. Field Setting
3.1 Field Setting from remote control
Individual function of indoor unit can be changed from the remote control. At the time of
installation or after service inspection / repair, make the local setting in accordance with the
following description.
Wrong setting may cause malfunction.
(When optional accessory is mounted on the indoor unit, setting for the indoor unit may be
required to change. Refer to information in the option handbook.)
CODE NO. 3 4
1 7 TEST
6 5 2
(V0292)
1. When in the normal mode, press the “ ” button for a minimum of four seconds, and the
FIELD SET MODE is entered.
2. Select the desired MODE NO. with the “ ” button (2).
3. During group control, when setting by each indoor unit (mode No. 20, 22 and 23 have been
selected), push the “ ” button (3) and select the INDOOR UNIT NO to be set. (This
operation is unnecessary when setting by group.)
4. Push the “ ” upper button (4) and select FIRST CODE NO.
5. Push the “ ” lower button (5) and select the SECOND CODE NO.
6. Push the “ ” button (6) once and the present settings are SET.
7. Push the “ ” button (7) to return to the NORMAL MODE.
(Example)
If during group setting and the time to clean air filter is set to FILTER CONTAMINATION,
HEAVY, SET MODE NO. to “10” FIRST CODE NO. to “0”, and SECOND CODE NO. to “02”.
Test Operation 87
Field Setting SiENBE34-802
BRC1D528
UNIT NO.
FIRST MODE NO.
CODE NO. UNIT No.
SECOND GROUP
SETTING
FIELD
CODE NO. SET
4 MODE
3
1
7
6 5 2
If optional accessories are mounted on the indoor unit, the indoor unit setting may have to be
changed. Refer to the instruction manual for each optional accessory.
1. When in the normal mode, press the “ ” button for a minimum of four seconds, and the
FIELD SET MODE is entered.
2. Select the desired MODE NO. with the “ ” button.
3. During group control, when setting by each indoor unit (mode No. 20, 21, 22 and 23 have
been selected), push the “ ” button and select the INDOOR UNIT NO. to be set. (This
operation is unnecessary when setting by group.)
4. Push the “ ” upper button and select FIRST CODE NO.
5. Push the “ ” lower button and select the SECOND CODE NO.
6. Push the “ ” button once and the present settings are SET.
7. Push the “ ” button to return to the NORMAL MODE.
(Example)
If during group setting and the time to clean the air filter is set to FILTER CONTAMINATION -
HEAVY, SET MODE NO. to “10”, FIRST CODE NO. to “0”, and SECOND CODE NO. to “02”.
Notes : 1. Setting is carried out in the group mode, however, if the mode number inside the
parentheses is selected, indoor units can also be set individually.
2. The SECOND CODE number is set to “01” when shipped from the factory.
3. Do not make any settings not given in the table.
4. Not displayed if the indoor unit is not equipped with that function.
5. When returning to the normal mode, “88” may be displayed in the LCD in order for the
remote control to initialize itself.
6. It is not possible to change field settings on the remote control that is set to “sub”.
88 Test Operation
SiENBE34-802 Field Setting
MODE NO.
FIELD SET MODE
1. When in the normal mode, push the “ ” button for 4 seconds or more, and operation
then enters the “field set mode.”
2. Select the desired “mode No.” with the “ ” button.
3. Pushing the “ UP ” button, select the first code No.
4. Pushing the “ DOWN ” button, select the second code No.
5. Push the timer “ ” button and check the settings.
6. Push the “ ” button to return to the normal mode.
(Example)
When setting the filter sign time to “Filter Dirtiness-High” in all group unit setting, set the Mode
No. to “10”, Mode setting No. to “0” and setting position No. to “02”.
Test Operation 89
Field Setting SiENBE34-802
MODE NO.
FIRST
CODE NO.
UNIT NO.
SECOND
CODE NO.
90 Test Operation
SiENBE34-802 Field Setting
Completion of
11 Start of airflow
(21) 7 Airflow adjustment OFF airflow adjustment — (5)
adjustment
Optional accessories output selection (field Indoor unit turned Operation Malfunction
0 selection of output for adapter for wiring) ON by thermostat — output output (6)
1 Selection of air flow direction (Set when F (4 directions) T (3 directions) W (2 directions) — (14)
a blocking pad kit has been installed.)
Air flow direction adjustment (Set at
13 3 installation of decoration panel.) Equipped Not equipped — — (15)
(23) Ceiling Soiling
4 Field set air flow position setting Draft prevention Standard — (16)
prevention
5 Setting of the Static Pressure Standard High static — — (17)
Selection pressure
01:30 02:50 03:60 04:70 05:80 06:90 07:100 08:110
6 External Static Pressure Settings (18)
09:120 10:130 11:140 12:150 13:160 14:180 15:200 *7
1 Thermostat OFF excess humidity Not equipped Equipped — — (19)
Direct duct connection
2 (when the indoor unit and heat Not equipped Equipped — — (20)
15 reclaim ventilation unit are
(25) connected by duct directly.) ∗Note 6
3 Drain pump humidifier interlock selection Not equipped Equipped — — (21)
Field set selection for individual
5 Not equipped Equipped — — (22)
ventilation setting by remote control
Notes : 1. Settings are made simultaneously for the entire group, however, if you select the mode No.
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
2. The mode numbers inside parentheses cannot be used by wireless remote controls, so they
cannot be set individually. Setting changes also cannot be checked.
3. Marked are factory set.
4. Do not make settings other than those described above. Nothing is displayed for functions
the indoor unit is not equipped with.
5. “88” may be displayed to indicate the remote control is resetting when returning to the
normal mode.
6. If the setting mode to “Equipped”, heat reclaim ventilation fan conducts the fan residual
operation by linking to indoor unit.
7. • The FXMQ50·63·80·100·125PVE cannot be set to 30Pa.
• The FXMQ40PVE cannot be set to 180 or 200Pa.
Test Operation 91
Field Setting SiENBE34-802
Ceiling mounted cassette Slim Ceiling Ceiling Ceiling Wall Floor Concealed New Ceiling Details
type Ceiling mounted Mounted suspended mounted standing Floor suspended No.
mounted built-in duct type type type type standing cassette
Round Double Corner duct type type (Middle and type type
flow flow type high static
pressure)
FXFQ FXCQ FXKQ FXDQ FXSQ FXMQ-P FXHQ FXAQ FXLQ FXNQ FXUQ
92 Test Operation
SiENBE34-802 Field Setting
Setting Table
Mode No. Setting Switch No. Setting Position No. Setting
01 Long-Life Filter
10 (20) 1 02 Ultra-Long-Life Filter (1)
03 —
Test Operation 93
Field Setting SiENBE34-802
F2 T1 T2
Forced stop
Input A
Setting Table
Setting Setting
Mode No. Operation by input of the signal A
Switch No. Position No.
ON: Forced stop (prohibition of using the remote control)
01 OFF: Permission of using the remote control
OFF → ON: Permission of operation
02
12 (22) 1 ON → OFF: Stop
ON: Operation
03 OFF: The system stops, then the applicable unit
indicates "A0". The other indoor units indicate "U9".
94 Test Operation
SiENBE34-802 Field Setting
For the above reasons, when the unit is set enabling to utilize “Auto restart function after power
failure reset”, utmost care should be paid for the occurrence of the following situation.
Caution 1. The air conditioner starts operation suddenly after power failure reset or
the main power supply turned on again. Consequently, the user might be
surprised (with question for the reason why).
2. In the service work, for example, turning off the main power switch during
the unit is in operation, and turning on the switch again after the work is
completed start the unit operation (the fan rotates).
Test Operation 95
Field Setting SiENBE34-802
96 Test Operation
SiENBE34-802 Field Setting
Setting Table
Second Code
Mode No. First Code No. Setting
No.
01 F : 4-direction air flow
13 (23) 1 02 T : 3-direction air flow
03 W : 2-direction air flow
Setting Table
Mode No. First Code No. Second Code No. Setting
01 Down-flow operation: Yes
13 (23) 3
02 Down-flow operation: No
(S2537)
Setting Table
Mode No. First Code No. Second Code No. Setting
Upward (Draft
01 prevention)
13 (23) 4 02 Standard
Downward (Ceiling
03 soiling prevention)
∗ Some indoor unit models are not equipped with draft prevention (upward) function.
Test Operation 97
Field Setting SiENBE34-802
98 Test Operation
SiENBE34-802 Field Setting
Test Operation 99
Field Setting SiENBE34-802
MODE NO.
GROUP NO.
UNIT NO.
FIELD SET
SETTING
MODE
TEST
3
5 4
2,6
Note:
For infrared remote control, see the following.
For setting group No. of HRV and wiring adapter for other air conditioners, etc., refer to the
instruction manual attached.
NOTICE
Enter the group No. and installation place of the indoor unit into the attached installation table.
Be sure to keep the installation table with the operation manual for maintenance.
BRC7 Type Group No. setting by infrared remote control for centralized control
BRC4 Type 1. When in the normal mode, push “ ” button for 4 seconds or more, and operation then
enters the “field set mode.”
2. Set mode No. “00” with “ ” button.
3. Set the group No. for each group with “ UP ” “ DOWN ” button (advance/backward).
4. Enter the selected group numbers by pushing “ ” button.
5. Push “ ” button and return to the normal mode.
MODE NO.
FIELD SET MODE
GROUP NO.
(V0916)
F1 F2
F1 F2 F1 F2 F1 F2 F1 F2
F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2
RC
Main RC RC Sub RC Group Control by Remote Contol
1-00
(autmatic unit address)
1-01 1-02
F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2 F1 F2 P1 P2
No Remote Control
RC
1-03 (V0917)
1-04
Caution When turning the power supply on, the unit may often not accept any operation while "88" is
displaying after all indications were displayed once for about 1 minute on the liquid crystal
display. This is not an operative fault.
How to Select Whether operation by remote control will be possible or not for turning on/off, controlling
Operation Mode temperature or setting operation mode is selected and decided by the operation mode given on
the right edge of the table below.
Example
ON by remote OFF by remote
Temperature Operation mode Control
control control OFF by control by setting by
(Unified ON by (Unified OFF by remote mode is "1."
remote control remote control
central remote central remote control
control) control)
↓ ↓ ↓ ↓ ↓
Rejection Rejection Rejection Acceptance Acceptance (VL069)
A1P
ON/OFF
DS1-1
switch knob
DS1 1 2
X2M
ABC
ABC
Cool/heat
selector
Caution Capacity Setting after changing the main PC Board(A1P) to spare parts PC Board
When you change the main PC Board(A1P) to spare parts PC Board, please carry out the
following setting.
Please Attach the Capacity Setting Adapter corresponding to Capacity Class (ex. 112, 140, 160) in connector X51A.
(See Below)
RXYSQ4 / 5 / 6PA7Y1B
X51A
RXYSQ4 / 5 / 6PA7V1B
X51A
Push and hold the BS1 (Normal) Push the BS1(MODE button)
(MODE button) for 5 seconds. one time.
Setting mode 2 Setting mode 1 Monitor mode
On Off Blinking
(Set): Select mode with BS2 (SET button) in each selection step.
Press BS1 (MODE button) for more than 5 sec. Setting mode 1 Press BS1(MODE button).
(Initial condition)
(V2762)
a. “Setting mode 1”
This mode is used to set and check the following items.
1. Set items ············ In order to make COOL/HEAT selection in a batch of outdoor unit group, change the setting.
• COOL/HEAT selection (IND) ·····················Used to select COOL or HEAT by individual outdoor
unit (factory set).
• COOL/HEAT selection (MASTER) ············Used to select COOL or HEAT by outdoor unit group
with the master unit.
• COOL/HEAT selection (SLAVE)················Used to select COOL or HEAT by outdoor unit group
with the slave unit.
2. Check items ······· The following items can be checked.
(1) Current operating conditions (Normal / Abnormal / In check operation)
(2) Setting conditions of COOL/HEAT selection (Individual / Batch master / Batch slave)
(3) Low noise operating conditions (In normal operation / In low noise operation)
(4) Demand operating conditions (In normal operation / In demand operation)
8 ON
7 OFF
9 Blink
COOL/HEAT select Low
Push the SET (BS2) button to set MODE TEST Demand
the blinking of LED to any of Setting (displaying) item IND MASTER SLAVE noise H7P
H1P H2P
conditions shown on the right. H3P H4P H5P H6P
For selection by individual outdoor unit (factory set) 7 7 9 7 7 7 7
For selection in a batch of outdoor unit group with master unit 7 7 7 9 7 7 7
For selection in a batch of outdoor unit group with slave unit 7 7 7 7 9 7 7
Pushing the RETURN (BS3) button will return the system to the initial condition of
Push the RETURN (BS3) button to
determine the setting. "Setting mode 1".
Push the SET button and match with the LEDs No. 1 - 15, push the RETURN button, and
confirm the data for each setting.
H Data such as addresses and number of units is expressed as binary numbers; the two
ways of expressing are as follows:
977 7979
The number of terminal blocks for No. 12 and 13 is expressed as
64 16
No.12 128 32 an 8-digit binary number, which is the combination of four upper,
and four lower digits for No. 12 and 13 respectively. (0 - 128)
977 7997 In d the address for No. 12 is 0101, the address for No. 13 is
4 1 0110, and the combination of the two is 01010110 (binary
No.13 8 2 number), which translates to 64 + 16 + 4 + 2 = 86 (base 10
number). In other words, the number of terminal block is 86.
H See the preceding page for a list of data, etc. for No. 0 - 25.
c Set Cool / Heat Separately for Each Outdoor Unit System by Indoor Unit remote control
It does not matter whether or not there is outdoor - outdoor unit wiring.
Set outdoor unit PC board DS1-1 to IN (factory set).
Set cool/heat switching to IND (individual) for “Setting mode 1” (factory set).
ON
Dip SW.
DS1-1
OFF
Remote Remote
control control
d Set Cool / Heat Separately for Each Outdoor Unit System by Cool/Heat Switching Remote control
It does not matter whether or not there is outdoor - outdoor unit wiring.
Set outdoor unit PC board DS1-1 to OUT (factory set).
Set cool/heat switching to IND (individual) for “Setting mode 1” (factory set).
ON
Dip SW.
DS1-1
OFF
C/H select
remote Indoor unit Indoor unit
control
Remote Remote
(V3059)
control control
When the low noise operation is carried out automatically at night (The external control
adapter for outdoor unit is not required)
1. While in "Setting mode 2", select the setting condition (i.e., "Mode 1", "Mode 2", or "Mode 3")
for set item No. 22 (Setting of nighttime low noise level).
2. If necessary, while in "Setting mode 2", select the setting condition (i.e., "20:00", "22:00", or
"24:00") for set item No. 26 (Setting of start time of nighttime low noise operation).
(Use the start time as a guide since it is estimated according to outdoor temperatures.)
3. If necessary, while in "Setting mode 2", select the setting condition (i.e., "06:00", "07:00", or
"08:00") for set item No. 27 (Setting of end time of nighttime low noise operation).
(Use the end time as a guide since it is estimated according to outdoor temperatures.)
4. If necessary, while in "Setting mode 2", set the setting condition for set item No. 29 (Setting
of capacity precedence) to "ON".
(If the condition is set to "ON", when the air-conditioning load reaches a high level, the
system will be put into normal operation mode even during nighttime.)
Image of operation
If capacity precedence is set in "Capacity
Operation sound precedence setting", the fan speed will be
increased according to the load of air
Time set with "Night-time low noise start setting" conditioning when load is heavier. Time set with "Night-time low noise end setting"
Rated operation
sound Operation sound during
Night time night-time low noise mode is
Operation sound instructed can be set with
of mode 1 "Night-time low noise level
setting".
Operation sound (Factory setting is "OFF".)
of mode 2
Operation sound
of mode 3 Operation sound level set with
"Night-time low noise setting”
Set with "Night-time low noise start setting" Set with "Night-time low noise end setting"
(Factory setting is "PM 10:00".) (Factory setting is "PM 8:00".) (V3079)
When the normal demand operation is carried out. (Use of the external control adapter
for outdoor unit is not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of constant demand)
to "ON".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then
set the setting condition to targeted mode.
Image of operation
(V3082)
{: ON z: OFF 9: Blink
c d e
Setting Setting Setting No. indication Setting No. indication Setting Setting contents indication (Initial setting)
No. contents contents
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12 External NO
low noise / { z z z z z z { z z { { z z (Factory { z z z z z 9
Demand set)
setting
YES { z z z z 9 z
22 Night-time OFF
low noise { z { z { { z (Factory { z z z z z z
setting setting)
Mode 1 { z z z z z 9
Mode 2 { z z z z 9 z
Mode 3 { z z z z 9 9
26 Night-time { z { { z { z PM 8:00 { z z z z z 9
low noise
start setting PM 10:00
(Factory { z z z z 9 z
setting)
PM 0:00 { z z z 9 z z
27 Night-time { z { { z { { AM 6:00 { z z z z z 9
low noise
end setting AM 7:00 { z z z z 9 z
AM 8:00
(Factory { z z z 9 z z
setting)
29 Capacity Low noise
precedence precedence
setting { z { { { z { (Factory { z z z z z 9
setting)
Capacity
precedence { z z z z 9 z
30 Demand 60 % of
setting 1 { z { { { { z rated power { z z z z z 9
consumption
70 % of
rated power
consumption { z z z z 9 z
(Factory
setting)
80 % of
rated power { z z z 9 z z
consumption
32 Normal OFF
demand { z z z z z z (Factory { z z z z z 9
setting setting)
ON { z z z z 9 z
Setting mode indication section Setting No. indication section Set contents indication section
* When the outdoor unit is stopped and the entire quantity of refrigerant cannot be
charged from the stop valve on the liquid side, make sure to charge the remaining
quantity of refrigerant using this procedure. If the refrigerant quantity is insufficient,
the unit may malfunction.
