0% found this document useful (0 votes)
49 views36 pages

Manual Ilia en

Uploaded by

Shakee Shk
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
49 views36 pages

Manual Ilia en

Uploaded by

Shakee Shk
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 36

MANUALE

USAGE ANDdi
INSTALLAZIONE
INSTALLATION
e MANUTENZIONE
GUIDE
CONTENTS

ILIA mod. ERHSO712 (Transmitter-Receiver version) Pagg. 2/10


Basic characteristics ..................................................................................................... 3
Product characteristics ................................................................................................. 3
Working Principle .......................................................................................................... 4
Calibration and assembly procedure ............................................................................ 5
Main calibration procedures ......................................................................................... 6
Procedure for further adjustment .................................................................................. 7
Technical features ........................................................................................................ 8
Diaphragm setting ........................................................................................................ 9

ILIA mod. ERRHSO712 (Reflection version) Pagg. 12/21


Basic characteristics ................................................................................................... 14
Product characteristics ............................................................................................... 14
Working Principle ........................................................................................................ 15
Calibration and assembly procedure .......................................................................... 16
Main calibration procedures ....................................................................................... 17
Procedure for further adjustment ................................................................................ 18
Technical features ...................................................................................................... 19
Diaphragm setting ...................................................................................................... 20

CONTROLLER mod. CSRLS Pagg. 22/30


Display message and programming step .............................................................. 23-30
Sensibility Setting
Modify of Transmitter level and check of the signal level received
Auto calibration of Transmitter level
Alarm Auto test
Alarm Reset
System Configuration
Modify of the password for menu access
Display messages for events
Typical connections .................................................................................................... 31
Board connections ...................................................................................................... 32
Dip-switch for the address of the smoke beam detectors .......................................... 33

MAINTENANCE Pagg. 34

ADDIZIONAL CONTROLS Pagg. 34


HIGH SENSITIVITY LINEAR BEAM DETECTOR

MODEL ERHS0712
TRANSMITTER – RECEIVER VERSION

rev. 00 del 16.07.2009 2/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
Basic characteristics

 Detector: Project, Technology, Design and Production fully made in Italy


 Suitable for use in all civil and industrial premises
 Very easy to install and program
 Low cost for mounting, cabling and maintenance
 The Detector can be installed horizontally or vertically and can work at any angle
 Micrometric adjustment for alignment
 Integrated diaphragm with a wide range of adjustment

 Control Unit for programming, calibration and performing of remote test on line
beam detectors.
 Basic configuration for two Detectors even of different types
Transmitter/Receiver or Reflection
 Expansion board for connection up to 3 to 8 detectors and line loop closure
(optional)
 Ground level installation for the Control Unit
 Alarm and Fault outputs can be programmed for each individual detector
 Operational access to keyboard protected by password
 Control Unit or Control Panel reset facility

 Base can also be installed separately from the detector for the pre wiring
 Plug-in base to detector connection
 Base complete with back up board short circuit isolator to ensure continued
work even after a short circuit

 Special Allen Key suitable for mechanical alignment, diaphragm regulation,


unhook of detector base and open/close of control unit

Product characteristics

• Standard EN 54/12
• Protection rating IP65 (Transmitter Unit, Receiver Unit and Controller Unit)
• RoHS Compatibility
• Operating distance 10 ÷ 200 m for Tx/Rx model for maximum permitted cover 1600
sq meters for detector - according to TS 54-14
• Width of cover up to 15 m according to T.S. European EN 54-14
• Connections to 4 serial line conductor RS485
• Local and remote maintenance request
• Automatic threshold compensation
• Angle misalignment ± 1degree max
• Complete directional stability over time
• Sensitivity adjustable and selectable over a wide range, using the control unit model
CSRLS
• Automatic reset of detector after break in infrared beam
• Self tester for RS485 communication
• Fault relay output delayed up to 90 seconds
• Power supply 12-24 V DC auto selected

3/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
WORKING PRINCIPLE

The ILIA MODEL ERHS0712 detector consists of a Transmitter Unit, a Receiver Unit
and a Beam Controller Unit for programming, setting and testing. The Beam Controller
Unit is used to remotely manage the detector or detectors in the field using a single line.
The Beam Controller Unit is put at a place on ground level from where the detector can
be controlled without having to climb up to the detector, as regards all normal operations.
The Beam Controller Unit is made of plastic, has a keyboard for programming and a
backlight 16x2 display.
By entering a password of 4 digits you can program the system from ground level to
determine the detector's signal level, to check environmental disturbances, to set the
required thresholds based on these and to check the alarm threshold; the default
password FFFF can be changed by the programmer by following the instructions in the
remote programming menu.
The system configuration menu becomes available when you just touch any of the 5
buttons on the keyboard and by then entering the default password FFFF on the first
programming session, customising the password from then on (the password can be
reset if lost or forgotten by use of the beam controller Unit reset hardware).
The Beam Controller Unit electronic base permits direct connection of two detector units;
by means of an expansion circuit, it is able to pilot up to 8 detectors connected together
even in a closed loop. This permits continued proper working even if the cables are cut or
in the case of a short circuit. There are also programmable relay contacts in the Unit for
each individual detector connected. These relays can have their polarity reversed with
the use of the software and permit the transmission to a single central unit of the
individual alarm, fault and maintenance request signals. Any breakdown in
communication between Beam Controller Unit and the detectors connected to it will be
immediately signalled by the simultaneous flashing of the yellow Led and the green Led
on the Transmitter and the Receiver, as well as being indicated on the display of the
Beam Controller Unit itself.
The working voltage of the equipment is between 12 and 24 Volts without switching
(± 20%). The Transmitter Unit emits a beam of modulated infrared light at 1 KHz in the
form of a cone which crosses the space under surveillance to reach the Receiver Unit. As
the modulated infrared crosses the environment under surveillance, it collects along its
path all information that could suggest the start of a fire. The events that intervene

