671 Vaneaxial Fans
671 Vaneaxial Fans
671 Vaneaxial Fans
VANEAXIAL
JANUARY, 2019
FANS
• Capacities to 60,000 CFM
DUCT FANS
• Static pressures to 2”WG
• diameters. • Bearings–selected
Heavy-gauge welded components–provide structural
durability, and minimal leakage.
• diameters.
Thirteen belt-drive sizes – 12” through 60” wheel to provide long service life…
50,000 hours average minimum L-10 on Class I,
•
Eleven direct-drive sizes – 21” through 60” wheel
• Straightening
III. External lubrication fittings are standard.
• Precision
Choice of arrangements – direct-drive or belt-drive vanes– aerodynamically designed
• Flanged
in five mounting positions [see page 6].
vanes convert velocity pressure to static pressure for
rolled tube – for minimum tip clear- maximum efficiency.
ance...maximum efficiency. connections–Sizes 12 to 36 integral to
• fittings
standard with holes.
• Adjustable
Arrangement 9-M
with optional inlet bell Lubrication–extended lubrication lines with external
with wire guard, motor, provided on all belt-drive Vaneaxial Fans.
• Shafting–
drive, and belt guard.
motor mount–positive screw adjustment
for easy belt-tensioning.
• assembly.
straightened to close tolerance to
minimize “run out” and ensure smooth operation.
Balance–all wheels are precision-balanced prior to
• Inner-tube
Fans with motors and drives mounted by
nyb are checked at the specified running speed.
construction–isolates bearings and drive
© Copyright 2011 by The New York Blower Company. ® Registered trademark of The New York Blower Company.
PAGE 2
APPLICATION ADVANTAGES
New York Blower’s Vaneaxial Fans are designed for high-
pressure ventilation and industrial-process applications.
Uses include heat, smoke, and fume removal; process
drying with ambient or preheated air; comfort and
process cooling and general ventilation. All applications
can be handled in either supply or exhaust configura-
tions. Numerous modifications and accessories make
the Vaneaxial Fan suitable for a wide range of systems.
Direct-drive Vaneaxial wheels feature New York Blower’s unique variable-pitch selection capability. Specific
blade-pitch angles, unique for each application, are used in the fabrication of each direct-drive Vaneaxial
wheel. Unique wheels allow the direct-drive Vaneaxial to exactly match system requirements while optimizing
operating efficiency.
New York Blower’s Vaneaxial Fans provide relatively large volumes of air at high static pressures. For even
higher pressure requirements, see New York Blower’s Tubular Acoustafoil® Fans utilizing centrifugal airfoil
wheels. For systems requiring lower pressure, refer to New York Blower’s Tubeaxial or Duct Fan bulletins.
PAGE 3
ACCESSORIES AND MODIFICATIONS
1. INLET BELL WITH GUARD – see page 5
3 ARRANGEMENT Inlet bell minimizes losses associated with non-ducted
9-M inlet applications. Includes wire guard.
2. VIBRATION ISOLATION – see page 6
Rubber-in-shear or spring-type isolation mounts reduce
the transmission of vibration to the mounting structure.
3. SAFETY EQUIPMENT/WEATHER COVER
Belt guards, inlet and outlet guards, and weather covers
are available. Selection of appropriate safety accessories
is the responsibility of the system designer familiar with
the specific installation.
4. COMPANION FLANGES – not shown
Fit flush with fan inlet and outlet flanges, provided with
matching hole pattern.
5. STACK HOOD
Stack hood with built-in back-draft dampers for outdoor
1 exhaust applications.
6. CURB CAP
Gussetted cover with nailer holes on perimeter includes
flange for fan mounting.
ARRANGEMENT 7. DRAINS – not shown
5 For horizontal mounted fans...drain located at the lowest
9-R
point of the housing tube.
8. ACCESS DOOR – not shown
3 Gasketed, latch-type door swings open on hinges after
turning cam levers...provides access to wheel...avail-
able in Sizes 245 and larger...inspection port available
on smaller sizes.
9. SHAFT SEAL– not shown
Ceramic-felt seal elements encased between metal back-
ing plate and retaining disc...elements can be easily split
for field installation and maintenance...lubricated lip
seals are also available.
6 10. MOTORS AND DRIVES
A wide-array of motor and drive components are avail-
able factory-mounted by nyb.
11. INLET VANE DAMPER
Bolt-on damper assembly provides volume control...for
modulating systems...electric and pneumatic damper
operators also available.
ARRANGEMENT 12. SPARK-RESISTANT CONSTRUCTION – not shown
9-D AMCA B [wheel type] SRC and AMCA C [buffer type]
SRC construction available on Sizes 165-605. SRC
construction not available with inlet damper, inlet
guard, or easy-access construction.
PAGE 4
ACCESSORY PERFORMANCE
CHART I
INLET BELL SILENCER
Catalog ratings shown in
this bulletin are for
Vaneaxial Fans with free VELOCITY
inlet and ducted outlet. PRESSURE
When no inlet duct is Velocity
VP
[FPM]
used, entrance loss must
be added to the static 1000 .063
pressure calculated for 1400 .122
the system. For bare 1800 .202
inlets, that loss is equal 2200 .302
to the fan velocity pres- 2600 .422 Available for all sizes of Vaneaxial Fans with
sure. Example: 4200 3000 .560 matching standard flanges for either inlet or
FPM velocity = 1.1”WG outlet applications. Silencers are available in
[see Chart I at right]. Inlet 3400 .721
two sizes to better match system cost as well
bells render such loss neg- 3800 .900
as sound attenuation parameters. All silencers
ligible and are available at 4200 1.100
utilize heavy-welded steel construction filled
nominal cost. Sizes 125 4800 1.436 with high-density acoustical absorption mater-
through 485 constructed 5000 1.560 ial. For more detailed application information
of fiberglass reinforced and attenuation performance, refer to
plastic; Sizes 545 and Engineering Supplement ES-673.
605 constructed of steel.
SAFETY EQUIPMENT
Safe operation of air-moving equipment is dependent must consider providing guards for all exposed moving
on proper installation and maintenance. This includes parts as well as protection from access to high velocity
selection and use of appropriate safety accessories for airstreams. Improper application, installation, mainte-
the specific installation. Such safety accessories are nance, or safety guard selection can create danger to
available from nyb. However, selection of the appropri- life and limb of personnel. Users and/or installers
ate devices is the responsibility of the system designer should read "Recommended Safety Practices for Air
who must be aware of the fan location, fan accessibility Moving Devices" as published by the Air Movement and
in the particular installation, and adjacent equipment. Control Association, 30 West University Drive,
Neither nyb nor its sales representatives are in a position Arlington Heights, Illinois 60004.
Fan to Size online allows customers to select fans without the need to download soft-
ware on their computers or tablets. Fans can be selected by product categories, types
or applications. Additionally, drawings are generated to supplement fan selections.
PAGE 5
MOUNTING ARRANGEMENTS
Arrangement 9-M
with optional inlet bell wire
guard, motor, drive, and Arrangement 4-S
belt guard. with optional
spring
isolation.
4-M WITH
AND
9-M Fabricated mounting legs facilitate fan
mounting on the floor, ceiling, or in a
vertical position on a wall. Flange 1 2 3
Mounting Positions
ARRANGEMENTS
Fans are equipped with four mounting
FLOW
FLOW
AIR
AIR
4-V FOR
AND
9-V brackets suitable for floor, platform, or
ceiling mounting. Motor is located on
centerline between two of the four 7 8
FLOW
FLOW
AIR
connections are standard.
