FusionModule2000 6.0 Smart Modular Data Center Product Descriptio1
FusionModule2000 6.0 Smart Modular Data Center Product Descriptio1
Product Description
Issue 06
Date 2023-11-30
and other Huawei trademarks are the property of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei
Digital Power Technologies Co., Ltd. and the customer. All or part of the products, services and features
described in this document may not be within the purchase scope or the usage scope. Unless otherwise
specified in the contract, all statements, information, and recommendations in this document are
provided "AS IS" without warranties, guarantees or representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Website: https://digitalpower.huawei.com
Purpose
The FusionModule2000 6.0 smart modular data center solution includes smart
modules A and B. This document describes the product positioning, features,
application scenarios, and system architecture of the smart modular data center
(smart module for short) to help you systematically understand the smart module.
Intended Audience
This document is intended for:
● Technical support engineers
● System engineers
● Sales engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Description
Symbol Description
Change History
Issue Date Description
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. iii
FusionModule2000 6.0 Smart Modular Data Center
Product Description Contents
Contents
5.1.2 Power Supply and Distribution System for Smart Module B............................................................................. 39
5.2 Hardware Description.......................................................................................................................................................... 49
5.2.1 Integrated UPS (180 kVA).............................................................................................................................................. 49
5.2.1.1 Product Structure........................................................................................................................................................... 49
5.2.1.2 Technical Specifications............................................................................................................................................... 51
5.2.1.2.1 Physical and Electrical Specifications...................................................................................................................51
5.2.1.2.2 Environmental Specifications................................................................................................................................. 55
5.2.1.2.3 Safety Compliance and EMC Specifications...................................................................................................... 55
5.2.2 Integrated UPS (60 kVA, 125 kVA).............................................................................................................................. 56
5.2.2.1 Product Structure........................................................................................................................................................... 56
5.2.2.2 Technical Specifications............................................................................................................................................... 58
5.2.2.2.1 Physical and Electrical Specifications...................................................................................................................58
5.2.2.2.2 Environmental Specifications................................................................................................................................. 62
5.2.2.2.3 Safety and EMC........................................................................................................................................................... 62
5.2.3 Integrated UPS (30 kVA–180 kVA).............................................................................................................................. 62
5.2.3.1 Product Structure........................................................................................................................................................... 62
5.2.3.2 Technical Specifications............................................................................................................................................... 63
5.2.3.2.1 Physical and Electrical Specifications...................................................................................................................63
5.2.3.2.2 Environmental Specifications................................................................................................................................. 68
5.2.3.2.3 Safety and EMC........................................................................................................................................................... 68
5.2.4 Integrated PDF................................................................................................................................................................... 70
5.2.5 Precision PDF...................................................................................................................................................................... 73
5.2.6 NMW Smart Busbar..........................................................................................................................................................74
5.2.6.1 NMW Smart Busbar 2.1............................................................................................................................................... 75
5.2.6.1.1 General Input Unit..................................................................................................................................................... 75
5.2.6.1.2 Power Distribution Unit............................................................................................................................................ 81
5.2.6.1.3 Busbar Trunking Unit................................................................................................................................................ 85
5.2.6.2 NMW Smart Busbar 2.0............................................................................................................................................... 87
5.2.6.2.1 General Input Unit..................................................................................................................................................... 88
5.2.6.2.2 Power Distribution Unit............................................................................................................................................ 95
5.2.6.2.3 Busbar Trunking Unit................................................................................................................................................ 97
5.2.7 Smart Cooling Product PDB........................................................................................................................................... 98
5.2.8 Battery Cabinet................................................................................................................................................................ 100
5.2.8.1 Lithium Battery Cabinet SmartLi 3.0.....................................................................................................................100
5.2.8.1.1 Product Structure..................................................................................................................................................... 101
5.2.8.1.2 Technical Specifications..........................................................................................................................................101
5.2.8.2 Lead-Acid Battery Cabinet........................................................................................................................................ 105
5.2.9 rPDU.................................................................................................................................................................................... 108
5.2.9.1 Basic rPDU......................................................................................................................................................................108
5.2.9.2 Smart rPDU.................................................................................................................................................................... 109
5.2.9.3 PDU2000M..................................................................................................................................................................... 111
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. vii
FusionModule2000 6.0 Smart Modular Data Center
Product Description Contents
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. viii
FusionModule2000 6.0 Smart Modular Data Center
Product Description 1 Positioning
1 Positioning
2 Features
i3 Intelligent Management
● iPower
– The entire link status of the power supply and distribution system is
displayed in real time, and alarms are intelligently converged and quickly
located.
– Temperature detection (optional) for circuit breaker terminals on power
distribution branches avoids poor connection of branch contacts. In
addition, miniature circuit breakers (MCBs) are hot-swappable and can be
maintained without power-off. This does not affect other branches.
– The smart rPDU (optional) implements socket status monitoring, remote
management, and IT equipment protection.
● iCooling
– The running status of the cooling system is displayed in real time, and
the status of smart cooling products and key components is detected.
– The 3D temperature map (optional) is linked with the cooling system to
eliminate local hotspots, and the load power is linked with the cooling
● Smart module A: The integrated UPS and air conditioner are deployed inside
the smart module. Lead-acid batteries can be deployed either inside or
outside the smart module. Lithium batteries are deployed outside the smart
module.
● Smart module B: The UPS and lead-acid batteries or lithium batteries are
deployed outside the smart module. The power distribution frame (PDF) and
air conditioner are deployed inside the smart module.
NOTE
Devices inside and outside the smart module can be deployed in one room or two rooms. If
they are deployed in one room, the smart module adopts the hot aisle containment design
to ensure that the ambient temperature for batteries meets requirements.
Smart
module
A (lead-
acid
batteries
deployed
inside
the
module)
Smart
module
A (lead-
acid
batteries
or
lithium
batteries
deployed
outside
the
module)
Smart
module
B
(integrat
ed PDF
or
precision
PDF)
Smart
module
B (NMW
smart
busbar)
Smart Integrated 160 A/250 A power input (input circuit breakers for
module B PDF IT equipment and smart cooling products), 48
power distribution routes for IT equipment, 16
power distribution routes for smart cooling
products, 6 power distribution routes (dual inputs)
for lighting or 3 power distribution routes (single
input) for lighting, supporting 95 kW/148.5 kW IT
loads
Typically, overhead cabling and overhead Typically, overhead cabling and underfloor or
piping overhead piping
Figure 3-1 Components of the dual-row 1200 mm wide cold aisle containment
(1) End door (2) Control skylight (3) Flat or rotating skylight
Door opening mode The front door is a single door, and the rear door is a
double one.
IP rating IP20
4.1.2 IT Cabinet
An IT cabinet complies with the International Electrotechnical Commission (IEC)
60297-1 standard and provides stable installation space for servers in the smart
module, thereby ensuring safe operation of servers.
● Two rPDUs can be vertically installed at the rear of each cabinet.
● The position of each U is marked on the vertical mounting bars.
● The front and rear doors of the cabinet can be locked, and can be unlocked
only by using dedicated keys.
● The cabinet supports a door status sensor and electronic access control.
● The maximum static load of the cabinet is 2400 kg.
Door opening The front door is a single door, and the rear door is a
mode double one.
IP rating IP20
Optional cabinet Cable ring, bottom sealing plate, guide rail, tray, side door
accessories panel, and bottom plate
4.2.1 Skylight
Skylights are used for sealing an aisle containment. Skylights are classified as
control skylights, rotating skylights, and flat skylights.
(1) Skylight connective plate (2) Control skylight panel (3) Cable separation panel
NOTE
● Control skylights are installed on both ends of an aisle and used to install monitoring
components such as the camera, multi-functional sensor, and smoke detector.
● If the smart module is longer than 7 m, add one control skylight in the middle of the
smart module for installing a multi-functional sensor or smoke detector.
(1) Magnetic lock fixing base (2) Glass skylight (3) Skylight connective plate
NOTE
● A rotating skylight is designed with an eccentric structure. When the trigger is activated,
a rotating skylight falls under gravity. The rotating skylight is triggered by a magnetic
lock.
● A rotating skylight requires a magnetic lock but a flat skylight does not.
(1) Magnetic lock (2) Glass skylight (3) Removable panel (4) Skylight connective
fixing base plate
NOTE
If smart busbars need to be maintained from the aisle, use a maintainable skylight.
