Load Management
Load Management
Load Management
v.8.20
© 2020 Ing. Punzenberger COPA-DATA GmbH
Distribution and/or reproduction of this document or parts thereof in any form are permitted solely
with the written permission of the company COPA-DATA. Technical data is only used for product
description and are not guaranteed properties in the legal sense. Subject to change, technical or
otherwise.
Contents
3 Introduction ................................................................................................................................................. 6
3.1 Initial situation in the electricity industry.................................................................................................6
3.2 Aims of an economic management ...........................................................................................................6
3.3 Gas grid ................................................................................................................................................................7
4 How the system works when electricity is used as the power source .......................................... 7
GENERAL HELP
If you cannot find any information you require in this help chapter or can think of anything that you
would like added, please send an email to [email protected].
PROJECT SUPPORT
You can receive support for any real project you may have from our customer service team, which
you can contact via email at [email protected].
2 Load Management
The Load Management is a tool for the support of the economical management. It is for
implementation of energy supply management for small and medium-sized power supply companies
and also for industrial firms whose energy supply is arranged by special contracts.
5 | 56
Introduction
3 Introduction
The task of a Load Management is to optimize the operation of customers with special contracts, such
as energy supply companies or industrial companies. Energy trend calculations are used as a
significant aid; these serve as the basis for automated optimization of energy consumption.
In order to set the price, these companies normally take into consideration a number of the peak
power consumptions which arose over the year. The determination of the average power
consumption takes place in a fixed measuring time, normally 15 to 30 minutes. In addition the price
also includes the received power. Contracts concluded on this basis are valid on the long term.
Potential savings come along when expensive peak power consumptions are avoided. The peak
power consumptions during a measuring period can be avoided by pointedly controlled
interventions.
Load shedding at switchable devices
Input of own generators
6 | 56
How the system works when electricity is used as the power source
The gas grid functionality has been removed. When importing, converting and compiling zenon
projects from earlier versions, a corresponding message is shown in the output window of the zenon
Editor if there is still some project configuration content for gas grids.
NOTICE TEXT
For project configurations with gas grid content, the following message is shown in the output
window of the zenon Editor:
The functionality gas grid of the module Load Management is no longer supported and will not be
imported.
The price is usually fitted to the three highest values which accrued for the measuring periods in
different months. The price is then valid on the long term.
The average power which is used to calculate the price can be reduced when corresponding peak
power consumptions are limited due to pointedly controlled interventions. This short term
optimization can be achieved by the following interventions:
Load shedding at switchable devices
Increasing input of own generators
The aim of this optimization is to not exceed the contractual set limit for the power in a measuring
period under no circumstances. Additionally, the energy consumption should stay very close below
the set limit in order to receive as much energy as possible.
The consumption optimization is performed by way of a short-term trend calculation. The measured
values which were gathered during the handling interval (typically 30, 60 or 180 seconds) are used to
perform a trend analysis. The calculated trend is projected to the end of the period.
7 | 56
Principal thoughts
5 Principal thoughts
The following chapter deals with thoughts and examples which make it easier for the user to indentify
and select changeable elements of your plant. The question is what elements and devices can be
influenced by the Load Management directly or indirectly in a sensible way.
Directly switchable devices Devices which can be switched off briefly without interrupting
any production processes are part of this group (industrial
furnaces, pumps for water storages etc.).
Direct heatings Because of their storage effect, these device can be switched off
briefly without decreasing the quality of supply significantly
(heating in warm water storages, electrically operated floor
heatings etc.).
Monovalent heat pumps In general these pumps are operated in the same way as direct
heatings.
Bivalent heat pumps These can choose between fuels they use. Beneath a certain
temperature they are switched to a different fuel by their control
unit of by the optimization.
8 | 56
Principal thoughts
Option Description
Night storage heatings These devices are supplied with energy according to schedule
or if there is any needed output during low rate periods. They
are switched off during the remaining time.
Peak load aggregates and These aggregates are switched on/off as required. In some
emergency power aggregates cases these aggregates are controllable. Because start-up
entails additional costs due to wear, the number of uses should
be limited. In addition these aggregates should run for a
minimum time in order to avoid thermal damages.
Combined heat and power These aggregates were primarily built to generate heat and are
units (CHPs) controlled by the heat demand during their operation (heat
priority).