AIR
MOUNTING
9 10
ARRANGEMENTS
Fans for suspended mounting are 9-S Mounting Positions
4-S FOR
AND
9-S equipped with side supports suitable for
attachment to rods hung from the
ceiling structure. Flange connections are
SUSPENDED standard. 11 12
MOUNTING
ARRANGEMENTS
4-D FOR
AND
9-D Units feature flanges on inlet and discharge for mounting to the
duct work.
DUCT
MOUNTING
ARRANGEMENTS
4-R FOR
AND
9-R Vaneaxial Fans are available packaged with stack hoods and curb
caps for outdoor exhaust applications. Arrangement 9 units also
feature weather covers. Roof-mounted units have round collars
extending below the curb caps for easy connection to the duct system.
ROOF
MOUNTING
PAGE 6
MAINTENANCE MADE EASY
INDUSTRIAL DESIGNS
At New York Blower, we recognize the importance of
long-term maintenance and the costs involved. All
New York Blower axial fans are designed for reduced
or simplified maintenance. The achievement of this
goal begins with rugged industrial designs using
heavy-gauge materials, welded construction, and
quality components.
EXTENDED SERVICE LIFE
Components for belt-drive fans are selected with up to
a 1.7 service factor for sheaves and belts. Bearings
are chosen for an average minimum L-10 Life of
80,000 hours and often exceed 100,000 hours.
PAGE 7
HOW TO USE CAPACITY TABLES
For a given fan size, CFM, and static pressure, capacity tables can be used to obtain outlet velocity, fan RPM, and BHP.
If capacities are at conditions other than 70°F, sea level, or standard density [.075 lb./cu. ft.], correction factors must
be applied to static pressure and BHP.
Select size, RPM, and BHP of fan from capacity table. A Size 275 is selected for 18000 CFM at 4”WG at
2872 RPM and 22.7 BHP.
PAGE 8
DIRECT-DRIVE VANEAXIAL FANS
Available in Sizes 185 through 605, the direct-drive Vaneaxial Fan is
ideally suited for relatively clean-air applications at temperatures to
105°F.
Elimination of the external motor mounting structure permits instal-
lation in extremely tight locations and substantial reduction in overall
unit weight. The Arrangement 4 configuration virtually eliminates all
regularly scheduled maintenance.
New York Blower’s unique method of wheel selection and fabrication,
matching blade pitch to specific airflow, pressure, and speed require-
ments, assures optimum performance. Each custom wheel is tested
and inspected to assure conformance to design and application
requirements prior to shipment.
11 ⁄2"SP 2"SP
Inlet and outlet area: 1.82 sq. ft.
2400 1319 22.5 0.20 25.4 0.31 30.9 0.53 21.7 1.98 24.3 2.43
2800 1538 25.9 0.28 28.9 0.43 34.3 0.66 20.6 1.72 23.2 2.31 25.7 2.78
3200 1758 29.4 0.38 32.3 0.56 37.8 0.86 20.5 1.61 22.1 2.05 24.6 2.62 27.3 3.23
3400 1868 31.1 0.43 34.0 0.61 39.6 0.96 21.2 1.75 22.8 2.20 25.4 2.83 28.0 3.44
3600 1978 32.8 0.48 35.7 0.69 41.2 1.10 20.7 1.53 21.9 1.89 23.5 2.35 26.1 3.04 28.7 3.64
3800 2088 34.5 0.53 37.5 0.79 43.0 1.25 21.4 1.66 22.7 2.06 24.2 2.50 26.8 3.25 29.5 3.86
4000 2198 36.3 0.62 39.2 0.90 21.0 1.46 22.1 1.79 23.4 2.20 25.0 2.67 27.6 3.48 30.1 4.04
4200 2308 38.0 0.70 40.9 1.01 20.6 1.26 21.7 1.57 22.9 1.95 24.1 2.34 25.7 2.88 28.3 3.70 30.9 4.28
4400 2418 39.7 0.78 42.6 1.16 20.7 1.21 21.3 1.37 22.5 1.72 23.6 2.08 24.9 2.51 26.4 3.08 29.0 3.91 31.6 4.49
5000 2747 22.9 1.55 23.5 1.72 24.6 2.07 25.8 2.56 27.1 3.12 28.6 3.74 31.2 4.58 33.8 5.14
5500 3022 24.7 1.82 25.3 2.02 26.5 2.52 27.6 3.02 28.9 3.62 30.5 4.31 33.0 5.14 35.6 5.80
6000 3297 26.5 2.17 27.2 2.44 28.3 2.94 29.4 3.48 30.7 4.13 32.3 4.86 34.8 5.71 37.4 6.69
7000 3846 30.2 2.94 30.8 3.22 31.9 3.80 33.1 4.49 34.4 5.22 35.9 6.15 38.5 7.58 41.1 8.76
8000 4396 33.9 3.75 34.5 4.07 25.6 4.83 36.8 5.83 38.0 6.92 39.6 8.05 42.2 10.0 44.8 11.3
9000 4945 37.5 5.15 38.1 5.32 39.3 6.38 40.4 7.51 41.7 9.01 43.3 10.7
10000 5495 41.8 7.04 41.8 7.04 43.0 8.51 44.1 9.95
11 ⁄2"SP 2"SP
Inlet and outlet area: 2.46 sq. ft.
4600 1870 30.5 0.58 33.2 0.75 36.4 1.00 26.6 3.98
5000 2033 32.6 0.66 35.3 0.86 38.5 1.17 27.6 4.35
5400 2195 34.7 0.75 37.4 1.02 40.6 1.36 26.3 3.82 28.7 4.77
5800 2358 36.8 0.88 39.6 1.17 42.7 1.60 25.6 3.46 27.4 4.23 29.8 5.18
6200 2520 39.0 1.03 41.7 1.39 44.8 1.85 26.6 3.82 28.4 4.59 30.5 5.45
6600 2583 41.1 1.21 43.8 1.62 46.9 2.05 26.2 3.54 27.7 4.21 29.5 5.00 31.9 5.99
7000 2846 43.2 1.41 45.9 1.83 49.1 2.25 25.9 3.28 27.2 3.88 28.8 4.61 30.6 5.42 33.0 6.42
7400 3008 45.3 1.62 48.0 2.01 25.6 3.01 26.9 3.61 28.3 4.26 29.8 4.97 31.6 5.80 34.0 6.81
8000 3252 26.1 3.01 26.7 3.28 27.2 3.51 28.5 4.13 29.9 4.82 31.5 5.61 33.2 6.42 35.6 7.59
9000 3659 28.8 3.82 29.3 4.06 29.9 4.37 31.2 5.05 32.6 5.79 34.1 6.58 35.9 7.69 38.3 9.34
10000 4065 31.4 4.59 32.0 4.92 32.5 5.20 33.8 5.93 35.2 6.77 36.8 8.04 38.5 9.35 40.9 11.2
11000 4472 34.1 5.44 34.6 5.73 35.2 6.13 36.5 7.21 37.9 8.39 39.4 9.65 41.2 11.4 43.6 13.8
12000 4878 36.7 6.57 37.3 7.09 37.9 7.61 39.1 8.68 40.5 10.0 42.1 11.9 43.9 13.9
13000 5285 39.4 7.97 39.9 8.44 40.5 9.12 41.8 10.6 43.2 12.4 44.7 14.2
14000 5691 42.0 9.74 42.6 10.5 43.2 11.2 44.4 12.8
15000 6098 44.7 11.7
Performance certified is for installation Type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses.
