FusionModule2000 6.

0 Smart Modular Data


Center

Product Description

Issue 06
Date 2023-11-30

HUAWEI DIGITAL POWER TECHNOLOGIES CO., LTD.


Copyright © Huawei Digital Power Technologies Co., Ltd. 2023. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Digital Power Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are the property of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei
Digital Power Technologies Co., Ltd. and the customer. All or part of the products, services and features
described in this document may not be within the purchase scope or the usage scope. Unless otherwise
specified in the contract, all statements, information, and recommendations in this document are
provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Digital Power Technologies Co., Ltd.


Address: Huawei Digital Power Antuoshan Headquarters

Futian, Shenzhen 518043

People's Republic of China

Website: https://digitalpower.huawei.com

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. i


FusionModule2000 6.0 Smart Modular Data Center
Product Description About This Document

About This Document

Purpose
The FusionModule2000 6.0 smart modular data center solution includes smart
modules A and B. This document describes the product positioning, features,
application scenarios, and system architecture of the smart modular data center
(smart module for short) to help you systematically understand the smart module.

Intended Audience
This document is intended for:
● Technical support engineers
● System engineers
● Sales engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description

Indicates a hazard with a high level of risk


which, if not avoided, will result in death or
serious injury.

Indicates a hazard with a medium level of risk


which, if not avoided, could result in death or
serious injury.

Indicates a hazard with a low level of risk


which, if not avoided, could result in minor or
moderate injury.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. ii


FusionModule2000 6.0 Smart Modular Data Center
Product Description About This Document

Symbol Description

Indicates a potentially hazardous situation


which, if not avoided, could result in
equipment damage, data loss, performance
deterioration, or unanticipated results.
NOTICE is used to address practices not
related to personal injury.

Supplements the important information in the


main text.
NOTE is used to address information not
related to personal injury, equipment damage,
and environment deterioration.

Change History
Issue Date Description

06 2023-11-30 ● Added 7.3.10 WLAN


Antenna.
● Updated 7.3.5 PAD.
● Updated 7.3.13.2
IVS1800.

05 2023-07-30 Added the N+1 power


supply and distribution
system (smart busbar 2.0
LAN switch scenario).

04 2023-04-30 ● Added the description


about aisle end doors.
● Added the description
about the integrated
UPS (180 kVA).

03 2023-03-15 Deleted the scenario


where lithium batteries
are deployed inside a
smart module.

02 2023-01-30 Updated the description


about the multi-
functional sensor.

01 2022-10-30 This issue is the first


official release.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. iii
FusionModule2000 6.0 Smart Modular Data Center
Product Description Contents

Contents

About This Document................................................................................................................ ii


1 Positioning................................................................................................................................ 1
2 Features..................................................................................................................................... 2
3 Typical Application Scenarios and Configurations.......................................................... 4
3.1 Typical Application Scenarios.............................................................................................................................................. 4
3.2 Typical Configurations........................................................................................................................................................... 4
3.3 Structure Configuration Solution....................................................................................................................................... 8
3.3.1 Dual-Row 1200 mm Wide Aisle Containment...........................................................................................................9

4 Cabinet Aisle System............................................................................................................ 10


4.1 Cabinets and Accessories................................................................................................................................................... 10
4.1.1 Network Cabinet................................................................................................................................................................ 10
4.1.2 IT Cabinet............................................................................................................................................................................. 11
4.1.3 Top Enclosure Plate...........................................................................................................................................................13
4.1.4 Cabinet Bottom Sealing Kit............................................................................................................................................ 14
4.1.5 Cabinet Enclosure Plate................................................................................................................................................... 15
4.2 Aisle and Mechanical Parts............................................................................................................................................... 16
4.2.1 Skylight................................................................................................................................................................................. 17
4.2.2 Door Header........................................................................................................................................................................ 19
4.2.3 Aisle End Door.................................................................................................................................................................... 20
4.2.3.1 Sliding Door..................................................................................................................................................................... 20
4.2.3.2 Revolving Door................................................................................................................................................................21
4.2.3.3 Electric Sliding Door...................................................................................................................................................... 23
4.2.3.4 Smart Screen Door Box................................................................................................................................................ 25
4.2.4 M-shaped Cable Trough.................................................................................................................................................. 26
4.2.5 Mesh Cable Trough........................................................................................................................................................... 27
4.2.6 Cable Tray.............................................................................................................................................................................28
4.2.7 Adaptive Frame.................................................................................................................................................................. 29
4.2.8 Ground Copper Bar........................................................................................................................................................... 30

5 Power Supply and Distribution System........................................................................... 33


5.1 System Description............................................................................................................................................................... 33
5.1.1 Power Supply and Distribution System for Smart Module A............................................................................. 33

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. iv


FusionModule2000 6.0 Smart Modular Data Center
Product Description Contents

5.1.2 Power Supply and Distribution System for Smart Module B............................................................................. 39
5.2 Hardware Description.......................................................................................................................................................... 49
5.2.1 Integrated UPS (180 kVA).............................................................................................................................................. 49
5.2.1.1 Product Structure........................................................................................................................................................... 49
5.2.1.2 Technical Specifications............................................................................................................................................... 51
5.2.1.2.1 Physical and Electrical Specifications...................................................................................................................51
5.2.1.2.2 Environmental Specifications................................................................................................................................. 55
5.2.1.2.3 Safety Compliance and EMC Specifications...................................................................................................... 55
5.2.2 Integrated UPS (60 kVA, 125 kVA).............................................................................................................................. 56
5.2.2.1 Product Structure........................................................................................................................................................... 56
5.2.2.2 Technical Specifications............................................................................................................................................... 58
5.2.2.2.1 Physical and Electrical Specifications...................................................................................................................58
5.2.2.2.2 Environmental Specifications................................................................................................................................. 62
5.2.2.2.3 Safety and EMC........................................................................................................................................................... 62
5.2.3 Integrated UPS (30 kVA–180 kVA).............................................................................................................................. 62
5.2.3.1 Product Structure........................................................................................................................................................... 62
5.2.3.2 Technical Specifications............................................................................................................................................... 63
5.2.3.2.1 Physical and Electrical Specifications...................................................................................................................63
5.2.3.2.2 Environmental Specifications................................................................................................................................. 68
5.2.3.2.3 Safety and EMC........................................................................................................................................................... 68
5.2.4 Integrated PDF................................................................................................................................................................... 70
5.2.5 Precision PDF...................................................................................................................................................................... 73
5.2.6 NMW Smart Busbar..........................................................................................................................................................74
5.2.6.1 NMW Smart Busbar 2.1............................................................................................................................................... 75
5.2.6.1.1 General Input Unit..................................................................................................................................................... 75
5.2.6.1.2 Power Distribution Unit............................................................................................................................................ 81
5.2.6.1.3 Busbar Trunking Unit................................................................................................................................................ 85
5.2.6.2 NMW Smart Busbar 2.0............................................................................................................................................... 87
5.2.6.2.1 General Input Unit..................................................................................................................................................... 88
5.2.6.2.2 Power Distribution Unit............................................................................................................................................ 95
5.2.6.2.3 Busbar Trunking Unit................................................................................................................................................ 97
5.2.7 Smart Cooling Product PDB........................................................................................................................................... 98
5.2.8 Battery Cabinet................................................................................................................................................................ 100
5.2.8.1 Lithium Battery Cabinet SmartLi 3.0.....................................................................................................................100
5.2.8.1.1 Product Structure..................................................................................................................................................... 101
5.2.8.1.2 Technical Specifications..........................................................................................................................................101
5.2.8.2 Lead-Acid Battery Cabinet........................................................................................................................................ 105
5.2.9 rPDU.................................................................................................................................................................................... 108
5.2.9.1 Basic rPDU......................................................................................................................................................................108
5.2.9.2 Smart rPDU.................................................................................................................................................................... 109
5.2.9.3 PDU2000M..................................................................................................................................................................... 111

6 Temperature Control System............................................................................................118

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. v


FusionModule2000 6.0 Smart Modular Data Center
Product Description Contents

6.1 System Overview................................................................................................................................................................ 118


6.2 Hardware Description....................................................................................................................................................... 118
6.2.1 FusionCol5000-A065 Smart Cooling Product........................................................................................................ 118
6.2.1.1 Indoor Unit..................................................................................................................................................................... 119
6.2.1.2 Outdoor Unit................................................................................................................................................................. 122
6.2.1.2.1 FusionCol500-A090..................................................................................................................................................123
6.2.1.2.2 FusionCol500-P090.................................................................................................................................................. 124
6.2.1.3 Environment and Space Requirements................................................................................................................ 124
6.2.1.4 Technical Specifications............................................................................................................................................. 126
6.2.1.4.1 Indoor Unit................................................................................................................................................................. 127
6.2.1.4.2 Outdoor Unit............................................................................................................................................................. 129
6.2.2 FusionCol5000-A050 Smart Cooling Product........................................................................................................ 132
6.2.2.1 Indoor Unit..................................................................................................................................................................... 133
6.2.2.2 Outdoor Unit................................................................................................................................................................. 136
6.2.2.2.1 FusionCol500-A070..................................................................................................................................................137
6.2.2.2.2 FusionCol500-P090.................................................................................................................................................. 138
6.2.2.3 Environment and Space Requirements................................................................................................................ 139
6.2.2.4 Technical Specifications............................................................................................................................................. 141
6.2.2.4.1 Indoor Unit................................................................................................................................................................. 141
6.2.2.4.2 Outdoor Unit............................................................................................................................................................. 143
6.2.3 NetCol5000-A (025, 035) Smart Cooling Product............................................................................................... 146
6.2.3.1 Indoor Unit..................................................................................................................................................................... 146
6.2.3.2 Outdoor Unit................................................................................................................................................................. 148
6.2.3.3 Environment and Space Requirements................................................................................................................ 149
6.2.3.4 Technical Specifications............................................................................................................................................. 151
6.2.4 NetCol5000-A050 Smart Cooling Product..............................................................................................................155
6.2.4.1 Indoor Unit..................................................................................................................................................................... 155
6.2.4.2 Outdoor Unit................................................................................................................................................................. 159
6.2.4.3 Environment and Space Requirements................................................................................................................ 159
6.2.4.4 Technical Specifications............................................................................................................................................. 162

7 Management System......................................................................................................... 169


7.1 System Description............................................................................................................................................................ 169
7.2 System Functions................................................................................................................................................................ 170
7.2.1 Monitoring......................................................................................................................................................................... 170
7.2.2 App View (PAD)............................................................................................................................................................... 171
7.2.3 App View (Smart Screen)............................................................................................................................................. 175
7.2.4 Alarm................................................................................................................................................................................... 176
7.2.5 History Query................................................................................................................................................................... 176
7.2.6 Linkage Control................................................................................................................................................................177
7.3 Hardware Description....................................................................................................................................................... 177
7.3.1 ECC800-Pro........................................................................................................................................................................ 177
7.3.1.1 Product Configuration................................................................................................................................................ 177

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. vi


FusionModule2000 6.0 Smart Modular Data Center
Product Description Contents

7.3.1.2 Main Control Module................................................................................................................................................. 179


7.3.1.3 PSU................................................................................................................................................................................... 185
7.3.2 UIM20A Expansion Module......................................................................................................................................... 186
7.3.3 Smart ETH Gateway....................................................................................................................................................... 189
7.3.4 FusionModule Actuator................................................................................................................................................ 191
7.3.5 PAD...................................................................................................................................................................................... 195
7.3.6 Smart Screen.....................................................................................................................................................................196
7.3.7 4G Antenna....................................................................................................................................................................... 197
7.3.8 RF_Z Antenna................................................................................................................................................................... 198
7.3.9 WiFi Module......................................................................................................................................................................199
7.3.10 WLAN Antenna.............................................................................................................................................................. 200
7.3.11 Environment Monitoring System............................................................................................................................ 201
7.3.11.1 WLDS900 Water Sensor.......................................................................................................................................... 201
7.3.11.2 Cabinet Temperature Sensor................................................................................................................................. 202
7.3.11.3 T/H Sensor................................................................................................................................................................... 203
7.3.11.4 Ambient T/H Sensor................................................................................................................................................. 204
7.3.11.5 Multi-Functional Sensor..........................................................................................................................................205
7.3.11.6 Alarm Beacon............................................................................................................................................................. 209
7.3.11.7 Smoke Sensor............................................................................................................................................................. 211
7.3.12 Access Control System................................................................................................................................................ 211
7.3.12.1 Access Actuator.......................................................................................................................................................... 211
7.3.12.2 Automatic Door Status Sensor............................................................................................................................. 215
7.3.12.3 Fingerprint and Card Reader with a Keypad................................................................................................... 216
7.3.12.4 Fingerprint and Card Reader................................................................................................................................. 218
7.3.12.5 Card Reader with a Keypad................................................................................................................................... 219
7.3.12.6 Cabinet Fingerprint and Card Lock..................................................................................................................... 220
7.3.12.7 Magnetic Lock............................................................................................................................................................ 221
7.3.12.8 Cabinet Electronic Lock........................................................................................................................................... 222
7.3.12.9 Cabinet Door Status Sensor...................................................................................................................................223
7.3.13 Video Surveillance System......................................................................................................................................... 224
7.3.13.1 Camera.......................................................................................................................................................................... 224
7.3.13.2 IVS1800......................................................................................................................................................................... 225
7.3.14 Aisle Light........................................................................................................................................................................ 227
7.3.15 eLight................................................................................................................................................................................ 228
7.3.16 Atmosphere Light......................................................................................................................................................... 230
7.3.17 (Optional) Smart U Space Manager...................................................................................................................... 231
7.4 NetEco.................................................................................................................................................................................... 232
7.4.1 System Description......................................................................................................................................................... 232
7.4.2 Hardware Description.................................................................................................................................................... 233
7.4.2.1 Server............................................................................................................................................................................... 233
7.4.2.2 LAN Switch..................................................................................................................................................................... 234
7.5 iManager-M.......................................................................................................................................................................... 234

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. vii
FusionModule2000 6.0 Smart Modular Data Center
Product Description Contents

8 Surge Protection and Grounding System...................................................................... 235


9 Integrated Cabling System............................................................................................... 237
A Acronyms and Abbreviations........................................................................................... 239

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. viii
FusionModule2000 6.0 Smart Modular Data Center
Product Description 1 Positioning

1 Positioning

FusionModule2000 6.0 is a new-generation smart module dedicated to providing


users with simple, reliable, and efficient data center solutions. It has obtained the
world's first Uptime Tier IV Ready certification that proves the highest reliability.
The FusionModule2000 6.0 adopts modular design. It integrates power supply and
distribution, cooling, cabinet aisle, cabling, and monitoring into one module to
meet the requirements for fast delivery and on-demand deployment. Furthermore,
the smart module uses the i3 intelligent management system to comprehensively
improve the reliability and energy efficiency of power supply and cooling systems.
The management system significantly improves operation and maintenance
(O&M) efficiency by alarm convergence and locating, automatic fault isolation,
and automated asset management.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 1


FusionModule2000 6.0 Smart Modular Data Center
Product Description 2 Features

2 Features

The FusionModule2000 6.0 features high integration, outstanding security and


reliability, space and energy saving, quick installation, compatible architecture, fast
and flexible deployment, intelligent monitoring, and efficient and stable cooling. It
is a next-generation smart modular data center solution.

Modular Architecture and Automatic Design


● Solution productization and modular design meet the requirements for quick
deployment and flexible capacity expansion.
● The eLight status indicator reflects the module status.
● Atmosphere lights enhance user experience.
● The manual or electric sliding doors or revolving doors prevent unauthorized
personnel from entering the equipment room to improve security.
● Lithium batteries adopt modular design and can be added by phase to expand
the capacity along with the increase of loads.
● One smart screen can be shared by a maximum of five smart modules and
can display the NetEco or ECC800-Pro UI.

i3 Intelligent Management
● iPower
– The entire link status of the power supply and distribution system is
displayed in real time, and alarms are intelligently converged and quickly
located.
– Temperature detection (optional) for circuit breaker terminals on power
distribution branches avoids poor connection of branch contacts. In
addition, miniature circuit breakers (MCBs) are hot-swappable and can be
maintained without power-off. This does not affect other branches.
– The smart rPDU (optional) implements socket status monitoring, remote
management, and IT equipment protection.
● iCooling
– The running status of the cooling system is displayed in real time, and
the status of smart cooling products and key components is detected.
– The 3D temperature map (optional) is linked with the cooling system to
eliminate local hotspots, and the load power is linked with the cooling

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 2


FusionModule2000 6.0 Smart Modular Data Center
Product Description 2 Features

system to avoid excessive temperature rise, ensuring the stability of the


temperature field.
– Optimal efficiency adjustment based on artificial intelligence (AI) and
automatic load adjustment plus linkage between indoor and outdoor
units reduce energy consumption for cooling by 8%–15%.
– Smart cooling products can be quickly restarted upon power-on, which
effectively prevents excessive temperature rise caused by long-time
restart after power-off.
– Innovative intelligent refrigerant leakage detection prevents cooling
capacity decrease or smart cooling product breakdown.
● iManage
– Room-level 3D visualized management and precise alarm locating
considerably improve O&M efficiency.
– The large screen displays information about key service segments such as
the monitoring view, alarm, energy efficiency analysis, capacity, and
battery.
– Aisle-level face recognition and access control information query enable
access control management to be more intuitive and reliable.
– U space-level asset management (optional) implements automated asset
control to maximize the use of cooling and power resources in the
equipment room.
– Infrastructure O&M KPIs standardize O&M actions and improve device
health.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 3


FusionModule2000 6.0 Smart Modular Data Center
Product Description 3 Typical Application Scenarios and Configurations

3 Typical Application Scenarios and


Configurations

3.1 Typical Application Scenarios


The FusionModule2000 6.0 uses an air-cooled cooling system and is mainly
applicable to small- and medium-sized data centers. The solution features simple
design and high building adaptability, lowering the requirements of room height
and reconstruction. It meets the data center deployment requirements of various
sectors such as enterprise headquarters or large branches, bank headquarters and
secondary branches, governments, carriers, education, and healthcare.

3.2 Typical Configurations


Smart modules are classified into smart module A and smart module B by
different power supply and distribution systems.

● Smart module A: The integrated UPS and air conditioner are deployed inside
the smart module. Lead-acid batteries can be deployed either inside or
outside the smart module. Lithium batteries are deployed outside the smart
module.
● Smart module B: The UPS and lead-acid batteries or lithium batteries are
deployed outside the smart module. The power distribution frame (PDF) and
air conditioner are deployed inside the smart module.

Table 3-1 Typical configurations

Smart Module Inside Smart Module Outside Smart Module


Scenario

Smart module A (lead- Integrated UPS, smart -


acid batteries deployed cooling product, lead-acid
inside the module) battery, cabinet, aisle,
and mechanical parts

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 4


FusionModule2000 6.0 Smart Modular Data Center
Product Description 3 Typical Application Scenarios and Configurations

Smart Module Inside Smart Module Outside Smart Module


Scenario

Smart module A (lead- Integrated UPS, smart Lead-acid battery or


acid batteries or lithium cooling product, cabinet, lithium battery
batteries deployed aisle, and mechanical
outside the module) parts

Smart module B Integrated PDF, smart UPS and lead-acid


(integrated PDF) cooling product, cabinet, battery or lithium battery
aisle, and mechanical
parts

Smart module B Precision PDF, smart UPS, lead-acid battery or


(precision PDF) cooling product, cabinet, lithium battery, and
aisle, and mechanical smart cooling product
parts PDB

Smart module B NMW, smart cooling UPS, lead-acid battery or


(NMW) product, cabinet, aisle, lithium battery, and
and mechanical parts smart cooling product
PDB

NOTE

Devices inside and outside the smart module can be deployed in one room or two rooms. If
they are deployed in one room, the smart module adopts the hot aisle containment design
to ensure that the ambient temperature for batteries meets requirements.

Table 3-2 Layout solutions


Smart N+1 Scenario 2N Scenario
Module
Scenario

Smart
module
A (lead-
acid
batteries
deployed
inside
the
module)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 5


FusionModule2000 6.0 Smart Modular Data Center
Product Description 3 Typical Application Scenarios and Configurations

Smart N+1 Scenario 2N Scenario


Module
Scenario

Smart
module
A (lead-
acid
batteries
or
lithium
batteries
deployed
outside
the
module)

Smart
module
B
(integrat
ed PDF
or
precision
PDF)

Smart
module
B (NMW
smart
busbar)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 6


FusionModule2000 6.0 Smart Modular Data Center
Product Description 3 Typical Application Scenarios and Configurations

Table 3-3 Power distribution specifications


Smart Power Specifications
Module Supply
Scenario and
Distributi
on System

Smart Integrated ● Configured with 30 kVA power modules, 24


module A UPS power distribution routes for IT equipment, and
8 power distribution routes for smart cooling
products
● Both the 60 kVA and 125 kVA models have one
MCCB input or two ATS inputs. The 180 kVA
model has one MCCB input.
● Supports a maximum of 60 kW, 125 kW, or 180
kW IT loads.
● 60 kVA: supports a maximum of (2+1) modules
(30 kVA per module).
125 kVA: supports a maximum of (5+1)
modules. (If Requisite modules is set to 5, the
maximum output capability of a single module is
25 kVA.)
180 kVA: supports a maximum of (6+1) modules
(30 kVA per module).

Smart Integrated 160 A/250 A power input (input circuit breakers for
module B PDF IT equipment and smart cooling products), 48
power distribution routes for IT equipment, 16
power distribution routes for smart cooling
products, 6 power distribution routes (dual inputs)
for lighting or 3 power distribution routes (single
input) for lighting, supporting 95 kW/148.5 kW IT
loads

Precision 160 A/250 A/400 A/630 A power input, maximum


PDF 144 power distribution routes for IT equipment,
supporting 95 kW/148.5 kW/235 kW/310 kW IT
loads

Smart 250 A/400 A power input, supporting 123 kW/198


busbar 2.0 kW IT loads

Smart ● 250 A/400 A/630 A model with switches: 250


busbar 2.1 A/400 A/630 A MCCB input, 225 A/360 A/462 A
input current, supporting 148 kW/237 kW/304
kW IT loads
● 630 A model without switches: 630 A input,
supporting 415 kW IT loads

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 7


FusionModule2000 6.0 Smart Modular Data Center
Product Description 3 Typical Application Scenarios and Configurations

3.3 Structure Configuration Solution


Table 3-4 Structure of a smart module with dual-row aisle containment

Dual-Row Aisle Containment

Table 3-5 Smart module installation modes

Without a Raised Floor With a Raised Floor

Typically, overhead cabling and overhead Typically, overhead cabling and underfloor or
piping overhead piping

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 8


FusionModule2000 6.0 Smart Modular Data Center
Product Description 3 Typical Application Scenarios and Configurations

3.3.1 Dual-Row 1200 mm Wide Aisle Containment


The dual-row 1200 mm wide aisle containment can be a cold or hot aisle
containment that involves the following components: IT cabinet, network cabinet,
PDF, smart cooling product, battery cabinet, skylight, end door, and cable trough.
A cold aisle containment is used as an example.

Figure 3-1 Components of the dual-row 1200 mm wide cold aisle containment

(1) End door (2) Control skylight (3) Flat or rotating skylight

(4) Alarm beacon (5) Cable trough (6) Cabinet

(7) Smart screen

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 9


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

4 Cabinet Aisle System

4.1 Cabinets and Accessories

4.1.1 Network Cabinet


The network cabinet provides space for integrated cabling and the cable
management interface for the smart module.

Figure 4-1 Network cabinet

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 10


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Table 4-1 Network cabinet technical specifications


Item Technical Specifications

Dimensions (H x W x ● 2000 mm x 600 mm x 1100 mm (with castors)


D) ● 2000 mm x 600 mm x 1200 mm (with castors)
● 2000 mm x 800 mm x 1200 mm (with castors)
● 2000 mm x 600 mm x 1200 mm (without castors)
● 2200 mm x 600 mm x 1200 mm (without castors)
● 2200 mm x 800 mm x 1200 mm (without castors)

Color Black (PANTONE426C/RAL9005)

Material High-intensity class A carbon cold rolled steel plate


and zinc-coated steel plate

Air channel Front-to-rear air channels

Installation space ● A 2000 mm high cabinet provides 42 U available


space.
● A 2200 mm high cabinet provides 47 U available
space.
● The distance between the front and rear mounting
bars can be adjusted by a step of 25 mm. Positions
at the rear of the cabinet are reserved for installing
two rPDUs vertically.

Installation mode Installed on an ESD floor, a base, or a concrete floor

Door opening mode The front door is a single door, and the rear door is a
double one.

IP rating IP20

4.1.2 IT Cabinet
An IT cabinet complies with the International Electrotechnical Commission (IEC)
60297-1 standard and provides stable installation space for servers in the smart
module, thereby ensuring safe operation of servers.
● Two rPDUs can be vertically installed at the rear of each cabinet.
● The position of each U is marked on the vertical mounting bars.
● The front and rear doors of the cabinet can be locked, and can be unlocked
only by using dedicated keys.
● The cabinet supports a door status sensor and electronic access control.
● The maximum static load of the cabinet is 2400 kg.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 11


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-2 IT cabinet

Table 4-2 Cabinet technical specifications


Item Technical Specifications

Dimensions (H x ● 2000 mm x 600 mm x 1100 mm (with castors)


W x D) ● 2000 mm x 600 mm x 1200 mm (with castors)
● 2000 mm x 800 mm x 1200 mm (with castors)
● 2000 mm x 600 mm x 1100 mm (without castors)
● 2000 mm x 600 mm x 1200 mm (without castors)
● 2200 mm x 600 mm x 1200 mm (without castors)
● 2200 mm x 800 mm x 1200 mm (without castors)

Color Black (PANTONE426C/RAL9005)

Material High-intensity class A carbon cold rolled steel plate and


zinc-coated steel plate

Air channel Front-to-rear air channels

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 12


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Item Technical Specifications

Installation space ● A 2000 mm high cabinet provides 42 U available space.


● A 2200 mm high cabinet provides 47 U available space.
● The distance between the front and rear mounting bars
can be adjusted for every 25 mm.
– For a 1200 mm deep cabinet: The maximum depth for
installing devices inside the cabinet is 750 mm and
can be extended to 850 mm by adjusting the
mounting bars.
– For a 1100 mm deep cabinet: The maximum depth for
installing devices inside the cabinet is 700 mm and
can be extended to 750 mm by adjusting the
mounting bars.
● Positions for vertically installing two rPDUs are provided
in the rear of the cabinet.

Installation mode Installed on an ESD floor, a base, or a concrete floor

Door opening The front door is a single door, and the rear door is a
mode double one.

IP rating IP20

Optional cabinet Cable ring, bottom sealing plate, guide rail, tray, side door
accessories panel, and bottom plate

4.1.3 Top Enclosure Plate


● Top enclosure plates are used to decorate the smart module.
● The top enclosure plates can be 300 mm, 600 mm, or 800 mm wide. They are
installed on the top of cabinets and smart cooling products of the respective
widths.

Figure 4-3 Top enclosure plate

Table 4-3 Dimensions of top enclosure plates

Name Dimensions (H x W x Applicable Cabinet


D)

Top enclosure plate 224.5 mm x 299 mm x 300 mm wide


59.5 mm

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 13


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Name Dimensions (H x W x Applicable Cabinet


D)

224.5 mm x 599 mm x 600 mm wide


59.5 mm

224.5 mm x 799 mm x 800 mm wide


59.5 mm

4.1.4 Cabinet Bottom Sealing Kit


Cabinet bottom sealing kits are used to seal the space under cabinets to ensure
that an aisle is airtight.