The load reduction with regard to the take over point depends
on the nominal size and for controlled or heat demand
controlled aggregates from their working point.
Lowering the voltage In the electrical power area it is possible to lower the voltage in
some grids. In order to achieve this, the transformers to the
medium voltage level are switched to a lower level.
9 | 56
Load management method
Constant output When switched on, an aggregate (pump, furnace) runs with a
previously defined power consumption. Accordingly the
output is reduced by the amount of the power consumption
when the device is switched off. In this case it is enough to
indicate the nominal power as a constant.
Loading period model At that the temperature makes itself felt with the size of the
switch-on output and the length of the following loading
period until the output drops when all heat stores are full.
Dependence on the switch-off At that several devices - because of the temporary cool
time down or warm up - are switched on dependent on the
previous switch-off time. After a short period of time they
switch themselves off again.
Dependent on the production In the industry sector behavior can occur - caused by
process production processes - which are subject to no behavior
patterns or dependencies. These can only be determined by
the production schedules.
10 | 56
Load management method
Attention: It must be made sure that the value is supplied exactly one time in the update interval.
Values must not be absent or be there twice.
Information
Because the Load Management is a component which can cause high costs if it
fails, it is very important the input values are secured. It is recommended that
values for this module are secured by using sensible alternate values or an
alternate value strategy.
POWER TREND
At the end of the period T the power P prog (T) is to calculate. In order to calculate the current power
trend, a linear function in the form of a polygon is used, which is extrapolated to the end of the
period.
P prog (T) = P const (t) + P trend (t) * ( T - t )
The mathematical polygon factors p0, p1 are named after their physical meaning in order to make it
easier to understand.
Factor Description
11 | 56
Load management method
Factor Description
t current time
ENERGY TREND
Deducted from this the energy trend up to the end of the period E(T) can be calculated with the
function
E prog (T) =P aver (t) * t + P const (t) * (T - t) + ½ * P trend (t) * (T - t)
Factor Description
The first addend describes the determined energy up to the time t. The energy can be either
determined by the average power value as described in the formula or is given as a direct calculated
energy value E(t).
The second addend continues the present constant power to the end of the period and calculates the
constant energy amount from that.
Concerning the energy calculation for the actual billing a value is necessary which is set back exactly
at the beginning of the measuring period. Therefore it is not possible to use externally filtered values.
From the formula mentioned above the average value at the end of the period is determinable.
P prog aver (T) = E prog (T) / T
Parameters Description
The amount of energy obtained exceeding / going below the usage E corr = E prog (T) - E limit is
determined by comparing this energy with the energy expected at the end of the period E prog (T).
12 | 56
Load management method
The trend functions are laid on top of each other and result in the real value forecast. It describes the
actual power consumption to the end of the billing period which is to be expected.
This is why there is a percentage of Safety distance [%] for the supply limit during parameterization,
which must be undershot before connections are triggered.
Digit Description
2 Safety distance
3 Deactivate hysteresis
4 Activate hysteresis
13 | 56
Load management method
Around this limit a hysteresis can be built with the help of Activate hysteresis [%] and Deactivate
hysteresis [%] . In doing so the Activate hysteresis [%] eliminates a part of the Safety distance
[%].
Attention
Take care that Activate hysteresis [%] is in any case smaller than the Safety
distance [%]. Otherwise the system reacts too late if the agreed limit is
exceeded
Information
In the Load Management module the immediate switching points do not have to
be used at the devices. You can decide whether you want to make direct
switching possible or whether switching must be cleared by the user first.
Attention
The unchecked use of the closed loop operation necessitates an intensive pilot
stage. At that all switchings which are then done by the control must be checked
by the user. This pilot stage must be adjusted to the size and complexity of the
system. It is possible that the pilot stage lasts up to one year.
In the system two mechanisms are implemented in order to determine the output
14 | 56
Load management method
The initial value for the output of the device is determined with a polling of the variable value during
the beginning of the optimization. In order to compensate errors due to fluctuations, the optimization
calculates a gliding average value using the consecutively arriving measurements.
Information
If a component is switched off when the optimization starts, its output is
presumed as zero. Thus the SCADA function cannot determine a valid output
value as prerequisite for the use of the component. The component must be
switch on by hand once.