The cables for the door header need to be connected onsite. The cables (BOM
number: 04095459) should be configured separately.
(1) FusionModule Actuator (2) eLight actuator (3) AC/DC power module
NOTE
Sliding doors can be opened only horizontally. Observe the local fire protection regulations
when using the doors.
NOTE
Electric sliding doors can be opened only horizontally. Observe the local fire protection
regulations when using the doors.
NOTE
Sliding doors can be opened only horizontally. Observe the local fire protection regulations
when using the doors.
Name Dimensions (H x W x D)
Name Dimensions (H x W x D)
(1) Side plate (2) Supporting plate (3) Partition plate (4) Position for the
smart ETH gateway
If a smart screen is configured, the PAD obtains power from the L1 layer.
Figure 5-1 N+1 power supply and distribution system (ATS scenario)
Figure 5-2 N+1 power supply and distribution system (MCCB scenario)
Figure 5-3 N+1 power supply and distribution system (integrated UPS for
continuous cooling)
Figure 5-4 N+1 power supply and distribution system (integrated UPS for
continuous cooling)
Figure 5-6 2N power supply and distribution system (integrated UPS for
continuous cooling)
If a smart screen is configured, the PAD obtains power from the L1 layer.
Figure 5-7 N+1 power supply and distribution system (integrated PDF)
Figure 5-8 N+1 power supply and distribution system (precision PDF scenario)
Figure 5-9 N+1 power supply and distribution system (smart busbar scenario)
Figure 5-10 N+1 power supply and distribution system (smart busbar 2.0 LAN
switch scenario)
NOTE
Figure 5-11 2N (isolation) power supply and distribution system (integrated PDF)
Figure 5-12 2N (non-isolation, dual power supplies for NetCol) power supply and
distribution system (integrated PDF)
Figure 5-13 2N (non-isolation, single power supply for NetCol) power supply and
distribution system (integrated PDF)
Figure 5-15 2N power supply and distribution system (smart busbar scenario)
Figure 5-16 2N power supply and distribution system (smart busbar 2.0 LAN
switch scenario)
NOTE
(1) Mains power input status (2) Electricity meter (3) Power distribution fuses for
indicator smart cooling products
(4) IT load switches (5) Bypass input switch (6) Intelligent detection
module
(7) Bypass power input status (8) Lighting switch (9) UPS input switch
indicator
(13) UPS output switch (14) Control module (15) Standby extended subrack
Physical Specifications
Item Specifications
Item Specifications
IP rating IP20
Weight 460 kg
Input power factor > 0.99 (full load); > 0.98 (half load)
Item Specifications
NOTICE
The UPS supports the SmartLi. For details about related parameters, see the
SmartLi user manual.
Item Specifications
Inverter output short- For the 180 kVA UPS (3+1 modules), 2.55 times of the
circuit capability rated current can be tolerated for 20 ms (that is, the
short-circuit current RMS is 697 A) in the case of
inverter output short-circuit.
Item Specifications
Item Specifications
Operating 0–40°C
temperature
Altitude 0–1000 m
When the altitude is higher than 1000 m, the power is
derated as described in IEC 62040-3. The upper limit of
the altitude is 4000 m.
CE EN IEC62040-1
CB IEC62040-1
NOTE
(1) Power input status (2) Input circuit breaker (3) Lighting circuit breaker
indicator
(4) Power distribution circuit (5) IT load circuit breakers (6) UPS input circuit breaker
breakers for smart cooling
products
(7) UPS maintenance bypass (8) Control module (9) Bypass module
circuit breaker
(10) Filler panels (11) Power modules (12) Monitor display unit
(MDU)
(1) Power input status (2) ATS (3) Lighting circuit breaker
indicator
(4) ATS handle installation slot (5) Power distribution circuit (6) IT load circuit breakers
breakers for smart cooling
products
(7) UPS input circuit breaker (8) UPS maintenance bypass (9) Control module
circuit breaker
Item Specifications
Item Specifications
IP rating IP20
Input power factor > 0.99 (full load); > 0.98 (half load)
Item Specifications
Current equalization 5%
specification
Operating 0–40°C
temperature
Altitude 0–4000 m
When the altitude is higher than 2000 m, the power is
derated as described in IEC 62040-3. The upper limit of
the altitude is 4000 m.
(1) Input circuit breaker (2) Power input status (3) Power distribution circuit
indicator breaker for smart cooling
products
(4) IT load circuit breakers (5) UPS input circuit breaker (6) Control module
(10) Lighting circuit breaker (11) Monitoring display unit (12) Power distribution
(MDU) monitoring boards
Item Specifications
IP rating IP20
Input power factor > 0.99 (full load); > 0.98 (half load)
Item Specifications
NOTICE
The UPS supports the SmartLi. For details about the parameters, see the SmartLi
User Manual.
Item Specifications
Item Specifications
No-load loss 1 kW
Item Specifications
Operating 0–40°C
temperature
Altitude 0–4000 m
When the altitude is higher than 2000 m, the power is
derated as described in IEC 62040-3. The upper limit of
the altitude is 4000 m.
CE EN 62040-1:2013
CB IEC 62040-1:2013
Item Specifications
Item Specifications
Item Specifications
Branch power output Phase current, active power, load rate, electric
energy, temperature, and circuit breaker status
Item Specifications
Item Specifications
Certification CCC, CE
Main power input Phase voltage, phase current, load rate, frequency,
power factor, total active power, total electric
energy, total apparent power, total reactive power,
busbar temperature, circuit breaker status, and SPD
status
Branch power output Phase current, active power, load rate, electric
energy, temperature, and circuit breaker status
Appearance
(1) General input unit (2) Connector (3) Power distribution (4) Busbar trunking
unit unit
(1) General input unit (2) Connector (3) Power distribution (4) Busbar trunking
unit unit
No. Meaning
1 Smart busbar
3 AC
6 Monitoring type
Appearance
The indicators show the running status of the smart busbar system. The BLINK
button is used for the blinking function of the ECC800-Pro.
(1) Alarm indicator (2) BLINK button (3) USB port (4) RS485 DIP switch
(red) and AC power
indicator (green)
(5) Board indicators (6) Monitoring panel (7) Surge protective (8) Input switch
device (SPD)
(9) SPD circuit breaker (10) Cable outlet (11) Cable inlet
1 5V
2 DM
3 DP
4 GND
NOTE
3 NC LXTMX1+ NC
6 NC LXTMX1– NTC_3
7 NC LXTMX3+ GND
8 NC LXTMX3– GND
1 LXTMX0+
2 LXTMX0–
3 LXTMX1+
4 LXTMX2+
5 LXTMX2–
6 LXTMX1–
Pin Description
7 LXTMX3+
8 LXTMX3–
Specifications
Figure 5-32 Dimensions of the 630 A general input unit (unit: mm)
Figure 5-33 Dimensions of the 400 A/250 A general input unit (unit: mm)
Packed Accessories
No. Meaning
1 Smart busbar
3 AC
7 Monitoring type
Appearance
(4) RS485 DIP switch (5) Board indicators (6) Load wiring port
NOTICE
The PoE port on the monitoring panel of the power distribution unit is a reserved
network port.
Blinking at 10 Hz Blinking
(on for 0.05s and
off for 0.05s)
Off No alarm is
generated.
Specifications
40 A/1P (hot-swap
switch)
40 A/3P
63 A/1P
63 A/3P
Packed Accessories
No. Meaning
1 Smart busbar
2 Current level:
0250: 250 A
0400: 400 A
0630: 630 A
3 AC
Appearance
Figure 5-39 Dimensions of the 630 A busbar trunking unit (unit: mm)
Figure 5-40 Dimensions of the 400 A/250 A busbar trunking unit (unit: mm)
Packed Accessories
NOTICE
Appearance
(1) General input unit (2) Connector (3) Power distribution (4) Busbar trunking
unit unit
(5) Column (6) Around-column (7) End plug (8) Low support
busbar trunking unit
and elbow (used in the
scenario with columns)
(1) General input unit (2) Connector (3) Power distribution (4) Busbar trunking
unit unit
(5) Column (6) Around-column (7) End plug (8) High support
busbar trunking unit
and elbow (used in the
scenario with columns)
● NMW-0250A4-GIU-M01
● NMW-0400A4-GIU-M02
● NMW-0250A4-GIU-M02
No. Meaning
1 Smart busbar
3 AC
6 Monitoring type
7 ● 01 right-mounted
● 02: left-mounted
Appearance
(1) Alarm indicator (2) Monitoring panel (3) Integrated (4) PWR_2 port
management card
(5) PWR_1 port (6) FE port (7) SPD (8) Input switch
(9) SPD circuit breaker (10) Cable inlet (11) Cable outlet
Status Description
The monitoring panel displays the running status of the smart busbar system by
indicators, implements the blink function with the ECC800-Pro by the BLINK
button, and provides USB, RS485, FE, and AI/DI ports.
