File E300 Electronic Overload Relays 193-SG010 EN 1
File E300 Electronic Overload Relays 193-SG010 EN 1
File E300 Electronic Overload Relays 193-SG010 EN 1
What’s Inside
Topic Page
Bulletin 193/592-E300 Overview 3
Bulletin 193/592-E300 Product Selection 11
Sensing Modules 11
Control Modules 12
Accessories 13
Bulletin 193/592-E300 Specifications 15
Bulletin 193/592-E300 Approximate Dimensions 25
NOTE: Your order must include 1) the Cat. No. of the sensing module, control module, and communication module selected,
and 2)if required, Cat. No. of any accessories.
Product Overview
The E300 consists of three modules: sensing, control and communications. Users have choices in each of the three with
additional accessories to tailor the electronic overload for their application’s exact needs.
Sensing Module
Sensing Options
• Voltage/current/ground fault
• Current/ground fault
• Current
Control Module
I/O I/O and Protection(1)
Control Voltage
Inputs Relay Outputs Inputs Relay Outputs
110…120V AC, 50/60 Hz 4 3 2 2
220…240V AC, 50/60 Hz 4 3 2 2
24V DC 6 3 4 2
(1) Includes PTC thermistor and external ground fault.
Communication Module
• EtherNet/IP
Thermal Overload
Thermal Utilization
The E300 Electronic Overload Relay provides overload protection through true RMS current measurement of the individual
phase currents of the connected motor. Based on this information, a thermal model that simulates the actual heating of the
motor is calculated. Percent of thermal capacity utilization (%TCU) reports this calculated value and can be read via a
communications network. An overload trip occurs when the value reaches 100%.
Adjustable Settings
Thermal overload protection setup is accomplished simply by programming the motor’s full load current (FLC) rating and the
desired trip class (5…30). Programming of the actual values through software programming ensures the accuracy of the
protection.
Thermal Memory
The E300 Electronic Overload Relay includes a thermal memory circuit designed to approximate the thermal decay for a trip
class 20 setting. This means that the thermal model of the connected motor is maintained at all times, even if the supply power
is removed.
Reset Modes
This flexibility allows the end-user in the ability to select between manual and automatic reset for an overload trip, allowing for
broad application. The point of reset is user adjustable from 1…100% TCU.
Time to Trip
During an overload condition, the E300 Electronic Overload Relay provides an estimated time to trip that is accessible via a
communications network. This allows corrective action to be taken so that production may continue uninterrupted.
Time to Reset
Following an overload trip, the E300 Electronic Overload Relay will not reset until the calculated percentage of thermal capacity
utilization falls below the reset level. As this value decays, the time to reset, which is accessible via a communications network, is
reported.
Thermal Warning
The E300 Electronic Overload Relay provides the capability to alert in the event of an impending overload trip. A thermal
warning bit is set in the Current Warning Status when the calculated percentage of thermal capacity utilization exceeds the
programmed thermal warning level, which has a setting range of 0…100% TCU.
Two-Speed Protection
The E300 Electronic Overload Relay offers a second FLA setting for 2-speed motor protection. What used to require two
separate overload relays - one for each set of motor windings - can now be accomplished with one device. Improved protection
is delivered as thermal utilization is maintained in one device during operation in both speeds.
Phase Loss
The E300 Electronic Overload Relay offers configurable phase loss protection, allowing the installer to enable or disable the
function plus set a time delay setting, adjustable from 0.1…25.0 seconds. The trip level is factory-set at a current imbalance
measurement of 100%.
Note: The E300 Electronic Overload Relay is not a Ground Fault Circuit Interrupter for personnel protection as defined in article
100 of the U.S. National Electric Code.
Stall
"Stall" is defined as a condition where the motor is not able to reach full-speed operation in the appropriate amount of time
required by the application. This can result in motor overheating as current draw is in excess of the motor’s full load current
rating. The E300 Electronic Overload Relay provides user-adjustable stall protection. The trip setting has a range of 100…600%
FLA, and the enable time is adjustable up to 250 seconds.
Jam (Overcurrent)
The E300 Electronic Overload Relay can respond quickly to take a motor off-line in the event of a mechanical jam, thereby
reducing the potential for damage to the motor and the power transmission components. Trip adjustments include a trip
setting adjustable from 50…600% FLA and a trip delay time with a range of 0.1…25.0 seconds. A separate warning setting is
adjustable from 50…600% FLA.
Underload (Undercurrent)
A sudden drop in motor current can signal conditions such as:
• Pump cavitation
• Tool breakage
• Belt breakage
For these instances, rapid fault detection can help minimize damage and aid in reducing production downtime.
Additionally, monitoring for an underload event can provide enhanced protection for motors that are coded by the medium
handled (e.g., submersible pumps that pump water). Such motors can become overheated despite being underloaded. This
can result from an absence or an insufficient amount of the medium (due to clogged filters, closed valves, etc.).
The E300 Electronic Overload Relay offers underload trip and warning settings adjustable from 10…100% FLA. The trip function
also includes a trip delay time with a range of 0.1…25.0 seconds.
Remote Trip
The remote trip function allows an external device (e.g., a vibration sensor) to induce the E300 Electronic Overload Relay to trip.
External device relay contacts are wired to the E300 Electronic Overload Relay discrete inputs. These discrete inputs are
configurable with an option for assigning the remote trip function.
Voltage Protection
The E300 sensing module with voltage, current, and ground fault current will provide the user with enhanced current-based
motor protection with the addition of voltage protection. With this option, users can protect against voltage issues (e.g.,
undervoltage, voltage imbalance, phase loss, frequency, and phase rotation).
Power Protection
While the motor is powering a load, the E300 sensing module with voltage, current, and ground fault current, will also protect
the motor based on power. This option will monitor and protect for both excessive and low real power (kW), reactive power
(kVAR), apparent power (kVA), and power factor for a specific application (e.g., pump applications).
Analog Protection
The E300 analog expansion module allows you to protect against over-analog readings from analog-based sensors
(overtemperature, overflow, overpressure, etc.)
Diagnostic Functions
The E300 Electronic Overload Relay allows the user to monitor the following diagnostic information over a communications
network:
Status Indicators
The E300 Electronic Overload Relay provides the following LED indicators:
• Power — This green/red LED indicates the status of the overload relay.
• TRIP/WARN — This LED flashes a yellow code under a warning condition and a red code when tripped.
Inputs/Outputs
Inputs allow the connection of such devices as contactor and disconnect auxiliary contacts, pilot devices, limit switches, and
float switches. Input status can be monitored via the network and mapped to a controller’s input image table. Inputs are rated
24V DC, 120V AC, or 240V AC and are current sinking. Power for the inputs is sourced separately with convenient customer
sources at terminal A1. Relay contact outputs can be controlled via the network or DeviceLogix function blocks for performing
such tasks as contactor operation.
Test/Reset Button
The Test/Reset button, located on the front of the E300 Electronic Overload Relay, allows the user to perform the following:
• Test — The trip relay contact will open if the E300 Electronic Overload Relay is in an untripped condition and the Test/
Reset button is pressed for 2 seconds or longer.
• Reset — The trip relay contact will close if the E300 Electronic Overload Relay is in a tripped condition, supply voltage is
present, and the Test/Reset button is pressed.
Single/Three-Phase Operation
The E300 Electronic Overload Relay can be applied to three-phase as well as single-phase applications. A programming
parameter is provided for selection between single- and three-phase operation. Straight-through wiring is afforded in both
cases.
EtherNet/IP Communications
The E300 EtherNet/IP communication module has two RJ45 ports that act as an Ethernet switch to support a star, linear, and
ring topology and supports the following:
• 2 concurrent Class 1 connections [1 exclusive owner + (1 input only or 1 listen only)]
• 6 simultaneous Class 3 connections (explicit messaging)
• Embedded web server
• SMTP server for trip and warning events (email and text messaging)
• Embedded EDS file
• RSLogix 5000 add-on profile
For more information on operation and maintenance of this product, please reference the user manual,
publication 193-UM015.
Notes:
Sensing Modules
Description Mounting Options Current Range [A] For Use With Cat. No.
100-C09…C23 193-ESM-I-30A-C23
0.5…30
100-C30…C55 193-ESM-I-30A-C55
IEC Contactors
6…60 100-C30…C55 193-ESM-I-60A-C55
10…100 100-C60…100-C97 193-ESM-I-100A-C97
0.5…30 All contactors and external current transformers 193-ESM-I-30A-T
DIN Rail / Panel Mount Power
6…60 193-ESM-I-60A-T
Terminals All contactors
10…100 193-ESM-I-100A-T
DIN Rail / Panel Mount Power 0.5…30 All contactors and external current transformers. 193-ESM-I-30A-E3T
Current
Terminals. 6…60 193-ESM-I-60A-E3T
Directly replaces 193-ECPM_ All contactors
10…100 193-ESM-I-100A-E3T
0.5…30 All contactors and external current transformers 193-ESM-I-30A-P
DIN Rail / Panel Mount Pass-thru 6…60 193-ESM-I-60A-P
All contactors
10…100 193-ESM-I-100A-P
0.5…30 592-ESM-I-30A-S2
NEMA Size 0…2
NEMA Contactors 6…60 592-ESM-I-60A-S2
10…100 NEMA Size 3 592-ESM-I-100A-S3
100-C09…C23 193-ESM-IG-30A-C23
0.5…30
100-C30…C55 193-ESM-IG-30A-C55
IEC Contactors
6…60 100-C30…C55 193-ESM-IG-60A-C55
10…100 100-C60…100-C97 193-ESM-IG-100A-C97
0.5…30 193-ESM-IG-30A-T
DIN Rail / Panel Mount Power
6…60 193-ESM-IG-60A-T
Terminals
10…100 193-ESM-IG-100A-T
DIN Rail / Panel Mount Power 0.5…30 193-ESM-IG-30A-E3T
Current/Ground Fault
Terminals. 6…60 All contactors 193-ESM-IG-60A-E3T
Directly replaces 193-ECPM_ 10…100 193-ESM-IG-100A-E3T
0.5…30 193-ESM-IG-30A-P
DIN Rail / Panel Mount Pass-thru 6…60 193-ESM-IG-60A-P
10…100 193-ESM-IG-100A-P
0.5…30 592-ESM-IG-30A-S2
NEMA Size 0…2
NEMA Contactors 6…60 592-ESM-IG-60A-S2
10…100 NEMA Size 3 592-ESM-IG-100A-S3
Description Mounting Options Current Range [A] For Use With Cat. No.
100-C09…C23 193-ESM-VIG-30A-C23
0.5…30
100-C30…C55 193-ESM-VIG-30A-C55
IEC Contactors
6…60 100-C30…C55 193-ESM-VIG-60A-C55
10…100 100-C60…100-C97 193-ESM-VIG-100A-C97
0.5…30 193-ESM-VIG-30A-T
DIN Rail / Panel Mount Power
6…60 193-ESM-VIG-60A-T
Terminals
10…100 193-ESM-VIG-100A-T
Voltage/Current/Ground Fault All contactors
DIN Rail / Panel Mount Power 0.5…30 193-ESM-VIG-30A-E3T
Terminals. 6…60 193-ESM-VIG-60A-E3T
Directly replaces 193-ECPM_ 10…100 193-ESM-VIG-100A-E3T
DIN Rail / Panel Mount Pass-thru 0.5…30 External current and potential transformers 193-ESM-VIG-30A-CT
0.5…30 592-ESM-VIG-30A-S2
NEMA Size 0…2
NEMA Contactors 6…60 592-ESM-VIG-60A-S2
10…100 NEMA Size 3 592-ESM-VIG-100A-S3
Control Modules
Communication Modules
Description Cat. No.
EtherNet/IP 193-ECM-ETR
Expansion Modules
Description No. of Inputs/Outputs Rated Control Voltage [V] Cat. No.
Digital Expansion Module, 24V DC 4 in/2 out 24V DC 193-EXP-DIO-42-24D
Digital Expansion Module, 120V AC 4 in/2 out 110…120V AC, 50/60 Hz 193-EXP-DIO-42-120
Digital Expansion Module, 240V AC 4 in/2 out 220…240V AC, 50/60 Hz 193-EXP-DIO-42-240
Analog Expansion Module: mA, V, RTD, and Resistance 3 universal in/1 out — 193-EXP-AIO-31 (1)
24V DC 193-EXP-PS-DC
Expansion Power Supply —
110…240V AC, 50/60 Hz 193-EXP-PS-AC
Starter Control Station with 3-Meter Cable — — 193-EOS-SCS
Starter Diagnostic Station with 3-Meter Cable — — 193-EOS-SDS (1)
(1) Module requires control module firmware v3.000 or higher.
Accessories
Description For Use With Cat. No.
100-C09…100-C23 contactors 193-EIO-CM-C23
Contactor Coil Module 100-C30…100-C55 contactors 193-EIO-CM-C55
100-C60…100-C97 contactors 193-EIO-CM-C97
1-Meter Expansion Module Cable — 193-EXP-CBL-1M
3-Meter Expansion Module Cable — 193-EXP-CBL-3M
193-EIOGP-42-24D 193-CBCT1
193-EIOGP-22-120 193-CBCT2,
Core Balanced Ground Fault Sensor
193-CBCT3
193-EIOGP-22-240
193-CBCT4
193-EIO-63-24D 193-NCIO-63-CNT
193-EIO-43-120
193-NCIO-43-CNT
193-EIO-43-240
193-EIOGP-42-24D 193-NCIOGP-42-CNT
193-EIOGP-22-120
193-NCIOGP-22-CNT
193-EIOGP-22-240
Replacement Connectors 193-ESM-VIG-30A-CT 193-NCSM-VIG-CNT
193-EXP-DIO-42-24D
193-EXP-DIO-42-120 193-NCXP-DIO-CNT
193-EXP-DIO-42-240
193-EXP-AIO-31 193-NCXP-AIO-CNT
193-EXP-PS-DC
193-NCXP-PS-CNT
193-EXP-PS-AC
193-ESM-I-30A-T
193-ESM-I-60A-T
193-ESM-IG-30A-T
193-ESM-IG-60A-T
193-ESM-VIG-30A-T
193-ESM-VIG-60A-T 140M-C-N45(1)
193-ESM-I-30A-P
193-ESM-I-60A-P
Panel Mount Screw Adapters
193-ESM-IG-30A-P
193-ESM-IG-60A-P
193-ESM-VIG-30A-CT
193-ESM-I-100A-T
193-ESM-IG-100A-T
193-ESM-VIG-100A-T 193-ESM-SA-100(2)
193-ESM-I-100A-P
193-ESM-IG-100A-P
(1) Sold in multiples of 10. Order quantity of 10 to receive a package of 10 pieces.
(2) Sold in multiples of 10. Order quantity of 1 to receive a package of 10 pieces.
Notes:
Wiring Diagrams
Figure 1 - Control Module
193-EIO-_ _-_ _ _ 193-EIOGP-_ _-_ _ _
RELAY 0 RELAY 0
IN2 IN3
+
Source
-
IN0 IN1 INC
+
Source
-
A1 A2
A1 A2
Electrical Specifications
Motor/Load Ratings
Terminals 1/L1, 3/L2, 5/L3, 2/T1, 4/T2, 6/T3
Rated Insulation Voltage Ui 690V AC
Rated Operating Voltage Ue, IEC 690V AC
Rated Operating Voltage Ue, UL 690V AC
Rated Impulse Voltage (Uimp) 6 kV
Rated Operating Current Ie See product selection table
Rated Frequency 45…65 Hz(1)
(1) Exception: Any E300 Overload Relay that uses an external ground fault sensor is limited to
50/60 Hz detection.
Environmental Specifications
Note: The E300 Electronic Overload Relay expansion power supplies (Cat. Nos. 193-EXP-PS-AC and 193-EXP-PS-DC) surrounding
air temperature must not exceed 55 °C (131 °F).
Ambient Temperature
Storage –40…+85 °C (–40…+185 °F)
Operating (open) –20…+55 °C (–4…+131 °F)
Operating (enclosed) –20…+40 °C (–4…+104 °F)
Humidity
Operating 5…95% Non-condensing
Damp Heat – Steady State (per IEC 68-2-3) 92% r.h., 40 °C (104 °F), 56 days
Damp Heat – Cyclic (per IEC 68-2-30) 93% r.h., 25 °C/40 °C (77 °F/104 °F), 21 Cycles
Cooling Method Natural convection
Vibration (per IEC 68-2-6) 2.5 G operating, 5 G non-operating
Shock (per IEC 68-2-27) 30 G
Maximum Altitude 2000 m(1)
Pollution Environment Pollution Degree 3
Terminal Marking EN 50012
Degree of Protection IP20
(1) Exception: Any E300 Overload Relay that uses an external ground fault sensor is limited to 50/60 Hz detection.
Protection
General Protection
Trip Warning Trip Warning
Overload Yes Yes Under Frequency Yes Yes
Phase Loss Yes No Over Frequency Yes Yes
Ground Fault Yes Yes Under Real Power (kW) Yes Yes
Stall Yes No Over Real Power (kW) Yes Yes
Jam Yes Yes Under Reactive Power Consumed (+kVAR) Yes Yes
Underload Yes Yes Over Reactive Power Consumed (+kVAR) Yes Yes
Thermistor (PTC) Yes Yes Under Reactive Power Generated (-kVAR) Yes Yes
Current Imbalance Yes Yes Over Reactive Power Generated (-kVAR) Yes Yes
Communication Fault Yes Yes Under Apparent Power (kVA) Yes Yes
Communication Idle Yes Yes Over Apparent Power (kVA) Yes Yes
Remote Trip Yes No Under Power Factor Lagging (-PF) Yes Yes
Blocked Start/Start Inhibit Yes No Over Power Factor Lagging (-PF) Yes Yes
Under Voltage L-L Yes Yes Under Power Factor Leading (+PF) Yes Yes
Over Voltage L-L Yes Yes Over Power Factor Leading (+PF) Yes Yes
Voltage Unbalance Yes Yes Power Value Overflow (kW, kVAR or KVA) Yes Yes
Phase Rotation Yes Yes Over Analog Yes Yes
Overload Protection
Type of Relay Ambient Compensated Time-Delay Phase Loss Sensitive
Nature of Relay Solid-State
FLA Setting See user manual
Trip Rating 120% FLA
Trip Class 5…30
Reset Mode Automatic or Manual
Overload Reset Level 1…100% TCU
Accuracy
Metering
Current ±2% of Sensing Module Current Range
Voltage ±2% of Sensing Module Voltage Range
Power ±5% of Sensing Module Current and Voltage Range
Protection Timers
All E300 Electronic Overload Relay trip timers have a resolution of ±0.1 s or 0.1 s/25 s (whichever is greater).
Notes:
n 5 (0.18)
190 (7.49)
60 (2.36)
(ADD 5 mm (0.19 in.)
FOR CONTACTOR COIL
ON LINE SIDE)
67 (2.65)
37 (1.47) FROM
CONTACTOR
MTG. HOLE
152 (5.98)
122 (4.81)
29 (1.14) 122
(4.78)
FROM
CONTACTOR
MTG. HOLE
190 (7.49)
(ADD 5 mm (0.19 in.) 60 (2.36)
FOR CONTACTOR COIL
ON LINE SIDE)
67 (2.65)
37 (1.48) FROM
CONTACTOR
MTG. HOLE
152 (5.98)
122 (4.81)
29 (1.13)
FROM
CONTACTOR 122
MTG. HOLE (4.78)
n 5 (0.18)
60 (2.36)
190 (7.49)
(ADD 5 mm (0.19 in.)
