Katalog Kabel Metal
Katalog Kabel Metal
Katalog Kabel Metal
NYY 11xx(1.5-800)
(1.5-800) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1
Construction Data
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors
Cross Diameter Weight and burried in the ground, for power stations, Copper Conductor
Section industry and switchgear as well as for urban
Area approx. approx. supply networks, if mechanical damage is PVC Insulation
mm² mm kg/km unlikely.
Electrical Data
Conductor Inductance Current - Carrying Capacity at 30° C * Short
circuit current
Nom. DC AC Trefoil Flat
at
Cross Resistance Resistance formation formation in air in ground in air in ground 1 sec
Sect. at 20°C at 70°C
800 0.0221 0.035 0.242 0.289 1018 775 1052 762 82.40
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYY 2 x (1.5-300) mm 2
0.6/1
NYY 2 x (1.5-300) mm 0.6/1
2
kV kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1
Construction Data
Application :
Nom. Overall Cable Copper Conductor
Power cable : Indoors, cable trunking, outdoors
Cross Diameter Weight and burried in the ground, for power stations,
Section industry and switchgear as well as for urban
PVC Insulation
Area approx. approx. supply networks, if mechanical damage is
mm² mm kg/km unlikely. PVC Inner Sheath
Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYY
NYY 33xx(1.5-400)
(1.5-400) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1
Construction Data
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors Copper Conductor
Cross Diameter Weight and burried in the ground, for power stations,
Section industry and switchgear as well as for urban
Area approx. approx. PVC Insulation
supply networks, if mechanical damage is
mm² mm kg/km unlikely.
PVC Inner Sheath
1.5 13.0 224 Special Features on Request :
• Fire Resistance
2.5 14.0 277 PVC Sheath
• Oil Resistance
4 16.1 383 • UV Resistance
• Flame Retardant Cat. A, B, C
6 17.3 471
• Flame Retardant Non Category
10 19.4 649 • Heat Resistance
• Anti Termite
16 22.0 875
• Anti Rodent
25 25.0 1,248 • Low Smoke Zero Halogen
• Nylon Coated
35 27.5 1,606
50 30.0 1,857
70 34.0 2,556
Note :
95 38.5 3,428 Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
120 41.5 4,152
conductor shape
150 46.0 5,115 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
185 50.5 6,330
50 - 400 sqmm supplied in sector shaped stranded (sm) conductor
240 57.0 8,215
Standard Packing
300 62.5 10,116
1.5 - 95 sqmm supplied in wooden drum @ 1000 m
400 69.0 12,765 120 - 400 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%
Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC at
at 30°C *
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYY
NYY 44xx(1.5-400)
(1.5-400) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1
Construction Data
Application :
Nom. Overall Cable
Power cable : Indoors, cable trunking, outdoors Copper Conductor
Cross Diameter Weight and burried in the ground, for power stations,
Section industry and switchgear as well as for urban
Area approx. approx. supply networks, if mechanical damage is
PVC Insulation
Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC at
at 30°C *
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYY
NYY 55xx(1.5-50)
(1.5-50) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / PVC
(Copper Conductor, PVC Insulated, PVC Sheathed)
Standard Specification : IEC 60502-1
Construction Data
Application :
Nom. Overall Cable PVC Filler
Power cable : Indoors, cable trunking, outdoors
Cross Diameter Weight and burried in the ground, for power stations, Copper Conductor
Section industry and switchgear as well as for urban
Area approx. approx. supply networks, if mechanical damage is PVC Insulation
mm² mm kg/km unlikely.
PVC Inner Sheath
1.5 14.8 302 Special Features on Request :
• Fire Resistance
2.5 16.0 382 • Oil Resistance PVC Sheath
35 33.0 2,478
50 38.0 3,161
Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
conductor shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%
Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC at
at 30°C *
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYFGbY
NYFGbY 22xx(1.5-300)
(1.5-300) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / SFWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009
Construction Data
Application :
Nom. Overall Cable Copper Conductor
For installation in the ground, indoors, cable
Cross Diameter Weight trunking and outdoors if increased mechanical
Section PVC Insulation
protection is required or where high-pulling
Area approx. approx. stresses may occur during installation or
PVC Inner Sheath
mm² mm kg/km operation.