(1) Indicators (2) BLINK button (3) USB port (4) RS485 port
RUN Green Blinking at 0.5 Hz, on for 1s and then off for The equipment is running
1s. properly.
Blinking at 10 Hz, on for 0.05s and then off The RUN indicator blinks.
for 0.05s.
1 5V
2 DM
3 DP
4 GND
NOTE
1 RS485+ TRX0+ -
2 RS485– TRX0- -
3 - TRX1+ GND
4 RS485+ TRX2+ -
5 RS485– TRX2- -
6 - TRX1- GND
7 - TRX3+ AIDI_1+
8 - TRX3- -
1 TRX0+_RTN
2 TRX0-_RTN
3 TRX1+_-48V
4 TRX2+_RTN
5 TRX2-_RTN
6 TRX1-_-48V
7 TRX3+_-48V
8 TRX3-_-48V
Specifications
● When the input switch is 400 A, the dimensions (H x W x D) of the general
input unit are 300 mm x 600 mm x 220 mm.
Figure 5-51 Dimensions of the 400 A general input unit (unit: mm)
Figure 5-52 Dimensions of the 250 A general input unit (unit: mm)
No. Meaning
1 Smart busbar
3 AC
No. Meaning
7 Monitoring type
Appearance
(1) Load wiring port (2) PWR_1 port (3) FE1 port (4) Monitoring panel
(5) Integrated (6) FE2 port (7) PWR_2 port (8) Output circuit
management card breaker (behind the
cover)
NOTICE
Specifications
Dimensions (H x W x D): 255 mm x 250 mm x 220 mm
● NMW-0250A4-BTU-01
● NMW-0400A4-BTU-01
● NMW-0400A4-BTU-02
● NMW-0400A4-BTU-03
No. Meaning
1 Smart busbar
2 Current level:
0250: for the general input unit with a 250 A MCCB
0400: for the general input unit with a 400 A MCCB
3 AC
Appearance
(1) Communications cable wiring terminal (2) SPD and SPD switch
IP rating IP20
NOTE
When multiple cabinets are connected in parallel, only the master cabinet has an LCD.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 100
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
(1) Air vent (2) Incoming cable glands (3) Battery circuit breaker
(4) Monitoring interface unit (5) Battery control unit (BCU) (6) Fuse
(7) Slots for battery modules (8) Communications cable (9) Monitoring display unit
outlet (MDU, available only on the
master cabinet)
Item Specifications
IP rating IP21
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 101
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
Item Specifications
Altitude 0–4000 m
CE EN 62477-1
CB EN 62477-1
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 102
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
Item Standard
Rated energy 61.44 kWh 53.76 kWh 46.08 kWh 38.4 kWh
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 103
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
Maximum number of UPS 2N+1, where N indicates the number of battery cabinets
modules supported
(UPS5000-E 50 kVA
modules)
Number of cabinets 6
connected in parallel
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 104
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
Item Specifications
Overcurrent protection ● Charge: level-1 protection: > 109.8 A; level-2 protection: > 120 A
● Discharge: level-1 protection: > 228 A; level-2 protection: > 252 A
EPO protection You can trigger the EPO protection by performing EPO on the UPS
or over the specified dry contact.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 105
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 106
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
Door opening mode The front door is a single door, and the rear door is a
double one.
IP rating IP20
NOTE
26 Ah 40
40 Ah
65 Ah 20
100 Ah
Table 5-51 Configuration scenarios (same for master and slave battery cabinets)
Battery Cabinet Number of Batteries
Specifica Layer
tions (from
Top to
Bottom)
- - 40 38 36 34 32
26 Ah/40 Layer 1 10 9 8 7 6
Ah
Layer 2 10 10 10 10 10
Layer 3 10 10 10 10 10
Layer 4 10 9 8 7 6
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 107
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
Table 5-52 Configuration scenarios (different for master and slave battery
cabinets)
- - 20 19 18 17 16 20 19 18 17 16
65 Layer 1 5 4 3 2 1 5 4 3 2 1
Ah/100
Ah Layer 2 5 5 5 5 5 5 5 5 5 5
Layer 3 5 5 5 5 5 5 5 5 5 5
Layer 4 5 5 5 5 5 5 5 5 5 5
5.2.9 rPDU
NOTE
The figures are for reference only. The actual product may vary.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 108
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
PDU2000-63-1PH-16/8-B2 16 x GB 10 A + 8 x GB 02120643-003
16 A
PDU2000-16-3PH-24/6-B4 24 x GB 10 A + 6 x GB 02120838-003
16 A
PDU2000-16-3PH-24/6-B5 24 x GB 10 A + 6 x GB 02120838-004
16 A
PDU2000-32-1PH-20/4-B11 02122118-001
20 x GB 10 A + 4 x GB
PDU2000-32-1PH-20/4-B10 20 x GB 10 A + 4 x GB 02122118
PDU2000-32-1PH-9/3-B3 9 x GB 10 A + 3 x GB 02120765-004
NOTE
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 109
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
(4) Main control module (5) Output sockets (6) Hydraulic circuit breaker
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 110
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
NOTE
5.2.9.3 PDU2000M
● The PDU2000M products accurately and effectively monitor the real-time
status changes of the current, voltage, power, and electric energy of IT devices
in the data center.
● The PDU2000M products are classified into switch-type and input monitoring-
type. They provide the following monitoring functions.
Input frequency √ √
detection
31-order harmonic √ √
detection of the input
current and voltage
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 111
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
LED display √ √
Connection to a T/H √ √
sensor, door status
sensor, smoke sensor,
water sensor, cabinet
electronic lock, and U
space manager
Communications √ √
protocols: Modbus TCP
protocol (FE port) for
ECC800-Pro connection,
SNMP, and RS485
(Modbus RTU protocol)
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 112
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
(1) Display (2) COM/DI 1– (3) COM4 (4) RS485 (5) FE1–FE2
COM/DI 3
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 113
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 114
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
NOTE
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 115
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
Display
(1) Running indicator (2) Minor alarm (3) Major alarm (4) Escape key
indicator indicator
(5) Page Up key (6) Page Down key (7) Enter key (8) LCD
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 116
FusionModule2000 6.0 Smart Modular Data Center
Product Description 5 Power Supply and Distribution System
Enter 3s Blink.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 117
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
An in-row air cooled smart cooling product works as follows: After the unit starts,
the low-pressure refrigerant vapor in the refrigerating system is suctioned into the
compressor, compressed into high-pressure vapor, and discharged to the
condenser. The outdoor air drawn in by the axial flow fan flows through the
condenser and carries away the heat emitted from the refrigerant so that the
high-pressure refrigerant vapor condenses into high-pressure liquid. The high-
pressure liquid passes through the filter and flow regulating mechanism and then
is ejected to the evaporator. Then the liquid vaporizes at low pressure and absorbs
ambient heat. The cross-flow fan draws air into the fins in the evaporator to
exchange heat and discharges cooled air to the cold aisle. The indoor air flows
cyclically to decrease the temperature.
In-row smart cooling products are close to heat sources, which shortens the air
supply distance, reduces airflow pressure loss and cold air loss, and maximizes the
use of cooling capacity.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 118
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 119
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
1 Electrical box The power supply unit (PSU) and built-in electrical
control component control the power supply efficiently.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 120
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
5 Filter dryer The filter dryer absorbs water from the refrigerant
pipes and filters out the foreign matter, which reduces
component damage rates and improves operating
efficiency and reliability.
6 Sight glass Allows you to observe the refrigerant flow and gas
content for easy maintenance and optimization.
7 Oil separator The oil separator separates the lubricant brought out
due to discharge of the compressor and brings back the
separated lubricant to the compressor.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 121
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Features
● The high-efficiency EC fan features large air volume, low noise, and high
efficiency.