Turn ON the power of the indoor unit and the outdoor unit.
Make sure to completely open the stop valve on the gas side and the stop valve on the
liquid side.
Connect the refrigerant charge hose to the service port (for additionally charging the
refrigerant).
In the stopped status, set to ON the refrigerant additional charging operation A in
set mode 2 (H1P: Turn on).
The operation is automatically started.
(The LED indicator H2P flickers, and "Test run" and "Under centralized control" are
displayed in the remote control.)
After charging the specified quantity of refrigerant, press the RETURN button (BS3) to stop
the operation.
The operation is automatically stopped within 30 minutes.
If charging is not completed within 30 minutes, set and perform the refrigerant
additional charging operation A again.
If the refrigerant additional charging operation is stopped soon, the refrigerant may be
overcharged.
Never charge extra refrigerant.
Disconnect the refrigerant charge hose.
V1 Y1
[Operation procedure]
c In “Setting Mode 2” with units in stop mode, set “B Refrigerant Recovery / Vacuuming mode”
to ON. The respective expansion valve of indoor and outdoor units are fully opened. “TEST
OPERATION” and “UNDER CENTRALIZED CONTROL” are displayed on the remote
control, and the indoor / outdoor unit operation is prohibited.
After setting, do not cancel “Setting Mode 2” until completion of refrigerant recovery
operation.
d Collect the refrigerant using a refrigerant recovery unit. (See the operation manual attached
to the refrigerant recovery unit for more detal.)
e Press Mode button “BS1” once and reset “Setting Mode 2”.
[Operating procedure]
c In “Setting Mode 2” with units in stop mode, set “B Refrigerant Recovery / Vacuuming mode”
to ON. The respective expansion valve of indoor and outdoor units are fully opened. “TEST
OPERATION” and “UNDER CENTRALIZED CONTROL” are displayed on the remote
control, and the indoor / outdoor unit operation is prohibited.
After setting, do not cancel “Setting Mode 2” until completion of Vacuuming operation.
d Use the vacuum pump to perform vacuuming operation.
e Press Mode button “BS1” once and reset “Setting Mode 2”.
Completion
Part 7
Troubleshooting
1. Symptom-based Troubleshooting .......................................................125
2. Troubleshooting by Remote Control ...................................................128
2.1 The INSPECTION / TEST Button.........................................................128
2.2 Self-diagnosis by Wired Remote Control .............................................129
2.3 Self-diagnosis by Wireless Remote Control .........................................130
2.4 Operation of the Remote Control’s Inspection /
Test Operation Button ..........................................................................132
2.5 Remote Control Service Mode .............................................................133
2.6 Remote Control Self-Diagnosis Function .............................................135
3. Troubleshooting by Indication on the Remote Control ........................142
3.1 “A0” Indoor Unit: Error of External Protection Device ...........................142
3.2 “A1” Indoor Unit: PC Board Defect ........................................................143
3.3 “A3” Indoor Unit: Malfunction of Drain Level Control System (S1L)......144
3.4 “A6” Indoor Unit: Fan Motor (M1F) Lock, Overload ..............................146
3.5 “A7” Indoor Unit: Malfunction of Swing Flap Motor (M1S) ....................147
3.6 Abnormal Power Supply Voltage..........................................................149
3.7 “A9” Indoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y1E)........................................................150
3.8 “AF” Indoor Unit: Drain Level above Limit .............................................152
3.9 “AJ” Indoor Unit: Malfunction of Capacity Determination Device..........153
3.10 “C1” Indoor Unit: Failure of Transmission
(Between Indoor unit PC Board and Fan PC Board)............................154
3.11 “C4” Indoor Unit: Malfunction of Thermistor (R2T) for
Heat Exchanger....................................................................................156
3.12 “C5” Indoor Unit: Malfunction of Thermistor (R3T) for Gas Pipes .........157
3.13 “C6” Indoor Unit: Failure of Combination
(Between Indoor unit PC Board and Fan PC Board)............................158
3.14 “C9” Indoor Unit: Malfunction of Thermistor (R1T) for Suction Air ........159
3.15 “CA” Indoor Unit: Malfunction of Thermistor for Discharge Air ..............160
3.16 “CC” Indoor Unit: Malfunction of Humidity Sensor System ....................161
3.17 “CJ” Indoor Unit: Malfunction of Thermostat Sensor in
Remote Control ....................................................................................162
3.18 “E1” Outdoor Unit: PC Board Defect......................................................163
3.19 “E3” Outdoor Unit: Actuation of High Pressure Switch..........................164
3.20 “E4” Outdoor Unit: Actuation of Low Pressure Sensor .........................166
3.21 “E5” Inverter Compressor Motor Lock...................................................168
3.22 “E7” Malfunction of Outdoor Unit Fan Motor .........................................169
3.23 “E9” Outdoor Unit: Malfunction of Moving Part of
Electronic Expansion Valve (Y1E, Y3E)...............................................170
3.24 “F3” Outdoor Unit: Abnormal Discharge Pipe Temperature..................172
3.25 “F6” Outdoor Unit: Refrigerant Overcharged ........................................173
3.26 “H9” Outdoor Unit: Malfunction of Thermistor (R1T) for Outdoor Air ....174
3.27 “J3” Outdoor Unit: Malfunction of Discharge Pipe Thermistor (R2T)....175
3.28 “J5” Outdoor Unit: Malfunction of Thermistor (R3T, R5T) for
Suction Pipe 1, 2 ..................................................................................176
Troubleshooting 123
SiENBE34-802
124 Troubleshooting
SiENBE34-802 Symptom-based Troubleshooting
1. Symptom-based Troubleshooting
Symptom Supposed Cause Countermeasure
1 The system does not start operation at all. Blowout of fuse(s) Turn Off the power supply and
then replace the fuse(s).
Cutout of breaker(s) • If the knob of any breaker is in
its OFF position, turn ON the
power supply.
• If the knob of any circuit
breaker is in its tripped position,
do not turn ON the power
supply.
ON
Knob
Tripped
OFF
Circuit breaker
Troubleshooting 125
Symptom-based Troubleshooting SiENBE34-802
126 Troubleshooting
SiENBE34-802 Symptom-based Troubleshooting
Troubleshooting 127
Troubleshooting by Remote Control SiENBE34-802
Normal
mode
Press Inspection/Test Operation button once.
Press Inspection/Test Operation
Or after 30 minutes
button once.
After 10 seconds
128 Troubleshooting
SiENBE34-802 Troubleshooting by Remote Control
ON/OFF button
Inspection display
Malfunction code
Inspection/Test button
Note:
1. Pressing the INSPECTION/TEST button will blink the check indication.
2. While in check mode, pressing and holding the ON/OFF button for a period of five seconds or
more will clear the failure history indication shown above. In this case, on the codes display,
the malfunction code will blink twice and then change to “00” (=Normal), the Unit No. will
change to “0”, and the operation mode will automatically switch from check mode to normal
mode (displaying the set temperature).
Troubleshooting 129
Troubleshooting by Remote Control SiENBE34-802
The upper digit of the code changes as shown below when the UP and DOWN buttons are
pressed.
*2 Number of beeps
Continuous beep : Both upper and lower digits matched. (Malfunction code confirmed)
2 short beeps : Upper digit matched.
1 short beep : Lower digit matched.
5. Press the MODE selector button.
The right “0” (lower digit) indication of the malfunction code flashes.
6. Malfunction code lower digit diagnosis
Press the UP or DOWN button and change the malfunction code lower digit until the
continuous malfunction code matching buzzer (*2) is generated.
130 Troubleshooting
SiENBE34-802 Troubleshooting by Remote Control
The lower digit of the code changes as shown below when the UP and DOWN buttons are
pressed.
Normal status
Enters inspection mode from normal
status when the INSPECTION/TEST
button is pressed.
If no button is pressed
for 1 minute, equipment
returns to normal status.
3. Press
MODE
selector
When MODE selector button.
button is pressed or no
button is pressed for 1
minute, equipment
returns to normal status.
If no button is pressed
for 1 minute, equipment
returns to normal status.
Troubleshooting 131
Troubleshooting by Remote Control SiENBE34-802
Inspection/test
operation Push the button.
Unit 0
Malfunction code L0 0 7 1... Capacity code Example of capacity code display
Inspection F... Indoor unit system code Example model Display
C... Indoor unit type code
Inspection mode J... Progression code FXCQ25 028
FXFQ63 071
Inspection/test
operation Push the button.
Indoor unit system code
Display Product classification System classification
1 VRV system (VAV indoor unit)
071
FCJ 2 VRV system Outdoor air processing unit
F VRV system Standard indoor unit
Indoor unit model code display H VRV system New ceilling suspended cassette
132 Troubleshooting
SiENBE34-802 Troubleshooting by Remote Control
Push the button for 4 seconds or longer. Push the button for 4 seconds or longer.
(VF020)
Troubleshooting 133
Troubleshooting by Remote Control SiENBE34-802
Mode Function Contents and operation method Remote control display example
No
40 Malfunction
hysteresis display
Display malfunction hysteresis.
The history No. can be changed with the Unit 1
button.
Malfunction code 40
2-U4
Malfunction code
Hystory No: 1 - 9
(VE007) 1: Latest
41 Display of sensor
and address data
Display various types of data.
Select the data to be displayed with the Sensor data display
button. Sensor data
0: Thermostat sensor in remote control. Unit No. Sensor type
1: Suction
2: Liquid pipe
41
3: Gas pipe 1 1
27
Address data
4: Indoor unit address Temperature ºC
5: Outdoor unit address
6: BS unit address Address display
7: Zone control address Unit No. Address type
8: Cool/heat group address
9: Demand / low noise address
41
1 8
1
Address
(VE008)
44 Individual setting Set the fan speed and air flow direction by each
unit
Unit 1
Select the unit No. with the time mode
44
button. Set the fan speed with the Code
button.
1 3
Set the air flow direction with the button.
Fan speed 1: Low Air flow direction
3: High P0 - P4
(VE010)
134 Troubleshooting
SiENBE34-802 Troubleshooting by Remote Control
Operation lamp
ON/OFF button
(VL050)
Troubleshooting 135
Troubleshooting by Remote Control SiENBE34-802
8: ON 7: OFF 9: Blink
Malfunction Operation Malfunction contents Page
code lamp Referred
Indoor Unit A0 9 Error of external protection device 142
A1 9 PC board defect, E2 PROM defect 143
A3 9 Malfunction of drain level control system (S1L) 144
A6 9 Fan motor (M1F) lock, overload 146
A7 8 Malfunction of swing flap motor (M1S) 147
A8 9 Abnormal power supply voltage 149
A9 9 Malfunction of moving part of electronic expansion valve (Y1E) 150
AF 8 Drain level above limit 152
AJ 9 Malfunction of capacity setting 153
C1 9 Failure of transmission (between indoor unit PC board and fan PC board) 154
C4 9 Malfunction of thermistor (R2T) for heat exchange (loose connection, 156
disconnection, short circuit, failure)
C5 9 Malfunction of thermistor (R3T) for gas pipes (loose connection, 157
disconnection, short circuit, failure)
C6 9 Failure of combination (between indoor unit PC board and fan PC board) 158
C9 9 Malfunction of thermistor (R1T) for suction air (loose connection, 159
disconnection, short circuit, failure)
CA 9 Malfunction of thermistor for discharge air (loose connection, 160
disconnection, short circuit, failure)
CC 8 Malfunction of humidity sensor system 161
CJ 8 Malfunction of thermostat sensor in remote control 162
Outdoor Unit E1 9 PC board defect 163
E3 9 Actuation of high pressure switch 164
E4 9 Actuation of low pressure sensor 166
E5 9 Compressor motor lock 168
E6 9 Standard compressor lock or over current —
E7 9 Malfunction of outdoor unit fan motor 169
E9 9 Malfunction of moving part of electronic expansion valve (Y1E, Y3E) 170
F3 9 Abnormal discharge pipe temperature 172
F6 9 Refrigerant overcharged 173
H3 8 Failure of high pressure switch —
H4 9 Actuation of low pressure switch —
H7 9 Abnormal outdoor fan motor signal —
H9 9 Malfunction of thermistor (R1T) for outdoor air (loose connection, 174
disconnection, short circuit, failure)
J2 9 Current sensor malfunction —
J3 9 Malfunction of discharge pipe thermistor (R2T) (loose connection, 175
disconnection, short circuit, failure)
J5 9 Malfunction of thermistor (R3T, R5T) for suction pipe (loose connection, 176
disconnection, short circuit, failure)
J6 9 Malfunction of thermistor (R6T) for heat exchanger (loose connection, 177
disconnection, short circuit, failure)
J7 9 Malfunction of thermistor (R7T) for outdoor unit liquid pipe 178
J9 9 Malfunction of subcooling heat exchanger gas pipe thermistor (R4T) 179
JA 9 Malfunction of high pressure sensor 180
JC 9 Malfunction of low pressure sensor 181
L0 9 Inverter system error —
L1 9 Malfunction of PC board 182
L4 9 Malfunction of inverter radiating fin temperature rise 183
L5 9 Inverter compressor abnormal 184
L8 9 Inverter current abnormal 185
L9 9 Inverter start up error 186
136 Troubleshooting
SiENBE34-802 Troubleshooting by Remote Control
8: ON 7: OFF 9: Blink
Malfunction Operation Malfunction contents Page
code lamp Referred
Outdoor Unit LA 9 Malfunction of power unit —
LC 9 Malfunction of transmission between inverter and control PC board 187
P1 9 High voltage of capacitor in main inverter circuit. 188
System U0 8 Low pressure drop due to refrigerant shortage or electronic expansion 189
valve failure
U1 9 Reverse phase / open phase —
U2 9 Power supply insufficient or instantaneous failure 191
U3 9 Check operation is not completed. 193
U4 9 Malfunction of transmission between indoor and outdoor units 194
U5 9 Malfunction of transmission between remote control and indoor unit 196
U5 7 Failure of remote control PC board or setting during control by remote 196
control
U7 9 Malfunction of transmission between outdoor units —
U8 9 Malfunction of transmission between main and sub remote controls 197
(malfunction of sub remote control)
U9 9 Malfunction of transmission between indoor unit and outdoor unit in the 198
same system
UA 9 Excessive number of indoor units 200
UC 8 Address duplication of central remote control 201
UE 9 Malfunction of transmission between central remote control and indoor unit 202
UF 9 System is not set yet 204
UH 9 Malfunction of system, refrigerant system address undefined 205
Central UE 9 Malfunction of transmission between centralized remote control and indoor 206
remote unit
control and M1 8 or 7 PC board defect 207
Schedule
Timer M8 8 or 7 Malfunction of transmission between optional controls for centralized 208
control
MA 8 or 7 Improper combination of optional controllers for centralized control 209
MC 8 or 7 Address duplication, improper setting 211
Heat 64 8 Indoor unit’s air thermistor error —
Reclaim 65 8 Outside air thermistor error —
Ventilation
68 8 Malfunction of HVU —
6A 8 Damper system alarm —
6A 9 Damper system + thermistor error —
6F 8 Malfunction of simple remote control —
94 9 Internal transmission error —
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Troubleshooting 137
Troubleshooting by Remote Control SiENBE34-802
138 Troubleshooting
SiENBE34-802 Troubleshooting by Remote Control
8: ON 7: OFF 9:Blink
MalfunctionConfirmation of malfunction 1 Confirmation of malfunction 2 Confirmation of malfunction 3 Confirmation of malfunction 4
code H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
E1 9 7 7 9 9 9 7 7 7 9 9 8 7 7 7 7 7 9 8 8 7 7 9 9
E3 9 7 7 9 9 9 7 7 7 7 9 7 7
E4 9 7 9 7 7 9 7 7 7 7 9 7 7
E5 9 7 9 7 9 9 7 7 7 7 9 7 7
E7 9 7 9 9 9 9 7 7 7 7 9 7 9 ∗1
9 7 7 7 9 9 7 9
E9 9 9 7 7 9 9 7 7 7 7 9 7 7
9 7 7 7 7 9 9 7
H9 9 9 7 7 9 9 7 7 7 7 9 7 7 ∗1
F3 9 7 9 7 9 9 7 7 9 9 9 7 7 7 7 9 7 7 ∗1
F6 9 7 9 9 7 9 7 7 7 7 9 7 7 9 9
J3 9 7 9 9 7 9 7 7 9 9 9 7 7 7 7 9 7 7
J5 9 7 9 7 9 9 7 7 7 7 9 7 7
9 7 7 7 7 9 7 9
J6 9 7 9 9 7 9 7 7 7 7 9 7 7
∗1
J7 9 7 9 9 9 9 7 7 7 7 9 7 7
J9 9 9 7 7 9 9 7 7 7 7 9 7 7
JA 9 9 7 9 7 9 7 7 7 7 9 7 7
JC 9 9 9 7 7 9 7 7 7 7 9 7 7
L1 9 7 9 9 9 9 7 7 7 9 9 7 7 7 7 9 7 7 7 7
9 7 7 7 9 9 7 7 7 7 9 7 7 7 9
9 7 7 7 9 9 7 7 7 7 9 7 7 9 7
9 7 7 7 9 9 7 7 7 7 9 7 7 9 9
9 7 7 7 9 9 7 7 7 7 9 7 9 7 7
L4 9 7 9 7 7 9 7 7 7 7 9 7 7
L5 9 7 9 7 9 9 7 7 7 7 9 7 7
L8 9 9 7 7 7 9 7 7 7 7 9 7 7
9 7 7 7 7 9 7 9
9 7 7 7 7 9 9 7
9 7 7 7 9 9 7 7 ∗1
L9 9 9 7 7 9 9 7 7 7 7 9 7 7
9 7 7 7 7 9 7 9
9 7 7 7 7 9 9 7
LC 9 9 9 7 7 9 7 7 7 7 9 7 9
Troubleshooting 139
Troubleshooting by Remote Control SiENBE34-802
140 Troubleshooting
SiENBE34-802 Troubleshooting by Remote Control
8: ON 7: OFF 9:Blink
Malfunction Confirmation of malfunction 1 Confirmation of malfunction 2 Confirmation of malfunction 3 Confirmation of malfunction 4
code H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
P1 9 9 7 7 7 9 7 7 7 9 9 7 7 7 7 9 7 7
∗1
P4 9 7 9 7 7 9 7 7 7 7 9 7 7
U0 9 9 7 7 9 9 7 7 7 7 9 7 7 7 7 9 7 7 9 9
U2 9 7 7 9 7 9 7 7 7 7 9 7 7
∗1
9 7 7 7 7 7 9
9 7 7 7 7 9 7 7 9 7
9 7 7 7 7 9 7 7 7 9
U3 9 7 7 9 9 9 7 7 7 7 9 7 7 9 9
9 7 7 7 7 9 7 9 9 9
U4 9 7 9 7 7 9 7 7 7 7 9 7 7 9 9
9 7 7 7 7 9 7 9 9 9
U9 9 9 7 7 9 9 7 7 7 7 9 7 7 9 9
UA 9 9 7 9 7 9 7 7 7 7 9 7 7 9 9
9 7 7 7 7 9 7 9 9 9
9 7 7 7 7 9 9 7 9 9
9 7 7 7 9 9 7 7 9 9
9 7 7 9 7 9 7 9 9 9
UH 9 9 7 9 9 9 7 7 7 7 9 7 7 9 9
UF 9 9 9 9 9 9 7 7 7 7 9 7 7 9 9
Troubleshooting 141
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
External
protection device is YES
connected to terminals T1 Actuation of external protection
and T2 of the indoor device.
