TEST REPORT
TEST REPORT ISSUED BY:BORIVALI LAB SAMPLE TESTED BY/AT:BORIVALI LAB
TEST REPORT NO. BVI-29801-TR-602354
TEST REPORT & ISSUE DATE: 22/08/2023
DISCIPLINE : MECHANICAL TEST GROUP NAME : BUILDING MATERIALS

CUSTOMER NAME & ADDRESS: PROJECT SITE ADDRESS:


M/s Big City Projects Private Limited Emerald Developers
G-1, Ground, Marigold, Almeda Road, Nil Compound ,Humera Park, Triveni Nagar, Rani Sati Marg Pathanwadi, Malad
Thane. (East),
Mumbai.

QUANTITY: 3 No(s)
DATE OF RECEIPT: 16/08/2023
CUSTOMER REF. NO & DATE: Letter Dated : 16/08/2023
CONDITION OF SAMPLE ON RECEIPT: Satisfactory
(*)SOURCE OF SAMPLE: Rehab Plinth Slab Beth C - 30 & C - 22
TEST METHOD: IS 516 Part-1 Sec-1: 2021

CONCRETE CUBE COMPRESSIVE STRENGTH TEST RESULTS


(*)CUBE SIZE(mm): 150*150*150 (*)DATE OF CASTING: 13/08/2023
(*)GRADE OF CONCRETE:M-50 DATE OF TESTING : 20/08/2023
(*)AGE OF SPECIMEN(DAYS):7
Sr Master Equipment Description/ Range/Resoluti Cal Certificate No. Calibration Calibration Due Calibrated by
No Equipment ID on Done on Date
1 Compression Testing Machine 2000kN/0.1 kN VSC-5463-CR-579 09/05/2023 08/05/2024 GLOBAL LAB
(Automated)/GL-VST-282 084 (ULR NO.: CC2
24523000001522F)

Sr. (*)ID Mark of Specimen Dimension of specimen, mm Cross Weight(kg) Maximum Compressive Type of
No Length Width Thickness sectional Load, kN Strength Failure
area mm2 N/mm2
1 Rehab Plinth Slab Beth C 150.4 150.7 150.8 22666 8.227 464.4 20.5 Satisfactory
- 30,34 & C - 37
2 Rehab Plinth Slab Beth C 150.5 149.9 149.6 22559 8.236 570.0 25.5 Satisfactory
- 30 & C - 22
3 Rehab Plinth Slab Beth C 151.1 150.9 150.5 22810 8.412 513.5 22.5 Satisfactory
- 30 & C - 22
Average Value = 23
Remark:(*) Mark Information furnished by the Customer.
Curing Declaration: Curing of the sample (s) submitted to the laboratory for testing was in the customer's scope till the successful registration
of the test request.
REMARKS:
i) As Per IS 516 Part-1/sec-1 Clause no 3.6, the individual variation should not be more than ±15% of the average. If more, The test results of the sample are
invalid.
ii) Acceptance criteria of Compressive Strength is given in IS 456: 2000 in clause No 16.1
NOTE:
- Sample/s was/were not drawn by the laboratory.
- The Reported result/s is/are valid only to the sample submitted to the laboratory.
- No part of the report, except in full, shall be reproduced without the written consent of the laboratory.

-- The authenticity of this report can be verified by scan QR Code to know your Report mentioned below.

******************End of Report******************