Table 4-4 Cabinet bottom sealing kit specifications


Installation Position Type Note

Middle cabinet 300 mm wide front and Applies only to 300 mm


rear sealing plates wide smart cooling
products.

600 mm wide front and Applies only to cabinets


rear sealing plates that are 600 mm wide
and 2000 mm high.

800 mm wide front and Applies only to cabinets


rear sealing plates that are 800 mm wide
and 2000 mm high.

End cabinet Bottom sealing plate Applies only to end


assembly: Front and rear cabinets that are 2000
sealing plates + side mm high.
sealing plates
(assembled by five
components)

Cabinets on both sides of Bottom sealing plate Applies only to cabinets


a column (scenarios with assembly: Front and rear that are located on both
columns) sealing plates + side sides of a column and
sealing plates are 2000 mm high.
(assembled by five
components)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 14


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-4 Bottom sealing plate assembly

(1) Side sealing plate (2) Front or rear sealing plate

Figure 4-5 600 mm/800 mm wide bottom sealing plate

Figure 4-6 300 mm wide bottom sealing plate

4.1.5 Cabinet Enclosure Plate


Enclosure plates are used as aisle sealing plates. Cabinet enclosure plates are 300
mm, 600 mm, or 800 mm wide.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 15


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-7 Cabinet enclosure plate

Table 4-5 Dimensions of cabinet enclosure plates


Name Dimensions (H x W x Applicable Cabinet
D)

2 m cabinet enclosure 2000 mm x 300 mm x 42 300 mm wide


plate mm

2000 mm x 600 mm x 42 600 mm wide


mm

2000 mm x 800 mm x 42 800 mm wide


mm

2.2 m cabinet enclosure 2200 mm x 300 mm x 42 300 mm wide


plate mm

2200 mm x 600 mm x 42 600 mm wide


mm

2200 mm x 800 mm x 42 800 mm wide


mm

4.2 Aisle and Mechanical Parts

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 16


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

4.2.1 Skylight
Skylights are used for sealing an aisle containment. Skylights are classified as
control skylights, rotating skylights, and flat skylights.

Table 4-6 Skylight technical specifications


Name Dimensions (H x W x D) Applicable Cabinet

Control skylight 341 mm x 605 mm x 1334 600 mm wide


mm

341 mm x 805 mm x 1334 800 mm wide


mm

300 mm wide flat 341 mm x 305 mm x 1334 300 mm wide


skylight mm

600 mm wide flat or 341 mm x 605 mm x 1334 600 mm wide


rotating skylight mm

800 mm wide flat or 341 mm x 805 mm x 1334 800 mm wide


rotating skylight mm

300 mm wide 455 mm x 305 mm x 1334 300 mm wide


maintainable flat mm
skylight

600 mm wide 455 mm x 605 mm x 1334 600 mm wide


maintainable flat or mm
rotating skylight

800 mm wide 455 mm x 805 mm x 1334 800 mm wide


maintainable flat or mm
rotating skylight

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 17


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-8 Control skylight

(1) Skylight connective plate (2) Control skylight panel (3) Cable separation panel

NOTE

● Control skylights are installed on both ends of an aisle and used to install monitoring
components such as the camera, multi-functional sensor, and smoke detector.
● If the smart module is longer than 7 m, add one control skylight in the middle of the
smart module for installing a multi-functional sensor or smoke detector.

Figure 4-9 Flat or rotating skylight

(1) Magnetic lock fixing base (2) Glass skylight (3) Skylight connective plate

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 18


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

NOTE

● A rotating skylight is designed with an eccentric structure. When the trigger is activated,
a rotating skylight falls under gravity. The rotating skylight is triggered by a magnetic
lock.
● A rotating skylight requires a magnetic lock but a flat skylight does not.

Figure 4-10 Maintainable flat or rotating skylight

(1) Magnetic lock (2) Glass skylight (3) Removable panel (4) Skylight connective
fixing base plate

NOTE

If smart busbars need to be maintained from the aisle, use a maintainable skylight.

4.2.2 Door Header


A prefabricated door header is preinstalled with the FusionModule Actuator, eLight
actuator, L1 cable, and access control cable.

The cables for the door header need to be connected onsite. The cables (BOM
number: 04095459) should be configured separately.

Figure 4-11 Prefabricated door header

(1) FusionModule Actuator (2) eLight actuator (3) AC/DC power module

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 19


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

4.2.3 Aisle End Door


End doors are installed on both ends of the aisle containment to form an
independent module, which improves equipment efficiency and allows personnel
or equipment to move in and out of the aisle containment.

4.2.3.1 Sliding Door

Figure 4-12 Sliding door (standard configuration, 21501112-003 or


21501113-002)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 20


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-13 Sliding door (advanced configuration, 21501718 or 21501712)

NOTE

Sliding doors can be opened only horizontally. Observe the local fire protection regulations
when using the doors.

4.2.3.2 Revolving Door


The double revolving door is an outward opening door with an opening angle of
90 degrees. It can ensure that the aisle containment is properly sealed and
separated.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 21


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-14 Double revolving door (standard configuration, 21501043-004 or


21501044-002)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 22


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-15 Double revolving door (advanced configuration, 21501713 or


21501714)

4.2.3.3 Electric Sliding Door


The electric sliding door is based on magnetic levitation and is silent, safe, and
easy to open in the case of a power failure.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 23


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-16 Electric sliding door (21501718-001 or 21501712-001)

NOTE

Electric sliding doors can be opened only horizontally. Observe the local fire protection
regulations when using the doors.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 24


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

4.2.3.4 Smart Screen Door Box

Figure 4-17 Smart screen door box (21502418)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 25


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-18 Smart screen door box (21503054)

NOTE

Sliding doors can be opened only horizontally. Observe the local fire protection regulations
when using the doors.

4.2.4 M-shaped Cable Trough


● Cabinet cable troughs are categorized into signal cable troughs and power
cable troughs, which are used to route signal cables and power cables
respectively. This ensures that extra-low voltage (ELV) cables are separated
from electrical cables.
● An M-shaped cable trough consists of several parts that are clamped together.
An M-shaped cable trough is assembled using two side plates, one supporting
plate, and one partition plate (used to separate ELV optical fibers from ELV
network cables and separate electrical route A from electrical route B).
● An M-shaped cable trough can be 300 mm, 600 mm, or 800 mm wide.

Table 4-7 Dimensions of M-shaped cable troughs

Name Dimensions (H x W x D)

M-shaped cable trough 310 mm x 300 mm x 170 mm

310 mm x 600 mm x 170 mm

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 26


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Name Dimensions (H x W x D)

310 mm x 800 mm x 170 mm

Figure 4-19 300 mm wide M-shaped cable trough

(1) Side plate (2) Supporting plate (3) Partition plate

Figure 4-20 600/800 mm wide M-shaped cable trough

(1) Side plate (2) Supporting plate (3) Partition plate (4) Position for the
smart ETH gateway

4.2.5 Mesh Cable Trough


Cable troughs are categorized into signal cable troughs and power cable troughs,
which are used to route signal cables and power cables respectively. This ensures
that ELV cables are separated from electrical cables. The length of cable troughs
needs to be tailored based on the actual aisle length. The cable troughs are
secured to the top of cabinets using fasteners.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 27


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-21 Mesh cable trough

(1) Mesh cable trough (2) Support

4.2.6 Cable Tray


Cable trays are used to route cables across two rows of cabinets in the smart
module. If two rows of cabinets are deployed, route electrical and ELV cables over
the control skylight at either end of the rows preferentially. If there are more than
24 cabinets, install one cable tray on the top of end cabinets for routing power
cables as there are many cables to be routed.
A cable tray is 2.5 m long.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 28


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-22 Cable tray

(1) Cable ladder support (2) Cable ladder

4.2.7 Adaptive Frame


To meet requirements for cabinet height and depth in different scenarios,
enclosure frames, top frames, and adaptive frames may need to be installed. In
this way, all cabinets in the smart module can have the same height and depth
and the two rows of cabinets can have the same length.

Table 4-8 Adaptive frame specifications


Component Width Depth Height Remarks
(mm) (mm) (mm)

Integrated UPS tail 600 100 2000 Increases the cabinet


frame depth by 100 mm.

PDF tail frame 600 100 2000 Increases the cabinet


depth by 100 mm.

300 mm wide 300 100 2000 Increases the cabinet


smart cooling depth by 100 mm.
product enclosure
frame

300 mm wide top 300 1200 200 Increases the cabinet


frame height by 200 mm.

600 mm wide top 600 1200 200


frame

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 29


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Component Width Depth Height Remarks


(mm) (mm) (mm)

300 mm wide 300 1100 2000 When there is an


smart cooling odd number of 300
product adaptive 300 1200 2000 mm smart cooling
frame products, use the
adaptive frame to
supplement the
opposite position to
ensure that the two
rows of cabinets
have the same
length.

4.2.8 Ground Copper Bar


Ground copper bars can be horizontal and vertical. Vertical ground copper bars are
longer than horizontal ones. Ground copper bars are used to ground cabinets.
Ground copper bars are installed in the battery cabinet or IT cabinet closest to the
PDF.

Figure 4-23 Horizontal ground copper bar

Figure 4-24 Vertical ground bar

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 30


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-25 Installation position for a horizontal ground copper bar

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 31


FusionModule2000 6.0 Smart Modular Data Center
Product Description 4 Cabinet Aisle System

Figure 4-26 Installation positions for vertical ground copper bars

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 32


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5 Power Supply and Distribution System

5.1 System Description

5.1.1 Power Supply and Distribution System for Smart Module


A
NOTE

If a smart screen is configured, the PAD obtains power from the L1 layer.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 33


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

N+1 Power Supply and Distribution System Diagram

Figure 5-1 N+1 power supply and distribution system (ATS scenario)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 34


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-2 N+1 power supply and distribution system (MCCB scenario)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 35


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-3 N+1 power supply and distribution system (integrated UPS for
continuous cooling)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 36


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-4 N+1 power supply and distribution system (integrated UPS for
continuous cooling)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 37


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

2N Power Supply and Distribution System Diagram

Figure 5-5 2N power supply and distribution system

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 38


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-6 2N power supply and distribution system (integrated UPS for
continuous cooling)

5.1.2 Power Supply and Distribution System for Smart Module


B
NOTE

If a smart screen is configured, the PAD obtains power from the L1 layer.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 39


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

N+1 Power Supply and Distribution System Diagram

Figure 5-7 N+1 power supply and distribution system (integrated PDF)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 40


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-8 N+1 power supply and distribution system (precision PDF scenario)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 41


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-9 N+1 power supply and distribution system (smart busbar scenario)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 42


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-10 N+1 power supply and distribution system (smart busbar 2.0 LAN
switch scenario)

NOTE

● LAN switch 1: used in the smart module.


● Switch 2: used in the NMW smart busbar 2.0 scenario.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 43


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

2N Power Supply and Distribution System Diagram

Figure 5-11 2N (isolation) power supply and distribution system (integrated PDF)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 44


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-12 2N (non-isolation, dual power supplies for NetCol) power supply and
distribution system (integrated PDF)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 45


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-13 2N (non-isolation, single power supply for NetCol) power supply and
distribution system (integrated PDF)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 46


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-14 2N power supply and distribution system (precision PDF)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 47


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-15 2N power supply and distribution system (smart busbar scenario)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 48


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-16 2N power supply and distribution system (smart busbar 2.0 LAN
switch scenario)

NOTE

● LAN switch 1: used in the smart module.


● Switch 2: used in the NMW smart busbar 2.0 LAN switch scenario.

5.2 Hardware Description


Select devices based on site requirements. For details about the differences
between models or versions, see the corresponding sections.

5.2.1 Integrated UPS (180 kVA)


The integrated UPS (continuous cooling feature) supports S-ECO and power
supply for continuous cooling.

5.2.1.1 Product Structure

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 49


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-17 Appearance

(1) Monitor display unit (MDU)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 50


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-18 Front view

(1) Mains power input status (2) Electricity meter (3) Power distribution fuses for
indicator smart cooling products

(4) IT load switches (5) Bypass input switch (6) Intelligent detection
module

(7) Bypass power input status (8) Lighting switch (9) UPS input switch
indicator

(10) MDU (11) Power distribution (12) Maintenance bypass


monitoring boards switch

(13) UPS output switch (14) Control module (15) Standby extended subrack

(16) Bypass module (17) Power modules

5.2.1.2 Technical Specifications

5.2.1.2.1 Physical and Electrical Specifications

Physical Specifications
Item Specifications

Cabling mode Routed in and out from the top

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 51


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications

IP rating IP20

Dimensions (H x W x 2000 mm x 600 mm x 1100 mm


D)

Communication Supports dry contacts, RS485 serial ports, and FE ports.

Weight 460 kg

Mains Input Electrical Specifications


Item Specifications

Input system Three-phase four-wire + PE

Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)

Input voltage range System specifications (3+1 modules): PF = 1, operating


voltage range 80–280 V AC (phase voltage)
● 0–30°C environment: not derated when the voltage
range is 176–280 V; derated to 40% load or higher
when the voltage range is 176–80 V
● 30–40°C environment: not derated when the
voltage range is 187–280 V; derated to 40% load or
higher when the voltage range is 187–80 V

Input frequency range 40–70 Hz

Rated frequency 50/60 Hz

Input power factor > 0.99 (full load); > 0.98 (half load)

THDi ≤ 3% (linear load; maximum: 3%); ≤ 5% (non-linear


load; maximum: 5%)

Overvoltage category OVC II

Bypass Input Electrical Specifications


Item Specifications

Power system Three-phase four-wire + PE

Rated voltage 380 V AC/400 V AC/415 V AC (line voltage)

Rated frequency 50/60 Hz

Frequency range 50/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6


Hz, ±2 Hz by default)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 52


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications

Overvoltage category OVC II

Battery Electrical Specifications

NOTICE

The UPS supports the SmartLi. For details about related parameters, see the
SmartLi user manual.

Item Specifications

Battery type ● Lead-acid battery (VRLA)


● SmartLi: For the supported version, contact
technical support.

Battery voltage (lead-acid System (3+1 modules) specifications, PF = 1,


battery) operating voltage range: 80–280 V
● 0–30°C environment: not derated when the
voltage range is 176–280 V; derated to 40%
load or higher when the voltage range is 176–
80 V
● 30–40°C environment: not derated when the
voltage range is 187–280 V; derated to 40%
load or higher when the voltage range is 187–
80 V
NOTE
● The default number of batteries is 0. Set this
parameter based on site requirements.
● When the UPS works in normal mode, if the
actual load rate exceeds the threshold that could
trigger battery derating, an output overload alarm
is generated.

Charger output power 5 kW per power module

Cold start When a mains outage occurs, batteries can start


the UPS and supply power to loads.

Charging voltage (lead- ● Equalized charge voltage:


acid battery) 2.3–2.4 V/cell, 2.35 V/cell by default
● Float charge voltage:
2.23–2.3 V/cell, 2.25 V/cell by default

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 53


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Output Electrical Specifications


Item Specifications

Output system Three-phase four-wire + PE

Voltage 380 V AC/400 V AC/415 V AC (line voltage)

Regulated voltage ±1% (balanced load)


precision

Output power factor 1

Transfer time ● Uninterruptible transfer: 0 ms


● Interruptible transfer: ≤ 10 ms

Output voltage Voltage imbalance: ±3%; phase imbalance: 120±1°


imbalance

Bypass overload Bypass overload capability of the system:


capability ● At 30°C: runs continuously at 135% load; generates
only alarms and depends on overtemperature
protection at 135–150% load.
● At 40°C: runs continuously at 125% load; generates
only alarms and depends on overtemperature
protection at 125–150% load.
● Load > 1000%: keeps working for 100 ms (a static
switch is used).

Inverter output short- For the 180 kVA UPS (3+1 modules), 2.55 times of the
circuit capability rated current can be tolerated for 20 ms (that is, the
short-circuit current RMS is 697 A) in the case of
inverter output short-circuit.

Inverter overload Overload capability of the system (3+1 modules):


capability ● 0–40°C, linear load ≤ 100%: long-term operation
● 0–40°C, 100% < linear load ≤ 110%: withstand
duration ≥ 60 min
● 0–40°C, 110% < linear load ≤ 125%: withstand
duration ≥ 10 min
● 0–40°C, 125% < linear load ≤ 150%: withstand
duration ≥ 1 min
● 0–40°C, linear load ≥ 150%: withstand duration ≥
200 ms

System Electrical Specifications


Item Specifications

No-load loss 1.2 kW

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 54


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications

Power distribution TN-S, TN-C, TN-C-S, TT


system

Redundancy and Supported


expansion

5.2.1.2.2 Environmental Specifications

Table 5-1 Environmental specifications

Item Specifications

Operating 0–40°C
temperature

Storage temperature –40°C to +70°C

Relative humidity 0%–95% RH (non-condensing)

Altitude 0–1000 m
When the altitude is higher than 1000 m, the power is
derated as described in IEC 62040-3. The upper limit of
the altitude is 4000 m.

5.2.1.2.3 Safety Compliance and EMC Specifications

Table 5-2 Safety compliance

Safety Certification Standard

CE EN IEC62040-1

CB IEC62040-1

Table 5-3 EMC

EMC Test Item Standard

Conducted emission (CE) EN/IEC 62040-2

Radiated emission (RE) EN/IEC 62040-2

Low-frequency signal immunity IEC 61000-2-2

ESD immunity IEC 61000-4-2

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 55


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

EMC Test Item Standard

Conducted susceptibility (CS) EN/IEC 62040-2


EN/IEC 61000-4-6

Radiated susceptibility (RS) EN/IEC 62040-2


EN/IEC 61000-4-3

Electrical fast transient (EFT) EN/IEC 62040-2


IEC 61000-4-4

Surge EN/IEC 62040-2


IEC 61000-4-5

Lightning protection YD/T 1095

Power magnetic susceptibility (PMS) IEC 61000-4-8

Voltage dips and short interruptions IEC 61000-4-11


(220 V AC)

5.2.2 Integrated UPS (60 kVA, 125 kVA)

5.2.2.1 Product Structure

NOTE

● The appearance of the UPS5000-E-60K-HABBS is similar to that of the UPS5000-E-60K-


HABBS-01, but the number of power modules is different.
● The appearance of the UPS5000-E-125K-HASBS is similar to that of the UPS5000-E-125K-
HASBS-01, but the number of power modules is different.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 56


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-19 UPS5000-E-60K-HABBS front view

(1) Power input status (2) Input circuit breaker (3) Lighting circuit breaker
indicator

(4) Power distribution circuit (5) IT load circuit breakers (6) UPS input circuit breaker
breakers for smart cooling
products

(7) UPS maintenance bypass (8) Control module (9) Bypass module
circuit breaker

(10) Filler panels (11) Power modules (12) Monitor display unit
(MDU)

(13) Power distribution (14) UPS output circuit breaker -


monitoring board

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 57


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-20 UPS5000-E-125K-HASBS-01 front view

(1) Power input status (2) ATS (3) Lighting circuit breaker
indicator

(4) ATS handle installation slot (5) Power distribution circuit (6) IT load circuit breakers
breakers for smart cooling
products

(7) UPS input circuit breaker (8) UPS maintenance bypass (9) Control module
circuit breaker

(10) Bypass module (11) Power modules (12) MDU

(13) Power distribution (14) UPS output circuit breaker -


monitoring board

5.2.2.2 Technical Specifications

5.2.2.2.1 Physical and Electrical Specifications

Table 5-4 Physical specifications

Item Specifications

Cabling mode Routed in and out from the top


Routed in and out from the bottom (tail frame
configured)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 58


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications

IP rating IP20

Dimensions (H x W x 2000 mm x 600 mm x 1100 mm


D) 2000 mm x 600 mm x 1200 mm (tail frame
configured)

Communication Supports dry contacts, RS485 serial ports, and FE ports.

Table 5-5 Mains input electrical specifications


Item Specifications

Input system Three-phase four-wire + PE

Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)

Input voltage range 80–280 V AC (phase voltage)


● 30–40°C environment: not derated when the
voltage range is 187–280 V; linearly derated to 40%
load when the voltage range is 187–80 V
● 0–30°C environment: not derated when the voltage
range is 176–280 V; linearly derated to 40% load
when the voltage range is 176–80 V

Input frequency range 40–70 Hz

Rated frequency 50 Hz/60 Hz

Input power factor > 0.99 (full load); > 0.98 (half load)

THDi ≤ 3% (linear load; maximum: 3%); ≤ 5% (non-linear


load; maximum: 5%)

Table 5-6 Bypass input electrical specifications


Item Specifications

Input mode Three-phase four-wire + PE

Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)

Input frequency range 50/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6


Hz, ±2 Hz by default)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 59


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-7 Battery specifications


Item Specifications

Battery voltage (lead-acid 360–528 V DC


battery) ● 12 V battery: 30–44 batteries, 40 batteries by
default; not derated when there are 36–44
batteries; power derated to 94% when there
are 34 batteries; power derated to 80% when
there are 32 or 30 batteries
● 2 V battery: 180–264 batteries, 240 batteries by
default; not derated when there are 216–264
batteries, power derated to 94% when there
are 204–214 batteries; power derated to 80%
when there are 180–202 batteries.
The number of batteries in the positive battery
string must be the same as that of batteries in
the negative battery string.

Battery management Intelligent battery management

Charger output power (6250 W±200 W) x N. The maximum charge


power of a power module is 6250 W±200 W
(maximum current limiting: 10 A). N indicates the
number of power modules in a rack.

Cold start When a mains outage occurs, batteries can start


the UPS and supply power to loads.

Charging voltage (lead- ● Equalized charge voltage:


acid battery) 2.3 V/cell to 2.4 V/cell, 2.35 V/cell by default
(30–42 batteries)
2.3 V/cell to 2.35 V/cell, 2.35 V/cell by default
(44 batteries)
● Float charge voltage:
2.23 V/cell to 2.3 V/cell, 2.25 V/cell by default
(30–44 batteries)

Table 5-8 Output electrical specifications


Item Specifications

Output system Three-phase four-wire + PE

Voltage 380 V AC/400 V AC/415 V AC (line voltage)

Regulated voltage ±1% (balanced load)


precision

Output power factor 1

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 60


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications

Transfer time ● Uninterruptible transfer: 0 ms


● Interruptible transfer: ≤ 20 ms

Output voltage Voltage imbalance: ±3%; phase imbalance: 120±2°


imbalance

Overload capability Inverter overload capability:


● 100% < load ≤ 110%: transfers to bypass mode
after 60 minutes or longer
● 110% < load ≤ 125%: transfers to bypass mode
after 10 minutes or longer (tolerance ±0.1 minutes)
● 125% < load ≤ 150%: transfers to bypass mode
after 1 minute or longer
● Load > 150% or a short circuit occurs: works for
200 ms
Bypass overload capability:
● 30°C environment: works for a long term at 135%
load
● 40°C environment: works for a long term at 125%
load
● If the bypass single-phase or three-phase has
150%–200% load, the bypass can keep working for
5 minutes.
● If the bypass single-phase or three-phase has more
than 200% load, the bypass can keep working for 1
minute.
● If the load exceeds 1000%, the bypass can keep
working for 100 ms.

Derating coefficient of ● 40 A circuit breaker: 0.75


output circuit breakers ● 63 A circuit breaker: 0.7

Table 5-9 System electrical specifications


Item Specifications

Current equalization 5%
specification

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 61


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.2.2.2 Environmental Specifications

Table 5-10 Environmental specifications


Item Specifications

Operating 0–40°C
temperature

Storage temperature –40°C to +70°C

Humidity 5%–95% RH (non-condensing)

Altitude 0–4000 m
When the altitude is higher than 2000 m, the power is
derated as described in IEC 62040-3. The upper limit of
the altitude is 4000 m.

5.2.2.2.3 Safety and EMC

Table 5-11 Safety compliance


Item Specifications

Safety compliance EN62040-1


IEC62040-1

5.2.3 Integrated UPS (30 kVA–180 kVA)

5.2.3.1 Product Structure

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 62


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-21 Front view of the UPS5000-E-180K-HABBS

(1) Input circuit breaker (2) Power input status (3) Power distribution circuit
indicator breaker for smart cooling
products

(4) IT load circuit breakers (5) UPS input circuit breaker (6) Control module

(7) Bypass module (8) Filler panel (9) Power modules

(10) Lighting circuit breaker (11) Monitoring display unit (12) Power distribution
(MDU) monitoring boards

(13) UPS maintenance bypass (14) UPS output circuit breaker -


circuit breaker

5.2.3.2 Technical Specifications

5.2.3.2.1 Physical and Electrical Specifications

Table 5-12 Physical specifications

Item Specifications

Cabling mode Routed in and out from the top

IP rating IP20

Dimensions (H x W x 2000 mm x 600 mm x 1200 mm (with an enclosure


D) frame)

Communication Supports dry contacts, RS485 serial ports, and FE ports.

Weight 520 kg (including seven power modules)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 63


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-13 Internal switch specifications


Item Specifications

Input MCCB 630 A

UPS input switch 400 A

UPS output switch 400 A

UPS maintenance 400 A


bypass switch

Power distribution for 63 A/3P x 8 (derating coefficient: 0.75)


smart cooling
products

Power distribution for ● 40 A/1P x 24 x 2 (derating coefficient: 0.7)


IT equipment ● 63 A/1P x 24 x 2 (derating coefficient: 0.7)

Table 5-14 Mains input electrical specifications


Item Specifications

Input system Three-phase four-wire + PE

Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)

Input voltage range 80–280 V AC (phase voltage)


● 0–30°C environment: not derated when the voltage
range is 176–280 V; linearly derated to 40% load
when the voltage range is 176–80 V
● 30–40°C environment: not derated when the voltage
range is 187–280 V; linearly derated to 40% load
when the voltage range is 187–80 V

Input frequency range 40–70 Hz

Rated frequency 50/60 Hz

Input power factor > 0.99 (full load); > 0.98 (half load)

THDi ≤ 3% (linear load; maximum: 3%); ≤ 5% (non-linear


load; maximum: 5%)

Overvoltage category OVC II

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 64


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-15 Bypass input electrical specifications


Item Specifications

Power system Three-phase four-wire + PE

Rated voltage 380 V AC/400 V AC/415 V AC (line voltage)

Rated frequency 50/60 Hz

Frequency range 50/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6


Hz, ±2 Hz by default)

Overvoltage category OVC II

Table 5-16 Battery specifications


Item Specifications

Battery voltage (lead-acid 360–528 V DC


battery) ● 12 V battery: 30–44 batteries, 40 batteries by
default; not derated when there are 36–44
batteries; power derated to 94% when there
are 34 batteries; power derated to 80% when
there are 32 or 30 batteries
● 2 V battery: 180–264 batteries, 240 batteries by
default; not derated when there are 216–264
batteries, power derated to 94% when there
are 204–214 batteries; power derated to 80%
when there are 180–202 batteries.
The number of batteries in the positive battery
string must be the same as that of batteries in
the negative battery string.
NOTE
● The default number of batteries is 0. Set this
parameter based on site requirements.
● When the UPS works in normal mode, if the
actual load rate exceeds the threshold that could
trigger battery derating, an output overload alarm
is generated.

Battery management Intelligent battery management

Charger output power (6250 W±200 W) x N. The maximum charge


power of a power module is 6250 W±200 W
(maximum current limiting: 10 A). N indicates the
number of power modules in a rack.