unit terminal
block.
NO
ON/OFF
input from
outside (mode No.
12, first code No. 1) has YES
been set to external Change the second code No. to
protection device input "01" or "02" .
(second code No.
03) by remote
control.
NO
Indoor unit PC board replacement.
(V2776)
142 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Malfunction When data could not be correctly received from the E²PROM
Decision E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power
Conditions supply is turned off.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Troubleshooting 143
Troubleshooting by Indication on the Remote Control SiENBE34-802
Malfunction When rise of water level is not a condition and the float switch goes OFF.
Decision
Conditions
144 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
The float A short
switch is connected to X8A NO circuit connector is NO
(or X15A) of the indoor unit connected to Connect either a short circuit
PC board. X8A. connector or float switch and
turn on again.
YES YES
The
float switch
contact is forming a Becomes NO
YES normal when X8A (or X15A) of
short circuit (continuity check Defect of indoor unit PC board.
with X8A (or X15A) the indoor unit PC board
disconnected) is short circuited
NO YES
Loose connection of connector.
YES YES
Modify the float switch's
connection and turn on again.
The
drain pump is
connected to X25A or NO
terminals Y1 and Y2 of the Connect the drain pump and
indoor unit PC turn on again.
board.
YES
The
drain pump works YES
when the power supply is Check the drain piping for
reset for the indoor clogging or upward slope, etc.
unit.
NO
The
voltage of
terminals Y1 and
Y2 or X25A is 220~240 NO
V (within 5minutes of Replace indoor unit PC board.
resetting the power
supply).
YES
Replace the drain pump or
check for dirt, etc.
(V2778)
Troubleshooting 145
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of Detection by failure of signal for detecting number of turns to come from the fan motor
Malfunction
Detection
Malfunction When number of turns can’t be detected even when output voltage to the fan is maximum
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
wiring from the
fan motor securely NO
connected to connectors on Connect the wiring and turn on
the indoor unit PC again.
board?
YES
Wiring
between the
indoor unit PC board and YES
fan motor is Fix the wiring and turn on again.
disconnected.
NO
YES
Does the fan motor Replace the indoor unit PC board.
run?
NO
Replace the fan motor.
(V2779)
146 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Method of Utilizes ON/OFF of the limit switch when the motor turns.
Malfunction
Detection
Malfunction When ON/OFF of the microswitch for positioning cannot be reversed even though the swing flap
Decision motor is energized for a specified amount of time (about 30 seconds).
Conditions
Troubleshooting 147
Troubleshooting by Indication on the Remote Control SiENBE34-802
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is power supply NO
220~240V provided? Provide 220~240V power
supply.
YES
Indoor unit is
a model equipped with a NO
swing flap function Replace indoor unit PC board.
YES
The The
swing motor works YES connector is connected to NO
when the power supply is X9A (or X15A) of the indoor unit Connect the connector to X9A
turned off and then PC board. and turn on again.
back on.
NO YES
The limit switch NO
functions normally. Replace swing motor.
YES
The
connecting cable is YES
After short-circuited or Replace the limit switch
turning the disconnected. connecting cable.
swing-flap ON
and then stopping NO
with the remote control,
the voltage of X6A (or X29A)
of the indoor unit PC board is NO
220 ~ 240 VAC (50 Hz) / 220 Replace indoor unit PC board.
VAC (60 Hz) when turned
on again (within 30
seconds of
turning on
again).
YES
The YES
connecting cable has no Replace the power supply
continuity. connecting cable.
NO
When
the air flow
direction flap's cam
mechanism is NO
disconnected from the swing Replace swing motor.
motor, operation is
normal when
turned on
again.
YES
Take the cam mechanism
apart, reassemble and turn on
again.
(V2780)
148 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable FXMQ40~125P
Models
Malfunction When the input voltage of fan motor is 150V and below, or 386V and above.
Decision
Conditions
Troubleshooting
There are
problems on the YES
condition of power source Correct any fault.
described above.
NO
Troubleshooting 149
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The
electronic
expansion valve is NO
connected to X7A of the After connecting, turn the power
indoor unit PC supply off and then back on.
board.
YES
Normal
when coil
check (∗1) of the NO
moving part of the electronic Replace the moving part of the
expansion valve is electronic expansion valve.
checked.
YES
NO
If you turn the power supply off
and turn on again, and it still does
not help, replace the indoor unit
PC board.
(V2781)
150 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
∗1: Coil check method for the moving part of the electronic expansion valve
Discount the electronic expansion valve from the PC board and check the continuity between
the connector pins.
(Normal)
Pin No. 1. White 2. Yellow 3. Orange 4. Blue 5. Red 6. Brown
1. White × { × { ×
Approx. Approx.
300Ω 150Ω
2. Yellow × { × {
Approx. Approx.
300Ω 150Ω
3. Orange × { ×
Approx.
150Ω
4. Blue × {
Approx.
150Ω
5. Red ×
6. Brown
{: Continuity
×: No continuity
Troubleshooting 151
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of Water leakage is detected based on float switch ON/OFF operation while the compressor is in
Malfunction non-operation.
Detection
Malfunction When the float switch changes from ON to OFF while the compressor is in non-operation.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Field drain
piping has a defect such YES
as upward sloping. Modify the drain piping.
NO
A
humidifier unit YES
(optional accessory) is installed Check if the humidifier unit is
on the indoor unit. leaking.
NO
Defect of indoor unit PC board.
(V2782)
152 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Method of Capacity is determined according to resistance of the capacity setting adapter and the memory
Malfunction inside the IC memory on the indoor unit PC board, and whether the value is normal or abnormal
Detection is determined.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The indoor
unit PC board was NO
replaced with a replacement Replace the indoor unit PC board.
PC board.
YES
The
indoor unit is a
model that requires
installation of a capacity NO
setting adapter when Replace the indoor unit PC board.
replacing the PC
board.
YES
Install a capacity setting adapter.
(V2783)
Troubleshooting 153
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable FXMQ40~125P
Models
Method of Check the condition of transmission between indoor PC board (A1P) and PC board for fan
Malfunction (A2P) using computer.
Detecion
Supposed Connection defect of the connecter between indoor PC board (A1P) and PC board for fan
Causes (A2P).
Malfunction of indoor PC board (A1P).
Malfunction of PC board for fan (A2P).
External factor, such as instantaneous blackout.
154 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Troubleshooting
Is the
connector between
indoor PC board (A1P) and PC NO
board for fan (A2P) accurately Connect the connector
connected? (*1) accurately.
YES
Confirm the condition of
transmission on indoor PC
board using local installation
mode. (*2)
Under above
local installation mode, NO
installation position is Replace indoor PC board
"01". (A1P).
YES
Connect the connecter X70A
and turn on the power again.
"C1"
YES
Malfunction breaks Replace PC board for fan
out again. (A2P).
NO
∗1. Pull out and insert the connecter once and check it is absolutely connected.
∗2. Method to check transmission part of indoor PC board.
1 Turn off the power and remove the connecter X70A of indoor PC board (A1P).
2 Short-circuit X70A.
3 After turning on the power, check below numbers under local setting remote control.
(Confirmation: Setting position NO. at the condition of setting switch No. 21 on mode No.
41)
↓
Determination 01: Normal
Other than 01: Transmission defect on indoor PC board
H After confirmation, turn off the power, take off the short-circuit and connect X70A back to
original condition.
Troubleshooting 155
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of Malfunction detection is carried out by temperature detected by heat exchanger thermistor.
Malfunction
Detection
Malfunction When the heat exchanger thermistor becomes disconnected or shorted while the unit is running.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector
is connected to X12A of NO
the indoor unit PC Connect the thermistor and turn
board. on again.
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO
(R2T) from the indoor unit Replace the thermistor (R2T).
PC board
(3.5kΩ~360kΩ)
YES
Replace the indoor unit PC board.
(V2784)
156 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Method of Malfunction detection is carried out by temperature detected by gas pipe thermistor.
Malfunction
Detection
Malfunction When the gas pipe thermistor becomes disconnected or shorted while the unit is running.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector is NO
connected to X11A of the Connect the thermistor and turn
indoor unit PC board.
on again.
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO
(R3T) from the indoor unit Replace the thermistor (R3T).
PC board.
(0.6kΩ~360kΩ)
YES
Replace the indoor unit PC board.
(V2785)
Troubleshooting 157
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable FXMQ40~125P
Models
Method of Conduct open line detection with PC board for fan (A2P) using indoor PC board (A1P).
Malfunction
Detection
Malfunction When the communication data of PC board for fan (A2P) is determined as incorrect.
Decision
Conditions
Troubleshooting
YES
Was indoor
NO PC board (A1P) replaced
with supplementary PC
board?
YES
Was
correct capacity
setting adaptor installed NO
when replacing it with Install correct capacity setting
supplementary PC adapter.
board?
YES
After establishing transmission for
indoor and outdoor, diagnose the
operation again.
158 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Method of Malfunction detection is carried out by temperature detected by suction air temperature
Malfunction thermistor.
Detection
Malfunction When the suction air temperature thermistor becomes disconnected or shorted while the unit is
Decision running.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector is NO
connected to X13A of Connect the thermistor and turn
the indoor unit PC
board. on again.
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO
(R1T) from the indoor unit Replace the thermistor (R1T).
PC board.
(7.2kΩ~112kΩ)
YES
Replace the indoor unit PC board.
(V2786)
Troubleshooting 159
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of Malfunction detection is carried out by temperature detected by discharge air temperature
Malfunction thermistor.
Detection
Malfunction When the discharge air temperature thermistor becomes disconnected or shorted while the unit
Decision is running.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector is NO
connected to the indoor Connect the thermistor and turn
unit PC board.
on again.
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO
from the indoor unit PC Replace the thermistor.
board.
(7.2kΩ~112kΩ)
YES
Replace the indoor unit PC board.
(V2786)
160 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable FXFQ
Models
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
Does it function normally? It is normal.
(Poor connector contact)
NO
Is "CC"
displayed on the YES
remote control? (*2) Replace the humidity sensor
PC board ASS'Y (A2P).
*3
NO
*1: To delete the record, the ON/OFF button of the remote control must be pushed and held
for 5 seconds in the check mode.
*2: To display the code, the Inspection/Test Operation button of the remote control must be
pushed and held in the normal mode.
*3: If "CC" is displayed even after replacing the humidity sensor PC board ASS'Y (A2P) and
taking the steps *1 and 2, replace the indoor PC board ASS'Y (A1P).
Troubleshooting 161
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of Malfunction detection is carried out by temperature detected by remote control air temperature
Malfunction thermistor. (Note1)
Detection
Malfunction When the remote control air temperature thermistor becomes disconnected or shorted while the
Decision unit is running.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
NO
External factor other than
equipment malfunction.
(for example, noise etc.)
(V2787)
Note: In case of remote control thermistor malfunction, unit is still operable by suction air thermistor on
indoor unit.
162 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Malfunction When data could not be correctly received from the E²PROM
Decision E²PROM : Type of nonvolatile memory. Maintains memory contents even when the power
Conditions supply is turned off.
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
Return to normal? External factor other than
malfunction (for example,
noise etc.).
NO
Replace the outdoor unit
main PC Board (A1P).
(V3064)
Troubleshooting 163
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Method of Abnormality is detected when the contact of the high pressure protection switch opens.
Malfunction
Detection
Malfunction Error is generated when the HPS activation count reaches the number specific to the operation
Decision mode.
Conditions (Reference) Operating pressure of high pressure switch
Operating pressure: 4.0MPa
Reset pressure: 3.0MPa
164 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
· Mount a pressure gauge on the high-pressure service port.
· Connect the Service Checker.
· Reset the operation using the remote control,
and then restart the operation.
Is
Does the stop YES the HPS NO
due to malfunction (E3) operating value normal Replace the HPS.
recur? (i.e., 4.0MPa)?
NO YES
Are the
characteristics of the high NO
Replace the high pressure sensor.
pressure sensor normal?
(See *1.)
YES
Is
the pressure NO
detected with the PC board Replace the main PC board.
normal? (See *2.)
YES
· The high pressure sensor is normal, and the pressure detected with the PC board is also normal.
· The high pressure has really become high.
(4) Red
High
(3) Black pressure
sensor
(2)
Micro controller
A/D input (1) White
Troubleshooting 165
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Method of Abnormality is detected by the pressure value with the low pressure sensor.
Malfunction
Detection
Malfunction Error is generated when the low pressure is dropped under specific pressure.
Decision Operating pressure:0.07MPa
Conditions
166 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
NO
Is the stop valve open? Open the stop valve.
YES
Are the
characteristics of the NO
low pressure sensor Replace the low pressure sensor.
normal? (See *1.)
YES
Is the
pressure
detected with the PC NO
Replace the main PC board.
board normal?
(See *2.)
YES
· The low pressure sensor is normal, and the pressure
detected with the PC board is also normal.
· The low pressure has really become low.
*1: Make a comparison between the voltage of the pressure sensor (*4) and that read by the
pressure gauge.
(As to the voltage of the pressure sensor, make measurement of voltage at the connector,
and then convert it to pressure according to information on P.253.)
*2: Make a comparison between the low pressure value checked with the Service Checker
and the voltage of the pressure sensor (see *1).
*3: Make measurement of voltage of the pressure sensor.
+5V
Connector for low pressure sensor
(Blue)
(4) Red
Troubleshooting 167
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Method of Inverter PC board takes the position signal from UVW line connected between the inverter and
Malfunction compressor, and the malfunction is detected when any abnormality is observed in the phase-
Detection current waveform.
Malfunction This malfunction will be output when the inverter compressor motor does not start up even in
Decision forced startup mode.
Conditions
Troubleshooting
Is
the stop valve NO
open? Open the stop valve.
