SSCM 008
SSCM 008
SSCM 008
UT TH
NO
M
R
GRAVITY FILTERS
55° 21' 39"
I I
N
PLANT
NORTH UT RTH K J I H G F E D C B A' A
NO
128775
M
13650 13650 13650 13650 13650 13650 13650 13650 13650 3675 2250
55° 21' 39"
GENERAL NOTES
N
H H
1. THE PROJECT LOCAL COORDINATES X=0.000,00m AND Y=0.000,00m, ARE IN CORRESPONDANCE WITH
UTM ZONE 39N WGS-84 REFERENCE SYSTEM COORDINATES E=379,000m AND N=2.969,400 m.
2. ALL DIMENSIONS ARE IN mm, UNLESS OTHERWISE INDICATED.
H
G
E
F
3. ALL ELEVATIONS ARE IN m UNLESS OTHERWISE INDICATED.
4. THE PROJECT NORTH FORMS AN ANGLE OF 55º 21' 39'' WITH GEOGRAPHIC NORTH.
5. ALL PROJECT ELEVATIONS WILL BE REFERRED TO PLANT VERTICAL DATUM. THE RELATIONSHIP
BETWEEN PLANT DATUM AND SAUDI ARAMCO VERTICAL DATUM (SAVD) IS: PLANT VERTICAL DATUM
±0,00 m = +3,95 m SAVD. FINISHED GROUND LEVELS ARE:
1500
350
N7 N7 N7 N7 N7 N7 N7 N7 N7 CYLINDER MAX.
MINIMUM
2 CONCRETE
CHARACTERISTIC
COMPRESSION w/c
CEMENT CEMENT EXPOSURE
CONTENT TYPE CONDITION
123200 STRENGTH
(kg/m³)
f 'c (N/mm²) (28 days) RATIO
B B SUPERSTRUCTURES
35 MPa 0,45 C
OVER 2,00M (INDOOR)
SUPERSTRUCTURES BETWEEN
350 0,50M AND 2,00M (OUTDOOR & 40 MPa 0,40 B
G EXPOSED TO WATER) G
FOUNDATIONS & TANKS AND
OTHER STRUCTURES CONTAINING 350 TYPE I
40 MPa 0,40 B
PRODUCT WATER (WITH RISK OF
CHLORIDES BUT NO SULPHATES)
17280
16930
275
275
N4 N4 - FOUNDATIONS: 100 MM
350
2750
- FOUNDATIONS (WITH OR WITHOUT MEMBRANE PROTECTION) : 75 MM
C) OUTDOOR SUPER STRUCTURES (NOT IN CONTACT WITH THE SEA WATER OR IN SPLASH ZONE):
- CONCRETE EXPOSED TO WEATHER ABOVE GROUND: 50MM
F D) INDOOR SUPER STRUCTURES (NOT IN CONTACT WITH THE SEA WATER OR IN SPLASH ZONE): F
- SLAB IN SITU, STAIRS: 40MM
- WALLS, COLUMNS, BEAMS AND INTERNAL FACE OF EXTERNAL WALLS: 50MM
POLYPROPYLENE 2300 9. CEMENTITIUS NON-SHRINK GROUTS SHALL BE USED MAINLY FOR BASE PLATES OF STEEL
POLYPROPYLENE
57360
10750
11100
STEPS
4900
STRUCTURES, SMALL PUMPS, CRANE RAILS, ETC. AS A RULE, PRE-PACKAGED, CEMENTITOUS,
STEPS
C 500
C MINERAL AGGREGATE, NON-SHRINK FLOWABLE GROUT IS RECOMMENDED. SELECTED GROUT
SHALL EXHIBIT THE FOLLOWING PROPERTIES:
POLYPROPYLENE 1800
A) NON-SHRINK WITH THE DIMENSION STABILITY OF ±1.0%
STEPS B) OIL RESISTANT
C) NO METALLIC AGGREGATE
N11 D) CAPABLE OF WITHSTANDING CONTINUED EXPOSURE TO TEMPERATURES IN EXCESS OF 205 °C
10. STEEL TO BE USED IN REBARS IS ASTM A 615 GRADE 60 (CARBON STEEL BARS) WITH fy= 420 MPa.
2750
D D ALL THE REBARS SHALL BE EPOXY COATED WITH THE EXCEPTION OF THOSE ONES LOCATED IN
STRUCTURES EXPOSED TO SEAWATER AND SEAWATER SPRAY WHERE A CATHODIC PROTECTION
METHOD WITH IMPRESSED CURRENT WILL BE USED.
4 DN 250 DN 250
11. EARTHING SYSTEM SHALL COMPLY WITH THE DETAILS INCLUDING IN“21SWCG00056-2-200-
R01BXE-1EG-05-100001_EARTHING SYSTEM DETAILS”
275
N4 N4 12. FOR WATERPROOFING DETAILS REFER TO“21SWCG00056-2-200-R0000U-1C0-19-100001 Civil & Steel
Structure General Notes.
800 13. GENERALLY, ALL ABOVE GROUND EXPOSED EDGES TO BE CHAMFER, AND SHALL HAVE A 25 mm BY
25 mm CHAMFER UNLESS OTHERWISE NOTED. THIS IS NOT APPLICABLE FOR EXPOSED CORNERS
INSIDE BUILDINGS.
14. FOR THE SOIL IMPROVEMENT DETAILS IN EACH AREA REFER TO SOIL IMPROVEMENT
SUBCONTRACTOR DOCUMENTS.
15. ANCHOR BOLTS AND NUTS SPECIFICATIONS AS PER“21SWCG00056-2-200-R0000U-1C0-19-100001
Civil & Steel Structure General Notes" UNLESS OTHERWISE INDICATED IN THE DRAWING.
E E
REFERENCE DRAWINGS
17280
16930
PARTICULAR NOTES
LEGEND:
1. F.F.L. FINISH FLOOR LEVEL
5 2. F.G.L. FINISH GOUND LEVEL
350
0 1 5 10 15m
SCALE 1:150
E
H
002 01/08/2023 CONSTRUCTION PHA JDB MPC MPC DSP
D
D
D
E
WE
NE
OV
KE
WN
SIG
VIE
EC
PR
REV No.: DATE: ISSUED FOR
CH
DR
RE
AP
DE
DRAWING
DRAWING STATUS LABEL
STATUS
Mashroat
C C
OWNER :
OWNER'S ENGINEER:
A A' B C D E F G H I J K
129300
3675 13650 13650 13650 13650 13650 13650 13650 13650 13650 175
CONTRACTOR : CONSORTIUM OF
HANDRAIL
DETAIL DETAIL
02 01
HANDRAIL SAUDI SERVICES FOR ELECTRO MECHANIC WORKS CO,
SHOKR
4360
DESIGNER:
400
12 11 10 9 8 7 6 5 4 3 2 1