● The variable frequency drive ensures stable running at low loads.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 122
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
6.2.1.2.1 FusionCol500-A090
Model FusionCol500-A0904C2
Number of fans 1
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 123
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
6.2.1.2.2 FusionCol500-P090
Model FusionCol500-P0904C2
Number of fans 1
Precautions
● If the actual total load of servers corresponding to a single smart cooling
product is less than 10% of the rated cooling capacity of the smart cooling
product or the equipment room is not properly sealed, the humidity in the
equipment room may be too high. This is not a product quality issue and
should be dealt with by adding a dehumidifier.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 124
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
● When determining the number of units, consider the redundancy design and
ensure that the redundancy design requirements in GB 50174 or TIA 942 are
met.
● Do not install smart cooling products near noise-sensitive places such as
offices and meeting rooms.
● Before installation, check whether the installation environment meets the
requirements and whether the building needs to be altered to facilitate pipe
layout, cable routing, and ventilation duct construction.
● To ensure good ventilation, do not place the indoor unit in the corner of a
room or at the end of a long and narrow room.
● Check that all doors and windows of the equipment room are closed to
reduce the workload of the smart cooling product during system operation.
Environmental Requirements
Item Requirement
Equipment The equipment room provides good heat insulation, and the
room walls and floor are dampproof.
Water supply The inlet water pressure should be in the range of 0.1–0.7 MPa
(a reducing valve must be installed at the humidifier water inlet
if the inlet water pressure exceeds 0.7 MPa). If the inlet water
pressure is lower than 0.1 MPa, a check valve must be installed
at the humidifier water inlet. The temperature should be in the
range of 1°C–40°C.
Specific requirements:
● Non-freezing and nephelometric turbidity units (NTU) < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO3) ≤ 450 mg/L
Drainage The distance between the top drainage of the water pump and
the cabinet installation surface should not exceed 4 m.
Power Leakage circuit breakers are not recommended for the main
distribution power route. If a leakage circuit breaker is required by the
customer or local regulations, select the residual current circuit
breaker (RCCB) that is insensitive to single-phase DC pulsation
and transient impulse current.
Space Requirements
Install the device according to the design drawing and reserve space for
maintenance. At least 1200 mm maintenance space must be reserved in front of
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 125
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
or at the rear of the indoor unit, and at least 600 mm maintenance space must be
reserved at the other end.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 126
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Model FusionCol5000-A065H4
Maximum current 46 A
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 127
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
IP rating IP20
Refrigerant R410A
Cooling capacity 65 kW
Tested under rated working conditions (indoor dry-
bulb temperature: 40°C; relative humidity: 24%;
outdoor temperature: 35°C)
Pipe routing mode Pipes can be routed from the top or bottom.
Caster Available
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 128
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Application Environment
Class D (marine environment) Areas within 500 m away from the seashore.
NOTE
If an outdoor unit needs to be used at a site 3.7–10 km away from the coast in a class B
environment, it is recommended that the unit be installed in a shielded area, such as a
podium building, ground, or building rear, to prevent mechanical parts from being corroded
by sea wind (the functionality and reliability of the system must not be affected).
Alternatively, use an outdoor unit that supports class C environments to avoid corrosion. If
the site is more than 10 km away from the coast, the unit can be properly installed.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 129
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
FusionCol500-A090
Model FusionCol500-A0904C2
Applicable Class B
environment
Number of fans 1
NOTE
Class B: Indoor environment where the ambient temperature and humidity are not
controlled or outdoor environments (with simple shielding measures) where the humidity
can reach 100%.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 130
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
FusionCol500-P090
Model FusionCol500-P0904C2
Applicable Class B
environment
Number of fans 1
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 131
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
NetCol500-A110
Model NetCol500-A110MC1E0
Applicable Class B
environment
Number of fans 2
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 132
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 133
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 134
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
6 Filter dryer The filter dryer absorbs water from the refrigerant
pipes and filters out the foreign matter, which reduces
component damage rates and improves operating
efficiency and reliability.
7 Sight glass Allows you to observe the refrigerant flow and gas
content for easy maintenance and optimization.
8 Oil separator The oil separator separates the lubricant brought out
due to discharge of the compressor and brings back the
separated lubricant to the compressor.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 135
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 136
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
6.2.2.2.1 FusionCol500-A070
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 137
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
6.2.2.2.2 FusionCol500-P090
2 Electric The IPX5 requirements are met. A built-in fan drive and
control box refrigerant pump drive are used:
● Modular design delivers high efficiency and facilitates
quick replacement.
● The fan drive is separated from the motor, which
facilitates fault locating and replacement.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 138
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Precautions
● If the actual total load of servers corresponding to a single smart cooling
product is less than 10% of the rated cooling capacity of the smart cooling
product or the equipment room is not properly sealed, the humidity in the
equipment room may be too high. This is not a product quality issue and
should be dealt with by adding a dehumidifier.
● When determining the number of units, consider the redundancy design and
ensure that the redundancy design requirements in GB 50174 or TIA 942 are
met.
● Do not install smart cooling products near noise-sensitive places such as
offices and meeting rooms.
● Before installation, check whether the installation environment meets the
requirements and whether the building needs to be altered to facilitate pipe
layout, cable routing, and ventilation duct construction.
● To ensure good ventilation, do not place the indoor unit in the corner of a
room or at the end of a long and narrow room.
● Check that all doors and windows of the equipment room are closed to
reduce the workload of the smart cooling product during system operation.
Environmental Requirements
Item Requirement
Equipment The equipment room provides good heat insulation, and the
room walls and floor are dampproof.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 139
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Item Requirement
Water supply The inlet water pressure should be in the range of 0.1–0.7 MPa
(a reducing valve must be installed at the humidifier water inlet
if the inlet water pressure exceeds 0.7 MPa). If the inlet water
pressure is lower than 0.1 MPa, a check valve must be installed
at the humidifier water inlet. The temperature should be in the
range of 1°C–40°C.
Specific requirements:
● Non-freezing and nephelometric turbidity units (NTU) < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO3) ≤ 450 mg/L
Drainage The distance between the top drainage of the water pump and
the cabinet installation surface should not exceed 4 m.
Power Leakage circuit breakers are not recommended for the main
distribution power route. If a leakage circuit breaker is required by the
customer or local regulations, select the residual current circuit
breaker (RCCB) that is insensitive to single-phase DC pulsation
and transient impulse current.
Space Requirements
Install the device according to the design drawing and reserve space for
maintenance. At least 1200 mm maintenance space must be reserved in front of
or at the rear of the indoor unit, and at least 600 mm maintenance space must be
reserved at the other end.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 140
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 141
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Model FusionCol5000-A050H4
Maximum 42 A
current
Operating 18–45°C
temperature
Maximum 4000 m
operating
altitude
IP rating IP20
Refrigerant R410A
Cooling 46 kW
capacity Tested under rated working conditions (indoor dry-bulb
temperature: 37°C, relative humidity: 21%, outdoor temperature:
35°C).
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 142
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Condensate Available
pump
Water pump 4m
lift
Caster Available
Application Environment
Type Description
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 143
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Type Description
Class D (marine environment) Areas within 500 m away from the seashore.
NOTE
If an outdoor unit needs to be used at a site 3.7–10 km away from the coast in a class B
environment, it is recommended that the unit be installed in a shielded area, such as a
podium building, ground, or building rear, to prevent mechanical parts from being corroded
by sea wind (the functionality and reliability of the system must not be affected).
Alternatively, use an outdoor unit that supports class C environments to avoid corrosion. If
the site is more than 10 km away from the coast, the unit can be properly installed.
FusionCol500-A070
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 144
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Model FusionCol500-A0704C2
Applicable Class B
environment
Number of fans 1
FusionCol500-P090
Model FusionCol500-P0904C2
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 145
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Applicable Class B
environment
Number of fans 1
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 146
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
(1) External signal port (2) Electric control box (3) Module subrack
(4) Drive (5) Wet film humidifier (6) Differential pressure switch
(13) Water pan cover (14) Water pump (15) Transformer (NetCol5000-
A025HNWE2)
● Compressor
The smart cooling product uses a DC variable-frequency compressor that
features compact size, light weight, a long service life, low noise, easy
installation, high reliability, stability, and energy efficiency.
● Oil separator
The oil separator separates the lubricant brought out due to discharge of the
compressor and brings back the separated lubricant to the compressor.