Performance ratings do not include the effects of appurtenances (accessories).
PAGE 9
SIZE 245
1 ⁄8"SP
DIRECT-DRIVE
1 ⁄4"SP 3⁄8"SP 1 ⁄2"SP
1150 RPM
1750 RPM
1 ⁄8"SP 1 ⁄4"SP
Wheel diameter: 24"
3⁄8"SP 1 ⁄2"SP
Inlet and outlet area: 3.24 sq. ft.
SIZE 275
1 ⁄4"SP
DIRECT-DRIVE
3⁄8"SP 1⁄2"SP 3⁄4"SP
1150 RPM
1750 RPM
1⁄4"SP 1 ⁄2"SP
Wheel diameter: 27"
3⁄4"SP 1"SP
Inlet and outlet area: 4.09 sq. ft.
5000 1222 26.1 0.48 27.8 0.59 32.9 0.93 27.1 2.14
5800 1418 27.1 0.49 28.9 0.61 30.6 0.74 35.7 1.12 26.4 1.97 28.9 2.49
6600 1614 29.9 0.62 31.7 0.75 33.4 0.88 38.5 1.39 26.5 1.91 28.2 2.31 30.8 2.84
7400 1809 32.7 0.75 34.5 0.89 36.2 1.07 41.3 1.71 25.1 1.49 26.6 1.83 28.4 2.24 30.0 2.66 32.6 3.20
8200 2005 35.5 0.89 37.3 1.10 39.0 1.32 44.1 2.09 25.3 1.44 26.9 1.78 28.4 2.14 30.2 2.58 31.8 3.02 34.4 3.57
9000 2200 38.3 1.11 40.1 1.33 41.8 1.63 46.9 2.43 25.6 1.40 27.1 1.72 28.7 2.08 30.2 2.46 32.0 2.92 33.7 3.37 36.3 4.10
9800 2396 41.1 1.36 42.9 1.67 44.6 1.98 49.7 2.75 57.5 1.66 28.9 2.00 30.6 2.38 32.1 2.79 33.8 3.26 35.5 3.80 38.1 4.70
10600 2592 43.9 1.67 45.7 1.98 47.4 2.28 29.3 1.92 30.8 2.29 32.4 2.69 33.9 3.11 35.7 3.69 37.3 4.40 39.9 5.31
11400 2787 46.7 1.95 48.5 2.26 31.1 2.19 32.6 2.58 34.2 3.00 35.7 3.52 37.5 4.26 39.2 4.99 41.7 6.17
12200 2983 49.5 2.20 32.9 2.47 34.4 2.87 36.0 3.43 37.5 4.07 39.3 4.84 41.0 5.73 43.6 7.04
13000 3178 34.8 2.74 36.2 3.30 37.9 3.95 39.4 4.61 41.1 5.57 42.8 6.60 45.4 7.88
14000 3423 37.1 3.29 38.5 3.91 40.1 4.61 41.7 5.51 43.4 6.60 45.1 7.67 47.7 8.78
15000 3667 39.3 3.86 40.8 4.61 42.4 5.54 43.9 6.50 45.7 7.58 47.4 8.55 50.0 9.67
16000 3912 41.6 4.61 43.1 5.49 44.7 6.47 46.2 7.38 48.0 8.42 49.7 9.43
17000 4156 43.9 5.43 45.4 6.35 47.0 7.25 48.5 9.18
19000 4645 48.5 6.84 49.9 7.78
SIZE 325
1 ⁄4"SP
DIRECT-DRIVE
1 ⁄2"SP 3⁄4"SP 1"SP
1150 RPM
1750 RPM
1⁄4"SP 1 ⁄2"SP
Wheel diameter: 32"
1"SP 11 ⁄2"SP
Inlet and outlet area: 5.76 sq. ft.
8000 1399 21.7 0.95 24.2 1.34 27.0 1.88 21.0 3.57 22.1 4.15 24.0 5.04
9000 1573 21.7 0.82 24.0 1.19 26.5 1.67 29.2 2.27 20.4 3.06 22.3 4.12 23.4 4.72 25.3 5.67
10000 1748 24.0 1.03 26.3 1.48 28.8 2.03 31.5 2.68 20.2 2.69 21.7 3.57 23.6 4.68 24.7 5.29 26.6 6.46
11000 1923 26.3 1.28 28.6 1.81 31.1 2.40 33.8 3.09 21.5 3.15 23.0 4.08 24.9 5.24 26.0 6.03 27.9 7.2
12000 2098 28.6 1.57 30.9 2.15 33.4 2.78 36.1 3.63 20.4 2.27 21.1 2.65 22.8 3.62 24.3 4.60 26.2 5.98 27.3 6.80 29.2 8.04
13000 2273 30.9 1.85 33.2 2.49 35.7 3.23 38.4 4.31 21.7 2.65 22.4 3.06 24.1 4.08 25.6 5.20 27.5 6.75 28.6 7.58 30.5 8.85
14000 2448 33.2 2.15 35.4 2.88 38.0 3.86 40.7 5.09 23.0 3.03 23.7 3.46 25.4 4.59 26.9 5.90 28.8 7.51 29.9 8.36 31.8 9.67
15000 2622 35.5 2.49 37.7 3.45 40.3 4.52 43.0 6.07 24.3 3.41 25.0 3.87 26.7 5.23 28.3 6.60 30.1 8.27 31.3 9.17 33.1 10.5
16000 2797 37.8 2.98 40.0 4.03 42.6 5.43 25.6 3.86 26.3 4.43 28.0 5.86 29.6 7.30 31.4 9.06 32.6 9.98 34.4 11.3
17000 2972 40.1 3.48 42.3 4.85 44.9 6.34 26.9 4.38 27.6 4.99 29.3 6.50 30.9 8.02 32.7 9.86 33.9 10.8 35.7 12.4
18000 3147 42.4 4.19 44.6 5.68 28.2 4.91 28.9 5.54 30.6 7.15 32.2 8.75 34.0 10.7 35.2 11.7 37.0 13.8
20000 3497 30.8 5.97 31.5 6.68 33.2 8.47 34.8 10.2 36.6 12.9 37.8 14.4 39.6 16.6
22000 3846 33.4 7.05 34.1 7.84 35.8 10.1 37.4 12.5 39.2 15.5 40.4 17.2 42.2 20.3
24000 4196 36.0 8.42 36.8 9.52 38.4 12.3 40.0 15.0 41.8 19.0 43.0 21.1 44.9 24.3
26000 4545 38.6 10.2 39.4 11.5 41.0 14.8 42.6 18.5 44.4 22.8
28000 4895 41.2 12.4 42.0 14.0 43.6 18.0
Performance certified is for installation Type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses.
Performance ratings do not include the effects of appurtenances (accessories).
PAGE 10
SIZE 365
1 ⁄4"SP
DIRECT-DRIVE
1 ⁄2"SP 3⁄4"SP 1"SP
1175 RPM
1750 RPM
11 ⁄4"SP 1 ⁄2"SP
Wheel diameter: 36"
1"SP 11 ⁄2"SP
Inlet and outlet area: 7.27 sq. ft.
