SQM5

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

7 815

SQM5..., gear train side SQM5..., rear, version without SQM5..., rear, version with
with drive shaft no. 7 second drive shaft end 2 drive shaft ends

Actuators for Air and Gas SQM5...


Dampers
with electronic modules

• Reversible electromotive actuators up to 40 Nm


• Running times from 10 to 90 seconds
• With 1 or 2 drive shaft ends; drive shafts can be exchanged or available as
separate items
• Can be equipped with electronic modules for control and position feedback
signal via steady signals
• Internal and external position indication
• Drive shaft and cam shaft can be separately disengaged
• Choice of UL-listed types for use in the U.S. and Canada
• Supplementary Data Sheets, refer to N7921 and N7922

The SQM5... and this Data Sheet are intended for use by OEMs which integrate the
SQM5... in their products!

Use

The SQM5... actuators are used to drive air and gas dampers of oil and gas burners of
medium to large capacity.

They are used primarily for load-dependent control of the amounts of gas, oil and com-
bustion air:
• In connection with 3-position or modulating controllers (e.g. 4...20 mA), or
• Directly by burner controls

CC1N7815en
Building Technologies
06.10.2008 HVAC Products
Warning notes

To avoid injury to persons, damage to property or the environment, the following


warning notes must be observed!

Only qualified staff may open, interfere with or modify the actuators!

• All activities (mounting, installation and service work, etc.) must be performed by
qualified staff
• Before making any wiring changes in the connection area, completely isolate the
plant from mains supply (all-polar disconnection). Ensure that the plant cannot be in-
advertently switched on again and that it is indeed dead. If not observed, there is a
risk of electric shock hazard
• Ensure protection against electric shock hazard by providing adequate protection for
the connection terminals
• Protection against electric shock hazard is ensured by folding upwards cover of con-
trol unit (made of plastic), allowing safe setting of the cams when mains voltage is
present
• Each time work has been carried out (mounting, installation, service work, etc.),
check to ensure that wiring is in an orderly state
• Fall or shock can adversely affect the safety functions. Such actuators must not be
put into operation even if they do not exhibit any damage

Mounting notes

• Ensure that the relevant national safety regulations are complied with

Standards and certificates


Conformity to EEC directives
- Electromagnetic compatibility EMC (immunity) 2004/108/EC
- Low-voltage directive 2006/95/EC

ISO 9001: 2000 ISO 14001: 2004


Cert. 00739 Cert. 38233

For use in the U.S. / Canada, the actuators carry type suffix «R» (see example) and are
UL- and CSA-listed.

Example: SQM50.480R1

Disposal notes

The actuator contains electrical and electronic components and must not be disposed of
together with domestic waste.
Local and currently valid legislation must be observed.

2/12

Building Technologies CC1N7815en


HVAC Products 06.10.2008
Mechanical design

Housing • Housing sections made of die-cast aluminium


• Covers made of impact-proof and heat-resistant plastic

Drive motor • Reversible and locking-proof synchronous motor

Couplings • Driven shaft and cam shaft can be adjusted via 2 separately couplers, independent
of the gear train
• Shaft can be disengaged from gear train and motor via manual operation of a cou-
pler (pressure pin «K», refer to «Technical data»).
• Automatic reengagement
• Pressure pin «K...»

- Disengagement of gear train / cam


shaft by pressing pin «K1»

7815z07e/0908
Pressure pin "K1"

- Disengagement of cam / gear train


by pressing pin «K2»
7815z08e/0908

Pressure pin "K1"

Cam shaft drive • Backlash-free gearing

Adjustment of • With rotating cams


switching points • Scales beside the cams indicate the angle of the switching point

Position indication • Internally:


– Scale at the end of the drive shaft
– Black scale for counterclockwise rotation, single arrow on the cam
– Red scale for clockwise rotation, double arrow on the cam
• Externally:
– Scale in viewing window

3/12

Building Technologies CC1N7815en


HVAC Products 06.10.2008
Mechanical design (cont´d)