Attention
As long as not at least one value has arrived, the output value of the component
is not known and cannot be used for the optimization.
If the requested amount of energy cannot be reached exactly, it is treated as a minimum value at a
switch-off request and a maximum value at a switch-on request. The consumption limits can thus be
safely adhered to.
Information
During the Runtime the amount of energy can be adjusted dynamically with the
help of a variable.
15 | 56
Load management method
AVAILABILITY
The availability controls if the device is usable in general. The availability can be set manually and is
always set back when the component cannot be used because of operational reasons (e.g. at
overhauls) or when the optimization should not use it.
Conditions which arise during the process can also determine the availability of the component and
control its use by the optimization.
Info
In the Runtime, the availability can be amended dynamically with the help of a
variable. For example time tables with respect to the availability can be
implemented with the help of a scheduler or the Production & Facility Scheduler.
Attention
During the lock times the components are not influenced by the optimization -
or only in the released direction. Thus the components remain in the state they
had reached at the end of the release time.
This parameter is important for aggregates because in order to avoid thermal damages and damages
caused by soot they must not be switched off right after they were switched on. Thus for example a
certain amount of time must have passed after the heating groups had been activated before they
switch on.
16 | 56
Load management method
SWITCHING FREQUENCY
If devices and generators can only be switched a limited number of times in a certain time period, the
components are no longer switched when this number is exceeded. Beside the number of switchings
a time period must also be defined in order to carry out the parameterization.
Example
Maximum 25 switchings in 12 hours
SWITCHING PRIORITIES
The switching of the components is planned in accordance with a priority schedule. At that switch-on
and switch-off priorities are listed separately. The user can determine the priorities in accordance with
the operation requirements. The component with the highest priority (highest numerical value) is
switched first.
If there is a requirement to switch the components in a sorted order by having the device that was
switched on first be the one switched off last, a number pattern must be applied to all components:
ascending for the first switch-on and descending for the last switch-off.
Information
If several devices have the same priority in one plant, the Load Management
automatically ensures that on average all devices of the same level are switched
equally often.
17 | 56
Load management method
Digit Description
1 Pre-warning on
2 Output order ON
4 Pre-warning off
This time - dependent on the aggregate - can be quite long; e.g. starting up the aggregate und
synchronization, rearwards controlled heating etc.
18 | 56
Load management method
lead time to carry out the switching is necessary. This is defiend by Advance warning time. Hereby
the user receives information about switchings which are planned before they are actually carried out.
Attention
As the Load Management module assumes that the switchings are carried out,
the suggested switchings should be carried out in the corresponding time in
respect to the exactness of the forecast.
The use of components with a much higher output than that is used for the correction is possible by a
specific time control. The components are used for such a short time that the compensate the
needed output.
That is why a Down time begin tariff interval can be engineered in the system. During this time the
optimization doe not carry out any switchings.
Attention
If for a long time no response is received for a switch command which was
issued by the EMS (on the response variable), the Load Management assumes
that the action failed und tries to carry out another switching (on the next
available component). Therefore you must always ensure that the correct
response about the success of a switchng operation is transferred to the Load
Management.
19 | 56
Multi-level combined heat and power plants (CHPs)
between these modules and the short term optimization, these switchings are not monitored in
regard of the output trend. They are also not displayed in the trend of the obtained output. They are
interfering in the short time optimization with regard to its result.
In order that these interferences do not have radical effects, external switchings should be engineered
in a way that they take place at period change. If this is not possible, they should be scheduled right
after a period change so that the interfering influence on the control can still be compensated. These
switchings should be finished within the Down time begin tariff interval and the influence of the
switching on the input value should be present.
The CHPs are controlled by a set value. Additionally different output levels can be defined which this
set value can take on. The actual output of the CHP is registered by a measurement (variable) and
sent to the Load Management.
Attention
A CHP is only available for the Load Management when it has reached its
nominal power. The availability flag is set accordingly by the engineering. The
Load Management cannot switch off the CHP but only switch it to its nominal
power.
The initialization is carried out with the currently measured output. If this value does not equal a
defined level, the next smaller level is allocated. The CHP is treated as unavailable as long as the
measured output does not match a level. If the measured output is disturbed, the CHP is not available
and the set value is initialized as recently as a valid measured value arrives.