YES
YES
Is high
differential pressure YES
starting? (0.5MPa or Remedy the cause.
more)
NO
Check and
see whether compressor YES
is short-circuited or Replace the compressor.
ground.
NO
Are inverter NO
output voltages the same Replace the inverter PC
for 3 phases? board Assy (A2P).
YES
Does low
or high pressure YES
vary even instantaneously
when restarting
compressor?
NO
Replace the compressor.
(V2793)
168 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Method of Malfunction of fan motor system is detected according to the fan speed detected by hall IC
Malfunction when the fan motor runs.
Detection
Malfunction When the fan runs with speed less than a specified one for 6 seconds or more when the fan
Decision motor running conditions are met
Conditions When malfunction is generated 4 times, the system shuts down.
Troubleshooting
NO
Is
there any obstacle YES
around the fan? Remove the obstacle.
NO
Can the Has either the
fan be turned fuse F4U on the control PC YES
smoothly with hand after NO board (A1P) or the fuse F1U on the If the F4U has blown out,
disconnect the connector inverter PC board (A2P) blown
of fan motor? replace the fuse.
out?
If the F1U has blown out,
replace the inverter PC
YES NO
board assy.
Check No. 3
Check on connector of fan
motor (Refer to information Replace the fan motor.
on P.220)
Are Has either the
the resistances NO fuse F4U on the control YES
between pins above PC board (A1P) or the fuse F1U on If the F4U has blown out,
judgment? the inverter PC board (A2P) replace the fuse.
blown out?
If the F1U has blown out,
YES replace the inverter PC
NO board assy.
Replace the fan motor.
Replace outdoor unit PC
board.
Troubleshooting 169
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Malfunction Error is generated under no common power supply when the power is on.
Decision
Conditions
170 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
YES
Return to normal? External factor other than
malfunction (for example, noise
NO etc.).
Electronic
expansion valve is
connected to X21A and NO
X22A of outdoor unit PC After connecting, turn the power
board off and then back on again.
(A1P).
YES
Normal
when coil check
(∗1) of the moving NO
part of the electronic Replace the moving part of the
expansion valve is electronic expansion valve.
checked.
YES
The
connecting cable is YES
short-circuited or Replace the connecting cable.
disconnected.
NO
Replace outdoor unit PC board
(A1P).
(V3067)
(Orange) 1
(Red) 2
Measuring points
(Yellow) 3 1-6
2-6
(Black) 4 3-6
4-6
5
(Gray) 6
(V3067)
Troubleshooting 171
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Method of Abnormality is detected according to the temperature detected by the discharge pipe
Malfunction temperature sensor.
Detection
Malfunction When the discharge pipe temperature rises to an abnormally high level
Decision When the discharge pipe temperature rises suddenly
Conditions
Troubleshooting
Discharge
pipe temperature is YES
120°C or higher when the Refrigerant shortage, compression
unit stop by defect, etc. Defect of the refrigerant
malfunction. system.
NO
Are the
characteristics of
the discharge pipe NO
thermistor normal? Replace the discharge pipe
(3.5~400KΩ)∗ thermistor.
YES
Replace outdoor unit PC board
(A1P).
(V3068)
172 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Method of Excessive charging of refrigerant is detected by using the heat exchanging deicer temperature
Malfunction during a check operation.
Detection
Malfunction When the amount of refrigerant, which is calculated by using the heat exchanging deicer
Decision temperature during a check run, exceeds the standard.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Are the
above thermistor NO
installed on pipes Install thermistor correctly.
correctly?
YES
Remove the heat exchanging
deicer thermister from the
outdoor PC board and measure
resistance with a tester.
Is the
characteristic of NO
the above thermistor Replace thermistor.
normal?
(V2797)
Troubleshooting 173
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Method of Malfunction is detected from the temperature detected by the outdoor air thermistor.
Malfunction
Detection
Malfunction When the outside air temperature thermistor has short circuit or open circuit.
Decision
Conditions
Troubleshooting
Connector
is connected to X11A NO
of outdoor PC board Connect the connector and turn
(A1P). on again.
YES
Resistance
is normal when
measured after NO
disconnecting the thermistor Replace the thermistor (R1T).
(R1T) from the outdoor
unit PC board.
(3.5kΩ to
360kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3070)
174 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Method of Malfunction is detected from the temperature detected by discharge pipe temperature
Malfunction thermistor.
Detection
Malfunction When a short circuit or an open circuit in the discharge pipe temperature thermistor is detected.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector
is connected to
X12A of outdoor unit PC NO
board (A1P). Connect the thermistor and turn
on again.
YES
Resistance
is normal when
measured after
disconnecting the thermistor NO
R2T from the outdoor unit PC Replace the thermistor (R2T).
board.
(5.0kΩ~640kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3072)
Troubleshooting 175
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Method of Malfunction is detected from the temperature detected by the thermistor for suction pipe 1, 2.
Malfunction
Detection
Malfunction When a short circuit or an open circuit in the thermistor for suction pipe 1, 2 are detected.
Decision
Conditions
Supposed Defect of thermistor (R3T, R5T) for outdoor unit suction pipe
Causes Defect of outdoor unit PC board (A1P)
Troubleshooting
Connector of
the thermistor for NO
suction pipe1, 2 is connected Connect the thermistor and turn
to X12A of outdoor unit on again.
PC board
(A1P).
YES
Resistance
is normal when
measured after
disconnecting the NO
thermistor (R3T, R5T) from Replace the thermistor (R3T, R5T).
the outdoor unit PC
board. (3.5kΩ
~360kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3073)
176 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Method of Malfunction is detected from the temperature detected by the heat exchanger thermistor.
Malfunction
Detection
Malfunction When a short circuit or an open circuit in the heat exchange thermistor is detected.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector
is connected to NO
X13A of outdoor unit PC Connect the thermistor and turn
board (A1P). on again.
YES
Resistance
is normal when
measured after NO
disconnecting the thermistor Replace the thermistor (R6T).
(R4T) from the outdoor
unit PC board.
(3.5kΩ~360kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3074)
Troubleshooting 177
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Method of Malfunction is detected from the temperature detected by the liquid pipe thermistor.
Malfunction
Detection
Malfunction When a short circuit or an open circuit in the heat exchange thermistor is detected.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Connector
is connected to NO
X13A of outdoor unit PC Connect the thermistor and turn
board (A1P). on again.
YES
Resistance
is normal when
measured after NO
disconnecting the thermistor Replace the thermistor (R6T).
(R4T) from the outdoor
unit PC board.
(3.5kΩ~360kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3074)
178 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Method of Malfunction is detected according to the temperature detected by subcooling heat exchanger
Malfunction gas pipe thermistor.
Detection
Malfunction When the subcooling heat exchanger gas pipe thermistor is short circuited or open.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
connector for
subcooling heat
exchanger gas pipe NO
thermistor connected to Connect connector and operate
X12A of outdoor unit unit again.
PC board
(A1P)?
YES
Is the
resistance
measured after
removing the thermistor NO
(R4T) from outdoor unit PC Replace thermistor (R4T).
board normal?
(3.5 kΩ to 360 kΩ)
YES
Replace outdoor unit PC board
(A1P).
(V3075)
Troubleshooting 179
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Method of Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Detection
Malfunction When the high pressure sensor is short circuit or open circuit.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The high
pressure sensor is
connected to X17A of NO
Connect the high pressure sensor
outdoor unit PC board and turn on again.
(A1P).
YES
The
relationship
between the ∗1
VH and high pressure
is normal (see ∗2) when YES
voltage is measured between Replace outdoor unit PC board
X17A pins (1) and (3) of (A1P).
outdoor unit PC board
(A1P) (see ∗1).
NO
Replace the high pressure sensor.
(V2806)
∗1: Voltage measurement point
Outside unit PC board A2P
+5V
X17A
High pressure sensor
4 Red
GND 3 Black
Microcomputer 1 White
A/D input
180 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Malfunction When the low pressure sensor is short circuit or open circuit.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The low
pressure sensor is NO
connected to X18A (blue) of Connect low pressure sensor
outdoor unit PC board
(A1P). property and restart system.
YES
The
relationship
between the ∗1VL
and low pressure is
normal (see ∗2) when voltage YES
is measured between X18A Replace outdoor unit PC board
pins (2) and (3) of outdoor (A1P).
unit PC board (A1P)
(see ∗1).
NO
Replace the low pressure sensor.
(V2808)
X18A
Low pressure sensor
4 Red
GND 3 Black
Microcomputer 2 White
A/D input
1
Troubleshooting 181
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Method of Detect malfunctions by current value during waveform output before compressor startup.
Malfunction Detect malfunctions by current sensor value during synchronized operation at the time of
Detection startup.
Troubleshooting
182 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Malfunction When the temperature of the inverter radiation fin increases above 83°C.
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The radiator
fin temperature is YES
supposed to have risen to Faulty heat radiation of power unit
84°C or more. • Air suction opening blocked
• Dirty radiator fin
• High outdoor temperature
NO
Is the
connector X111A of the fin NO
thermistor properly connected to Properly connect.
the outdoor PC board?
YES
Turn ON the power supply,
and then press the remote
control check button once.
Is the
malfunction code "P4" YES
displayed on the remote To "P4" troubleshooting
control?
NO
Does the
malfunction code "L4" YES
recur when the unit starts Replace the inverter PC board
operation? assy (A2P) as well.
NO
Continue operation.
Troubleshooting 183
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Compressor inspection
The
compressor's coil is YES
disconnected or the Replace the compressor.
insulation is
defective.
NO
Disconnect the connection
between the compressor and
inverter. Make the power
transistor check mode setting
ON by service mode.
Inverter
output voltage
check Inverter output
voltage is not balanced. YES
(Normal if within ±5V Must Replace the inverter unit (A2P).
be measured when
frequency is
stable.
NO
Higher voltage than actual is displayed when the inverter output voltage is checked by tester.
184 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The
secondary current
of the inverter is higher YES
than 13.1A, 260 sec. for Compressor overload
each phase. Inspection of the compressor and
refrigerant system is required.
NO
Compressor
inspection The YES
compressor's coil is Replace the compressor.
disconnected.
NO
Disconnect the the connection
between the compressor and
inverter. Make the power
transistor check mode setting
ON by service mode.
Inverter
output voltage
check Inverter output
voltage is not balanced NO
(Normal if within ±5V). Must Replace the inverter PC board
be measured when assy (A2P).
frequency is stable.
YES
After turning on NO
again, "L8" blinks again. Reset and restart.
YES
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
compressor.
(V3184)
Troubleshooting 185
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The
difference between
high and low pressure NO
when starting is above Unsatisfactory pressure
0.2MPa. equalization
Check refrigerant system.
YES
Disconnect the connection
between the compressor and
inverter. Make the power
transistor check mode ON by
service mode.
Inverter
output voltage
check Inverter output
voltage is not balanced. NO
(Normal if within ±5V) Must Replace the inverter PC board
be measured when assy (A2P).
frequency is
stable.
YES
After turning on NO
again, "L9" blinks Reset and restart.
again.
YES
Compressor inspection
Inspect according to the diagnosis
procedure for odd noises, vibration
and operating status of the
(V2814)
186 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Method of Check the communication state between inverter PC board and control PC board by micro-
Malfunction computer.
Detection
Supposed Malfunction of connection between the inverter microcomputer and outdoor control
Causes microcomputer
Defect of outdoor unit PC board (A1P)
External factor (Noise etc.)
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Wa Are
s the inverter the inverter PC board
PC board or the control YES and the control PC board used in NO
Correct the combination following
PC board replaced? combination of types listed in Table 1, and then restart
Table 1? operation.
NO YES
Are the
connectors of
the inverter PC board NO
and the control PC board Connect a connecting wire, and
securely then restart operation.
connected?
YES
Are there
any broken wires
in the connectors of the YES
inverter PC board and the Repair the broken wires, and then
control PC board? restart operation.
NO
Replace the inverter PC board
(A2P) or the control PC board
(A1P).
Troubleshooting 187
Troubleshooting by Indication on the Remote Control SiENBE34-802
Applicable RXYSQ4~6PA
Models
Method of Malfunction is detected according to the voltage waveform of main circuit capacitor built in the
Malfunction inverter.
Detection
Malfunction When the aforementioned voltage waveform becomes identical with the waveform of the power
Decision supply open phase.
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Have the
power supply voltages NO
of three phases fallen within the Correct the power supply voltages.
range of rated voltage
±10%?
YES
Has the
imbalance of NO
phase-to-phase voltages Correct the power supply voltages.
fallen within
±10%?
YES
Replace the inverter PC board
assy (A2P).
188 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Method of Short of gas malfunction is detected by discharge pipe temperature thermistor and low pressure
Malfunction saturation temperature.
Detection
Troubleshooting 189
Troubleshooting by Indication on the Remote Control SiENBE34-802
Troubleshooting
The NO
suction pipe1 Replace low pressure sensor.
temp. minus low pressure YES
saturation temp. is 20 Out of gas or refrigerant
°C or higher. system is clogged. Requires
check of refrigerant system.
NO
Resistance
is normal when
measured with the
thermistor (R3T) for suction NO
pipe1 disconnected from Replace the thermistor.
the outdoor unit PC
board. ∗1
YES
Is
the low pressure NO
sensor correct? Replace the low pressure
sensor.
YES
Replace the outdoor unit PC
board (A1P).
(V2819)
X18A
Low pressure sensor
4 Red
GND 3 Black
Microcomputer 2 White
A/D input
1
190 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Method of Detection of voltage of main circuit capacitor built in the inverter and power supply voltage.
Malfunction
Detection
Malfunction When the abnormal voltage of main circuit capacitor built in the inverter and abnormal power
Decision supply voltage are detected.
Conditions
Troubleshooting 191
Troubleshooting by Indication on the Remote Control SiENBE34-802
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Have the
power supply
voltages between L1 and L2,
L2 and L3, and L1 and L3 fallen within NO
the range of 380 to 415V±10% (50 Hz) and Correct the power supply
between L and N within the range voltages.
of 220 to 240V±10% If L2 or Phase N is open,
(50 Hz)? replace the switch box.
YES
YES
Is the
measured voltage 220 YES Monitor the voltage
VDC or more? (Instantaneous voltage drop)
NO
Replace the inverter PC board
(A1P).
(S2605)
192 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Applicable RXYSQ4~6PA
Models
Malfunction Malfunction is decided when the unit starts operation without check operation.
Decision
Conditions
Troubleshooting
Has the
check operation NO
performed on Outdoor unit Press the BS4 on PC board on the
PC board? master outdoor unit for 5 seconds
or more to execute check
YES operation.
Troubleshooting 193
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of Microcomputer checks if transmission between indoor and outdoor units is normal.
Malfunction
Detection
Malfunction When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed Indoor to outdoor, outdoor to outdoor transmission wiring F1, F2 disconnection, short circuit
Causes or wrong wiring
Outdoor unit power supply is OFF
System address doesn’t match
Defect of outdoor unit PC board
Defect of indoor unit PC board
194 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Troubleshooting
Has
the indoor
or outdoor unit
PC board been
replaced, or has the indoor - YES
outdoor or outdoor - outdoor Push and hold the RESET
unit transmission button on the master outdoor
wiring been unit PC Board for 5 seconds.
modified? ∗ The unit will not operate
for up to 12 minutes.
NO
All Is
indoor unit indoor -
remote controllers NO outdoor and outdoor - YES
of the same refrigerant outdoor unit transmission Replace the indoor unit PC
system display wiring normal? board.
"U4."
NO Fix the indoor/outdoor unit
YES
transmission wiring.
Reset the power supply.
Are there
Outdoor unit any broken wires in
PC board microcomputer NO the connectors of the inverter NO
monitor (HAP) blinks. PC board (A1P) and the Repair the broken wires, and
control PC board then restart operation.
(A2P)?
YES
YES
The
voltage between
terminals L3 and N of the NO
outdoor unit PC board is Supply 220~240 V.
220~240 V.
YES
Has
either the fuse
F4U on the outdoor YES Check No. 3 ∗
unit PC board (A1P) or the Check for the fan motor
fuse F1U on the inverter connector.
PC board (A2P)
blown out?
Is
resistance NO Replace the fuse F4U and
NO between pins in excess of
judgment criteria? the inverter PC board (A2P).
Replace the fan motor.
NO Operation YES
ready lamp (H2P) is Replace the inverter PC
board.
blinking. Replace the fuse F4U.
YES Replace outdoor unit PC
board (A1P).
Lamp does not YES
go off for 12 minutes or Push and hold the RESET
more. button on the outdoor unit PC
NO board for 5 seconds.
Is
indoor -
outdoorand outdoor - NO
outdoor unit transmission Fix the indoor/outdoor unit
wiring normal? transmission wiring.
YES
Replace the outdoor unit PC
board (A1P).
(V3187)
Troubleshooting 195
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of In case of controlling with 2-remote control, check the system using microcomputer is signal
Malfunction transmission between indoor unit and remote control (main and sub) is normal.
Detection
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
All Operation
indoor PC board NO returns to normal NO
microcomputer monitors when the power is turned Replace indoor unit PC
blink. off momentarily. board.
