Alternator Generator Manual From Aem
Alternator Generator Manual From Aem
ELEKTROMOTORENWERK
DESSAU GMBH
KAD 30240/E
Edition 01/2014
Read through before initial operation and store carefully for later reference!
Mounting, operating
and maintenance instructions
for series SE and SEH
brushless three-phase synchronous generators
AEM
Anhaltische Elektromotorenwerk Dessau GmbH
Daheimstr. 18
D - 06842 Dessau - Roßlau
After-sales service
Tel.: +49 (0) 340 203 304
Fax: +49 (0) 340 203 311
e-mail: [email protected]
homepage: www.aemdessau.de
ANHALTISCHE
ELEKTROMOTORENWERK
DESSAU GMBH
Danger!
Is used for activities that may cause considerable personal or material damage.
Please read and observe these notes carefully and act particularly cautiously in these
cases. Make other users aware of these notes concerning work safety.
ATTENTION! Concerns the observation of regulations, notes or the correct sequence of working
steps to avoid damaging or destroying the generator, its parts and/or parts of the
equipment.
______________________________________________________________________________________
All work to be carried out on electrical generators such as assembly, connection or maintenance must
only be carried out while the system carries no voltage and is out of operation. Protect the system
against unintended reactivation.
These generators must only be transported, put up, connected, put into operation, maintenanced and operated
by specialized staff being trained to observe the relevant safety and installation regulations. All processes must
be checked by responsible specialized staff. These specialized staff must have been authorized for their activi-
ties by the security system officer (for specialized staff regulations see DIN EN 50110-1 / DIN IEC 60364).
The manufacturer's liability is only maintained if the operating instructions are being observed at any
time!
Table of contents
1 Description................................................................................................................................................... 6
1.1 Regulations and classifications ............................................................................................................ 6
1.2 Design .................................................................................................................................................. 6
1.3 Bearings ............................................................................................................................................... 6
1.4 Cooling system ..................................................................................................................................... 6
1.5 Exciter system ...................................................................................................................................... 6
1.6 Voltage regulator .................................................................................................................................. 7
2 Behaviour during operation and notes on use ............................................................................................ 8
2.1 Excitation, de-excitation ....................................................................................................................... 8
2.2 Setting range for voltages, set-point adjuster ...................................................................................... 8
2.3 Voltage behaviour ................................................................................................................................ 8
2.4 Radio interference suppression ........................................................................................................... 9
2.5 Operational behaviour .......................................................................................................................... 9
2.5.1 Overload capability ....................................................................................................................... 9
2.5.2 Operation with different temperatures of the cooling agent .......................................................... 9
2.5.3 Operation at power factors p.f. < 0.8 ............................................................................................ 9
2.5.4 Underspeed .................................................................................................................................. 9
2.6 Short-circuit behaviour ......................................................................................................................... 9
2.7 Single operation ................................................................................................................................... 9
2.8 Parallel operation ................................................................................................................................. 9
2.8.1 Practical applications .................................................................................................................... 9
2.8.2 Neutral earthing current .............................................................................................................. 10
2.8.3 Synchronisation .......................................................................................................................... 10
2.8.4 Parallel operation with static ....................................................................................................... 11
2.8.5 Parallel operation with compensating line .................................................................................. 11
2.8.6 Parallel network operation with static ......................................................................................... 12
2.9 Emergency operation without regulator ............................................................................................. 12
3 Transport ................................................................................................................................................... 12
3.1 Check after delivery ........................................................................................................................... 12
3.2 Transport locking device .................................................................................................................... 12
3.2.1 Cylindrical roller bearings............................................................................................................ 13
3.2.2 Slide bearings .............................................................................................................................13
3.2.3 Single bearing - and vertical generators ..................................................................................... 13
4 Mounting .................................................................................................................................................... 13
4.1 Installation and connection................................................................................................................. 13
4.2 Electrical connection .......................................................................................................................... 14
4.3 Terminal box and connections ........................................................................................................... 15
4.4 Direction of rotation ............................................................................................................................ 15
5 First start up............................................................................................................................................... 16
5.1 Electrical check .................................................................................................................................. 16
5.2 Measuring of the insulation resistance ............................................................................................... 16
5.3 Mechanical check ............................................................................................................................... 17
6 Maintenance .............................................................................................................................................. 17
6.1 General information ............................................................................................................................ 17
6.1.1 Insulation value and standstill heater.......................................................................................... 17
6.1.2 Maintenance work at the drive .................................................................................................... 17
6.1.3 Preventive maintenance ............................................................................................................. 17
6.2 Lubrication and maintenance instructions for antifriction bearings .................................................... 18
6.2.1 Lubricant information .................................................................................................................. 18
6.2.2 Bearings with relubrication device .............................................................................................. 18
6.2.3 Removing used grease ............................................................................................................... 18
6.2.4 Bearings without relubrication device ......................................................................................... 18
6.2.5 Maintenance instructions ............................................................................................................ 19
6.3 Lubricating and maintenance instructions for slide bearings ............................................................. 19
6.3.1 Oil renewal .................................................................................................................................. 19
6.3.2 Inspection of bearings ................................................................................................................. 19
6.4 Cleaning ............................................................................................................................................. 19
6.5 Drying the winding ..............................................................................................................................19
6.6 Assembly of bearings ......................................................................................................................... 20
7 Supplementary installations ...................................................................................................................... 21
7.1
11 R R31
6.1 7
9.2
8
9
6
S1
10
5
Description of view
1 Description
1.1 Regulations and classifications
The generators are made in compliance with the regulations of DIN EN 60034 / VDE 0530 (Rotating electri-
cal machines), all applicable IEC recommendations and the harmonized EG-standards and order-specific
customized classifications – specially acc. to the most important marine classifications associations.