As a measured output does not have to equal a set value exactly, a hysteresis is defined around the
set value. A level counts as reached or set as soon as the current output value is within the hysteresis
of the given set value. The hysteresis can be defined for each CHP individually.
20 | 56
Multi-level combined heat and power plants (CHPs)
The defined levels must not be skipped when allocating the set value. The Load Management
appoints the set value only to the next higher or lower level.
A set value input is only carried out if the CHP shows an explicit level (considering the hysteresis) at
that time. Otherwise the CHP is not available because the measured value does not equal a level.
Attention
You must consider that the forewarning is only given at a defined level setting.
Thus you must regard the length of the forewarning time for the individual levels
when creating the switching schedule.
The priorities are not set for each level individually but are valid for the whole CHP.
If a least two CHPs have the same priority, the rolling priority procedure is used. A more important
condition for CHPs with same priority is that they are set to the same level if possible or that they
differentiate by one level at the most. The prerequisite for this is that both the switch-on priority and
the switch-off priority of these CHPs is the same.
The internal reference counter for the number of switchings is incremented when the CHP is switched
on. This is exactly the case when the current output passes over from one level to the next higher
level. At devices using electrical current the reference counter is incremented when the component is
switched off. Thus within one priority level the switching between two CHPs is compared to the
switch-on and switch-off of a device.
21 | 56
Multi-level combined heat and power plants (CHPs)
The minimum running time (switch-on time) of a level indicates how long the CHP has to run at the
least on this level. After a level is reached, the optimization must wait at least this amount of time
before a new set value input can be made for the next lower level.
The maximum running time of a level indicates how long a CHP is allowed to run on this level at the
most. With the exception of the lowest level (nominal power), the CHP is switched to the next lower
level after this time expires. At that a level counts as active even if the CHP actually runs on a higher
level. The maximum running time of the individual levels must be attuned to other restrictions with
regard to minimum running time and forewarning. Thus a timely switch to a lower level is possible.
The optimization must also prevent set value inputs to a higher level when the maximum running
time cannot be adhered to e.g. because of the minimum running time of the higher level.
Information
Manual switching can cause violations of the defined restrictions. These are
intercepted by the Load Management.
For the lowest level (nominal level) the maximum running time has a different meaning than for the
other levels. The maximum running time of the lowest level indicates how long a CHP is allowed to
run on this level alone at the most. After that the CHP must be switched to the next higher level.
Minimum value for the maximum switch-on time (in 210 240 180 120 60
seconds)
The times which must be entered in the parameterization for the switch-on or switch-off always refer
to the level for which they are entered. This means that the switch-off time which is parameterized for
22 | 56
Multi-level combined heat and power plants (CHPs)
one level is considered if a "switching" is carried out from this level to the next lower level. The
switch-on time is considered if a "switching" is carried out from a lower level to this level.
As the lowest level represents the CHP running with nominal power, no information for minimal
running time, forewarn time, delay time for switch-on and delay time for switch-off is necessary.
The minimal allowed values for the maximum switch-on times of each level are as follows:
For the first level:
Forewarn time of the next higher level
For the last level:
maximum/minimum switch-on time, forewarn time of the last level
For all other levels:
maximum/minimum switch-on time, forewarn time of next higher level
+ delay time for switch-on for the next higher level
+ minimum value for the maximum switch-on time of the next higher level
+ forewarn time of the next higher level
+ delay time for switch-off for the next higher level
If for one CHP the maximum switch-on time for one level is below the calculated minimum value for
the maximum switch-on time, the CHP is treated as not available and a corresponding availability
identification is set for the readiness.
23 | 56
Engineering of the module Load Management
Switching plans to the next levels must be revised or exchanged if the previously configured set value
of a switching action for a CHP was not reached. For any further switching actions, different
components will be preferred.
If a measured value of the current output re-enters the hysteresis area of a defined level, the
difference to the set value is registered and the difference at the level setting is assumed to be
manual operation. The set value is set to the newly identified level.
A recognized manual operation is transmitted to the forecast so that it can be considered in the trend
calculation.
All objects have property Name and Description. The engineering of the individual objects is carried
out via the property window.
All properties that can be amended in the property window are briefly described in the Property help
window after you click on the respective property name.