Cold start When a mains outage occurs, batteries can start


the UPS and supply power to loads.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 65


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications

Charging voltage (lead- ● Equalized charge voltage:


acid battery) 2.3 V/cell to 2.4 V/cell, 2.35 V/cell by default
(30–42 batteries)
2.3 V/cell to 2.35 V/cell, 2.35 V/cell by default
(44 batteries)
● Float charge voltage:
2.23 V/cell to 2.3 V/cell, 2.25 V/cell by default
(30–44 batteries)

NOTICE

The UPS supports the SmartLi. For details about the parameters, see the SmartLi
User Manual.

Table 5-17 Output electrical specifications


Item Specifications

Output mode Three-phase four-wire + PE

Voltage 380 V AC/400 V AC/415 V AC (line voltage)

Regulated voltage ±1% (balanced load)


precision

Output power factor 1

Transfer time ● Uninterruptible transfer: 0 ms


● Interruptible transfer: ≤ 20 ms

Output voltage Voltage imbalance: ±3%; phase imbalance: 120°±2°


imbalance

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 66


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications

Overload capability Inverter overload capability:


0°C to 30°C:
● 100% < load ≤ 105%: works for a long time
● 105% < load ≤ 110%: transfers to bypass mode
after 60 minutes
● 110% < load ≤ 125%: transfers to bypass mode
after 10 min (tolerance ± 0.1 min)
● 125% < load ≤ 150%: transfers to bypass mode
after 1 min
● Load > 150% or a short circuit occurs: works for
200 ms
30°C to 40°C:
● 100% < load ≤ 105%: works for a long time
● 105% < load ≤ 110%: transfers to bypass mode
after 60 min
● 110% < load ≤ 125%: transfers to bypass mode
after 3 min (tolerance ±0.1 min)
● 125% < load ≤ 150%: transfers to bypass mode
after 30s
● Load > 150% or a short circuit occurs: works for
200 ms
Bypass overload capability:
● 30°C environment: works for a long term at 135%
load
● 40°C environment: works for a long term at 125%
load
● If the bypass single-phase or three-phase has
150%–200% load, the bypass can keep working for
5 minutes.
● If the bypass single-phase or three-phase has more
than 200% load, the bypass can keep working for 1
minute.
● If the load exceeds 1000%, the bypass can keep
working for 100 ms.
(Note: current test under the 400 V AC voltage
system)

Branch short-circuit 724 A


current

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 67


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-18 System electrical specifications

Item Specifications

Redundancy and Supported


expansion

No-load loss 1 kW

Power distribution ● TN-S, TN-C, TN-CS


system ● TT
● IT

5.2.3.2.2 Environmental Specifications

Table 5-19 Environmental specifications

Item Specifications

Operating 0–40°C
temperature

Storage temperature –40°C to +70°C

Relative humidity 5%–95% RH (non-condensing)

Altitude 0–4000 m
When the altitude is higher than 2000 m, the power is
derated as described in IEC 62040-3. The upper limit of
the altitude is 4000 m.

5.2.3.2.3 Safety and EMC

Table 5-20 Safety compliance

Safety Certification Standard

CE EN 62040-1:2013

CB IEC 62040-1:2013

Table 5-21 EMC

EMC Test Item Standard

Conducted emission (CE) EN/IEC 62040-2

Radiated emission (RE) EN/IEC 62040-2

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 68


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

EMC Test Item Standard

Low-frequency signal interference IEC 61000-2-2

ESD immunity IEC 61000-4-2

Conducted susceptibility (CS) EN/IEC 62040-2


EN/IEC 61000-4-6

Radiated susceptibility (RS) EN/IEC 62040-2


EN/IEC 61000-4-3

Electrical fast transient (EFT) EN/IEC 62040-2


IEC 61000-4-4

Surge EN/IEC 62040-2


IEC 61000-4-5

Lightning protection YD/T 1095-2008

Power magnetic susceptibility (PMS) IEC 61000-4-8

Voltage dips and short interruptions IEC 61000-4-11


(220 V AC)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 69


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.4 Integrated PDF


Figure 5-22 Integrated PDF

Table 5-22 Technical specifications of the integrated PDF

Item Specifications

Engineering Dimensions (H x W x D, ● Basic dimensions: 2000 mm x 600


specification mm) mm x 1100 mm, 2000 mm x 600
s mm x 1200 mm, 2000 mm x 600
mm x 1350 mm
● Extended dimensions: 2200 mm
(with a top frame) x 600 mm x
1200 mm, 2200 mm (with a top
frame) x 600 mm x 1350 mm

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 70


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications

Weight (kg) < 350

Enclosure IP rating IP20

Cabling mode ● 1100 mm deep cabinet: routed in


and out from the top
● 1200 mm deep cabinet: routed in
and out from the top or bottom

Maintenance mode Operated from the front and


maintained from the rear

Installation mode Installed on an ESD floor or concrete


floor

Electrical Rated voltage (V AC) 380/400/415


specification
s Rated insulation voltage 690
(V AC)

Rated frequency (Hz) 50/60

Power distribution input ● One 3-pole 160 A MCCB input


mode of IT equipment ● One 3-pole 250 A MCCB input
● Two 3-pole 160 A MCCB inputs
● Two 3-pole 250 A MCCB inputs

Power distribution input ● One 3-pole 160 A MCCB input


mode of smart cooling ● One 3-pole 250 A MCCB input
products
● Two 3-pole 160 A MCCB inputs
● Two 3-pole 250 A MCCB inputs

Output switch (standard ● Power distribution branch for IT


configuration) equipment: a maximum of 48
branches (single-phase), a
maximum 40 A current for each
branch
● Power distribution branch for smart
cooling products: a maximum of 16
routes (three-phase), a maximum
of 40 A current for each branch
● (Optional) Hot-swappable MCB

Lighting power Dual inputs for smart cooling


distribution products: 6 x 10 A/1P
Single input for smart cooling
products: 3 x 10 A/1P

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 71


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications

Surge protection Level C; nominal discharge current In


(8/20 μs) = 20 kA; maximum
discharge current Imax (8/20 μs) = 40
kA; voltage protection level Up (20 kA,
8/20 μs) ≤ 1.8 kV (L-N), ≤ 1.0 kV (N-
PE)

Monitoring Detection Three-phase input voltage, current,


frequency, active power, reactive
power, electric energy, power factor,
and temperature

Communication mode Modbus TCP and Modbus RTU

(Optional) Branch temperature monitoring

Certification CE and CCC

Table 5-23 Monitoring parameters


Item Specifications

Main power input Phase voltage, phase current, load rate,


frequency, power factor, total active power,
total electric energy, total apparent power,
total reactive power, busbar temperature,
circuit breaker status, and SPD status

Branch power output Phase current, active power, load rate, electric
energy, temperature, and circuit breaker status

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 72


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.5 Precision PDF

Figure 5-23 Precision PDF

Table 5-24 Precision PDF specifications

Item Specifications

Dimensions (H x W x D, 2000 x 600 x 1100, 2000 x 600 x 1200, 2200 x 600 x


mm) 1200

Weight (kg) < 400

Rated operating voltage 380/400/415


(V)

Rated insulation voltage 690


(V)

Rated frequency (Hz) 50/60

Rated operating current 630/400/250/160


(A)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 73


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications

Enclosure IP rating IP20

Output switch ● Single- or three-phase 40 A/63 A; maximum: 144


single-phase routes or 48 three-phase routes
● (Optional) Hot-swappable MCB

Surge protection Level C; nominal discharge current In (8/20 μs) = 20


kA; maximum discharge current Imax (8/20 μs) =
40 kA; voltage protection level Up (20 kA, 8/20 μS)
≤ 1.8 kV (L-N), ≤ 1.0 kV (N-PE)

Cabling mode ● 400 A/250 A/160 A input scenario: routed in and


out from the top or bottom
● 630 A input scenario: routed in from the top and
out from the top or bottom

Certification CCC, CE

Environmental protection RoHS, REACH

Table 5-25 Monitoring specifications


Item Specifications

Main power input Phase voltage, phase current, load rate, frequency,
power factor, total active power, total electric
energy, total apparent power, total reactive power,
busbar temperature, circuit breaker status, and SPD
status

Branch power output Phase current, active power, load rate, electric
energy, temperature, and circuit breaker status

5.2.6 NMW Smart Busbar


Select devices based on site requirements. For details, see the Smart Busbar User
Manual.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 74


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.6.1 NMW Smart Busbar 2.1

Appearance

Figure 5-24 Single-route smart busbar installation scenario

(1) General input unit (2) Connector (3) Power distribution (4) Busbar trunking
unit unit

(5) Column (6) Around-column (7) End plug (8) Single-layer


busbar trunking unit support
and elbow (used in the
scenario with columns)

Figure 5-25 Dual-route smart busbar installation scenario

(1) General input unit (2) Connector (3) Power distribution (4) Busbar trunking
unit unit

(5) Column (6) Around-column (7) End plug (8) Double-layer


busbar trunking unit support
and elbow (used in the
scenario with columns)

5.2.6.1.1 General Input Unit


It is used as a cable entry unit.

Model Number Description

Figure 5-26 General input unit

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 75


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

No. Meaning

1 Smart busbar

2 Input MCCB current level:


0250: 250 A (derated to 225 A at 40°C)
0400: 400 A (derated to 360 A at 40°C)
0630: 630 A (with a switch: derated to 462 A at 40°C; without a
switch: not derated at 40°C)

3 AC

4 Rated 380–415 V, three-phase

5 General input unit

6 Monitoring type

7 1X (if X is an odd number: right-installed; if X is an even number:


left-installed)

Appearance

Figure 5-27 General input unit

The indicators show the running status of the smart busbar system. The BLINK
button is used for the blinking function of the ECC800-Pro.

(1) Alarm indicator (2) BLINK button (3) USB port (4) RS485 DIP switch
(red) and AC power
indicator (green)

(5) Board indicators (6) Monitoring panel (7) Surge protective (8) Input switch
device (SPD)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 76


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

(9) SPD circuit breaker (10) Cable outlet (11) Cable inlet

Figure 5-28 Monitoring panel

(1) NTC port (2) RS485 port (3) FE2 port

(4) FE1 port (5) 48V_OUT port (6) PWR_1 port

Table 5-26 Indicator description


Indicator Color Status Description

AC power Green Steady on The cables at the


cable inlet are
energized, and the
device is running.

Off The cables at the


cable inlet are not
energized, and the
device does not run.

ALM Red Steady on An alarm is generated.

Off No alarm is generated


or the board is not
powered on.

Blinking at 10 Hz (on for Blinking


0.05s and off for 0.05s)

RS485 Green Steady on Master


network
port Off Slave
indicator

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 77


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-29 USB port pins

Table 5-27 USB pin definition


Pin Description

1 5V

2 DM

3 DP

4 GND

NOTE

This port is protected by a security mechanism.

Figure 5-30 RS485, FE, and NTC port pins

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 78


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-28 RS485, FE, and NTC port pin definition


Pin RS485 FE NTC

1 RS485_A LXTMX0+ NTC_1

2 RS485_B LXTMX0– GND

3 NC LXTMX1+ NC

4 RS485_A LXTMX2+ NTC_2

5 RS485_B LXTMX2– GND

6 NC LXTMX1– NTC_3

7 NC LXTMX3+ GND

8 NC LXTMX3– GND

Figure 5-31 PoE port pins

Table 5-29 PoE port pin definition


Pin Description

1 LXTMX0+

2 LXTMX0–

3 LXTMX1+

4 LXTMX2+

5 LXTMX2–

6 LXTMX1–

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 79


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Pin Description

7 LXTMX3+

8 LXTMX3–

Specifications

Table 5-30 Specifications of the general input unit

Input Switch Power Dimensions (H x W x D) Weight


Specifications

250 A/3P 148.5 kW 300 mm x 825 mm x 265 26 kg


mm

400 A/3P 237.6 kW 300 mm x 825 mm x 265 28 kg


mm

630 A/3P with a 304.9 kW 300 mm x 825 mm x 285 33 kg


switch mm

630 A/3P without 415.8 kW 300 mm x 825 mm x 285 31 kg


a switch mm

Figure 5-32 Dimensions of the 630 A general input unit (unit: mm)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 80


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-33 Dimensions of the 400 A/250 A general input unit (unit: mm)

Packed Accessories

Table 5-31 List of accessories


Item Quantity Function

MCCB auxiliary lever 1 PCS Used to operate the


MCCB.

48 V DC parallel cable 1 PCS Used in a 48 V DC power


supply ring network.

5.2.6.1.2 Power Distribution Unit


The power distribution unit is a cable outlet unit from which power is led out from
the busbar trunking unit.

Model Number Description

Figure 5-34 Power distribution unit model

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 81


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

No. Meaning

1 Smart busbar

2 Current level: 125 A

3 AC

4 Rated 380–415 V, three-phase

5 Number of single-phase circuit breakers

6 Number of three-phase circuit breakers

7 Monitoring type

8 11: 16 A output circuit breaker (derated to 12.8 A at 40°C)


12: 40 A output circuit breaker (derated to 32 A at 40°C)
13: 63 A output circuit breaker (derated to 44 A at 40°C)
14: 40 A output circuit breaker (hot-swappable, derated to 32 A
at 40°C)

Appearance

Figure 5-35 Power distribution unit

(1) Monitoring panel (2) BLINK button (3) USB port

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 82


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

(4) RS485 DIP switch (5) Board indicators (6) Load wiring port

(7) Output circuit breaker - -

Figure 5-36 Monitoring panel

(1) PWR_1 (2) 48V_OUT (3) FE port

(4) PoE port (5) RS485 port (6) NTC port

NOTICE

The PoE port on the monitoring panel of the power distribution unit is a reserved
network port.

Table 5-32 Indicator description

Indicator Color Status Description

RUN Green Blinking 0.5 Hz The operation is


(on for 1s and off normal.
for 1s)

Blinking at 10 Hz Blinking
(on for 0.05s and
off for 0.05s)

ALM Red Steady on An alarm is


generated.

Off No alarm is
generated.

RS485 network Green Steady on Master


port indicator
Off Slave

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 83


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Specifications

Table 5-33 Specifications of the power distribution unit


Input Switch Dimensions (H x W x D) Weight
Specifications

16 A/1P 276 mm x 245 mm x 245 10 kg


mm
40 A/1P

40 A/1P (hot-swap
switch)

40 A/3P

63 A/1P

63 A/3P

Figure 5-37 Dimensions of the power distribution unit (unit: mm)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 84


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Packed Accessories

Table 5-34 List of accessories


Item Quantity Function

Sliding block nut 2 PCS Used to install and


assembly secure a power
distribution unit.

5.2.6.1.3 Busbar Trunking Unit


The busbar trunking unit consists of busbars, busbar supports, insulation parts,
housing, fasteners, and connective kits connected to other units.

Model Number Description

Figure 5-38 Busbar trunking unit

No. Meaning

1 Smart busbar

2 Current level:
0250: 250 A
0400: 400 A
0630: 630 A

3 AC

4 Rated 380–415 V, three-phase

5 Busbar trunking unit

6 11: 1200 mm long busbar trunking unit


12: 440 mm long busbar trunking unit
13: around-column busbar trunking unit

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 85


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-35 Specifications of the busbar trunking unit


Length Input Switch Dimensions (H x W x D) Weight
Specifications

440 mm 250 A 440 mm x 175 mm x 102 mm 5.5 kg

400 A 440 mm x 175 mm x 102 mm 6.7 kg

630 A 440 mm x 175 mm x 137 mm 10.5 kg

1200 mm 250 A 1200 mm x 175 mm x 102 mm 13.6 kg

400 A 1200 mm x 175 mm x 102 mm 17.1 kg

630 A 1200 mm x 175 mm x 137 mm 26 kg

Appearance

Figure 5-39 Dimensions of the 630 A busbar trunking unit (unit: mm)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 86


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-40 Dimensions of the 400 A/250 A busbar trunking unit (unit: mm)

Packed Accessories

Table 5-36 List of accessories


Item Quantity Function

M3x8 screw 2 PCS Used to lock the front


cover.

M6x12 screw 4 PCS Used to connect the


busbar trunking unit or
install the end plug.

5.2.6.2 NMW Smart Busbar 2.0

NOTICE

● Use professional insulated tools when installing or operating the equipment.


● The smart busbar must be installed, commissioned, and maintained in strict
accordance with requirements. Otherwise, personal injury or device damage
may occur, and the resulting faults of the smart busbar are beyond the
warranty scope.
● The figures provided in this document are for reference only. The actual product
may vary.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 87


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Appearance

Figure 5-41 Single-route smart busbar installation scenario

(1) General input unit (2) Connector (3) Power distribution (4) Busbar trunking
unit unit

(5) Column (6) Around-column (7) End plug (8) Low support
busbar trunking unit
and elbow (used in the
scenario with columns)

Figure 5-42 Dual-route smart busbar installation scenario

(1) General input unit (2) Connector (3) Power distribution (4) Busbar trunking
unit unit

(5) Column (6) Around-column (7) End plug (8) High support
busbar trunking unit
and elbow (used in the
scenario with columns)

5.2.6.2.1 General Input Unit


It is used as a cable entry unit.

Model Number Description


This document involves the following product models:
● NMW-0400A4-GIU-M01

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 88


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

● NMW-0250A4-GIU-M01
● NMW-0400A4-GIU-M02
● NMW-0250A4-GIU-M02

Figure 5-43 General input unit

No. Meaning

1 Smart busbar

2 Input MCCB current level:


● 0250: 250 A three-phase MCCB
● 0400: 400 A three-phase MCCB

3 AC

4 Rated 380–415 V, three-phase

5 General input unit

6 Monitoring type

7 ● 01 right-mounted
● 02: left-mounted

Appearance

Figure 5-44 General input unit

(1) Alarm indicator (2) Monitoring panel (3) Integrated (4) PWR_2 port
management card

(5) PWR_1 port (6) FE port (7) SPD (8) Input switch

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 89


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

(9) SPD circuit breaker (10) Cable inlet (11) Cable outlet

Table 5-37 Alarm indicator description

Status Description

Steady on An alarm is generated.

Off No alarm is generated or the board is not powered on.

Figure 5-45 Monitoring panel

The monitoring panel displays the running status of the smart busbar system by
indicators, implements the blink function with the ECC800-Pro by the BLINK
button, and provides USB, RS485, FE, and AI/DI ports.

(1) Indicators (2) BLINK button (3) USB port (4) RS485 port

(5) AIDI_1 port (6) FE port (7) AIDI_2 port

Table 5-38 Indicator description

Indicat Color Status Description


or

RUN Green Blinking at 0.5 Hz, on for 1s and then off for The equipment is running
1s. properly.

Blinking at 10 Hz, on for 0.05s and then off The RUN indicator blinks.
for 0.05s.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 90


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Indicat Color Status Description


or

PWR Green Steady on The power supply to the


CPU of the monitoring
board is normal.

Off The power supply to the


CPU of the monitoring
board is abnormal.

ALM Red Steady on There is an alarm.

Off No alarm is generated or


the board is not powered
on.

Figure 5-46 USB pins

Table 5-39 USB pin definition


Pin Description

1 5V

2 DM

3 DP

4 GND

NOTE

The USB port is protected by a security mechanism.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 91


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-47 RS485, FE, and AI/DI pins

Table 5-40 RS485, FE, and AIDI pin definition


Pin RS485 FE AIDI

1 RS485+ TRX0+ -

2 RS485– TRX0- -

3 - TRX1+ GND

4 RS485+ TRX2+ -

5 RS485– TRX2- -

6 - TRX1- GND

7 - TRX3+ AIDI_1+

8 - TRX3- -

Figure 5-48 Integrated management card (optional)


The card supports 48 V DC power supply and FE communication extension. It is
hot-swappable.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 92


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

(1) PWR indicator (2) POE port (3) 48 V output port

Figure 5-49 Smart module LAN switch (optional)

(1) PoE ports

Figure 5-50 POE pins

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 93


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-41 POE pin definition


Pin Description

1 TRX0+_RTN

2 TRX0-_RTN

3 TRX1+_-48V

4 TRX2+_RTN

5 TRX2-_RTN

6 TRX1-_-48V

7 TRX3+_-48V

8 TRX3-_-48V

Specifications
● When the input switch is 400 A, the dimensions (H x W x D) of the general
input unit are 300 mm x 600 mm x 220 mm.

Figure 5-51 Dimensions of the 400 A general input unit (unit: mm)

● When the input switch is 250 A, the dimensions (H x W x D) of the general


input unit are 270 mm x 600 mm x 220 mm.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 94


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-52 Dimensions of the 250 A general input unit (unit: mm)

5.2.6.2.2 Power Distribution Unit


The power distribution unit is a cable outlet unit from which power is led out from
the busbar trunking unit.

Model Number Description


This document involves the following product models:
● NMW-125A4-0/2-M01
● NMW-125A4-6/0-M02
● NMW-125A4-0/2-M02
● NMW-125A4-6/0-M04
● NMW-125A4-6/0-M03
● NMW-125A4-0/2-M03

Figure 5-53 Power distribution unit model

No. Meaning

1 Smart busbar

2 Current level: 125 A (derated to 88 A, ambient temperature ≤


40°C)

3 AC

4 Rated 380–415 V, three-phase

5 Number of single-phase circuit breakers

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 95


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

No. Meaning

6 Number of three-phase circuit breakers

7 Monitoring type

8 ● 01: 16 A single-phase MCB


● 02: 40 A single-phase/three-phase MCB
● 03: 63 A single-phase/three-phase MCB
● 04: 40 A single-phase MCB (hot-swappable)

Appearance

Figure 5-54 Power distribution unit

(1) Load wiring port (2) PWR_1 port (3) FE1 port (4) Monitoring panel

(5) Integrated (6) FE2 port (7) PWR_2 port (8) Output circuit
management card breaker (behind the
cover)

NOTICE

The monitoring panel, integrated management card model, and FE port


definitions of the power distribution unit and general input unit are the same.

Specifications
Dimensions (H x W x D): 255 mm x 250 mm x 220 mm

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 96


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.6.2.3 Busbar Trunking Unit


The busbar trunking unit consists of busbars, busbar supports, insulation parts,
housing, fasteners, and connective kits connected to other units.

Model Number Description


This document involves the following product models:

● NMW-0250A4-BTU-01
● NMW-0400A4-BTU-01
● NMW-0400A4-BTU-02
● NMW-0400A4-BTU-03

Figure 5-55 Busbar trunking unit

No. Meaning

1 Smart busbar

2 Current level:
0250: for the general input unit with a 250 A MCCB
0400: for the general input unit with a 400 A MCCB

3 AC

4 Rated 380–415 V, three-phase

5 Busbar trunking unit

6 01: 1200 mm long busbar trunking unit


Dimensions (H x W x D): 114 mm x 1200 mm x 76.5 mm
02: 407 mm long busbar trunking unit
Dimensions (H x W x D): 114 mm x 407 mm x 76.5 mm
NOTE
● A 407 mm long busbar trunking unit is used only for supplementation
at the end. It is recommended that you do not use multiple 407 mm
long busbar trunking units.
● In support-mounted installation, the distance between two supports is
600 mm. If a 407 mm busbar trunking unit is required for
supplementation, you are advised to install it at the position for the
last but one busbar trunking unit. If you install it at the position for
the last busbar trunking unit, it cannot be supported at two points.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 97


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Appearance

Figure 5-56 Busbar trunking unit

5.2.7 Smart Cooling Product PDB


The smart cooling product PDB can supply power to smart cooling products and
aisle lighting in the precision PDF or smart busbar scenario.

Figure 5-57 Appearance

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 98


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-58 Interior

(1) Communications cable wiring terminal (2) SPD and SPD switch

(3) Transformer (4) Input ACB

(5) N copper bar (6) PE copper bar

(7) Output ACB

Table 5-42 Technical specifications

Item Technical Specifications

Rated operating 380 V/400 V/415 V


voltage

Rated frequency 50/60 Hz

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 99


FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Technical Specifications

Rated operating 250 A/400 A


current

Input switch ● 250 A/3P MCCB


● 400 A/3P MCCB

Output switch 8 x 63 A/3P + 2 x 10 A/1P + 1 x 32 A/1P MCCB

IP rating IP20

Surge protection level Level C SPD

Certification CE, CCC

Installation mode Wall-mounted

5.2.8 Battery Cabinet


Select devices based on the site requirements. For details about the differences
between models or versions, see the corresponding sections.

5.2.8.1 Lithium Battery Cabinet SmartLi 3.0


Scenario where SmartLi 3.0 lithium battery cabinets are deployed outside the
smart module: One integrated UPS can connect to a maximum of six SmartLi 3.0
lithium battery cabinets.

NOTE

When multiple cabinets are connected in parallel, only the master cabinet has an LCD.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 100
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

5.2.8.1.1 Product Structure

Figure 5-59 SmartLi Cabinet Description

(1) Air vent (2) Incoming cable glands (3) Battery circuit breaker

(4) Monitoring interface unit (5) Battery control unit (BCU) (6) Fuse

(7) Slots for battery modules (8) Communications cable (9) Monitoring display unit
outlet (MDU, available only on the
master cabinet)

(10) Carbon monoxide gas (11) Document holder


sensor (optional)

5.2.8.1.2 Technical Specifications

Table 5-43 Physical specifications

Item Specifications

Cabling mode Routed in and out from the top only

IP rating IP21

Fire extinguishing solution Module-level fire suppression module (extinguishant:


perfluorohexanone; extinguishant quantity: 160 g)

Dimensions (H x W x D) 2000 mm x 600 mm x 850 mm

Weight < 800 kg

Circuit breaker 750 V DC, 250 A, 4P


specifications

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 101
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications

Fuse specifications 800 V DC, 250 A

Table 5-44 Environmental specifications


Item Specifications

Operating temperature 0–40°C


CAUTION
● When the operating temperature is beyond the range of 0°C to 40°C, the
power backup capability of the system may be unavailable or not reach
the rated value.
● When the operating temperature is below 0°C, the battery modules
switch off the charge and discharge circuits. As a result, the battery
modules cannot be charged or discharged. Start the air conditioner to
heat the battery modules to 3°C or above, and the charge and discharge
will be resumed.

Storage temperature 0–60°C

Humidity 5%–95% RH (non-condensing)

Altitude 0–4000 m

Pollution degree Degree 2

Table 5-45 Safety


Item Standard

CE EN 62477-1

CB EN 62477-1

Table 5-46 EMC


Item Standard

Certification standard EN 55011/EN 61000-6-2

Conducted emission (CE) EN 55011

Radiated emission (RE) EN 55011

ESD immunity IEC 61000-4-2

Conducted susceptibility EN IEC 62040-2


(CS) EN/IEC 61000-4-6

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 102
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Standard

Radiated susceptibility (RS) EN IEC 62040-2


EN/IEC 61000-4-3

Electrical fast transient EN IEC 62040-2


(EFT) IEC 61000-4-4

Surge EN IEC 62040-2


IEC 61000-4-5

Power magnetic IEC 61000-4-8


susceptibility (PMS)

Table 5-47 Electrical specifications

Item Eight-Module Seven- Six-Module Five-Module


Scenario Module Scenario Scenario
Scenario

Nominal capacity (battery 100 Ah


capacity)

Calculated capacity (actual 100 Ah


discharge capacity when
backup power is used)

Rated battery voltage 614.4 V DC 537.6 V DC 460.8 V DC 384 V DC

Rated energy 61.44 kWh 53.76 kWh 46.08 kWh 38.4 kWh

Battery charge voltage 3.4 V DC x N x 24


Note: N indicates the number of battery modules connected in
series. The value can be 5, 6, 7, or 8.