rev. 00 del 16.07.2009 4/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
between Transmitter and Receiver affect the infrared carrier, alternatively optically
modulating it in frequency and in amplitude.
The Receiver Unit demodulating from the infrared received the information that is
optically gathered, transforms each symptom of a possible fire into corresponding
electrical signals referable to “smoke”.
Such signals are electronically assessed by means of a special algorithm local to the
Receiver Unit, and are transmitted to the Beam Controller Unit. All the units have a
microcontroller that carries out a full scan of the working mode, i.e. not only of the alarm,
but also of faults, blinding and maintenance requests. The messages are clearly given on
the display and repeated by the four leds on the Unit, as well as with the local led’s on
every individual piece of equipment. A message on the display will indicate the type of
event and the detector number.
Note: The Dip-Switch must always be used during installation to determine the
detector address number.
The connection of one or more detectors is with leads of a minimum cross-section, in
accordance with current regulations, of 0.5 mm2. The detection of the start of a fire will
mean information is sent from the field (detector) to the Beam Controller Unit which will in
turn send an alarm signal to a central control unit. System resetting is possible both from
the Beam Controller with a dedicated command or from the central control unit. The
Beam Controller Unit can be used to set the blinding fault relay switching delay for every
individual detector, for times from 0 to 90 seconds.
The Receiving Unit (RX) has an internal diaphragm that means it is possible, following
the instruction to mechanically set for the use of a diaphragm filter, to solve
environmental problems in particular architectural situation where there are awkward
reflections or the optical beam must work in limited spaces.

5/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
CALIBRATION AND ASSEMBLY PROCEDURE

NOTE: Use the SETRONIC "Allen Key" for the opening and closing of the detector
and the mechanical alignment of the equipment.

1. Fix the socket connection of the detector and carry out the wiring of the line (power
supply and serial line).

2. Set the address of the detector between 1 and 8 consequently using the Dip-Switch
according to the table on page 30th

NOTE: The Dip-Switch 4 must be set to ON only in the last detector connected to the
line open. It must also be set with a single detector.

3. Insert the connector plug on the bottom of the detector into the socket until you hear a
"click", then lock the unit to the socket by rotating the hooks with the appropriate Allen
key and guide it to the paired device from the opposite.

4. Repeat above operations for all the detectors installed. Verify that the Transmitter and
Receiver pair have the same address.

5. Power the system via the controller and set the number of detectors connected and
the configuration of connection to serial line. The controller also allows the use of the
two serials in an independent manner, as if they were two separate lines open. In this
case, the addresses remain the same from set 1 to 8, but you set the end of the line
(Dip-Switch 4 to ON) of both the last detector.

6. At this point the green led of the two units of detectors and you must switch controller,
a short flash confirms the continuous scanning of the line. If the condition of led
flashing green and yellow with flashes of about 2 sec., means that there is no serial
communication (check the wiring for possible errors or inversions) or incorrect
configuration of the switch address.

7. Orient the Transmitter through the Allen key adjustment in order to obtain the led
blinking yellow.

8. Starting i.e. to the left to move the unit slowly until the yellow led stops flashing. Then
rotate the unit to the right (the yellow led starts to flash again). Count how many turns
of the key are made to obtain the yellow led off to the opposite side. Reposition the
center of movement found by dividing in half the number of revolutions counted. The
yellow led continues to blink.

9. Do the same for the vertical axis.

10. Orient the Receiver following the same steps 7, 8, 9.

11. Perform the calibration by the ground controller to follow the menu <Autoadjust>.

12. Now cover the Transmitter Unit or Receiver Unit with a card or opaque object. When
you cover the Unit check that the yellow led remains continuously on.

rev. 00 del 16.07.2009 6/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
MAIN CALIBRATION PROCEDURES

1. Enter menu:
- from the main screen, press OK;
- enter the password, using the direction buttons ▲►▼◄; press OK;

2. Set up detection lines:


- press ► or ◄ until you get to < System Setup >; press OK;
- press ▲ or ▼ to edit the number of the detection lines; press OK;
- press ▲ or ▼ to change the delay time for fault outputs; press OK;
- press ▲ or ▼ to change the configuration of fault outputs; press OK;
- press ▲ or ▼ to set the <Com line> configuration; press OK;
- press OK to skip debug function.

3. First calibration of the detection lines (after mechanical adjustment of the detectors):
- press ► or ◄ until you get to < AUTO Adjust. >; press OK;
- press ▲ or ▼ to change the number of the detection line to be worked on; press OK;
- wait until the TX value stabilises (about 1 minute) and press OK;
- the value of the RX must be about 100%
- press OK to confirm the setting.