SIZE 425
1 ⁄4"SP
DIRECT-DRIVE
1⁄2"SP 3⁄4"SP 1"SP
875 RPM
1175 RPM
1⁄4"SP
Wheel diameter: 423⁄8"
12000 1204 20.3 1.34 22.3 1.89 25.1 2.60 23.4 5.50
14000 1404 20.9 1.29 22.7 1.76 24.8 2.36 27.5 3.28 20.2 3.47 21.5 4.27 25.26.44
16000 1605 23.3 1.66 25.2 2.19 27.2 2.99 29.9 3.97 21.0 3.57 22.0 4.28 23.2 5.12 27.0 7.67
18000 1805 25.7 2.08 27.6 2.76 29.6 3.63 32.3 4.68 20.7 3.03 21.7 3.65 22.7 4.33 23.8 5.09 25.0 5.98 28.7 8.90
20000 2006 28.2 2.59 30.0 3.34 32.0 4.29 34.8 5.39 21.7 3.14 22.5 3.69 23.5 4.37 24.5 5.09 25.5 5.99 26.8 7.15 30.5 10.2
22000 2207 30.6 3.11 32.4 3.93 34.4 4.96 37.2 6.52 23.5 3.76 24.2 4.36 25.2 5.11 26.3 6.05 27.3 7.09 28.5 8.31 32.3 11.4
24000 2407 33.0 3.64 34.8 4.53 36.8 5.96 39.6 7.71 25.2 4.40 26.0 5.16 27.0 6.09 28.0 7.09 29.1 8.20 30.3 9.49 34.0 12.7
26000 2608 35.4 4.24 37.2 5.49 39.2 7.07 42.0 9.33 27.0 5.24 27.8 6.06 28.8 7.06 29.8 8.12 30.8 9.32 32.1 10.7 35.8 14.4
28000 2808 37.8 5.12 39.6 6.48 41.7 8.52 44.4 11.0 28.8 6.07 29.5 6.97 30.5 8.05 31.6 9.20 32.6 10.5 33.8 11.9 37.6 16.5
30000 3009 40.2 6.05 42.0 7.85 44.1 10.1 30.5 6.92 31.3 7.91 32.3 9.06 33.3 10.3 34.4 11.6 35.6 13.4 39.3 18.6
32000 3210 42.6 7.33 44.5 9.29 32.3 7.79 33.1 8.85 34.0 10.1 35.1 11.4 36.1 13.3 37.4 15.4 41.1 21.4
34000 3410 34.1 8.66 34.8 9.79 35.8 11.4 36.9 13.2 37.9 15.2 39.1 17.5 42.9 24.4
36000 3611 35.8 9.80 36.6 11.3 37.6 13.1 38.6 15.0 39.7 17.1 40.9 19.9 44.6 27.5
38000 3811 37.6 11.3 38.4 12.9 39.3 14.8 40.4 17.0 41.4 19.7 42.7 22.9
40000 4012 39.4 12.7 40.1 14.5 41.1 16.9 42.1 19.5 43.2 22.4 44.4 25.8
42000 4213 41.1 14.6 41.9 16.8 42.9 19.4 43.9 22.1 45.0 25.2
11⁄4"SP
Wheel diameter: 423⁄8"
24000 2407 20.3 10.98 21.3 13.02 22.3 15.34 23.3 17.90 24.9 20.92
27000 2708 20.1 9.23 20.5 10.06 20.8 10.70 21.2 11.56 22.1 13.49 23.0 15.66 24.10 18.13 25.1 20.90 26.6 24.94
30000 3009 21.4 10.06 21.6 10.75 21.8 11.41 22.3 12.31 22.5 13.01 23.0 13.93 23.8 16.00 24.8 18.30 25.8 21.39 26.9 24.92 28.4 29.05
33000 3310 23.1 12.08 23.4 12.85 23.6 13.58 24.0 14.56 24.3 15.32 24.7 16.29 25.6 18.82 26.6 21.81 27.6 25.21 28.6 28.94 30.1 33.17
36000 3611 24.9 14.10 25.1 15.01 25.4 15.92 25.8 17.16 26.0 18.13 26.5 19.39 27.4 22.26 28.3 25.42 29.3 29.03 30.4 32.99 31.9 37.44
39000 3912 26.7 16.81 26.9 17.89 27.1 18.90 27.5 20.24 27.8 21.29 28.2 22.63 29.1 25.69 30.1 29.05 31.1 32.94 32.1 37.17 33.6 41.71
42000 4213 28.4 19.58 28.6 20.77 28.9 21.88 29.3 23.32 29.6 24.45 30.0 25.87 30.9 29.19 31.8 32.80 32.8 36.91 33.9 41.34 35.4 46.64
45000 4514 30.2 22.35 30.4 23.68 30.6 24.89 31.0 26.46 31.3 27.70 31.8 29.24 32.6 32.75 33.6 33.56 34.6 40.88 35.6 46.53 37.2 53.75
48000 4814 31.9 25.22 32.1 26.67 32.4 27.98 32.8 29.66 33.1 30.98 33.5 32.60 34.4 36.32 35.3 40.80 36.3 46.86 37.4 53.48 38.9 60.87
51000 5115 33.7 28.09 33.9 29.66 34.1 31.08 34.5 32.85 34.8 34.26 35.3 36.30 36.1 41.42 37.1 47.06 38.1 53.48 39.2 60.44 40.7 69.20
54000 5416 35.4 31.43 35.7 33.39 35.9 35.22 36.3 37.63 36.6 39.52 37.0 41.91 37.9 47.36 38.9 53.31 39.9 60.09 40.9 69.00
57000 5717 37.2 36.22 37.4 38.38 37.7 40.38 38.1 42.95 38.3 44.98 38.8 47.52 39.6 58.30 40.6 60.54 41.6 69.40
60000 6018 38.9 41.00 39.2 43.37 39.4 45.53 39.8 48.27 41.0 50.59 40.5 53.88 41.4 61.36 42.4 69.58
63000 6319 40.7 46.64 40.9 49.52 41.2 52.21 41.6 55.72 41.9 58.49 42.3 61.98 43.2 69.94
66000 6620 42.5 53.55 42.7 56.72 42.9 59.65 43.3 63.41 43.6 66.38 44.0 70.08
69000 6921 44.2 60.46 44.4 63.93 44.7 67.09
Performance certified is for installation Type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses.
Performance ratings do not include the effects of appurtenances (accessories).
PAGE 11
SIZE 485
1 ⁄4"SP
DIRECT-DRIVE
1 ⁄2"SP 1"SP 11 ⁄4"SP
875 RPM
1175 RPM
1 ⁄4"SP
Wheel diameter: 483⁄8"
1"SP 2"SP
Inlet and outlet area: 16.5 sq. ft.
SIZE 605
1 ⁄4"SP
DIRECT-DRIVE
1"SP 11⁄2"SP 13⁄4"SP
875 RPM
1175 RPM
2"SP 21 ⁄4"SP
Wheel diameter: 60"
1 ⁄4"SP 1"SP
Inlet and outlet area: 20.3 sq. ft.
