Ref - 615 - Abb
Ref - 615 - Abb
Document ID
Issue
Revision: H Produ
Copyright
This document and parts thereof must not be reproduced or copied without written permissi
the contents thereof must not be imparted to a third party, nor used for any unauthorized pu
The software or hardware described in this document is furnished under a license and may b
disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of ABB Group. All other brand or product name
document may be trademarks or registered trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
ABB OyDistribution AutomationP.O. Box 699FI-65101 Vaasa, Finland Telephone: +358 10 2211Fa
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or pro
are not to be deemed as a statement of guaranteed properties. All persons responsible for a
equipment addressed in this manual must satisfy themselves that each intended application
acceptable, including that any applicable safety or other operational requirements are com
particular, any risks in applications where a system failure and/ or product failure would c
to property or persons (including but not limited to personal injuries or death) shall be the
of the person or entity applying the equipment, and those so responsible are hereby reques
measures are taken to exclude or mitigate such risks.
This document has been carefully checked by ABB but deviations cannot be completely ru
errors are detected, the reader is kindly requested to notify the manufacturer. Other than u
contractual commitments, in no event shall ABB be responsible or liable for any loss or da
the use of this manual or the application of the equipment.
Conformity
This product complies with the directive of the Council of the European Communities on th
the laws of the Member States relating to electromagnetic compatibility (EMC Directive 20
concerning electrical equipment for use within specified voltage limits (Low-voltage directi
This conformity is the result of tests conducted by ABB in accordance with the product stan
EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60
voltage directive. The IED is designed in accordance with the international
standards of the IEC 60255 series.
Table of contents
Section 1 Introduction. 5
This manual 5
Intended audience 5
Product documentation 6
Product documentation set 6
Document revision history 7
Related documentation 8
Symbols and conventions 8
Safety indication symbols 8
Manual conventions 9
Functions, codes and symbols 9
Section 2 REF615 overview 13
Overview 13
Product version history 14
PCM600 and IED connectivity package version 14
Operation functionality 15
Optional functions 15
Physical hardware 15
Local HMI 17
Display 17
LEDs 18
Keypad 18
Web HMI 19
Authorization 20
Communication 21
Section 3 REF615 standard configurations 23
Standard configurations 23
Connection diagrams 27
Presentation of standard configurations 33
Standard configuration A 33
Applications 33
Functions 34
Default I/O connections 35
Default disturbance recorder settings 36
Functional diagrams 37
Functional diagrams for protection 37
Functional diagrams for disturbance recorder and trip
circuit supervision 43
Presentation of standard configurations 33
Standard configuration A 33
Applications 33
Functions 34
Default I/O connections 35
Default disturbance recorder settings 36
Functional diagrams 37
Functional diagrams for protection 37
Functional diagrams for disturbance recorder and trip
circuit supervision 43
Section 1 Introduction
1.1 This manual
The application manual contains application descriptions and setting guidelines sorted per
manual can be used to find out when and for what purpose a typical protection function ca
manual can also be used when calculating settings.
Technical manual
Communication protocol
manual
en07
Figure 1: The intended use of manuals in different lifecycles
The engineering manual contains instructions on how to engineer the IEDs using the differe
The manual provides instructions on how to set up a PCM600 project and insert IEDs to the
The manual also recommends a sequence for engineering of protection and control function
as well as communication engineering for IEC 61850 and other supported protocols.
The installation manual contains instructions on how to install the IED. The manual provide
mechanical and electrical installation. The chapters are organized in chronological order in
should be installed.
The commissioning manual contains instructions on how to commission the IED. The manu
by system engineers and maintenance personnel for assistance during the testing phase. The
procedures for checking of external circuitry and energizing the IED, parameter setting and
well as verifying settings by secondary injection. The manual describes the process of test
substation which is not in service. The chapters are organized in chronological order in wh
be commissioned.
The operation manual contains instructions on how to operate the IED once it has been co
manual provides instructions for monitoring, controlling and setting the IED. The manual
to identify disturbances and how to view calculated and measured power grid data to deter
fault.
The service manual contains instructions on how to service and maintain the IED. The ma
procedures for de-energizing, de-commissioning and disposal of the IED.
The application manual contains application descriptions and setting guidelines sorted per
manual can be used to find out when and for what purpose a typical protection function ca
manual can also be used when calculating settings.
The technical manual contains application and functionality descriptions and lists function
diagrams, input and output signals, setting parameters and technical data sorted per functi
be used as a technical reference during the engineering phase, installation and commission
during normal service.
The communication protocol manual describes a communication protocol supported by th
concentrates on vendor-specific implementations.
The point list manual describes the outlook and properties of the data points specific to the
should be used in conjunction with the corresponding communication protocol manual.
5
5
5
6
6
7
8
8
8
9
9
13
13
14
14
15
15
15
17
17
18
18
19
20
21
rations 23
23
27
33
33
33
34
35
36
37
37
nd trip
43
33
33
33
34
35
36
37
37
nd trip
43
interlocking 45
47
47
48
49
s 50
51
51
recorder and trip
57
interlocking 59
63
63
63
64
s 65
65
66
recorder and trip
71
interlocking 72
74
74
74
75
s 76
77
77
recorder and trip
82
interlocking 83
86
86
87
88
s 89
90
90
recorder and trip
96
interlocking 98
82
interlocking 83
86
86
87
88
s 89
90
90
recorder and trip
96
interlocking 98
103
103
103
105
106
107
107
d trip
116
117
122
122
122
124
125
126
127
127
d trip
135
137
141
141
141
143
144
145
145
d trip
153
155
rement transformers 161
161
tional
161
y limit factor
162
ion 163
165
165
165
165
161
tional
161
y limit factor
162
ion 163
165
165
165
165
165
165
166
166
166
166
168
169
169
169
171
173
ailable yet.
Document revision/date Product version History
F/2010-06-11 3.0 Content updated to correspond to the product
version
G/2010-06-29 3.0 Terminology corrected
H/2010-09-24 3.0 Content corrected
Download the latest documents from the ABB web site http://www.abb.com/substatio
The caution icon indicates important information or warning related to the con
text. It might indicate the presence of a hazard which could result in corruptio
damage to equipment or property.
e ABB web site http://www.abb.com/substationautomation.
The tip icon indicates advice on, for example, how to design your project o
certain function.
Although warning hazards are related to personal injury, it should be understood that operation of damaged equipment
operational conditions, result in degraded process performance leading to personal injury or death.
Therefore, comply fully with all warning and caution notices.
1.4.2 Manual conventions
Conventions used in IED manuals. A particular convention may not be used in this manual.
• Abbreviations and acronyms in this manual are spelled out in the glossary. The glossary also contains definitions o
• Push button navigation in the LHMI menu structure is presented by using the push button icons, for example:
To navigate between the options, use and .
• HMI menu paths are presented in bold, for example: Select Main menu/Settings.