● Fan
The energy-efficient EC fan that supports stepless speed adjustment is used to
reduce the fan energy consumption. Each fan is light and easy to maintain.
The system will not shut down if a single fan fails.
● Evaporator
The finned-tube evaporator with a high cooling efficiency adopts the synergy
field principle and computational fluid dynamics (CFD) to optimize the flow
path design, which greatly improves the heat exchange efficiency.
● Electronic expansion valve (EEV)
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 147
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Components
A NetCol500 outdoor unit mainly consists of an electric control box, a condenser, a
rack, and fans. The following, uses NetCol500-A060 as an example, describes the
components and configuration.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 148
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Features
● The outdoor unit is equipped with a high-efficiency variable-frequency drive
axial fan to implement big air volume, low noise, and high efficiency.
● The outdoor unit has good waterproof performance and meets IPX5
requirements.
● The outdoor unit adopts the variable-frequency drive. The speed adjustment
of the outdoor fan ranges from 10% to 100%. The minimum operating
frequency of the fan is less than or equal to 5 Hz. The outdoor unit is running
more steadily at low loads.
● The outdoor unit adopts the galvanized sheet and surface phosphatization +
powder coating techniques, the outdoor unit adapts to harsh environments
with its sound rigidity and anticorrosion performance.
● Pressure preservation is performed on the condenser before delivery, and the
pipe ports are properly sealed to prevent foreign matter from entry.
Operating environment
Operating 18–45°C
temperature
Temperature 18–45°C
adjustment range
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 149
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Item Specifications
Installation requirements
NOTICE
If the equipment room is not properly sealed, the humidity in the equipment room
may exceed the upper limit, which is not a product quality issue and should be
dealt with by adding a dehumidifier.
Item Specifications
Height difference ● If the outdoor unit is placed higher than the indoor
between the indoor unit, the vertical distance between them should be
and outdoor units less than or equal to 30 m.
● If the indoor unit is placed higher than the outdoor
unit, the vertical distance between them should be
less than or equal to 8 m.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 150
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Item Specifications
Thermal insulation ≥ 13 mm
foam thickness
Water supply ● The water supply pressure ranges from 0.1 MPa to
0.7 MPa.
● The water supply temperature ranges from 1°C to
40°C.
● The transient water flow volume is greater than or
equal to 1.2 L/min.
Note: If certain conditions are not met, contact Huawei technical support.
Refrigerant R410A
Cooling capacity test conditions: dry bulb temperature at air return vent: 37°C;
relative humidity at air return vent: 20%; outdoor temperature: 35°C.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 151
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Volta If upstream voltage fluctuation exceeds the rated voltage±10%, you are
ge advised to add a voltage regulator. Otherwise, the smart cooling
product may generate alarms frequently and fail to work properly.
Cond No Yes
ensat
e
pump
Wate - 4m
r
pump
lift
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 152
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
a: In the preceding table, No indicates that the corresponding model does not
provide the function.
Number of 1 2
fans
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 153
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Protection IPX5
level
NOTE
Outdoor unit installation environments are classified as follows based on the harshness:
● Class A (controlled environment): indoor environments where the ambient temperature
and humidity are controlled, including rooms where people live.
● Class B (uncontrollable environment): indoor environments where the ambient
temperature and humidity are not controlled or general outdoor environments with
simple shielding measures where the humidity sometimes reaches 100%.
● Class C (harsh environment): refers to sea environments or outdoor land environments
with simple shielding measures near pollution sources.
● Class D (marine environment): environments that are within 500 m from the coast.
NetCol500-A060MS and NetCol500-A040MS outdoor unit must not be installed in Class
D environments, and other outdoor units must not be installed in Class C or Class D
environments.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 154
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Appearance
(1) Cabinet connecting (2) Display module (3) Door lock (4) Front door
kit
(5) Mounting hole (6) Side panel (7) Rear door (8) Anchor
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 155
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
(1) Power cable hole (Φ28 mm) on the top (2) Humidifier water inlet pipe hole (Φ43 mm)
on the top
(3) Skylight signal cable hole (Φ28 mm) on (4) Refrigerant gas pipe hole (Φ43 mm) on the
the top top
(5) Refrigerant liquid pipe hole (Φ43 mm) on (6) Drainpipe hole (Φ43 mm) on the top
the top
(7) Signal cable holes (Φ28 mm) on the top (8) Power cable hole (Φ28 mm) at the bottom
(9) Humidifier water inlet pipe hole (Φ43 mm) (10) Refrigerant gas pipe hole (Φ60 mm) at
at the bottom the bottom
(11) Drainpipe hole (Φ60 mm) at the bottom (12) Refrigerant liquid pipe hole (Φ60 mm) at
the bottom
Interior Components
The NetCol5000-A mainly consists of a DC variable-frequency compressor, EC fan,
evaporator, electronic expansion valve (EEV), oil separator, sight glass, filter dryer,
air filter, electric heater (optional), wet film humidifier (optional), condensate
pump (optional), differential pressure switch, and temperature and humidity
sensor (T/H sensor).
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 156
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
● Compressor
– The smart cooling product uses a DC variable-frequency compressor that
features compact size, light weight, a long service life, low noise, easy
installation, high reliability, stability, and energy efficiency.
– The high-precision drive automatically adapts to the system pressure
fluctuations.
– The drive conducts precision self-check. Compressor and drive faults are
separated.
● EC fan
– The energy-efficient EC fan that supports stepless speed adjustment is
used to reduce the fan energy consumption.
– There are 10 EC fans in total. The smart cooling product will not shut
down if a single fan fails.
– Fans can be maintained with power-on. You can replace one faulty fan
without shutting down the smart cooling product.
● Evaporator
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 157
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
– The evaporator adopts the inner threaded copper pipe and blue
hydrophilic aluminum foil to prevent water blowing due to condensate
water accumulation and improve heat exchange performance. The V-
shaped evaporator optimizes the airflow organization and reduces the air
resistance.
– The finned-tube evaporator with a high cooling efficiency adopts the
synergy field principle and computational fluid dynamics (CFD) to
optimize the flow path design, which greatly improves the heat exchange
efficiency.
– The small-diameter tubes are adopted to enhance the heat exchange
performance, increasing the heat exchange efficiency by more than 10%
when compared with a traditional solution.
– The designed pressure bearing capacity of the heat exchange coil is 4.35
MPa, providing excellent pressure resistance capability.
● EEV
– The throttling device uses a miniature controller to control the operation
of the step motor, thereby changing the pass-through area of the EEV to
regulate the flow of refrigerant.
– The main control module contains an EEV energy storage unit to prevent
slugging due to refrigerant migration after an unexpected power-off.
● Oil separator
The oil separator separates the lubricant brought out due to discharge of the
compressor and brings back the separated lubricant to the compressor.
● Sight glass
The sight glass allows users to observe the refrigerant flow and the content of
gas and liquid for easy maintenance and optimization.
● Filter dryer
The filter dryer absorbs water from the refrigerant pipes and filters out the
foreign matter, which reduces component damage rates and improves
operating efficiency and reliability.
● Air filter
The G4 air filter is used.
● Electric heater
– The positive temperature coefficient (PTC) electric heater automatically
adjusts heating capacity and provides multiple protection measures to
ensure safe and reliable operation.
– The heater features quick start, large heating capacity, and even heating.
● Wet film humidifier
– The wet film humidifier has low water quality requirements and high
environment adaptability.
– Uses a simple structure and is easy to remove, clean, and maintain.
– Quickly starts and generates huge humidification capacity.
– Consumes low power, saving more than 95% energy compared with a
traditional electrode humidifier.
– Provides a longer service life and maintenance interval than a traditional
electrode humidifier.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 158
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
● Condensate pump
The water pump provides power for top drainage with a maximum lift of 4 m.
● Check valve
The check valve effectively prevents gas or liquid backflow.
● Differential pressure switch
When the air filter is dirty or blocked, the differential pressure switch triggers
an alarm, prompting for air filter replacement.
● T/H sensor
The smart cooling product contains the negative temperature coefficient
(NTC) temperature sensor and the return air T/H sensor.
Appearance
Features
● The outdoor unit is equipped with a high-efficiency variable-frequency drive
axial fan and the distinctive sickle blades adopt the owl-inspired fan blade
design to implement big air volume, low noise, and high efficiency.
● The outdoor unit has excellent waterproof performance and meets IPX5
requirements.