1.2 Design
The generators consist of
• one inner-pole main machine with salient pole or non-salient pole rotor
• one external-pole exciter with rotating rectifiers for transmission of the exciting power and
• one exciter device with electronic voltage regulator.
Generator, exciter and all other components required for excitation and regulation are designed to form one
compact unit. The casing consists of the stator, the end shields and a hood to serve as a cover for the exciter
unit on the N side. In the standard design, the terminal box is at the top and can be turned by 180°. Both
terminal box and casing have specially designated earth connection points.
1.3 Bearings
The system is equipped with spring-loaded deep groove ball bearings (standard mode), cylindrical roller
bearings or plain bearings as defined in the order.
In case of increased loads on the bearings, a cylindrical roller bearing is installed on the D side while a deep
groove ball bearing is on the N side to serve as counter bearing or, if necessary, a double bearing made up
of a cylindrical roller bearing and a deep groove ball bearing.
Generators in vertical design have an angular contact ball bearing to serve as counter bearing. All bearings
are dust-proof, are permanently lubricated up to shaft centre height 315 mm and are provided with relubrica-
tion devices with grease quantity regulation on both the D and the N side as from shaft centre height
400 mm. Relubrication devices for shaft centre height 315 mm are subject to special arrangements.
NOTE For bearing configuration observe Data sheet “Bearings” and lubrication- and maintenance
instructions observe section 6.2.
The load current flows through the current transformer [7]. When load is put on the generator, the secon-
dary current of the current transformer [7] is added to the choke current. After rectification in the stationary
rectifier stack [8] – a six-pulse bridge circuit –, this alternating exciter current flows to the stator winding [4] of
the exciter.
In order to protect the diodes against voltage peaks, both the stationary rectifier stack [8] and the rotating
rectifier stack [5] are equipped with varistors [S1], [S2].
Choke current and secondary current of the current transformer are adjusted such as to permanently main-
tain a generator voltage of approx. 10 % above the rated generator voltage while the generator rotates at its
rated speed and the voltage regulator is disconnected.
Every time the rated generator voltage is exceeded, the voltage regulator (AVR) [9] periodically switches on
step-down resistor R31 that is located in parallel to the stator winding of the exciter [4]. This ensures that the
teminal voltage of the generator is kept at the value set by the set-point adjuster.
NOTE The chosen tappings of the winding to choke and current transformer have been optimally
adjusted to the generator in the manufacturer's test shop. You should therefore always con-
tact the manufacturer prior to making any changes.
NOTE: Check the regulator documentation supplied with the machine regarding operation and ad-
justment of the regulator!
NOTE If the generator voltage deviates from the permissible operating voltage range of the regula-
tor, the regulator will be either connected to tappings of the stator winding or special measur-
ing transformers. For generator voltages higher 1 kV the AVR is connected to a special
measuring transformeras well as decoupled from the operating voltage of the generator.
Danger!
Only trained specialized staff are allowed to change settings using a suitable tool.
Observe during all setting and other work to be carried out on exciter and regulator
that all components supply voltage potential.
Danger!
Measure the generator voltage during the excitation process. Remove the external
voltage source immediately, when the generator voltage rises. Use a diode to be pro-
tected against Danger of reverse current!
If self-excitation of the generator does not work, excitation can be induced by briefly applying an external
voltage (6 or 12 V battery) to terminals X100:3/+ (battery plus), X100:4/- (battery minus) in the terminal box
of the generator (figure 1).
Danger!
After de-excitation and while the drive is running, there is a residual voltage of up to
10 % of the network voltage on the generator terminals. Special notice for generators
with voltage more than 1 kV.
Use a contactor or suitable switch to produce a short-circuit between terminals X100:3/+ and X100:4/-.
Current load on the contacts is < 10 A (figure 3).
T / °C 30 35 40 45 50 55 60
PS / PN 1.06 1.03 1.00 0.96 0.92 0.88 0.84
2.5.4 Underspeed
Particular protection of the generator, the exciter or the regulator against underspeed of the generator drive
(e.g. during warm-up) is not required. Voltage is maintained constant down to speeds of approx. 90 % of the
rated speed. Below this value, the voltage is reduced approximately proportionally to the speed so that every
speed is admissible in no-load without time limitation.