• LHMI messages are shown in Courier font, for example:
To save the changes in non-volatile memory, select Yes and press .
• Parameter names are shown in italics, for example:
The function can be enabled and disabled with the Operation setting.
• Parameter values are indicated with quotation marks, for example: The corresponding parameter values are "On" a
• IED input/output messages and monitored data names are shown in Courier font, for example:
When the function starts, the START output is set to TRUE.
in this manual.
ary. The glossary also contains definitions of important terms.
ng the push button icons, for example:
u/Settings.
Admittance based earth-fault protection, EFPADM1 Yo> -> (1) 21YN (1)
instance 1
Admittance based earth-fault protection, EFPADM2 Yo> -> (2) 21YN (2)
instance 2
Admittance based earth-fault protection, EFPADM3 Yo> -> (3) 21YN (3)
instance 3
Transient / intermittent earth-fault protection INTRPTEF1 Io> -> IEF 67NIEF
X120 AI/BI module Only with configurations A and B: 3 phase current inputs (1/5 A)
1 residual current input (1/5 A or 0.2/1 A) 1) 1 residual voltage
input (60-120 V)
3 binary inputs
X000 Optional See technical manual for details about different type of
communication module communication modules.
1) The 0.2/1 A input is normally used in applications requiring sensitive earth-fault protection and featuring core-
transformers.
Rated values of the current and voltage inputs are basic setting parameters of the IED. The b
thresholds are selectable within the range 18…176 V DC by adjusting the binary input setti
The connection diagrams of different hardware modules are presented in this manual.
See the installation manual for more information about the case and the plug-i
C 4 1 - 4 6
D 4 - - 12 (18) 1)
10 (13)1)
E 4 52) - 16 10
F 4 52) - 16 10
G 1 - 33) 8 10
H 4 5 - 16 10
1) With optional BIO module
2) One of the five channels reserved for future applications
3) Combi sensor inputs for three-phase current and voltage
standard configurations
ements:
e character size depends on the selected language. The amount
REF615
2.4.2 LEDs
The LHMI includes three protection indicators above the display: Ready, Start and Trip.
There are also 11 matrix programmable LEDs on front of the LHMI. The LEDs can be configured with PCM600 and the
be selected with the LHMI, WHMI or PCM600.
2.4.3 Keypad
The LHMI keypad contains push-buttons which are used to navigate in different views or menus. With the push-buttons
close commands to one object in the primary circuit, for example, a circuit breaker, a contactor or a disconnector. The pu
used to acknowledge alarms, reset indications, provide help and switch between local and remote control mode.
1 2
3 4
Figure 4: LHMI keypad with object control, navigation and command push- but
communication port
The menu tree structure on the WHMI is almost identical to the one on the LHMI.
2.6 Authorization
The user categories have been predefined for the LHMI and the WHMI, each with different
passwords.
The default passwords can be changed with Administrator user rights.
ault.
identical to the one on the LHMI.
.
D via the front communication port.
LHMI and the WHMI, each with different rights and default
Client A
Client B
Network
Network
Managed Ethernet switch with
RSTP support
5 REM615
lution
rts the connection of up to thirty 615 series IEDs. If more than 30
commended that the network is split into several rings with no
Section 3 REF615 standard configurations
3.1 Standard configurations
REF615 is available in eight alternative standard configurations. The standard signal configuration can be altered by m
signal matrix or the optional graphical application functionality of the Protection and Control IED Manager PCM600. F
application configuration functionality of PCM600 supports the creation of multi-layer logic functions using various lo
including timers and flip-flops. By combining protection functions with logic function blocks, the IED configuration ca
user-specific application requirements.
Table 6: Standard configurations
Directional overcurrent and directional earth-fault protection with phase-voltage based measurements, undervoltage
and overvoltage protection F
Directional overcurrent and directional earth-fault protection, phase-voltage based protection and measurement
functions, sensor inputs G
Non-directional overcurrent and non-directional earth-fault protection, phase-voltage and frequency based
protection and measurement functions, synchro-check H
Std. conf.
A and B
C and D
G H
- ●
- ●
- ●
● ●
● -
● -
Functionality A B C D E F
Three-phase directional overcurrent protection, - - - - - ●
high stage
Non-directional earth-fault protection, low stage, - - ●3) ●3) - -
instance 1
Non-directional earth-fault protection, low stage, - - ●3) ●3) - -
instance 2
Non-directional earth-fault protection, high - - ●3) ●3) - -
stage, instance 1
Non-directional earth-fault protection, - - ●3) ●3) - -
instantaneous stage
Directional earth-fault protection, low stage, ●2)3)5) ●2)3)5) - - ●2)3)4) ●2)3)4)
instance 1
Directional earth-fault protection, low stage, ●2)3)5) ●2)3)5) - - ●2)3)4) ●2)3)4)
instance 2
Directional earth-fault protection, high stage ●2)3)5) ●2)3)5) - - ●2)3)4) ●2)3)4)
Circuit-breaker control ● ● ● ● ● ●
Disconnector position indication, instance 1 - ● - ● ● ●
Disturbance recorder ● ● ● ● ● ●
Three-phase current measurement, instance 1 ● ● ● ● ● ●
[1] Additional BIO-module (X110 in the diagram) is included in the IED variant B
Figure 8:
Connection diagram for the C and D configurations [2]
[2] Additional BIO-module (X110 in the diagram) is included in the IED variant D
Figure 9: Connection diagram for the E and F configurations
G H
● -
- ●3)
- ●3)
- ●3)
- ●3)
●2)3)6) -
●2)3)6) -
●2)3)6) -
●2)3)6) -
●2)3)6) -
●2)3)6) -
●8) -
● ●
● ●
● ●
●6) ●4)
●6) ●4)
●6) ●4)
● ●
● ●
● ●
● ●
● ●
● ●
G H
● -
● -
- ●
- ●
- ●
● -
● ●
● ●
● ●
● ●
o o
o o
o o
● ●
● ●
● ●
● ●
● ●
o o
- ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
● ●
- ●
● ●
G H
● ●
- ●
ons [1]
ns [2]
igurations
Figure 10: Connection diagram for the E and F configurations
Figure 10: Connection diagram for the E and F configurations
Figure 11: Connection diagram for the G configuration
configuration A
ns
The standard configuration for non-directional overcurrent and directional earth- fault protection is mainly intended for c
line feeder applications in isolated and resonant-earthed distribution networks.
The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user f
incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to diff
layouts and the related functionality needs by modifying the internal functionality using PCM600.
3.4.2 Functions
Table 8: Functions included in the standard configuration A
Directional earth-fault protection, low stage, instance 2 DEFLPDEF2 Io> -> (2) 67N-1 (2)
Admittance based earth-fault protection, instance 2 EFPADM2 Yo> -> (2) 21YN (2)
Admittance based earth-fault protection, instance 3 EFPADM3 Yo> -> (3) 21YN (3)
Additionally, all the digital inputs that are connected by default are also enabled with the se
triggering settings are selected depending on the connected input signal type. Typically all p
signals are selected to trigger the disturbance recorded by default.