4. Calibration of detection lines (with the barriers already previously installed):


- press ► or ◄ until you get to < AUTO Adjust. >; press OK;
- press ▲ or ▼ to change the number of the detection line to be worked on; press OK;
- wait until the TX value stabilises (about 1 minute) and press OK;
- the value of the RX must be about 100%
- press OK to confirm the setting.

5. Adjustment of detection line sensitivity:


- press ► or ◄ until you get to < sensitivity >; press OK;
- press ▲ or ▼ to change the number of the detection line to be worked on; press OK;
- read the Detec value to quantify environmental disturbances for 1 to 2 minutes;
- press ▲ or ▼ to change the smoke threshold value (the value of the highest
disturbance value seen by Detec shall be less than the threshold setted) ; press OK;
- read the Detec value to quantify environmental disturbances for 1 to 2 minutes;
- press ▲ or ▼ to change the fire threshold value (the value of the highest disturbance
value seen by Detec shall be less than the threshold setted);
- press OK to confirm the setting.

7/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
PROCEDURE FOR FURTHER ADJUSTMENT

1. Enter menu:
- from the main screen, press OK;
- enter the password, using the direction buttons ▲►▼◄; press OK;

2. Checking the signal and manual adjustment of detection lines


- press ► or ◄ until you get to < adjustment >; press OK;
- press ▲ or ▼ to edit the number of the detection lines; press OK;
- read the RX signal; it must normally be about 100%;
- press ▲ or ▼ to change the TX value;
- press OK to confirm the setting.

3. Alarm simulation for detection lines:


- press ► or ◄ until you get to < Alarm Test >; press OK;
- press ▲ or ▼ to edit the number of the detection lines; press OK;
- press OK to start the alarm testing;
- wait for the barrier alarm;
- press OK to reset the barriers;

4. Reset the detection lines alarm:


- press ► or ◄ until you get to < Reset Alarm >; press OK;
- press OK to reset the alarm;

5. Change the password for access to the menu:


- press ► or ◄ until you get to <Change password>; press OK;
- enter the new password, using the direction buttons ▲►▼◄;
- press OK to confirm the setting.

rev. 00 del 16.07.2009 8/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
TECHNICAL FEATURES

ILIA High Sensitivity Transmitter / Receiver Linear Beam Detector model ERHS0712

Working temperature -20°/+65° C


Storage temperature -20°/+70° C
Electromagnetic disturbance EMC test up to 30 Volt/m
Power supply 12/24 V d.c. (± 20%) without switching
Cable type minimum section of 0,5 mm² with 4 wires
type CEI 20-22
Maximum cable length max 1200 m from Control Unit to line detectors
(double in loop configuration)
Operating distance from 10 to 200 meters
Maximum permitted cover 1600 sq metres for detector - according to TS 54-14
Width cover max 15 meters - according to TS 54-14
Size 162x145x193 mm
Weight Tx Unit 735g, Rx Unit 775g
Angle misalignment ± 1 degree max for Tx Unit and Rx Unit
Detector protection rating IP65
RAL Colour 5004

Beam Controller Unit mod.: CSRLS

Working temperature -20°/+65° C


Storage temperature -20°/+70° C
Power supply 12/24 V dc (± 20%)
Maximum cable length Max 1000 m with 1 sq mm cable – Type CEI 20-22
to Control Panel
Cable section per output max 0,5 sq mm
Contact capacity Alarm/Fault optorelay max 150 mA
Size 145x177x68 mm
Weight 375g
Connectable detectors 1 to 8
Control Unit protection rating IP65

Current absorption

POWER SUPPLY 24V ± 20% 12V ± 20%


Stand By max 048 mA max 098 mA
1 DETECTOR CONNECTED
Typical (allarm or fault relay) max 050 mA max 100 mA
Stand By max 261 mA max 502 mA
8 DETECTORS CONNECTED
Typical (allarm or fault relay) max 270 mA max 512 mA

9/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
DIAPHRAGM SETTING FOR MODEL ERHS0712
has an internal 6 (0 Totally open ÷ 5 mac closure) position diaphragm that can be used where problems
arise in the protected environment, for example the presence of direct sunlight or awkward reflections or flare.
The diaphragm permits short distance adjustments and/or to have the beam pass through narrow spaces or in
any case to limit its size.

Receiver Unit Fix the key Turn clockwise

SETTING

Diaphragm position 0 Diaphragm position 1 Diaphragm position 2


Distance from 30 m up to 200 m Distance from 50 m up to 180 m Distance from 40 m up to 170 m

Diaphragm position 3 Diaphragm position 4 Diaphragm position 5


Distance from 30 m up to 150 m Distance from 15 m up to 120 m Distance from 10 m up to 80 m

rev. 00 del 16.07.2009 10/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
ERRHS0712
HIGH SENSITIVITY REFLECTION SYSTEM DETECTOR

MODEL ERRHS0712

rev. 00 del 16.07.2009 12/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
REFLECTION VERSION

Basic characteristics

 Detector: Project, Technology, Design and Production fully made in Italy


 Suitable for use in all civil and industrial premises
 Very easy to install and program
 Low cost for mounting, cabling and maintenance
 The Detector can be installed horizontally or vertically and can work at any angle
 Micrometric adjustment for alignment
 Integrated diaphragm with a wide range of adjustment

