Power Grid Company of Bangladesh (PGCB)

POWER GRID NETWORK STRENGTHING PROJECT UNDER PGCB


(PGCB/GtoG/01)
Control Room Roof Slab Design (Level +18.825m)

1 2 3 4 5 6 7 8 9
Case

Input
Concrete fc' = 30.00 MPa Lb
Steel fy = 500.00 MPa
(1)
Concrete Density c = 24.00 kN/m3
(2) (2)
Span -- Long Lb = 7.25 m (3)

La
Span -- Short La = 5.65 m OK
(4)
Slab Case = 2 (1)
Thickness Used T = 150.00 mm CASE 2
L a / L b= 0.779
Super Imposed Dead Load
- Finishes = 1.10 kN/m2
- Partitions = 0.00 kN/m2

Live Load LL = 2.50 kN/m2 C..,dl C ..,ll Moment


M1 -ve 0.067 20.895
Loadings M1 -ve = Ca * W ult * La2
Self weight ( c* T/1000) = 3.750 kN/m2 M2 -ve 0.025 12.868
2
M2 -ve = Cb * W ult * Lb
Total DL DL = 4.850 kN/m2 M3 +ve 0.027 0.043 10.431
M3 +ve = Ca,dl* W u,d*La + Ca,ll*W u,l*La2
2

Total ult ( 1.2DL + 1.6LL ) ACI 9.2.1 M4 +ve 0.010 0.016 6.425
W ult = 9.820 kN/m2 M4 +ve = Cb,dl* W u,d*Lb2 + Cb,ll*W u,l*Lb2

Effective depth ( T - C - db ) davg = 122.00 mm


Temperature Steel At = 270 mm2 [ACI 318M-05, 7.12.2.1]

Moment  req. Ast reqd. Bar Dia. Spacing


kN - m % mm2/m  mm
M1 -ve 20.895 0.322 393 10 190
M2 -ve 12.868 0.196 270 10 290
M3 +ve 10.431 0.158 270 10 290 Spacing
M4 +ve 6.425 0.097 270 10 290 [ACI 318M-05,7.6.5]

Summary

M1 -ve  10 @ 100 mm c/c , Ast prov. = 785 > 393 OK


M2 -ve  10 @ 100 mm c/c , Ast prov. = 785 > 270 OK
M3 +ve  10 @ 150 mm c/c , Ast prov. = 524 > 270 OK
M4 +ve  10 @ 150 mm c/c , Ast prov. = 524 > 270 OK

Design by : Md Nazmul Hoque


Power Grid Company of Bangladesh (PGCB)
POWER GRID NETWORK STRENGTHING PROJECT UNDER PGCB
(PGCB/GtoG/01)
Control Room Roof Slab Design (Level +18.825m)

Shear Requirements

W a= 0.73 W b= 0.27
W Lb (Dead) = 10.0 kN/m W La (Dead) = 4.7 kN/m
W Lb (Dead) = W a * La * DL / 2 W La (Dead) = W b * Lb * DL / 2
W Lb (Live) = 5.2 kN/m W La (Live) = 2.4 kN/m
W Lb (Live) = W a * La * LL / 2 W La (Live) = W b * Lb * LL / 2
W Lb (Ult) = 20.2704271 kN/m W La (Ult) = 9.586775 kN/m
W Lb(Ult.)=1.2 W Lb(D)+1.6 W Lb(L) W La(Ult.)=1.2 W La(D)+1.6 W La(L)

0.85 * f c '  2 * M ult 



 req  * 1 1
 
Fy  0.9 * 0.85 * f c '*b * d 2 

Asreq  Max At ,  reqd * b * d avg 


 A *b 
S  Min (3 * T ), b ,500 [ACI 318M-05,7.6.5]
 Astreq 
 

Design by : Md Nazmul Hoque