3.4.3 Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function- to-function connections. The defa
be viewed and changed with PCM600 according to the application requirements, if necessary.
The analog channels have fixed connections towards the different function blocks inside the IED’s standard configurat
this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable
disturbance recorder’s parameter settings.
The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase
marked with Io represents the measured residual current via a core balance current transformer. The signal marked with
measured residual voltage via open delta connected voltage transformers.
The EFHPTOC protection function block for double (cross-country) earth-faults uses the calculated residual current or
measured phase currents.
3.4.3.2 Functional diagrams for disturbance recorder and trip circuit supervi
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There
timers (TPGAPC1..4) available in the IED. The remaining ones not described in the funct
available in PCM600 for connection where applicable.
rip and to the alarm LEDs. LED 1 is used for overcurrent and
ion operate indication. LED 4 is also used for phase
on
ult protection. According to the order code, the directional
onventional directional earth-fault (DEFxPDEF) or admittance
cated protection stage (INTRPTEF) either for transient-based
arth-fault protection in compensated networks.
n block (EFHPTOC) is intended for protection against double
networks. This protection function uses the calculated residual
n
) provides earth-fault protection by detecting abnormal level of
nonselective backup protection for the selective directional
connected to alarm LED 3.
overload and circuit breaker failure protection
C1) provides protection for interruptions in the normal three-
ductor situations. The operate signal of the phase discontinuity
also to an alarm LED and the disturbance recorder. The thermal
tion on overload situations. The operate signal of the phase
ster Trip and also to an alarm LED. LED 4 is used for the phase
same as for negative sequence overcurrent protection operate
verload protection alarm indication.
initiated via the start input by a number of different protection
n function offers different operating modes associated with the
and residual currents. The breaker failure protection has two
RET operate output is used for retripping its own breaker
used to give a back-up trip to the breaker feeding upstream.
al is connected to the output PO2 (X100:
e indication.
ng (DARREC1) are included as optional functions.
ks for three arc sensors that can be connected to the IED. Each
peration modes, with or without the phase and residual current
are connected to the Master Trip and also to the alarm LED 10
nimum pulse length for the outputs. There are four generic
remaining ones not described in the functional diagram are
licable.
red from the factory with default settings and parameters. The
internal signal designation within the IED enables this configuration to be further adapted to different primary circuit lay
functionality needs by modifying the internal functionality using PCM600.
3.5.2 Functions
Table 13: Functions included in the standard configuration B
Directional earth-fault protection, low stage, instance 2 DEFLPDEF2 Io> -> (2) 67N-1 (2)
Admittance based earth-fault protection, instance 2 EFPADM2 Yo> -> (2) 21YN (2)
Admittance based earth-fault protection, instance 3 EFPADM3 Yo> -> (3) 21YN (3)
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering set
depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturb
default.
3.5.3 Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function- to-function connections. The defa
be viewed and changed with PCM600 according to the application requirements, if necessary.
The analog channels have fixed connections towards the different function blocks inside the IED’s standard configurat
this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable
disturbance recorder’s parameter settings.
The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase
marked with Io represents the measured residual current via a core balance current transformer. The signal marked with
measured residual voltage via open delta connected voltage transformers.
The EFHPTOC protection function block for double (cross-country) earth-faults uses the calculated residual current or
measured phase currents.
3.5.3.2 Functional diagram for disturbance recorder and trip circuit supervisio
Figure 27: Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the disturbance
alternatively only to be recorded by the disturbance recorder depending on the parameter se
the selected autorecloser, the ARC protection signals and the three binary inputs from X120
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15
for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TR
circuit breaker open signal. The TCS alarm indication is connected to LED 9.
By default it is expected that there is no external resistor in the circuit brea
circuit connected parallel with circuit
breaker normally open auxiliary contact.
3.5.3.3 Functional diagrams for control and interlocking
Figure 28: Master trip
The operate signals from the protections are connected to the two trip output contacts PO3
PO4 (X100:20-24) via the corresponding Master Trips TRPPTRC1 and TRPPTRC2. Open
to the circuit breaker from local or remote CBXCBR1-exe_op or from the auto-recloser D
are connected directly to the output PO3 (X100:15-19).
TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip sign
If the lockout operation mode is selected, one binary input can be reassigned to the RST_L
Master Trip to enable external reset with a push button.
bled with the setting. Default triggering settings are selected
RT signals are selected to trigger the disturbance recorded by
rip and to the alarm LEDs. LED 1 is used for overcurrent and
ion operate indication. LED 4 is also used for phase
n
) provides earth-fault protection by detecting abnormal level of
nonselective backup protection for the selective directional
connected to alarm LED 3.
overload and circuit breaker failure protection
C1) provides protection for interruptions in the normal three-
ductor situations. The operate signal of the phase discontinuity
also to an alarm LED and the disturbance recorder. The thermal
tion on overload situations. The operate signal of the phase
ster Trip and also to an alarm LED. LED 4 is used for the phase
same as for negative sequence overcurrent protection operate
verload protection alarm indication.
initiated via the start input by a number of different protection
n function offers different operating modes associated with the
and residual currents. The breaker failure protection has two
RET operate output is used for retripping its own breaker
used to give a back-up trip to the breaker feeding upstream.
al is connected to the output PO2 (X100:
e indication.
ng (DARREC1) are included as optional functions.
ks for three arc sensors that can be connected to the IED. Each
residual current check. Operate signals from the arc protection
p and also to the alarm LED 10 as a common operate
The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line-s
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input
the configuration logic, which is a combination of the disconnector or breaker truck and ear
statuses and the statuses
of the master trip logics and gas pressure alarm and circuit-breaker spring charging. This c
interlocking conditions is called LOCAL_FEEDER_READY and is transferred also to the
binary signal transfer. The OKPOS output from DCSXSWI defines if the disconnector or
definitely either open (in test position) or close (in service position). This, together with th
and non-active trip signals, activates the close-enable signal to the circuit breaker control
open operation is always enabled.
The auto-recloser close command signals are directly connected to the output contact PO1
The ITL_BYPASS input can be used, for example, to always enable the closing of the circ
circuit breaker truck is in the test position, despite of the interlocking conditions being act
breaker truck is closed in service position.
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There ar
(TPGAPC1..4) available in the IED. The remaining ones not described in the functional dia
PCM600 for connection where applicable.
XSWI1…3) available in the IED. The remaining two not
in PCM600 for connection where applicable.
X110 are used for busbar disconnector (DCSXSWI1) or circuit-
y inputs 5 and 6
uted to LED 8.
give dedicated information on:
10-12)
O2 (X100: 13-15)
mum pulse length for the outputs. There are four generic timers
ng ones not described in the functional diagram are available in
3.6 Standard configuration C
3.6.1 Applications
The standard configuration for non-directional overcurrent and non-directional earth- fault protection is mainly intende
overhead-line feeder applications in directly or resistance earthed distribution networks.