1.5 17.9 611 Special Features on Request : Galvanized Steel Flat Wire Armor
• Tinned Coated Copper Conductor Galvanized Steel Tape
2.5 18.0 630
• Fire Resistance PVC Sheath
4 17.8 648 • Oil Resistance
6 18.1 687 • UV Resistance
• Flame Retardant Cat. A, B, C
10 20.5 881
• Flame Retardant Non Category
16 22.5 1,085 • Heat Resistance
25 25.5 1,428 • Anti Termite
• Anti Rodent
35 27.5 1,753 • Low Smoke Zero Halogen
50 31.0 2,120
70 35.0 2,716 Note :
Conductor Shape
95 39.5 3,528
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor
120 43.0 4,177 shape
150 47.0 5,012 16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 300 sqmm supplied in compacted circular stranded (cm) conductor shape
185 52.0 6,116
240 58.0 7,695 Tinned Coated Copper Conductor
Electrical properties for tinned coated copper conductor will be submitted upon request
300 64.0 9,384
Standard Packing
1.5 - 95 sqmm supplied in wooden drum @ 1000 m
120 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%
Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYFGbY
NYFGbY 33xx(1.5-300)
(1.5-300) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / SFWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009
Construction Data
Application :
Nom. Overall Cable Copper Conductor
For installation in the ground, indoors, cable
Cross Diameter Weight
trunking and outdoors if increased mechanical
Section protection is required or where high-pulling
PVC Insulation
Area approx. approx. stresses may occur during installation or
operation. PVC Inner Sheath
mm² mm kg/km
Galvanized Steel Flat Wire Armor
1.5 17.8 620 Special Features on Request : Galvanized Steel Tape
2.5 18.0 648 • Tinned Coated Copper Conductor
• Fire Resistance PVC Sheath
4 18.0 681 • Oil Resistance
6 19.0 789 • UV Resistance
• Flame Retardant Cat. A, B, C
10 21.5 997 • Flame Retardant Non Category
16 23.5 1,280 • Heat Resistance
• Anti Termite
25 27.0 1,709 • Anti Rodent
35 29.5 2,123 • Low Smoke Zero Halogen
Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYFGbY
NYFGbY 44xx(1.5-300)
(1.5-300) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / SFWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009
Construction Data
Application :
Nom. Overall Cable
For installation in the ground, indoors, cable
Cross Diameter Weight Copper Conductor
trunking and outdoors if increased mechanical
Section protection is required or where high-pulling PVC Insulation
Area approx. approx. stresses may occur during installation or
operation. PVC Inner Sheath
mm² mm kg/km
1.5 17.9 630 Special Features on Request : Galvanized Steel Flat Wire Armor
2.5 18.0 662 • Tinned Coated Copper Conductor Galvanized Steel Tape
• Fire Resistance
4 19.0 773 PVC Sheath
• Oil Resistance
6 20.5 912 • UV Resistance
• Flame Retardant Cat. A, B, C
10 23.0 1,174
• Flame Retardant Non Category
16 25.5 1,520 • Heat Resistance
25 29.0 2,053 • Anti Termite
• Anti Rodent
35 32.0 2,584 • Low Smoke Zero Halogen
50 37.5 3,173
Note :
70 40.5 4,087 Conductor Shape
95 46.5 5,359 1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor
shape
120 50.5 6,459
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
150 56.5 7,868 25 - 35 sqmm supplied in compacted circular stranded (cm) conductor shape
185 61.0 9,556 50 - 300 sqmm supplied in sector shaped stranded (sm) conductor
240 68.0 12,138 Tinned Coated Copper Conductor