Discharge Maximum 100 kW 87.5 kW 75 kW 62.5 kW


capacity load power
(Operating supported
temperature by a single
of cells: 0– cabinet
30°C) Backup time 30 min 30 min 30 min 30 min

Discharge Maximum 75 kW 65.6 kW 56.3 kW 46.9 kW


capacity load power
(Operating supported
temperature by a single
of cells: 0– cabinet
40°C) Backup time 40 min 40 min 40 min 40 min

Rated charge current 50 A/0.5C

Discharge cut-off voltage 2.65 V per cell

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 103
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Eight-Module Seven- Six-Module Five-Module


Scenario Module Scenario Scenario
Scenario

Rated discharge current 200 A

Maximum number of UPS 6 5 4 3


modules supported by one
cabinet (UPS5000-E 30 kVA
modules)

Maximum number of UPS 7 7 7 6


modules supported by two
cabinets (UPS5000-E 30
kVA modules)

Maximum number of UPS 2N+1, where N indicates the number of battery cabinets
modules supported
(UPS5000-E 50 kVA
modules)

Number of cabinets 6
connected in parallel

Number of battery modules 8 7 6 5

Overvoltage category OVC II

Table 5-48 Protection functions


Item Specifications

Battery overvoltage ● Cell: overvoltage warning: ≥ 3.8 V; level-1 protection: ≥ 3.65 V;


protection level-2 protection: ≥ 3.9 V; level-3 protection: > 4.0 V
● Battery string (8 packs): level-1 protection: ≥ 676.8 V; level-2
protection: ≥ 681.6 V; level-3 protection: ≥ 696 V
● Battery string (7 packs): level-1 protection: ≥ 592.2 V; level-2
protection: ≥ 596.4 V; level-3 protection: ≥ 609 V
● Battery string (6 packs): level-1 protection: ≥ 507.6 V; level-2
protection: ≥ 511.2 V; level-3 protection: ≥ 522 V
● Battery string (5 packs): level-1 protection: ≥ 423 V; level-2
protection: ≥ 426 V; level-3 protection: ≥ 435 V

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 104
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Specifications

Battery undervoltage ● Cell: undervoltage warning: ≤ 2.9 V; level-1 protection: ≤ 2.65 V;


protection level-2 protection: ≤ 2.3 V; level-3 protection: < 1.8 V
● Battery string (8 packs): undervoltage warning: ≤ 537.6 V;
protection: ≤ 489.6 V
● Battery string (7 packs): undervoltage warning: ≤ 470.4 V;
protection: ≤ 428.4 V
● Battery string (6 packs): undervoltage warning: ≤ 403.2 V;
protection: ≤ 367.2 V
● Battery string (5 packs): undervoltage warning: ≤ 336 V;
protection: ≤ 306 V

Overtemperature > 65°C


protection

Undertemperature < 0°C


protection

Overcurrent protection ● Charge: level-1 protection: > 109.8 A; level-2 protection: > 120 A
● Discharge: level-1 protection: > 228 A; level-2 protection: > 252 A

EPO protection You can trigger the EPO protection by performing EPO on the UPS
or over the specified dry contact.

5.2.8.2 Lead-Acid Battery Cabinet


A maximum of three battery groups in up to six battery cabinets can be deployed
inside the smart module. If many batteries are configured, they can be deployed
outside the smart module.
● If the configured batteries can be placed in six or fewer battery cabinets, it is
recommended that battery cabinets be deployed inside the smart module
(smart module A). Battery cabinets or racks can also be deployed outside
smart module A (batteries deployed outside) or smart module B.
● If the configured batteries require the space of more than six battery cabinets,
it is recommended that battery cabinets or battery racks be deployed outside
smart module A (batteries deployed outside) or smart module B.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 105
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-60 Battery cabinet

Table 5-49 Battery cabinet technical specifications


Item Technical Specifications

Dimensions (H x W x ● Basic dimensions: 2000 mm x 600 mm x 1100 mm


D) ● Basic dimensions: 2000 mm x 600 mm x 1200 mm
● Extended dimensions: 2200 mm x 600 mm x 1200
mm (with the top frame)

Color Black (PANTONE426C/RAL9005)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 106
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Item Technical Specifications

Material High-intensity class A carbon cold rolled steel plate


and zinc-coated steel plate

Air channel Front-to-rear air channels

Installation mode Installed on an ESD floor or a concrete floor

Door opening mode The front door is a single door, and the rear door is a
double one.

Weight 128 kg (excluding batteries)

IP rating IP20

NOTE

Shoto batteries are supported.

Table 5-50 Maximum number of batteries inside a battery cabinet


Battery Specifications Maximum Number of Batteries
Inside a Battery Cabinet

26 Ah 40

40 Ah

65 Ah 20

100 Ah

Table 5-51 Configuration scenarios (same for master and slave battery cabinets)
Battery Cabinet Number of Batteries
Specifica Layer
tions (from
Top to
Bottom)

- - 40 38 36 34 32

26 Ah/40 Layer 1 10 9 8 7 6
Ah
Layer 2 10 10 10 10 10

Layer 3 10 10 10 10 10

Layer 4 10 9 8 7 6

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 107
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-52 Configuration scenarios (different for master and slave battery
cabinets)

Battery Cabinet Master Battery Cabinet Slave Battery Cabinet


Specifica Layer (Number of Batteries) (Number of Batteries)
tions (from
Top to
Bottom)

- - 20 19 18 17 16 20 19 18 17 16

65 Layer 1 5 4 3 2 1 5 4 3 2 1
Ah/100
Ah Layer 2 5 5 5 5 5 5 5 5 5 5

Layer 3 5 5 5 5 5 5 5 5 5 5

Layer 4 5 5 5 5 5 5 5 5 5 5

5.2.9 rPDU

5.2.9.1 Basic rPDU


By default, IEC sockets are configured for all rPDUs. GB sockets are optional.

Figure 5-61 Full-height rPDU

Figure 5-62 Half-height rPDU

NOTE

The figures are for reference only. The actual product may vary.

Table 5-53 rPDU specifications

Model Install Output Port BOM Number


ation
Mode

PDU2000-32-3PH-12/9-B2 Full 12 x C13 + 9 x C19 02121737-001


height
PDU2000-32-3PH-12/9-B4 12 x GB 10 A + 9 x GB 02121737-003
16 A

PDU2000-63-1PH-16/8-B1 16 x C13 + 8 x C19 02120643-002

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 108
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Model Install Output Port BOM Number


ation
Mode

PDU2000-63-1PH-16/8-B2 16 x GB 10 A + 8 x GB 02120643-003
16 A

PDU2000-16-3PH-24/6-B4 24 x GB 10 A + 6 x GB 02120838-003
16 A

PDU2000-16-3PH-24/6-B5 24 x GB 10 A + 6 x GB 02120838-004
16 A
PDU2000-32-1PH-20/4-B11 02122118-001
20 x GB 10 A + 4 x GB

PDU2000-32-1PH-20/4-B10 20 x GB 10 A + 4 x GB 02122118

PDU2000-32-1PH-20/4-B9 20 x C13 + 4 x C19 02120837-009

PDU2000-40-2PH-20/2-B1 20 x C13 + 2 x C19 02121839-001

PDU2000-32-1PH-9/3-B1 Half 9 x C13 + 3 x C19 02120765-002


height
PDU2000-32-1PH-9/3-B2 9 x GB 10 A + 3 x GB 02120765-003

PDU2000-32-1PH-9/3-B3 9 x GB 10 A + 3 x GB 02120765-004

PDU2000-16-1PH-8/0-B1 Horizo 8 x C13 02120814


ntal
PDU2000-16-1PH-7/0-B1 installa 7 x GB 10 A 02120813

PDU2000-16-1PH-6/0-B1 tion 6 x C13 02120635

NOTE

The output current of C13 is 10 A, and that of C19 is 16 A.

5.2.9.2 Smart rPDU


The smart rPDU accurately and effectively monitors the real-time status changes
of the current, voltage, power, and electric energy of electrical devices in the data
center.
The smart rPDU provides the following monitoring functions:
● Detects and displays the total input current.
– Detects and displays the input current of each phase.
– Detects and displays the input voltage of each phase.
– Displays the voltage and current in pooling mode.
● Provides remote input management.
● Remotely queries the input voltage, total input current, input power, and
input energy through a serial port.
● Remotely queries the PDU status through a serial port. The status that can be
queried includes normal input power, overcurrent, overvoltage, and

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 109
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

undervoltage, as well as the communication status (normal or abnormal) of


the monitoring board.
● Remotely sets the input overcurrent warning threshold, overvoltage alarm
threshold, and undervoltage alarm threshold through a serial port, or locally
set these parameters.
● Working status indicator: The built-in input status indicator indicates the
working status of the rPDU.
● Input alarm: If any of input overcurrent, overvoltage, and undervoltage occur,
the working status indicator indicates the fault, and an alarm is reported over
the Modbus port.

Figure 5-63 Smart rPDU

(1) Input power cable (2) Industrial connector (3) Display

(4) Main control module (5) Output sockets (6) Hydraulic circuit breaker

Table 5-54 Technical specifications of the smart rPDU

Type Model Output BOM Number Monitoring


Port Function

Switc MD-1324-2004 20 x C13 + 02122280 ● Monitors the


h type 4 x C19 input power,
voltage,
PN1-32I10-20E4G- 20 x C13 + 02122201 current, power
AV4 4 x C19 factor, and
ZFIF-112-0800 8 x C13 02123125 electric energy.
● Monitors the
PN1-16X18-8E- 8 x C13 02122935 power, current,
AH4W power factor,
and electric
ZZIF-130-2004 20 x C13 + 02123126
energy of each
4 x C19
output.
PN1-32I15-20E4G- 20 x C13 + 02122936
AV4W 4 x C19

ZZIF-160-1406 14 x C13 + 02122850


6 x C19

PDU2000-32A-3PH 24 x C13 + 02123242


-M 6 x C19

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 110
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Type Model Output BOM Number Monitoring


Port Function

PN1-63I15-14E6G- 14 x C13 + 02122761


AV4W 6 x C19

Monit PDU2000-32-1PH-2 20 x C13 + 02120701 Monitors the


oring 0/4-M1 4 x C19 input power,
type voltage, current,
PN3-32J15-12E12G 12 x C13 + 02123074 power factor, and
-AV1 12 x C19 electric energy.
ZFIA-330-1212 12 x C13 + 02123236
12 x C19

NOTE

The output current of C13 is 10 A, and that of C19 is 16 A.

5.2.9.3 PDU2000M
● The PDU2000M products accurately and effectively monitor the real-time
status changes of the current, voltage, power, and electric energy of IT devices
in the data center.
● The PDU2000M products are classified into switch-type and input monitoring-
type. They provide the following monitoring functions.

Table 5-55 Functions

Function Switch-Type Monitoring-Type

Input current detection √ √

Input voltage detection √ √

Input frequency √ √
detection

Input power detection √ √

Input electric energy √ √


detection

31-order harmonic √ √
detection of the input
current and voltage

Switch status detection √ √

Output socket remote √ -


shutdown

Output socket current √ -


detection

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 111
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Function Switch-Type Monitoring-Type

Output socket power √ -


detection

Output socket electric √ -


energy detection

Output socket indicator √ -

LED display √ √

Connection to a T/H √ √
sensor, door status
sensor, smoke sensor,
water sensor, cabinet
electronic lock, and U
space manager

Communications √ √
protocols: Modbus TCP
protocol (FE port) for
ECC800-Pro connection,
SNMP, and RS485
(Modbus RTU protocol)

Web access, software √ √


upgrade, data export,
and onsite O&M

Remote query and √ √


management: view
running parameters
and set alarm
thresholds.

Figure 5-64 PDU2000M appearance

(1) Industrial connector (2) Input power cable (3) Switch

(4) Display (5) Main control module (6) Output sockets

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 112
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Figure 5-65 Main control module of the PDU2000M

(1) Display (2) COM/DI 1– (3) COM4 (4) RS485 (5) FE1–FE2
COM/DI 3

Table 5-56 Ports on the main control module


Port Function Definition

FE1 ● Northbound port, which can be connected to the


ECC800-Pro.
FE2
● Connect to the NMS through SNMP.
● Support web access.

COM/DI 1 Connects to a southbound device and provides 12 V


power.

COM/DI 2 Connects to a southbound device and provides 12 V


power.

COM/DI 3 Connects to a southbound device and provides 12 V


power.

COM4 The port is used as a southbound port by default, which


connects to a southbound device and provides 12 V
power. If the northbound RS485 function needs to be
used, the port should be set as a northbound port, which
can only be used as an RS485 cascading port and cannot
directly connect to a northbound device.

RS485 Northbound RS485 (Set the port as a northbound port


when needed.)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 113
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-57 PDU2000M technical specifications


Type Model Output BOM Specifications Descripti
Port Number on

Switch- PDU2000- 24 x C13 + 0212338 ● Input The


type 32-3PH-24 6 x C19 1 voltage: output is
-6-S1 three-phase divided
380 V/400 into six
V/415 V branches,
● Input each with
current: a 16 A
three-phase protectio
32 A n switch.

PDU2000- 24 x C13 + 0212338 ● Input The


32-1PH-24 6 x C19 2 voltage: output is
-6-S1 single- divided
phase 220 into two
V/230 branches,
V/240 V each with
● Input a 16 A
current: protectio
single- n switch.
phase 32 A

PDU2000- 24 x C13 + 0212338 ● Input The


63-1PH-24 6 x C19 6 voltage: output is
-6-S1 single- divided
phase 220 into four
V/230 branches,
V/240 V each with
● Input a 16 A
current: protectio
single- n switch.
phase 63 A

Monitor PDU2000- 18 x C13 + 0212338 ● Input The


ing- 32-3PH-18 12 x C19 4 voltage: output is
type -12-M1 three-phase divided
380 V/400 into six
V/415 V branches,
● Input each with
current: a 16 A
three-phase protectio
32 A n switch.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 114
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Type Model Output BOM Specifications Descripti


Port Number on

PDU2000- 24 x C13 + 0212338 ● Input The


32-1PH-24 6 x C19 5 voltage: output is
-6-M1 single- divided
phase 220 into two
V/230 branches,
V/240 V each with
● Input a 2-pole
current: 16 A
single- protectio
phase 32 A n switch.
Neutral
conducto
r
disconne
ction is
supporte
d.

PDU2000- 24 x C13 + 0212338 ● Input The


63-1PH-24 6 x C19 7 voltage: output is
-6-M1 single- divided
phase 220 into four
V/230 branches,
V/240 V each with
● Input a 16 A
current: protectio
three-phase n switch.
63 A

NOTE

● The output current of C13 is 10 A, and that of C19 is 16 A.


● Based on the energy efficiency grading standard, the PF value at full load must be
greater than 0.94.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 115
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Display

Figure 5-66 Appearance

(1) Running indicator (2) Minor alarm (3) Major alarm (4) Escape key
indicator indicator

(5) Page Up key (6) Page Down key (7) Enter key (8) LCD

Table 5-58 Indicator description

Indicator Status Indicator Color Meaning

Running Green Off The monitoring module


indicator is faulty or has no DC
input.

Blinking slowly (0.5 The monitoring module


Hz) is running properly and
communicating with the
host properly.

Blinking fast (4 Hz) The communication is


abnormal.

Minor alarm Yellow Off No minor alarm is


indicator generated.

Steady on A minor alarm is


generated.

Major alarm Red Off No critical or major


indicator alarm is generated.

Steady on A critical or major alarm


is generated.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 116
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System

Table 5-59 Button description


Button Function Description

Enter 3s Blink.

Cancel+Enter 10s Restart.

Cancel+Down 10s Restore the password.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 117
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

6 Temperature Control System

6.1 System Overview


The cooling system uses in-row air cooled smart cooling products and an aisle
containment for cooling. The in-row air cooled smart cooling products and
equipment cabinets form an aisle containment to separate hot air from cold air.

An in-row air cooled smart cooling product works as follows: After the unit starts,
the low-pressure refrigerant vapor in the refrigerating system is suctioned into the
compressor, compressed into high-pressure vapor, and discharged to the
condenser. The outdoor air drawn in by the axial flow fan flows through the
condenser and carries away the heat emitted from the refrigerant so that the
high-pressure refrigerant vapor condenses into high-pressure liquid. The high-
pressure liquid passes through the filter and flow regulating mechanism and then
is ejected to the evaporator. Then the liquid vaporizes at low pressure and absorbs
ambient heat. The cross-flow fan draws air into the fins in the evaporator to
exchange heat and discharges cooled air to the cold aisle. The indoor air flows
cyclically to decrease the temperature.

In-row smart cooling products are close to heat sources, which shortens the air
supply distance, reduces airflow pressure loss and cold air loss, and maximizes the
use of cooling capacity.

6.2 Hardware Description


Select devices based on the site requirements. For details about the differences
between models or versions, see the corresponding sections.

6.2.1 FusionCol5000-A065 Smart Cooling Product


● The FusionCol5000-A065 is a 65 kW smart data center cooling product, which
is usually deployed between cabinets. It is easy to expand capacity, and is able
to intelligently match load requirements. It adopts a high supply and return
air temperature design to reduce the power usage effectiveness (PUE). The V-
shaped outdoor unit is equipped with a refrigerant pump to save energy.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 118
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

6.2.1.1 Indoor Unit

Figure 6-1 Components 1

No. Name Description

1 Fan ● The energy-efficient EC fan that supports stepless


speed adjustment is used to reduce the fan energy
consumption.
● The direct drive that the fan adopts supports a wide
speed adjustment range which is not subject to the
transmission ratio. It has higher transmission
efficiency than the belt drive, which reduces belt
replacements and routine checks.
● The fan is controlled over RS485. You can view the
fan speed and running status in real time on the
display module and can obtain fault information
including fan blockage, overvoltage, and
undervoltage. The features allow you to view the
status and locate a fault.
● Each fan is controlled by an independent switch and
can be maintained online. If a fan fails, the entire
system does not shut down.

2 Display The display module provides a 7-inch true-color


module touchscreen that provides man-machine interfaces for
query, setting, management, and maintenance.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 119
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

No. Name Description

3 Electric heater ● The positive temperature coefficient (PTC) electric


(optional) heater automatically adjusts heating capacity and
provides multiple protection measures to ensure
safe and reliable operation.
● The heater features quick start, large heating
capacity, and even heating.

4 Condensate Drives the drainage if water is drained from the top of


pump the unit.

5 Check valve Prevents component damage caused by gas or liquid


backflow.

6 Air filter The G4 air filter is used.

Figure 6-2 Components 2

No. Name Description

1 Electrical box The power supply unit (PSU) and built-in electrical
control component control the power supply efficiently.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 120
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

No. Name Description

2 Compressor ● The variable-frequency compressor drive and 24 V


drive PSU are integrated into one device to deliver high
efficiency and save space in the smart cooling
product.
● The compressor drive is controlled over RS485. You
can view the drive alarms on the display module in
real time for fault locating.

3 Wet film ● Lowers the water quality requirements and improves


humidifier the environment adaptability.
(optional) ● Uses a simple structure and is easy to remove and
maintain.
● Quickly starts and generates huge humidification
capacity.
● Consumes low power, saving more than 95% energy
compared with a traditional electrode humidifier.
● Provides a longer service life and maintenance
interval than a traditional electrode humidifier.

4 Compressor ● A DC variable-frequency compressor is adopted,


which features compact size, light weight, low noise,
a long service life, and high reliability, stability, and
energy efficiency.
● Threaded connection negates the need of welding
during replacement, making maintenance easy.
● The high-precision drive automatically adapts to the
system pressure fluctuations.
● The drive conducts precision self-check. Compressor
and drive faults are separated.

5 Filter dryer The filter dryer absorbs water from the refrigerant
pipes and filters out the foreign matter, which reduces
component damage rates and improves operating
efficiency and reliability.

6 Sight glass Allows you to observe the refrigerant flow and gas
content for easy maintenance and optimization.

7 Oil separator The oil separator separates the lubricant brought out
due to discharge of the compressor and brings back the
separated lubricant to the compressor.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 121
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

No. Name Description

8 Evaporator ● The evaporator adopts the inner threaded copper


pipes and blue hydrophilic aluminum foil to prevent
water blowing due to condensate water
accumulation and improve heat exchange
performance. The V-type evaporator optimizes the
airflow organization and reduces the air resistance.
● The finned-tube evaporator with a high cooling
efficiency adopts the synergy field principle and the
Computational Fluid Dynamics (CFD) to optimize
the process design, which improves the heat
exchange efficiency greatly.
● The small-diameter pipes are adopted to enhance
the heat exchange performance. The heat exchange
efficiency is increased by more than 10% compared
with that of a traditional solution.
● The designed pressure bearing capacity of the heat
exchange coil is 4.35 MPa, providing excellent
pressure resistance capability.

9 Electronic ● The throttling device uses a miniature controller to


expansion control the operation of the step motor, thereby
valve (EEV) changing the pass-through area of the EEV to
regulate the flow of refrigerant in the cooling
system.
● The main control module contains an EEV energy
storage unit to prevent slugging due to refrigerant
migration caused by unexpected power-off.

10 Extra-low Built-in ELV control components:


voltage (ELV) ● The main control module manages the unit
box operation and connects the teamwork and
monitoring communications cables. Modular design
facilitates replacement.
● The temperature and humidity (T/H) sensor
measures the return air temperature and humidity.
● When the air filter is dirty or blocked, the
differential pressure switch triggers an alarm,
prompting you to replace the air filter.

6.2.1.2 Outdoor Unit

Features
● The high-efficiency EC fan features large air volume, low noise, and high
efficiency.
● The variable frequency drive ensures stable running at low loads.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 122
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

● Using the galvanized sheet and surface phosphatization + powder coating


techniques, the outdoor unit adapts to harsh environments with its sound
rigidity and anticorrosion performance.
● Pressure preservation is performed on the condenser before delivery, and the
pipe ports are properly sealed to prevent foreign matter from entry.
● If equipped with a low-temperature refrigerant pump, the outdoor unit can
work outdoors within the temperature range of –40°C to +20°C and supports
pPUE 0.08 at 50% load in Beijing.

6.2.1.2.1 FusionCol500-A090

Figure 6-3 Dimensions

Model FusionCol500-A0904C2

Power supply Powered by the indoor unit

Fan air volume 25000 m3/h

Temperature control Available


intelligent
monitoring board

Operating –20°C to +45°C


temperature

Storage temperature –40°C to +70°C

Storage humidity 5%–95% RH (non-condensing)

Environment type Class B

Number of fans 1

Net weight 242 kg

IP rating of the IPX5


electric control box

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 123
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

6.2.1.2.2 FusionCol500-P090

Figure 6-4 Dimensions

Model FusionCol500-P0904C2

Power supply Powered by the indoor unit

Fan air volume 25000 m3/h

Temperature control Available


intelligent
monitoring board

Operating –40°C to +45°C


temperature

Storage temperature –40°C to +70°C

Storage humidity 5%–95% RH (non-condensing)

Environment type Class B

Number of fans 1

Net weight 302 kg

IP rating of the IPX5


electric control box

6.2.1.3 Environment and Space Requirements

Precautions
● If the actual total load of servers corresponding to a single smart cooling
product is less than 10% of the rated cooling capacity of the smart cooling
product or the equipment room is not properly sealed, the humidity in the
equipment room may be too high. This is not a product quality issue and
should be dealt with by adding a dehumidifier.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 124
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

● When determining the number of units, consider the redundancy design and
ensure that the redundancy design requirements in GB 50174 or TIA 942 are
met.
● Do not install smart cooling products near noise-sensitive places such as
offices and meeting rooms.
● Before installation, check whether the installation environment meets the
requirements and whether the building needs to be altered to facilitate pipe
layout, cable routing, and ventilation duct construction.
● To ensure good ventilation, do not place the indoor unit in the corner of a
room or at the end of a long and narrow room.
● Check that all doors and windows of the equipment room are closed to
reduce the workload of the smart cooling product during system operation.

Environmental Requirements
Item Requirement

Room door Width ≥ 1.2 m; height ≥ 2.3 m

Equipment The equipment room provides good heat insulation, and the
room walls and floor are dampproof.

Floor Floor bearing capacity ≥ 530 kg/m2

Water supply The inlet water pressure should be in the range of 0.1–0.7 MPa
(a reducing valve must be installed at the humidifier water inlet
if the inlet water pressure exceeds 0.7 MPa). If the inlet water
pressure is lower than 0.1 MPa, a check valve must be installed
at the humidifier water inlet. The temperature should be in the
range of 1°C–40°C.
Specific requirements:
● Non-freezing and nephelometric turbidity units (NTU) < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO3) ≤ 450 mg/L

Drainage The distance between the top drainage of the water pump and
the cabinet installation surface should not exceed 4 m.

Power Leakage circuit breakers are not recommended for the main
distribution power route. If a leakage circuit breaker is required by the
customer or local regulations, select the residual current circuit
breaker (RCCB) that is insensitive to single-phase DC pulsation
and transient impulse current.

Space Requirements
Install the device according to the design drawing and reserve space for
maintenance. At least 1200 mm maintenance space must be reserved in front of

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 125
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

or at the rear of the indoor unit, and at least 600 mm maintenance space must be
reserved at the other end.

Figure 6-5 Space requirements

(1) FusionCol5000-A (2) Equipment

6.2.1.4 Technical Specifications


NOTE

You can view the BOM number on the equipment barcode.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 126
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

6.2.1.4.1 Indoor Unit

Figure 6-6 Appearance and dimensions

Model FusionCol5000-A065H4

Heating function Available Not available

Humidifying function Available Not available

Humidifier water inlet Available Not available


hose

Reheating capacity 6 kW Not available

Humidification capacity 3 kg/h Not available

Net weight/Gross 365 kg/396 kg 360 kg/391 kg


weight

Power specifications 380–415 V AC, 50 Hz/60 Hz, 3W+PE


Tolerance: rated voltage –10% to +10%; rated
frequency –3 Hz to +3 Hz

Power supply Dual power supplies

Maximum current 46 A

Operating temperature 18–45°C

Operating humidity ≤ 95% RH (32°C)


Maximum humidity: 95% RH at 32°C

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 127
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Storage temperature –40°C to +70°C

Storage humidity 5%–95% RH (non-condensing)

Maximum operating 4000 m


altitude

IP rating IP20

Refrigerant R410A

Cooling capacity 65 kW
Tested under rated working conditions (indoor dry-
bulb temperature: 40°C; relative humidity: 24%;
outdoor temperature: 35°C)

Air supply mode Horizontal flow

Air volume 12,000 m3/h

Pipe routing mode Pipes can be routed from the top or bottom.

Condensate pump Available

Water pump lift 4m

Compressor connection Threaded connection


mode

Filter dryer connection Threaded connection


mode

Caster Available

Table 6-1 Derating coefficients


Altitude [0, 1000 1500 2000 2500 3000 3500 4000
(m) 1000)

Density 1 0.887 0.835 0.785 0.737 0.692 0.649 0.608


coefficient

Air volume 1 0.887 0.835 0.785 0.737 0.692 0.649 0.608


coefficient

Cooling 1 0.940 0.909 0.878 0.846 0.815 0.784 0.753


capacity
coefficient

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 128
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

6.2.1.4.2 Outdoor Unit

Application Environment

Table 6-2 Application environment


Type Description

Class A (controlled Indoor environments where the temperature


environment) and humidity are controlled, including rooms
where human beings live

Class B (uncontrolled Indoor environment where the ambient


environment) temperature and humidity are not controlled
or outdoor environments (with simple
shielding measures) where the humidity can
reach 100%.