YES YES
There is possibility of
malfunction caused by noise.
Check the surrounding area
Multi-core and turn on again.
cableis used for the YES
indoor unit remote control Switch to double-core
transmission wiring. independent cable.
replacement
NO
Defect of remote control PC
board or indoor unit PC board.
Replace whichever is
defective.
(V2823)
196 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Method of In case of controlling with 2-remote control, check the system using microcomputer if signal
Malfunction transmission between indoor unit and remote control (main and sub) is normal.
Detection
Troubleshooting
Troubleshooting 197
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
198 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
The "UA"
display blinks on
the remote controls of YES
other units within the same Refer to failure diagnosis for "UA"
refrigerant system. malfunction code.
NO
The "A1"
display blinks on
the remote controls of YES
other units within the same Refer to failure diagnosis for "A1"
refrigerant system. malfunction code.
NO
The
"A9" display
blinks on the remote YES
controls of other units within Refer to failure diagnosis for "A9"
the same refrigerant malfunction code.
system.
NO
The "U4"
display blinks on
the remote controls of YES
other units within the same Refer to failure diagnosis for "U4"
refrigerant system. malfunction code.
NO
Refer to failure diagnosis for "U5"
malfunction code.
(V2826)
Troubleshooting 199
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is the
outdoor PC board YES
replaced to spare parts PC The outdoor PC board replaced is
board? wrong, check PC board type.
NO
The
total of indoor
units displaying "UA"
and indoor units connected NO
to the same refrigerant system There are too many indoor units
is within connectable within the same refrigerant
number of unit∗ system.
YES
Push and hold the RESET
button on the outdoor unit
PC board for 5 seconds.
NO
Does a malfunction occur? Normal
YES
Does the
refrigerant type of indoor NO
Matches the refrigerant type of
and outdoor unit
match? indoor and outdoor unit.
YES
Replace outdoor unit PC board
(A1P).
(V3169)
∗ The number of indoor units that can be connected to a single outdoor unit system depends on
the type of outdoor unit.
200 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting
Optional
controls for
centralized control are YES
Address duplication of central
connected to the remote control
indoor unit. The setting must be changed so
that the central remote control
address is not duplicated.
NO
Replace indoor unit PC board.
(V2828)
Troubleshooting 201
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of Microcomputer checks if transmission between indoor unit and centralized remote control is
Malfunction normal.
Detection
Malfunction When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed Malfunction of transmission between optional controls for centralized control and indoor unit
Causes Connector for setting master controller is disconnected.
Failure of PC board for centralized remote control
Defect of indoor unit PC board
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has an
indoor unit once
connected been remove or its
YES
Reset power supply
address changed? simultaneously for all optional
controls for centralized control.
NO
Is
the power
supply turned on for NO
indoor units displaying Turn indoor unit's power
malfunction? supply.
YES
Is
transmission wiring NO
disconnected or wired Fix the wiring correctly.
incorrectly?
YES
Is Is
transmission with the group No.
NO of malfunctioning indoor NO
all indoor units Set the group No. correctly.
malfunctioning? units set?
YES YES
Replace indoor unit PC
board.
Is the
transmission
wiring with the master NO
controller disconnected or Fix the wiring correctly.
wired incorrectly?
YES
Is
the master
controller's NO
connector for setting Connect the connector
master controller correctly.
disconnected?
YES
Replace the central PC
board.
(V2829)
202 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Remote Control
Method of On check operation, the number of indoor units in terms of transmission is not corresponding to
Malfunction that of indoor units that have made changes in temperature.
Detection
Malfunction The malfunction is determined as soon as the abnormality aforementioned is detected through
Decision checking the system for any erroneous connection of units on the check operation.
Conditions
Supposed Improper connection of transmission wiring between indoor-outdoor units and outdoor-
Causes outdoor units
Failure to execute check operation
Defect of indoor unit PC board
Stop valve is left in closed
Troubleshooting
Are
the stop valves NO
openned? Open stop valve.
YES
Is
Is indoor
the check NO -outdoor and YES
operation carried out? outdoor-outdoor unit Replace indoor unit PC board.
transmission wiring
normal?
YES
Is NO
indoor -
outdoor and outdoor NO
- outdoor unit transmission After fixing incorrect wiring,
wiring normal? push and hold the RESET
button on the master outdoor
unit PC board for 5 seconds.
YES ∗ The unit will not run for up to
12 minutes.
Note: Wiring check operation may not be successful if carried out after the outdoor unit has been off
for more than 12 hours, or if it is not carried out after running all connected indoor units in the
fan mode for at least an hour.
Troubleshooting 203
Troubleshooting by Indication on the Remote Control SiENBE34-802
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed Improper connection of transmission wiring between outdoor unit and outdoor unit outside
Causes control adapter
Defect of indoor unit PC board
Defect of outdoor unit PC board (A1P)
Troubleshooting
Is Does a
electricity malfunction
being introduce for occur even after
the first time after YES 12 minutes elapses NO
installationor after an indoor from the time when electricity Normal
or outdoor unit PC is introduced to indoor
board has been and outdoor
replaced? units?
NO YES
Is
indoor -
outdoor and NO
outdoor - outdoor unit After fixing incorrect wiring,
transmission wiring push and hold the RESET
normal? button on the master outdoor
unit PC board for 5 seconds.
YES ∗ The unit will not run for up to
12 minutes.
After fixing incorrect wiring,
push and hold the RESET
button on the outdoor unit
PC board for 5 seconds
Does a NO
malfunction occur? Normal
YES
Does a
"UH" malfunction NO
occur for all indoor units Replace indoor unit PC board.
in the system?
YES
Replace outdoor unit PC
board (A1P).
(V2831)
204 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Centralized Remote Control
Method of Microcomputer checks if transmission between indoor unit and central remote control is normal.
Malfunction
Detection
Malfunction When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed Malfunction of transmission between optional controllers for centralized control and indoor unit
Causes Connector for setting master controller is disconnected.
Failure of PC board for central remote control
Defect of indoor unit PC board
Troubleshooting 205
Troubleshooting by Indication on the Centralized Remote Control SiENBE34-802
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has an
indoor unit once YES
connected been remove or its Reset power supply
address changed? simultaneously for all optional
controllers for centralized
NO control.
Is
the power
supply turned on for NO
indoor units displaying Turn indoor unit's power
malfunction? supply.
YES
Is
transmission
wiring disconnected or NO
Fix the wiring correctly.
wired incorrectly?
YES
Is Is
transmission the group No. NO
NO of malfunctioning indoor
with all indoor units Set the group No. correctly.
malfunctioning? units set?
YES YES
Is Replace indoor unit PC board.
the
transmission
wiring with the master NO
controller disconnected or Fix the wiring correctly.
wired incorrectly?
YES
Is
the master
controller's
connector for setting master NO
controller disconnected? Connect the connector
correctly.
YES
Replace the central PC board.
(V2832)
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
206 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Centralized Remote Control
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has a
once
connected optional
controller for centralized YES
control been disconnected
Reset power supply simultaneously
or its address for all optional controllers for
changed? centralized control.
NO
Is
the power
supply turned on
for all optional controllers NO
for centralized control? Turn on power supply for all
optional controllers for centralized
control.
YES
Is
the reset
switch of all
optional controllers for NO
centralized control set to Set reset switch to "normal."
''normal?''
YES
Is
transmission
wiring disconnected or YES
Fix the wiring correctly.
wired incorrectly?
NO
The PC board of one of the
optional controllers for centralized
control is defective. Try turning
on/off using each optional
controllers for centralized control,
and replace the PC board of the
one that is unable to control the
indoor unit.
(V2833)
Troubleshooting 207
Troubleshooting by Indication on the Centralized Remote Control SiENBE34-802
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
208 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Centralized Remote Control
Troubleshooting
Is Cannot be used in
the wiring combination with a wiring
adapter for electrical YES adapter for electrical
appendices connected? appendices. Remove the
wiring adapter for electrical
appendices and reset the
NO power supply for all optional
controllers for centralized
control simultaneously.
Are
there two or Arrange so that the
more optional connector for setting master
controllers for centralized YES control is connected to one
control connected with the controller for centralized
connector for setting control and reset the power
master supply for all optional
control? controllers for centralized
control simultaneously.
NO
Disconnect the connector for
setting master control from
Reset the power supply for the master controller,
all optional controllers for connect to another optional
centralized control controller for centralized
simultaneously. control and simultaneously
If the malfunction is still not cleared: reset all optional controllers
for centralized control again.
The controller connected by
the connector for setting
master control when the
malfunction is cleared is
defective and must be
replaced. (V2834)
Troubleshooting 209
Troubleshooting by Indication on the Centralized Remote Control SiENBE34-802
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Are two or
more centralized remote YES
controls connected? Disconnect all centralized
remote controls except one
and reset the power supply of
NO the centralized remote control.
210 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Unified ON/OFF Controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting 211
Troubleshooting by Indication on the Unified ON/OFF Controller SiENBE34-802
Troubleshooting
Is
a malfunction
code displayed on the YES
remote control? Diagnose the cause with the
air conditioner's failure
diagnosis manual.
NO
Has a once
connected indoor YES
unit been removed or its Reset power supply for all
address changed? optional controllers for
centralized control
simultaneously.
NO
Is the
power supply for
the indoor unit displaying NO
a malfunction turned on? Turn the power supply of the
indoor unit on.
YES
Is
transmission wiring YES
disconnected or wired Fix the wiring correctly.
incorrectly?
NO
Is Is
transmission the group No.
with all indoor units NO NO
of malfunctioning indoor Set the group No.
malfunctioning? units set? correctly.
YES YES
YES
Is the
master controller's YES
connector for setting master
controller disconnected. Connect the connector
correctly.
NO
Replace the central PC board.
(V2841)
212 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Unified ON/OFF Controller
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Troubleshooting 213
Troubleshooting by Indication on the Unified ON/OFF Controller SiENBE34-802
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Has a
once
connected optional
controller for centralized YES
control been disconnected Reset power supply
or its address simultaneously for all optional
changed? controllers for centralized
control.
NO
Is the
power supply
turned on for all NO
optional controllers for Turn on power supply for all
centralized optional controllers for
control? centralized control.
YES
Is the
reset switch of all
optional controllers for NO
centralized control set to Set reset switch to
"normal"? "normal."
YES
Is
transmission
wiring disconnected or YES
wired incorrectly? Fix the wiring correctly.
NO Is
Is the central
a central YES remote control or YES
remote control or schedule schedule timer displaying Refer to failure diagnosis for
timer connected? a malfunction? central remote control or
schedule timer.
NO
NO
Is the
setting of the
Are two or unified ON/OFF
more unified ON/OFF YES NO
controllers connected?
controller's switch for setting Correct the setting of the
each address unified ON / OFF controller's
duplicated? switch for setting each
NO address and reset the power
supply of the unified ON /
YES OFF controller.
A
(V2842)
214 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Unified ON/OFF Controller
Is
the wiring
adapter for electrical YES
appendices connected? Cannot be used in
combination with a wiring
adapter for electrical
NO appendices. Remove the
wiring adapter for electrical
appendices and reset the
power supply for all optional
controllers for centralized
Is a control simultaneously.
schedule timer YES Is a data station YES
connected? connected? Schedule timer and data
station cannot be used in
NO NO combination. Disconnect
either the schedule timer or
data station and reset the
power supply for all optional
controllers for centralized
Is a control simultaneously.
parallel interface YES
connected? Schedule timer and parallel
interface cannot be used in
combination. Disconnect
NO either the schedule timer or
parallel interface and reset the
power supply for all optional
controllers for centralized
Is the control simultaneously.
schedule timer's YES
individual/combined connector Disconnect the schedule
connected? timer's individual / combined
connector and reset the power
supply for all optional
NO controllers for centralized
control simultaneously.
Are
there two or
more optional
controllers for centralized YES
control connected with the Arrange so that the connector
connector for setting for setting master control is
master control? connected to one controller for
centralized control and reset
the power supply for all
NO optional controllers for
centralized control
Reset the power supply for simultaneously.
all optional controllers for
centralized control
simultaneously.
Troubleshooting 215
Troubleshooting by Indication on the Unified ON/OFF Controller SiENBE34-802
Method of
Malfunction
Detection
Malfunction
Decision
Conditions
Supposed Central control address (group No.) is not set for indoor unit.
Causes Improper address setting
Improper wiring of transmission wiring
Troubleshooting
Be sure to turn off power switch before connect or disconnect connector,
Caution or parts damage may be occurred.
Is
the central
control address NO
(group No.) Set by remote control the central
set for the control address for all indoor units
indoor unit? connected to the central control
line.
YES
Is
the switch
for setting each address NO
Set the switch for setting each
set correctly? address correctly and
simultaneously reset the power
YES supply for all optional controllers
Is for centralized control.
the
transmission YES
wiring disconnected or Fix the wiring correctly.
wired incorrectly?
NO
Replace the PC board of the
unified ON/OFF controller.
(V2844)
216 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Unified ON/OFF Controller
[In cooling] ←Is the suction air temperature not more than 46°C?
High suction air Short circuit
temperature of ←Is the outdoor temperature not more than 46°C?
High suction outdoor unit High ambient temperature
air
temperature
of the High suction Short circuit ←Is the suction air temperature not more than 27°C?
condenser air temperature
of indoor unit High ambient temperature ←Is the indoor temperature not more than 27°C?
Faulty suction air thermistor of indoor unit ←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
[In heating]
High suction air temperature of outdoor unit ←Is the outdoor temperature not more than 16°CWB?
Faulty outdoor temperature thermistor of outdoor unit ←Is the connector properly connected?
Are the thermistor resistance characteristics normal?
Degradation Dirty condenser ←Is the heat exchanger clogged? (In cooling)
in condensing
capacity
Mixing of non-condensable gas ←Is air or else mixed in the refrigerant system?
*1: In cooling, it is normal if the outdoor unit electronic expansion valve (EV1) is fully open.
*2: In heating, the indoor unit electronic expansion valve is used for “subcooled degree control”.
(For details, refer to “Electronic Expansion Valve Control” on P.72.)
C: SDK04009
Troubleshooting 217
Troubleshooting by Indication on the Unified ON/OFF Controller SiENBE34-802
[In cooling]
(See *1.) Faulty Faulty low pressure sensor ←Are the electrical characteristics normal?
Faulty low compressor ←Is the pressure value checked with the Service Checker
capacity Faulty control PCB
pressure corresponding to the measurement of the pressure sensor?
control control
Faulty low pressure sensor ←Are the electrical characteristics normal?
Faulty low
pressure
Faulty hot gas solenoid valve ←Are the coil resistance and insulation normal?
[In both cooling protection
and heating]
control ←Is the pressure value checked with the Service Checker
Faulty control PCB
(See *2.) corresponding to the measurement of the pressure sensor?
Abnormally low Faulty indoor
low-pressure [In cooling]
unit electronic Faulty valve coil ←Are the coil resistance and insulation normal?
(Low evaporating If the indoor unit expansion valve
temperature) electronic Faulty valve body
expansion valve is
throttled too much: Faulty gas pipe ←Check for the thermistor resistance and connection.
(See *3.) thermistor of indoor unit
Faulty
control
Faulty electronic Faulty liquid pipe thermistor ←Check for the thermistor resistance and connection.
expansion valve of indoor unit
control ←Is the pressure value checked with the Service Checker
Faulty control PCB
corresponding to the measurement of the pressure sensor?
Faulty outdoor Faulty valve coil ←Are the coil resistance and insulation
unit electronic normal?
expansion valve Faulty valve body
[In heating]
If the outdoor unit Faulty low pressure sensor ←Are the electrical characteristics normal?
electronic
expansion valve Faulty
Faulty suction pipe thermistor ←Check for the thermistor resistance and
excessively control
throttled: connection.
(See *4.) Faulty control PCB
[In cooling]
Low suction air Short circuit ←Is the suction air temperature not less than 14°C
temperature of
indoor unit Low ambient temperature ←Is the indoor temperature not less than 14°C
*1: For details of the compressor capacity control while in cooling, refer to “Compressor PI Control” on P.50.
*2: The “low pressure protection control” includes low pressure protection control and hot gas bypass control. For details, refer to P.61.
*3: In cooling, the indoor unit electronic expansion valve is used for “superheated degree control”. (For details, refer to P.72.)
*4: In heating, the outdoor unit electronic expansion valve (EV1) is used for “superheated degree control of outdoor unit heat exchanger”.
(For details, refer to P.51.)
C: SDK04009
218 Troubleshooting
SiENBE34-802 Troubleshooting by Indication on the Unified ON/OFF Controller
1 White
Measurement point Judgment
2 Orange 1-4 1MΩ or more
2-4 100kΩ or more
3 Brown
3-4 100Ω or more
GND 4-7 100kΩ or more
4 Blue
7 Red
Troubleshooting 219
Troubleshooting by Indication on the Unified ON/OFF Controller SiENBE34-802
220 Troubleshooting
SiENBE34-802
Part 8
Appendix
1. Piping Diagrams..................................................................................222
1.1 Outdoor Unit .........................................................................................222
1.2 Indoor Unit............................................................................................224
2. Wiring Diagrams..................................................................................227
2.1 Outdoor Unit .........................................................................................227
2.2 Field Wiring ..........................................................................................229
2.3 Indoor Unit............................................................................................231
3. Option List ...........................................................................................246
3.1 Option List of Controllers......................................................................246
3.2 Option List of Outdoor Unit...................................................................248
4. Example of Connection .......................................................................249
5. Thermistor Resistance / Temperature Characteristics........................251
6. Pressure Sensor .................................................................................253
7. Method of Replacing the Inverter’s Power Transistors Modules.........254
Appendix 221
222
1.1
Piping Diagrams
Electronic
expansion valve
Double pipe Electronic
heat exchanger expansion valve
Filter
RXYSQ4 / 5 / 6PA7Y1B
Heat exchanger
Pressure
Outdoor Unit
regulating valve
Four way
valve
High pressure
Servic port sensor
Low pressure
sensor
Filter
Capillary
tube
Solenoid
valve Capillary
Filter tube
Filter
Compressor
Capillary Solenoid
tube valve
High pressure
switch
Accumulator
Stop valve (With service port on field piping side Ø7.9 mm flare connection)
Appendix
SiENBE34-802
Appendix
SiENBE34-802
Heat exchanger
Pressure regulating valve
Four way
valve
Solenoid valve
Filter Capillary tube
Filter
Compressor
Capillary tube Solenoid valve
High pressure
switch
Accumulator
Stop valve (With service port on field piping side ø 7.9 mm flare connection)
C : 3D052712
223
Piping Diagrams
Piping Diagrams SiENBE34-802
Fan
(2)
(3)
(1)
Filter Electronic Filter
expansion valve
(mm)
Capacity GAS Liquid
20 / 25 / 32 / 40 / 50 φ12.7 φ6.4
63 / 80 / 100 / 125 φ15.9 φ9.5
224 Appendix
SiENBE34-802 Piping Diagrams
FXDQ
Gas side
Liquid side
Electronic
expansion valve
Filter Filter
Fan
4D043864H
Appendix 225
Piping Diagrams SiENBE34-802
FXUQ + BEVQ
Indoor Unit
Filter
Field piping Ø9.5 C1220T-0
To outdoor
Field piping Ø15.9 C1220T-0 unit
Indoor unit
4D037995F
Connection Unit
Electronic
Liquid piping expansion valve Liquid piping
connection port Filter Filter connection port
4D034127B
226 Appendix
2.1
Appendix
L1-RED L2-WHT L3-BLK N-BLU
A1P Printed circuit board (Main)
SiENBE34-802
3N ~ Note 4
380-415V F1,3,4U(A1P) Fuse(T6.3A 250V)
50Hz H1P~8P Pilot Lamp (service monitor orange)
[H2P] Prepare, Test --- Flickering
Malfunction detection - light up
HAP (A1P) Operation pilot lamp
Outdoor Unit
227
228
Wiring Diagrams
Appendix
SiENBE34-802
2.2
Appendix
SiENBE34-802
Power supply Notes 1. All wiring, components and materials to be procured on the site must be 6. Unit shall be grounded in compliance with the applicable local and national codes.
comply with the applicable local and national codes. 7. Wiring shown are general points-of-connection guides only and are not intended for or to include all details
2. Use copper conductors only. for a specific installation.
Main switch 3. As for details, see wiring diagram. 8. Be sure to install the switch and the fuse to the power line of each equipment.
4. Instal circuit breaker for safety. 9. Install the main switch that can interrupt all the power sources in an integrated manner because this system
5. All field wiring and components must be provided by licensed electrician. consists of the equipment utilizing the multiple power sources.
RXYSQ4 / 5 / 6PA7Y1B
10.If ther exists the possibility of reversed phase, lose phase, momentary blackout or the power goes on and off
while the product is operating, attach a reversed phase protection circuit locally.
OUTDOOR UNITS Running the product in reversed phase may break the compressor and other parts.
Field Wiring
Switch
Fuse
Power supply
Main
switch
2 wires cable
(Transmission line) 2 wires cable 2 wires cable 2 wires cable
(Transmission line) (Transmission line) (Transmission line)
2 wires cable
(Power line)
INDOOR UNITS
3D057919
Wiring Diagrams
229
230
Power supply Notes 1. All wiring, components and materials to be procured on the site must be 6. Unit shall be grounded in compliance with the applicable local and national codes.
comply with the applicable local and national codes. 7. Wiring shown are general points-of-connection guides only and are not intended for or to include all details
Wiring Diagrams
OUTDOOR UNIT
Switch
Fuse
2 wires cable
(Transmission line) 2 wires cable 2 wires cable 2 wires cable
(Transmission line) (Transmission line) (Transmission line)
INDOOR UNITS
3D052597
Appendix
SiENBE34-802
SiENBE34-802 Wiring Diagrams
indoor
Switch box
Wired remote
control
(Note 2)
33H Float switch R2T, R3T Thermistor (Coil) H1P Light emitting diode (On-Red)
33S Limit switch (swing flap) Q2E Earth leak detector H2P Light emitting diode (Timer-Green)
A1P Printed circuit board RyA Magnetic relay (M1S) H3P Light emitting diode (Filter sign-Red)
C1R Capacitor (M1F) RyF1-3 Magnetic relay (M1F) H4P Light emitting diode (Defrost-Orange)
F1T Thermal fuse (152°C) (M1F embedded) RyP Magnetic relay (M1P) SS1 Selector switch (Main/Sub)
F1U Fuse (250V, 5A) T1R Transformer (220-240V/22V) SS2 Selector switch (Wireless adress set)
F2U Field fuse X1M Terminal strip (Power) Connector for optional parts
HAP Light emitting diode X2M Terminal strip (Control) X18A Connector
(Service monitor-Green) Y1E Electronic expansion valve (Wiring, adapter for electrical appendices)
M1F Motor (Indoor fan) Receiver/Display unit X23A Connector (infrared remote control)
M1S Motor (Swing flap) (Attached to infrared remote control)
M1P Motor (Drain pump) A2P, A3P Printed circuit board
R1T Thermistor (Air) BS ON/OFF button
Notes
1. When using a central remote control, see manual for connection to the unit.
2. X23A is connected when the Infrared remote control kit is used.
3. When connecting the input wires from the outdoor unit, “forced off” or “on/off” operation can be selected by the remote control.
For more details see installation manual.
4. Use copper conductors only.
2TW23776-1D
Appendix 231
Wiring Diagrams SiENBE34-802
indoor
Switch box
Wired remote
control
(Note 2)
33H Float switch R2T, R3T Thermistor (Coil) H1P Light emitting diode (On-Red)
33S Limit switch (swing flap) Q2E Earth leak detector H2P Light emitting diode (Timer-Green)
A1P Printed circuit board RyA Magnetic relay (M1S) H3P Light emitting diode (Filter sign-Red)
C1R Capacitor (M1F) RyF1-3 Magnetic relay (M1F) H4P Light emitting diode (Defrost-Orange)
F1T Thermal fuse (152°C) (M1F embedded) RyP Magnetic relay (M1P) SS1 Selector switch (Main/Sub)
F1U Fuse (250V, 5A) T1R Transformer (220-240V/22V) SS2 Selector switch (Wireless adress set)
F2U Field fuse X1M Terminal strip (Power) Connector for optional parts
HAP Light emitting diode X2M Terminal strip (Control) X18A Connector
(Service monitor-Green) Y1E Electronic expansion valve (Wiring, adapter for electrical appendices)
M1F Motor (Indoor fan) Receiver/Display unit X23A Connector (infrared remote control)
M1S Motor (Swing flap) (Attached to infrared remote control)
M1P Motor (Drain pump) A2P, A3P Printed circuit board
R1T Thermistor (Air) BS ON/OFF button
Notes
1. When using a central remote control, see manual for connection to the unit.
2. X23A is connected when the infrared remote control kit is used.
3. When connecting the input wires from the outdoor unit, “forced off” or “on/off” operation can be selected by the remote control.
For more details see installation manual.
4. Use copper conductors only.
2TW23806-1D
232 Appendix
SiENBE34-802 Wiring Diagrams
Receiver/display unit
Control Box Input from outside
220~240/220V (note 4)
~50/60Hz To central remote
control (note 2)
Wired remote
control
20~63-Class 80~125-Class
(22~71 Class) (90~140 Class)
Indoor unit M1S Motor (Swing flap) Reciever/display unit (Attached to SS2 Selector switch
A1P Printed circuit board PS Power supply circuit infrared remote control) (Wireless adress set)
A2P Printed circuit board Q1DI Earth leak detector A3P Printed circuit board Connector for optional parts
C1 Capacitor R1T Thermistor (Air) A4P Printed circuit board X24A Connector
F1U Fuse (T, 5A, 250V) R2T Thermistor (Coil) BS1 Push button (on/off) (infrared remote control)
F2U Field Fuse R3T Thermistor (Header) H1P Light emitting diode (on-red) X33A Connector (adapter for wiring)
HAP Light emitting diode S1L Float switch H2P Light emitting diode (timer-green) X35A Connector (group control adapter)
(Service monitor green) X1M Terminal strip H3P Light emitting diode (filter sign-red) Wired remote control
KPR Magnetic relay (M1P) X2M Terminal strip H4P Light emitting diode R1T Thermistor (air)
L1 Coil Y1E Electronic expansion valve (defrost-orange) SS1 Selector switch (main/sub)
M1F Motor (Indoor fan) Z1C Ferrite core SS1 Selector switch (main/sub)
M1P Motor (Drain pump)
Notes:
1. Terminal Connector Field wiring
2. In case of using a central remote control, connect it to the unit in accordance with the attached installation manual.
3. X24A, X33A and X35A are connected when the optional accessories are being used.
4. When connecting the input wires from outside, forced off or on/off control operation can be selected by the remote control
5. Confirm the method of setting the selector switch (SS1,SS2) by installation manual end engineering data, etc.
6. Colour legend: RED : Red BLK : Black WHT : White YLW : Yellow GRN : Green
ORG : Orange BRN : Brown GRY : Grey BLU : Blue PNK : Pink
3TW28836-1B
Appendix 233
Wiring Diagrams SiENBE34-802
Power supply
220~240V Input from outside (see note 4)
~ See Transmission wiring central
50Hz note 3
remote control (see note 2)
Wired remote
control
Switch Box
See note 3
Indoor unit Q1M Thermal protector Wired remote control SS1 Selector switch (main/sub)
A1P Printed circuit board (M1F embedded) R1T Thermistor (air) SS2 Selector switch
C1 Capacitor R1T Thermistor (Air) SS1 Selector switch (Main/sub) (Wireless adress set)
F1U Fuse (B, 5A, 250V) R2T Thermistor (Coil-liquid) Wireless remote control Connector for optional parts
F2U Field Fuse R3T Thermistor (Coil-gas) (Reciever/display unit) X16A Connector (adapter for wire)
HAP Light emitting diode S1L Float switch A3P Printed circuit board X18A Connector (on/off)
(Service monitor green) T1R Transformer (220-240V/22V) A4P Printed circuit board (Wiring adapter for electrical
KPR Magnetic relay (M1P) V1TR Triac BS1 Push button (on/off) appendices)
M1F Motor (Indoor fan) X1M Terminal strip H1P Light emitting diode (on-red)
M1P Motor (Drain pump) X2M Terminal strip H2P Light emitting diode (timer-green)
M1S Motor (Swing flap) Y1E Electronic expansion valve H3P Light emitting diode (filter sign-red)
Q1DI Earth leak detector (Max. 300mA) H4P Light emitting diode (defrost-orange)
Notes:
1. In case of using a remote control, connect it to the unit in accordance with the attached installation manual.
2. X23A is connected when the wireless remote control is being used.
3. When connecting the input wires from outside, forced off or on/off control operation can be selected by the remote control
4. Remote control model varies according to the combination system.
See technical data and catalogs, etc. before connecting
3TW28826-1B
234 Appendix
Appendix
SiENBE34-802
Notes
1. Terminal block Connector Terminal
Wired remote control
2. Field wiring (Optional accessory)
3. In case using central remote control, connect it to the unit in accordance with the
attached instruction manual.
4. When connecting the input wires from outside, forced off or on/off control operation can
be selected by remote control.
In details, refer to the installation manual attached the unit.
5. In case high ESP operation, change over the wiring connection from X2A to X3A.
6. Symbols show as follows
PNK : Pink WHT : White YLW : Yellow ORG : Orange BLU : Blue
BLK : Black RED : Red BRN : Brown GRY : Grey
7. Use copper conductors only.
3D039564C-1
Wiring Diagrams
235
236
A1P Printed circuit board
C1 Capacitor (M1F)
F1U Fuse (F5A/250V)
HAP Light emitting diode
Wiring Diagrams
Notes:
1. Terminal
Connector Control box
2. Field wiring
3. In case of using a central remote control, connect it to the unit in accordance with the attached installation manual.
4. Remote control model varies according to the combination system, confirm engineering materials and catalogs, etc. before connecting.
5. When connecting the input wires from outside, forced off or on/off control operation can be selected by the remote control.
In details, refer to the installation manual attached the unit.
6. Colour legend: RED : Red BLK : Black WHT : White YLW : Yellow PRP : Purple
GRY : Grey BLU : Blue PNK : Pink ORG : Orange GRN : Green
3D045500C
Appendix
SiENBE34-802
Appendix
SiENBE34-802
FXDQ20M8 / 25M8V3
A1P Printed circuit board RyF1-3 Magnetic relay (Fan) Adapter for wiring X1M Terminal strip
C1R Capacitor (Fan) T1R Transformer RyC,RyF Magnetic relay Connector for optional parts
F1U Fuse (250V, 10A) (220-240V/22V) RyH Magnetic relay (J1EH) X16A Connector (wiring adapter)
F2U Field Fuse X1M Terminal strip (Power) F1U,F2U Fuse (250V,5A) X18A Connector (wiring adapter for
HAP Light emitting diode X2M Terminal strip (Control) X1A,X2A Connector (wiring adapter) electrical appendices)
(Service monitor green) Y1E Electronic expansion valve
M1F Motor (Fan) Compressor
Q1E Earth leak detector Optional parts operation
R1T Thermistor (Air) J1EH Electric heater 1N~50Hz indoor
Fan
indicator
230V operation
Adaptor for wiring
237
Wiring Diagrams SiENBE34-802
operation indicator
20~63 class compressor
Terminals for
(22~71 class) operation
indoor fan
operation
Switch box
Note 5 input
from outside
Colors BLK : Black Central remote
BLU : Blue control note 2
BRN : Brown
GRY : Grey
Wired
ORG : Orange remote
PNK : Pink control
RED : Red Note 3
WHT : White Seperate power supply
YLW : Yellow 1N~50Hz 230V
Low ESP operation
Field wiring
L Live
N Neutral
Connector High ESP operation
Wire clamp
Protective earth (screw) 20~32 class 40~63 class
(22~36 class) (45~71 class)
Note 4
33H Float switch R1T Thermistor (Air) K1R Magnetic relay (J1EH)
A1P Printed circuit board R2T, R3T Thermistor (Refrigerant) Adapter for wiring
A2P Terminal board RyF1-3 Magnetic relay (Fan) RyC,RyF Magnetic relay
C1R Capacitor (Fan) RyP Magnetic relay (Drain pump) RyH Magnetic relay (J1EH)
F1U Fuse (250V, 5A) T1R Transformer (220-240V/22V) F1U, F2U Fuse (250V, 5A)
F2U Field fuse X1M Terminal strip (Power) X1A,X2A Connector (wiring adapter)
HAP Light emitting diode X2M Terminal strip (Control) X1M Terminal strip
(Service monitor-Green) Y1E Electronic expansion valve Connector for optional parts
M1F Motor (Indoor fan) Optional parts X16A Connector (Wiring adapter)
M1P Motor (Drain pump) F3-5U Fuse (250, 16A) X18A Connector
Q2E Earth leak detector J1EH Electric heater (Wiring adapter for electrical appendices)
Notes
1. Use copper conductors only.
2. When using a central remote control, see manual for connection to the unit.
3. When installing the electric heater change the wiring for the heater circuit. The main power supply has to be supplied independently.
4. For High or Low ESP operation, change the wiring connection of X4A as shown on the wiring diagram.
5. When connecting the input wires from the outdoor unit, “forced off” or “on/off” operation can be selected by the remote control.
For more details see installation manual.