45000 2217 25.3 8.30 27.9 11.7 31.2 16.2 32.9 18.4 34.8 20.8 37.7 26.3 27.4 29.9 31.9 42.8
50000 2463 27.7 10.4 30.2 14.0 33.5 18.8 35.3 21.3 37.1 25.2 40.1 30.9 25.5 23.2 29.1 34.3 33.6 47.4
55000 2709 30.1 12.5 32.6 16.4 35.9 22.1 37.7 25.7 39.5 29.6 42.4 37.4 27.2 27.3 30.8 38.7
60000 2956 32.4 14.6 35.0 18.9 38.3 26.4 40.0 30.2 41.9 35.7 26.1 21.8 28.9 31.4 32.5 43.3
65000 3202 34.8 16.8 37.3 22.9 40.6 31.3 42.4 36.6 25.9 19.3 27.8 25.4 30.6 35.5 34.2 47.8
70000 3446 37.2 20.3 39.7 26.9 43.0 37.6 27.6 22.6 29.4 29.0 32.3 39.7
75000 3695 39.5 23.9 42.1 32.5 29.2 25.9 31.1 32.7 33.9 44.0
80000 3941 41.9 28.8 44.4 38.3 30.9 29.2 32.8 36.5 35.6 49.4
‘ 85000 4187 44.3 34.0 32.6 32.6 34.5 40.2
90000 4433 34.3 36.0 36.2 45.7
95000 4680 36.0 40.7
10000 4923 37.6 46.4
Performance certified is for installation Type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses.
Performance ratings do not include the effects of appurtenances (accessories).
PAGE 12
BELT-DRIVE VANEAXIAL FANS
Belt-drive Vaneaxial Fans are available in Sizes 126 through
606 for more aggressive airstreams or applications where
temperatures may reach 200°F. Belt-drive arrangements
include an inner tube and belt-well assembly that isolates
bearings and drive components from airborne moisture and
contaminants. In the event that system pressures or flow
requirements change, belt-drive Vaneaxial Fans offer inherent
performance flexibility. New performance is easily achieved
by modifying readily accessible drives.
11 ⁄4"SP 11 ⁄2"SP
Inlet and outlet area: 0.81 sq. ft.
11 ⁄2"SP 13⁄4"SP
Inlet and outlet area: 1.10 sq. ft.
2000 1818 2155 0.7 2264 0.8 2361 0.8 2572 1.0
2400 2182 2512 0.9 2602 0.9 2684 1.0 2857 1.2 3026 1.3 3227 1.5
2800 2545 2879 1.1 2953 1.2 3023 1.2 3170 1.4 3320 1.6 3466 1.7 3626 1.9 3790 2.1
3000 2727 3063 1.2 3134 1.3 3199 1.4 3335 1.6 3476 1.7 3615 1.9 3748 2.1 3892 2.3 3973 2.4 4057 2.5
3100 2818 3156 1.3 3225 1.4 3288 1.5 3419 1.6 3553 1.8 3685 2.0 3823 2.2 3962 2.4 4031 2.5 4102 2.6 4186 2.7
3200 2909 3249 1.4 3316 1.5 3377 1.5 3506 1.7 3634 1.9 3763 2.1 3893 2.3 4023 2.5 4089 2.6 4167 2.7 4228 2.8
3300 3000 3343 1.5 3409 1.6 3468 1.6 3593 1.8 3718 2.0 3840 2.2 3967 2.4 4093 2.6 4157 2.7 4222 2.8 4290 3.0
3400 3091 3437 1.6 3500 1.6 3558 1.7 3679 1.9 3798 2.1 3921 2.3 4044 2.5 4162 2.7 4223 2.8 4287 3.0 4352 3.1
3500 3182 3530 1.6 3592 1.7 3649 1.8 3765 2.0 3885 2.2 4001 2.4 4117 2.6 4239 2.8 4290 3.0 4360 3.1 4414 3.2
3600 3273 3624 1.7 3685 1.8 3741 1.9 3854 2.1 3967 2.3 4084 2.5 4196 2.7 4315 3.0 4364 3.1 4424 3..2 4484 3.3
3700 23364 3719 1.8 3777 1.9 3832 2.0 3943 2.2 4050 2.4 4163 2.6 4276 2.9 4390 3.1 4438 3.2
3800 3455 3812 1.9 3871 2.0 3923 2.1 4031 2.3 4139 2.5 4249 2.8 4354 3.0 4465 3.3
3900 3545 3908 2.1 3964 2.1 4014 2.2 4119 2.4 4224 2.7 4330 2.9 4439 3.2
4000 3636 4002 2.2 4056 2.3 4107 2.4 4210 2.6 4312 2.8 4411 3.0
4100 3727 4096 2.3 4150 2.4 4199 2.5 4301 2.7 4399 3.0 4498 3.2
4200 3818 4192 2.4 4245 2.5 4293 2.6 4391 2.9 4486 3.1
Performance certified is for installation Type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses.
Performance ratings do not include the effects of appurtenances (accessories).
PAGE 13
SIZE 166 BELT-DRIVE
1 ⁄4"SP 3⁄8"SP 1⁄2"SP 3⁄4"SP 1"SP 11⁄2"SP
Wheel diameter: 16"
13⁄4"SP 2"SP
Inlet and outlet area: 1.44 sq. ft.
2400 1667 1634 0.7 1712 0.7 1784 0.8 1946 0.9
2800 1944 1861 0.8 1928 0.9 1990 0.9 2122 1.1 2260 1.2
3200 2222 2091 1.0 2151 1.0 2206 1.1 2317 1.3 2432 1.4 2682 1.8
3600 2500 2326 1.1 2378 1.2 2428 1.3 2526 1.5 2628 1.7 2833 2.1 2944 2.3
4000 2778 2562 1.4 2610 1.5 2654 1.6 2745 1.8 2833 2.0 3015 2.4 3111 2.6 3213 2.9
4200 2917 2681 1.5 2728 1.6 2769 1.7 2855 1.9 2941 2.1 3113 2.5 3202 2.8 3292 3.1 3487 3.6
4400 3056 2801 1.7 2844 1.8 2885 1.9 2967 2.1 3048 2.3 3213 2.8 3296 3.0 3379 3.3 3558 3.8
4600 3194 2920 1.8 2962 1.9 3001 2.0 3081 2.3 3158 2.5 3317 3.0 3394 3.2 3475 3.5 3639 4.1 3819 4.7
4800 3333 3040 2.0 3081 2.1 3118 2.2 3194 2.4 3271 2.7 3419 3.2 3494 3.5 3569 3.8 3728 4.4 3892 5.0 4070 5.7
5000 3472 3160 2.2 3200 2.3 3235 2.4 3309 2.7 3382 2.9 3524 3.5 3598 3.8 3671 4.0 3816 4.6 3974 5.3 4135 5.9
5200 3611 3281 2.4 3319 2.5 3353 2.6 3424 2.9 3493 3.2 3633 3.7 3701 4.0 3771 4.3 3913 4.9 4056 5.6 4209 6.3
5400 3750 3402 2.6 3438 2.8 3471 2.9 3540 3.2 3607 3.5 3740 4.0 3806 4.3 3875 4.6 4008 5.3 4145 5.9 4293 6.6
5600 3889 3522 2.9 3557 3.0 3590 3.2 3656 3.5 3720 3.7 3850 4.3 3915 4.7 3978 5.0 4110 5.6 4243 6.3 4375 6.9
5800 4028 3643 3.2 3678 3.3 3709 3.5 3773 3.8 3836 4.1 3959 4.7 4022 5.0 4083 5.3 4211 6.0 4338 6.6 4466 7.3
6200 4306 3886 3.8 3918 4.0 3947 4.1 4008 4.4 4066 4.7 4185 5.4 4243 5.7 4300 6.0 4415 6.7
6600 4583 4128 4.5 4159 4.7 4186 4.8 4243 5.1 4299 5.5 4409 6.2 4463 6.5
21 ⁄2"SP 3"SP
Inlet and outlet area: 1.82 sq. ft.
