Boiler Performance Parameter

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

OWNER MAHARASHTRA STATE POWER GENERATION CO. LTD.

MAHAGENCO

CONSULTANT

JOB NO : PROJECT
STATUS: CONTRACT 1x660 MW BHUSAWAL TPS UNIT-6
DISTRIBUTION
TO Dept Name Sign Date
Code
No. of BHARAT HEAVY ELECTRICALS LTD. DRN
REV. Date ALTD CHD APPD UNIT : HIGH PRESSURE BOILER PLANT DESN SKD -Sd- 10.10.18
TIRUCHIRAPPALLI – 620 014 CHD AVR -Sd- 10.10.18
APPD BMM/ACR -Sd- 10.10.18
TITLE:
BOILER PERFORMANCE PARAMETER
DEPT. SCALE DRAWING. NO.
SIGN.
DATE. SHEET 1 OF 3 REV 00
CAUTION: THIS DRAWING IS THE PROPERTY OF BHARAT HEAVY ELECTRICALS LTD., AND IS NOT TO BE REPRODUCED OR USED TO FURNISH ANY INFORMATION FOR
MAKING OF DRAWINGS OR APPARATUS EXCEPT WHERE PROVIDE FOR AGREEMENT WITH SAID COMPANY.
BOILER PARAMETERS

LOAD
DESCRIPTION HP Heater In
100% 80% 60%
BMCR VWO
TMCR TMCR TMCR

MAIN STEAM

Steam flow at SH Outlet t/h 2120 2053.6 1893.0 1476.9 1076.6

Pressure at SH Outlet Turbine inlet kg / cm2 (g) 255.0 254.5 253.2 222.5 166.9

Temperature at SH Outlet oC 568 568 568 568 568

REHEAT STEAM

Steam flow at RH Outlet t/h 1671.6 1683.1 1574.4 1250.7 929.6

Pressure at HPT Outlet / RH Inlet kg / cm2 (g) 54.90 55.35 51.78 41.14 30.52

Temperature at HPT Outlet / RH Inlet oC 336.5 337.5 326.4 324 329.3

Pressure drop allowed CRHL / RH / HRHL kg / cm2 2.40 2.41 2.24 1.79 1.35

Pressure at RH Outlet / IPT Inlet kg / cm2 (g) 52.50 52.94 49.54 39.35 29.17

Temperature at RH Outlet / IPT Inlet oC 596 596 596 596 596

FEED WATER

Feed Water Temperature oC 299.2 299.8 294.8 281.1 264.3

Customer / Plant : MAHAGENCO / Bhusawal TPS, Unit #6 – 1x660 MW


Engineer : SKD Title : BOILER PERFORMANCE PARAMETER
Reviewer : AVR Drg No. :
Approver : BMM/ACR SHEET: 02 of 03 Rev 00
BOILER PARAMETERS

LOAD
DESCRIPTION HP Heater In HPH
Out
60% 50% 35% 100%
BMCR TMCR BMCR# TMCR

MAIN STEAM

Steam flow at SH Outlet t/h 1260.0 891.6 742.0 1658.7

Pressure at SH Outlet kg / cm2 (g) 193.31 140.2 119.0 251.6

Temperature at SH Outlet oC 568 568 510 568

REHEAT STEAM

Steam flow at RH Outlet t/h 1088.74 755.07 626.3 1637.96

Pressure at HPT Outlet / RH Inlet kg / cm2 (g) 35.87 24.78 19.29 54.76

Temperature at HPT Outlet / RH Inlet oC 329 329.2 280.14 342.7

Pressure drop allowed CRHL / RH / HRHL kg / cm2 1.61 1.10 0.86 2.32

Pressure at RH Outlet / IPT Inlet kg / cm2 (g) 34.26 23.68 18.43 52.44

Temperature at RH Outlet / IPT Inlet oC 596 596 510 596

FEED WATER

Feed Water Temperature oC 270.0 253.3 238.0 195.8

# Minimum Once Through Load

Customer / Plant : MAHAGENCO / Bhusawal TPS, Unit #6 – 1x660 MW


Engineer : SKD Title : BOILER PERFORMANCE PARAMETER
Reviewer : AVR Drg No. :
Approver : BMM/ACR SHEET: 03 of 03 Rev 00