24 | 56
Engineering of the module Load Management
Information
All mentioned or shown properties are only visible if the module Load
Management is licensed. The licensed Load Management module is a separate
element in the project tree. The settings in the Load Management can be made
with the help of this entry.
Attention
Within the Load Management all existing units (grids, device groups, generators,
devices etc.) should have a distinct name in order to ensure the perfect function
of the forecast and the optimization.
Information
All values of variables which are used in the Load Management to state or adjust
time values during the Runtime (e.g. switch-on time variable) are interpreted as
seconds. Therefore a numerical value of 300 corresponds to a time period of 5
minutes (=300 seconds).
In order to ensure the correct functionality of the Load Management, you must create the following
variables for a supply area:
Current total consumption
Supply limit
Start value of estimation
First switching value
Estimated error range
Estimated final consumption
Last switching value
Gross actual deviation
Net actual deviation
Information
Use the "Create and link variables automatically" command menu entry in
the context menu for a supply area. This command automatically creates
variables for the properties listed above and links the variables with the
properties.
25 | 56
Engineering of the module Load Management
You must at least create the following variables for a generator/device in order to ensure the
functionality of the Load Management.
Switching state for the generator
Switching state for the device
Availability
SUPPLY AREA
For the correct functionality of the Load Management, you must create at least the following variables
for a supply area:
Current total consumption
Supply limit
Start value of estimation
First switching value
Estimated error range
Estimated final consumption
Last switching value
Gross actual deviation
Net actual deviation
Info
You can find the Create and link variables automatically option in the context
menu for a supply area. It automatically creates variables for the properties listed
above and links the variables with the properties. Properties Current total
consumption and Supply limit are an exception. You must create them
manually.
GENERATORS/DEVICES
For the correct functionality of the Load Management, you must create at least the following variables
for a generator/device:
for the device
Switching state
26 | 56
Engineering of the module Load Management
Entry Description
27 | 56
Engineering of the module Load Management
Entry Description
Generator new Creates a new generator for the selected supply area.
New device group Creates a new device group for the selected supply area.
Create and link variables Automatically creates all variables that are required for the correct
28 | 56
Engineering of the module Load Management
Menu/Entry Description
automatically calculation of the module. The variables created this way are
automatically linked to the respective properties (on page 26).
Copy Copies the currently-selected supply area. You cannot copy more
than one supply area at a time (no multi-select).
Paste Pastes content from the clipboard. Supply area objects can be
pasted.
Export selected as XML... Exports the currently-selected supply area. You cannot export more
than one supply area at a time (no multi-select).
Generator new Creates a new generator for the currently-selected supply area.
29 | 56
Engineering of the module Load Management
Menu/Entry Description
generators using multi-select is possible.
Export selected as XML... Exports the configured generators of the currently-selected device
group. It is possible to export several generators by means of
multi-select.
New device group Creates a new device group for the selected supply area.
Paste Pastes objects of the type Device group from the clipboard.
Export selected as XML... Exports the device group including all configured devices within the
group.
Paste Pastes objects of the type Device group from the clipboard.
Export selected as XML... Exports the currently-selected device group. You cannot copy more
than one group at a time (no multi-select).
30 | 56
Engineering of the module Load Management
Menu/Entry Description
Copy Copies the selected device group to the clipboard. You cannot copy
more than one group at a time (no multi-select).
Paste Pastes objects of the type Device group, device from the clipboard.
Delete Deletes the currently-selected device group. You cannot delete more
than one group at a time (no multi-select).
Export all as XML Exports all device groups of the selected grid.
Export selected as XML... Exports the currently-selected device group. You cannot copy more
than one group at a time (no multi-select).
At the moment the Load Management has no interface to the Historian. This is not necessary for the
short term optimization. For this the historic data which were recorded via option Harddisk data
storage are enough.
The following settings depending on the period length are recommended for the recording of the HD
data.
31 | 56
Engineering of the module Load Management
The Historic data area which is provided by the Harddisk data storage has to be at least 1.5 times
the size of the corresponding Billing period. If there is not a sufficient amount of data, the
calculation of the optimization is not instigated.
Attention
At the beginning of the Billing period the Load Management needs a Current
total consumption for the displayed supply area. Thereby the new value must
be transferred to the Load Management during the next but one Optimization
cycle, i.e. if the optimization cycle is 30 seconds, the value must be transferred
in the period between 30 an 60 seconds.
