Unit4 - Load Frequency Control
Unit4 - Load Frequency Control
Introduction:
The frequency of a power system is dependent entirely upon the speed at which the generators
are rotated by their prime- movers. Therefore, frequency control is basically a matter of speed control of the
machines in the generating stations. All prime- movers, whether they are steam or hydraulic turbines are
equipped with speed governors which, almost without exception, are purely mechanical speed-sensitive
devices to adjust the gate or control value opening for constant speed. For example, a load is suddenly
applied to the system; the individual generators will meet this demand by the action of the prime-mover
governors. The immediate effect of a sudden load demand is a reduction in speed of the synchronous
generators. However, the kinetic energy is normally sufficient to maintain the energy balance until the
reduction in speed is detected by the drooping characteristic of the governor, which operates the gate or
control valve opening to restore the output and input balance by increasing (more steam input in case of
steam turbines) the prime-mover torque. Thus the function of load-frequency control on a power system
becomes one of changing the control-valve or gate openings of the generator prime-movers as a function of
load variations in order to hold system frequency constant.
Power system operation at a lower frequency than that specified maximum permissible change in
frequency is ( + 0.5 Hz){ As per the Indian Electricity Rules 1956 (amended up to 25th Nov
2000), the permissible range for grid frequency is ± 3% of nominal i.e. 48.5 Hz to 51.5 Hz. The
nominal frequency of operation in the Indian arid is 50.0 Hz and the permissible frequency band
specified by Indian Electricity Grid Code (IEGC) is 49.5 Hz to 50.2 Hz with reference to 3rd
May 2010.[ As per IE rules the permissible variation of voltage at the consumer end is ±6%. In the
case of low or medium voltage, it is more than 6 percent. In the case of high voltage, it is more than
6 per cent on the higher side or by more than 9 per cent on the lower side.]} affects the quality of
power supply and is not allowed because of the following:
(a) When operating at frequencies below 49.5 Hz, some types of steam turbines undergo excessive vibration
in certain turbine rotor states with resultant metal fatigue and blade failures.
(b) When the frequency falls below 49 Hz, the turbine regulating devices fully open and the generating
units become completely loaded. A further decrease in frequency reduces the efficiency of the auxiliary
mechanisms at thermal power stations, especially feed pumps. The result in the case of prolonged operation
at a lowered frequency is a drop in the generated output and further loss of power. The decrease in power
system frequency may assume an avalanche nature which can stop the power stations for a prolonged
outage.
(c) As the frequency decreases, the generator exciters lose their speed and the generator e.m.f. falls, the
voltage in the power system units drop. This brings the danger of a "voltage avalanche" and disconnection
of the consumers.
(d) For synchronous operation of various units in the power system network it is necessary to maintain
frequency constant.
(e) Further the quality of the products of the manufacturers is also affected due to the change in the power
system frequency, because the speed of some types of motors depends upon the frequency.
(f) Electrical clocks will lose or gain time if they are driven by synchronous motors and the accuracy of the
clock depends on frequency and also the integral of this frequency error is loss or gain of time by electric
clocks.
Load frequency control represents the first realization of a higher level control in power systems. It
has made the operation of inter-connected systems possible and to-day it is still the basis of any advanced
concept for the guidance of large systems. In the historical development L.F.C. systems were installed
because of stability problems and the need for better control of the MWh exchange, etc. The relative case of
controlling hydro-power stations has contributed very much to the success of L.F.C. Now a days L.F.C. has
gained in importance with the growth of interconnected systems mainly supplied by thermal power plants.
In all systems the percentage of thermal power plants is at present increasing and the control
requirements are becoming more demanding. In opposition to these demands, thermal units have the
disadvantage that they respond much more slowly to the control signal than hydraulic units. This inferior
response is due to a number of things, such as boiler control, limitations derived from mechanical and
thermal stresses, limitations in the boiler pressure variations, steam storage in the reheater, etc.
By combining all i.e. governor model, turbine model and generator model we get LFC of isolated power system (can
say Single area)
A single area is a coherent area in which all the generators swing in union to the
changes in load or speed changer settings & in which the frequency is assumed to be
constant throughout both static & dynamic conditions. This single control area can be
represented by an isolated power system consisting of a turbine it's speed governor
generator and load.
XTL
hee i,2 ae votaqe masnitudes,, ae the
pas emales of Areq-) &Ahta-2 TeSpectiely qmd
TL S the tie- hne eactance
sinfrodtaleaj
=U1|v2l sin C- :) cosCDi- 4d)
(0d-Ao)
(osCo-o)
SinCBi-c)t ca base
sinco-y)
ade)NO
(oo-
since
pow%
-\ine
oy
divide
APT
(acua
Pease
+ie-Ime
(oy)
Ceffcieot
tie
the
inGeameta) yalue
of as
oeiten
PFiet
al
actu nzn
meanS
in (oe
be
s SymchOcan
hemae
as
expressed
be
value
eValu
()
ut =Te=
eqution
fot
hee
Thee pes |n
ee
whee Prnax= (v|ve] statie AreSission.
of the tfe-1fne.
apaciny
XL
(onste, the change n Sequeny
dt
-(Ad)
(Do) He.
dt
-(hd) QT dt
In theç loosde
dt
dtrad
BF
| t STS
DfS)
DfresAs)
S
Smilaly fos conto) aeea- 0 e hay
APTLCs) = TTey (0facs)- 4fc)
Afcs) -Afacs)
S
Afat
R
(1+Tps1s Fig. |(1+Tsg1$)(1+THs)+
3 8.16
1 1
X3
1+71s provided
Composite APei(s)
12 1 2
APo1(s)
APie,1(8)
Wi with
block
integral 1+lps1|
1+Tps1s Kpst Kps1 AFi(s)
diagram
X
of
|27tT12 respective 2rT12
of S
two-area
f -a12
AFls)
-a12
1+7ps25 Kps2 1+Tps2s Kps2
4 area
load
-a12X7 control
W2 frequency APp2(s) APie,2(8)
+|+T2s| errors)
1 (5)
+(1+Tsg2s)\(1+Tas) APczs)
1_X 1 control
1 Uz=-
1+Tsg25
(feedback
KplACE,dt
R2 1
loops R2 1
2
APcals) =
9ACE AÇEz
b b2
8.6 AUTOMATICVOLTAGE CONTROL
Figure 8.20 gives the schematic diagram of an Main exciter
Gen field
SCR
automatic voltage regulator of a generator. It Exciter Generator
basically consists of a main exciter which excites Error implifier
power field.
amplifier t
the alternator field to control the output voltage.
The exciter field is automatically controlled Vs V2t VE