• Parallel operation with static with other generators as long as these provide parallel operation features
and if practically the same static voltage curves with falling characteristics can be set for all generators;
• Parallel operation with compensator circuits of generators of the same type;
• Parallel network operation either with non-regulated power factor in static mode or with regulated
power factor according to regulator type with power factor regulation.
For parallel operation of several generators, reactive power distribution as well as current and power output
variations must be within the range of applicable regulations. Prerequisites for this kind of operation are that
generator drives, and their speed governors in particular, are designed correspondingly providing the same
P range (speed drop between no-load and full load operation) or that an active power distribution propor-
tional to the power output is ensured by an automatic active power distribution installation.
Measure Effect during Main effect during
single operation parallel operation
Voltage set point of the gen- Over-excited: generator supplies more
Ï Generator voltage Ï
erator reactive power
Under-excited: generator supplies
Generator statics Ð ----------- less reactive power
Voltage set point of the gen- Generator voltage Ð Over-excited: generator supplies less
Ð
erator reactive power
Under-excited: generator supplies
Generator statics Ï ----------- more reactive power
Rated speed of the drive Ï Frequency Ï Generator supplies more active power
Rated speed of the drive Ð Frequency Ð Generator supplies less active power
NOTE Wrong distribution of active power (kW indicator not proportional to power output) is always
caused by the speed regulation of the generator drives.
Wrong distribution of reactive current (kW distribution o.k., different current distribution) is
caused by the voltage and static settings of the regulator.
2.8.2 Neutral earthing current
In parallel operation there are not neutral-earthing currents normally while using of same generator types of
one manufacturer.
Connecting the generator star point to the star points of generators of another type or to the network earthed
neutral can cause compensation currents of mainly three times the network frequency to flow in the neutral
earth conductor that have been caused by different voltage curve lines of generators and mains network.
Neutral currents of up to 40 % of the rated current are admissible unless other values have been defined.
Reducing the neutral current can be achieved by inserting a special type of choke coil in the network
switchboard (please contact the manufacturer).
2.8.3 Synchronisation
The generators can be synchronized by manual synchronisation, automatically quick synchronisation or start
up synchronisation (please contact the manufacturer).
The following conditions must be observed for synchronisation processes:
• almost identical frequency of the two voltage systems Δf ≤ 0.2 Hz
• almost identical terminal voltage of the generator and mains network, admissible difference < 6 %
• identical phase sequence of the two voltage systems
• closing of switching contacts at a phase angle of < 15 degrees in relation to the zero crossover of the dif-
ference voltage of the two voltage systems.
ATTENTION! Wrong synchronisation causes extremely high electrical and mechanical loads on the
generator which must be avoided under all circumstances.
Manual synchronisation
Use the set-point adjuster to set the generator voltage to the network voltage. After setting smallest fre-
quency and phase differences possible by means of a synchronoscope, the generator can be switched on.
To avoid the occurrence of inverse power after switching on the generator, the generator frequency should
be about 0.2 Hz above the network frequency.
Quick synchronisation
Use an electronic synchronisation device to adjust the system to smallest possible voltage, frequency and
phase differences automatically. The generator will be switched on considering that time element (switch) is
in zero crossover range of the difference voltage.
2.8.4 Parallel operation with static
ATTENTION! Check whether the jumper between terminals 4 and 5 of the regulator have been re-
moved.
Depending on current and power factor, the generator voltage characteristics show a decline. The voltage drop
can be set on the regulator (max. 8 % at p.f. = 0). The manufacturer sets the static to approx. 2 % (in relation to
no-load voltage) at rated current and a power factor of p.f. = 0.8. Constant voltage during parallel operation de-
pends on the static setting. If static setting and static voltage characteristics are nearly the same, the reactive
power (in relation to the rated power of the corresponding generator) is distributed proportionally.
ATTENTION! Make sure to do a generator adjustment before starting operation.
Only specialized staff must do these steps.
Check whether all drives have the same percentage value for speed drop between no-
load speed and full speed while in single operation.
Use the set-point adjuster to adjust the equal values of no-load voltages (±1 V) at all
generators. For this setting please use the same meter.
Put rated power at rated power factor on the generators in single operation if possible
and check whether an almost identical voltage drop can be observed for all generators.
If you find larger differences, the static potentiometer must be readjusted. Static values of 2 – 3 % at rated
power and rated power factor are sufficient for stable parallel operation. This test must not be made with just
using active power as this renders the static inefficient.
NOTE Proceed as follows to make a supplementary test if only active power operation is possible
when changing the setting:
1. Connect the blue cable from phase U to W and the brown cable from phase V to
phase U on the choke terminal strip [6.1].
2. Put load on the generators.
3. The voltage drop corresponds to static setting at p.f. = 0.5 and normal switching condi-
tions.