 Control Unit for programming, calibration and performing of remote test on line
beam detectors.
 Basic configuration for two Detectors even of different types
Transmitter/Receiver or Reflection
 Expansion board for connection up to 3 to 8 detectors and line loop closure
(optional)
 Ground level installation for the Control Unit
 Alarm and Fault outputs can be programmed for each individual detector
 Operational access to keyboard protected by password
 Control Unit or Control Panel reset facility

 Base can also be installed separately from the detector for the pre wiring
 Plug-in base to detector connection
 Base complete with back up board short circuit isolator to ensure continued
work even after a short circuit

 Special Allen Key suitable for mechanical alignment, diaphragm regulation,


unhook of detector base and open/close of control unit

Product characteristics

• Standard EN 54/12
• Protection rating IP65 (Transmitter- Receiver Unit, Reflection Unit and Controller Unit)
• RoHS Compatibility
• Operating distance 10 ÷ 150 m for Reflection model for maximum permitted cover
1600 sq meters for detector - according to TS 54-14
• Width of cover up to 15 m according to T.S. European EN 54-14
• Connections to 4 serial line conductor RS485
• Local and remote maintenance request
• Automatic threshold compensation
• Angle misalignment: ±1 grado max TRx Unit
±5 gradi max Ref Unit
• Complete directional stability over time
• Sensitivity adjustable and selectable over a wide range, using the control unit model
CSRLS
• Automatic reset of detector after break in infrared beam
• Self tester for RS485 communication
• Fault relay output delayed up to 90 seconds
• Power supply 12-24 V DC auto selected

13/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
WORKING PRINCIPLE

The ILIA mod. MODEL ERRHS0712 detector consists of a Transmitter/Receiver Unit,


with a Reflection Unit and a Beam Controller Unit for programming, setting and testing.
The Beam Controller Unit is used to remotely manage the detector or detectors in the
field using a single line. The Beam Controller Unit is put at a place on ground level from
where the detector can be controlled without having to climb up to the detector, as
regards all normal operations. The Beam Controller Unit is made of plastic, has a
keyboard for programming and a backlight 16x2 display.
By entering a password of 4 digits you can program the system from ground level to
determine the detector's signal level, to check environmental disturbances, to set the
required thresholds based on these and to check the alarm threshold; the default
password FFFF can be changed by the programmer by following the instructions in the
remote programming menu.
The system configuration menu becomes available when you just touch any of the 5
buttons on the keyboard and by then entering the default password FFFF on the first
programming session, customising the password from then on (the password can be
reset if lost or forgotten by use of the Beam Controller Unit's reset hardware).
The Beam Controller Unit electronic base permits direct connection of two detector units;
by means of an expansion circuit, it is able to pilot up to 8 detectors connected together
even in a closed loop. This permits continued proper working even if the cables are cut or
in the case of a short circuit. There are also programmable relay contacts in the unit for
each individual detector connected. These relays can have their polarity reversed with
the use of the software and permit the transmission to a single central unit of the
individual alarm, fault and maintenance request signals. Any breakdown in
communication between Beam Controller Unit and the detectors connected to it will be
immediately signalled by the simultaneous flashing of the yellow Led and the green Led
on the Transmitter and the Receiver, as well as being indicated on the display of the
Beam Controller Unit itself.
The working voltage of the equipment is between 12 and 24 Volts without switching
(± 20%). The Transmitter/Receiver Unit emits a beam of modulated infrared light at
1 KHz in the form of a cone which crosses the space under surveillance to reach the
Reflection Unit. As the modulated infrared crosses the environment under surveillance, it
collects along its path all information that could suggest the start of a fire. The events that

rev. 00 del 16.07.2009 14/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
intervene between Transmitter/Receiver Unit and Reflection Unit affect the infrared
carrier, alternatively optically modulating it in frequency and in amplitude.
The Transmitter/Receiver Unit demodulating from the infrared received the information
that is optically gathered, transforms each symptom of a possible fire into corresponding
electrical signals referable to “smoke”.
Such signals are electronically assessed by means of a special algorithm local to the
Transmitter/Receiver Unit, and are transmitted to the Beam Controller Unit. All the units
have a microcontroller that carries out a full scan of the working mode, i.e. not only of the
alarm, but also of faults, blinding and maintenance requests. The messages are clearly
given on the display and repeated by the four leds on the Unit, as well as with the local
led’s on every individual piece of equipment. A message on the display will indicate the
type of event and the detector number.
Note: The Dip-Switch must always be used during installation to determine the
detector address number.
The connection of one or more detectors is with leads of a minimum cross-section, in
accordance with current regulations, of 0.5 mm2. The detection of the start of a fire will
mean information is sent from the field (detector) to the Beam Controller Unit which will in
turn send an alarm signal to a central control unit. System resetting is possible both from
the Beam Controller Unit with a dedicated command or from the central control unit. The
Beam Controller Unit can be used to set the blinding fault relay switching delay for every
individual detector, for times from 0 to 90 seconds.
The Transmitter/Receiver Unit (TRX) has an internal diaphragm that means it is possible,
following the instruction to mechanically set for the use of a diaphragm filter to solve
environmental problems in particular architectural situation where there are awkward
reflections or the optical beam must work in limited spaces.

15/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
CALIBRATION AND ASSEMBLY PROCEDURE

NOTE: Use the SETRONIC "Allen Key" for the opening and the closing of the detector
and the mechanical alignment of the equipment.