2TW23686-1C
238 Appendix
SiENBE34-802 Wiring Diagrams
operation indicator
(90,112,140 class)
compressor
Terminals for
operation
indoor fan
operation
Switch box
Note 5 input
Colors BLK : Black from outside
BLU : Blue Central remote
BRN : Brown control note 2
GRY : Grey
ORG : Orange
Wired
PNK : Pink remote
RED : Red control
WHT : White
YLW : Yellow Note 3
Seperate power supply
1N~50Hz 230V
Field wiring
L Live
Note 4
N Neutral High ESP operation
Connector
Wire clamp
Protective earth (screw)
33H Float switch R1T Thermistor (Air) K1R Magnetic relay (J1EH)
A1P Printed circuit board R2T, R3T Thermistor (Refrigerant) Adapter for wiring
A2P Terminal board RyF1-3 Magnetic relay (Fan) RyC,RyF Magnetic relay
C1R Capacitor (Fan) RyP Magnetic relay (Drain pump) RyH Magnetic relay (J1EH)
F1U Fuse (250V, 10A) T1R Transformer (220V/27V) F1U, F2U Fuse (250V, 5A)
F2U Field fuse X1M Terminal strip (Power) X1A,X2A Connector (wiring adapter)
HAP Light emitting diode X2M Terminal strip (Control) X1M Terminal strip
(Service monitor-Green) Y1E Electronic expansion valve Connector for optional parts
M1F Motor (Fan) Optional parts X16A Connector (Wiring adapter)
M1P Motor (Drain pump) F3-5U Fuse (250V, 16A) X18A Connector
Q2E Earth leak detector J1EH Electric heater (Wiring, adapter for electrical appendices)
Notes
1. Use copper conductors only.
2. When using a central remote control, see manual for connection to the unit.
3. When installing the electric heater change the wiring for the heater circuit. The main power supply has to be supplied independently.
4. For High ESP operation, change the wiring connection of X4A as shown on the wiring diagram.
5. When connecting the input wires from the outdoor unit, “forced off” or “on/off” operation can be selected by the remote control.
For more details see installation manual.
2TW23636-1C
Appendix 239
240
R1T R2T R3T R4T
M1P M
~ S1L
Z2C t° t° t° t°
POWER A1P
Wiring Diagrams
SUPPLY
N=1
F1U X16A X18A X17A X13A X15A
KPR
L L X25A
K1R + C1 MS R1
Z1F 3~ F4U
- RED
F2U
X10A K1R + C1 Z2C
R2 M1F L1P
Z1F X28A
V1R V2R 5 BLU -
MS A
3~ 3
X10A A X35A
V1R R2 A2P P
HAP GRN 1
* P
PS PS Z
X2A HAP X8A 1 X33A
C X1M X2M
3D058783
Appendix
SiENBE34-802
Appendix
SiENBE34-802
3D039801D
Wiring Diagrams
241
242
INDOOR UNIT A2P A3P
Wiring Diagrams
MS MSW M
CONTROL BOX 3~ 5. WHEN CONNECTING THE INPUT WIRES FROM
A2P PRINTED CIRCUIT BOARD
M1S Y1E
PRINTED CIRCUIT BOARD (INDOOR UNIT) M1F OUTSIDE, FORCED OFF OR ON/OFF CONTROL
A3P
NOTES OPERATION CAN BE SELECTED BY REMOTE CONTROL
BS1 PUSH BUTTON (ON/OFF)
1. : TERMINAL : CONNECTOR IN DETAILS, REFER TO THE INSTALLATION MANUAL
H1P LIGHT EMITTING DIODE (ON-RED)
: FIELD WIRING : CONNECTOR ATTACHED THE UNIT.
H2P LIGHT EMITTING DIODE 2. IN CASE USING CENTRAL REMOTE CONTROL, CONNECT IT TO THE UNIT 6. REMOTE CONTROL MODEL VARIES ACCORDING TO
(TIMER-GREEN)
IN ACCORDANCEWITH THE ATTACHED INSTALLATION MANUAL. THE COMBINATION SYSTEM, CONFIRM ENGINEERING
H3P LIGHT EMITTING DIODE 3. SYMBOLS SHOWS AS FOLLOWS: RED : RED WHT : WHITE GRN : GREEN DATA AND CATALOGS, ETC. BEFORE CONNECTING.
(FILTER SIGN-RED) PNK : PINK YLW : YELLOW BLK : BLACK ORG : ORANGE 7. CONFIRM THE METHOD OF SETTING THE SELECTOR
H4P LIGHT EMITTING DIODE BRN : BROWN BLU : BLUE SWITCH (SS1, SS2) OF WIRED REMOTE CONTROL AND
(DEFROST-ORENGE) 4. SHOWS SHORT CIRCUIT CONNECTOR. INFRARED REMOTE CONTROL BY INSTALLATION
MANUAL AND ENGINEERING DATA, ETC.
SS1 SELECTOR SWITCH (MAIN/SUB) WIRED REMOTE CONTROLLER CONNECTOR FOR OPTIONAL PARTS
8. X24A IS CONNECTED WHEN THE INFRARED REMOTE
SS2 SELECTOR SWITCH R1T THERMISTOR (AIR) X15A CONNECTOR (FLOAT SWITCH)
CONTROL KIT IS BEING USED.
(WIRELESS ADDRESS SET) SS1 SELECTOR SWITCH (MAIN/SUB) X35A CONNECTOR (GROUP CONTROL ADAPTER)
3D034206D
Appendix
SiENBE34-802
Appendix
SiENBE34-802
Note 4
Input from outside
Notes Note 3
Transmission wiring
1. Terminal block Connector Terminal central remote control
2. Field wiring
3. In case using central remote control, connect it to the unit in accordance
with the attached instruction manual.
4. When connecting the input wires from outside, forced off or on/off control
operation can be selected by remote control.
In details, refer to the installation manual attached the unit.
5. Symbols show as follows
PNK : Pink WHT : White YLW : Yellow ORG : Orange
Wired remote control Control box
BLU : Blue BLK : Black RED : Red BRN : Brown
(Optional accessory)
6. Use copper conductors only.
3D039826D
Wiring Diagrams
243
244
Wiring Diagrams
Notes
1. Terminal block Connector
2. Field wiring Control box
3. The BEV unit shows an outline, please refer to a wiring diagram of BEV unit pasting in detail.
4. In case using central remote control, connect it to the unit in accordance with the attached instruction manual.
5. X24A is connected when the infrared remote control kit is being used.
6. Remote control model varies according to the combination system.
Confirm engineering materials and catalogs, etc. before connecting.
7. Confirm the method of setting th selector switch (SS1,SS2) of wired remote control and infrared remote control by installation manual and engineering data, etc.
8. Symbols show as follows
RED : Red BLK : Black WHT : White YLW : Yellow GRN : Green BLU : Blue
3D044973A
Appendix
SiENBE34-802
SiENBE34-802 Wiring Diagrams
Control box
To outdoor unit
Notes
1. Terminal Connector
2. Field wiring
3. This wiring diagram only shows the BEV unit.
See the wiring diagrams and installation manuals for the wiring and settings for the indoor, outdoor and BS units.
4. See the indoor unit’s wiring diagram when installing optional parts for the indoor unit.
5. Only one indoor unit may be connected to the BEV unit.
See the indoor unit’s wiring diagram for when connecting the remote control.
6. Always use de sky air connection adapter for the indoor unit when using a central control unit.
Refer to the manual attached the unit when connecting.
7. Cool/heat changeover of indoor units connected to BEV unit cannot be carried out unless they are conencted to BS unit.
In case of a system with BEV unit only, cool/heat selector is required.
8. Set the SS1 to “M” only for the BEV unit connected to the indoor unit which is to have cool/heat switching capability, when
connecting the BS unit.
The ‘M/S” on the SS1 stands for “Main/Sub”. This is set to “S” when shipped from the factory.
9. Connect the attached thermistor to the R3T.
10. Symbols show as follows
3D044901B
Appendix 245
Option List SiENBE34-802
3. Option List
3.1 Option List of Controllers
Operation Control System Optional Accessories
Type FXDQ-
No. Item FXFQ FXZQ FXCQ FXKQ FXDQ M8 FXSQ FXMQ FXUQ FXHQ FXAQ FXLQ FXNQ
1 Wired remote control BRC1D52
Infrared remote cooling only BRC7F533 BRC7E531 BRC7C67 BRC4C63 BRC4C64 BRC4C66 BRC7C529 BRC7E66 BRC7E619 BRC4C64
2
control heat pump BRC7F532 BRC7E530 BRC7C62 BRC4C61 BRC4C62 BRC4C65 BRC7C528 BRC7E63 BRC7E618 BRC4C62
3 Simplified remote control — BRC2C51 — BRC2C51
Simplified remote control for hotel
4 — BRC3A61 — BRC3A61
use
5 Centralised remote control DCS302C51
6 Unified ON/OFF control DCS301B51
7 Schedule timer DST301B51
8 Wiring adapter — KRP1B57*1 — KRP1B61 KRP1B61 KRP1B56 — KRP1C64 KRP4A53 KRP1B3 — KRP1B61
9 Wiring adapter (hour meter) EKRP1C11*1 — EKRP1B2 — EKRP1B2*2 — EKRP1B2 — —
Wiring adapter for electrical
10 appendices (1) KRP2A526*1 KRP2A516*1 KRP2A61 KRP2A516 KRP2A53 KRP2A516 KRP2A61 KRP2A62* KRP2A51
11 Wiring
adapter for electrical KRP4AA53*1 KRP4A536*1 KRP4A516*1 KRP4A51 KRP4A516 KRP4A54 KRP4A516 KRP4A51 KRP4A52* KRP4A51
appendices (2)
12 Remote sensor KRCS01-4 KRCS01-1B
13 Installation box for adapter PCB KRP1H98 KRP1BA101 KRP1B96*3/4 — KRP1BA101 — KRP1B97 KRP1C93*3 KRP4A93*3/4 —
Electrical box with earth terminal
14 (3 blocks) — KJB311A
17 External control adapter — DTA104A52 DTA104A51*1 DTA104A61 DTA104A53 DTA104A51 DTA104A61 DTA104A62 DTA104A51 DTA104A61
18 Interface adapter for SkyAir series — DTA102A52 —
19 Connector for forced on/forced off — EKRORO —
Note:
1. Installation box is required
2. Fixingbox is KRP1A90
3. Up to 2 adapters can be fixed per installation box
4. Only 1 installation box can be installed per indoor unit
Various PC Boards
No. Part name Model No. Function
KRP1B56
KRP1B57
1 Adapter for wiring KRP1B61 PC board when equipped with auxiliary electric heater in the indoor unit.
KRP1B3
KRP4A53
Up to 1,024 units can be centrally controlled in 64 different groups.
2 DIII-NET Expander Adapter DTA109A51 Wiring restrictions (max. length: 1,000 m, total wiring length: 2,000 m, max. number of
branches: 16) apply to each adapter.
System Configuration
No. Part name Model No. Function
• Up to 16 groups of indoor units (128 units) can be easily controlled using the large LCD
Note2
1 Residential central remote control DCS303A51
panel. ON/OFF, temperature setting and scheduling can be controlled individually for
indoor units.
2 Central remote control DCS302C51 • Up to 64 groups of indoor units(128 units) can be connected, and ON/OFF, temperature
setting and monitoring can be accomplished individually or simultaneously. Connectable up
Electrical box with earth terminal to 2 controllers in one system.
2-1 KJB311A
(3 blocks)
3 Unified ON/OFF controller DCS301B51
Electrical box with earth terminal • Up to 16 groups of indoor units(128 units) can be turned, ON/OFF individually or
3-1 KJB212A(A) simultaneously, and operation and malfunction can be displayed. Can be used in
(2 blocks)
combination with up to 8 controllers.
3-2 Noise filter (for electromagnetic KEK26-1A
interface use only)
• Programmed time weekly schedule can be controlled by unified control for up to 64 groups
4 Schedule timer DST301B51
of indoor units (128 units). Can turn units ON/OFF twice per day.
• Adapters required to connect products other than those of the VRV System to the high-
R-407C/R-22 HDTA102A52 speed DIII-NET communication system adopted for the VRV System.
Interface adapter
5
for SkyAir-series * To use any of the above optional controllers, an appropriate adapter must be installed on
R-410A HDTA112B51
the product unit to be controlled.
• Up to 1024 units can be centrally controlled in 64 different groups.
DIII -NET • Wiring restrictions (max. lengh : 1,000m, total wiring lengh : 2,000m, max. number of
6 DTA109A51
Expander Adapter branches : 16)
apply to each adapter.
6-1 Mounting plate KRP4A92 • Fixing plate for DTA109A51
Note:
1. Installation box for H adapter must be procured on site.
2. For residential use only. Cannot be used with other centralized control equipment.
246 Appendix
SiENBE34-802 Option List
2-2 Option Software Web DAM004A51 • Monitors and controls the air conditioning system using the Internet
and a Web browser application on a PC.
2-3 Eco DAM003A51 • ECO (Energy saving functions.)
2-4 Optional DIII Ai unit DAM101A51 • External temperature sensor for intelligent Manager III.
2-5 Di unit DEC101A51 • 8 pairs based on a pair of On/Off input and abnormality input.
2-6 Dio unit DEC102A51 • 4 pairs based on a pair of On/Off input and abnormality input.
• Interface unit to allow communications between VRV and BMS.
3 *1 Interface for use in BACnet® DMS502B51 Operation and monitoring of air-conditioning systems through
Communication line
BACnet® communication.
• Expansion kit, installed on DMS502B51, to provide 2 more DIII-NET
3-1 Optional DIII board DAM411B51 communication ports. Not usable independently.
3-2 Optional Di board DAM412B51 • Expansion kit, installed on DMS502B51, to provide 16 more
wattmeter pulse input points. Not usable independently.
• Interface unit to allow communications between VRV and BMS.
4 *2 Interface for use in LONWORKS® DMS504B51 Operation and monitoring of air-conditioning systems through
LONWORKS® communication.
Parallel interface • Enables ON/OFF command, operation and display of malfunction;
5 Basic unit DPF201A51 can be used in combination with up to 4 units.
[
Contact/analog
Temperature
6 DPF201A52 • Enables temperature measurement output for 4 groups; 0-5VDC.
signal
measurement units
Temperature
7 DPF201A53 • Enables temperature setting input for 16 groups; 0-5VDC.
setting units
Unification adapter for • Interface between the central monitoring board and central control
8 computerized control HDCS302A52 units.
Notes:
H
1. BACnet® is a registered trademark of American Society of Heating, Refrigerating and Air-
Conditioning Engineers (ASHRAE).
H
2. LONWORKS®‚ is a registered trade mark of Echelon Corporation.
H
3. Installation box for H adapter must be procured on site.
Appendix 247
Option List SiENBE34-802
248 Appendix
Appendix
Example of connection Branch with refnet joint Branch with refnet joint and refnet header Branch with refnet header
(Connection of 8 indoor units Heat pump system)
SiENBE34-802
indoor unit
i
a a
refnet joint A B
a b c d e f g k
H1 b j
A B C D E F G H1 H1
refnet header p 7 8
h i j k l m n H2 b c d e f g h i
c d e f g h
1 2 3 4 5 6 7 H2 1 2 3 4 5 6 7 H2
1 2 3 4 5 6
8 8
Pipe size selection A. Piping between outdoor unit and refrigerant branch kit B. Piping between refrigerant branch kits C. Piping between refrigerant branch kit and indoor unit
Caution on selecting connection pipes • Match to the size of the connection piping on the outdoor unit. • Use the pipe size from the following table. • Pipe size for direct connection to indoor unit must be the same as the
If the overall equivalent piping length is ≤90 m, be sure to connection size of indoor unit.