Electrical • Blade terminal on micro switch


connections • Screw terminals for «N» and «PE»
• Subassembly and fixing of wiring by means of removable Pg plastic insert possible
• Easy introduction of cables through large openings in the housing
• Fixing of Pg insert with all cables by means of a screw

Gear train • Maintenance-free gearwheels and bearings

Drive shaft • Secured with a removable circlip


• Easily exchangeable
• With corresponding shaft both sides transmission possible

Actuator • Fixing holes on the front of the housing and at the bottom
fixing • Front fixing also possible from inside the housing
• Variable mounting height through the use of an extra adapter

4/12

Building Technologies CC1N7815en


HVAC Products 06.10.2008
Type summary (other types are available on request)
When ordering, please give type reference according to following tables. Accessories are to be ordered separately.
Actuators with premounted accessories are only available on request.

AC 220 V -15 %...AC 240 V+10 %, 50…60 Hz ±6 %

Standard types! Torque and Running time at Auxiliary Type of shaft Electronic Potentiometer
(other versions on holding 50 Hz for switches incl. module
request) torque angular rotation 2 end (integrated ex (integrated ex
1) switches works) works)
3) 5) 6)
Type reference max. Nm 2) 90° 130° Piece AGA… AGA… ASZ…
4
SQM50.260A2G4 10 10 s 14 s 4 --- ) 56.41A27 12.33
SQM50.341A2 10 15 s 22 s 4 58.1 --- ---
SQM50.341A2G3 10 15 s 22 s 4 58.1 56.41A27 12.30
SQM50.341A2K3 10 15 s 22 s 4 58.1 56.43A27 12.30
SQM50.381A2 10 15 s 22 s 8 58.1 --- ---
SQM50.381A2G3 10 15 s 22 s 8 58.1 56.41A27 12.30
SQM50.441A2 10 30 s 43 s 4 58.1 --- ---
SQM50.441A2G3 10 30 s 43 s 4 58.1 56.41A27 12.30
4
SQM50.480A2 15 30 s 43 s 8 --- ) --- ---
4
SQM50.480A2Z3 15 30 s 43 s 8 --- ) 56.9A27 12.30
SQM50.481A2 10 30 s 43 s 8 58.1 --- ---
SQM50.481A2G3 10 30 s 43 s 8 58.1 56.41A27 12.30
SQM50.481A2Z3 10 30 s 43 s 8 58.1 56.9A27 12.30
SQM50.482A2 15 30 s 43 s 8 58.2 --- ---
SQM50.482A2Z3 15 30 s 43 s 8 58.2 56.9A27 12.30
SQM50.483A2Z3 15 30 s 43 s 8 58.3 56.9A27 12.30
SQM50.681A2 10 60 s 87 s 8 58.1 --- ---
SQM53.482A2 20 30 s 43 s 8 58.2 --- ---
SQM53.482A2Z3 20 30 s 43 s 8 58.2 56.9A27 12.30
SQM53.489A2 25 30 s 43 s 8 58.9 --- ---
4
SQM54.480A2 25 30 s 43 s 8 --- ) --- ---
SQM54.482A2 20 30 s 43 s 8 58.2 --- ---
4
SQM54.580A2Z3 25 45 s 65 s 8 --- ) 56.9A27 12.30
4
SQM56.680A2 40 60 s 87 s 8 --- ) --- ---
SQM56.684A2G4 30 60 s 87 s 8 58.4 56.41A27 12.33
SQM56.684A2Z3 30 60 s 87 s 8 58.4 56.9A27 12.30
SQM56.687A2 40 60 s 87 s 8 58.7 --- ---
SQM56.687A2G3 40 60 s 87 s 8 58.7 56.41A27 12.30
SQM56.687A2Z3 40 60 s 87 s 8 58.7 56.9A27 12.30

5/12

Building Technologies CC1N7815en


HVAC Products 06.10.2008
Type summary (other types are available on request) [cont´d]