If the Load Management does not receive a value in this period, the new
initialization of the Load Management can be carried out during the next billing
period at the earliest.
8.4 Grids
The collective node contains all projects which have been created in the grid but does not offer any
setting possibilities itself.
Options:
Menu/Entry Description
Note: Only one electricity grid per zenon project can be configured.
This entry is grayed out if another grid has already been configured.
A unique Name must be issued for each newly-created grid. A free Descriptioncan also be entered
as an option for easier identification.
Information
For each project only 1 power grid can be created or administrated.
32 | 56
Engineering of the module Load Management
Information
In order to start the Load Management for a particular supply area, a function of
the type "Load Management" must be executed which has this supply area as
parameter.
All in the respective groups adjustable properties are described in the help window after you click on
them.
Menu/Entry Description
Generator new Creates a new generator for the selected supply area.
33 | 56
Engineering of the module Load Management
Menu/Entry Description
New device group Creates a new device group for the selected supply area.
Create and link variables Automatically creates all variables that are required for the correct
automatically calculation of the module. The variables created this way are
automatically linked to the respective properties (on page 26).
Copy Copies the currently-selected supply area. You cannot copy more
than one supply area at a time (no multi-select).
Paste Pastes content from the clipboard. Supply area objects can be
pasted.
Export selected as XML... Exports the currently-selected supply area. You cannot export more
than one supply area at a time (no multi-select).
34 | 56
Engineering of the module Load Management
Menu/Entry Description
New device group Creates a new device group for the selected supply area.
Paste Pastes objects of the type Device group from the clipboard.
Export selected as XML... Exports the device group including all configured devices within the
group.
Menu/Entry Description
Paste Pastes objects of the type Device group from the clipboard.
Export selected as XML... Exports the currently-selected device group. You cannot copy more
35 | 56
Engineering of the module Load Management
Menu/Entry Description
than one group at a time (no multi-select).
8.7 Generator
Generators serve to lower the amount of power being obtained from external energy providers.
Basically it is possible to engage each generator or to set it on higher load (Peak performance). An
active generator (switched or on higher load) reduces the current value for power being obtained. An
average figure for the power being obtained is saved in the variable linked in the Current average
consumption property.
For the configuration of a new generator, select the New generator context menu entry in the
selected supply area in the Generator node.
Menu/Entry Description
Generator new Creates a new generator for the currently-selected supply area.
PROPERTIES
In addition to name and identification, properties can be defined in different groups for the
generator:
36 | 56
Engineering of the module Load Management
Capacity/Priority: Defines the basic behavior of pieces of equipment in the electric grid.
Switching times: Default of different life spans or timely requirements to single pieces of
equipment.
Switching frequency: Definition of the maximum number of switchings per time unity.
Switching variables: Variable for the adaption of important parameters during the Runtime.
Locking Times: Excludes single pieces of equipment of the Load Management from the
optimization.
Switching Steps: Defines switching levels for combined heat and power units. (on page 38)
All adjustable properties are described in the help window after you click on them.
Attention
The switching priority is regarded by the Load Management taking all equipment
into account. That means the same number circle is applied for generators and
devices. Therefore the priorities for all defined equipment must be considered
because it is not distinguished between generators and devices.
Menu/Entry Description
Export selected as XML... Exports the configured generators of the currently-selected device
group. It is possible to export several generators by means of
multi-select.
37 | 56
Engineering of the module Load Management
Menu/Entry Description
Basically you can define under the node Switching Steps settings for the Setpoint variable, for the
current output and for the Hysteresis for each CHP.
Each switching level offers settings for the output, the forewarning of the switching and the switch-on
and switch-off. All adjustable properties are described in the help window after you click on them.
Attention
If switching levels are defined for a generator, these settings overwrite the
standard parameters of the generator. An according warning is displayed during
compiling in the output window. "
38 | 56
Engineering of the module Load Management
8.8 Devices
In the Load Management devices are the essential components which "use up" energy. By switching
devices on or off the Load Management can interfere in a regulative way. At that it helps to avoid
peak loads.
Menu/Entry Description
Copy Copies the currently-selected device group. You cannot copy more
than one group at a time (no multi-select).