3000 1648 1524 0.7 1616 0.8 1698 0.9 2049 1.3
3500 1923 1725 0.9 1802 1.0 1875 1.0 2173 1.5 2469 1.9
4000 2198 1934 1.1 1998 1.1 2061 1.2 2323 1.7 2584 2.2 2849 2.8 3072 3.4
4500 2473 2148 1.3 2203 1.4 2256 1.5 2490 2.0 2720 2.5 2958 3.1 3184 3.8 3388 4.5
5000 2747 2364 1.6 2413 1.7 2459 1.8 2670 2.3 2879 2.9 3088 3.6 3307 4.3 3505 5.1 3699 5.8
5500 3022 2582 1.9 2627 2.0 2668 2.2 2856 2.7 3047 3.4 2326 4.1 3428 4.8 3621 5.6 3810 6.5 3990 7.3 4156 8.1
6000 3297 2801 2.3 2843 2.5 2880 2.6 3047 3.2 3223 3.9 3399 4.7 3570 5.4 3748 6.3 3921 7.1 4096 8.0 4260 8.9
6500 3571 3023 2.9 3060 3.0 3095 3.2 3245 3.8 3405 4.5 3568 5.3 3729 6.1 3885 6.9 4054 7.9 4215 8.8 4376 9.8
6750 3709 3133 3.2 3170 3.3 3204 3.5 3347 4.1 3501 4.9 3660 5.7 3812 6.5 3968 7.3 4121 8.2 4274 9.2 4440 10.2
7000 3846 3244 3.5 3280 3.7 3312 3.8 3449 4.5 3595 5.2 3751 6.1 3899 6.9 4045 7.7 4197 8.7 4344 9.6
7250 3984 3355 3.8 3389 4.0 3421 4.2 3553 4.8 3693 5.6 3841 6.5 3989 7.3 4130 8.2 4272 9.1 4413 10.1
7500 4121 3467 4.2 3500 4.4 3530 4.5 3657 5.2 3791 6.0 3931 6.9 4074 7.8 4210 8.7 4346 9.6 4491 10.6
7750 4258 3578 4.6 3610 4.8 3639 4.9 3763 5.7 3891 6.4 4027 7.3 4166 8.3 4297 9.2 4428 10.1
8000 4396 3689 5.0 3720 5.2 3749 5.4 3869 6.1 3990 6.9 4123 7.8 4257 8.7 4383 9.7
8500 4670 3913 6.0 3942 6.1 3969 6.3 4081 7.1 4194 7.9 4314 8.8 4442 9.8
9000 4945 4136 7.0 4164 7.2 4190 7.4 4295 8.2 4403 9.0
13⁄4"SP 2"SP
Inlet and outlet area: 2.46 sq. ft.
Performance certified is for installation Type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses.
Performance ratings do not include the effects of appurtenances (accessories).
PAGE 14
SIZE 246 BELT-DRIVE
1 ⁄4"SP 1⁄2"SP 3⁄4"SP 1"SP 11⁄2"SP 13⁄4"SP
Wheel diameter: 24"
2"SP 21 ⁄2"SP
Inlet and outlet area: 3.24 sq. ft.
21 ⁄2"SP 3"SP
Inlet and outlet area: 4.09 sq. ft.
2"SP 21⁄2"SP
Inlet and outlet area: 5.76 sq. ft.
Performance certified is for installation Type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses.
Performance ratings do not include the effects of appurtenances (accessories).
PAGE 15
SIZE 366 BELT-DRIVE
1 ⁄4"SP 1⁄2"SP 3⁄4"SP 1"SP 11⁄2"SP 2"SP
Wheel diameter: 36"
21 ⁄2"SP 3"SP
Inlet and outlet area: 7.27 sq. ft.
11600 1596 663 1.2 756 1.8 847 2.5 947 3.5
13200 1816 730 1.5 814 2.2 893 3.0 975 3.9
14800 2036 800 1.9 875 2.7 948 3.5 1019 4.4 1167 6.5
16400 2256 872 2.4 938 3.3 1005 4.2 1071 5.1 1200 7.2 1338 9.8
18000 2476 946 3.0 1005 3.9 1067 4.9 1126 5.9 1242 8.0 1360 10.5 1490 13.4
19600 2696 1021 3.7 1073 4.7 1130 5.7 1186 6.8 1295 9.1 1401 11.5 1513 14.4 1632 17.6
21200 2916 1097 4.5 1144 5.6 1195 6.7 1247 7.8 1349 10.2 1449 12.7 1547 15.5 1651 18.6 1761 22.1
22800 3136 1174 5.5 1215 6.5 1263 7.7 1311 8.9 1408 11.4 1501 14.1 1593 17.0 1682 19.9 1781 23.4 1883 27.1 1987 31.2
24400 3356 1251 6.5 1289 7.7 1331 8.9 1378 10.2 1467 12.8 1554 15.5 1641 18.5 1728 21.6 1815 25.0 1907 28.7 2004 32.8
26000 3576 1329 7.7 1363 8.9 1402 10.2 1444 11.6 1530 14.4 1614 17.3 1691 20.2 1775 23.4 1856 26.8 1940 30.5 2023 34.2
27600 3796 1407 9.1 1439 10.4 1474 11.7 1512 13.1 1592 16.0 1673 19.1 1749 22.1 1825 25.3 1900 28.7 1977 32.4 2057 36.3
29200 4016 1485 10.6 1515 12.0 1548 13.4 1582 14.8 1657 17.9 1736 21.1 1808 24.3 1880 27.8 1950 31.0 2022 34.6 2098 38.7
30800 4237 1563 12.3 1591 13.7 1621 15.2 1654 16.7 1725 19.9 1797 23.2 1870 26.6 1937 30.0 2007 33.6 2073 37.2
32400 4457 1642 14.2 1668 15.6 1696 17.2 1727 18.8 1792 22.0 1860 25.5 1930 29.0 1997 32.6 2062 36.3 2127 40.1
34000 4677 1720 16.2 1745 17.8 1771 19.3 1800 21.0 1861 24.4 1926 28.0 1992 31.6 2055 35.3 2119 39.2
35800 4897 1799 18.5 1822 20.1 1847 21.7 1874 23.4 1931 26.9 1993 30.7 2056 34.5 2119 38.4
21 ⁄2"SP 3"SP
Inlet and outlet area: 9.97 sq. ft.
Performance certified is for installation Type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses.
Performance ratings do not include the effects of appurtenances (accessories).
PAGE 16
SIZE 546 BELT-DRIVE
1 ⁄4"SP 1⁄2"SP 3⁄4"SP 1"SP 11⁄2"SP 13⁄4"SP
Wheel diameter: 54"
2"SP 21 ⁄2"SP
Inlet and outlet area: 16.5 sq. ft.