AC 100 V -15 %...AC 110 V+10 %, 50…60 Hz ±6 %

Standard types! Torque and Running time at Auxiliary Type of shaft Electronic Potentiometer
(other versions on holding 50 Hz for switches incl. module
request) torque angular rotation 2 end (integrated ex (integrated ex
1) switches works) works)
3) 5) 6)
Type reference max. Nm 2) 90° 130° Piece AGA… AGA… ASZ…
4
SQM50.480A1 15 30 s 43 s 8 --- ) --- ---
4
SQM50.480A1Z3 15 30 s 43 s 8 --- ) 56.9A17 12.30
SQM50.483A1Z3 15 30 s 43 s 8 58.3 56.9A17 12.30
4
SQM53.480A1 25 30 s 43 s 8 --- ) --- ---
SQM53.482A1Z3 20 30 s 43 s 8 58.2 56.9A17 12.30
SQM56.687A1 40 60 s 87 s 8 58.7 --- ---
SQM56.687A1Z3 40 60 s 87 s 8 58.7 56.9A17 12.30

AC 24 V -15 / +10 %, 50…60 Hz ±6 %

Standard types! Torque and Running time at Auxiliary Type of shaft Electronic Potentiometer
(other versions on holding 50 Hz for switches incl. module
request) torque angular rotation 2 end (integrated ex (integrated ex
1) switches works) works)
3) 5) 6)
Type reference max. Nm 2) 90° 130° Piece AGA… AGA… ASZ…
4
SQM50.380A8 10 15 s 22 s 8 --- ) --- ---
SQM50.443A8 15 30 s 43 s 4 58.3 --- ---
SQM50.444A8 15 30 s 43 s 4 58.4 --- ---
SQM50.444A8Z3 15 30 s 43 s 4 58.4 56.9A87 12.30
SQM50.454A8 15 30 s 43 s 5 58.4 --- ---
SQM50.483A8 15 30 s 43 s 8 58.3 --- ---
SQM50.483A8Z3 15 30 s 43 s 8 58.3 56.9A87 12.30

1) At 60 Hz frequency, running times are about 17 % shorter


2) Based on 250,000 position changes
3) Refer to «Drive shafts» and «Torques», depending on voltage

4) Drive shaft to be ordered separately

5) For details, refer to Data Sheet N7922

6) For details, refer to Data Sheet N7921

6/12

Building Technologies CC1N7815en


HVAC Products 06.10.2008
Accessories
Potentiometers ASZ... refer to Data Sheet N7921
- ASZxx.3x refer to Mounting Instruction M7921 (4 319 9604 0)
- ASZxx.7xx refer to Mounting Instruction M7806 / M7808 / M7812 (4 319 2263 0)
- ASZxx.8xx refer to Mounting Instruction M7806 / M7808 / M7812 (4 319 2263 0)
- ASZxx.9xx refer to Mounting Instruction M7806 / M7808 / M7812 (4 319 2263 0)

Mounting kit ASK33.9


- For fitting the SQM5... to butterfly valves VKF41... , always with drive shaft AGA58.1
- Refer to Mounting Instruction M7815.4 (4 319 9535 0)

Pg insert AGA55.2
- Inclusive sealing and screw, for SQM5...

Kit for shaft seal AGA55.5


- For sealing the shaft feedthrough and therewith for perfecting the degree of protection
- On both sides shaft seals for actuator SQM5...
- Packed as kit together with O-rings inclusive mounting screws
- Refer to Mounting Instruction M7815.5 (74 319 0577 0)

Spacer AGA57.1
- Adapter for SQM10... / SQM20...
- Refer to Mounting Instructions M7815.1 (4 319 9529 0)

Adapter for actuator ME8 AGA57.2


- Refer to Mounting Instruction M7815.2 (4 319 9536 0)

Adapter for Honeywell Mod. III actuator AGA57.3


- Refer to Mounting Instruction M7815.2 (4 319 9536 0)

Electronic modules AGA56...