● The outdoor unit adopts the variable-frequency drive. The outdoor fan speed
is adjustable from 10% to 100%. The minimum operating frequency of the
fan is no greater than 5 Hz. The outdoor unit is running more steadily at low
loads.
● Adopted the galvanized sheet and surface phosphatization + powder coating
techniques, the outdoor unit adapts to harsh environments with its sound
rigidity and anticorrosion performance.
● Pressure preservation is performed on the condenser before delivery, and the
pipe ports are properly sealed to prevent foreign matter from entry.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 159
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Operating Environment
Item Specifications
Humidity ±5% RH
adjustment
precision
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 160
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Installation Requirements
NOTICE
If the total actual load of servers for each smart cooling product is less than 10%
of the rated cooling capacity or the equipment room is not properly sealed, the
humidity in the equipment room may exceed the upper limit, which is not a
product quality issue and should be dealt with by adding a dehumidifier.
Equivale ≤ 100 m
nt
length
of the
one-
way
pipe
Height ● If the outdoor unit is placed higher than the indoor unit, the
differen maximum vertical distance between them is 30 m.
ce ● If the indoor unit is placed higher than the outdoor unit, the
betwee maximum vertical distance between them is 8 m.
n indoor
and
outdoor
units
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 161
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Item Specifications
Water The inlet water pressure should be in the range of 0.1–0.7 MPa, and
supply the temperature should be in the range of 1–40°C.
require The wet film humidifier uses tap water and does not require an
ments additional water treatment device at the water inlet. The water
requirements are as follows:
● Non-freezing and nephelometric turbidity units (NTU) < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO3) ≤ 450 mg/L
For details, see GB 5749-2006 Standards for Drinking Water Quality.
Power Leakage circuit breakers are not recommended for the main power
distribut route. If a leakage circuit breaker is required by the customer or local
ion regulations, select the residual current circuit breaker (RCCB) that is
require insensitive to single-phase DC pulsation and transient impulse
ments current.
Note: If the requirements are not met, contact technical support engineers for
an optimization solution.
Refrigerant R410A
Cooling 46 kW
capacitya
IP rating IP20
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 162
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Maximum 46 A 36 A 46 A
current
Condensa Yes No
te pump
Water 4m -
pump lift
Reheating 6 kW No 6 kW No 6 kW 6 kW No
capacity
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 163
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Castor No Yes
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 164
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Number of fans 1 2 2
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 165
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
IP rating IPX5
Class D (marine environment) Areas within 500 m away from the seashore.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 166
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
NOTE
● If an outdoor unit needs to be used at a site 3.7–10 km away from the coast in a class B
environment, it is recommended that the unit be installed in a shielded area, such as a
podium building, ground, or building rear, to prevent mechanical parts from being
corroded by sea wind (the functionality and reliability of the system must not be
affected). Alternatively, use an outdoor unit that supports class C environments to avoid
corrosion. If the site is more than 10 km away from the coast, the unit can be properly
installed.
● The NetCol500-A060MS1E0 outdoor unit must not be installed in class D environments,
and other outdoor units must not be installed in class C or class D environments.
Refrigerant R410A
Heat exchanging 55 kW
capacity
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 167
FusionModule2000 6.0 Smart Modular Data Center
Product Description 6 Temperature Control System
Maximum 125°C
operating
temperature on the
refrigerant side
Maximum 60°C
operating
temperature on the
cooling water side
IP rating IP21
Net weight 63 kg
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 168
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
7 Management System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 169
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
NOTE
● In the figure, RF_Z indicates wireless networking. RF_Z(1) devices can communicate with
the ECC800-Pro in wireless mode. RF_Z(1) and RF_Z(2) devices use different protocols
and are isolated from each other.
● After the access actuator, FusionModule Actuator, and multi-functional sensor are
connected to the ECC800-Pro through PoE and they communicate successfully, wireless
communication is automatically set up.
● The smart screen can be connected to an ETH gateway or switch.
● Connect the signal cable from each camera and IVS1800 to the LAN switch in the
following scenarios:
● (1) Four or more cameras and IVS1800s are deployed in a single smart module.
● (2) The cameras outside the smart module are connected to the smart module,
and there are at least four cameras and IVS1800s inside and outside the smart
module.
● (3) Multiple smart modules share one IVS1800.
● (4) There are at least two IVS1800s.
7.2.1 Monitoring
● Temperature and humidity monitoring: detects and collects statistics on the
ambient temperature and humidity inside the smart module.
● Water leakage monitoring: detects water leakage at the bottom of the smart
module and provides real-time alarm signals.
● Smoke monitoring: detects smoke in the smart module and provides real-time
alarm signals.
● Power distribution monitoring:
a. Detects and collects statistics on the total input phase voltage, current,
frequency, power factor, electric energy, active power, apparent power,
load rate, THDv, THDi, and cabinet interior busbar temperature for the
smart module.
b. Detects the current, electric energy, switch status, contact temperature,
and load rate of the power distribution branches for IT equipment and
smart cooling products; collects statistics on electric energy by month or
year.
● Smart cooling product monitoring:
a. Monitors the supply and return air temperature and humidity in real
time.
b. Configures the supply air temperature set point for all smart cooling
products, without the need to separately configure it for each smart
cooling product.
c. Monitors and displays the fan speed, and displays the running
percentage.
d. Displays the cooling load rate.
e. Monitors and displays the compressor running status.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 170
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
● Supports full link display of the power supply and distribution system for the
smart module. The connection mode and topology of power supply and
distribution devices such as the integrated UPS, battery, PDF, and cabinet
rPDU are included. You can check the switch status and running status of
power supply and distribution devices in a view.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 171
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
● Shows the cooling system of the smart module, displays the air intake and
outtake temperatures and running parameters of smart cooling products, aisle
temperature and humidity, and temperatures (optional) at the front and rear
of a single cabinet. The app also displays the detailed running parameters of
a single smart cooling product and the running status of components such as
the compressor, fan, and expansion valve.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 172
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
● Displays the resource usage of the power, space, and cooling capacity of the
smart module and each cabinet.
● Displays the real-time status and alarms of the aisle T/H sensor, door status
sensor, water sensor, and lighting in the plan view.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 173
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
● Displays the PUE value of the smart module in a data dashboard; allows you
to view the historical PUE curve and power consumption of the smart module
by day, month, or year.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 174
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 175
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
7.2.4 Alarm
● The system monitors the status of smart cooling products, power distribution,
and environment. If a fault or parameter error occurs, the system generates
an alarm in real time. You can view the alarm cause and solution in the alarm
details.
● Alarms can be classified into four severities: critical, major, minor, and
warning. The alarm severities can be user-defined.
● Active alarms can be filtered by device and alarm severity.
● Real-time alarms can be displayed in different colors on the power supply link
view of the app. Alarms can be associated with the alarm beacon and eLight.
The color corresponding to the alarm severity is displayed on the aisle door of
the smart module.
● Alarm notifications can be sent by email and SMS.
● A maximum of 500 concurrent active alarms are supported.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 176
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
● Data export: You can export historical data of the ECC800-Pro and some
southbound devices.
Aisle smoke alarms cannot trigger the customer's fire extinguishing system. Only dry
contact alarm signals are provided.
● Smart cooling products in the aisle can be shut down when the customer's
fire extinguishing system generates dry contact alarms.
● Skylights and doors can be opened and lights can be turned on when the
customer's (or external) fire extinguishing system generates dry contact
alarms or signals.
● You can manually configure linkage policies for monitoring systems inside the
smart module.
● Intelligent lighting (motion detection) is supported. When an object is
detected in the aisle, the aisle lights turn on. If no object is detected within 10
minutes, the aisle lights automatically turn off.
7.3.1 ECC800-Pro
NOTE
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 177
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
(1) Slot 1: PSU (2) Slot 2: PSU (3) Slot 3: main control
module
(4) AC_INPUT2
Power Port
The ECC800-Pro provides four power ports, including two AC input ports
(AC_INPUT1 and AC_INPUT2) and two DC output ports (DC_OUT1 and
DC_OUT2). Table 7-1 provides the power port pin definitions.
DC RTN+ 48V+
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 178
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
NOTE
Signal Port
The ECC800-Pro provides the following communications ports. The pins of the
RJ45 port are shown in the figure.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 179
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
There are four GE ports, that is, two WAN ports (WAN1 and WAN2) and two LAN
ports (LAN1/PoE and LAN2/PoE).