Class C (harsh environment) Sea environments or outdoor land


environments (with simple shielding measures)
near pollution sources. Pollution sources refer
to the following areas:
● Areas within 3.7 km away from saline water
areas such as the ocean and saline lakes
● Areas within 3 km of serious pollution
sources, such as metallurgic plants, coal
mines, and heat and power plants
● Areas within 2 km away from medium
pollution sources, such as chemical
factories, rubber plants, and electroplating
factories
● Areas within 1 km away from light pollution
sources, such as food factories, tanneries,
and heating boilers

Class D (marine environment) Areas within 500 m away from the seashore.

NOTE

If an outdoor unit needs to be used at a site 3.7–10 km away from the coast in a class B
environment, it is recommended that the unit be installed in a shielded area, such as a
podium building, ground, or building rear, to prevent mechanical parts from being corroded
by sea wind (the functionality and reliability of the system must not be affected).
Alternatively, use an outdoor unit that supports class C environments to avoid corrosion. If
the site is more than 10 km away from the coast, the unit can be properly installed.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 129
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

FusionCol500-A090

Figure 6-7 Dimensions

Model FusionCol500-A0904C2

BOM number 52275411

Power supply Powered by the indoor unit

Fan air volume 25,000 m3/h

Temperature control Available


intelligent
monitoring board

Operating –20°C to +45°C


temperature

Storage temperature –40°C to +70°C

Storage humidity 5%–95% RH (non-condensing)

Applicable Class B
environment

Number of fans 1

Net weight 242 kg

IP rating of the IPX5


electric control box

NOTE

Class B: Indoor environment where the ambient temperature and humidity are not
controlled or outdoor environments (with simple shielding measures) where the humidity
can reach 100%.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 130
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

FusionCol500-P090

Figure 6-8 Dimensions

Model FusionCol500-P0904C2

BOM number 52275411-001

Power supply Powered by the indoor unit

Fan air volume 25,000 m3/h

Temperature control Available


intelligent
monitoring board

Operating –40°C to +45°C


temperature

Storage temperature –40°C to +70°C

Storage humidity 5%–95% RH (non-condensing)

Applicable Class B
environment

Number of fans 1

Net weight 302 kg

IP rating of the IPX5


electric control box

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 131
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

NetCol500-A110

Figure 6-9 Dimensions

Model NetCol500-A110MC1E0

BOM number 52274570

Power supply Powered by the indoor unit

Fan air volume 40,000 m3/h

Temperature control Unavailable


intelligent
monitoring board

Operating –5°C to +55°C


temperature

Storage temperature –40°C to +70°C

Storage humidity 5%–95% RH (non-condensing)

Applicable Class B
environment

Number of fans 2

Net weight 366 kg

IP rating of the IPX5


electric control box

6.2.2 FusionCol5000-A050 Smart Cooling Product


The FusionCol5000-A065 is a 50 kW smart data center cooling product, which is
usually deployed between cabinets. It is easy to expand capacity, and is able to
intelligently match load requirements. It adopts a high supply and return air
temperature design to reduce the power usage effectiveness (PUE). The V-type
outdoor unit is equipped with a refrigerant pump to save energy.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 132
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

6.2.2.1 Indoor Unit

Figure 6-10 Components

No. Name Description

A View from the -


front door

B View from the -


rear door

1 Fan ● The energy-efficient EC fan that supports stepless


speed adjustment is used to reduce the fan energy
consumption.
● Each fan is controlled by an independent switch and
can be maintained online. If a fan fails, the entire
system does not shut down.

2 Display The display module provides a 7-inch true-color


module touchscreen that provides man-machine interfaces for
query, setting, management, and maintenance.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 133
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

No. Name Description

3 Electric heater ● The positive temperature coefficient (PTC) electric


(optional) heater automatically adjusts heating capacity and
provides multiple protection measures to ensure
safe and reliable operation.
● The heater features quick start, large heating
capacity, and even heating.

4 Condensate Drives the drainage if water is drained from the top of


pump the unit.

5 Check valve Prevents component damage caused by gas or liquid


backflow.

6 Air filter The G4 air filter is used.

Figure 6-11 Internal components

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 134
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

No. Name Description

1 Electrical box The PSU and built-in electrical control component


control the power supply efficiently.

2 Compressor ● The variable-frequency compressor drive, 24 V


drive power supply unit (PSU), and outdoor unit power
supply are integrated into one device to deliver high
efficiency and save space in the smart cooling
product.
● The compressor drive is controlled over RS485. You
can view the drive alarms on the display module in
real time for fault locating.

3 Wet film ● Lowers the water quality requirements and improves


humidifier the environment adaptability.
(optional) ● Uses a simple structure and is easy to remove and
maintain.
● Quickly starts and generates huge humidification
capacity.
● Consumes low power, saving more than 95% energy
compared with a traditional electrode humidifier.
● Provides a longer service life and maintenance
interval than a traditional electrode humidifier.

4 Water inlet Controls the water supply to the humidifier to meet


solenoid valve humidification requirements.
(optional)

5 Compressor ● A DC variable-frequency compressor is adopted,


which features compact size, light weight, low noise,
a long service life, and high reliability, stability, and
energy efficiency.
● Threaded connection negates the need of welding
during replacement, making maintenance easy.
● The high-precision drive automatically adapts to the
system pressure fluctuations.
● The drive conducts precision self-check. Compressor
and drive faults are separated.

6 Filter dryer The filter dryer absorbs water from the refrigerant
pipes and filters out the foreign matter, which reduces
component damage rates and improves operating
efficiency and reliability.

7 Sight glass Allows you to observe the refrigerant flow and gas
content for easy maintenance and optimization.

8 Oil separator The oil separator separates the lubricant brought out
due to discharge of the compressor and brings back the
separated lubricant to the compressor.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 135
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

No. Name Description

9 Evaporator ● The evaporator adopts the inner threaded copper


pipes and blue hydrophilic aluminum foil to prevent
water blowing due to condensate water
accumulation and improve heat exchange
performance. The V-type evaporator optimizes the
airflow organization and reduces the air resistance.
● The finned-tube evaporator with a high cooling
efficiency adopts the synergy field principle and the
Computational Fluid Dynamics (CFD) to optimize
the process design, which improves the heat
exchange efficiency greatly.
● The small-diameter pipes are adopted to enhance
the heat exchange performance. The heat exchange
efficiency is increased by more than 10% compared
with that of a traditional solution.
● The designed pressure bearing capacity of the heat
exchange coil is 4.35 MPa, providing excellent
pressure resistance capability.

10 Electronic ● The throttling device uses a miniature controller to


expansion control the operation of the step motor, thereby
valve (EEV) changing the pass-through area of the EEV to
regulate the flow of refrigerant in the cooling
system.
● The main control module contains an EEV energy
storage unit to prevent slugging due to refrigerant
migration caused by unexpected power-off.

11 Extra-low Built-in ELV control components:


voltage (ELV) ● The main control module manages the unit
box operation and connects the teamwork and
monitoring communications cables. Modular design
facilitates replacement.
● The temperature and humidity (T/H) sensor
measures the return air temperature and humidity.
● When the air filter is dirty or blocked, the
differential pressure switch triggers an alarm,
prompting you to replace the air filter.

6.2.2.2 Outdoor Unit


Using the galvanized sheet and surface phosphatization + powder coating
techniques, the outdoor unit provides strong environmental adaptability with its
sound rigidity and anticorrosion performance.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 136
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

6.2.2.2.1 FusionCol500-A070

Figure 6-12 Appearance

No. Name Description

1 Fan ● The highly efficient EC fan saves more than 30%


energy than a common fan.
● The fan adopts the direct drive mode. Fan speed
control by the direct drive has a wide application
range.
● RS485 communication control is used. The fan
running status can be viewed in real time on the
display module.

2 Electric The IPX5 requirements are met. A built-in fan drive is


control box used:
● Modular design delivers high efficiency and facilitates
quick replacement.
● The drive is separated from the motor, which
facilitates fault locating and replacement.

3 Temperature The sensor detects the outdoor ambient temperature to


sensor determine whether refrigerant leakage occurs.

4 Condenser ● The V-shaped condenser has a small footprint.


● Pressure preservation is performed on the condenser
before delivery, and the pipe ports are properly sealed
to prevent foreign matter from entry.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 137
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

6.2.2.2.2 FusionCol500-P090

Figure 6-13 Appearance

No. Name Description

1 Fan ● The highly efficient EC fan saves more than 30% of


energy than a common fan.
● The fan adopts the direct drive mode. Fan speed
control by the direct drive has a wide application
range.
● RS485 communication control is used. The fan
running status can be viewed in real time on the
display module.

2 Electric The IPX5 requirements are met. A built-in fan drive and
control box refrigerant pump drive are used:
● Modular design delivers high efficiency and facilitates
quick replacement.
● The fan drive is separated from the motor, which
facilitates fault locating and replacement.

3 Temperature The sensor detects the outdoor ambient temperature.


sensor

4 Condenser ● The V-shaped condenser has a small footprint.


● Pressure preservation is performed on the condenser
before delivery, and the pipe ports are properly sealed
to prevent foreign matter from entry.

5 Liquid storage The tank supplies liquid refrigerant to the refrigerant


tank pump to ensure reliable operation.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 138
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

No. Name Description

6 Refrigerant ● In a low-temperature environment, the high-efficiency


pump variable-frequency refrigerant pump substitutes for a
compressor to transport the superheated refrigerant
to the outdoor for free cooling. After cooling, the
liquid refrigerant is transported to the indoor unit to
continue heat exchange.
● RS485 communication control is used. The refrigerant
pump running status can be viewed in real time on
the display module.

6.2.2.3 Environment and Space Requirements

Precautions
● If the actual total load of servers corresponding to a single smart cooling
product is less than 10% of the rated cooling capacity of the smart cooling
product or the equipment room is not properly sealed, the humidity in the
equipment room may be too high. This is not a product quality issue and
should be dealt with by adding a dehumidifier.
● When determining the number of units, consider the redundancy design and
ensure that the redundancy design requirements in GB 50174 or TIA 942 are
met.
● Do not install smart cooling products near noise-sensitive places such as
offices and meeting rooms.
● Before installation, check whether the installation environment meets the
requirements and whether the building needs to be altered to facilitate pipe
layout, cable routing, and ventilation duct construction.
● To ensure good ventilation, do not place the indoor unit in the corner of a
room or at the end of a long and narrow room.
● Check that all doors and windows of the equipment room are closed to
reduce the workload of the smart cooling product during system operation.

Environmental Requirements
Item Requirement

Room door Width ≥ 1.2 m; height ≥ 2.3 m

Equipment The equipment room provides good heat insulation, and the
room walls and floor are dampproof.

Floor Floor bearing capacity ≥ 530 kg/m2

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 139
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Item Requirement

Water supply The inlet water pressure should be in the range of 0.1–0.7 MPa
(a reducing valve must be installed at the humidifier water inlet
if the inlet water pressure exceeds 0.7 MPa). If the inlet water
pressure is lower than 0.1 MPa, a check valve must be installed
at the humidifier water inlet. The temperature should be in the
range of 1°C–40°C.
Specific requirements:
● Non-freezing and nephelometric turbidity units (NTU) < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO3) ≤ 450 mg/L

Drainage The distance between the top drainage of the water pump and
the cabinet installation surface should not exceed 4 m.

Power Leakage circuit breakers are not recommended for the main
distribution power route. If a leakage circuit breaker is required by the
customer or local regulations, select the residual current circuit
breaker (RCCB) that is insensitive to single-phase DC pulsation
and transient impulse current.

Space Requirements
Install the device according to the design drawing and reserve space for
maintenance. At least 1200 mm maintenance space must be reserved in front of
or at the rear of the indoor unit, and at least 600 mm maintenance space must be
reserved at the other end.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 140
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Figure 6-14 Space requirements

(1) FusionCol5000-A (2) Equipment

6.2.2.4 Technical Specifications


NOTE

You can view the BOM number on the equipment barcode.

6.2.2.4.1 Indoor Unit

Figure 6-15 Dimensions

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 141
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Model FusionCol5000-A050H4

Heating Available Not available


function

Humidifying Available Not available


function

Humidifier Available Not available


water inlet
hose

Reheating 6 kW Not available


capacity

Humidificati 3 kg/h Not available


on capacity

Net weight/ 330 kg/372 kg 325 kg/357 kg


Gross
weight

Power 380–415 V AC, 50/60 Hz, 3W+N+PE


specification Tolerance: rated voltage –10% to +10%; rated frequency –3 Hz
s to +3 Hz

Power Dual power supplies


supply

Maximum 42 A
current

Operating 18–45°C
temperature

Operating ≤ 95% RH (32°C)


humidity Maximum humidity: 95% RH at 32°C

Storage –40°C to +70°C


temperature

Storage 5%–95% RH (non-condensing)


humidity

Maximum 4000 m
operating
altitude

IP rating IP20

Refrigerant R410A

Cooling 46 kW
capacity Tested under rated working conditions (indoor dry-bulb
temperature: 37°C, relative humidity: 21%, outdoor temperature:
35°C).

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 142
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Air supply Horizontal flow


mode

Air volume 9000 m3/h

Pipe routing Pipes can be routed from the top or bottom.


mode

Condensate Available
pump

Water pump 4m
lift

Compressor Threaded connection


connection
mode

Filter dryer Threaded connection


connection
mode

Caster Available

Table 6-3 Derating coefficients

Altitude [0, 1000 1500 2000 2500 3000 3500 4000


(m) 1000)

Density 1 0.887 0.835 0.785 0.737 0.692 0.649 0.608


coefficient

Air volume 1 0.887 0.835 0.785 0.737 0.692 0.649 0.608


coefficient

Cooling 1 0.940 0.909 0.878 0.846 0.815 0.784 0.753


capacity
coefficient

6.2.2.4.2 Outdoor Unit

Application Environment

Table 6-4 Application environment

Type Description

Class A (controlled Indoor environments where the temperature


environment) and humidity are controlled, including rooms
where human beings live

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 143
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Type Description

Class B (uncontrolled Indoor environment where the ambient


environment) temperature and humidity are not controlled
or outdoor environments (with simple
shielding measures) where the humidity can
reach 100%.

Class C (harsh environment) Sea environments or outdoor land


environments (with simple shielding measures)
near pollution sources. Pollution sources refer
to the following areas:
● Areas within 3.7 km away from saline water
areas such as the ocean and saline lakes
● Areas within 3 km of serious pollution
sources, such as metallurgic plants, coal
mines, and heat and power plants
● Areas within 2 km away from medium
pollution sources, such as chemical
factories, rubber plants, and electroplating
factories
● Areas within 1 km away from light pollution
sources, such as food factories, tanneries,
and heating boilers

Class D (marine environment) Areas within 500 m away from the seashore.

NOTE

If an outdoor unit needs to be used at a site 3.7–10 km away from the coast in a class B
environment, it is recommended that the unit be installed in a shielded area, such as a
podium building, ground, or building rear, to prevent mechanical parts from being corroded
by sea wind (the functionality and reliability of the system must not be affected).
Alternatively, use an outdoor unit that supports class C environments to avoid corrosion. If
the site is more than 10 km away from the coast, the unit can be properly installed.

FusionCol500-A070

Figure 6-16 Dimensions

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 144
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Model FusionCol500-A0704C2

BOM number 52275862

Power supply Powered by the indoor unit

Fan air volume 25,000 m3/h

Temperature control Available


intelligent
monitoring board

Operating –20°C to +45°C


temperature

Storage temperature –40°C to +70°C

Storage humidity 5%–95% RH (non-condensing)

Applicable Class B
environment

Number of fans 1

Net weight 235 kg

IP rating of the IPX5


electric control box

FusionCol500-P090

Figure 6-17 Dimensions

Model FusionCol500-P0904C2

BOM number 52275411-001

Power supply Powered by the indoor unit

Fan air volume 25,000 m3/h

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 145
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Temperature control Available


intelligent
monitoring board

Operating –40°C to +45°C


temperature

Storage temperature –40°C to +70°C

Storage humidity 5%–95% RH (non-condensing)

Applicable Class B
environment

Number of fans 1

Net weight 302 kg

IP rating of the IPX5


electric control box

6.2.3 NetCol5000-A (025, 035) Smart Cooling Product


The NetCol5000-A (025, 035) is a 25/35 kW in-row air cooled smart cooling
product. It can be deployed abreast with standard cabinets to provide close-
coupled cooling, thereby reducing energy consumption for cooling, optimizing the
PUE, and increasing energy efficiency for data centers.

6.2.3.1 Indoor Unit


The NetCol5000-A indoor unit mainly consists of a compressor, oil separator, fan,
heat exchanger, EEV, check valve, filter dryer, sight glass, electric heater (optional),
wet film humidifier (optional), water pump (optional), and display panel.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 146
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Figure 6-18 Components

(1) External signal port (2) Electric control box (3) Module subrack

(4) Drive (5) Wet film humidifier (6) Differential pressure switch

(7) Compressor (8) Drainpipe (9) Refrigerant gas pipe

(10) Refrigerant liquid pipe (11) Air filter (12) Fans

(13) Water pan cover (14) Water pump (15) Transformer (NetCol5000-
A025HNWE2)

● Compressor
The smart cooling product uses a DC variable-frequency compressor that
features compact size, light weight, a long service life, low noise, easy
installation, high reliability, stability, and energy efficiency.
● Oil separator
The oil separator separates the lubricant brought out due to discharge of the
compressor and brings back the separated lubricant to the compressor.
● Fan
The energy-efficient EC fan that supports stepless speed adjustment is used to
reduce the fan energy consumption. Each fan is light and easy to maintain.
The system will not shut down if a single fan fails.
● Evaporator
The finned-tube evaporator with a high cooling efficiency adopts the synergy
field principle and computational fluid dynamics (CFD) to optimize the flow
path design, which greatly improves the heat exchange efficiency.
● Electronic expansion valve (EEV)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 147
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

The throttling device uses a miniature controller to control the operation of


the step motor, thereby changing the pass-through area of the EEV to
regulate the flow of refrigerant.
● Check valve
The one-way valve efficiently controls backflow of gas or liquid.
● Filter dryer
The filter dryer absorbs moisture from the refrigerant pipes and filters out
foreign matters, which reduces the component damage probability and
improves operating efficiency and reliability of components.
● Sight glass
The sight glass allows users to observe the refrigerant flow and the content of
gas and liquid for easy maintenance and optimization.
● Electric heater
The positive temperature coefficient (PTC) electric heater features quick start,
large heating capacity, and even heat dissipation. It has multiple protection
mechanisms to ensure the safe and stable running of the equipment.
● Humidifier
The humidifier controls the humidity in an equipment room.
● Water pump
The pump drives the drainage.
● Display panel
The 7-inch display panel with the true-color touchscreen provides user
interfaces for query, setting, monitoring, and maintenance.

6.2.3.2 Outdoor Unit

Components
A NetCol500 outdoor unit mainly consists of an electric control box, a condenser, a
rack, and fans. The following, uses NetCol500-A060 as an example, describes the
components and configuration.

Figure 6-19 Outdoor unit components

(1) Electric control box (2) Rack (3) Fan

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 148
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Features
● The outdoor unit is equipped with a high-efficiency variable-frequency drive
axial fan to implement big air volume, low noise, and high efficiency.
● The outdoor unit has good waterproof performance and meets IPX5
requirements.
● The outdoor unit adopts the variable-frequency drive. The speed adjustment
of the outdoor fan ranges from 10% to 100%. The minimum operating
frequency of the fan is less than or equal to 5 Hz. The outdoor unit is running
more steadily at low loads.
● The outdoor unit adopts the galvanized sheet and surface phosphatization +
powder coating techniques, the outdoor unit adapts to harsh environments
with its sound rigidity and anticorrosion performance.
● Pressure preservation is performed on the condenser before delivery, and the
pipe ports are properly sealed to prevent foreign matter from entry.

6.2.3.3 Environment and Space Requirements

Operating environment

Table 6-5 Operating environment


Item Specifications

Operating 18–45°C
temperature

Operating humidity 20%–80% RH

Storage temperature –40ºC to +70ºC

Storage humidity 5%–95% RH (non-condensing)

Temperature 18–45°C
adjustment range

Temperature ±1°C; temperature change rate < 5°C/h


adjustment precision

Humidity adjustment 20%–80% RH


range

Humidity adjustment ±5% RH


precision

Protection level Indoor unit: IP20


Outdoor unit: IPX5

Quakeproof level 8–9-degree Mercalli intensity scale

Installation mode Installed on an ESD floor or a concrete floor

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 149
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Item Specifications

Altitude 0–4000 m (derated when the altitude exceeds 1000 m.


For details on derating, contact Huawei Technologies
Co., Ltd.)

Water Quality Requirements for Wet Film Humidifiers


The inlet water pressure should be in the range of 0.1–0.7 MPa (A reducing valve
must be installed if the inlet water pressure exceeds 0.7 MPa.), and the
temperature should be in the range of 1°C–40°C.
The wet film humidifier should use tap water (no water treatment facility needed
for the inlet water) that meets the following requirements:
● Non-freezing and nephelometric turbidity units (NTU): < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
Total hardness (in CaCO3): ≤ 450 mg/L

Installation requirements

NOTICE

If the equipment room is not properly sealed, the humidity in the equipment room
may exceed the upper limit, which is not a product quality issue and should be
dealt with by adding a dehumidifier.

Table 6-6 Installation requirements

Item Specifications

Equipment room Width: ≥ 0.9 m; height: ≥ 2.3 m


door

Floor Bearing capacity: ≥ 350 kg/m2; height of the raised floor


≥ 250 mm

Installation mode Installed on a concrete floor, base, or an ESD floor

Equivalent length of ≤ 100 m


one-way pipe

Height difference ● If the outdoor unit is placed higher than the indoor
between the indoor unit, the vertical distance between them should be
and outdoor units less than or equal to 30 m.
● If the indoor unit is placed higher than the outdoor
unit, the vertical distance between them should be
less than or equal to 8 m.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 150
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Item Specifications

Thermal insulation ≥ 13 mm
foam thickness

Inner diameter of the Liquid pipe: 16 mm


thermal insulation Gas pipe: 19 mm
foam

Water supply ● The water supply pressure ranges from 0.1 MPa to
0.7 MPa.
● The water supply temperature ranges from 1°C to
40°C.
● The transient water flow volume is greater than or
equal to 1.2 L/min.

Power distribution Leakage circuit breakers are not recommended for


requirements mains. If leakage circuit breakers are required by the
customer or by local regulations, use the residual
current circuit breaker (RCCB) that is not sensitive to
the single-phase DC pulses and transient current pulses.

Note: If certain conditions are not met, contact Huawei technical support.

6.2.3.4 Technical Specifications


Table 6-7 and Table 6-8 respectively show the main technical specifications of the
NetCol5000-A in-row smart cooling product.

Table 6-7 General specifications


Item Specifications

Cooling mode Air cooled

Refrigerant R410A

Cooling capacity NetCol5000-A035: 35 kW (T3)


NetCol5000-A025: 25 kW

Air volume 6000 m3/h

Air supply mode Horizontal air supply

Cooling capacity test conditions: dry bulb temperature at air return vent: 37°C;
relative humidity at air return vent: 20%; outdoor temperature: 35°C.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 151
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Table 6-8 Technical specifications of the indoor unit


Item NetCol50 NetCol50 NetCol50 NetCol50 NetCol50 NetCol50
00- 00- 00- 00- 00- 00-
A035H4 A035H40 A035H4 A035H40 A025H4 A025HN
WE0 E0 WE2 E2 WE2 WE2

Powe Single power supply Dual power supplies


r
suppl
y
mode

Powe 380–415 V, 3PH+N+PE, 50 Hz/60 Hz 208V-220


r V, 3W+N
syste +PE, 60Hz
m

Volta If upstream voltage fluctuation exceeds the rated voltage±10%, you are
ge advised to add a voltage regulator. Otherwise, the smart cooling
product may generate alarms frequently and fail to work properly.

Heati Yes No Yes No Yes Yes


ng

Humi Yes No Yes No Yes Yes


difica
tion

Pipe Bottom pipe routing Top and bottom pipe routing


routin
g

Cond No Yes
ensat
e
pump

Wate - 4m
r
pump
lift

Certifi REACH, REACH, REACH, REACH, REACH, REACH,


catio RoHS/ RoHS/ RoHS/ RoHS/ RoHS/ RoHS/
n RoHS 2.0, RoHS 2.0, RoHS 2.0, RoHS 2.0, RoHS 2.0, RoHS 2.0,
CE, WEEE, CE, WEEE, CE, WEEE, CE, WEEE, CE, WEEE, CB, WEEE
China China China China China and IEC
Energy Energy Energy Energy Energy
Conservat Conservat Conservat Conservat Conservat
ion ion ion ion ion
Certificati Certificati Certificati Certificati Certificati
on and on and on and on and on and
IEC IEC IEC IEC IEC

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 152
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Item NetCol50 NetCol50 NetCol50 NetCol50 NetCol50 NetCol50


00- 00- 00- 00- 00- 00-
A035H4 A035H40 A035H4 A035H40 A025H4 A025HN
WE0 E0 WE2 E2 WE2 WE2

a: In the preceding table, No indicates that the corresponding model does not
provide the function.

Figure 6-20 Dimensions

Table 6-9 Technical specifications of the outdoor unit


Item NetCol500- NetCol500- NetCol500- NetCol500-
A040 A060 A080 A120

Power Power supplied by the indoor unit


supply
mode

Model of NetCol5000- NetCol5000- NetCol5000- NetCol5000-


the indoor A025 A025 A035 A025
unit NetCol5000- NetCol5000-
A035 A035

Operating -20°C to 55°C 35 kW: -20°C -5°C to +55°C 35 kW: -20°C


temperatu (With a low- to 45°C (With to 45°C (With
re range temperature a low- a low-
component temperature temperature
-40°C to 45°C) component component
-40°C to 45°C) -40°C to 45°C)
25 kW: -20°C 25 kW: -20°C
to 55°C (With to 55°C (With
a low- a low-
temperature temperature
component component
-40°C to 45°C) -40°C to 45°C)

Fan speed 10%–100%


range

Number of 1 2
fans

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 153
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Item NetCol500- NetCol500- NetCol500- NetCol500-


A040 A060 A080 A120

Dimension 52274285-002: 52273539: BOM number 52273755-002:


s H1 (H2) 1096 (665) x 1107 (677) x 52273541-005: 1107 (655) x
x W1 (W2) 1120 (984) x 1356 (1217) x 1107 (655) x 1356 (1217) x
x D (mm) 1094 1094 2186 (2047) x 2188
52273539-005: 1094
1107 (655) x
1356 (1217) x
1094
52273539-006:
1156 (703) x
1356 (1217) x
1094

Storage –40°C to +70°C


temperatu
re

Storage 5%–95% RH (non-condensing)


humidity

Protection IPX5
level

Altitude 0–4000 m. If the altitude exceeds 1000 m, the cooling performance


is derated. For detailed derating data, contact Huawei technical
support.