The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user
incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to d
circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.
3.6.2 Functions
Table 19: Functions included in the standard configuration C
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering set
depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturb
default.
3.6.3 Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function- to-func
The default connections can be viewed and changed with PCM600 according to the applica
necessary.
The analog channels have fixed connections towards the different function blocks inside the
configuration. Exceptions from this rule are the 12 analog channels available for the disturb
function. These channels are freely selectable and a part of the disturbance recorder’s param
The analog channels are assigned to different functions. The common signal marked with 3
phase currents. The signal marked with Io represents the measured residual current via a sum
of the phase current transformers.
Trip and to the alarm LEDs. LED 1 is used for overcurrent and
ction operate indication. LED 4 is also used for phase
EFLPTOC1 I0 > EARTH FAULT PROTECTION
51N-1
I0 START
BLOCK OPERATE
ENA_MULT
EFHPTOC1 I0 >>
51N-2
I0
BLOCK
OR START
OPERATE
ENA_MULT
control command to the circuit breaker, either local or remote, also blocks the autoreclose
CBXCBR-selected signal.
The circuit breaker availability for the autoreclosure sequence is expressed with the CB_R
DARREC1. In the configuration, this signal is not connected to any of the binary inputs. A
function assumes that the breaker is available all the time.
The autoreclose sequence in progress indication is connected to the alarm LED 11.
3.6.3.2 Functional diagram for disturbance recorder and trip circuit supervisio
Figure 35: Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the disturbanc
alternatively only to be recorded by the disturbance recorder depending on the parameter s
Additionally, the selected autorecloser, the ARC protection signals and the three binary in
also connected.
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:1
TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The T
is connected to LED 9.
By default it is expected that there is no external resistor in the circuit breaker
connected parallel with circuit breaker normally open auxiliary contact.
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There
timers (TPGAPC1..4) available in the IED. The remaining
EARTH FAULT PROTECTION
control command to the circuit breaker, either local or remote, also blocks the autoreclose function via the
CBXCBR-selected signal.
The circuit breaker availability for the autoreclosure sequence is expressed with the CB_RDY input in
DARREC1. In the configuration, this signal is not connected to any of the binary inputs. As a result, the
function assumes that the breaker is available all the time.
The autoreclose sequence in progress indication is connected to the alarm LED 11.
3.6.3.2 Functional diagram for disturbance recorder and trip circuit supervision
Figure 35: Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the disturbance recorder or
alternatively only to be recorded by the disturbance recorder depending on the parameter settings.
Additionally, the selected autorecloser, the ARC protection signals and the three binary inputs from X120
also connected.
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15-19) and
TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked
by the Master Trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open signal. The TCS alarm indica
is connected to LED 9.
By default it is expected that there is no external resistor in the circuit breaker tripping coil circ
connected parallel with circuit breaker normally open auxiliary contact.
If the ENA_CLOSE signal is completely removed from the breaker control function block
CBXCBR with PCM600, the function assumes that the breaker close commands are allowe
continuously.
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There are four generic
timers (TPGAPC1..4) available in the IED. The remaining
ones not described in the functional diagram are available in PCM600 for connection where
Three-phase thermal protection for feeders, cables and T1PTTR1 3Ith>F 49F
distribution transformers
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Three-phase inrush detector INRPHAR1 3I2f> 68
Table continues on next page
available in PCM600 for connection where applicable.
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering set
depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturb
default.
3.7.3 Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function- to-fu
The default connections can be viewed and changed with PCM600 according to the applic
if necessary.
The analog channels have fixed connections towards the different function blocks inside t
configuration. Exceptions from this rule are the 12 analog channels available for the distur
function. These channels are freely selectable and a part of the disturbance recorder’s para
The analog channels are assigned to different functions. The common signal marked with
three phase currents. The signal marked with Io represents the measured residual current v
connection of the phase current transformers.
51N-1
I0 START
BLOCK OPERATE
ENA_MULT
EFHPTOC1 I0 >>
51N-2
I0
BLOCK
OR START
OPERATE
ENA_MULT
51N-1
I0 START
BLOCK OPERATE
ENA_MULT
EFHPTOC1 I0 >>
51N-2
I0 START
BLOCK OPERATE
ENA_MULT
3.7.3.2 Functional diagram for disturbance recorder and trip circuit supervision
X110
3
4
DISTURBANCE RECORDER
LED7 (DR TRIGGERED)
LED9 (TCS ALARM)
3.7.3.2 Functional diagram for disturbance recorder and trip circuit supervision
DISTURBANCE RECORDER
LED7 (DR TRIGGERED)
LED9 (TCS ALARM)
RDRE1
PHLPTOC1-start BI#1 TRIGGERED
PHHPTOC1-start BI#2 PHHPTOC2-
start BI#3 PHIPTOC1-start BI#4
NSPTOC1-start BI#5 NSPTOC2-start
BI#6 EFLPTOC1-start BI#7
EFHPTOC1-start BI#8 EFIPTOC1-start
BI#9 EFLPTOC2-start BI#10
PHLPTOC1-operate BI#11
PHHPTOC1-operate PDNSPTOC1-start BI#12
OR T1PTTR1-start BI#13 CCRBRF1-
PHHPTOC2-operate
PHIPTOC1-operate trret BI#14 CCRBRF1-trbu
NSPTOC1-operate
OR
NSPTOC2-operate BI#15
EFLPTOC11-operate BI#16 BI#17
BI#18
BI#19
EFHPTOC1-operate OR
EFIPTOC1-operate EFLPTOC2-operate BI#20
DARREC1-close cb
OR
DARREC1-unsuc_recl
BI 1(Blocking)
BI 2 (CB Closed) BI 3 (CB Open)
TCSSCBR1
BLOCK ALARM
TRPPTRC1- trip OR OR
TRPPTRC2- trip
TCSSCBR2
BLOCK ALARM
By default it is expected that there is no external resistor in the circuit breaker trippin
circuit connected parallel with circuit breaker normally open auxiliary contact.
The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line-s
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input
the configuration logic, which is a combination of
the disconnector or breaker truck and earth-switch position statuses and the statuses of the
and gas pressure alarm and circuit-breaker spring charging. This combination of interlock
called LOCAL_FEEDER_READY and is transferred also to the remote end via binary sig
OKPOS output from DCSXSWI defines if the disconnector or breaker truck is definitely e
position) or close (in service position). This, together with the open earth-switch and non-
activates the close-enable signal to the circuit breaker control function block. The open op
enabled.
The auto-recloser close command signals are directly connected to the output contact PO1
The ITL_BYPASS input can be used, for example, to always enable the closing of the circ
circuit breaker truck is in the test position, despite of the interlocking conditions being act
breaker truck is closed in service position.