1. Fix the socket connection of the detector and carry out the wiring of the line (power
supply and serial line).

2. Set the address of the detector between 1 and 8 consequently using the Dip-Switch
according to the table on page 30th

NOTE: The Dip-Switch 4 must be set to ON only in the last detector connected to the
line open. It must also be set with a single detector.

3. Insert the connector plug on the bottom of the detector into the socket until you hear
a "click", then lock the unit to the socket by rotating the hooks with the appropriate
Allen key and guide it to the paired device from the opposite.

4. Repeat above operations for all the detectors are installed and the units of
Reflection (Ref) omitting the part relating to the connection line.

5. Power the system via the controller and set the number of detectors connected and
the configuration of connection to serial line. The controller also allows the use of
the two serials in an independent manner, as if they were two separate lines open.
In this case, the addresses remain the same from set 1 to 8, but you set the end of
the line (Dip-Switch 4 to ON) of both the last detector.

6. At this point the green led of the detector unit and the controller should turn on, a
brief flash confirms the continuous scanning of the line. If the condition of led
flashing green and yellow with flashes of about 2 sec., means that there is no serial
communication (check the wiring for possible errors or inversions) or incorrect
configuration of the switch address.

7. Orient the TRX by Allen key adjustment in order to obtain the led blinking yellow.

8. Starting with an example to the left to move the unit slowly until the yellow led stops
blinking. Then rotate the unit to the right (the yellow led starts to flash again). Count
how many turns of the key are made to obtain the yellow led off to the opposite side.
Reposition the center of movement found by dividing in half the number of
revolutions counted. The yellow led continues to blink.

9. Do the same for the vertical axis.

10. Point the unit of reflection following the same steps 7, 8, 9.

11. Perform the calibration by the ground controller to follow the menu <Autoadjust.>.

12. Now cover the Reflection Unit with a card or opaque object. When you cover the
Reflection Unit check that the yellow led on the Transmitter-Receiver Unit remains
continuously on.

rev. 00 del 16.07.2009 16/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
MAIN CALIBRATION PROCEDURES

1. Enter menu:
- from the main screen, press OK;
- enter the password, using the direction buttons ▲►▼◄; press OK;

2. Set up detection lines:


- press ► or ◄ until you get to < System Setup >; press OK;
- press ▲ or ▼ to edit the number of the detection lines; press OK;
- press ▲ or ▼ to change the delay time for fault outputs; press OK;
- press ▲ or ▼ to change the configuration of fault outputs; press OK;
- press ▲ or ▼ to set the <Com line> configuration; press OK;
- press OK to skip debug function.

3. First calibration of the detection lines (with mechanical adjustment of barriers):


- press ► or ◄ until you get to < AUTO Adjust. >; press OK;
- press ▲ or ▼ to change the number of the detection line to be worked on; press OK;
- wait until the TX value stabilises (about 1 minute) and press OK;
- the value of the RX must be about 100%
- press OK to confirm the setting.

4. Calibration of detection lines (with the barriers already previously installed):


- press ► or ◄ until you get to < AUTO Adjust. >; press OK;
- press ▲ or ▼ to change the number of the detection line to be worked on; press OK;
- wait until the TX value stabilises (about 1 minute) and press OK;
- the value of the RX must be about 100%
- press OK to confirm the setting.

5. Adjustment of detection line sensitivity:


- press ► or ◄ until you get to < sensitivity >; press OK;
- press ▲ or ▼ to change the number of the detection line to be worked on; press OK;
- read the Detec value to quantify environmental disturbances for 1 to 2 minutes;
- press ▲ or ▼ to change the smoke threshold value (the value of the highest
disturbance value seen by Detec shall be less than the threshold setted) ; press OK;
- read the Detec value to quantify environmental disturbances for 1 to 2 minutes;
- press ▲ or ▼ to change the fire threshold value (the value of the highest disturbance
value seen by Detec shall be less than the threshold setted);
- press OK to confirm the setting.

17/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
PROCEDURE FOR FURTHER ADJUSTMENT

1. Enter menu:
- from the main screen, press OK;
- enter the password, using the direction buttons ▲►▼◄; press OK;

2. Checking the signal and manual adjustment of detection lines


- press ► or ◄ until you get to < adjustment >; press OK;
- press ▲ or ▼ to edit the number of the detection lines; press OK;
- read the RX signal; it must normally be about 100%;
- press ▲ or ▼ to change the TX value;
- press OK to confirm the setting.

3. Alarm simulation for detection lines:


- press ► or ◄ until you get to < Alarm Test >; press OK;
- press ▲ or ▼ to edit the number of the detection lines; press OK;
- press OK to start the alarm testing;
- wait for the barrier alarm;
- press OK to reset the barriers;

4. Reset the detection lines alarm:


- press ► or ◄ until you get to < Reset Alarm >; press OK;
- press OK to reset the alarm;

5. Change the password for access to the menu:


- press ► or ◄ until you get to <Change password>; press OK;
- enter the new password, using the direction buttons ▲►▼◄;
- press OK to confirm the setting.

rev. 00 del 16.07.2009 18/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
TECHNICAL FEATURES

