ROOM TEMPERATURE

ENERGY SYSTEMS INC SENSOR


TSRC Series
The TSRC series is an attractive, low profile
enclosure that incorporates a precision
temperature sensor used to monitor room
temperatures. Additional options are available
that include setpoint adjustment, manual
override, fan speed and LCD

SPECIFICATION:
Sensing Element ...............Various thermistors and RTDs
Sensor Accuracy ................Thermistors: ±0.2˚C (±0.36˚F),
0 to 70˚C (32 to 158˚F)
Platinum RTD’s: ±0.3˚C (±0.54˚F)
@ 0˚C (32˚F)
Nickel RTD’s: ±0.4˚C (±0.72˚F) PART NUMBER SELECTED
@ 0˚C (32˚F)
Operating Conditions .....0-50 °C (32-122 °F),
0-95 %RH non-condensing
Wiring Connections .........Screw terminal block (14 to 22 AWG)
Sensor only - Pigtail, 2 or 3 wire
Enclosure .............................Wall mount enclosure,
White ABS - IP30 (NEMA 1) PRODUCT SELECTION INFORMATION:
84 w x 119 h x 29 d mm (3.3” x 4.7” x 1.15”) MODEL Product Description
OPTIONS:
TSRC Room Temperature Sensor
Override Switch
Switch Type ........................Front panel, momentary pushbutton, CODE Sensor
N.O., SPST, 50 mA @12 Vdc 2 100 Ω Plat. IEC 751, 385 Alpha, thin film
Fan Speed Switch
Range ...................................Off, Auto, Low, Medium, High 5 1801 Ω, NTC Thermistor, ±0.2 C
Signal ....................................Resistance: 0, 2, 4, 6 and 8 KΩ 6 3000 Ω, NTC Thermistor, ±0.2 C
standard (Custom ranges available) 7 10,000 Ω, type 3, NTC Thermistor, ±0.2 C
8 2.252K Ω, NTC Thermistor, ±0.2 C
Setpoint Slide Pot 12 1000 Ω Platinum, IEC 751, 385 Alpha, thin film
Range ...................................Front panel pot as resistive output, 13 1000 Ω Nickel, Class B, DIN 43760
0-10 KΩ standard 14 10,000 Ω, type 3, NTC Thermistor, ±0.2 C c/w 11K shunt resistor
Custom spans available..1K, 2K, 5K, 10K or 20K Ω 20 20,000 Ω, NTC Thermistor, ±0.2 C
Occupied Input 24 10,000 Ω, type 2, NTC Thermistor, ±0.2 C
Signal Type .........................Digital input, 0/5 Vdc standard, active low
Action ...................................Causes “OCC” segment to light on LCD CODE Options (Multiple selections can be made)

LED Input P 0-10K linear slide pot for set point control
Signal Type .........................Active high, low or 2-wire, S Exposed push button momentary switch - N.O.
5 V current limit standard C 3-digit LCD temperature indicator ˚C / ˚F selectable
LED Colors ..........................Red, Green or Yellow F Fan speed switch (Auto, Off, Low, Mid, High)
Power Supply ....................5 Vdc standard, 10 Vdc or 24 Vdc optional Y Yellow LED (n/a if AC option selected)
R Red LED (n/a if AC option selected)
LCD Display G Green LED (n/a if AC option selected)
Power Supply ....................12-24 Vdc / 24 Vac ± 10% E External jack for remote system access (4-pin header)
(non-isolated half-wave rectified)
Consumption @ 24 Vdc ..13 mA max (no backlight), GS Greystone Customized Version (TE200AC*GS***)
23 mA max (with backlight)
Protection Circuitry .........Reverse voltage protected
Range ...................................0.0-35.0 °C or 32.0-95.0 °F
jumper selectable
Resolution ...........................0.1 °C/°F
Display Size ........................ 38.1 w x 16.5 h mm(1.5” x 0.65”) Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice.
Digit Height ........................11.43 mm (0.45” )
Symbols ...............................°C,°F, OCC Due to the many possible configurations, special part numbers may be
Backlight .............................Enable or disable via jumper required. Please contact Greystone for more information

TSRC*GS*** Description:
TYPICAL INSTALLATION:
For complete installation and wiring details, please refer to the product installation instructions.

The TSRC series can be mounted directly to a single gang electrical box or directly to a wall. Insulating foam is adhered to the back
of the enclosure to provide a thermal barrier from internal wall temperatures.

For sensor only models a 2 wire or 3 wire pigtail is used for connection to the Building Automation System. In models with
options such as setpoint adjustment or manual override, a terminal block connection is provided.

DIMENSIONS:

29 mm
1.15 “

82.6 mm
119 mm 3.25 “

V.12/13
4.7“

Copyright © Greystone Energy Systems Inc. All Rights Reserved


84 mm
58 mm
3.3“
2.3 “

Greystone Energy Systems, Inc. reserves the right to make design modifications without prior notice.

ENERGY SYSTEMS INC Greystone Energy Systems Inc. is one of North America’s
largest manufacturers of HVAC sensors and transmitters for
Greystone Energy Systems, Inc. Building Automation Management Systems.
150 English Drive, Moncton, We have conscientiously established a worldwide
New Brunswick, Canada E1E 4G7 reputation as an industry leader by maintaining leading-
(506) 853-3057 Fax : (506) 853-6014 edge design technology, prompt technical support, and a
North America: 1-800-561-5611 commitment to on-time deliveries. We take pride in our
PRINTED IN CANADA

e-mail: [email protected] Quality Management System , assuring our customers of


www.greystoneenergy.com consistent product reliability.

You might also like