The circuit breaker condition monitoring function (SSCBR) supervises the circuit breaker
binary input information connected and measured current levels. The function introduces
methods. The corresponding supervision alarm signals are routed to LED 8.
Figure 46: Alarm indication
The signal outputs from the IED are connected to give dedicated information on:
• Start of any protection function SO1 (X100:10-12)
• Operation (trip) of any protection function SO2 (X100:13-14)
• Operation (trip) of any stage of the overcurrent protection function SO2 (X110:17-19)
• Operation (trip) of any stage of the earth-fault protection function SO3 (X110:20-22)
TPGAPC are timers and used for setting the minimum pulse length for the outputs. There ar
(TPGAPC1..4) available in the IED. The remaining ones not described in the functional dia
PCM600 for connection where applicable.
y inputs 5 and 6
tch position statuses and the statuses of the master trip logics
ng charging. This combination of interlocking conditions is
ferred also to the remote end via binary signal transfer. The
disconnector or breaker truck is definitely either open (in test
gether with the open earth-switch and non-active trip signals,
reaker control function block. The open operation is always
mum pulse length for the outputs. There are four generic timers
ng ones not described in the functional diagram are available in
The standard configuration for non-directional overcurrent and directional earth- fault protection with phase-voltage ba
mainly intended for cable and overhead-line feeder applications in isolated and resonant-earthed distribution networks.
The IED with a standard configuration is delivered from the factory with default settings and parameters. The end-user
incoming, outgoing and internal signal designation within the IED enables this configuration to be further adapted to d
circuit layouts and the related functionality needs by modifying the internal functionality using PCM600.
3.8.2 Functions
Table 30: Functions included in the standard configuration E
Directional earth-fault protection, low stage, instance 2 DEFLPDEF2 Io> -> (2) 67N-1 (2)
Admittance based earth-fault protection, instance 2 EFPADM2 Yo> -> (2) 21YN (2)
Admittance based earth-fault protection, instance 3 EFPADM3 Yo> -> (3) 21YN (3)
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering setti
depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturba
default.
3.8.3 Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function- to-function connections. The defaul
viewed and changed with PCM600 according to the application requirements, if necessary.
The analog channels have fixed connections towards the different function blocks inside the IED’s standard configuratio
this rule are the 12 analog channels available for the disturbance recorder function. These channels are freely selectable a
disturbance recorder’s parameter settings.
The analog channels are assigned to different functions. The common signal marked with 3I represents the three phase c
marked with Io represents the measured residual current via a core balance current transformer. The signal marked with
measured residual voltage via open delta connected voltage transformers.
The EFHPTOC protection function block for double (cross-country) earth-faults uses the calculated residual current orig
measured phase currents.
for sending a blocking signal to the relevant overcurrent protection stage of the
IED at the infeeding bay.
Figure 48: Directional earth-fault protection
Three stages are offered for directional earth-fault protection. According to the order code,
fault protection method can be based on conventional directional earth-fault (DEFxPDEF) o
(EFPADM). In addition, there is a dedicated protection stage (INTRPTEF) either for transie
protection or for cable intermittent earth-fault protection in compensated networks.
A dedicated non-directional earth-fault protection block (EFHPTOC) is intended for prote
earth-fault situations in isolated or compensated networks. This protection function uses th
current originating from the phase currents.
The binary input 2 (X110:3-4) is intended for directional earth-fault protection blocks’ rel
angle (RCA: 0°/-90°) or operation mode (I0Sinφ/ I0Cosφ) change. All operate signals are c
Master Trip as well as to the alarm LEDs. LED 2 is used for directional earth-fault and LE
earth- fault protection operate indication.
3.8.3.2 Functional diagram for disturbance recorder and trip circuit supervision
Figure 52: Disturbance recorder
All start and operate signals from the protection stages are routed either to trigger the distu
to be recorded by the disturbance recorder, depending on the parameter settings. Addition
autorecloser, the ARC protection signals and the three binary inputs from X120 are also c
Figure 53: Trip circuit supervision
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3 (X100:15
for PO4 (X100:20-24). Both functions are blocked by the Master Trip (TRPPTRC1 and TR
circuit breaker open signal. The TCS alarm indication is connected to LED 9.
Trip and to the alarm LEDs. LED 1 is used for overcurrent and
ction operate indication. LED 4 is also used for phase
on
V) provides earth-fault protection by detecting abnormal level
as a nonselective backup protection for the selective
on signal is connected to alarm LED 3.
erload and circuit breaker failure protection
1) provides protection for interruptions in the normal three-
ctor situations. The operate signal of the phase discontinuity
o to an alarm LED and the disturbance recorder. The thermal
on on overload situations. The operate signal of the phase
er Trip and also to an alarm LED. LED 4 is used for the phase
me as for negative sequence overcurrent protection operate
rload protection alarm indication.
itiated via the start input by a number of different protection
unction offers different operating modes associated with the
nd residual currents. The breaker failure protection has two
ET operate output is used for retripping its own breaker through
ve a back-up trip to the breaker feeding upstream. For this
ected to the output PO2 (X100:
indication.
ing (DARREC1) are included as optional functions.
ocks for three arc sensors that can be connected to the IED.
erent
esidual current check. Operate signals from the arc protection
and also to the alarm LED 10 as a common operate indication.
operate signals from a number of protection stages through the
l autoreclose sequences for each input.
INHIBIT_RECL input. By default, the operation of selected
A control command to the circuit breaker, either local or remote,
CBR-selected signal.
ure sequence is expressed with the binary input 4 (X110:6-7) by
. In case this signal is completely removed from the autoreclose
es that the breaker is available all the time.
s connected to the alarm LED 11.
terlocking
The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line-s
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input
the configuration logic, which is a combination of the disconnector or breaker truck and ear
statuses and the statuses
of the master trip logics and gas pressure alarm and circuit-breaker spring charging. This c
interlocking conditions is called LOCAL_FEEDER_READY and is transferred also to the
binary signal transfer. The OKPOS output from DCSXSWI defines if the disconnector or
definitely either open (in test position) or close (in service position). This, together with th
and non-active trip signals, activates the close-enable signal to the circuit breaker control
open operation is always enabled.
The auto-recloser close command signals are directly connected to the output contact PO1
The ITL_BYPASS input can be used, for example, to always enable the closing of the circ
the circuit breaker truck is in the test position, despite of the interlocking conditions being
circuit breaker truck is closed in service position.
y inputs 5 and 6
Directional earth-fault protection, low stage, instance 2 DEFLPDEF2 Io> -> (2) 67N-1 (2)
Admittance based earth-fault protection, instance 2 EFPADM2 Yo> -> (2) 21YN (2)
Three-phase thermal protection for feeders, cables and T1PTTR1 3Ith>F 49F
distribution transformers
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Three-phase inrush detector INRPHAR1 3I2f> 68
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)
Control
Additionally, all the digital inputs that are connected by default are also enabled with the setting. Default triggering set
depending on the connected input signal type. Typically all protection START signals are selected to trigger the disturb
default.
