Zone Sizing Summary for FCU-B1-P-01-01 ENTRANCE

Project Name: MBG 11/02/2022


Prepared by: HTCO 08:56AM

Air System Information


Air System Name ......... FCU-B1-P-01-01 ENTRANCE Number of zones .......................................................... 1
Equipment Class .............................................. TERM Floor Area .............................................................. 396.1 ft²
Air System Type ............................................... 2P-FC Location ..................................................... Cairo, Egypt

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ............ Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 14.6 631 631 Jul 1500 1.8 396.1 1.59

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 10.1 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 18.5 13.8 76.4 / 64.9 56.0 / 55.0 3.67 Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 3.7 67.1 / 72.6 0.37 631 0.038 0.030 82

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
B1-P-01-01-ENTRANCE 1 14.6 Jul 1500 631 1.8 396.1 1.59

Hourly Analysis Program v4.90 Page 1 of 7


Zone Sizing Summary for FCU-B1-P-01-08 IT ROOM
Project Name: MBG 11/02/2022
Prepared by: HTCO 08:56AM

Air System Information


Air System Name .............. FCU-B1-P-01-08 IT ROOM Number of zones .......................................................... 1
Equipment Class .............................................. TERM Floor Area ................................................................ 91.5 ft²
Air System Type ............................................... 2P-FC Location ..................................................... Cairo, Egypt

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ............ Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 7.8 338 338 Jul 1500 0.7 91.5 3.69

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 10.1 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 7.9 7.4 76.8 / 63.2 56.4 / 55.1 1.57 Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 0.9 69.4 / 72.0 0.09 338 0.020 0.016 11

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
B1-P-01-08-IT ROOM 1 7.8 Jul 1500 338 0.7 91.5 3.69

Hourly Analysis Program v4.90 Page 2 of 7


Zone Sizing Summary for FCU-B1-P-01-10 ENTRANCE
Project Name: MBG 11/02/2022
Prepared by: HTCO 08:56AM

Air System Information


Air System Name ......... FCU-B1-P-01-10 ENTRANCE Number of zones .......................................................... 1
Equipment Class .............................................. TERM Floor Area .............................................................. 396.1 ft²
Air System Type ............................................... 2P-FC Location ..................................................... Cairo, Egypt

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ............ Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 14.6 631 631 Jul 1500 1.8 396.1 1.59

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 10.1 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 18.5 13.8 76.4 / 64.9 56.0 / 55.0 3.67 Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 3.7 67.1 / 72.6 0.37 631 0.038 0.030 82

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
B1-P-01-10-ENTRANCE 1 14.6 Jul 1500 631 1.8 396.1 1.59

Hourly Analysis Program v4.90 Page 3 of 7


Zone Sizing Summary for FCU-B1-P-01-16 DAS ROOM
Project Name: MBG 11/02/2022
Prepared by: HTCO 08:56AM

Air System Information


Air System Name .......... FCU-B1-P-01-16 DAS ROOM Number of zones .......................................................... 1
Equipment Class .............................................. TERM Floor Area .............................................................. 214.2 ft²
Air System Type ............................................... 2P-FC Location ..................................................... Cairo, Egypt

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ............ Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 19.0 820 820 Jul 1500 1.1 214.2 3.83

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 10.1 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 19.6 18.8 76.2 / 61.9 54.8 / 53.4 3.88 Jul 1500

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 1.5 69.6 / 71.3 0.15 820 0.049 0.039 18

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
B1-P-01-16-DAS ROOM 1 19.0 Jul 1500 820 1.1 214.2 3.83

Hourly Analysis Program v4.90 Page 4 of 7


Zone Sizing Summary for FCU-B1-P-01-22 BMS ROOM
Project Name: MBG 11/02/2022
Prepared by: HTCO 08:56AM

Air System Information


Air System Name ......... FCU-B1-P-01-22 BMS ROOM Number of zones .......................................................... 1
Equipment Class .............................................. TERM Floor Area .............................................................. 203.4 ft²
Air System Type ............................................... 2P-FC Location ..................................................... Cairo, Egypt

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ............ Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 17.8 769 769 Jul 1500 1.1 203.4 3.78

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 10.1 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 18.2 17.5 76.4 / 62.1 55.1 / 53.8 3.61 Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 1.1 69.2 / 70.5 0.11 769 0.046 0.036 17

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
B1-P-01-22-BMS 1 17.8 Jul 1500 769 1.1 203.4 3.78

Hourly Analysis Program v4.90 Page 5 of 7


Zone Sizing Summary for FCU-B1-P-01-24 CCTV
Project Name: MBG 11/02/2022
Prepared by: HTCO 08:56AM

Air System Information


Air System Name ................... FCU-B1-P-01-24 CCTV Number of zones .......................................................... 1
Equipment Class .............................................. TERM Floor Area .............................................................. 411.2 ft²
Air System Type ............................................... 2P-FC Location ..................................................... Cairo, Egypt

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ............ Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 43.4 1875 1875 Jul 1500 1.6 411.2 4.56

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 10.1 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 43.9 42.9 76.6 / 62.1 55.2 / 53.9 8.71 Jul 1600

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 2.0 69.7 / 70.7 0.20 1875 0.112 0.088 30

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
B1-P-01-24-CCTV ROOM 1 43.4 Jul 1500 1875 1.6 411.2 4.56

Hourly Analysis Program v4.90 Page 6 of 7


Zone Sizing Summary for FCU-B1-P-01-26 CONTROL ROOM
Project Name: MBG 11/02/2022
Prepared by: HTCO 08:56AM

Air System Information


Air System Name FCU-B1-P-01-26 CONTROL ROOM Number of zones .......................................................... 1
Equipment Class .............................................. TERM Floor Area .............................................................. 260.5 ft²
Air System Type ............................................... 2P-FC Location ..................................................... Cairo, Egypt

Sizing Calculation Information

Calculation Months .................................... Jan to Dec Zone CFM Sizing ................ Sum of space airflow rates
Sizing Data ................................................ Calculated Space CFM Sizing ............ Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 20.6 890 890 Jul 1500 1.3 260.5 3.41

Terminal Unit Sizing Data - Cooling

Total Sens Coil Coil Water Time


Coil Coil Entering Leaving Flow of
Load Load DB / WB DB / WB @ 10.1 °F Peak
Zone Name (MBH) (MBH) (°F) (°F) (gpm) Load
Zone 1 20.9 20.2 76.4 / 62.2 55.2 / 53.9 4.16 Jul 1400

Terminal Unit Sizing Data - Heating, Fan, Ventilation

Heating Htg Coil


Heating Coil Water Fan OA Vent
Coil Ent/Lvg Flow Design Fan Fan Design
Load DB @20.0 °F Airflow Motor Motor Airflow
Zone Name (MBH) (°F) (gpm) (CFM) (BHP) (kW) (CFM)
Zone 1 2.0 69.9 / 72.0 0.20 890 0.053 0.042 21

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
B1-P-01-26-CONTROL ROOM 1 20.6 Jul 1500 890 1.3 260.5 3.41

Hourly Analysis Program v4.90 Page 7 of 7