Item Description
Pin 3 GE2+
Pin 4 GE3+
Pin 5 GE3–
Pin 6 GE2–
Pin 7 GE4+
Pin 8 GE4–
Item Description
Pin 3 12 V DC_OUT
Pin 4 RS485+
Pin 5 RS485–
Pin 6 DI–
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 180
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Description
Pin 7 DI+
Pin 8 GND
Pin 3 12 V DC_OUT
Pin 4 RS485+
Pin 5 RS485–
Pin 6 -
Pin 7 -
Pin 8 GND
Pin 3 -
Pin 4 RS485+
Pin 5 RS485–
Pin 6 -
Pin 7 CAN_H
Pin 8 CAN_L
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 181
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Pin 3 12 V DC
Pin 4 Type_3
Pin 5 Type_4
Pin 6 DI–
Pin 7 DI+
Pin 8 GND
Pin Pin 1 -
sequence
Pin 2 -
Pin 3 12 V DC_OUT
Pin 4 -
Pin 5 -
Pin 6 DO_OUT+
Pin 7 DO_OUT–
Pin 8 GND
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 182
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Indicators
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 183
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
SW Button
Hold down the button for more than The RF_Z indicator is
8s to erase network parameters. The blinking at super
system automatically enters the short intervals.
wireless network pairing mode.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 184
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
7.3.1.3 PSU
Indicators
Output overvoltage
Hibernation
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 185
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
(1) DIP switch (reserved) (2) COM_OUT (reserved) (3) COM_IN (reserved)
Item Specifications
Width 120 mm
Depth 200 mm
Height 43 mm
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 186
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Environmen RoHS5
tal
protection
Technical Specifications
Item Specifications
Communications Ports
The following table describes the pin definitions for ports COM1/AIDI_1 to COM8/
AIDI_8.
Item Description
Pin 3 12 V
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 187
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Description
Pin 4 RS485+
Pin 5 RS485–
Pin 6 D-
Pin 7 D+
Pin 8 GND
The following table describes the pin definitions for the COM_IN and COM_OUT
ports.
Table 7-14 Pin definitions for the COM_IN and COM_OUT ports
Item Description
Pin 4 RS485+
Pin 5 RS485–
Pin 6 -
Pin 7 -
Pin 8 GND
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 188
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Blinking Blinking at super short intervals for 0.5s and then off for
0.5s; last 10s (blinking at super short intervals: 10 Hz,
on for 0.05s and then off for 0.05s)
Blinking Press the button for The RUN indicator blinks at super
less than 2s. short intervals for 0.5s and then off for
0.5s; last 10s (blinking at super short
intervals for 10 Hz, on for 0.05s and
then off for 0.05s).
(1) PWR_IN cascading (2) FE_1 cascading (3) PoE_1–2 ports (4) PoE_3–4 ports
power port signal port
(5) 48V_OUT1 power (6) 48V_OUT2 power (7) FE_2 cascading (8) PWR_OUT
output port output port signal port cascading power port
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 189
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Specifications
Power input PWR_IN D-type power input terminal, for power cascading, input
voltage range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A, 48 V DC);
power of cascaded smart ETH gateways: max (25 A, 48 V DC)
PoE port Four PoE ports, RJ45 terminal with an indicator, 10/100 Mbit/s
communications rate, complying with IEEE 802.3, IEEE 802.3u,
IEEE 802.3af/at
BLINK If you press the BLINK button, the RUN indicator blinks
button intermittently at super short intervals (blinking at super short
intervals for 0.5s and then off for 0.5s, lasting 5 seconds in total).
Indicators
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 190
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 191
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Appearance
(1) 48 V DC power (2) LAN port (3) RS485 ports (4) RS485 port COM3
input port (COM1/COM2) (reserved)
(5) DIP switch (6) AC OUT power (7) Terminal cover (8) AC IN power input
output ports port
(9) Fuse (10) Indicators (11) BLINK button (12) Spare fuse box
(13) Wiegand ports (14) AI/DI ports (15) DO/12V port (16) DO/DI ports
Specifications
Item Specifications
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 192
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Wireless One wireless port that complies with IEEE 802.15.4, mutual
communicat backup with FE communication
ion
RS485 serial COM1/2: two RS485 ports (one route) with a default
port communication rate of 9600 bit/s, physical port cascading
(reserved)
COM3: southbound or northbound communication (reserved)
DO/DI port ● Access: One DO output port is used to control the power
output of the electronic door lock, and one DI input port is
used to connect to the door status switch. Both ports use
terminals.
● Skylight: One DO output port is used to control the power
output of the skylight magnetic lock, and one DI input port is
connected to the skylight open button. Both ports use
terminals.
AI/DI port Five AI/DI ports, in which one is for detecting one door open
button, two for detecting lighting buttons, and one for detecting
fire extinguishing linkage signal. One port is reserved.
BLINK ● Press the button for less than 1 second to start blinking.
button ● Hold down the button for 1–5 seconds to search for a network
and start networking.
● Hold down the button for more than 6 seconds to clear
network parameters.
Fuse 16 A, 250 V AC
E-label Supported
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 193
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Indicators
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 194
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
7.3.5 PAD
● The PAD allows the wireless access from the data center management system.
You can monitor the equipment in the data center and environmental
parameters in real time over the app.
● You are advised not to set Sleep to Never for the PAD, which may shorten the
service life of the screen and battery.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 195
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
(1) Camera (2) Power port (3) Power button (4) RJ45 port
(5) HDMI port (6) AUDIO-OUT (7) USB-OTG/USB (8) SIM card slot
(9) TP card slot (10) Infrared sensor (11) Indicator (12) Remote control
receiver
(13) Built-in
microphone
Item Specifications
Weight 27 kg
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 196
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Storage ● Body: 32 GB
● Memory: 4 GB
● Expansion card: TF card, up to 128 GB (non-standard
configuration)
7.3.7 4G Antenna
Figure 7-23 4G antenna
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 197
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Input 50 Ω
impedance
Polarization Vertical
Maximum 10 W
power
Connector SMA-J
Item Specifications
Input 50 Ω
impedance
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 198
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Gain ≥ 3 dBi
Polarization Vertical
Maximum 10 W
power
Connector RP-SMA-J
Item Specifications
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 199
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Maximum 3
number of
connected
devices
Item Specifications
Input 50 Ω
impedance
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 200
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Gain ≥ 3 dBi
Polarization Vertical
Maximum 10 W
power
Connector RP-SMA-J
Maximum 3
number of
connected
devices
The WLDS900 water sensor with the BOM number of 33010352 consists of a
water detection cable, a water detector, and a conversion cable.
(1) Water detector (2) Conversion cable end A, connected to (3) Conversion cable
the water detector
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 201
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
(4) Conversion cable (5) Water detection cable end A, (6) Water detection cable
end B, connected to the connected to the conversion cable
water detection cable
Item Specifications
Item Specifications
Temperature detection ● ±1°C (≥ –10°C, < 25°C) & (> 25°C, ≤ 55°C)
tolerance ● ±2°C (≥ –20°C, < –10°C) & (> +55°C, ≤ +70°C)
● ±0.5°C (25°C)
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 202
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Item Specifications
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 203
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Output RS485
NOTE
Pin Description
Pin 1 or Pin 4 A
Pin 2 or Pin 5 B
Pin 3 V+
Pin 6 or Pin 8 V–
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 204
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Pin Description
Pin 7 Disconnected
Output RS485
NOTE
The infrared detection function is enabled only when the intelligent lighting function is
enabled.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 205
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
(1) Address DIP switch (2) BLINK button (3) TEST button
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 206
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
(1) Address DIP switch (2) BLINK button (3) TEST button
Specifications
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 207
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
PoE port One PoE port that complies One PoE port that complies with
with IEEE 802.3at IEEE 802.3at
RS485 port One RS485 port is reserved. One RS485 port reserved,
supporting 12 V DC power input
TEST button Supports the smoke sensor Supports the smoke sensor test.
(for testing test. Hold down the button for 3s to
the smoke Hold down the button for 3s trigger a smoke alarm, and
detection) to trigger a smoke alarm, release the button to stop the
and release the button to smoke alarm.
stop the smoke alarm.