Certificatio RoHS/RoHS 2.0, REACH, WEEE, CE and China RoHS/RoHS


n Energy Conservation Certification 2.0, REACH,
WEEE and
China Energy
Conservation
Certification

NOTE

Outdoor unit installation environments are classified as follows based on the harshness:
● Class A (controlled environment): indoor environments where the ambient temperature
and humidity are controlled, including rooms where people live.
● Class B (uncontrollable environment): indoor environments where the ambient
temperature and humidity are not controlled or general outdoor environments with
simple shielding measures where the humidity sometimes reaches 100%.
● Class C (harsh environment): refers to sea environments or outdoor land environments
with simple shielding measures near pollution sources.
● Class D (marine environment): environments that are within 500 m from the coast.
NetCol500-A060MS and NetCol500-A040MS outdoor unit must not be installed in Class
D environments, and other outdoor units must not be installed in Class C or Class D
environments.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 154
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

6.2.4 NetCol5000-A050 Smart Cooling Product


The NetCol5000-A050 is a 50 kW in-row air cooled smart cooling product. It can
be deployed abreast with standard cabinets to provide close-coupled cooling,
thereby reducing energy consumption for cooling, optimizing the power usage
effectiveness (PUE), and increasing energy efficiency for data centers.

6.2.4.1 Indoor Unit

Appearance

Figure 6-21 Dimensions (unit: mm)

(1) Cabinet connecting (2) Display module (3) Door lock (4) Front door
kit

(5) Mounting hole (6) Side panel (7) Rear door (8) Anchor

Table 6-10 Dimensions

Cabinet H x W x D (mm) Expansion Method


Dimensions

Standard 2000 x 600 x 1200 -


dimensions

Expanded 2200 x 600 x 1200 Install a top frame.


dimensions

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 155
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Figure 6-22 Holes

(1) Power cable hole (Φ28 mm) on the top (2) Humidifier water inlet pipe hole (Φ43 mm)
on the top

(3) Skylight signal cable hole (Φ28 mm) on (4) Refrigerant gas pipe hole (Φ43 mm) on the
the top top

(5) Refrigerant liquid pipe hole (Φ43 mm) on (6) Drainpipe hole (Φ43 mm) on the top
the top

(7) Signal cable holes (Φ28 mm) on the top (8) Power cable hole (Φ28 mm) at the bottom

(9) Humidifier water inlet pipe hole (Φ43 mm) (10) Refrigerant gas pipe hole (Φ60 mm) at
at the bottom the bottom

(11) Drainpipe hole (Φ60 mm) at the bottom (12) Refrigerant liquid pipe hole (Φ60 mm) at
the bottom

(13) Signal cable hole (Φ28 mm) at the


bottom

Interior Components
The NetCol5000-A mainly consists of a DC variable-frequency compressor, EC fan,
evaporator, electronic expansion valve (EEV), oil separator, sight glass, filter dryer,
air filter, electric heater (optional), wet film humidifier (optional), condensate
pump (optional), differential pressure switch, and temperature and humidity
sensor (T/H sensor).

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 156
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Figure 6-23 Components

(1) Fan (2) Condensate pump

(3) Drainage check valve (4) Electric heater

(5) Electrical box (6) Evaporator

(7) Wet film humidifier (8) Compressor

(9) Filter dryer (10) Oil separator

(11) EEV (12) Drive

(13) T/H sensor (14) Extra-low voltage (ELV) box

(15) Signal cable terminal block (16) Differential pressure switch

● Compressor
– The smart cooling product uses a DC variable-frequency compressor that
features compact size, light weight, a long service life, low noise, easy
installation, high reliability, stability, and energy efficiency.
– The high-precision drive automatically adapts to the system pressure
fluctuations.
– The drive conducts precision self-check. Compressor and drive faults are
separated.
● EC fan
– The energy-efficient EC fan that supports stepless speed adjustment is
used to reduce the fan energy consumption.
– There are 10 EC fans in total. The smart cooling product will not shut
down if a single fan fails.
– Fans can be maintained with power-on. You can replace one faulty fan
without shutting down the smart cooling product.
● Evaporator

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 157
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

– The evaporator adopts the inner threaded copper pipe and blue
hydrophilic aluminum foil to prevent water blowing due to condensate
water accumulation and improve heat exchange performance. The V-
shaped evaporator optimizes the airflow organization and reduces the air
resistance.
– The finned-tube evaporator with a high cooling efficiency adopts the
synergy field principle and computational fluid dynamics (CFD) to
optimize the flow path design, which greatly improves the heat exchange
efficiency.
– The small-diameter tubes are adopted to enhance the heat exchange
performance, increasing the heat exchange efficiency by more than 10%
when compared with a traditional solution.
– The designed pressure bearing capacity of the heat exchange coil is 4.35
MPa, providing excellent pressure resistance capability.
● EEV
– The throttling device uses a miniature controller to control the operation
of the step motor, thereby changing the pass-through area of the EEV to
regulate the flow of refrigerant.
– The main control module contains an EEV energy storage unit to prevent
slugging due to refrigerant migration after an unexpected power-off.
● Oil separator
The oil separator separates the lubricant brought out due to discharge of the
compressor and brings back the separated lubricant to the compressor.
● Sight glass
The sight glass allows users to observe the refrigerant flow and the content of
gas and liquid for easy maintenance and optimization.
● Filter dryer
The filter dryer absorbs water from the refrigerant pipes and filters out the
foreign matter, which reduces component damage rates and improves
operating efficiency and reliability.
● Air filter
The G4 air filter is used.
● Electric heater
– The positive temperature coefficient (PTC) electric heater automatically
adjusts heating capacity and provides multiple protection measures to
ensure safe and reliable operation.
– The heater features quick start, large heating capacity, and even heating.
● Wet film humidifier
– The wet film humidifier has low water quality requirements and high
environment adaptability.
– Uses a simple structure and is easy to remove, clean, and maintain.
– Quickly starts and generates huge humidification capacity.
– Consumes low power, saving more than 95% energy compared with a
traditional electrode humidifier.
– Provides a longer service life and maintenance interval than a traditional
electrode humidifier.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 158
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

● Condensate pump
The water pump provides power for top drainage with a maximum lift of 4 m.
● Check valve
The check valve effectively prevents gas or liquid backflow.
● Differential pressure switch
When the air filter is dirty or blocked, the differential pressure switch triggers
an alarm, prompting for air filter replacement.
● T/H sensor
The smart cooling product contains the negative temperature coefficient
(NTC) temperature sensor and the return air T/H sensor.

6.2.4.2 Outdoor Unit

Appearance

Figure 6-24 NetCol500-A

Features
● The outdoor unit is equipped with a high-efficiency variable-frequency drive
axial fan and the distinctive sickle blades adopt the owl-inspired fan blade
design to implement big air volume, low noise, and high efficiency.
● The outdoor unit has excellent waterproof performance and meets IPX5
requirements.
● The outdoor unit adopts the variable-frequency drive. The outdoor fan speed
is adjustable from 10% to 100%. The minimum operating frequency of the
fan is no greater than 5 Hz. The outdoor unit is running more steadily at low
loads.
● Adopted the galvanized sheet and surface phosphatization + powder coating
techniques, the outdoor unit adapts to harsh environments with its sound
rigidity and anticorrosion performance.
● Pressure preservation is performed on the condenser before delivery, and the
pipe ports are properly sealed to prevent foreign matter from entry.

6.2.4.3 Environment and Space Requirements

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 159
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Operating Environment

Table 6-11 Environmental specifications

Item Specifications

Supply air 15–35°C


temperature
range

Supply air 15%–80% RH


humidity
range

Return air 18–45°C


temperature
range

Return air 15%–80% RH


humidity
range

Temperature ±1°C, temperature change rate < 5°C/hour


adjustment
precision

Humidity ±5% RH
adjustment
precision

Storage –40°C to +70°C


temperature

Storage 5%–95% RH (non-condensing)


humidity

IP rating ● Indoor unit: IP20


● Outdoor unit: IPX5

Installation Installed on an ESD floor or a concrete floor


mode

Altitude 0–4000 m, derated at above 1000 m For details about derating


coefficients, see Table 6-12.

Table 6-12 Derating coefficients

Altitude 0 1000 1500 2000 2500 3000 3500 4000


(m)

Air 1 0.887 0.835 0.785 0.737 0.692 0.649 0.608


volume
coefficie
nt

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 160
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Altitude 0 1000 1500 2000 2500 3000 3500 4000


(m)

Cooling 1 0.940 0.909 0.878 0.846 0.815 0.784 0.753


capacity
coefficie
nt

Installation Requirements

NOTICE

If the total actual load of servers for each smart cooling product is less than 10%
of the rated cooling capacity or the equipment room is not properly sealed, the
humidity in the equipment room may exceed the upper limit, which is not a
product quality issue and should be dealt with by adding a dehumidifier.

Table 6-13 describes the installation requirements for the NetCol5000-A.

Table 6-13 Installation requirements


Item Specifications

Room Width ≥ 1.2 m; height ≥ 2.3 m


door

Floor Floor bearing capacity ≥ 530 kg/m2

Equivale ≤ 100 m
nt
length
of the
one-
way
pipe

Height ● If the outdoor unit is placed higher than the indoor unit, the
differen maximum vertical distance between them is 30 m.
ce ● If the indoor unit is placed higher than the outdoor unit, the
betwee maximum vertical distance between them is 8 m.
n indoor
and
outdoor
units

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 161
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Item Specifications

Water The inlet water pressure should be in the range of 0.1–0.7 MPa, and
supply the temperature should be in the range of 1–40°C.
require The wet film humidifier uses tap water and does not require an
ments additional water treatment device at the water inlet. The water
requirements are as follows:
● Non-freezing and nephelometric turbidity units (NTU) < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO3) ≤ 450 mg/L
For details, see GB 5749-2006 Standards for Drinking Water Quality.

Power Leakage circuit breakers are not recommended for the main power
distribut route. If a leakage circuit breaker is required by the customer or local
ion regulations, select the residual current circuit breaker (RCCB) that is
require insensitive to single-phase DC pulsation and transient impulse
ments current.

Note: If the requirements are not met, contact technical support engineers for
an optimization solution.

6.2.4.4 Technical Specifications

Table 6-14 NetCol5000-A general specifications


Item Specifications

Refrigerant R410A

Cooling 46 kW
capacitya

Air supply Horizontal flow


mode

Airflow 9000 m3/h

Dimensions ● 2000 mm x 600 mm x 1200 mm (cabinet dimensions)


(H x W x D) ● 2200 mm x 600 mm x 1200 mm (including a top frame)

IP rating IP20

a: Tested under rated working conditions (indoor dry-bulb temperature: 37°C,


relative humidity: 20%, outdoor temperature: 35°C).

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 162
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Table 6-15 NetCol5000-A optional specifications


Item NetCol NetCol NetCol NetCol NetCol NetCol NetCol5
5000- 5000- 5000- 5000- 5000- 5000- 000-
A050H A050H A050H A050H A050H A050H A050H4
4WD2 40D2 4WE2 40E2 RWE2 4WE0 0E0

Power 380–415 V AC, 50/60 Hz, 3 Ph+N+PE 440– 380–415 V AC,


system Tolerance: –10% to +10% of rated 480 V 50/60 Hz, 3 Ph+N
voltage, rated frequency±3 Hz AC, 60 +PE
Hz, 3 Tolerance: –10%
Ph+PE to +10% of rated
Toleran voltage, rated
ce: – frequency±3 Hz
10% to
+10%
of
rated
voltage
, rated
frequen
cy±3
Hz

Power Dual power supplies Single power


supply supply
mode

Pipe Top and bottom pipe routing Bottom pipe


routing routing

Maximum 46 A 36 A 46 A
current

Condensa Yes No
te pump

Water 4m -
pump lift

Heating Yes No Yes No Yes Yes No


function

Humidific Yes No Yes No Yes Yes No


ation
function

Humidifie No No Yes No Yes Yes No


r water
inlet hose

Reheating 6 kW No 6 kW No 6 kW 6 kW No
capacity

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 163
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Item NetCol NetCol NetCol NetCol NetCol NetCol NetCol5


5000- 5000- 5000- 5000- 5000- 5000- 000-
A050H A050H A050H A050H A050H A050H A050H4
4WD2 40D2 4WE2 40E2 RWE2 4WE0 0E0

Connectio Welding Thread connection


n mode
of the
compress
or and
filter
dryer

Castor No Yes

Humidific 3 kg/h No 3 kg/h No 3 kg/h 3 kg/h No


ation
capacity

Net 314.5 312 318 323 305 309 314.5


weight/ kg/ kg/329 kg/346 kg/340 kg/333 kg/337 kg/
Gross 331.5 kg kg kg kg kg 331.5 kg
weight kg

Figure 6-25 Appearance and dimensions

Table 6-16 Technical specifications of outdoor units


Item NetCol500-A060 NetCol500-A080 NetCol500-A120

BOM number NetCol500- NetCol500- NetCol500-


A060MC1D0: A080MC1D0: A120MC1D0:
52273539, 52273541-005, 52273755-002,
52273539-005, 52273541-010 52273755-004
52273539-007,
52273539-010
NetCol500-
A060MS1E0:
52273539-006

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 164
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Item NetCol500-A060 NetCol500-A080 NetCol500-A120

Power supply Powered by the indoor unit


mode

Temperature 52273539 and 52273541-005 52273755-002


control intelligent 52273539-007: and and
monitoring board available 52273541-010: 52273755-004:
52273539-005, unavailable unavailable
52273539-010,
and
52273539-006:
unavailable

Operating –20°C to +45°C (– –5°C to +55°C –20°C to +45°C (–


temperature 40°C to +45°C 40°C to +45°C
range with a low with a low
temperature temperature
component) component)

Fan speed range 10%–100%

Number of fans 1 2 2

Dimensions (H1 BOM numbers BOM numbers BOM numbers


(H2) x W1 (W2) x 52273539 and 52273541-005 52273755-002
D) (mm) 52273539-007: and and
1107 (677) x 1356 52273541-010: 52273755-004:
(1217) x 1094 1107 (655) x 2186 1107 (655) x 1356
BOM numbers (2047) x 1094 (1217) x 2188
52273539-005
and
52273539-010:
1107 (655) x 1356
(1217) x 1094
BOM number
52273539-006:
1156 (703) x 1356
(1217) x 1094

Net weight 52273539 and 52273541-005 52273755-002


52273539-007: and and
122 kg 52273541-010: 52273755-004:
52273539-005 200 kg 265 kg
and
52273539-010:
121 kg
52273539-006:
154 kg

Storage –40°C to +70°C


temperature

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 165
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Item NetCol500-A060 NetCol500-A080 NetCol500-A120

Storage humidity 5%–95% RH (non-condensing)

IP rating IPX5

Altitude 0–4000 m. If the altitude exceeds 1000 m, the cooling


performance is derated. For details about derating data,
contact technical support.

Table 6-17 Application environment


Type Description

Class A (controlled Indoor environments where the temperature


environment) and humidity are controlled, including rooms
where human beings live

Class B (uncontrolled Indoor environment where the ambient


environment) temperature and humidity are not controlled
or outdoor environments (with simple
shielding measures) where the humidity can
reach 100%.

Class C (harsh environment) Sea environments or outdoor land


environments (with simple shielding measures)
near pollution sources. Pollution sources refer
to the following areas:
● Areas within 3.7 km away from saline water
areas such as the ocean and saline lakes
● Areas within 3 km of serious pollution
sources, such as metallurgic plants, coal
mines, and heat and power plants
● Areas within 2 km away from medium
pollution sources, such as chemical
factories, rubber plants, and electroplating
factories
● Areas within 1 km away from light pollution
sources, such as food factories, tanneries,
and heating boilers

Class D (marine environment) Areas within 500 m away from the seashore.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 166
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

NOTE

● If an outdoor unit needs to be used at a site 3.7–10 km away from the coast in a class B
environment, it is recommended that the unit be installed in a shielded area, such as a
podium building, ground, or building rear, to prevent mechanical parts from being
corroded by sea wind (the functionality and reliability of the system must not be
affected). Alternatively, use an outdoor unit that supports class C environments to avoid
corrosion. If the site is more than 10 km away from the coast, the unit can be properly
installed.
● The NetCol500-A060MS1E0 outdoor unit must not be installed in class D environments,
and other outdoor units must not be installed in class C or class D environments.

Figure 6-26 NetCol500-W dimensions

Figure 6-27 NetCol500-W hole dimensions

Table 6-18 Operating environment specifications of the water-cooled module

Item Technical Specifications

Power system 220–240 V AC, 1 Ph+N+PE, 50/60 Hz

Refrigerant R410A

Heat exchanging 55 kW
capacity

Temperature range 4°C to 45°C

Humidity range 5%–90% RH

Storage –40°C to +70°C


temperature

Storage humidity 5%–95% RH (non-condensing)

Inlet water 10°C to 37°C


temperature range
of chilled water

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 167
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System

Item Technical Specifications

Maximum 125°C
operating
temperature on the
refrigerant side

Maximum 60°C
operating
temperature on the
cooling water side

Water flow rate 9.5 m3/h

Water-side pressure 1.2 MPa


bearing

Refrigerant-side 4.35 MPa


pressure bearing

IP rating IP21

Altitude 0–4000 m (derated when the altitude is greater than 1000


m)

Environment Enclosed indoor environment in which the temperature


and humidity can be controlled within the ranges of 4°C
to 45°C and 5% RH to 90% RH respectively. If the indoor
installation position is ventilated, it should be more than
3.7 km away from the sea or pollution sources (such as
salt lakes, chemical plants, mineral plants, thermal power
plants, and coal mines).

Net weight 63 kg

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 168
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

7 Management System

7.1 System Description


Each smart module provides an independent and integral interface for
environment and power monitoring. This interface constantly monitors devices
such as the power supply and distribution equipment, smart cooling products, T/H
sensors, water sensors, smoke detectors, and video surveillance equipment inside
the module. If a component fault or parameter error is detected, alarms are
generated and reported through indicator light, email, and short message service
(SMS). Historical data and alarm events are recorded, and all monitoring
information is reported to the management platform.
The PAD or mobile phone app can be used to query device information in real
time, facilitating mobile O&M.
To improve the reliability of the monitoring system, Ethernet ring bus networking
is used for intelligent node signal transmission and sensor power supply.

Figure 7-1 System networking diagram (FusionModule Actuator scenario)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 169
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

NOTE

● In the figure, RF_Z indicates wireless networking. RF_Z(1) devices can communicate with
the ECC800-Pro in wireless mode. RF_Z(1) and RF_Z(2) devices use different protocols
and are isolated from each other.
● After the access actuator, FusionModule Actuator, and multi-functional sensor are
connected to the ECC800-Pro through PoE and they communicate successfully, wireless
communication is automatically set up.
● The smart screen can be connected to an ETH gateway or switch.
● Connect the signal cable from each camera and IVS1800 to the LAN switch in the
following scenarios:
● (1) Four or more cameras and IVS1800s are deployed in a single smart module.
● (2) The cameras outside the smart module are connected to the smart module,
and there are at least four cameras and IVS1800s inside and outside the smart
module.
● (3) Multiple smart modules share one IVS1800.
● (4) There are at least two IVS1800s.

7.2 System Functions

7.2.1 Monitoring
● Temperature and humidity monitoring: detects and collects statistics on the
ambient temperature and humidity inside the smart module.
● Water leakage monitoring: detects water leakage at the bottom of the smart
module and provides real-time alarm signals.
● Smoke monitoring: detects smoke in the smart module and provides real-time
alarm signals.
● Power distribution monitoring:
a. Detects and collects statistics on the total input phase voltage, current,
frequency, power factor, electric energy, active power, apparent power,
load rate, THDv, THDi, and cabinet interior busbar temperature for the
smart module.
b. Detects the current, electric energy, switch status, contact temperature,
and load rate of the power distribution branches for IT equipment and
smart cooling products; collects statistics on electric energy by month or
year.
● Smart cooling product monitoring:
a. Monitors the supply and return air temperature and humidity in real
time.
b. Configures the supply air temperature set point for all smart cooling
products, without the need to separately configure it for each smart
cooling product.
c. Monitors and displays the fan speed, and displays the running
percentage.
d. Displays the cooling load rate.
e. Monitors and displays the compressor running status.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 170
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

f. Provides reminders on regular air filter replacement.


g. Displays the real-time running status of heaters and humidifiers.
● Video surveillance: Connects to four cameras and provides PoE power supply;
accesses real-time video images on the WebUI and invokes historical
monitoring data.
● Access control management: The cabinet access control system supports
permission management by fingerprint and card. If an automatic door is
deployed for the aisle access control system, the automatic door sensor can
detect intrusion and door opening.

7.2.2 App View (PAD)


NOTE

The app views are for reference only.


● Generates a 3D layout view that matches the actual layout of the smart
module, including the PDF, smart cooling product, IT cabinet, and T/H sensor.
The app can also graphically display the power, space (optional), and
temperature (optional) of a single cabinet. In addition, the resource usage
rate of power, space, and cooling capacity, PUE value, power consumption,
ambient temperature and humidity, and alarm information of the smart
module are displayed on the home screen of the app.

Figure 7-2 App home screen (power)

● Supports full link display of the power supply and distribution system for the
smart module. The connection mode and topology of power supply and
distribution devices such as the integrated UPS, battery, PDF, and cabinet
rPDU are included. You can check the switch status and running status of
power supply and distribution devices in a view.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 171
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Figure 7-3 Power supply link view

● Shows the cooling system of the smart module, displays the air intake and
outtake temperatures and running parameters of smart cooling products, aisle
temperature and humidity, and temperatures (optional) at the front and rear
of a single cabinet. The app also displays the detailed running parameters of
a single smart cooling product and the running status of components such as
the compressor, fan, and expansion valve.

Figure 7-4 Cooling view

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 172
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Figure 7-5 Running view of a single smart cooling product

● Displays the resource usage of the power, space, and cooling capacity of the
smart module and each cabinet.

Figure 7-6 Power view

● Displays the real-time status and alarms of the aisle T/H sensor, door status
sensor, water sensor, and lighting in the plan view.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 173
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Figure 7-7 Environment status view

● Displays the PUE value of the smart module in a data dashboard; allows you
to view the historical PUE curve and power consumption of the smart module
by day, month, or year.

Figure 7-8 PUE curve

● Supports facial recognition. After facial recognition information is added, you


can quickly log in to the system without entering the user name and
password. Access control rights can be flexibly set for different users.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 174
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

7.2.3 App View (Smart Screen)


NOTE

The app views are for reference only.


● Generates a 3D layout view that matches the actual layout of the smart
module, including the PDF, IT cabinet, and T/H sensor. In addition, the
resource usage rate of power, space, and cooling capacity, PUE value, power
consumption, ambient temperature and humidity, and alarm information of
the smart module are displayed on the home screen of the app.

Figure 7-9 App home screen (power)

Figure 7-10 App home screen (temperature)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 175
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

● Supports facial recognition. After facial recognition information is added, you


can quickly log in to the system without entering the user name and
password. Access control rights can be flexibly set for different users.

Figure 7-11 Facial recognition

7.2.4 Alarm
● The system monitors the status of smart cooling products, power distribution,
and environment. If a fault or parameter error occurs, the system generates
an alarm in real time. You can view the alarm cause and solution in the alarm
details.
● Alarms can be classified into four severities: critical, major, minor, and
warning. The alarm severities can be user-defined.
● Active alarms can be filtered by device and alarm severity.
● Real-time alarms can be displayed in different colors on the power supply link
view of the app. Alarms can be associated with the alarm beacon and eLight.
The color corresponding to the alarm severity is displayed on the aisle door of
the smart module.
● Alarm notifications can be sent by email and SMS.
● A maximum of 500 concurrent active alarms are supported.

7.2.5 History Query


● Historical alarm query: You can view the alarms that have been generated in
the system. The historical alarm information includes the device name, alarm
name, alarm severity, alarm generation time, and alarm clearance time.
● Performance data statistics: You can view historical data of devices to help
analyze data or problems.
● Operation log query: You can view logs of key operations, such as user login,
parameter modification, data export, device upgrade, and access control
events.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 176
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

● Data export: You can export historical data of the ECC800-Pro and some
southbound devices.

7.2.6 Linkage Control


● The linkage logic is added for aisle smoke alarms or high temperature alarms.
By default, the skylights are opened if such alarms are generated. You can
also set the linkage logic to open end doors (electric sliding doors), turn on
aisle lights, and shut down smart cooling products.
NOTE

Aisle smoke alarms cannot trigger the customer's fire extinguishing system. Only dry
contact alarm signals are provided.
● Smart cooling products in the aisle can be shut down when the customer's
fire extinguishing system generates dry contact alarms.
● Skylights and doors can be opened and lights can be turned on when the
customer's (or external) fire extinguishing system generates dry contact
alarms or signals.
● You can manually configure linkage policies for monitoring systems inside the
smart module.
● Intelligent lighting (motion detection) is supported. When an object is
detected in the aisle, the aisle lights turn on. If no object is detected within 10
minutes, the aisle lights automatically turn off.

7.3 Hardware Description

7.3.1 ECC800-Pro

7.3.1.1 Product Configuration


The ECC800-Pro data center controller is mainly used to monitor the devices and
environment in a data center. It consists of the power supply units (PSUs) and
main control module, which are pluggable.
You can configure the ECC800-Pro collector in the following two manners:
Configuration 1 (typical configuration): one PSU and one main control module
Configuration 2: two PSUs and one main control module.

NOTE

● In configuration 1, a PSU is installed in slot 1, and a filler panel is installed in slot 2.


● In configuration 2, PSUs are installed in slots 1 and 2.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 177
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Figure 7-12 ECC800-Pro collector in configuration 2

(1) Slot 1: PSU (2) Slot 2: PSU (3) Slot 3: main control
module

Figure 7-13 ECC800-Pro (rear view)

(1) 53.5V DC_OUT1 (2) 53.5V DC_OUT2 (3) AC_INPUT1

(4) AC_INPUT2

Power Port
The ECC800-Pro provides four power ports, including two AC input ports
(AC_INPUT1 and AC_INPUT2) and two DC output ports (DC_OUT1 and
DC_OUT2). Table 7-1 provides the power port pin definitions.

Table 7-1 Power port pin definitions


Port Type Silk Description
Screen

DC RTN+ 48V+

RTN- 48V GND

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 178
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

7.3.1.2 Main Control Module

Figure 7-14 ECC800-Pro main control module

(1) USB (2) Status indicator (3) AIDI_1 (4) AIDI_2

(5) COM1/AIDI_4 (6) COM3/12V (7) WAN1 (8) LAN1/PoE

(9) LAN2/PoE (10) WAN2 (11) COM4/CAN (12) COM2/AIDI_5

(13) AIDI_3 (14) DO/12V (15) RF_Z (802.15.4) (16) WLAN

(17) 4G (18) SW button

Figure 7-15 ECC800-Pro main control module (side view)

(1) SIM card slot (2) Micro SD card slot (reserved)

NOTE

The dimensions of the SIM card are 25 mm x 15 mm.

Signal Port
The ECC800-Pro provides the following communications ports. The pins of the
RJ45 port are shown in the figure.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 179
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Figure 7-16 RJ45 port pins

There are four GE ports, that is, two WAN ports (WAN1 and WAN2) and two LAN
ports (LAN1/PoE and LAN2/PoE).

Table 7-2 GE port pin definitions

Item Description

Pin Pin 1 GE1+


sequence
Pin 2 GE1–

Pin 3 GE2+

Pin 4 GE3+

Pin 5 GE3–

Pin 6 GE2–

Pin 7 GE4+

Pin 8 GE4–

Indicator Green Linked, steady on


indicator

Yellow ACT data communication, blinking


indicator

Table 7-3 COM1/AIDI_4 and COM2/AIDI_5 port pin definitions

Item Description

Pin Pin 1 RS485+


sequence
Pin 2 RS485–

Pin 3 12 V DC_OUT

Pin 4 RS485+

Pin 5 RS485–

Pin 6 DI–

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 180
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Description

Pin 7 DI+

Pin 8 GND

Indicator Green Power output indicator


indicator ● Steady on: The 12 V DC output is normal.
● Off: No 12 V DC output is provided.