- For control of the actuator
- Modular installable, complete with mounting frame and fixing screws
- Refer for AGA56.1... Data Sheet N7922 and Mounting Instruction M7922.3 (4 319 9602 0)
- Refer for AGA56.4... Data Sheet N7922 and Mounting Instruction M7922.2 (4 319 9542 0)
- Refer for AGA56.9... Data Sheet N7922 and Mounting Instruction M7922.1 (4 319 9532 0)

Drive shafts:

Type of drive shaft Max. Type Order


torque no. no.
10 mm dia., single-sided, Woodruff key to DIN 6888, equivalent to drive shaft of 10 Nm 1 AGA58.1
SQM10...
10 mm dia., single-sided, Woodruff key to DIN 6888, equivalent to drive shaft of
10 Nm 1 AGA58.1(10)
SQM10..., packs of 10 pieces
12 mm dia., single-sided, Woodruff key to DIN 6888, equivalent to drive shaft of 20 Nm 2 AGA58.2
SQM20...
9 mm square, double-sided, equivalent to drive shaft of ME8 25 Nm 3 AGA58.3
9.5 mm square, double-sided, equivalent to drive shaft of Honeywell Mod. III 30 Nm 4 AGA58.4
9.5 mm square, double-sided, equivalent to drive shaft of Honeywell Mod. III,
30 Nm 4 AGA58.4(10)
packs of 10 pieces
10 mm dia. gear train side, 9,5“ square rear, Woodruff key to DIN 6888, equiva-
10 6 AGA58.6
lent to drive shaft of Honeywell Mod. SQM10...
14 mm dia., single-sided with parallel key to DIN 6885, mandatory with SQM56... 40 Nm 7 AGA58.7
14 mm dia., single-sided with parallel key to DIN 6885, mandatory with SQM56...,
40 Nm 7 AGA58.7(10)
packs of 10 pieces
12 mm square, single-sided 30 Nm 9 AGA58.9

Refer to Mounting Instruction M7815.3 (4 319 9534 0)

7/12

Building Technologies CC1N7815en


HVAC Products 06.10.2008
Technical data

General unit data Kind of current AC


Operating voltage and frequency refer to «Type summary»
Drive motor synchronous motor
Power consumption 20 VA
Angular rotation adjustable between 0! and max. 160°
(scale range)
Mounting position optional
Degree of protection IP 54 (provided knockout holes remain
closed for mounting or are closed off, with
adequate cable entries)
Cable entry 4 x Pg13.5 with thread
Direction of rotation facing the gear train side:
counterclockwise or clockwise (selectable),
delivery: counterclockwise
Torque refer to torque charts and drive shafts
Holding torque max. torque
Running time 10...90 s (refer to «Type summary»)
End and auxiliary switches
- Type to DIN 41636
- Switching voltage AC 24...250 V
- Switching capacity to CEE 24 / VDE 0630
7.5 (3) A, AC 250 V
Number of end switches 2
Number of auxiliary switches max. 6
Drive shaft exchangeable
Weight approx. 3.3 kg

Environmental conditions Storage DIN EN 60 721-3-1


Climatic conditions class 1K2
Mechanical conditions class 1M2
Temperature range without integrated -50...+60 °C
AGA56...
Humidity < 95 % r.h.
Transport DIN EN 60 721-3-2
Climatic conditions class 2K2
Mechanical conditions class 2M2
Temperature range without integrated -50...+60 °C
AGA56...
Humidity < 95 % r.h.
Operation DIN EN 60 721-3-3
Climatic conditions class 3K3
Mechanical conditions class 3M3
Temperature range without integrated -20...+60 °C
AGA56...
Humidity < 95 % r.h.

Condensation, formation of ice and ingress of water are not permitted!