4. While corrections of the static adjustment using the equivalent circuit is to be noted that
the static adjustment is made with p.f. = 0.5. The static adjustment will be accordingly
smaller with p.f. = 0.8 therefore.
5. Reconnect all devices after the setup procedure.
NOTE For synchronisation processes the generator voltage have to be approx. 1 % higher than the
network voltage is.
The static device lowers the generator voltage if the reactive power increases. Greater static causes small
current changes if the network voltage changes. We recommend setting the no load voltage higher than the
highest network voltage occurring at the feeding point to avoid reactive current absorption by the generator
from the network.
ATTENTION! Observe the neutral earthing current (section 2.8.2) and synchronisation conditions
(section 2.8.3).
Danger!
The resistor is under network potential and must therefore be protected against touch-
ing.
The resistor can be used to set the rated generator voltage in the no-load of generator.
The voltage can be kept in the required range by readjustment under load. The voltage tolerance value is
approx. –5 % without readjustment.
3 Transport
ATTENTION! Only use suitable attachment devices (ring bolts, eye bolts) for transportation. The at-
tachment elements that are part of the generator are only made to carry the genera-
tor's own weight.
Check whether screw-type eye bolts are firmly screwed in.
It is not allowed to sling parts of the transport gear around shaft ends, pillow blocks,
sleeves, hoods or similar elements as this could cause considerable damage.
If a generator or unit is transported on its base plate you must use the attachment de-
vices provided in the base plate. Units that must not be transported in one piece are
marked by a corresponding notice on the base plate.
NOTE When transporting parts of disassembled generators ropes for lifting armatures should not
be slung around the shafts bearing site. If no other way of transporting the element is possi-
ble, the shaft must be sufficiently protected.
4 Mounting
Danger!
Observe general security information (see page 2)!
• Use taring screws for aligning the generator. The final installation position is to be fixed by sheet metal
put underneath the generator. Bolt the generator up if necessary (holes are drilled into place already).
• When assembling generators that come to you in several pieces, you have to make sure only to use
parts that have been marked as belonging together.
• The generator must only be assembled and operated according to design (see rating plate).
• Always observe the connection conditions for water quantity, pressure and temperature at the inlet given
in the data sheet for water coolers (see appendix).
• If you are working with a pipe connection with self-ventilation, the pressure drop indicated by the manu-
facturer must in no case be exceeded due to length and layout of piping.
• Make sure to keep sufficient distance to walkways and operating stands as the temperatures of exhaust
air or surface can be up to 80 °C.
ATTENTION! Provide information signs or protective railing.
Coupling
The generator and bearings have been carefully mounted, aligned and completely tested by the manufacturer.
NOTE The rotor is dynamically balanced. The balancing state is marked in accordance with DIN
ISO 8821 at the D-side shaft-end.
Coupling of generators in two-bearing design to the drive unit should be realized by an elastic clutch.
Coupling of generators in single-bearing design: Observe the special documentations in appendix!
Pay attention to absolutely!
Putting on couplings or pulleys
It is not necessary to remove the corrosion protection at the shaft ends during installation.
ATTENTION! Make sure to use a mounting device for mounting couplings or pulleys.
A suitable means for this is the centring drill hole in the shaft end. When putting in the clutch you have to
make sure that the shaft of the drive mechanism and the shaft of the machine to be driven are perfectly
aligned. Misalignment must be not greater than 0.05 mm. To avoid angle errors, the gap between the two
halves of the clutch must be measured at a 90° offset. The difference must be no greater than 0.05 mm.
If elastic bolts or denture clutches are used you must make sure to have congruent separations of the two
halves of the clutch. Changing the half clutches round is not allowed.
ATTENTION! Because of the danger of damages occurring on the bearings, hammering or knocking
the driving elements on is not allowed.
Pulleys are only allowed for generators of the type IM C2 as special feature design; they too must be dy-
namically balanced. Furthermore you must make sure to carefully align the two disks making up one pulley,
i.e. both shafts must be parallel to each other and the connecting line between the two disk centres must be
at a 90° angle to the shafts.
ATTENTION! Check the pull of the belt. For information about the max. admissible belt tension
please contact the manufacturer. Increasing the pull of the belt shortens the service-
able generator life.
Figure 4: Dimension X
ATTENTION! Connect the generators to earth using the corresponding protective earth terminals
inside the terminal box and on the foot of the generator stand.
Tightly set all connections to avoid high transitory resistances. At the same time permissible tightening
torques have to be held (according to DIN 46200):
Thread M 10 M 12 M 16 M 20
Tightening torque in Nm 10 15.5 30 52
Align the cable lugs at the largest possible distance to other connecting points and to the casing.
ATTENTION! Do not fall below the following distances between live components and to the case:
Round terminal bolts of low voltage generators (<1 kV) have not been designed to serve as conductors for
the rating current. You must therefore always make sure to put cable lug on cable lug (figure 5). If more than
three cable lugs are connected to one terminal, you should use a flat nut in between. Arrangement of cable
lugs, nuts and counter nuts is to be made according to the illustration below.