3.9.3 Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function- to-fu
The default connections can be viewed and changed with PCM600 according to the applic
if necessary.
The analog channels have fixed connections towards the different function blocks inside t
configuration. Exceptions from this rule are the 12 analog channels available for the distur
function. These channels are freely selectable and a part of the disturbance recorder’s para
The analog channels are assigned to different functions. The common signal marked with
three phase currents and 3U the three phase voltages. The signal marked with Io represent
residual current via a core balance current transformer. The signal marked with Uo represe
residual voltage via open-delta connected voltage transformers.
The EFHPTOC protection function block for double (cross-country) earth-faults uses the c
current originating from the measured phase currents.
Figure 59: Phase discontinuity, thermal overload and circuit breaker failure protecti
The phase discontinuity protection (PDNPSTOC1) provides protection for interruptions in t
phase load supply, for example, in downed conductor situations. The operate signal of the p
protection is connected to the Master Trip and also to an alarm LED and the disturbance rec
overload protection (T1PTTR1) provides indication on overload situations. The operate sign
discontinuity protection is connected to the Master Trip and also to an alarm LED. LED 4 is
discontinuity protection operate indication, the same as for negative sequence overcurrent p
indication, and LED 5 is used for the thermal overload protection alarm indication.
The breaker failure protection (CCBRBRF1) is initiated via the start input by a number of
stages in the IED. The breaker failure protection function offers different operating modes
circuit breaker position and the measured phase and residual currents. The breaker failure
operating outputs: TRRET and TRBU. The TRRET operate output is used for retripping it
through the Master Trip 2. The TRBU output is used to give a back-up trip to the breaker
For this purpose, the TRBU operate output signal is connected to the output PO2 (X100:
8-9). LED 6 is used for back-up (TRBU) operate indication.
Figure 60: Arc protection
Arc protection (ARCSARC1...3) and autoreclosing (DARREC1) are included as optional fu
The arc protection offers individual function blocks for three arc sensors that can be connec
arc protection function block has two different
operation modes, with or without the phase and residual current check. Operate signals fro
function blocks are connected to the Master Trip and also to the alarm LED 10 as a comm
indication.
The autorecloser is configured to be initiated by operate signals from a number of protecti
the INIT1...5 inputs. It is possible to create individual autoreclose sequences for each inpu
The autoreclose function can be blocked with the INHIBIT_RECL input. By default, the o
protection functions are connected to this input. A control command to the circuit breaker
remote, also blocks the autoreclose function via the CBXCBR-selected signal.
The circuit breaker availability for the autoreclosure sequence is expressed with the binary
by connecting the input signal to the CB_RDY input. In case this signal is completely rem
autoreclose function block with PCM600, the function assumes that the breaker is availab
The autoreclose sequence in progress indication is connected to the alarm LED 11.
The fuse failure supervision SEQRFUF1 detects failures in voltage measurement circuits.
open miniature circuit breaker, are detected and the alarm is connected to the alarm LED 9
Failures in current measuring circuits are detected by CCRDIF. When a failure is detected
activated in current protection functions that are measuring calculated sequence componen
unnecessary operation can be avoided. The alarm signal is connected to the alarm LED 9.
on
rip and to the alarm LEDs. LED 1 is used for overcurrent and
ion operate indication. LED 4 is also used for phase
protection
ages (PHxPTOV and PHxPTUV) offer protection against
n of voltage functions is connected to alarm LED 3. A failure in
use failure function and the activation is connected to
undervoltage tripping.
ge and negative-sequence overvoltage protection
negative-sequence overvoltage (NSPTOV) protection
ction. The operation signals of voltage-sequence functions are
d voltage protection alarm LED.
on
V) provides earth-fault protection by detecting abnormal level
as a non- selective backup protection for the selective
D 2.
corder and trip circuit supervision
nterlocking
ected to the two trip output contacts PO3 (X100:15-19) and
Trips TRPPTRC1 and TRPPTRC2. Open control commands to
R1-exe_op or from the auto-recloser DARREC1- open_cb are
9).
unction, event generation and the trip signal duration setting. If
y input can be reassigned to the RST_LKOUT input of the
button.
Figure 67: Circuit breaker control
There are three disconnector status blocks (DCSXSWI1…3) available in the IED. The rem
described in the functional diagram are available in PCM600 for connection where applica
The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (D
circuit-breaker truck position indication.
Table 41: Device positions indicated by binary inputs 5 and 6
The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The inpu
the configuration logic, which is a combination of the disconnector or breaker truck and e
statuses and the statuses
of the master trip logics and gas pressure alarm and circuit-breaker spring charging. This co
interlocking conditions is called LOCAL_FEEDER_READY and is transferred also to the r
binary signal transfer. The OKPOS output from DCSXSWI defines if the disconnector or br
definitely either open (in test position) or close (in service position). This, together with the
and non-active trip signals, activates the close-enable signal to the circuit breaker control fu
open operation is always enabled.
The auto-recloser close command signals are directly connected to the output contact PO1 (
The ITL_BYPASS input can be used, for example, to always enable the closing of the circu
circuit breaker truck is in the test position, despite of the interlocking conditions being activ
breaker truck is closed in service position.
TPGAPC 1...3 are timers used for setting the minimum pulse length for the outputs. Four ge
(TPGAPC1..4) are available in the IED. The remaining one not described in the functional d
in PCM600 for connection where applicable.
Directional earth-fault protection, low stage, instance 2 DEFLPDEF2 Io> -> (2) 67N-1 (2)
Admittance based earth-fault protection, instance 2 EFPADM2 Yo> -> (2) 21YN (2)
Admittance based earth-fault protection, instance 3 EFPADM3 Yo> -> (3) 21YN (3)
Three-phase thermal protection for feeders, cables and T1PTTR1 3Ith>F 49F
distribution transformers
Circuit breaker failure protection CCBRBRF1 3I>/Io>BF 51BF/51NBF
Three-phase inrush detector INRPHAR1 3I2f> 68
Master trip, instance 1 TRPPTRC1 Master Trip (1) 94/86 (1)
Master trip, instance 2 TRPPTRC2 Master Trip (2) 94/86 (2)
Arc protection, instance 1 ARCSARC1 ARC (1) 50L/50NL (1)
Arc protection, instance 2 ARCSARC2 ARC (2) 50L/50NL (2)
Arc protection, instance 3 ARCSARC3 ARC (3) 50L/50NL (3)
Control
Additionally, all the digital inputs that are connected by default are also enabled with the se
triggering settings are selected depending on the connected input signal type. Typically all p
signals are selected to trigger the disturbance recorded by default.