Export all as XML Exports all device groups of the selected grid.
Export selected as XML... Exports the currently-selected device group. You cannot copy more
than one group at a time (no multi-select).
PROPERTIES
In addition to name and identification, properties can be defined in different groups for the device:
Capacity/Priority: Defines the basic behavior of pieces of equipment in the electric grid.
Switching times: Default of different life spans or timely requirements to single pieces of equipment.
Switching frequency: Definition of the maximum number of switchings per time unity.
39 | 56
Engineering of the module Load Management
Switching variables: Variable for the adaption of important parameters during the Runtime.
Locking Times: Excludes single pieces of equipment of the Load Management from the optimization.
All adjustable properties are described in the help window after you click on them.
Menu/Entry Description
Copy Copies the selected device group to the clipboard. You cannot copy
more than one group at a time (no multi-select).
Paste Pastes objects of the type Device group, device from the clipboard.
Delete Deletes the currently-selected device group. You cannot delete more
than one group at a time (no multi-select).
Export all as XML Exports all device groups of the selected grid.
Export selected as XML... Exports the currently-selected device group. You cannot copy more
than one group at a time (no multi-select).
Ensure that lock times do not overlap one another. If there are time overlaps, it is possible that a
device can no longer be switched by the Load Management module.
40 | 56
Engineering of the module Load Management
Information
The lock time parameters are set in the project and cannot be changed in the
Runtime.
ENGINEERING
Two procedures are available to create a screen:
The use of the screen creation dialog
The creation of a screen using the properties
Steps to create the screen using the properties if the screen creation dialog has been deactivated in
the menu bar under Tools, Settings and Use assistant:
1. Create a new screen.
To do this, select the New screen command in the tool bar or in the context menu of the
Screens node.
41 | 56
Engineering of the module Load Management
CONTROL ELEMENTS
Control element Description
Insert template Opens the dialog for selecting a template for the screen
type.
42 | 56
Engineering of the module Load Management
COMPATIBLE ELEMENTS
Control elements that are replaced or removed by newer versions and continue to be available for
compatibility reasons. These elements are not taken into account with automatic insertion of
templates.
Control element Description
Supply area name Static Win32 control element. Was replaced by a dynamic
text field. For the description, see current element.
Note: The dialog shown shows the values for a selected electricity grid and supply area, as well for
configured variables. The option fields of the Linked Variable option group are empty by default.
43 | 56
Engineering of the module Load Management
In the Runtime, the Load Management screen is opened with the help of a screen switch function. The
following parameters can be configured:
Parameter Description
Grids Selection of the grids. Shows the name of the configured grid.
GRAPHICAL DESIGN
In this area, you configure the appearance of the load management screen in the Runtime.
Parameter Description
Current value Display color and line thickness of the current value
in the configured load management screen in
Runtime:
Color field
Clicking on the color field opens the
dialog to select the display color.
Width:
Width of the displayed line in pixel.
Auxiliary lines Display color and line thickness of the auxiliary lines
in the configured load management screen in
Runtime.
Color field
Clicking on the color field opens the
dialog to select the display color.
Width:
44 | 56
Engineering of the module Load Management
Parameter Description
Width of the displayed line in pixel.
Scale minimum Lower limit of the range scale for the display of the
characteristic curve in the configured Load
Management screen in Runtime.
Scale maximum Upper limit of the range scale for the display of the
characteristic curve in the configured Load
Management screen in Runtime.
Font Setting the parameters for the font that is used for
the axis captions and the trend curve in the
Runtime.
Default: 15 min
LINKED VARIABLES
The configured variables for the corresponding values are shown in this area.
Configuration is not possible in this dialog. Configuration is carried out directly in the properties of the
elements of the module.
Parameter Description
Current value This field is only for display. You cannot change the value. The
value of the variable that is linked in the current power property
for the currently-selected area is linked.
Current average This field is only for display. You cannot change the value.
45 | 56
Engineering of the module Load Management
Parameter Description
consumption value
The value of the variable that is linked in the current average
consumption value for the currently-selected device is displayed.
Estimated final This field is only for display. You cannot change the value. The
consumption value of the variable that is linked in the estimated final
consumption for the currently-selected area is displayed.