Terminal bridge
Wrong!
Figure 5: Cable lug arrangement inside the terminal box.
NOTE Generators that have been made to work only in one direction of rotation, this direction is
marked by an arrow on the generator, the ventilator or on the rating plate.
Contact the manufacturer if you want to change the direction of rotation of this type of
generator!
5 First start up
When putting the generator into operation for the first time or after long downtimes, the following checks
have to be made.
Danger!
Protect the system against unintended reactivation!
Earth the windings before and after the measuring of insulation at least 10s.
Don’t touch the windings before!
Measuring instrument: The measurement should be effected by a standard measuring instrument. Observe
exactly the operating instruction.
Measuring voltage: Observe the table below.
Measuring time: The measuring time should be 1 min at least.
ATTENTION! Disconnect the internal radio interference protection capacitors [10] before measuring
of the insulation resistance value.
The capacitors are attached to the exciter and connected to the generator frame via a cable. Disconnect this
line and re-connect it after measuring.
The following table serve to estimate the insulation resistance. Always estimate the insulation resistance (Ris) of
the cold generator, i.e. on room temperature (approx. 25 °C). “Warm-values“ are not to comprehend clearly.
The minimum insulation resistance on room temperature of a brand new generator or a repaired generator
with a new winding you find under item 1. of the next table.
This value can drop by virtue of transportation and storage under bad environmental conditions. In this case
the insulation is not damaged. Generators, which stand still under bad environmental conditions for a long
time and do not have a standstill heater (dew on the windings), can be started-up, so long as the insulation
resistance of the cold generator do not drop under the values like shown in item 2. of the next table.
Drop the insulation resistance under values of item 2, the windings must be dried. Under special operating
conditions the windings must be cleaned before drying (for that look to the section 6.5 “Drying the winding“).
The insulation resistance must rise after a short operation of the generator. Under normal transportation,
storage and operating conditions the insulation resistance of the cold generator must not drop under the val-
ues in item 2.
NOTE To avoid environment pollution as a succession of transport damage the oil is drained out of
the bearing during transport by slide-bearing generators.
At generators with slide bearings the prescribed amount of oil (see data sheet) have
to be filled up absolutely! Make sure that the oil has the correct viscosity! A list of re-
commended oils is part of the documentation of slide bearings.
Then turn every generator rotor manually and listen to monitor it.
6 Maintenance
6.1 General information
Maintenance activities include bearings, cleaning the generator and the cooling air filters, if exist.
The following must be done according to operating condition but at least once every year:
• check the terminal boxes and terminals for cleanliness and corrosion
• check the electrical connections for tight fit. Maximal torques see section 4.2
• check the bearings for leckages of grease or oil
• check the cooling air circuit for cleanliness and sufficient operability.
6.1.1 Insulation value and standstill heater
Regularly check the insulation value of generators that are not used permanently or used in particularly
damp environments (see section 5.2 "Measuring of the insulation resistance").
If the generator is equipped with a standstill heater, then the heater bands and corresponding switching ele-
ments must be checked every six months.
6.1.2 Maintenance work at the drive
Danger!
In case of maintenance at the drive the short-circuited generators have to be de-ex-
citated absolutely according to section 2.1 by short-circuiting of the terminals
X100:3,"+" and X100:4,"-".
Earth-leakage circuit breaker and terminals for de-excitation should be interlocked.
NOTE Medium-high-voltage generators (type SEH) have to be short-circuited by an earth-leakage
circuit breaker in case of maintenance. The generator will be damaged if it will be driven in
this operation because it can be excited up to sustained short-circuit current.
6.1.3 Preventive maintenance
Depending on operating conditions, preventive maintenance is to be carried out every 15 000 to 24 000 h by
experienced and specialized staff.
Maintenance activities include cleaning the inside of the generator, checking bearings and close fitting of the
end-wire binding bands and, if necessary, applying a new coat of finishing varnish.
Check the alignment of generators and the safe connection of all screws.
If new sort of grease will be used (with same consistency class and saponification also) the bearings should
be regreased 3 times with half regreasing periods.
In case of longer downtimes or storage please remember that the maximum storage time of these greases
is 36 months. So we recommend to regrease brand new generators too with half regreasing periods after
longer standstill time.
Check the proper functioning of the generator before and after each lubrication.
6.2.2 Bearings with relubrication device
ATTENTION! Lubricate the bearings only with the generator running.
Relubrication is done via the button head lubricating nipple in accordance with DIN 3404. All lubrication
points are marked on the generator. Information plates and the data sheet „Antifriction bearings” tell you
about lubrication dates and grease quantities.
In case the grease indicated for generators to be relubricated or another grease of the same type of saponi-
fication is not available, open the bearing covers and remove the grease. Then clean the bearing and relu-
bricate using a grease of a similar quality.
NOTE Avoid mixing greases of different type of saponification for roller bearing lubrication, because
the greases decrease their lubricity in this case.