In
K
I
pr r
RSV
fn
In the application nominal current
Ipr the sensor rated primary current
fn network nominal frequency
Kr the sensor rated voltage (in mV) at the rated current
RSV the Rated Secondary Value in mV/Hz
50Hz Hz
With this information, the IED Rogowski sensor settings can be set.
cted by default are also enabled with the setting. Default
connected input signal type. Typically all protection START
orded by default.
d current
The fuse failure supervision SEQRFUF1 detects failures in voltage measurement circuits. F
open miniature circuit breaker, are detected and the alarm is connected to the alarm LED 9.
Failures in current measuring circuits are detected by CCRDIF. When a failure is detected,
activated in current protection functions that are measuring calculated sequence component
unnecessary operation can be avoided. The alarm signal is connected to the alarm LED 9.
tage protection
on (ROVPTOV) provides earth-fault protection by detecting abnormal level of
or example, as a non- selective backup protection for the selective directional
to alarm LED 2.
sturbance recorder and trip circuit supervision
corder
m the protection stages are routed either to trigger the disturbance recorder or
e recorder, depending on the parameter settings. Additionally, the selected
n signals and the two binary inputs from X110 are also connected.
vision
on functions are included, TCSSCBR1 for PO3 (X100:15-19) and
4). Both functions are blocked by the Master Trip (TRPPTRC1 and
er open signal. The TCS alarm indication is connected to LED 9.
cted that there is no external resistor in the circuit breaker tripping coil circuit
with circuit breaker normally open auxiliary contact.
otections are connected to the two trip output contacts PO3 (X100:15-19) and
sponding Master Trips TRPPTRC1 and TRPPTRC2. Open control commands
or remote CBXCBR1-exe_op or from the auto-recloser DARREC1- open_cb
put PO3 (X100:15-19).
ockout/latching function, event generation and the trip signal duration setting.
selected, one binary
input can be reassigned to the RST_LKOUT input of the Master Trip to enable
external reset with a push button.
Figure 82: Circuit breaker control
There are three disconnector status blocks (DCSXSWI1…3) available in the IED. The rema
described in the functional diagram are available in PCM600 for connection where applicab
The binary inputs 5 and 6 of the additional card X110 are used for busbar disconnector (DC
breaker truck position indication.
Table 47: Device positions indicated by binary inputs 5 and 6
The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line-s
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The inpu
the configuration logic, which is a combination of the disconnector or breaker truck and e
statuses and the statuses of the master trip logics and gas pressure alarm and circuit-break
This combination of interlocking conditions is called LOCAL_FEEDER_READY and is t
remote end via binary signal transfer. The OKPOS output from DCSXSWI defines if the d
breaker truck is definitely either open (in test position) or close (in service position). This,
open earth-switch and non-active trip signals, activates the close-enable signal to the circu
function block. The open operation is always enabled.
The auto-recloser close command signals are directly connected to the output contact PO1
The ITL_BYPASS input can be used, for example, to always enable the closing of the circ
circuit breaker truck is in the test position, despite of the interlocking conditions being act
breaker truck is closed in service position.
y inputs 5 and 6
TPGAPC 1...3 are timers used for setting the minimum pulse length for the outputs. Four
(TPGAPC1..4) are available in the IED. The remaining one not described in the functiona
available in PCM600 for connection where applicable.
Additionally, all the digital inputs that are connected by default are also enabled with the se
triggering settings are selected depending on the
connected input signal type. Typically all protection START signals are selected to trigger the disturbance recorded by
3.11.3 Functional diagrams
The functional diagrams describe the default input, output, alarm LED and function- to-fu
The default connections can be viewed and changed with PCM600 according to the applic
if necessary.
The analog channels have fixed connections towards the different function blocks inside t
configuration. Exceptions from this rule are the 12 analog channels available for the distur
function. These channels are freely selectable and a part of the disturbance recorder’s para
The analog channels are assigned to different functions. The common signal marked with
three phase currents and 3U the three phase voltages. The signal marked with Io represent
residual current via a core balance current transformer. The signal marked with Uo represe
residual voltage via open-delta connected voltage transformers.
The EFHPTOC protection function block for double (cross-country) earth-faults uses the c
current originating from the measured phase currents.
tection
nt and short-circuit protection. The instantaneous stage
inary input 1 (X120:1-2). The inrush detection block’s
king the function or multiplying the active settings for any of
rip and to the alarm LEDs. LED 1 is used for overcurrent and
ion operate indication. LED 4 is also used for phase
otection
h-fault protection. One stage is dedicated to sensitive earth-fault
n
initiated via the start input by a number of different protection
n function offers different operating modes associated with the
e and residual currents. The breaker failure protection has two
RET operate output is used for retripping its own breaker
used to give a back-up trip to the breaker feeding upstream.
al is connected to the output PO2 (X100:
te indication.
The fuse failure supervision SEQRFUF1 detects failures in voltage measurement circuits. F
open miniature circuit breaker, are detected and the alarm is connected to the alarm LED 9.
Failures in current measuring circuits are detected by CCRDIF. When a failure is detected,
activated in current protection functions that are measuring calculated sequence component
unnecessary operation can be avoided. The alarm signal is connected to the alarm LED 9.
s expected that there is no external resistor in the circuit breaker tripping coil circuit
rallel with circuit breaker normally open auxiliary contact.
The binary inputs 7 and 8 (X110:11-13) are designed for the position indication of the line
The circuit breaker closing is enabled when the ENA_CLOSE input is activated. The input
the configuration logic, which is a combination of the disconnector or breaker truck and ear
statuses and the statuses of the master trip logics and gas pressure alarm and circuit-breaker
This combination of interlocking conditions is called LOCAL_FEEDER_READY and is tra
remote end via binary signal transfer. The OKPOS output from DCSXSWI defines if the dis
truck is definitely either open (in test position) or close (in service position). This, together
switch and non-active trip signals, activates the close-enable signal to the circuit breaker co
The open operation is always enabled.
The auto-recloser close command signals are directly connected to the output contact PO1 (
The ITL_BYPASS input can be used, for example, to always enable the closing of the circu
circuit breaker truck is in the test position, despite of the interlocking conditions being activ
breaker truck is closed in service position.
TPGAPC 1...3 are timers used for setting the minimum pulse length for the outputs. Four ge
(TPGAPC1..4) are available in the IED. The remaining one not described in the functional d
in PCM600 for connection where applicable.
SXSWI1…3) available in the IED. The remaining two not
e in PCM600 for connection where applicable.
X110 are used for busbar disconnector (DCSXSWI1) or
Accuracy class Current error at rated Phase displacement at rated primary Composite error at
primary current (%) current rated accuracy limit
minutes centiradians primary current (%)
5P ±1 ±60 ±1.8 5
10P ±3 - - 10
The accuracy classes 5P and 10P are both suitable for non-directional overcurrent protecti
provides a better accuracy. This should be noted also if there are accuracy requirements fo
functions (current metering, power metering, and so on) of the IED.