ILIA High Sensitivity Reflection Linear Beam Detector model ERRHS0712

Working temperature -20°/+65° C


Storage temperature -20°/+70° C
Electromagnetic disturbance EMC test up to 30 Volt/m
Power supply 12/24 V d.c. (± 20%) without switching
Cable type minimum section of 0,5 mm² with 4 wires
type CEI 20-22
Maximum cable length max 1200 m from Control Unit to line detectors
(double in loop configuration)
Operating distance from 10 to 150 meters
Maximum permitted cover 1600 sq metres for detector - according to TS 54-14
Width cover max 15 meters - according to TS 54-14
Size 162x145x193 mm
Weight TRx Unit 780g, Ref Unit 770g
Angle misalignment ± 1 degree max for TRx Unit
± 5 degree max for Ref Unit
Detector protection rating IP65
RAL Colour 5004, front cover 5005

Beam Controller Unit mod.: CSRLS

Working temperature -20°/+65° C


Storage temperature -20°/+70° C
Power supply 12/24 V dc (± 20%)
Maximum cable length Max 1000 m with 1 sq mm cable – Type CEI 20-22
to Control Panel
Cable section per output max 0,5 sq mm
Contact capacity Alarm/Fault optorelay max 150 mA
Size 145x177x68 mm
Weight 375g
Connectable detectors 1 to 8
Control Unit protection rating IP65

Current absorption

POWER SUPPLY 24V ± 20% 12V ± 20%


Stand By max 087 mA max 042 mA
1 DETECTOR CONNECTED
Typical (allarm or fault relay) max 089 mA max 045 mA
Stand By max 190 mA max 362 mA
8 DETECTORS CONNECTED
Typical (allarm or fault relay) max 200 mA max 372 mA

19/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
TECHNICAL FEATURES
DIAPHRAGM SETTING FOR MODEL ERRHS0712
has an internal 6 (0 Totally open ÷ 5 mac closure) position diaphragm that can be used where problems
arise in the protected environment, for example the presence of direct sunlight or awkward reflections or flare.
The diaphragm permits short distance adjustments and/or to have the beam pass through narrow spaces or in
any case to limit its size.

Transmitter / Receiver Unit Fix the key Turn clockwise

SETTING

Diaphragm position 0 Diaphragm position 1 Diaphragm position 2


Distance from 20 m up to 150 m Distance from 40 m up to 125 m Distance from 30 m up to 90 m

Diaphragm position 3 Diaphragm position 4 Diaphragm position 5


Distance from 20 m up to 80 m Distance from 15 m up to 65 m Distance from 10 m up to 50 m

rev. 00 del 16.07.2009 20/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
CSRLS
CONTROLLER FOR BEAM DETECTORS

MODEL CSRLS

rev. 00 del 16.07.2009 22/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
DISPLAY MESSAGE AND PROGRAMMING STEPS
To start the programming the displayed message must be the following:

SETRONIC Verona Main Screen


Normal Operation Normal Operation

1. Sensibility Setting

PRESS OK

Press the arrows ►◄ and moving the blinking cursor


Insert password by arrows ▲▼ it is possible to change the default
FFFF password that is FFFF The changes could be made
with the characters from 0 to 9 and from A to F

PRESS OK

If a wrong code is inserted, after the confirm with OK


Password error! the mistake message is displayed. Check the error
and repeat the procedure

With the right password the menu is available


< Sensibility >
PRESS OK

Press the arrows ▲▼ is setting the detector of which


< choose line > should be changed the sensitivity and read the noise
N.: x
PRESS OK

Loading data Waiting for the loading of the data


From device: x

Look the value of Detector for a couple of minutes and set a value higher that the
highest read. Repeat the operation as for SMOKE as for FIRE

Press the arrows ▲▼ SMOKE sensitivity will be set


Detec: x
Smoke: xxxx PRESS OK

Note: if the threshold of sensibility comes from the


value required by the Norm, you will see <Warn>
(for example Smoke: 284 Warn ).

23/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
Press the arrows ▲▼ FIRE sensitivity will be set
Detec: x
Fire: xxxx PRESS OK

When the threshold as been chosen and set… PRESS OK

Saving data... If the sensitivity has been changed will be displayed…

If any change has been made, (may be has been just


Data not changed made a check of the values) the message on the
Ok to exit display will be:

At the end of operation… PRESS OK

2. Modify of Transmitter level and check of the signal level received

PRESS OK

Insert password as for step 1


Insert Password
FFFF PRESS OK

< Sensibility > Menu access

Press one time ► to visualize on display:


< Adjustment >
PRESS OK

Press the arrows ▲▼ select the Detector which will


< choose line > be regulated the IR power transmission
N.: x
PRESS OK

Loading data Wait for the loading of the data


From device: x

rev. 00 del 16.07.2009 24/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
Press the arrows ▲▼ so can be increased or
Rx: XXX.X% decreased the value of the TX (strength of the IR
Tx: XXX.X% emitted). For a correct working of the Detector the
reception value RX must be around 100%.

When the setting is done… PRESS OK

Saving data... If the TX level has been changed will be displayed…

If any change has been made, (may be has been just


Data not changed made a check of the values) the message on the
Ok to exit display will be:

At the end of operation…PRESS OK

3. Auto calibration of Transmitter level

PRESS OK

Insert password as for step 1


Insert Password
FFFF PRESS OK

< Sensibility > Menu access

Press the arrow ► until to visualize on display:


< AUTO Adjust. >
PRESS OK

Press the arrows ▲▼ select the Detector which will


< choose line > be regulated the IR power transmission
N.: x
PRESS OK

Loading data Wait for the loading of the data


From device: x

25/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
Let the Detector level adjusting of the Transmitter is
around 100%, then press OK to save the level.
It is possible, when the value is tidy near the 100%
Rx: XXX.X% increased or decreased the value with the arrows
Tx: XXX.X% ▲▼so to take it up to the effective 100%. Avoid
carefully to set value Higher of 102% and under the
96%. If the 96% is not reachable it means that some
obstacle reduce the strength of the Infra red beam, or
the correct axis position has not been found.