NOTE Extending the recommended lubrication periods causes danger to the bearings and may lead to
a loss of bearing sealing usually provided by the grease thus allowing dust to enter the bearing.
By generators with low operation periods (e.g. emergency generators) it will be recommend
to regrease yearly with reduced grease quantity. A periodical putting into operation, at least
every three months, is important that grease in bearing will be worked through.
The used grease is automatically collected in a chamber underneath the bearing. The grease collector must
be emptied after three lubrication cycles unless otherwise stated. The grease collectors are marked by par-
ticular signs on the generator.
6.2.3 Removing used grease
Danger!
Remove the used grease only while the generator is standing still.
• It is mandatory to observe the dates for removing the used grease, because too much increased grease
quantities would lead to an impermissible warming-up of the bearings.
• In some generator types, the used grease comes out of a covered gap in the bearing lid, accumulates
around the end shield and must be removed from there after several lubrication cycles.
• Generators of type V1 are equipped with grease pipes on the D and the N side. To clean these, you re-
move the plugs on either side and push the used grease out to the left or right using a round stick
(Ø approx. 25 mm).
ATTENTION! Make sure to dispose of the used grease in an environmentally friendly way.
6.2.4 Bearings without relubrication device
Unless otherwise marked or agreed, generators up to type 250 are equipped with bearings with lifetime lubri-
cation. The bearing producer calculate (appr. 20 000 h as life time. This value can fluctuate very much de-
pending on operating case (pollution, vibrations, temperature). So it will be recommended to open bearing
covers after 2 years operation and remove waste grease. The bearings have to be regreased.
For the bearings used see the Data sheet “Antifriction bearings”.
6.2.5 Maintenance instructions
Bearings have to be checked regarding to unusual sounds and admissible bearing temperatures periodically.
If there are SPM measuring nipples or vibration pickups, then the values measured must be analysed at the
same time intervals. To remove the hood or the end shield of bearings with relubrication device, you have to
separate the lubrication tube from the screw connection (see 6.6 “Assembly of bearings”).
6.4 Cleaning
Use a vacuum cleaner or bellows to remove dust from the generator, do not use pressurized air containing
oil or water. Make sure not to blow any dirt or dust into the inside of the generator. Do not use sharp tools
for cleaning!
If the winding is very dirty (oil vapours or grease squelching out of the bearings), use industrial solvent-based
cleaners (petroleum ether or diluter on petrol basis) or other aqueous industrial cleaners or emulsion clean-
ers to remove the dirt. Make sure that the cleaners do not dissolve paint coats or plastic materials.
ATTENTION! Provide sufficient ventilation when cleaning the generator and make sure not to let
any cleaning agents get into the waste water. Observe the environmental protection
regulations.
Cleaning cooling air filters
The filtering effect of the filter is achieved by a metal filter or layer of fiber filter element on the air inlet side.
Corresponding to operating conditions, clean the filter at regular intervals or after the thermal safety device
has reacted:
• Remove filter plate
• Shake or blow off loose dirt
• Wash the layer of fiber filter elements using water and solvent-free agents, then dry
• Wash metal filters with petroleum ether or similar solvents, blow through with air and then lubricate with
filter oil.
Check the heating up of the casing or measure the temperature of the winding by ther-
mocouples or a thermometer.
Selection of the drying method depends on the type of generator and the possibilities provided at the loca-
tion. Redrying can be achieved by warming up the winding using direct current (e.g. welding machine). The
current intensity used should not exceed 60 % of the rated current indicated on the performance plate. En-
sure power feed to two phases. Minimum drying time is 1 hour.
Generators with enclosed ventilation (IP 23) can be dried with warm air ventilators. Required drying time is
several hours. Generators can be dried while the generator is running and short-circuited stator winding. The
short-circuit can be produced immediately via the switch on the switching panel such that the stator current
can be monitored by an ammeter. Otherwise you have to measure the current in the generator directly. To
do so produce external excitation of the generator by an adjustable DC source.
Connection is made to terminals X100:3 (+pole) and X100:4 (-pole) inside the terminal box. Required setting
ranges are up to approx. 24 V for generators up to frame size 315 and up to approx. 48 V for generators up
to frame size 710. Required current intensity is < 5 A.
After drying you must measure the insulation resistance.
Drying conditions
• Keep check-up records with values measured!
• Always dry the winding slowly and thoroughly.
• The maximum drying temperature is 75 °C.
• Continue the drying process until the insulation resistance increases considerably and arrives at the
minimum value.
• Ensure condensation drain by opening terminal box and / or covers.
• Put the generator back into a normal operating state after drying.
2. Pull Aassembly:
Push tube right in
Lubricating tube
• Disconnect the cables connected to terminals X100:1 to X100:6 inside the terminal box and pull the ca-
ble through and in.
• Disconnect cables U, V, W from choke terminal strip or rectifier plate for exciter supply.
• Disconnect the primary winding cables of the current transformer.