Estimated average value This field is only for display. You cannot change the value. The
value of the variable that is linked in the estimated average
value for the currently-selected area is displayed.
Estimated average value Field is for information only, the value cannot be changed.
error range The value of the variable that is linked for the estimated average
error value for the currently selected area is displayed.
Supply limit This field is only for display. You cannot change the value. The
value of the variable that is linked for the supply limit for the
currently-selected area is displayed.
SWITCHING OPERATION
For the configuration of the switching preview, define the filter settings for the display in the Runtime
in the Column settings for the switching operations preview tab. You can find details in chapter
Column settings for the switching operations preview (on page 49).
46 | 56
Engineering of the module Load Management
Hint
In order to stop areas according to pre-defined times, you can control the Start
Load Management or Stop Load Management functions with the help of the
Production & Facility Scheduler.
For example: in the night or in certain shifts.
47 | 56
Engineering of the module Load Management
CLOSE DIALOG
Options Description
OK Applies settings and closes the dialog.
48 | 56
Engineering of the module Load Management
3. Paste the switching operations preview element into the Load Management screen.
Note: The table display: switching operations preview element is already contained in the
screen by default:
You can customize color and font using its properties.
LANGUAGE SWITCH
You can switch between languages for all information displayed in the switching operations preview
with the help of the language table.
For this you can define the name for the column titles in the filter dialog (on page 49). If you select a
name such as @Switching time, @Object name or similar, these names are replaced by the
corresponding entries from the language table in the Runtime.
In addition the whole content of the switching operations preview can be replaced:
1. Object names are replaced by putting a @ in front of them during the Load Management
engineering. For example: @Generator1
2. Current value and switching value can either have a numerical content (with CHP steps) or
@On/@Off
49 | 56
Engineering of the module Load Management
Note: The language of all information displayed in the switching operations can be switched using
the language table:
Select the name with a @ before it, for example @Schaltzeit, so that this can be replaced with the
corresponding language table entries in the Runtime.
In the list field of this tab all available column types are displayed. With the help of a checkbox you
decide which column types are displayed. You can change the description and the width of each
column type by left-clicking the corresponding area and entering the desired value in the input field.
Parameter Description
Column type Type of the column. Cannot be edited. The display in the
Runtime is activated or deactivated by means of a
checkbox.
50 | 56
Internal state of the components
Parameter Description
Move selected entry up Moves the selected column up. You can also move the
columns with drag&drop.
Move selected entry down Moves the selected column down. You can also move the
columns with drag&drop.
Field with horizontal display of the Shows the columns which are active in the list. You can
column names define the size of the columns by clicking and dragging the
column borders with the mouse.
Attention
The column width is dependent on the used font. If the column width is not a
multiple of the character width of the used font, the actual column width can
differ from the set column width.
The variable Internal switching state of components can take on the following values:
51 | 56
Internal state of the components
106 It is not possible to add output at the end of the rate interval because of the
parameterization.
207 No data for the gliding average value of the output are available yet.
52 | 56
Internal state of the components
Value Description
221 Extended parameterization for minimum power-on time per time unit not valid.
223 Switched on implicitly because of "minimum switch-on time per time unit".
5000 The current output does not comply with a level output.
5002 The CHP only has one level can cannot be switched.
5003 The CHP runs with nominal power and cannot be switched down further.
5004 The highest switched on level cannot be switched off because of the minimal
switch-on time per time unit.
5006 The variable which is used to measure the current output is invalid.
5007 The forewarning for a level was activated. Waiting for set value input.
53 | 56
Creation of the Runtime files
Value Description
5010 The value of a parameterized maximum switch-on time of a level is too small.
5011 Maximum running time of a level has been reached. The level is switched off.
The single operating elements are positioned in the screen with the help control elements (prognosis
area and the display of the current supply area).
Information
The screen in the Runtime only serves for the display of optimization and
prediction data. No interventions can be carries out in the screen. Parameters of
the Load Management module are exclusively controlled via variables.
54 | 56
Operation of the load management in Runtime
3 Supply limit
55 | 56
Operation of the load management in Runtime
Information
With the preview, after an invalid value it is always the second valid value of the
following values that is applied first. If no value change is established, the same
value as the one last received is assumed. This ensures a preview that is as
precise as possible.
56 | 56