The CT accuracy primary limit current describes the highest fault current magnitude at whic
specified accuracy. Beyond this level, the secondary current of the CT is distorted and it mi
effects on the performance of the protection IED.
In practise, the actual accuracy limit factor (F a) differs from the rated accuracy limit factor (
proportional to the ratio of the rated CT burden and the actual CT burden.
The actual accuracy limit factor is calculated using the formula:
S S
in n
S S
in
F F a n
ransformers
external burden S n
n the high-set stages are not used, the AC component of the fault
times the starting current. Otherwise, the inverse operation time
rent protection
tion is implemented as three-stage definite time non-directional
rrent protection
kA and the minimum three-phase short circuit current is 22.8
calculated to be 59.
s selected to be about twice the nominal current of the cable.
e with the next IED (not visible in the figure above). The
stage are defined also so that grading is ensured with the
rent settings have to be defined so that the IED operates with
e with the maximum load current. The settings for all three
Terminal Description
X120-13, 14 Io
Table 57: Residual current input included in configuration G
Terminal Description
X130–1, 2 Io
Terminal Description
X130-11, 12 U1
X130-13, 14 U2
X130-15, 16 U3
ions
configurations A, B, C, D, E, F and H
and H
uded in configuration G
Table 59: Reference voltage input for SECRSYN1 included in configuration H
Terminal Description
X130-9, 10 U12B
Terminal Description
X120-5, 6 Uo
Table 61: Additional residual voltage input included in configurations E, F and H
Terminal Description
X130-17, 18 Uo
Terminal Description
X131 IL1 U1
X132 IL2 U2
X133 IL3 U3
Terminal Description
X100-1 + Input
X100-2 - Input
sor inputs
ded in configuration G
Terminal Description
X110-1 BI1, +
X110-2 BI1, -
X110-3 BI2, +
X110-4 BI2, -
X110-5 BI3, +
X110-6 BI3, -
X110-6 BI4, -
X110-7 BI4, +
X110-8 BI5, +
X110-9 BI5, -
X110-9 BI6, -
X110-10 BI6, +
X110-11 BI7, +
X110-12 BI7, -
X110-12 BI8, -
X110-13 BI8, +
Terminal Description
X120-1 BI1, +
X120-2 BI1, -
X120-3 BI2, +
X120-2 BI2, -
X120-4 BI3, +
X120-2 BI3, -
X120-5 BI4, +
X120-6 BI4, -
nfigurations A, B, C, D, E, F and H.
igurations B and D.
Table 66: Binary input terminals X130-1...9
Terminal Description
X130-1 BI1, +
X130-2 BI1, -
X130-2 BI2, -
X130-3 BI2, +
X130-4 BI3, +
X130-5 BI3, -
X130-5 BI4, -
X130-6 BI4, +
X130-7 BI5, +
X130-8 BI5, -
X130-8 BI6, -
X130-9 BI6, +
Terminal Description
X130-1 BI1, +
X130-2 BI1, -
X130-3 BI2, +
X130-4 BI2, -
X130-5 BI3, +
X130-6 BI3, -
X130-7 BI4, +
X130-8 BI4, -
The IED is provided with connection sockets X13, X14 and X15 only if the op
communication module with light sensor inputs has been installed. If the arc p
selected when ordering an IED, the light sensor inputs are included in the com
figurations E, F and H.
5.2 Outputs
5.2.1 Outputs for tripping and controlling
Output contacts PO1, PO2, PO3 and PO4 are heavy-duty trip contacts capable of controlling most circuit breakers. On
factory, the trip signals from all the protection stages are routed to PO3 and PO4.
Table 69: Output contacts
Terminal Description
X100-6 PO1, NO
X100-7 PO1, NO
X100-8 PO2, NO
X100-9 PO2, NO
Output contacts of slot X110 are available with configurations B, D, E, F, G and H..
Table 71: Output contacts X110-14...24
Terminal Description
X110-14 X110-15 SO1, common SO1, NO
X110-16 SO1, NC
Output contacts of slot X130 are available in the optional BIO module (BIOB02A). Output
are optional for configurations B and D.
Table 72: Output contacts X130-10...18
Terminal Description
X130-10 X130-11 SO1, common SO1, NO
X130-12 SO1, NC
Terminal Description
X100-3 IRF, common
X100-4 Closed; IRF, or Uaux disconnected
172
Section 6 Glossary
ANSI American National Standards Institute
ASCII American Standard Code for Information Interchange BI
Binary input
BI/O Binary input/output
BO Binary output
CB Circuit breaker
CT Current transformer
DNP3 A distributed network protocol originally developed by Westro
Users Group has the ownership of the protocol and assumes responsibility for its e
EMC Electromagnetic compatibility
GOOSE Generic Object Oriented Substation Event HMI
interface
HW Hardware
IEC International Electrotechnical Commission
IEC 60870-5-103 Communication standard for protective equipment; A serial m
protocol for point-to-point communication
IEC 61850 International standard for substation communication and mod
IED Intelligent electronic device
IP address A set of four numbers between 0 and 255, separated by peri
connected to the Internet is assigned a unique IP address that specifies the locatio
protocol.
IRIG-B Inter-Range Instrumentation Group's time code format B LA
Local area network
LC Connector type for glass fibre cable
LCD Liquid crystal display
LED Light-emitting diode
LHMI Local human-machine interface
LHMI Local human-machine interface
m of the protection IED. Under normal operating conditions,
tected by the self-supervision system or the auxiliary voltage is
Glossary
ndards Institute
de for Information Interchange BI
chnical Commission
rd for protective equipment; A serial master/slave
ss fibre cable
interface
interface
Glossary
Modbus A serial communication protocol developed by the Modicon co
Originally used for communication in PLCs and RTU devices.
Modbus TCP/IP Modbus RTU protocol which uses TCP/IP and Ethernet to carry
devices
PCM600 Protection and Control IED Manager
PO Power output
RCA Also known as MTA or base angle. Characteristic angle.
RJ-45 Galvanic connector type
RS-232 Serial interface standard
RS-485 Serial link according to EIA standard RS485 RTU
unit
Single-line diagram
SO Signal output
TCP/IP Transmission Control Protocol/Internet Protocol TCS
supervision
WAN Wide area network
WHMI Web human-machine interface
174
Contact us
ABB Oy
Distribution Automation
P.O. Box 699
FI-65101 VAASA, Finland Phone +358 10 22 11
Fax +358 10 22 41094
www.abb.com/substationautomation
A serial communication protocol developed by the Modicon company in 1979.
ed for communication in PLCs and RTU devices.
P/IP Modbus RTU protocol which uses TCP/IP and Ethernet to carry data between
Signal output
Transmission Control Protocol/Internet Protocol TCS Trip-circuit
REF615
Application Manual
175
2 11
ent (Xiamen) Co. Ltd. ABB Industrial Park, Torch Hi-tech Development Zone 361006