When the detector is up to 100%… PRESS OK

Saving data...

4. Alarm Auto test

PRESS OK

Insert password as for step 1


Insert Password
FFFF
PRESS OK

< Sensibility > Menu access

Press the arrow ► until to visualize on display:


< Alarm Test >
PRESS OK

Press the arrows ▲▼ select the Detector which will


< choose line > be tested
N.: x
PRESS OK

Loading data Wait for the loading of the data


From device: x

Press OK to start the test and wait for the alarm signal
Press OK key (LED Alarm lighted)
to Test Alarm
rev. 00 del 16.07.2009 26/35
SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
Press OK to reset the Detector. In case that the reset
Press OK key in not working properly, wait for a minute and reset the
to Reset Alarm Alarm by the reset menu.

5. Alarm Reset

PRESS OK

Insert password as for step 1


Insert Password
FFFF PRESS OK

< Sensibility > Menu access menu

Press the arrow ► until to visualize on display:


< Reset Alarm >
PRESS OK

Press OK for the reset of all the Detector


Press OK key
to Reset Alarm PRESS OK

6. System Configuration

PRESS OK

Insert password as for step 1


Insert Password
FFFF PRESS OK

< Sensibility > Menu access

27/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
Press the arrow ► until to visualize on display:
< System Setup >
PRESS OK

Press the arrows ▲▼ it is selected the number of


Set number detector connected to the detection line. Press OK for
of Detector: x confirmation.
PRESS OK

Press the arrows ▲▼ and select the delay time from 0


Fault Delay sec to 90 sec for the activation of fault output. The
x seconds steps are of 30 sec.

PRESS OK

Fault Output Press the arrows ▲▼ and set the contact of the fault
Normal Open output normally close or normally open

PRESS OK
Press the arrows ▲▼ is activated (on) or deactivated
Com Line 2 (off) la second serial line (to be used only if the
OFF expansion module is inserted)

PRESS OK

Press the arrows ▲▼ is possible to set up the serial


Com Line Loop line as closed loop (close) or Open Error, if the wish is
Close to have two different stub lines with n detector
connected (function available only with expansion card
inserted).

PRESS OK

Press the arrows ▲▼ will be active (on) or not active


(off) the check control of the correct serial line
Com Error check communication.
OFF Note: to be used only if it is necessary make a check
of the line for some problems during the first
initialization.

PRESS OK

rev. 00 del 16.07.2009 28/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
7. Modify of the password for menu access

PRESS OK

Insert default password as for step 1


Insert Password
FFFF PRESS OK

If a wrong code is inserted, after the confirm with OK


Password error! the mistake message is displayed. Check the error
and repeat the procedure

< Sensibility > Menu access

Press the arrow ► until to visualize on display:


<Change Password
PRESS OK

Press the arrows ►◄ and moving the blinking cursor


Set NEW Password by arrows ▲▼ it is possible to change the default
FFFF password The changes could be made with the
characters from 0 to 9 and from A to F. Press OK for
confirm
PRESS OK

Password changed
OK to exit

PRESS OK

8. Display messages for events

 ALARM INDICATION:

Example with alarm on zone (detector) 1, 5 e 6 (the


Alarm:1---56-- dash shows the zone out of the incoming event)
Note: the Led ALARM is on and the output related to
the zone(s) is activated

29/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
 FAULT INDICATION:

Example with fault on zone (detector) 2 e 6 (the dash


Fault:-2---6-- shows the zone out of the incoming event)
Note: the led TROUBLE is on and there is the change
of the status of the related output. (open/close and/or
timing of delay as for programmed configuration.

 MAINTENANCE REQUEST:

Example with maintenance request on zone (the dash


Maint:----5--- shows the zone out of the incoming event)
Note: the Led MAINTENANCE is on and there is the
change of the status of the related fault output
(open/closed as for chosen configuration)

 INDICATION OF PROBLEMS ON SERIAL LINE:

Example of loop interrupted. In this condition, the


Detector from 1 to 3 will continue to work on serial line
A-Err:123----- A (zone 1, 2 e 3). The Detectors related to zone from
B-Err:---45678 4 to 8 will continue to work on serial line B. The dash
will indicated where the line is cut.
Note: Led TROUBLE is on and will be activated the
output of zone 1.

Example of interruption of the loop between TX and


RX of zone (detector) 3. This message is shown only
when the line is cut between Transmitter and
A-Err:123----- Receiver.
B-Err:--345678 Note: the Led TROUBLE is on and if the line i san
open one all the output of the detectors from 3 to 8
will be activated, if it is a closet loop only the output 1
will be activated, and in any case the system is still
working.

Example with only one detector really connected and


C-Err:-2345678 system configuration with 8 Detectors.
Fault:-2345678 Note: Led TROUBLE is on and will be activated the
output of zone 1.