8/12

Building Technologies CC1N7815en


HVAC Products 06.10.2008
Torques
1)
SQM50... 50 Hz
Nm

7815z02/0102
30
25 > 60 s / 87 s > 45 s / 65 s
MaxB - 22
20 65 s
45 s /
> 45 s / 65 s > 15 s / 22 s
MaxN - 15 s
/ 49
34 s s
10 / 22
15 s
5

AC 220...240 V -15 / +10 % 0 Volt


187 200 220 240 264
AC 24 V -15 / +10 % Volt
20 22 24 26,4

1)
SQM53... / SQM54... 50 Hz
Nm

7815z03/0102
> 45 s / 65 s > 30 s / 43 s
MaxB - 30
> 45 s / 65 s > 30 s / 43 s
MaxN - 25
3s
20 s /4
30 s
22
15 s/
15
10
5

AC 220...240 V -15 / +10 % 0 Volt


187 200 220 240 264
AC 24 V -15 / +10 % Volt
20 22 24 26,4

1)
SQM56... 50 Hz
Nm
MaxB - 60
7815z04/0102

50 7s
s/8
60
> 60 s / 87 s > 45 s / 65 s
MaxN - 40
s
s / 65 43 s
30 45 30 s /

20 22 s
15 s /

10

AC 220...240 V -15 / +10 % 0 Volt


187 200 220 240 264
AC 24 V -15 / +10 % Volt
20 22 24 26,4

Legend 1) At 60 Hz frequency, running times are about 17 % shorter and torques are proportionally lower

)
Each drive side is capable of delivering the maximum torque, but the total torque of both sides must not
exceed the maximum permissible torque of actuator.

With appropriate running time for 90° / 130°:


—— Torque in continuous operation
------- Release or starting torque = short-time torque
MaxN Max. permissible torque in continuous operation for all running times
MaxB Max. permissible release or starting torque for all running times

9/12

Building Technologies CC1N7815en


HVAC Products 06.10.2008
Connection terminals

Diagram shows the maximum number of switches (2 end and 6 auxiliary switches).
On versions with fewer than 6 auxiliary switches, the higher numbers are not used. For
example, the actuator version with 2 end and 2 auxiliary switches does not use switches
V, VI, VII and VIII.

Direction of rotation

By exchanging the 2 motor connecting cables, the actuator’s direction of rotation can be
changed from counterclockwise to clockwise.

Counterclockwise rotation Clockwise rotation

Note When changing the direction of rotation from counterclockwise to clockwise, the cams
must be readjusted.
Clockwise rotation: Red scales on the cam shaft, double arrow on the cams.
Counterclockwise rotation: Black scales on the cam shaft, single arrow on the cams.

10/12

Building Technologies CC1N7815en


HVAC Products 06.10.2008
Dimensions
Dimensions in mm
SQM5...
180

1) Identical with fixing points SQM1... /


SQM2...
1 3.5
M6

80
132
113
Example: AGA58.4

8.5 164 7.5

Pg13.5
52.5 52.5 Pg13.5
M6 M6

M8
55.5

55.5

M51)

30
36

133

10
25
44.5

41.5
44.5

67

7815m06e/0908
M6 M6

25 25

52.5 52.5
58
4.6 dia. for self-tapping screws M5
180
25.5
8 20 10
9 3
11.2

AGA58.1

25.5
20 12
9 3
13.2

AGA58.2

20.5 21.5
9 9 11 9

AGA58.3
M5 x 9
M5 x 9

17
19,8
10.6
10.6
#8-32UNC-2Bx14
#8-32UNC-2Bx14

9.5
9.5 2,5 2,5
AGA58.4
1.3 1,3

43.5 14
28 5
5
15.1

AGA58.7

25,5 12
15 M4 x 14
7815m07/0202

AGA58.9

11/12

Building Technologies CC1N7815en


HVAC Products 06.10.2008
Dimensions (cont’d)
Dimensions in mm

AGA57.1

4 mm

7815z05/0602

44,5 86,5 124,5 164


AGA57.2 10 (6x) 40
17

7815m08/0102
113
130
80

7 (4x)
7 (4x)

7 (4x) 3
AGA57.3
7815m05/0202
123,8

113
80

14,5 103,3 18
164

©2008 Siemens Building Technologies HVAC Products GmbH


12/12 Subject to change!

Building Technologies CC1N7815en


HVAC Products 06.10.2008

You might also like