24000 1455 432 2.2 508 3.7 580 5.4 643 7.2 749 11.4
27500 1668 476 2.8 540 4.47 606 6.2 669 8.2 776 12.7 819 14.9
31000 1880 522 3.6 576 5.2 636 7.2 694 9.3 799 13.9 845 16.4 888 19.0
34500 2092 571 4.5 618 6.3 669 8.3 723 10.5 825 15.4 871 18.0 914 20.8
38000 2304 621 5.6 661 7.5 707 9.6 753 11.8 850 17.0 896 19.8 940 22.7 1018 28.7
41500 2517 671 7.0 707 9.0 747 11.1 790 13.5 880 18.9 922 21.7 963 24.7 1043 31.0 1117 37.8 1182 44.8 1238 51.4
45000 2729 722 8.5 755 10.6 791 12.9 828 15.4 909 20.9 950 23.9 990 26.9 1067 33.4 1140 40.5 1205 47.6 1266 55.1
48500 2941 773 10.3 803 12.6 835 14.9 869 17.5 946 23.1 981 26.2 1020 29.5 1092 36.0 1165 43.5 1231 51.0 1293 58.8
52000 3153 825 12.4 852 14.7 882 17.2 913 19.9 979 25.6 1015 28.9 1051 32.2 1121 39.1 1189 46.4 1255 54.3 1315 62.1
55500 3366 877 14.7 903 17.2 930 19.9 958 22.6 1019 28.6 1051 31.8 1085 35.2 1151 42.4 1217 50.0 1281 58.1 1342 66.4
59000 3578 929 17.4 953 20.0 978 22.7 1004 25.5 1060 31.8 1090 35.1 1121 38.7 1182 45.8 1244 53.5 1307 61.9 1365 70.3
62500 3790 982 20.3 1004 23.1 1028 26.0 1052 28.9 1103 35.3 1130 38.6 1159 42.3 1217 49.8 1275 57.6 1334 65.9
66000 4002 1035 23.6 1056 26.5 1407 29.4 1100 32.6 1147 39.1 1173 42.7 1199 46.3 1253 53.9 1308 62.0 1363 70.3
69500 47215 1087 27.2 1107 30.2 1128 33.4 1149 36.6 1193 43.4 1217 47.1 1240 50.6 1291 58.4 1343 66.7
73000 4427 1140 31.3 1159 34.4 1178 37.6 1198 41.0 1240 48.0 1262 51.7 1284 55.4 1332 63.6 1379 71.8
76500 4639 1193 35.6 1211 38.9 1229 42.4 1246 45.8 1288 53.1 1308 56.8 1329 60.7 1373 68.9
2"SP 21 ⁄2"SP
Inlet and outlet area: 20.3 sq. ft.
31790 1566 407 2.8 466 4.6 521 6.5 575 8.6
35606 1754 441 3.5 496 5.47 546 7.4 594 9.6 695 15.0 743 17.9
39402 1941 477 4.3 527 6.4 574 8.6 619 10.9 707 16.1 752 19.1 797 22.4
43198 2128 514 5.2 560 7.5 604 9.8 645 12.2 727 17.6 765 20.4 807 23.8 889 30.9
46994 2315 551 6.3 593 8.7 635 11.2 675 13.8 749 19.3 786 22.3 824 25.5 898 32.5 974 40.5
50811 2503 590 7.6 628 10.0 667 12.7 705 15.6 775 21.3 809 24.3 844 27.6 912 34.6 981 42.2 1053 51.2 1121 60.5
54607 2690 628 9.1 664 11.6 701 14.5 737 17.5 803 23.5 837 26.8 866 29.8 930 36.9 993 44.4 1061 53.4 1124 62.4
58403 2877 660 10.7 700 13.4 734 16.3 769 19.5 833 25.9 865 29.3 894 32.7 952 39.7 1013 47.5 1072 55.8 1135 65.3
62199 3064 708 12.6 737 15.4 769 18.4 801 21.7 864 28.6 893 32.0 921 35.4 978 42.8 1032 50.4 1089 58.9 1146 68.1
65995 3251 748 14.7 774 17.5 804 20.7 835 24.2 894 31.3 923 34.9 950 38.5 1004 46.2 1057 54.2 1107 62.3 1162 71.7
69791 3438 788 17.1 812 20.0 841 23.4 869 26.9 926 34.2 9583 38.0 980 41.9 1032 49.8 1082 67.9 1131 66.4
73608 3626 828 19.7 852 22.8 877 26.1 904 29.0 959 37.6 985 41.4 1012 45.7 1061 53.8 1111 62.4 1157 70.9
77404 3813 869 22.6 891 25.8 915 29.3 940 32.9 992 41.0 1017 45.1 1042 49.3 1092 58.0 1138 66.8
81200 4000 909 25.8 930 29.1 952 32.6 976 36.4 1026 44.9 1050 49.1 1075 53.5 1121 62.2 1167 71.5
84996 4187 950 29.3 969 32.6 991 36.3 1013 40.3 1060 48.8 1083 53.2 1107 57.7 1154 67.3
88792 4374 991 33.1 1009 36.5 1029 40.4 1050 44.4 1095 53.1 1117 57.7 1141 62.6 1184 71.9
Performance certified is for installation Type B: Free inlet, Ducted outlet. Power rating (BHP) does not include transmission losses.
Performance ratings do not include the effects of appurtenances (accessories).
ELECTRONIC CATALOG
A complete New York Blower Catalog on one CD. No more manual calculations and
bulky product catalogs. A critical tool for all system-designers and engineers who select
and specify air-moving equipment.
PAGE 17
MATERIAL SPECIFICATIONS
Dimensions in inches. Weights in pounds. WR² in lb.-ft.². Tolerance: ±1 ⁄8”
185 203⁄4 254T 251⁄4 215T 185 10 181 ⁄4 195 ⁄8 20 203 ⁄8 211 ⁄4 8 7 ⁄16 x 13 ⁄16
215 203⁄4 256T 251⁄4 215T 215 10 211 ⁄4 225 ⁄8 23 233 ⁄8 241 ⁄4 8 7 ⁄16 x 13 ⁄16
245 23 256T 301⁄2 125T 245 10 243 ⁄8 253 ⁄4 261 ⁄8 261 ⁄2 273 ⁄8 8 7 ⁄16 x 13 ⁄16
275 253⁄4 286T 301⁄2 256T 275 10 273 ⁄8 283 ⁄4 291 ⁄8 291 ⁄2 303 ⁄8 8 7 ⁄16 x 13 ⁄16
325 27 364T 31 215T 325 10 321 ⁄2 337 ⁄8 341 ⁄4 345 ⁄8 351 ⁄2 16 7 ⁄16 x 13 ⁄16
365 27 365T 31 286T 365 10 361 ⁄2 38 383 ⁄8 383 ⁄4 401 ⁄2 16 7 ⁄16 x 13 ⁄16
425 273⁄4 365T 323⁄8 326T 425 10 423 ⁄4 45 45 455 ⁄8 471 ⁄8 16 9 ⁄16 x 1
485 273⁄4 365T 323⁄8 365T 485 10 483 ⁄4 503 ⁄4 51 515 ⁄8 531 ⁄8 16 9 ⁄16 x 1
545 303⁄4* 365T 413⁄8 365T 545 7 55 57 573 ⁄8 577⁄8 591 ⁄2 16 9 ⁄16 x 1
605 303⁄4* 365T 413⁄8 365T 605 7 61 63 633 ⁄8 637 ⁄8 651 ⁄2 16 9 ⁄16 x 1
Arrangement 9 maximums are with or without *Holes spaced equally, straddling centerline. †Sizes 18-60 have slotted holes.
weather cover. *Longer motors will extend
beyond fan inlet; weather covers not available.