300 74.5 14,773 Electrical properties for tinned coated copper conductor will be submitted upon request
Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
70 - 300 sqmm will be suplied in wooden drum on available length
Length Tolerance per drum ± 2%
Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYFGbY
NYFGbY 55xx(1.5-50)
(1.5-50) mm²
mm² 0.6/1
0.6/1 kV kV
Cu / PVC / SFWA / PVC
(Copper Conductor, PVC Insulated, Galvanized Steel Flat Wire Armor, PVC Sheathed)
Standard Specification : SNI IEC 60502-1 : 2009
Construction Data
Application : PVC Filler
Nom. Overall Cable
For installation in the ground, indoors, cable Copper Conductor
Cross Diameter Weight
trunking and outdoors if increased mechanical
Section protection is required or where high-pulling PVC Insulation
Area approx. approx. stresses may occur during installation or
operation. PVC Inner Sheath
mm² mm kg/km
Galvanized Steel Flat Wire Armor
1.5 17.8 642 Special Features on Request :
Galvanized Steel Tape
• Tinned Coated Copper Conductor
2.5 17.9 682 • Fire Resistance
PVC Sheath
4 20.5 891 • Oil Resistance
• UV Resistance
6 22.0 1,056 • Flame Retardant Cat. A, B, C
• Flame Retardant Non Category
10 24.5 1,391 • Heat Resistance
16 27.5 1,778 • Anti Termite
• Anti Rodent
25 32.0 2,463 • Low Smoke Zero Halogen
35 35.0 3,106
50 40.0 3,904 Note :
Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm) conductor
shape
16 sqmm supplied in non compacted circular stranded (rm) conductor shape
25 - 50 sqmm supplied in compacted circular stranded (cm) conductor shape
Standard Packing
1.5 - 50 sqmm supplied in wooden drum @ 1000 m
Length Tolerance per drum ± 2%
Electrical Data
Conductor Inductance Current - Carrying Short
Capacity circuit current
Nom. DC AC
at 30°C * at
Cross Resistance Resistance 1 sec
Sect. at 20°C at 70°C in air in ground
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification
NYA 1.5- -400
NYA 1.5 400mm²
mm² 450/750
450/750 V V
Cu / PVC
(Copper Conductor, PVC Insulated)
Standard Specification : IEC 60227-1
Construction Data
Application :
Nom. Overall Cable
For building wire installed in conduit in dry
Cross Diameter Weight location and interwiring in swich board and Copper Conductor
Section control panel.
Area approx. approx.
mm² mm kg/km Special Features on Request :
• Fire Resistance PVC Insulation
1.5 3.1 22 • Oil Resistance
• Flame Retardant Cat. A, B, C
2.5 3.7 34
• Flame Retardant Non Category
4 4.3 50 • Heat Resistance
• Nylon Coated
6 4.8 70
10 6.2 117
16 7.2 173
Note :
25 9.0 277 Conductor Shape
1.5 - 10 sqmm supplied in solid (re) or non compacted circular stranded (rm)
35 10.1 369
conductor shape
50 12.1 513 16 - 400 sqmm supplied in non compacted circular stranded (rm) conductor shape
70 13.8 709
Standard Packing
95 16.0 958 1.5 - 16 sqmm supplied in coil @ 100 m
25 - 400 sqmm supplied in wooden drum @ 1000 m
120 17.6 1,183
Length Tolerance per drum ± 2%
150 19.5 1,448
185 22.0 1,835
240 25.5 2,413
300 28.0 2,958
400 31.5 3,782
Electrical Data
Conductor Insulation Inductance Current - Carrying Short
Nom. DC AC Insulation Capacity circuit current
at 30°C * at
Cross Resistance Resistance Resistance 1 sec
Sect. at 20°C at 70°C at 70°C in pipe in air
www.kmi.co.id
PT KMI Wire and Cable Tbk reserves the right to change the data content without prior notification