Table 7-4 COM3/12V port pin definitions


Item Description

Pin Pin 1 RS485+


sequence
Pin 2 RS485–

Pin 3 12 V DC_OUT

Pin 4 RS485+

Pin 5 RS485–

Pin 6 -

Pin 7 -

Pin 8 GND

Indicator Green Power output indicator


indicator ● Steady on: The 12 V DC output is normal.
● Off: No 12 V DC output is provided.

Table 7-5 COM4/CAN port pin definitions


Item Description

Pin Pin 1 RS485+


sequence
Pin 2 RS485–

Pin 3 -

Pin 4 RS485+

Pin 5 RS485–

Pin 6 -

Pin 7 CAN_H

Pin 8 CAN_L

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 181
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Table 7-6 AIDI_1, AIDI_2, and AIDI_3 ports pin definitions


Item Description

Pin Pin 1 Type_1


sequence
Pin 2 Type_2

Pin 3 12 V DC

Pin 4 Type_3

Pin 5 Type_4

Pin 6 DI–

Pin 7 DI+

Pin 8 GND

Indicator Green Power output indicator


indicator ● Steady on: The 12 V DC output is normal.
● Off: No 12 V DC output is provided.

● Pins 1, 2, 4, and 5 identify sensor types.


● Pins 3 and 8 are power output ports.
● Pins 6 and 8 can detect current type sensors (4–20 mA). Pins 6 and 7 can
detect the output status of passive dry contact type sensors. Pins 3 and 7 can
detect temperature sensors.

Table 7-7 DO/12V port pin definitions


Item Description

Pin Pin 1 -
sequence
Pin 2 -

Pin 3 12 V DC_OUT

Pin 4 -

Pin 5 -

Pin 6 DO_OUT+

Pin 7 DO_OUT–

Pin 8 GND

Indicator Green Power output indicator


indicator ● Steady on: The 12 V DC output is normal.
● Off: No 12 V DC output is provided.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 182
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Indicators

Table 7-8 Indicators on the ECC800-Pro main control module


Indicator Color Name Status Description

RUN Green Running Steady on The power supply is


status normal and the program
indicator is being loaded.

Off The power supply is


abnormal.

Blinking The software runs


at long properly and the
intervals management system is
successfully registered
(the indicator blinks at 0.5
Hz, on for 1s and then off
for 1s).

Blinking The ECC800-Pro does not


at short register with the
intervals management system (the
indicator blinks at 5 Hz,
on for 0.1s and then off
for 0.1s).

ALM Red Alarm Steady on A system failure alarm is


indicator generated.

Off The system is normal.

RF_Z Green Communicati Blinking A network is set up, and


on status at long no node access is allowed
indicator intervals (the indicator blinks at 0.5
Hz, on for 1s and then off
for 1s).

Blinking A network is set up, and


at super node access is allowed
short (the indicator blinks at 10
intervals Hz, on for 0.05s and then
off for 0.05s).

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 183
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

SW Button

Table 7-9 SW button description


Function Operation Description Indicator Status
Description

Wireless In non-wireless network (802.15.4) The RF_Z indicator is


network RF_Z pairing mode, press and hold the blinking at super
(802.15.4) button for 3s to 5s to enter the short intervals.
pairing wireless network pairing mode.

In wireless network (802.15.4) The RF_Z indicator is


pairing mode, press and hold the blinking at long
button for 3s to 5s to exit the intervals.
pairing mode; or the system
automatically exits the pairing mode
after 30 minutes without pressing
the button.

Hold down the button for more than The RF_Z indicator is
8s to erase network parameters. The blinking at super
system automatically enters the short intervals.
wireless network pairing mode.

WLAN enabling Hold down the button for 1s to -


enable WLAN.

Restoring the Press and hold down the button for -


default IP 1 minute.
address, local
default settings,
and user
management
information;
clearing the
devices that
failed to
communicate,
historical alarms,
and
performance
data.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 184
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

7.3.1.3 PSU

Indicators

Table 7-10 PSU indicator description


Indicator Color Name Status Description

Green Power Steady on The PSU has input power.


indicator
Off The PSU has no input power or
is faulty.

Blinking at The PSU is being queried (the


long indicator blinks at 0.5 Hz, on
intervals for 1s and then off for 1s).

Blinking at The PSU application program is


short being loaded (the indicator
intervals blinks at 4 Hz, on for 0.125s
and then off for 0.125s).

Yellow Alarm Steady on Power limiting warning due to


indicator ambient overtemperature;
shutdown alarm for protection
against ambient
overtemperature or
undertemperature

Power input overvoltage or


undervoltage protection

Reverse DC input connection

Slight current imbalance

Output overvoltage

Hibernation

Off The PSU generates no


protection alarms.

Blinking at The communication between


long the PSU and the external
intervals equipment is interrupted (the
indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).

Red Fault Steady on The PSU locks out due to


indicator output overvoltage.

The PSU has no output due to


internal faults.

Off The PSU is normal.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 185
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

7.3.2 UIM20A Expansion Module


The UIM20A expansion module is used to increase the number of device ports. It
can connect to sensors such as the smoke detector, water sensor, door status
sensor, and infrared sensor.

Figure 7-17 Front panel of the UIM20A expansion module

(1) Indicators and button (2) COM1/AIDI_1–COM8/ (3) POE


AIDI_8

Figure 7-18 Rear panel of the UIM20A expansion module

(1) DIP switch (reserved) (2) COM_OUT (reserved) (3) COM_IN (reserved)

Table 7-11 Structural specifications of the UIM20A expansion module

Item Specifications

Width 120 mm

Depth 200 mm

Height 43 mm

Operating –30°C to +65°C


temperature

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 186
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Installation Installed in a 19-inch rack


requirement
s

Environmen RoHS5
tal
protection

Technical Specifications

Table 7-12 Technical specifications of the UIM20A expansion module

Item Specifications

Power input Supports the RS485 or PoE power supply.

COM/AIDI (RJ45) ● Supports eight RS485 or AI/DI signal inputs.


● Can connect to sensors such as the smoke sensor, water
sensor, door status sensor, and infrared sensor.
● Each port can supply power. Two RJ45 ports share one
12 V DC power supply that is controlled independently.
The maximum output current is 900 mA when the
voltage is 12 V. (COM1/AIDI_1 and COM2/AIDI_2 form a
group, COM3/AIDI_3 and COM4/AIDI_4 form a group,
COM5/AIDI_5 and COM6/AIDI_6 form a group, and
COM7/AIDI_7 and COM8/AIDI_8 form a group).
● The 12 V DC power supply can be switched on or off
and is on by default.

POE Connects to the ECC800-Pro through the PoE port.

E-label 4.0 Supported

Communications Ports
The following table describes the pin definitions for ports COM1/AIDI_1 to COM8/
AIDI_8.

Table 7-13 Pin definitions for ports COM1/AIDI_1 to COM8/AIDI_8

Item Description

Pin Pin 1 RS485+


sequence
Pin 2 RS485–

Pin 3 12 V

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 187
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Description

Pin 4 RS485+

Pin 5 RS485–

Pin 6 D-

Pin 7 D+

Pin 8 GND

The following table describes the pin definitions for the COM_IN and COM_OUT
ports.

Table 7-14 Pin definitions for the COM_IN and COM_OUT ports

Item Description

Pin Pin 1 RS485+


sequence
Pin 2 RS485–

Pin 3 12 V (input power, supplying power to the module)

Pin 4 RS485+

Pin 5 RS485–

Pin 6 -

Pin 7 -

Pin 8 GND

Indicators and Button

Table 7-15 UIM20A indicators

Indicator Status Description

RUN Steady A board application is being loaded.


on

Off The board is not running.

Blinking The ECC800-Pro is successfully registered, and the


at long software runs properly (blinking at long intervals (0.5
intervals Hz), on for 1s and then off for 1s).

Blinking The communication is interrupted or the ECC800-Pro is


at short unsuccessfully registered (blinking at 2.5 Hz, on for 0.2s
intervals and then off for 0.2s).

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 188
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Indicator Status Description

Blinking Blinking at super short intervals for 0.5s and then off for
0.5s; last 10s (blinking at super short intervals: 10 Hz,
on for 0.05s and then off for 0.05s)

ALM Steady A system fault alarm is raised.


on

Off The system is normal.

Table 7-16 BLINK button description

Function Operation Indicator Status


Description Description

Blinking Press the button for The RUN indicator blinks at super
less than 2s. short intervals for 0.5s and then off for
0.5s; last 10s (blinking at super short
intervals for 10 Hz, on for 0.05s and
then off for 0.05s).

7.3.3 Smart ETH Gateway


A smart ETH gateway allows the extension of the 53.5 V DC power supply and FE
communication for the ECC800-Pro and can be flexibly deployed in a smart
module.

Figure 7-19 Smart ETH gateway

(1) PWR_IN cascading (2) FE_1 cascading (3) PoE_1–2 ports (4) PoE_3–4 ports
power port signal port

(5) 48V_OUT1 power (6) 48V_OUT2 power (7) FE_2 cascading (8) PWR_OUT
output port output port signal port cascading power port

(9) BLINK button (10) Status indicator

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 189
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Specifications

Table 7-17 Technical specifications for a smart ETH gateway


Item Specifications

Power input PWR_IN D-type power input terminal, for power cascading, input
voltage range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A, 48 V DC);
power of cascaded smart ETH gateways: max (25 A, 48 V DC)

Power ● PWR_OUT D-type power output terminal, for power


output cascading, output voltage range: 45–55 V DC
● 48V_OUT1 and 48V_OUT2, terminal (1 A, 48 V DC), output
voltage range: 45–55 V DC

FE port Two FE ports, RJ45 terminal with an indicator, 10/100 Mbit/s


communications rate, for the cascading between smart ETH
gateways and the communications with the host

PoE port Four PoE ports, RJ45 terminal with an indicator, 10/100 Mbit/s
communications rate, complying with IEEE 802.3, IEEE 802.3u,
IEEE 802.3af/at

BLINK If you press the BLINK button, the RUN indicator blinks
button intermittently at super short intervals (blinking at super short
intervals for 0.5s and then off for 0.5s, lasting 5 seconds in total).

Indicators

Table 7-18 Indicators on a smart ETH gateway


Indicator Color Name Status Description

PWR Green Power input Steady on The power input is


status normal.
indicator
Off There is no power input.

RUN Green Module Off The power supply is


running abnormal.
status
indicator Blinking The smart ETH gateway
at long successfully registers with
intervals the ECC800-Pro and the
software runs properly
(the indicator blinks at 0.5
Hz, on for 1s and then off
for 1s).

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 190
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Indicator Color Name Status Description

Blinking The indicator blinks at


super short intervals for
0.5s (blinking at 10 Hz, on
for 0.05s and then off for
0.05s) and then turns off
for 0.5s. The cycle lasts for
5s.

ALM Red Alarm Steady on The PoE output current is


indicator overloaded.

Off The PoE output is normal


or not connected.

7.3.4 FusionModule Actuator


The FusionModule Actuator is applied in a smart module. It controls the lighting
inside the smart module through the access control system, host instructions,
infrared linkage information (disabled by default), or lighting button, and provides
a PAD charging port. The FusionModule Actuator can also control the rotating
skylight of the aisle based on the fire alarm linkage information or the host
control information, and opens the magnetic lock when detecting the card swiping
information of the card reader, exit button information, and fire linkage
information. In addition, the FusionModule Actuator manages access rights,
records entrance and exit events, and records alarms.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 191
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Appearance

Figure 7-20 FusionModule Actuator

(1) 48 V DC power (2) LAN port (3) RS485 ports (4) RS485 port COM3
input port (COM1/COM2) (reserved)

(5) DIP switch (6) AC OUT power (7) Terminal cover (8) AC IN power input
output ports port

(9) Fuse (10) Indicators (11) BLINK button (12) Spare fuse box

(13) Wiegand ports (14) AI/DI ports (15) DO/12V port (16) DO/DI ports

Specifications

Table 7-19 Indicators

Item Specifications

Power Input ● AC IN: one AC input, 90 V AC to 240 V AC


● 48 V DC input: terminal, with an input voltage of 36 V DC to
60 V DC

Power ● AC OUT1: two AC outputs, 90 V AC to 240 V AC. The


output maximum current of two outputs is 5 A.
● AC OUT2: one AC output, 90 V AC to 240 V AC. The maximum
current is 5 A.

LAN port FE communication with a communications rate of 10/100 Mbit/s

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 192
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Wireless One wireless port that complies with IEEE 802.15.4, mutual
communicat backup with FE communication
ion

RS485 serial COM1/2: two RS485 ports (one route) with a default
port communication rate of 9600 bit/s, physical port cascading
(reserved)
COM3: southbound or northbound communication (reserved)

DO/DI port ● Access: One DO output port is used to control the power
output of the electronic door lock, and one DI input port is
used to connect to the door status switch. Both ports use
terminals.
● Skylight: One DO output port is used to control the power
output of the skylight magnetic lock, and one DI input port is
connected to the skylight open button. Both ports use
terminals.

DO/12V One DO port with 12 V DC power supply (reserved)

AI/DI port Five AI/DI ports, in which one is for detecting one door open
button, two for detecting lighting buttons, and one for detecting
fire extinguishing linkage signal. One port is reserved.

Wiegand Two Wiegand ports, 12 V DC card reader operating power


port output; two routes of card readers can operate at the same time.

BLINK ● Press the button for less than 1 second to start blinking.
button ● Hold down the button for 1–5 seconds to search for a network
and start networking.
● Hold down the button for more than 6 seconds to clear
network parameters.

Address DIP 4-pin address DIP switch (reserved)


switch

Fuse 16 A, 250 V AC

Spare fuse Two 16 A, 250 V AC fuses


box

E-label Supported

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 193
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Indicators

Table 7-20 Indicators


Indicat Color Name Status Description
or

Power Green Power input Steady on The power input is normal.


status
indicator Off There is no power input.

RUN Green Running Off The power is abnormal or the


status board program is loading.
indicator
Blinking at The FusionModule Actuator
long successfully registers with the
intervals ECC800-Pro and the software
runs properly (the indicator
blinks at 0.5 Hz, on for 1s
and then off for 1s).

Blinking at The communication fails or


short the FusionModule Actuator
intervals fails to register with the
ECC800-Pro (the indicator
blinks at 4 Hz, on for 0.125s
and then off for 0.125s).

Blinking The indicator blinks at super


short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 5s.

ALM Red Alarm Steady on A system failure alarm is


indicator generated.

Off No system alarm is


generated.

RF_Z Green Communicati Steady on No network parameters exist,


on status or a network is to be created.
indicator
Blinking at A network is set up, and no
long node access is allowed (the
intervals indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).

Blinking at A network is being set up,


super short and node access is allowed
intervals (the indicator blinks at 10
Hz, on for 0.05s and then off
for 0.05s).

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 194
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Indicat Color Name Status Description


or

Blinking The FusionModule Actuator


intermittent is searching for a network
ly at super (the indicator blinks at super
short short intervals for 0.5s and
intervals then turns off for 0.5s).

7.3.5 PAD
● The PAD allows the wireless access from the data center management system.
You can monitor the equipment in the data center and environmental
parameters in real time over the app.
● You are advised not to set Sleep to Never for the PAD, which may shorten the
service life of the screen and battery.

Figure 7-21 PAD

Table 7-21 PAD technical specifications


Item Specifications (53010KXA) Specifications (53013YDR)

Dimensions 243 mm × 164 mm × 7.8 mm 246.9 mm x 156.7 mm x 7.85


(H x W x D) mm

Weight (with About 460 g About 468 g


the battery)

Touchscreen 10.1-inch, 1920 x 1200 10.4-inch, 2000 x 1200


resolution, IPS screen, and resolution, IPS screen, and
multi-touch multi-touch

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 195
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications (53010KXA) Specifications (53013YDR)

Button/Port ● Touch button + power ● Touch button + power


switch and volume button switch and volume button
● 3.5 mm stereo headphones ● 3.5 mm stereo headset
port jack, LRGM pinout order
● Micro SD card port ● Type-C, supporting USB 2.0
● Micro USB port

7.3.6 Smart Screen


The smart screen allows wireless and wired access to the data center management
system. You can monitor the equipment in the data center and environmental
parameters in real time over the app.

Figure 7-22 Appearance

(1) Camera (2) Power port (3) Power button (4) RJ45 port

(5) HDMI port (6) AUDIO-OUT (7) USB-OTG/USB (8) SIM card slot

(9) TP card slot (10) Infrared sensor (11) Indicator (12) Remote control
receiver

(13) Built-in
microphone

Table 7-22 Structural specifications

Item Specifications

Dimensions (H x W x 602 mm x 1010 mm x 60 mm


D)

Weight 27 kg

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 196
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Table 7-23 Technical specifications


Item Specifications

Touchscreen 43-inch, 1920 x 1080 resolution, multi-touch

Storage ● Body: 32 GB
● Memory: 4 GB
● Expansion card: TF card, up to 128 GB (non-standard
configuration)

Button/Port ● Touch key + physical power button + remote control


● Rated AC input voltage range: 100–240 V AC; AC
input current: < 5 A
● Network port: FE communication
● Output ports: one HDMI 1.4 A port (reserved), two
USB 2.0 ports, and one audio output (reserved)

Function ● Built-in camera, supporting facial recognition, 2.8


megapixels
● Touchless wakeup by an infrared sensor

7.3.7 4G Antenna
Figure 7-23 4G antenna

Table 7-24 Technical specifications of the 4G antenna


Item Specifications

Frequency 698–960 MHz/1710–2700 MHz


range

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 197
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Voltage < 2.2


standing wave
ratio

Input 50 Ω
impedance

Gain ≥ 1.0 dBi (698–960 MHz)


≥ 2.0 dBi (1710–2700 MHz)

Polarization Vertical

Maximum 10 W
power

Connector SMA-J

7.3.8 RF_Z Antenna

Figure 7-24 RF_Z antenna

Table 7-25 Technical specifications of the RF_Z antenna

Item Specifications

Frequency 2400–2500 MHz


range

Voltage < 2.5


standing wave
ratio

Input 50 Ω
impedance

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 198
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Gain ≥ 3 dBi

Polarization Vertical

Maximum 10 W
power

Connector RP-SMA-J

7.3.9 WiFi Module


A WiFi module can be installed at the USB port on the main control module
(02312QAA or 02312QAA-001) to provide WiFi signals for devices such as the PAD
to exchange data with the ECC800-Pro.

Figure 7-25 WiFi module

Table 7-26 Technical specifications of a WiFi module

Item Specifications

Wireless IEEE 802.11n, IEEE 802.11g, and IEEE 802.11b


standard

Frequency band 2.4–2.4835 GHz

Wireless 20 dBm (MAX EIRP)


transmission
power

Port USB 2.0 Hi-Speed connector

Voltage range 5.0 V DC±5%

Operating –20°C to +70°C


temperature

Storage –40°C to +90°C


temperature

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 199
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Relative 10%–90% RH (non-condensing)


humidity

Storage 5%–90% RH (non-condensing)


humidity

Power < 0.8 W

Maximum 3
number of
connected
devices

7.3.10 WLAN Antenna


A WLAN antenna can be connected only to the WLAN port on the main control
module (02312QAA-004) to provide WiFi signals for devices such as the PAD to
exchange data with the ECC800-Pro.

Figure 7-26 WLAN antenna

Table 7-27 Technical specifications of the WLAN antenna

Item Specifications

Frequency 2400–2500 MHz


range

Voltage < 2.5


standing wave
ratio

Input 50 Ω
impedance

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 200
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Gain ≥ 3 dBi

Polarization Vertical

Maximum 10 W
power

Connector RP-SMA-J

Maximum 3
number of
connected
devices

7.3.11 Environment Monitoring System

7.3.11.1 WLDS900 Water Sensor


The WLDS900 water sensor monitors water leakage in the equipment room and
generates alarms.

The WLDS900 water sensor with the BOM number of 33010352 consists of a
water detection cable, a water detector, and a conversion cable.

Figure 7-27 WLDS900 water sensor

(1) Water detector (2) Conversion cable end A, connected to (3) Conversion cable
the water detector

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 201
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

(4) Conversion cable (5) Water detection cable end A, (6) Water detection cable
end B, connected to the connected to the conversion cable
water detection cable

Table 7-28 Technical specifications of the WLDS900 water sensor

Item Specifications

Operating 12 V DC (9–16 V DC)


voltage

Operating –20°C to +70°C


temperature

Storage –40°C to +85°C


temperature

Humidity 10%–80% RH (non-condensing)

7.3.11.2 Cabinet Temperature Sensor


The cabinet temperature sensor monitors the cabinet temperature.

Figure 7-28 Cabinet temperature sensor

Table 7-29 Technical specifications of a cabinet temperature sensor

Item Specifications

Temperature detection –20°C to +70°C


range

Temperature detection ● ±1°C (≥ –10°C, < 25°C) & (> 25°C, ≤ 55°C)
tolerance ● ±2°C (≥ –20°C, < –10°C) & (> +55°C, ≤ +70°C)
● ±0.5°C (25°C)

Operating temperature –20°C to +70°C

Operating humidity 5%–95% RH

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 202
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Storage temperature –40°C to +70°C

Storage humidity ≤ 95% RH, non-condensing

7.3.11.3 T/H Sensor


The temperature and humidity sensor (T/H sensors) monitors the temperature
and humidity of the cabinet.

Figure 7-29 Appearance

(1) RS485-OUT (2) RS485-IN (3) DIP switch (4) Button

(5) NTC1–3 (6) NTC4–6 (7) Display -

Table 7-30 T/H sensor specifications

Item Specifications

Temperature measuring range –20°C to +70°C

Temperature precision ±1°C

Humidity measuring range 5%–95% RH

Humidity precision ±5% RH (25°C, 20%–80% RH)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 203
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Operating temperature –20°C to +70°C

Operating voltage 9–16 V DC

Storage temperature –40°C to +70°C

Output RS485

7.3.11.4 Ambient T/H Sensor


The ambient T/H sensor is installed at the remote end of the smart cooling
product to monitor the ambient temperature and humidity.

Figure 7-30 Appearance

The T/H sensor uses an RJ45 connector.

NOTE

The appearance of the T/H sensor delivered onsite may vary.

Figure 7-31 Pins of an RJ45 connector

Table 7-31 RJ45 port pin definitions

Pin Description

Pin 1 or Pin 4 A

Pin 2 or Pin 5 B

Pin 3 V+

Pin 6 or Pin 8 V–

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 204
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Pin Description

Pin 7 Disconnected

Table 7-32 T/H sensor specifications


Item Specifications

Temperature measuring range –20°C to +70°C

Temperature precision ±1°C

Humidity measuring range 5%–95% RH

Humidity precision ±5% RH (25°C, 20%–80% RH)

Operating temperature –20°C to +70°C

Operating voltage 9–16 V DC

Storage temperature –40°C to +70°C

Output RS485

7.3.11.5 Multi-Functional Sensor


A multi-functional sensor detects and monitors the temperature, humidity, smoke,
and infrared, and supports connection to the ECC800-Pro over FE or wireless
communication.

NOTE

The infrared detection function is enabled only when the intelligent lighting function is
enabled.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 205
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Figure 7-32 Multi-functional sensor

(1) Address DIP switch (2) BLINK button (3) TEST button

(4) RF_Z indicator (5) RUN indicator (6) ALM indicator

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 206
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Figure 7-33 Multi-functional sensor (33010680)

(1) Address DIP switch (2) BLINK button (3) TEST button

(4) ALM indicator (5) RUN indicator (6) RF_Z indicator

Specifications

Table 7-33 Multi-functional sensor technical specifications

Item Specifications (33010477) Specifications (33010680)

Temperature –40°C to +70°C. Precision ≤ –20°C to +70°C, precision ≤ ±1°C


monitoring ±0.5°C (25°C). (0°C to 60°C, precision ≤ ±0.5°C
@ 25°C)

Humidity 0 to 100% RH (non- 0 to 100% RH (non-condensing).


monitoring condensing). Precision ≤ ±5% Precision ≤ ±5% RH (25°C, 20%–
RH (25°C, 20%–80% RH) 80% RH)

Smoke Complies with UL217. The Complies with GB 4715-2005.


monitoring smoke sensor generates an
alarm when detecting 3.2%
weak dust per foot.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 207
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications (33010477) Specifications (33010680)

PoE port One PoE port that complies One PoE port that complies with
with IEEE 802.3at IEEE 802.3at

RS485 port One RS485 port is reserved. One RS485 port reserved,
supporting 12 V DC power input

DI input One DI input port, 12 V DC -


power input

BLINK Wireless communication: Wireless communication:


button ● If the sensor is not ● If the sensor is not connected
connected to the network, to the network, hold down
hold down the button for the button for 2s to 3s to
2s to 3s to connect the connect the sensor to the
sensor to the network in network in RF_Z mode.
RF_Z mode. ● If the sensor is connected to
● If the sensor is connected the network, hold down the
to the network, hold button for 1s, and the RUN
down the button for 2s to indicator blinks.
3s, and the RUN indicator ● Hold down the button for
blinks. more than 6s to clear
● Hold down the button for network parameters.
more than 6 seconds to
clear network parameters.

TEST button Supports the smoke sensor Supports the smoke sensor test.
(for testing test. Hold down the button for 3s to
the smoke Hold down the button for 3s trigger a smoke alarm, and
detection) to trigger a smoke alarm, release the button to stop the
and release the button to smoke alarm.
stop the smoke alarm.

E-label Supported Supported

Certification CE, safety CE, safety

Indicators

Table 7-34 Indicators on the multi-functional sensor

Indica Color Name Status Status Description


tors

RUN Green Module Blinking at The device successfully


running long registers with the ECC800-
indicator intervals Pro and the software runs
properly (the indicator blinks
at 0.5 Hz, on for 1s and then
off for 1s).

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 208
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Indica Color Name Status Status Description


tors

Blinking at The device fails to register


short with the ECC800-Pro or the
intervals communication is
disconnected (the indicator
blinks at 4 Hz, on for 0.125s
and then off for 0.125s).

Blinking The indicator blinks at super


short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 10s.

ALM Red Alarm Steady on A system failure alarm is


indicator generated.

Off No system alarm is


generated.

Blinking The indicator is initialized


when the device is powered
on or reset.

RF_Z Green Communicat Steady on No network parameters


ion indicator exist, or a network is to be
created.

Blinking at The device has been


long connected to the network
intervals and the communication is
normal (the indicator binks
at 0.5 Hz, on for 1s and then
off for 1s).

Blinking The device is searching for a


intermittentl network (the indicator blinks
y at super at super short intervals for
short 0.5s and then turns off for
intervals 0.5s).

7.3.11.6 Alarm Beacon


When a fire occurs or smokes are generated in the micro-modular equipment
room, the alarm beacon generates an audible signal and flashes to inform
operators of fire and security risks.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 209
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Figure 7-34 Alarm beacon

Table 7-35 Structural specifications of an alarm beacon

Item Specifications

Dimensions (L x W x 124.6 mm x 73 mm x 48 mm
H)

Installation Mounting supported


requirements

Environmental RoHS, Reach


protection

Table 7-36 Technical specifications of an alarm beacon

Item Specifications

Power input RJ45 port; input voltage: 10–15 V DC; operating current:
≤ 300 mA

Sound pressure ≥ 108 dB/30 cm

Continuous operating ≥ 40 min


time

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 210
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

7.3.11.7 Smoke Sensor


Smoke sensors are used to detect the smoke concentration.