• Carefully mark the primary cable of the static current transformer; during assembly observe direction K-L
of current flow (see functional diagram).
• Disconnect cables of the rotating rectifier stack.
• Loosen carrier disk and remove the rotating rectifier stack.
• Line the generator air gap.
NOTE Set the rotor such that one pole points down
• Disassembly the bearing components, bearing lid, labyrinth box, excenter and remove the end shield in-
cluding the entire exciter unit after unscrewing the screws in the ring around the stator casing.
NOTE Use the attachment screws to remove the end shield from the centring device by screwing
them into the threads provided for this purpose.
• Pull out the old bearing and put in the new one after warming it up to 100 °C (water test).
• Lubricate the bearing. Completely fill the bearings to the rim with grease.
• Fill the gap between bearing lid and shaft with grease leaving the bearing lid empty.
Proceed in opposite direction for assembly making sure in particular to carefully connect all cables according
to the enclosed wiring diagram.
D-side
• Line the generator air gap from the N-side.
• Disassemble all bearing components and the end shield and change bearings as described for the N-side.
7 Supplementary installations
These only exist in customized solutions upon special request.
NOTE This protective systems only indirectly protects rotor and other windings.
7.1.2 Thermal bearing monitoring
According to agreement measuring and monitoring bearing temperatures are possible. To realize these op-
tions, sensors on the basis of PTC thermistors or Platinum measuring resistors and / or thermometers are
used after pressure-resistant mounting in corresponding screw-type casings.
The actual casing used depends on the corresponding end shield, crown or the bearing to be monitored.
Please refer to the wiring plan for the sensor connections inside the terminal box.
7.1.3 Thermal cooling air monitoring
For cooling air monitoring of generators with water/air cooler, air/air cooler or pipe connection, there is the
option of installing a Pt100 sensor and / or a thermometer at the cold air end (inlet).
If agreed, another sensor and / or a thermometer can be connected to the warm air side (outlet).
7.1.4 PTC resistor temperature probe (PTC thermistors in acc. to DIN 44081)
In this case, the sudden increase in thermistor resistance occurring in the range of ± 5 K of rated reaction
temperature is used for temperature monitoring. In an electronic module, this change in resistance is con-
verted to a signal which can then be used for switching off the generator or for outputting a warning.
PTC resistors with rated reaction temperatures between 90 °C and 170 °C are used.
Type designation includes the rated reaction temperature.
PTC thermistors in accordance with DIN 44081 can be exchanged or switched in series.
A typical stator winding has one PTC thermistor per phase. The stranded hook-up wires of these three ther-
mistors are series connected. It is possible to install a second set of thermistors which is then used in con-
junction with a second module either as reserve, for two separate windings or for thermal warning.
7.1.5 Platinum measuring resistors (Pt100 sensors in acc. to DIN EN 60751)
In this case, temperature monitoring is based on the linear change of Pt100 sensor resistances in a wide
temperature range. In conjunction with suitable temperature limit switches or Pt100 temperature measuring
circuits they can be used for both automatic triggering at certain preset temperatures or for permanent
measurement, control or indication of temperatures.
Pt100 sensors can be installed in windings like thermistors.
Each sensor is connected separately to the terminal panel and must be analyzed separately.
Special Pt100 slot resistance thermometers can be installed in the generator slots according to agreement.
This allows very precise checking of the winding temperature and the sheet metal package even in very in-
accessible places.
Temperature control of components, cables and bearings in particular is possible by using surface sensors.
NOTE Create a four-wire connection by later adding two additional terminals in conjunction with a
terminal bridge or parallel terminals for the current and voltage wires (figure 7).
KTY sensors may be replaced by the same types only. If you inform us of the generator number, we will no-
tify you of the precise KTY type designation.
Danger!
Switch off the standstill heater via the control centre before opening the terminal box!
Check whether the system is in a voltage-free condition.
The following heating output is customarily assigned to the shaft centre heights:
Shaft centre height in mm 225 - 250 315 - 400 450 - 500 560 / 630 710
Heating output in W 84 150 300 520 780
The connecting terminals are marked and located in the generator's terminal box.
The standard supply voltage is 230 V one-phase unless otherwise agreed. Connect the standstill heater to
the relevant terminals in the terminal box according to the current switching diagram.
Î For specific heater output and voltages : see information sign in the terminal box
ATTENTION! Activate the standstill heater only after switching off the generator.
Provide suitable means to avoid unintentional operation of the standstill heater while
the generator is running (locking mechanism).
8 Storage instructions
The generators should be stored vibration-free in a dry room free of dust. In this case, special packaging is
not required. Otherwise, the generators must be kept in plastic foil with humidity absorbing material. Provide
covers to protect it against rain and sun.
ATTENTION! Manually race the armature at regular intervals to avoid damage to the bearing.
NOTE Armatures of generators provided with transport locking devices are not raced as long as the
transport locking device is applied and functional. Observe the instructions given in section 5
prior to first operation
9 Troubleshooting
ATTENTION! Immediately switch off the drive if a failure occurs.
Carefully inspect the generator while in a voltage-free condition.
Danger!
While measuring or setting parameters with the generator running, you must be aware
of the fact that all unprotected terminals may carry very dangerous voltages and that
they are in immediate proximity to rotating parts. The generator must therefore be
locked to avoid contact by unauthorized persons.
ATTENTION! Check-ups of exchanging of parts must only be carried out by trained specialized staff
in accordance with IEC 60364 observing all applicable regulations of health care,
safety at work and fire protection.
The references to components correspond to the connection diagram of the generator.
9.1 Thermal and mechanical problems
Generator too hot:
• Check cooling air inlet and outlet and air filter and remove obstructions if necessary
• Check whether the values given on the performance plate are kept (stator current, voltage, power factor,
unbalanced load)
• Check the coolant temperature
Unsteady generator operation:
• Check alignment of clutch and generator
• Check clutch status
• Check temperature of and noise made by bearings
• Exclude influences caused by the drive (e.g. ignition failures)
• Check whether all armature components are firmly attached
Screws: 5 Nm
Terminals: 3 Nm
Figure 8: Test instrument setting for stat. rectifier Figure 9: Test instrument setting for rot. rectifier
ATTENTION! Carefully observe the terminal assignment plan. Wrong connections damages the
generator.
NOTE The system may have to be readjusted (voltage, static, stability) after replacing the regulator.
9.6 Problems overview
ATTENTION! For generator voltages < 1 kV measure the remanence voltage on the main terminals
only! For generator voltages > 1 kV measure the remanence voltage on the terminals
of auxiliary winding terminal X 020!
For safety reasons, you must interrupt the connection between stationary rectifier [8]
and stator winding [4] of the exciter before measuring the remanence voltage.
Do not touch voltage-carrying parts, as the remanence voltage is usually in the range
between approx. 5 to 10 % of the rated voltage.
Problem: Generator voltage too high and not adjustable during operation
Action Consequence Cause of failure, further actions
Check connection of external set-
point adjuster
Check function of step-down resis- Generator voltage - Step-down resistor R31 or connections defect
tor R31 is approx. 1.1 x UN - Replace resistor, repair line
- Regulator problem
Generator voltage - Replace reg. or go into emergency operating
does not change mode (section 2.9)
- Check air gap of choke [6] If the yoke is loose, set the air gap such that the
- Yoke and shims must be firmly systems sets itself to approx. 1.1 x UN at rated
attached speed and without voltage regulator
Check connection of static current Remove jumper from static input of the regulator
transformer [11] and direction of ro- if it is in
tation (see circuit diagram) Connect up properly
Measure transformer current under
Current = 0 A Replace static current transformer [11]
load
Check performance-dependent dis-
Readjust speed regulator
tribution of active load
Check setting of no-load voltage of adjust no-load voltage on the regulator or via ex-
all generators (section 2.8.4) ternal set-point adjuster
- Readjust static on the regulator for the genera-
tor
- Observe in any case: if one generator accepts
too much reactive power during parallel opera-
Check whether static setting is even tion with static and increasing load, then you
must increase its static setting or reduce that of
the other generators (do not fall below about
2 % at rated current and p.f. = 0.8)!
(section 2.8.4)
For operation with compensating
line: Check the connection between
Check switch contact
generator terminal X100:3 – X100:4
and compensating line
Problem: Generator voltage too high or too low when putting into operation
Action Consequence Cause of failure, further actions
Check speed of drive system
Voltage o.k.
Modify voltage set-point Voltage setting Check connection of external set-point adjuster
range insufficient
ATTENTION! Measure the generator voltage before trying to find the problem.
Action Consequence Cause of failure, further actions
- Check stat. rectifier [8] (section 9.3),
replace if defect
- Check rot. diodes [5] and varistor [S1],
replace if defect
No generator exci- Check current forwarding of rot. exciter winding
tation [2] on "+" and "-" bar of the rot. exciter [5]
- Check current forwarding of exciter winding [4]
Connect battery via reverse current of the exciter,
diode ("+" pole to X100:3 and "-" to do so disconnect wire 3 from X100:3,
pole to X00:4) X100:4 and measure between X100:3 – X100:4
Generator excita- - Remanence voltage was too low
tion to rated volt- - Immediately disconnect battery
age
Without battery - Check stat. rectifier [8] (section 9.3),
support voltage replace if defect
breakdown of gen- Check current forwarding of choke [6] between
erator voltage UVW and XYZ
10 Spare parts
The following information is required for ordering spare parts:
What? Where?
Name of part Enclosed spare parts list
Generator type Rating plate
Output ”
Voltage ”
Serial number of generator (absolutely necessary!) ”
Carry out dynamic balancing after replacing any rotating parts (with the exception of the rotating rectifier [5]).
Bearing configuration - see data sheet “Bearings”
Spare parts and names of parts - see appendix