Unitrol 1000-15
Unitrol 1000-15
Unitrol 1000-15
9.1 General
Continuous current at 60 °C 5A
Overload (maximum 10 s) 30 A DC
Overload (maximum 4 min) 20 A DC
10 to 100 Hz
Frequency range of measuring values UM and Maximum overcurrent 3A
Machine current IM2: Voltage regulation <0.1%
Accuracy:
Test voltage:
Power electronics supply UPWR against case and auxiliary supply UAUX 2830 V DC, 2 s
Auxiliary supply UAUX against case and power electronics supply UPWR 2830 V DC, 2 s
Voltage measurement inputs UM, UNET: High impedance voltage input without galvanic separation
According to (USA, Canada) UL specification:
The screw-type terminals for inputs and outputs are approved for maximum voltage 150 V
9.1.7 Reliability
MTBF (MIL-HDBK-217F) GB(40°C) 4100 FIT / 27.6 years
Plant:
Order No.:
Plant Schematic No.:
Device Identification:
Type Plate:
Delivery Date:
Software Revision: Control:
Panel:
CMT 1000:
Remarks: