SQM5
SQM5
SQM5
SQM5..., gear train side SQM5..., rear, version without SQM5..., rear, version with
with drive shaft no. 7 second drive shaft end 2 drive shaft ends
The SQM5... and this Data Sheet are intended for use by OEMs which integrate the
SQM5... in their products!
Use
The SQM5... actuators are used to drive air and gas dampers of oil and gas burners of
medium to large capacity.
They are used primarily for load-dependent control of the amounts of gas, oil and com-
bustion air:
• In connection with 3-position or modulating controllers (e.g. 4...20 mA), or
• Directly by burner controls
CC1N7815en
Building Technologies
06.10.2008 HVAC Products
Warning notes
Only qualified staff may open, interfere with or modify the actuators!
• All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
• Before making any wiring changes in the connection area, completely isolate the
plant from mains supply (all-polar disconnection). Ensure that the plant cannot be in-
advertently switched on again and that it is indeed dead. If not observed, there is a
risk of electric shock hazard
• Ensure protection against electric shock hazard by providing adequate protection for
the connection terminals
• Protection against electric shock hazard is ensured by folding upwards cover of con-
trol unit (made of plastic), allowing safe setting of the cams when mains voltage is
present
• Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state
• Fall or shock can adversely affect the safety functions. Such actuators must not be
put into operation even if they do not exhibit any damage
Mounting notes
• Ensure that the relevant national safety regulations are complied with
For use in the U.S. / Canada, the actuators carry type suffix «R» (see example) and are
UL- and CSA-listed.
Example: SQM50.480R1
Disposal notes
The actuator contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.
2/12
Couplings • Driven shaft and cam shaft can be adjusted via 2 separately couplers, independent
of the gear train
• Shaft can be disengaged from gear train and motor via manual operation of a cou-
pler (pressure pin «K», refer to «Technical data»).
• Automatic reengagement
• Pressure pin «K...»
7815z07e/0908
Pressure pin "K1"
3/12
Actuator • Fixing holes on the front of the housing and at the bottom
fixing • Front fixing also possible from inside the housing
• Variable mounting height through the use of an extra adapter
4/12
Standard types! Torque and Running time at Auxiliary Type of shaft Electronic Potentiometer
(other versions on holding 50 Hz for switches incl. module
request) torque angular rotation 2 end (integrated ex (integrated ex
1) switches works) works)
3) 5) 6)
Type reference max. Nm 2) 90° 130° Piece AGA… AGA… ASZ…
4
SQM50.260A2G4 10 10 s 14 s 4 --- ) 56.41A27 12.33
SQM50.341A2 10 15 s 22 s 4 58.1 --- ---
SQM50.341A2G3 10 15 s 22 s 4 58.1 56.41A27 12.30
SQM50.341A2K3 10 15 s 22 s 4 58.1 56.43A27 12.30
SQM50.381A2 10 15 s 22 s 8 58.1 --- ---
SQM50.381A2G3 10 15 s 22 s 8 58.1 56.41A27 12.30
SQM50.441A2 10 30 s 43 s 4 58.1 --- ---
SQM50.441A2G3 10 30 s 43 s 4 58.1 56.41A27 12.30
4
SQM50.480A2 15 30 s 43 s 8 --- ) --- ---
4
SQM50.480A2Z3 15 30 s 43 s 8 --- ) 56.9A27 12.30
SQM50.481A2 10 30 s 43 s 8 58.1 --- ---
SQM50.481A2G3 10 30 s 43 s 8 58.1 56.41A27 12.30
SQM50.481A2Z3 10 30 s 43 s 8 58.1 56.9A27 12.30
SQM50.482A2 15 30 s 43 s 8 58.2 --- ---
SQM50.482A2Z3 15 30 s 43 s 8 58.2 56.9A27 12.30
SQM50.483A2Z3 15 30 s 43 s 8 58.3 56.9A27 12.30
SQM50.681A2 10 60 s 87 s 8 58.1 --- ---
SQM53.482A2 20 30 s 43 s 8 58.2 --- ---
SQM53.482A2Z3 20 30 s 43 s 8 58.2 56.9A27 12.30
SQM53.489A2 25 30 s 43 s 8 58.9 --- ---
4
SQM54.480A2 25 30 s 43 s 8 --- ) --- ---
SQM54.482A2 20 30 s 43 s 8 58.2 --- ---
4
SQM54.580A2Z3 25 45 s 65 s 8 --- ) 56.9A27 12.30
4
SQM56.680A2 40 60 s 87 s 8 --- ) --- ---
SQM56.684A2G4 30 60 s 87 s 8 58.4 56.41A27 12.33
SQM56.684A2Z3 30 60 s 87 s 8 58.4 56.9A27 12.30
SQM56.687A2 40 60 s 87 s 8 58.7 --- ---
SQM56.687A2G3 40 60 s 87 s 8 58.7 56.41A27 12.30
SQM56.687A2Z3 40 60 s 87 s 8 58.7 56.9A27 12.30
5/12
Standard types! Torque and Running time at Auxiliary Type of shaft Electronic Potentiometer
(other versions on holding 50 Hz for switches incl. module
request) torque angular rotation 2 end (integrated ex (integrated ex
1) switches works) works)
3) 5) 6)
Type reference max. Nm 2) 90° 130° Piece AGA… AGA… ASZ…
4
SQM50.480A1 15 30 s 43 s 8 --- ) --- ---
4
SQM50.480A1Z3 15 30 s 43 s 8 --- ) 56.9A17 12.30
SQM50.483A1Z3 15 30 s 43 s 8 58.3 56.9A17 12.30
4
SQM53.480A1 25 30 s 43 s 8 --- ) --- ---
SQM53.482A1Z3 20 30 s 43 s 8 58.2 56.9A17 12.30
SQM56.687A1 40 60 s 87 s 8 58.7 --- ---
SQM56.687A1Z3 40 60 s 87 s 8 58.7 56.9A17 12.30
Standard types! Torque and Running time at Auxiliary Type of shaft Electronic Potentiometer
(other versions on holding 50 Hz for switches incl. module
request) torque angular rotation 2 end (integrated ex (integrated ex
1) switches works) works)
3) 5) 6)
Type reference max. Nm 2) 90° 130° Piece AGA… AGA… ASZ…
4
SQM50.380A8 10 15 s 22 s 8 --- ) --- ---
SQM50.443A8 15 30 s 43 s 4 58.3 --- ---
SQM50.444A8 15 30 s 43 s 4 58.4 --- ---
SQM50.444A8Z3 15 30 s 43 s 4 58.4 56.9A87 12.30
SQM50.454A8 15 30 s 43 s 5 58.4 --- ---
SQM50.483A8 15 30 s 43 s 8 58.3 --- ---
SQM50.483A8Z3 15 30 s 43 s 8 58.3 56.9A87 12.30
6/12
Pg insert AGA55.2
- Inclusive sealing and screw, for SQM5...
Spacer AGA57.1
- Adapter for SQM10... / SQM20...
- Refer to Mounting Instructions M7815.1 (4 319 9529 0)
Drive shafts:
7/12
8/12
7815z02/0102
30
25 > 60 s / 87 s > 45 s / 65 s
MaxB - 22
20 65 s
45 s /
> 45 s / 65 s > 15 s / 22 s
MaxN - 15 s
/ 49
34 s s
10 / 22
15 s
5
1)
SQM53... / SQM54... 50 Hz
Nm
7815z03/0102
> 45 s / 65 s > 30 s / 43 s
MaxB - 30
> 45 s / 65 s > 30 s / 43 s
MaxN - 25
3s
20 s /4
30 s
22
15 s/
15
10
5
1)
SQM56... 50 Hz
Nm
MaxB - 60
7815z04/0102
50 7s
s/8
60
> 60 s / 87 s > 45 s / 65 s
MaxN - 40
s
s / 65 43 s
30 45 30 s /
20 22 s
15 s /
10
Legend 1) At 60 Hz frequency, running times are about 17 % shorter and torques are proportionally lower
)
Each drive side is capable of delivering the maximum torque, but the total torque of both sides must not
exceed the maximum permissible torque of actuator.
9/12
Diagram shows the maximum number of switches (2 end and 6 auxiliary switches).
On versions with fewer than 6 auxiliary switches, the higher numbers are not used. For
example, the actuator version with 2 end and 2 auxiliary switches does not use switches
V, VI, VII and VIII.
Direction of rotation
By exchanging the 2 motor connecting cables, the actuator’s direction of rotation can be
changed from counterclockwise to clockwise.
Note When changing the direction of rotation from counterclockwise to clockwise, the cams
must be readjusted.
Clockwise rotation: Red scales on the cam shaft, double arrow on the cams.
Counterclockwise rotation: Black scales on the cam shaft, single arrow on the cams.
10/12
80
132
113
Example: AGA58.4
Pg13.5
52.5 52.5 Pg13.5
M6 M6
M8
55.5
55.5
M51)
30
36
133
10
25
44.5
41.5
44.5
67
7815m06e/0908
M6 M6
25 25
52.5 52.5
58
4.6 dia. for self-tapping screws M5
180
25.5
8 20 10
9 3
11.2
AGA58.1
25.5
20 12
9 3
13.2
AGA58.2
20.5 21.5
9 9 11 9
AGA58.3
M5 x 9
M5 x 9
17
19,8
10.6
10.6
#8-32UNC-2Bx14
#8-32UNC-2Bx14
9.5
9.5 2,5 2,5
AGA58.4
1.3 1,3
43.5 14
28 5
5
15.1
AGA58.7
25,5 12
15 M4 x 14
7815m07/0202
AGA58.9
11/12
AGA57.1
4 mm
7815z05/0602
7815m08/0102
113
130
80
7 (4x)
7 (4x)
7 (4x) 3
AGA57.3
7815m05/0202
123,8
113
80
14,5 103,3 18
164