Figure 7-35 Smoke sensor

Table 7-37 Technical specifications of a smoke sensor


Item Specifications

Operating voltage 12 V DC (9–16 V DC)

Quiescent current < 8 mA

Alarm current < 35 mA

Output mode Relay output

Output contact capacity 3 A/120 V AC or 3 A/24 V AC

Operating temperature –10ºC to +50ºC

Ambient humidity < 95% RH (non-condensing)

Dimensions Diameter: 112 mm, height: 41 mm

7.3.12 Access Control System

7.3.12.1 Access Actuator


The access actuator is the control component for the aisle door in a smart module.
It connects to the ECC800-Pro controller over FE port, wireless networking
(802.15.4). It opens the magnetic lock by detecting the card swiping information
of the card reader, door open button information, and fire linkage information. It
has access right management, access event record, and alarm record functions.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 211
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Figure 7-36 Access actuator

(1) 48 V power port (2) PoE port (3) RS485 port COM2

(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator

(7) BLINK button (8) WG_2 Wiegand interface (9) WG_1 Wiegand interface

(10) AI/DI_2 dry contact (11) AI/DI_1 dry contact (12) LOCK/GND/GATE/COM door
(reserved port for linkage (reserved port for exit status sensor and magnetic lock
control or third-party fire button) port
extinguishing system dry
contacts)

Specifications

Table 7-38 Access actuator technical specifications


Item Specifications

Power input ● DC input: terminal, with an input voltage of 36 V DC–60 V DC


● PoE power supply: one PoE port that complies with
IEEE802.3at

PoE port FE communication with the rate of 10/100 Mbit/s

Wireless One wireless communication port that complies with IEEE


communicat 802.15.4, mutual backup with FE communication
ion

AI/DI port Two AI/DI ports, can connect to the fire alarm and exit button

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 212
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

DO/DI port ● One 12 V DC power output that controls magnetic locks,


terminal
● One DI input port for connecting to the door status switch

RS485 serial Two RS485 ports (one route) with the default communication
port rate of 9600 bit/s, physical port cascading supported (reserved
expansion function)

Wiegand Two Wiegand ports, 12 V DC card reader operating power output;


port two routes of card readers can operate at the same time.

BLINK ● Press the button for less than 1 second to start blinking.
button ● Hold down the button for 1–5 seconds to search for a network
and start networking.
● Hold down the button for more than 10 seconds to clear
network parameters.

Address DIP 4-pin address DIP switch


switch

E-label Supported

Indicators

Table 7-39 Access actuator indicators


Indicator Color Name Status Description

PWR Green Power input status ● Steady on: The


indicator power input is
normal.
● Off: There is no
power input.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 213
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Indicator Color Name Status Description

RUN Green Communication ● Off: The power is


status indicator abnormal or the
board program is
loading.
● Blinking at long
intervals: The access
actuator
successfully registers
with the ECC800-
Pro and the
software runs
properly (the
indicator blinks at
0.5 Hz, on for 1s
and then off for 1s).
● Blinking at short
intervals: The
communication fails
or the access
actuator fails to
register with the
ECC800-Pro (the
indicator blinks at 4
Hz, on for 0.125s
and then off for
0.125s).
● Blinking: The
indicator blinks at
super short intervals
for 0.5s (blinking at
10 Hz, on for 0.05s
and then off for
0.05s) and then
turns off for 0.5s.
The cycle lasts for
5s.

ALM Red Alarm indicator ● Steady on: A system


failure alarm is
generated.
● Off: No system
alarm is generated.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 214
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Indicator Color Name Status Description

RF_Z Green Wireless ● Steady on: No


communication network parameters
status indicator exist, or a network
is to be created.
● Blinking at long
intervals: A network
is set up, and no
node access is
allowed (the
indicator blinks at
0.5 Hz, on for 1s
and then off for 1s).
● Blinking
intermittently at
super short
intervals: The access
actuator is
searching for a
network (the
indicator blinks at
super short intervals
for 0.5s and then
turns off for 0.5s).

Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/
COM). Table 7-40 lists the LOCK/GND/GATE/COM port pin definitions.

Table 7-40 LOCK/GND/GATE/COM port pin definitions


Item Description

LOCK/GND LOCK 12V_OUT


(control
magnetic GND GND
locks) pin
sequence

GATE/COM GATE DI1


(door
status) pin COM COM
sequence

7.3.12.2 Automatic Door Status Sensor


An automatic door status sensor can be installed on the automatic door of a
smart module to check whether people outside the aisle door are close to the

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 215
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

door. When a person enters the detection range of the sensor, the sensor supplies
a feedback signal to the access actuator or ECC, which will open the aisle door of
the smart module.

Figure 7-37 Automatic door status sensor

Table 7-41 Technical specifications of the automatic door status sensor


Item Specifications

Operating voltage 9–16 V DC, power < 2 W

Detection mode Motion

Detection range (W x D) ±0.6 m x 1 m

Dimensions 120 mm x 80 mm x 56 mm

7.3.12.3 Fingerprint and Card Reader with a Keypad

Figure 7-38 Fingerprint and card reader with a keypad

(1) Fingerprint reader (2) LED indicator

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 216
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Table 7-42 Technical specifications of a fingerprint and card reader with a keypad
Item Specifications

Dimensions (L x W x H) 156 mm x 53 mm x 38 mm

Rated operating voltage 12 V DC±15%

Rated operating current 300 mA±15%

Card type supported IC card

Authorized storage A maximum of 3000 authorized users, with a


maximum of 6000 fingerprints

Communications mode RS485 and Wiegand communications ports

Table 7-43 Access control device operating status


Item Status Description

Standby LED indicator The indicator is steady


blue.

Fingerprint reader The indicator is off.

Unauthorized fingerprint LED indicator The indicator blinks blue,


collection red, blue, red, and blue
in order.

Fingerprint reader The indicator turns on


(white).

Buzzer sounds The buzzer sounds three.

Authorized fingerprint LED indicator The indicator blinks blue,


collection red, and blue in order.

Fingerprint reader The indicator turns on


(white).

Buzzer sounds The buzzer sounds once.

Card swiping LED indicator The indicator blinks blue,


red, and blue in order.

Buzzer sounds The buzzer sounds once.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 217
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

7.3.12.4 Fingerprint and Card Reader

Figure 7-39 Fingerprint and card reader

(1) Fingerprint reader (2) LED indicator

Table 7-44 Technical specifications of a fingerprint and card reader

Item Specifications

Dimensions (L x W x H) 156 mm x 53 mm x 38 mm

Rated operating voltage 12 V DC±5%

Rated operating current 300 mA±5%

Card type supported IC card

Authorized storage A maximum of 3000 authorized users, with a


maximum of 6000 fingerprints

Communications mode RS485 and Wiegand communications ports

Table 7-45 Access control device operating status

Item Status Description

Standby LED indicator The indicator is steady


blue.

Fingerprint reader The indicator is off.

Unauthorized fingerprint LED indicator The indicator blinks blue,


collection red, blue, red, and blue
in order.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 218
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Status Description

Fingerprint reader The indicator turns on


(white).

Buzzer sounds The buzzer sounds three.

Authorized fingerprint LED indicator The indicator blinks blue,


collection red, and blue in order.

Fingerprint reader The indicator turns on


(white).

Buzzer sounds The buzzer sounds once.

Card swiping LED indicator The indicator blinks blue,


red, and blue in order.

Buzzer sounds The buzzer sounds once.

7.3.12.5 Card Reader with a Keypad

Figure 7-40 Card reader with a keypad

Table 7-46 Technical specifications of a card reader with a keypad


Item Specifications

Dimensions (L x W x H) 114 mm x 63 mm x 25 mm

Operating voltage Operating voltage range: 10.8–13.2 V DC; rated


voltage: 12 V DC

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 219
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Operating current Static standby current: 80 mA; dynamic operating


current (card swiping, key pressing): 150 mA;
minimum input current: 12 V DC/300 mA

Communication mode Wiegand communications port

7.3.12.6 Cabinet Fingerprint and Card Lock

Figure 7-41 Cabinet fingerprint and card lock

Table 7-47 Technical specifications of the cabinet fingerprint and card lock
Item Specifications

Lock body dimensions (L x 234 mm x 44.1 mm x 36.8 mm±5%


W x H)

Hole dimensions (W x H) 24 mm x 145 mm

Net weight of the lock 696 g±5% (excluding bolts and washers)
body

Color Black

Rated operating voltage 12 V DC

Operating current ≤ 250 mA in static standby mode; ≤ 400 mA in


dynamic electric control unlocking mode

Card type supported Standard configuration: Mifare1 card and CPU card

Unlock mode Card, fingerprint, fingerprint + card, remote


command, and mechanical key

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 220
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Fingerprint capacity Standard configuration: 500; Huawei model: 1500;


customization: more

Authorized users 500 (customization: > 1000)

Fingerprint sensor type Capacitive, 3D live fingerprint recognition

Communication mode RS485 communications port

Indicator LED and buzzer

7.3.12.7 Magnetic Lock

Figure 7-42 Double-door magnetic lock

Figure 7-43 Single-door magnetic lock

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 221
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Figure 7-44 Sliding-door magnetic lock

(1) Magnetic lock fastener (2) Magnetic lock

(3) Magnet (4) Magnet fastener

7.3.12.8 Cabinet Electronic Lock


The cabinet electronic lock applies to cabinets in the aisle containment to ensure
data and device security.

Figure 7-45 Cabinet electronic lock

Table 7-48 Cabinet electronic lock specifications

Item Specifications

Rated input voltage 12 V DC

Rated current 200–300 mA

Unlock mode Power on to unlock

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 222
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Card type supported IC card

Mechanically unlock Supported

Features:

● An IC card can be used after being authorized using software.


● An IC card can be authorized for one lock or all locks.
● Door opening information is recorded through a network.
● The system displays the status of cabinet doors and locks in real time, and
generates alarms for unauthorized door opening.
● The system supports remote door opening.

7.3.12.9 Cabinet Door Status Sensor

Figure 7-46 Door status switch

Table 7-49 Technical specifications of the door status switch

Item Specifications

Connection method Using wiring terminals

Rated current 500 mA

Opening distance 25 mm ≤ Opening distance ≤ 45 mm

Rated power 10 W

Securing mode Using screws

Distance between mounting holes 40 mm ±0.8 mm

Open-circuit voltage 100 V DC (maximum)

Contact withstand voltage 150 V DC (maximum)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 223
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Impedance 0.3 ohm

Switch status Normally open

Outer material White acrylonitrile butadiene styrene


(ABS) engineering plastic

7.3.13 Video Surveillance System


The video surveillance subsystem consists of the camera and network video
recorder and implements real-time monitoring, video storage, and video playback.

7.3.13.1 Camera
The C3220 camera is a two-megapixel infrared zoom dome camera that can be
ceiling-mounted.

Figure 7-47 C3220 camera

Table 7-50 C3220 camera technical specifications

Item Specifications

Image sensor 1/2.7" 2-megapixel progressive scan CMOS

Minimum illumination ● Color: 0.002 lux (F1.2, AGC ON, 1/30s shutter
speed)
● Black/White: 0.0005 lux (F1.2, AGC ON, 1/30s
shutter speed)
0 lux (IR illuminator enabled)

Wide dynamic range 120 dB

Focal length 2.8–12 mm

Video compression H.265/H.264/MJPEG


standard

Maximum resolution 1920x1080

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 224
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications

Power supply 12 V DC, PoE

IP rating IP67

Vandal resistant rating IK10

7.3.13.2 IVS1800

Figure 7-48 Appearance

Table 7-51 Performance specifications


Categ Item IVS1800-D08 IVS1800-B08 IVS1800-C08-04T IVS1800-C08-04T
ory (64CH) (64CH) (16CH) (64CH)

Devic Networ 64-channel 1080p, 64-channel 16-channel 64-channel


e k video up to 320 Mbit/s 1080p, up to 320 1080p, up to 160 1080p, up to 320
perfor inputs access bandwidth Mbit/s access Mbit/s access Mbit/s access
manc Up to 160 Mbit/s bandwidth bandwidth bandwidth
e access bandwidth Up to 160 Mbit/s Up to 160 Mbit/s
with intelligent access bandwidth access bandwidth
services enabled with intelligent with intelligent
services enabled services enabled

Video 64-channel 1080p, 64-channel 16-channel 64-channel


transfer up to 320 Mbit/s 1080p, up to 320 1080p, up to 160 1080p, up to 320
forwarding Mbit/s forwarding Mbit/s forwarding Mbit/s forwarding
bandwidth bandwidth bandwidth bandwidth
Up to 160 Mbit/s Up to 160 Mbit/s Up to 160 Mbit/s
forwarding forwarding forwarding
bandwidth with bandwidth with bandwidth with
intelligent services intelligent intelligent
enabled services enabled services enabled

Playbac 32-channel 1080p, 32-channel 16-channel 32-channel


k/ up to 160 Mbit/s 1080p, up to 160 1080p, up to 80 1080p, up to 160
Downlo playback Mbit/s playback Mbit/s playback Mbit/s playback
ad bandwidth bandwidth bandwidth bandwidth

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 225
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Categ Item IVS1800-D08 IVS1800-B08 IVS1800-C08-04T IVS1800-C08-04T


ory (64CH) (64CH) (16CH) (64CH)

Platfo IP 64 cameras to one 64 cameras to 16 cameras to 64 cameras to


rm camera IVS1800 one IVS1800 one IVS1800 one IVS1800
perfor s
manc connect
e ed

Table 7-52 Hardware specifications


Categ Item IVS1800-D08 (64CH) IVS1800-B08 (64CH) IVS1800-C08-04T
ory Specifications Specifications (16CH/64CH)
Specifications

Storag Hard disk 8 8 8


e quantity
capacit
y Hard disk SATA3.0 SATA3.0 SATA3.0
port

Hard disk Enterprise-level disks: 4 Enterprise-level disks: Enterprise-level disks: 4


type TB, 6 TB, 8 TB, or 16 4 TB or 6 TB TB, 6 TB, 8 TB, or 10 TB
TB Monitoring-level disks: Monitoring-level disks:
Monitoring-level disks: 4 TB or 6 TB 4 TB or 6 TB
6 TB or 8 TB

Contro Processor Hi3536A Hi3536 Hi3559A


ller
Memory 32 GB eMMC 3 GB (DDR3) 8 GB (DDR4)

Extern Network 2 x 1000M Ethernet Two 10/100/1000 Two 10/100/1000


al port port Mbit/s Ethernet ports Mbit/s Ethernet ports
ports
USB ports Front: 2 x USB 2.0 3 x USB port (one USB Three USB ports (two
Rear: 1 x USB 3.0 2.0 port on the front USB 2.0 ports on the
panel, and one USB front panel and one
2.0 port and one USB USB 3.0 port on the
3.0 port on the rear rear panel)
panel)

Audio input 1 channel, RCA port 1 channel, RCA port 1 channel, RCA port

Audio 1 channel, RCA port 1 channel, RCA port 1 channel, RCA port
output

Alarm port 16-channel Boolean 4-channel alarm input, 4-channel alarm input,
value input and 4- 2-channel alarm 2-channel alarm
channel Boolean value output output
output

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 226
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Categ Item IVS1800-D08 (64CH) IVS1800-B08 (64CH) IVS1800-C08-04T


ory Specifications Specifications (16CH/64CH)
Specifications

Other Power 124 W 98 W 124 W


specifi consumptio
cations n (8 hard
disks
included)

Power 100–240 V AC; 200 W 100–240 V AC; 200 W 110–220 V AC; 200 W
supply

Weight 6.60 kg 6.70 kg 6.60 kg


(hard disks
excluded)

Dimensions 447 mm x 470 mm x 440 mm x 460 mm x 442 mm x 467 mm x


(W x D x 86.1 mm 89 mm 86 mm
H)

NOTICE

When the room temperature of the IVS1800-B08 is poor, an overheat alarm may
be generated when the IVS1800-B08 is fully configured with eight 6 TB hard disks.
You are advised to install a maximum of four 6 TB hard disks at different layers.

7.3.14 Aisle Light


LED lights are used for lighting in an aisle. The lights are installed on the top at
the two sides of the aisle.

Figure 7-49 LED light (600 mm)

Figure 7-50 LED light (1200 mm)

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 227
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Table 7-53 LED light technical specifications


Item Specifications (600 Specifications (1200 mm)
mm)

Installation Ceiling-mounted Ceiling-mounted


mode

Light base The light base and light The light base and light are
requirement are integrated. integrated.

IP rating ≥ IP20 ≥ IP20

Electrical CLASS I -
insulation
class

Standards IEC 60598 IEC 60598, CCC certification


compliance

Rated 220–240 V AC 220–240 V AC


operating
voltage

Light color Pure white Pure white

Luminous flux Each AC light: ≥ 800 lm Each AC light: ≥ 1200 lm

Rated power < 12 W < 16 W

7.3.15 eLight
● The eLight BOM number is 52220928 if an end door with a smart screen
(21502418) or an end door without a smart screen is installed. The eLight
system consists of the eLight power system, eLight actuator, eLight strip light,
and cables.
● The eLight BOM number is 52221774 if an end door with a smart screen
(21503054) is installed. The eLight system consists of the eLight actuator,
eLight strip light, and cables.

Figure 7-51 eLight strip light

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 228
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Figure 7-52 eLight actuator (52220928)

Figure 7-53 eLight actuator (52221774)

NOTE

The appearance of the eLight actuator depends on the actual delivery.

Table 7-54 Description of the eLight strip light colors

Scenario Light Color Remarks

Non-associated Blue -
alarm severity NOTE
On the ECC800-Pro WebUI, set
Associated Alarm Severity to None.

Associated alarm Mapping between smart module Critical and major


severity alarm severities and strip light alarms are
colors: associated by
● Critical: red default. Alarms of
any severity can be
● Major: orange associated manually.
● Minor: yellow Alarms are
● Warning: white gray associated with the
eLight on both ends.
● No alarm: strip light off If associated alarms
at multiple severities
appear, the strip light
color indicates only
the highest alarm
severity.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 229
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Scenario Light Color Remarks

eLight fault The eLight disconnects from the -


ECC800-Pro and blinks in red.

Table 7-55 eLight technical specifications


Item Specifications

eLight power supply ● Rated input voltage: 220/230/240 V AC


NOTE ● Frequency: 50/60 Hz
If the eLight BOM
number is 52221774, ● Output: ≥ 93 W, 24 V DC
the eLight actuator ● Certification: CE
contains the eLight
power supply.

eLight actuator ● Rated input voltage: 24 V DC


● Two output channels. The I output is connected to
the RGBW flexible strip light, and supplies different
voltages depending on host instructions so that the
light can be in different colors. The II output
supplies a fixed voltage of 24 V DC.
● Modbus communications protocol, RS485 port, two
RJ45 ports
● Certification: CE

eLight strip light ● Rated input voltage: 24 V DC


● Light type: RGBW LED strip light, in different colors
depending on instructions
● Power: RGB fully on under the maximum working
condition, power P ≤ 12 W/m
● Installation mode: snap-fit in a sheet metal light slot
● Certification: CE

IP rating ≥ IP20

Environment ● Operating temperature range: 4°C to 40°C


● Humidity range: 5%–95% RH, non-condensing

7.3.16 Atmosphere Light


The atmosphere light is installed at the bottom of the cabinet in the aisle, creating
a relaxing atmosphere in the smart module.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 230
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Table 7-56 Technical specifications

Item Specifications

Lighting Blue LED strip light

Rated voltage PSU: 230 V AC input


LED strip light: 24 V DC

Voltage range 176–264 V AC

IP rating IP68

Operating environment Indoor temperature: 30°C; operating


temperature: 0°C to 40°C; humidity: 5%–95%
RH (non-condensing); altitude: 4000 m

7.3.17 (Optional) Smart U Space Manager


The smart U space manager is designed for IT asset management of the data
center. The system automatically detects the physical location of IT devices in the
data center, and collects IT asset codes and the information about U space usage.

Figure 7-54 Smart U space manager

(1) Asset detection strip (2) U space e-label

Table 7-57 Technical specifications of the smart U space manager

Item Specifications Specifications (52276710)


(52275819)

Characteristic Applicable to 42 U Applicable to 47 U cabinets


cabinets

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 231
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

Item Specifications Specifications (52276710)


(52275819)

Communications RS485, Modbus-RTU


port

Communication Rate: 9600 bit/s


Communication format: one start bit, eight data bits, no
parity bit, one stop bit
Rate: 9600 bit/s

Power input Typical input voltage: 12 V; wide input range: 9–15 V DC

Rated current and 90 mA 100 mA


power

Data upload port One RS485 port. A maximum of four RS485 ports can be
connected to the UIM20A expansion module. A
maximum of one RS485 port can be connected to the
intelligent rPDU. Direct connection to the ECC800-Pro is
not supported.

Dimensions Detection strip: 1867 mm Detection strip: 2089 mm x


x 18 mm x 6.5 mm (H x W 18 mm x 6.5 mm (H x W x
x D) D)

Weight ≤ 0.5 kg ≤ 0.51 kg

Installation mode Magnet-based installation

7.4 NetEco

7.4.1 System Description


With a flexible structure and modular design, the NetEco can manage facilities of
a single smart module or centrally manage facilities of smart modules in different
regions.

The management system provides a graphical user interface (GUI) to implement


comprehensive management functions based on requirements. The system mainly
monitors the following equipment:

● Power equipment: in-room smart cooling product, PDF, UPS, and so on


● Environment equipment: water sensor, T/H sensor, and so on
● Video equipment: camera, and so on
● Access control equipment: A standard access management system is
integrated to manage and monitor key information such as door status, card
swiping, and permission setting.
● Standard network management interface: The NetEco provides SNMP
interfaces to communicate with third-party network management systems

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 232
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

(NMSs). The system can be customized to support other protocols for the
access from different devices.

Figure 7-55 Networking diagram

7.4.2 Hardware Description

7.4.2.1 Server
The NetEco can be deployed on one of the following servers according to the
management capability requirement.

Table 7-58 Servers

Model Configuration

TaiShan 200 (Model 2280) 2 x Kunpeng 920 [email protected] GHz, 4 x 32


standard configuration GB memory, 2 x 1.2 TB + 8 x 1.8 TB drives

TaiShan 200 (Model 2180) basic 1 x Kunpeng 920 [email protected] GHz, 2 x 32


configuration GB memory, 2 x 1.2 TB drives

2288X V5-H22X-standard 2 x 5218 [email protected] GHz CPU, 4 x 32 GB


configuration memory, 2 x 1.2 TB + 8 x 1.8 TB SAS drives

2288X V5-H22X-basic 2 x 4208 [email protected] GHz CPU, 2 x 32 GB


configuration memory, 2 x 1.2 TB SAS drives

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 233
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System

7.4.2.2 LAN Switch


Select LAN switches based on site requirements.

Table 7-59 LAN switch


Model Maximum Number of Ports

S5331-H24P4XC Twenty-four 10/100/1000BASE-T Ethernet ports, four


10GE SFP+ ports

S5731-H24P4XC Twenty-four 10/100/1000BASE-T Ethernet ports, four


10GE SFP+ ports

7.5 iManager-M
The iManager-M system monitors the status of the entire network on the GIS
home page. After an abnormal site is detected, you can double-click it to access
the site monitoring page. Information about environment, energy consumption,
key devices, alarm, and security monitoring is provided on the site monitoring
page without requiring additional hardware.
● Environment monitoring: Monitors the temperature, humidity, water, and
smoke.
● Key device monitoring: Monitors the UPS, air conditioners, and related power
distribution devices in real time, and displays the energy flow diagram and air
conditioner link diagram.
● Alarm monitoring: Displays site alarm information in real time and quickly
locates device faults.
● Security monitoring: Monitors the cabinet door status and cameras in sites.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 234
FusionModule2000 6.0 Smart Modular Data Center
Product Description 8 Surge Protection and Grounding System

8 Surge Protection and Grounding System

The surge protection and grounding system consists of the surge protection
solution and grounding solution.

Surge Protection Solution


SPDs are installed upstream of the target equipment. The conducting wires to
each SPD are short (within 0.15 m) and straight. The SPD wires are copper wires
with a minimum cross-sectional area of 10 mm2, and the ground cables to SPDs
are copper cables with a minimum cross-sectional area of 16 mm2.

M-shaped (Grid) Grounding Solution

Figure 8-1 M-shaped (grid) grounding solution for a dual-row aisle containment

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 235
FusionModule2000 6.0 Smart Modular Data Center
Product Description 8 Surge Protection and Grounding System

1. Each cabinet in the smart module connects to the nearest ground grid using
ground cables with the minimum cross-sectional area of 16 mm2.
2. Use 100 x 0.3 copper foils or copper braids with a cross-sectional area of 25
mm2 for the equipotential bonding grid. Use 30 x 3 copper strips for the
equipotential bonding bar based on the customer's configurations.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 236
FusionModule2000 6.0 Smart Modular Data Center
Product Description 9 Integrated Cabling System

9 Integrated Cabling System

The integrated cabling system of the smart module includes cable routing devices
and cables.

Cable Troughs
Cable troughs are installed on the top of cabinets for routing cables. There are
two types of cable troughs: signal cable troughs and power cable troughs.
If a dual-row aisle containment is equipped with one PDF and one network
cabinet, power cables need to be routed to the other end of the module through
the control skylight on the top of the PDF while signal cables need to be routed to
the other end of the module through the control skylight on the top of the
network cabinet.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 237
FusionModule2000 6.0 Smart Modular Data Center
Product Description 9 Integrated Cabling System

Figure 9-1 Cable routes through cable troughs

(1) Network cabinet (2) Optical fiber cables (3) Signal cables

(4) Smart ETH gateway (5) PDF (6) Power cables

Cables
● The power cables include power cables to the UPS, battery cabinet, smart
cooling product, and rPDU.
● The ground cables include ground cables to the PDF, battery cabinet, and IT
cabinet.
● The monitoring cables include monitoring cables to the smart cooling
product, UPS, and video devices, access control alarm cables, cables in the
network cabinet, and various sensor cables.
● The cables to auxiliary fire control components include cables to the alarm
beacon and FusionModule Actuator.

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 238
FusionModule2000 6.0 Smart Modular Data Center
Product Description A Acronyms and Abbreviations

A Acronyms and Abbreviations

A
AC alternating current
ATS auto transfer switch

B
BCB battery circuit breaker
BIB battery control I/O board
BIM battery interface module
BSPP British Standard Pipe Parallel Thread

C
CAN controller area network
CE Conformité Européenne
CFD computational fluid dynamics
CIM communication interface module

D
DC direct current

E
EC electronic commutation
ECC energy control center
ETH Ethernet

F
FE fast Ethernet

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 239
FusionModule2000 6.0 Smart Modular Data Center
Product Description A Acronyms and Abbreviations

IC integrated circuit
IDC Internet data center
IDS integrated data-center solution
IT Internet technology

L
LCD liquid crystal display
LED light emitting diode

M
MTBF mean time between failures
MTTR mean time to repair

N
NTC negative temperature coefficient

P
PDU power distribution unit
PE protective earthing
POE power over Ethernet
PUE power usage effectiveness

R
RCCB residual current circuit breaker

S
SD Secure Digital Memory
SIM subscriber identity module
SNMP Simple Network Management Protocol
SPD surge protective device

U
USB Universal Serial Bus
UPS uninterruptible power system

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 240
FusionModule2000 6.0 Smart Modular Data Center
Product Description A Acronyms and Abbreviations

V
VCN video cloud node

W
WiFi Wireless Fidelity

Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 241