Indicators
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 208
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 209
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Dimensions (L x W x 124.6 mm x 73 mm x 48 mm
H)
Item Specifications
Power input RJ45 port; input voltage: 10–15 V DC; operating current:
≤ 300 mA
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 210
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 211
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
(1) 48 V power port (2) PoE port (3) RS485 port COM2
(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand interface (9) WG_1 Wiegand interface
(10) AI/DI_2 dry contact (11) AI/DI_1 dry contact (12) LOCK/GND/GATE/COM door
(reserved port for linkage (reserved port for exit status sensor and magnetic lock
control or third-party fire button) port
extinguishing system dry
contacts)
Specifications
AI/DI port Two AI/DI ports, can connect to the fire alarm and exit button
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 212
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
RS485 serial Two RS485 ports (one route) with the default communication
port rate of 9600 bit/s, physical port cascading supported (reserved
expansion function)
BLINK ● Press the button for less than 1 second to start blinking.
button ● Hold down the button for 1–5 seconds to search for a network
and start networking.
● Hold down the button for more than 10 seconds to clear
network parameters.
E-label Supported
Indicators
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 213
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 214
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/
COM). Table 7-40 lists the LOCK/GND/GATE/COM port pin definitions.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 215
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
door. When a person enters the detection range of the sensor, the sensor supplies
a feedback signal to the access actuator or ECC, which will open the aisle door of
the smart module.
Dimensions 120 mm x 80 mm x 56 mm
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 216
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Table 7-42 Technical specifications of a fingerprint and card reader with a keypad
Item Specifications
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 217
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 218
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Dimensions (L x W x H) 114 mm x 63 mm x 25 mm
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 219
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Table 7-47 Technical specifications of the cabinet fingerprint and card lock
Item Specifications
Net weight of the lock 696 g±5% (excluding bolts and washers)
body
Color Black
Card type supported Standard configuration: Mifare1 card and CPU card
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 220
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 221
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 222
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
Features:
Item Specifications
Rated power 10 W
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 223
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
7.3.13.1 Camera
The C3220 camera is a two-megapixel infrared zoom dome camera that can be
ceiling-mounted.
Item Specifications
Minimum illumination ● Color: 0.002 lux (F1.2, AGC ON, 1/30s shutter
speed)
● Black/White: 0.0005 lux (F1.2, AGC ON, 1/30s
shutter speed)
0 lux (IR illuminator enabled)
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 224
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
IP rating IP67
7.3.13.2 IVS1800
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 225
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Audio input 1 channel, RCA port 1 channel, RCA port 1 channel, RCA port
Audio 1 channel, RCA port 1 channel, RCA port 1 channel, RCA port
output
Alarm port 16-channel Boolean 4-channel alarm input, 4-channel alarm input,
value input and 4- 2-channel alarm 2-channel alarm
channel Boolean value output output
output
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 226
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Power 100–240 V AC; 200 W 100–240 V AC; 200 W 110–220 V AC; 200 W
supply
NOTICE
When the room temperature of the IVS1800-B08 is poor, an overheat alarm may
be generated when the IVS1800-B08 is fully configured with eight 6 TB hard disks.
You are advised to install a maximum of four 6 TB hard disks at different layers.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 227
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Light base The light base and light The light base and light are
requirement are integrated. integrated.
Electrical CLASS I -
insulation
class
7.3.15 eLight
● The eLight BOM number is 52220928 if an end door with a smart screen
(21502418) or an end door without a smart screen is installed. The eLight
system consists of the eLight power system, eLight actuator, eLight strip light,
and cables.
● The eLight BOM number is 52221774 if an end door with a smart screen
(21503054) is installed. The eLight system consists of the eLight actuator,
eLight strip light, and cables.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 228
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
NOTE
Non-associated Blue -
alarm severity NOTE
On the ECC800-Pro WebUI, set
Associated Alarm Severity to None.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 229
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
IP rating ≥ IP20
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 230
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Item Specifications
IP rating IP68
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 231
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
Data upload port One RS485 port. A maximum of four RS485 ports can be
connected to the UIM20A expansion module. A
maximum of one RS485 port can be connected to the
intelligent rPDU. Direct connection to the ECC800-Pro is
not supported.
7.4 NetEco
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 232
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
(NMSs). The system can be customized to support other protocols for the
access from different devices.
7.4.2.1 Server
The NetEco can be deployed on one of the following servers according to the
management capability requirement.
Model Configuration
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 233
FusionModule2000 6.0 Smart Modular Data Center
Product Description 7 Management System
7.5 iManager-M
The iManager-M system monitors the status of the entire network on the GIS
home page. After an abnormal site is detected, you can double-click it to access
the site monitoring page. Information about environment, energy consumption,
key devices, alarm, and security monitoring is provided on the site monitoring
page without requiring additional hardware.
● Environment monitoring: Monitors the temperature, humidity, water, and
smoke.
● Key device monitoring: Monitors the UPS, air conditioners, and related power
distribution devices in real time, and displays the energy flow diagram and air
conditioner link diagram.
● Alarm monitoring: Displays site alarm information in real time and quickly
locates device faults.
● Security monitoring: Monitors the cabinet door status and cameras in sites.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 234
FusionModule2000 6.0 Smart Modular Data Center
Product Description 8 Surge Protection and Grounding System
The surge protection and grounding system consists of the surge protection
solution and grounding solution.
Figure 8-1 M-shaped (grid) grounding solution for a dual-row aisle containment
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 235
FusionModule2000 6.0 Smart Modular Data Center
Product Description 8 Surge Protection and Grounding System
1. Each cabinet in the smart module connects to the nearest ground grid using
ground cables with the minimum cross-sectional area of 16 mm2.
2. Use 100 x 0.3 copper foils or copper braids with a cross-sectional area of 25
mm2 for the equipotential bonding grid. Use 30 x 3 copper strips for the
equipotential bonding bar based on the customer's configurations.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 236
FusionModule2000 6.0 Smart Modular Data Center
Product Description 9 Integrated Cabling System
The integrated cabling system of the smart module includes cable routing devices
and cables.
Cable Troughs
Cable troughs are installed on the top of cabinets for routing cables. There are
two types of cable troughs: signal cable troughs and power cable troughs.
If a dual-row aisle containment is equipped with one PDF and one network
cabinet, power cables need to be routed to the other end of the module through
the control skylight on the top of the PDF while signal cables need to be routed to
the other end of the module through the control skylight on the top of the
network cabinet.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 237
FusionModule2000 6.0 Smart Modular Data Center
Product Description 9 Integrated Cabling System
(1) Network cabinet (2) Optical fiber cables (3) Signal cables
Cables
● The power cables include power cables to the UPS, battery cabinet, smart
cooling product, and rPDU.
● The ground cables include ground cables to the PDF, battery cabinet, and IT
cabinet.
● The monitoring cables include monitoring cables to the smart cooling
product, UPS, and video devices, access control alarm cables, cables in the
network cabinet, and various sensor cables.
● The cables to auxiliary fire control components include cables to the alarm
beacon and FusionModule Actuator.
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 238
FusionModule2000 6.0 Smart Modular Data Center
Product Description A Acronyms and Abbreviations
A
AC alternating current
ATS auto transfer switch
B
BCB battery circuit breaker
BIB battery control I/O board
BIM battery interface module
BSPP British Standard Pipe Parallel Thread
C
CAN controller area network
CE Conformité Européenne
CFD computational fluid dynamics
CIM communication interface module
D
DC direct current
E
EC electronic commutation
ECC energy control center
ETH Ethernet
F
FE fast Ethernet
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 239
FusionModule2000 6.0 Smart Modular Data Center
Product Description A Acronyms and Abbreviations
IC integrated circuit
IDC Internet data center
IDS integrated data-center solution
IT Internet technology
L
LCD liquid crystal display
LED light emitting diode
M
MTBF mean time between failures
MTTR mean time to repair
N
NTC negative temperature coefficient
P
PDU power distribution unit
PE protective earthing
POE power over Ethernet
PUE power usage effectiveness
R
RCCB residual current circuit breaker
S
SD Secure Digital Memory
SIM subscriber identity module
SNMP Simple Network Management Protocol
SPD surge protective device
U
USB Universal Serial Bus
UPS uninterruptible power system
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 240
FusionModule2000 6.0 Smart Modular Data Center
Product Description A Acronyms and Abbreviations
V
VCN video cloud node
W
WiFi Wireless Fidelity
Issue 06 (2023-11-30) Copyright © Huawei Digital Power Technologies Co., Ltd. 241