Outdoor unit connection piping size Piping size (outer diameter x minimum thickness)
enlarge the pipe diameter of the gas-side main piping. If the Piping size
recommended pipe size is not available, stick to the original Gas pipe Liquid pipe
Piping size (outer diameter x minimum Indoor capacity (outer diameter x minimum thickness)
pipe diameter (which may result in a small capacity decrease). Ø15.9x1.0 Ø9.5x0.8
Outdoor unit thickness) index Gas pipe Liquid pipe
[Gas side]
capacity type Gas pipe Liquid pipe 20+25+32+40+50 Ø12.7x0.8 Ø6.4x0.8
RXYSQ4+5: Ø15.9→Ø19.1
RXYSQ6: Ø19.1→Ø22.2 RXYSQ4+5 Ø15.9x1.0 63+80+100+125 Ø15.9x1.0 Ø9.5x0.8
(Ø19.1x1.0)
Ø9.5x0.8
Main pipe First refrigerant RXYSQ6 Ø19.1x1.0
(enlarge) branch kit (Ø22.2x1.0)
Indoor
unit
How to calculate the additional refrigerant to be charged Example for refrigerant branch using refnet joint and refnet header
Additional refrigerant to be charged R (kg) Total length (m) of liquid Total length (m) of liquid
R should be rounded off in units of 0.1 kg R= x0.054+ x0.022 a: Ø9.5x30 m d: Ø9.5x13 m g: Ø6.4x10 m j: Ø6.4x10 m
( piping size at Ø9.5 ) ( piping size at Ø6.4 ) b: Ø9.5x10 m e: Ø6.4x10 m h: Ø6.4x20 m k: Ø6.4x9 m
c: Ø9.5x10 m f: Ø6.4x10 m i: Ø9.5x10 m
249
Example of connection
Example of connection SiENBE34-802
250 Appendix
SiENBE34-802 Thermistor Resistance / Temperature Characteristics
Appendix 251
Thermistor Resistance / Temperature Characteristics SiENBE34-802
Outdoor Unit
Thermistors for
Discharge Pipe
(R2T)
(kΩ)
T°C 0.0 0.5 T°C 0.0 0.5 T°C 0.0 0.5
0 640.44 624.65 50 72.32 70.96 100 13.35 13.15
1 609.31 594.43 51 69.64 68.34 101 12.95 12.76
2 579.96 565.78 52 67.06 65.82 102 12.57 12.38
3 552.00 538.63 53 64.60 63.41 103 12.20 12.01
4 525.63 512.97 54 62.24 61.09 104 11.84 11.66
5 500.66 488.67 55 59.97 58.87 105 11.49 11.32
6 477.01 465.65 56 57.80 56.75 106 11.15 10.99
7 454.60 443.84 57 55.72 54.70 107 10.83 10.67
8 433.37 423.17 58 53.72 52.84 108 10.52 10.36
9 413.24 403.57 59 51.98 50.96 109 10.21 10.06
10 394.16 384.98 60 49.96 49.06 110 9.92 9.78
11 376.05 367.35 61 48.19 47.33 111 9.64 9.50
12 358.88 350.62 62 46.49 45.67 112 9.36 9.23
13 342.58 334.74 63 44.86 44.07 113 9.10 8.97
14 327.10 319.66 64 43.30 42.54 114 8.84 8.71
15 312.41 305.33 65 41.79 41.06 115 8.59 8.47
16 298.45 291.73 66 40.35 39.65 116 8.35 8.23
17 285.18 278.80 67 38.96 38.29 117 8.12 8.01
18 272.58 266.51 68 37.63 36.98 118 7.89 7.78
19 260.60 254.72 69 36.34 35.72 119 7.68 7.57
20 249.00 243.61 70 35.11 34.51 120 7.47 7.36
21 238.36 233.14 71 33.92 33.35 121 7.26 7.16
22 228.05 223.08 72 32.78 32.23 122 7.06 6.97
23 218.24 213.51 73 31.69 31.15 123 6.87 6.78
24 208.90 204.39 74 30.63 30.12 124 6.69 6.59
25 200.00 195.71 75 29.61 29.12 125 6.51 6.42
26 191.53 187.44 76 28.64 28.16 126 6.33 6.25
27 183.46 179.57 77 27.69 27.24 127 6.16 6.08
28 175.77 172.06 78 26.79 26.35 128 6.00 5.92
29 168.44 164.90 79 25.91 25.49 129 5.84 5.76
30 161.45 158.08 80 25.07 24.66 130 5.69 5.61
31 154.79 151.57 81 24.26 23.87 131 5.54 5.46
32 148.43 145.37 82 23.48 23.10 132 5.39 5.32
33 142.37 139.44 83 22.73 22.36 133 5.25 5.18
34 136.59 133.79 84 22.01 21.65 134 5.12 5.05
35 131.06 128.39 85 21.31 20.97 135 4.98 4.92
36 125.79 123.24 86 20.63 20.31 136 4.86 4.79
37 120.76 118.32 87 19.98 19.67 137 4.73 4.67
38 115.95 113.62 88 19.36 19.05 138 4.61 4.55
39 111.35 109.13 89 18.75 18.46 139 4.49 4.44
40 106.96 104.84 90 18.17 17.89 140 4.38 4.32
41 102.76 100.73 91 17.61 17.34 141 4.27 4.22
42 98.75 96.81 92 17.07 16.80 142 4.16 4.11
43 94.92 93.06 93 16.54 16.29 143 4.06 4.01
44 91.25 89.47 94 16.04 15.79 144 3.96 3.91
45 87.74 86.04 95 15.55 15.31 145 3.86 3.81
46 84.38 82.75 96 15.08 14.85 146 3.76 3.72
47 81.16 79.61 97 14.62 14.40 147 3.67 3.62
48 78.09 76.60 98 14.18 13.97 148 3.58 3.54
49 75.14 73.71 99 13.76 13.55 149 3.49 3.45
50 72.32 70.96 100 13.35 13.15 150 3.41 3.37
252 Appendix
SiENBE34-802 Pressure Sensor
6. Pressure Sensor
PH = 1.38V-0.69 PH : Detected Pressure [High Side] MPa
PL = 0.57V-0.28 PL : Detected Pressure [Low Side] MPa
Detected Pressure PH : High pressure (MPa) VH : Output Voltage [High Side] VDC
VL : Low pressure (MPa) VL : Output Voltage [Low Side] VDC
V : Voltage (V)
Appendix 253
Method of Replacing the Inverter’s Power Transistors Modules SiENBE34-802
C+
C-
254 Appendix
SiENBE34-802 Method of Replacing the Inverter’s Power Transistors Modules
C+
C–
Appendix 255
Method of Replacing the Inverter’s Power Transistors Modules SiENBE34-802
The following abnormalities are also doubted besides the PC board abnormality.
1 Faulty compressor (ground fault, ground leakage)
1 Faulty fan motor (ground leakage)
256 Appendix
SiENBE34-802
Part 9
Precautions for New
Refrigerant (R-410A)
1. Precautions for New Refrigerant (R-410A) .........................................258
1.1 Outline ..................................................................................................258
1.2 Refrigerant Cylinders............................................................................260
1.3 Service Tools........................................................................................261
Temperature Steam pressure Density Specific heat at constant Specific enthalpy Specific entropy
(°C) (kPa) (kg/m3) pressure (kJ/kgK) (kJ/kg) (kJ/KgK)
Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor Liquid Vapor
Cylinder
Siphon tube
Refrigerant can be charged in liquid state with cylinder in
upright position.
Handling of cylinders
(1) Laws and regulations
R-410A is liquefied gas, and the High-Pressure Gas Safety Law must be observed in
handling them. Before using, refer to the High-Pressure Gas Safety Law.
The Law stipulates standards and regulations that must be followed to prevent accidents
with high-pressure gases. Be sure to follow the regulations.
(3) Storage
Although R-410A is not flammable, it must be stored in a well-ventilated, cool, and dark
place in the same way as any other high-pressure gases.
It should also be noted that high-pressure vessels are equipped with safety devices that
releases gas when the ambient temperature reaches more than a certain level (fusible plug
melts) and when the pressure exceeds a certain level (spring-type safety valve operates).
Tool compatibility
Compatibility
Tool HFC HCFC Reasons for change
R-410A R-407C R-22
2Do not use the same tools for R-22
Gauge manifold and R-410A.
5
Charge hose 2Thread specification differs for
R-410A and R-407C.
Charging cylinder 5 { 2Weighting instrument used for HFCs.
Gas detector { 5 2The same tool can be used for HFCs.
Vacuum pump 2To use existing pump for HFCs,
(pump with reverse flow { vacuum pump adapter must be
preventive function) installed.
Weighting instrument {
2Seal material is different between
R-22 and HFCs.
Charge mouthpiece 5 2Thread specification is different
between R-410A and others.
Flaring tool (Clutch type) { 2For R-410A, flare gauge is necessary.
Torque wrench { 2Torque-up for 1/2 and 5/8
Pipe cutter {
Pipe expander {
Pipe bender {
2Due to refrigerating machine oil
Pipe assembling oil 5 change. (No Suniso oil can be used.)
Refrigerant recovery Check your recovery device.
device
2Only φ19.1 is changed to 1/2H material
Refrigerant piping See the chart below. while the previous material is "O".
As for the charge mouthpiece and packing, 1/2UNF20 is necessary for mouthpiece size of
charge hose.
R-407C R-410A
Pipe size Thickness Thickness
Material Material
t (mm) t (mm)
φ6.4 O 0.8 O 0.8
φ9.5 O 0.8 O 0.8
φ12.7 O 0.8 O 0.8
φ15.9 O 1.0 O 1.0
φ19.1 O 1.0 1/2H 1.0
φ22.2 1/2H 1.0 1/2H 1.0
φ25.4 1/2H 1.0 1/2H 1.0
φ28.6 1/2H 1.0 1/2H 1.0
φ31.8 1/2H 1.2 1/2H 1.1
φ38.1 1/2H 1.4 1/2H 1.4
φ44.5 1/2H 1.6 1/2H 1.6
* O: Soft (Annealed)
H: Hard (Drawn)
1. Flaring tool
Flare gauge
Specifications
2 Dimension A
Unit:mm
Nominal size
Tube O.D. A +0
-0.4
Differences
2 Change of dimension A
Dimension A
Conventional flaring tools can be used when the work process is changed.
(change of work process)
Previously, a pipe extension margin of 0 to 0.5mm was provided for flaring. For R-410A air
conditioners, perform pipe flaring with a pipe extension margin of 1.0 to 1.5mm.
(For clutch type only)
Conventional tool with pipe extension margin adjustment can be used.
2. Torque wrench
Specifications
2 Dimension B Unit:mm
Nominal size Class-1 Class-2 Previous
1/2 24 26 24
5/8 27 29 27
No change in tightening torque
No change in pipes of other sizes
Differences
2 Change of dimension B
Only 1/2", 5/8" are extended
Dimension B
Specifications
2 Discharge speed z Maximum degree of vacuum
50 l/min (50Hz) Select a vacuum pump which is able to keep
60 l/min (60Hz) the vacuum degree of the system in excess of
2 Suction port UNF7/16-20(1/4 Flare) –100.7 kPa (5 torr – 755 mmHg).
UNF1/2-20(5/16 Flare) with adapter
Differences
2 Equipped with function to prevent reverse oil flow
2 Previous vacuum pump can be used by installing adapter.
4. Leak tester
Specifications
2 Hydrogen detecting type, etc.
2 Applicable refrigerants
R-410A, R-407C, R-404A, R-507A, R-134a, etc.
Differences
2 Previous testers detected chlorine. Since HFCs do not contain chlorine, new tester detects
hydrogen.
Specifications
2 Contains synthetic oil, therefore it can be used for piping work of every refrigerant cycle.
2 Offers high rust resistance and stability over long period of time.
Differences
2 Can be used for R-410A and R-22 units.
Specifications
2 High pressure gauge
- 0.1 to 5.3 MPa (-76 cmHg to 53 kg/cm2)
2 Low pressure gauge
- 0.1 to 3.8 MPa (-76 cmHg to 38 kg/cm2)
2 1/4" → 5/16" (2min → 2.5min)
2 No oil is used in pressure test of gauges.
→ For prevention of contamination
2 Temperature scale indicates the relationship between pressure and temperature in gas
saturated state.
Differences
2 Change in pressure
2 Change in service port diameter
Specifications
2 Working pressure 5.08 MPa (51.8 kg/cm2)
2 Rupture pressure 25.4 MPa (259 kg/cm2)
2 Available with and without hand-operate valve that prevents refrigerant from outflow.
Differences
2 Pressure proof hose
2 Change in service port diameter
2 Use of nylon coated material for HFC resistance
8. Charging cylinder
Specifications
2 Use weigher for refrigerant charge listed below to charge directly from refrigerant cylinder.
Differences
2 The cylinder can not be used for mixed refrigerant since mixing ratio is changed during
charging.
When R-410A is charged in liquid state using charging cylinder, foaming phenomenon is
generated inside charging cylinder.
Specifications
2 High accuracy
TA101A (for 10-kg cylinder) = ± 2g
TA101B (for 20-kg cylinder) = ± 5g
2 Equipped with pressure-resistant sight glass to check liquid refrigerant charging.
2 A manifold with separate ports for HFCs and previous refrigerants is equipped as standard
accessories.
Differences
2 Measurement is based on weight to prevent change of mixing ratio during charging.
Specifications
2 For R-410A, 1/4"→ 5/16" (2min → 2.5min)
2 Material is changed from CR to H-NBR.
Differences
2 Change of thread specification on hose connection side (For the R-410A use)
2 Change of sealer material for the HFCs use.
Index
A Outdoor Unit ................................................... 30
A0 .........................................................................142 Electronic Expansion Valve PI Control .................. 51
A1 .........................................................................143 Error of External Protection Device ..................... 142
A3 .........................................................................144 Excessive Number of Indoor Units ...................... 200
A6 .........................................................................146
A7 .........................................................................147 F
A8 .........................................................................149 F3 ........................................................................ 172
A9 .........................................................................150 F6 ........................................................................ 173
Abnormal Discharge Pipe Temperature ...............172 Failure of Combination (Between Indoor unit PC
Abnormal Power Supply Voltage .........................149 Board and Fan PC Board) ............................ 158
About Refrigerant R-410A ....................................258 Failure of Transmission (Between Indoor unit PC
Actuation of High Pressure Switch .......................164 Board and Fan PC Board) ............................ 154
Actuation of Low Pressure Sensor .......................166 Fan Motor (M1F) Lock, Overload ........................ 146
Address Duplication of Central Remote Control ..201 Field Setting .......................................................... 87
Address Duplication, Improper Setting .................210 Field Setting from Outdoor Unit ........................... 104
AF .........................................................................152 Field Setting from Remote Control ........................ 87
AJ .........................................................................153 Freeze Prevention ................................................. 70
Applicable range of Field setting ............................92 Functional Parts Layout ........................................ 44
C H
C1 .........................................................................154 H9 ........................................................................ 174
C4 .........................................................................156 Heating Operation Prohibition ............................... 64
C5 .........................................................................157 High Pressure Protection Control .......................... 60
C6 .........................................................................158 High Voltage of Capacitor in Main Inverter Circuit ....
C9 .........................................................................159 188
CA ........................................................................160
CC ........................................................................161 I
Centralized Control Group No. Setting .................100 Improper Combination of Optional Controllers for
Check for causes of drop in low pressure ............218 Centralized Control ...................................... 208
Check for causes of rise in high pressure ............217 Inverter Compressor Abnormal ........................... 184
Check Operation ....................................................82 Inverter Compressor Motor Lock ......................... 168
Check Operation not Executed ............................193 Inverter Current Abnormal ................................... 185
CJ .........................................................................162 Inverter Protection Control .................................... 63
Compressor PI Control ...........................................50 Inverter Start up Error ......................................... 186
Contents of Control Modes ..................................102
Cool / Heat Mode Switching .................................113 J
Cooling Operation Fan Control ..............................52 J3 ........................................................................ 175
J5 ........................................................................ 176
D J6 ........................................................................ 177
Defrosting Operation ..............................................56 J7 ........................................................................ 178
Demand Operation .................................................64 J9 ........................................................................ 179
Detailed Explanation of Setting Modes ..................93 JA ........................................................................ 180
Discharge Pipe Protection Control .........................62 JC ........................................................................ 181
Display “Under Host Computer Integrate Control”
Blinks (Repeats Double Blink) ......................216 L
Display “Under Host Computer Integrate Control” L1 ........................................................................ 182
Blinks (Repeats Single Blink) ........................213 L4 ........................................................................ 183
Drain Level above Limit ........................................152 L5 ........................................................................ 184
Drain Pump Control ................................................65 L8 ........................................................................ 185
L9 ........................................................................ 186
E LC ........................................................................ 187
E1 .........................................................................163 List of Electrical and Functional Parts
E3 .........................................................................164 Indoor Unit ...................................................... 32
E4 .........................................................................166 Louver Control for Preventing Ceiling Dirt ............. 67
E5 .........................................................................168 Low Pressure Drop Due to Refrigerant Shortage or
E7 .........................................................................169 Electronic Expansion Valve Failure .............. 189
E9 .........................................................................170 Low Pressure Protection Control .......................... 61
Electrical and Functional Parts
Index i
SiENBE34-802
ii Index
SiENBE34-802
O
operation lamp blinks ...........................................211
operation mode ......................................................48
operation of the remote control’s inspection / test op-
eration button ................................................132
outdoor unit pc board layout ...................................86
P
pc board defect ....................................143, 163, 206
piping diagrams ....................................................222
power supply insufficient or instantaneous failure 191
pressure sensor ...................................................253
R
refrigerant circuit ....................................................40
refrigerant overcharged ........................................173
remote control self-diagnosis function ..................135
remote control service mode ................................133
S
self-diagnosis by wired remote control .................129
self-diagnosis by wireless remote control ............130
setting of low noise operation and demand operation
115
image of operation .........................................116
setting of refrigerant additional charging operation ....
119
check operation .............................................121
simplified remote control ........................................90
brc2c51 ............................................................90
system is not set yet .............................................203
T
thermostat sensor in remote control .......................68
cooling .............................................................68
heating .............................................................69
torque wrench ......................................................263
troubleshooting by remote control ........................128
turn power on .........................................................74
W
weigher for refrigerant charge ..............................266
wired remote control ...............................................87
wireless remote control - indoor unit ......................89
brc4 type ..........................................................89
brc7 type ..........................................................89
wiring diagrams ....................................................227
Naamloze Vennootschap
Zandvoordestraat 300 VRV products are not within the scope of the Eurovent
certification programme.
B-8400 Oostende - Belgium
www.daikin.eu
BTW: BE 0412 120 336
RPR Oostende
ÉSiENBE34-802iËÍ