NOTICE: in all conditions above mentioned, in case of an alarm of one or more zone
(detector), the first line of the display will always show the alarm condition.
rev. 00 del 16.07.2009 30/35
SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
TYPICAL CONNECTIONS

31/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
BOARD CONNECTIONS

rev. 00 del 16.07.2009 32/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
DIP-SWITCH FOR THE ADDRESS OF THE SMOKE BEAM DETECTORS

DIP-SWITCH SW1 SW2 SW3 ADDRESS

ON ON ON ZONE 1

OFF ON ON ZONE 2

ON OFF ON ZONE 3

OFF OFF ON ZONE 4

ON ON OFF ZONE 5

OFF ON OFF ZONE 6

ON OFF OFF ZONE 7

OFF OFF OFF ZONE 8

NOTE: THE DIP-SWITCH 4 MUST BE SET IN ON POSITION ONLY ON THE LAST


DETECTOR CONNECTED ON A STUB LINE. MUST BE SET ALSO IF ONLY
ONE DETECTOR IS CONNECTED.

33/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
MAINTENANCE

Normal conditions of installation require maintenance intervals as indicated by current


regulations (UNI9795 of 2005, point 9.2 UNI 11224).
These intervals, on the basis of every 5 months, may sometimes be more frequent
depending on the many kinds of conditions of application of the devices, especially in
industrial environments where there may be stationary dust and steam or the products of
various production stages.

PROCEDURE

The maintenance of the ILIA line does not require particular equipment and is both simple
and fast.
The operation is carried according to the following procedure:

1. Clean the front cover with water and/or neutral soap without the use of abrasive
cloths. If the surfaces are very scratched, yellowed or significantly dimmed, they
must be replaced as this may jeopardise the proper optical working of the detector.
2. With a soft cloth clean the outer surface of the front cover (Transmitter Unit,
Receiver Unit or Transmitter-Receiver Unit and Reflection Unit).
3. Check the correct infrared signal level trough the menu < adjustment >, observing
conformity of the Led signals. It is advisable in any case to adjust the level of Rx at
100%. If the value of the Rx is too low, repeat the alignment procedure until
saturation point, and repeat the <Autoadjust> procedure.
4. Check the Alarm conditions, the Fault conditions and the corresponding outputs,
following “Alarm Test” and “Fault Test” procedures as set forth in the chapter
“CALIBRATION AND ASSEMBLY PROCEDURE” at page 5 or 14.

ADDITIONAL CONTROLS

SIGNAL DROP
If the infrared signal carried emitted by the detector tends over times to fall in intensity, the
system will carry out a proportional up rating by way of long term self-regulated
compensation). If the infrared signal falls to the minimum set threshold due to the build up of
dust or settling of the building structure to which the equipment is fastened, an green Led will
flash locally as a warning. The consequent opening of the fault contact will send the detector
control unit a maintenance request.

INSUFFICIENT SIGNAL / FAULT


When the infrared signal emitted by the detector falls below a minimum level or is interrupted
by an obstacle, the “fault” contact will open, rather than that of “fire alarm”.
When the correct signal level has returned or the obstacle removed the detector will return to
normal working in less than one second. The detection units currently have memory
retention also of fault conditions so if the detector comes immediately back into service, on
removal of the obstacle it must always be checked that the control unit locally resets the fault
signal, whether it be visual or sound.

ALARM
A red Led will indicated the start of a fire detection without enabling an output. After a certain
analysis time, typically 16 seconds, the red Led will start flashing and the output will be
enabled to signal alarm confirmation.

rev. 00 del 16.07.2009 34/35


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com
You are advised that as Setronic Verona constantly strives to improve its
products it reserves the right to make any changes it considers necessary
without prior warning. The same reservation applies to any corrections of
printing errors including of details and measurements that may have found their
way into this booklet.
Any recommendations made in this booklet, must be considered as replaced
by any conflicting Italian or European regulations that may come into force in
the future, as of the date these come into force.
Since the products herein are sold outside the country in which they are
manufactured, we must point out that any installation regulations in force in the
country of installation must be followed, even where they do not accord with
our suggestions. We shall consider any such regulations as having been
followed, as from the date they come into force.

Keep this booklet close to hand for future reference.


The information contained in this booklet is available in PDF files at our
website: www.setronicverona.com

Copyright 2009 Setronic Verona S.r.l.

Setronic is the sole owner of the data and images contained in this booklet. It is
expressly forbidden to duplicate, in whole or in part, including in digital form,
the images and/or data without formal prior authorisation from our Company.
Legal action will be taken in case of infringement.
The products described herein are guaranteed for one year. Our Company’s
contractual guarantee terms are available on request and run from the date of
delivery of the goods. The normally and universally used guarantee terms
apply to the products described.

SETRONIC Verona S.r.l.


Via F. Da Levanto, 14/b B.V.
37138 VERONA (Italy)
Tel. +39-0458347777 Kerkweg 70
Fax +39-0458347778 6155 KN Puth (NL)
www.setronicverona.com Tel.: +31 (0)46 443 55 77
E-mail: [email protected] Fax: +31 (0)46 443 04 82
E-mail: [email protected]
Internet: www.astec.nl

35/35 rev. 00 del 16.07.2009


SETRONIC Verona Srl – Via F. Da Levanto 14B – 37138 Verona www.setronicverona.com

You might also like