Size Y O.D. Size X
INLET BELL INLET VANE
DIMENSIONS 125 21 ⁄8 161 ⁄4 DAMPER 125 9
145 21 ⁄2 19 DIMENSIONS 145 9
165 3 213 ⁄4 165 9
185 31 ⁄4 241 ⁄4 185 9
215 33 ⁄4 281 ⁄4 215 9
245 41 ⁄8 321 ⁄8 245 9
O.D. 275 43 ⁄4 363 ⁄8 275 9
325 53 ⁄4 431 ⁄2 325 9
365 61 ⁄4 481 ⁄2 365 9
425 71 ⁄4 563 ⁄4 425 10
485 81 ⁄4 643 ⁄4 485 10
545 91 ⁄4 73 545 10
Y 605 101 ⁄4 81 X 605 10
PAGE 18
ARRANGEMENTS
DIMENSIONS
Dimensions should not be used
4-M AND 9-M, 4-S AND 9-S, 4-D AND 9-D
ARRANGEMENTS
4-V AND 9-V
L [ID]
AIR
FLOW ARRANGEMENTS S
C 4-R AND 9-R
[roof-mounted]
with exhaust-type R
stack hood. G
GG Mounting flange
Cover Collar
H
Y-size
of slots
WW 6" minimum M
8" recommended AIR 9/16" Dia. Holes
TT
Roof FLOW
Line Z
4 support 1 1/4"
brackets
per unit F F F F B
2"
4 34" L [ID]
[inside] P inside square
DIMENSIONS [INCHES]
GG
Size A B C E F FF* G H J JJ L M P R S T TT U V W WW Y
[max.]
125 83⁄4 21⁄2 25 31⁄4 41⁄2 9 ⁄16 251⁄4 235⁄8 463⁄4 195⁄8 141⁄4 121⁄4 41⁄2 22 14 171⁄4 41⁄2 93⁄8 181⁄2 41⁄4 51⁄2 105⁄8 9 ⁄16x1
145 93⁄4 21⁄2 25 31⁄4 41⁄2 9 ⁄16 261⁄4 26 473⁄4 195⁄8 161⁄4 141⁄4 41⁄2 24 15 191⁄4 51⁄2 103⁄8 181⁄2 41⁄4 61⁄2 115⁄8 9 ⁄16x1
165 111⁄4 21⁄2 32 31⁄4 5 9 ⁄16 271⁄4 27 553⁄4 195⁄8 183⁄4 161⁄4 41⁄2 261⁄8 16 211⁄4 61⁄4 113⁄8 251⁄2 111⁄4 71⁄2 125⁄8 9 ⁄16x1
185 121⁄2 21⁄2 32 31⁄4 51⁄2 9 ⁄16 281⁄2 28 573⁄4 195⁄8 203⁄4 181⁄4 41⁄2 281⁄8 18 231⁄4 63⁄4 123⁄8 251⁄2 111⁄4 8 135⁄8 9 ⁄16x1
215 141⁄2 21⁄2 32 31⁄4 6 9 ⁄16 293⁄4 291⁄2 603⁄4 195⁄8 233⁄4 211⁄4 41⁄2 311⁄8 21 261⁄4 77⁄8 137⁄8 251⁄2 111⁄4 91⁄8 151⁄8 9 ⁄16x1
245 161⁄2 21⁄2 38 31⁄4 7 9 ⁄16 373⁄4 361⁄8 733⁄4 247⁄8 281⁄8 243⁄8 41⁄2 341⁄4 23 293⁄8 9 151⁄2 311⁄2 91⁄2 101⁄4 163⁄4 9 ⁄16x1
275 19 21⁄2 38 31⁄4 8 9 ⁄16 391⁄4 375⁄8 753⁄4 247⁄8 311⁄8 273⁄8 41⁄2 371⁄4 25 323⁄8 101⁄4 17 311⁄2 91⁄2 111⁄2 181⁄4 9 ⁄16x1
325 221⁄4 3 40 41⁄4 9 9 ⁄16 413⁄4 401⁄4 801⁄4 247⁄8 361⁄4 321⁄2 5 413⁄4 26 371⁄4 113⁄4 203⁄8 311⁄2 111⁄2 131⁄4 217⁄8 3 ⁄4x11 ⁄2
365 243⁄4 3 40 41⁄4 101⁄2 9 ⁄16 433⁄4 421⁄4 851⁄4 247⁄8 401⁄4 361⁄2 5 463⁄8 31 411⁄2 131⁄2 223⁄8 311⁄2 111⁄2 15 237⁄8 3 ⁄4x11 ⁄2
425 283⁄4 3 43 41⁄4 12 3 ⁄4 51 475⁄8 911⁄4 43 461⁄2 423⁄4 5 525⁄8 34 473⁄4 15 251⁄2 341⁄2 41⁄2 161⁄2 27 3 ⁄4x11 ⁄2
485 323⁄4 3 43 41⁄4 13 3 ⁄4 54 505⁄8 971⁄4 43 521⁄2 483⁄4 5 585⁄8 40 533⁄4 163⁄4 281⁄2 341⁄2 41⁄2 181⁄4 30 3 ⁄4x11 ⁄2
545 37 3 47 41⁄4 14 3 ⁄4 591⁄4 533⁄4 1041⁄4 453⁄4 597⁄8 55 5 647⁄8 43 60 183⁄4 321⁄4 381⁄2 51⁄4 201⁄4 333⁄4 1x2
605 41 3 47 41⁄4 141⁄2 3 ⁄4 621⁄4 563⁄4 1081⁄4 453⁄4 657⁄8 61 5 707⁄8 47 66 203⁄4 351⁄4 381⁄2 51⁄4 221⁄4 363⁄4 1x2
*FF: Mounting hole size; Sizes 125-485 use two holes per side; Sizes 545 and 605 use three holes per side.
Dimensions X and XX pertain to Sizes 545 and 605 only: X = 171⁄4”, XX = 181⁄4”. Z = 2” on Sizes 125-225, 3” on Sizes 325-605.
The New York Blower Company has a policy of continual product improvement
and reserves the right to change designs and specifications without notice.
PAGE 19
COMPLETE SELECTION OF
AIR-MOVING EQUIPMENT
The New York Blower Company offers thousands
of different types, models, and sizes of air-moving
equipment. Contact your nyb representative for
assistance in identifying the best fan for your
application.
AIR-HANDLING FIBERGLASS
[AXIAL] REINFORCED
For the ideal handling of clean PLASTIC [FRP]
to moderately dirty airstreams. Choice of performance and duty for
Commercial and industrial HVAC, corrosive gas streams. Applications
drying and cooling systems, fume include chemical process, wastewater
extraction, and process-heat treatment, laboratory hood exhaust,
removal are typical applications. and tank aeration.
CUSTOM PRODUCTS
DUST/MATERIAL AIR-HANDLING Designed for unique applications. Variety of configurations,
temperatures, flows, and pressures. Wide range of
HANDLING [CENTRIFUGAL] modifications and
Wide range of duty available Designed for clean to moderately accessories are
with unique fan lines capable dirty gas streams. Commercial available to
of handling light dust to heavy and industrial HVAC, process meet the most
material. Typical applications cooling, light material-conveying, demanding
include dust-collection and heat removal, and dryer exhaust specifications.
high-pressure process along are just a few of the numerous
PROCESS/FAN
HEATING COMPONENTS
ROOF VENTILATORS PRODUCTS Plug fans, plenum fans, wheels, inlet cones,
Including both hooded and upblast ventilators, Industrial-duty steam and housings for a wide variety of OEM
propeller fans, and centrifugal roof exhausters. unit heaters with steam applications. Process/fan components are
These units are ideal for industrial, commercial, heating coils are available used in air-handling units, ovens, dryers,
and institutional applications. for facility heating and freezer tunnels, and filtration systems.
process-heat transfer.