FOR CONTACTOR COIL
ON LINE SIDE)
67 (2.65)
37 (1.48) FROM
CONTACTOR
MTG. HOLE
152 (5.98)
34 (1.34)
FROM
CONTACTOR
MTG. HOLE
122
45 (1.76) (4.82)
235.1 101
(9.26) (3.98)
(ADD 0.24 in. FOR
CONTACTOR COIL
ON LINE SIDE)
91.6
(3.60)
43.5 FROM
(1.71) CONTACTOR
MTG. HOLE 177.6
(6.99)
129.5
(5.10)
38.9
(1.53) FROM 135.2
CONTACTOR (5.32)
MTG. HOLE
Figure 9 - E300 Overload Relay Mounted on Bulletin 500 NEMA Size 0 and Size 1 Contactor
90
(3.56)
n 6 (0.22)
180 (7.06)
157 (6.17)
249 (9.78)
12 (0.46)
125
35 (1.38) (4.91)
70
(2.75)
Figure 10 - E300 Overload Relay Mounted on Bulletin 500 NEMA Size 2 Contactor
100.1 (3.94)
n 5.58 (0.22)
183.9
(7.24)
219.2
(8.63)
275.59
(10.85)
11.68 (0.46)
124.71
40.13 (4.91)
(1.58)
80.01
(3.15)
Figure 11 - E300 Overload Relay Mounted on Bulletin 500 NEMA Size 3 Contactor
138.2
(5.44)
11.35
161.6
(0.45)
(6.36)
19.9 7.9
(0.78) (0.31)
219.9 274.1
(8.66) (10.79)
368
(14.49)
121
(4.76) 138.4
(5.45)
139.85
(5.51)
155.45
(6.12)
Figure 12 - E300 Overload Relay, 193-ESM-___-30A-E3T and -60A-E3T, DIN Rail/Panel Mounted
30
45 126 (1.18)
(1.764) (4.94)
6 (0.24)
9 (0.33)
46 (1.81)
4 (0.16)
q
148 (5.83)
135 (5.32)
4 (0.14)
6 (0.217)
101 (3.96)
4 (0.154)
n 5 (0.17)
8 (0.30)
41.2 17.7
(1.62) (0.70)
139.9
(5.51)
130
q (5.12)
76.6
(3.02)
41.4
(1.63) 4.05
141.5 (0.16)
(5.57)
Figure 14 - E300 Overload Relay, 193-ESM-___-30A-T and -60A-T, DIN Rail Mounted
SHOWN WITH PANEL MOUNT FEET ACCESSORY
CAT. NO. 140M-C-N45
11.35
n 4.8
(0.45)
(0.189)
39
(1.53)
4.5
135 (0.18)
(5.32) 30.1
WITH MTG. FEET (1.19) 116.2 125
q (4.58) (4.921)
W/O MTG. FEET
5
124
(0.197)
(4.88)
45
(1.76)
60
11.4 (2.36)
q (0.45)
41.2
(1.62)
WITH FEET
139.9
(5.51)
120.7 WITH FEET
130
(4.75) 36.6
(5.12)
W/O FEET (1.44)
W/O FEET q
52.9
(2.08)
Figure 16 - E300 Overload Relay, 193-ESM-___-30A-P, -30A-CT, and -60A-P, DIN Rail Mounted
11.35
(0.45)
FROM MOUNTING FOOT
MOUNTING HOLE TO
RESET BUTTON
21.5 n 4.8
(0.85) (0.19)
FROM MOUNTING FOOT
MOUNTING HOLE TO
RESET BUTTON
102 108
(4.00) (4.25)
30.2 W/ MTG. FEET W/ MTG. FEET
106.3 (1.19) 91.5
(4.18) q (3.60)
W/O MTG. FEET
5
45 123.5
(0.20)
(1.76) (4.86)
3 PIN CONNECTOR ONLY WITH
CAT. NO. 193-ESM-VIG-30A-CT
109.9
21.4 (4.33) 100
106.3
(0.84) WITH FEET (3.94)
(4.18)
W/O FEET W/O FEET q
38.8
(1.53)
n 5.8 60
71.6 (0.23) (2.36)
(2.82)
140.9
(5.55)
22.5
(0.89)
2 x 4.5 (0.18) dia.
120
(4.73)
22.5
(0.89)
2 x 4.5 (0.18) dia.
120
(4.73)
98 87
(3.86) (3.43) 80.75 (3.18)
12
(0.47)
45 (1.77)
100
(3.94) 18.5
(0.73)
n 22.1
70 (0.87)
(2.76)
13.5
(0.53)