Checklist For Retaining Wall Submission and Inspection Requirements
Checklist For Retaining Wall Submission and Inspection Requirements
Checklist For Retaining Wall Submission and Inspection Requirements
1. Definitions:
a. Wall Height: Wall height is the measurement from the grade level in front of the wall at a given location
to the grade level behind the wall at the same cross section. In the case of a tiered wall system, this
measurement is from the grade level in front of the lowest wall to the highest wall at a given cross
section.
b. Tiered Wall: When several small height walls are constructed to replace one high wall along a given
cross section, these walls will be considered to act together as one wall if the horizontal distance
between adjacent walls is less than two times the height of the wall at the lower elevation.
Note: If the spacing between the walls is greater than two times the height of the wall at the lower
elevation, each wall will be considered to act independently and will be treated as a separate wall and a
separate permit shall be obtained for each wall.
c. Surcharge: Load transmitted to a retaining wall either from a slope steeper than 3H:1V or from parking
areas, roadways, or building foundations.
2. Separate building permits are required for each retaining wall higher than 3 feet.
3. Retaining walls shall require a structural design, signed and sealed by a design professional registered in the
Commonwealth of Virginia, to be submitted for plan review approval and issuance of a building permit. The
following are two exceptions to this requirement:
a. A retaining wall that does not support a surcharge and is no more than 4 feet in height will generally be
a walk through process.
b. The structural design for a retaining wall with a wall height equal to or less than 6 feet and not
associated with any surcharge does not require the seal and signature of a design professional.
4. Provide two copies of a site plan showing the location of the retaining walls. Indicate on the site plan
surface drainage behind and in front of the wall, the location of all structures within the vicinity of the
retaining walls, and the surcharge loads on the walls. Also, indicate the location of property lines and any
existing or proposed utility lines and their associated easements.
5. Provide two copies of construction plans. Construction plans shall show the following:
a. Wall elevations and multiple cross sections of each retaining wall. Show the actual ground slope at the
top and the toe of the retaining wall.
b. Method of subsurface drainage behind the wall.
c. Guardrail location and details for retaining wall systems in excess of 48 inches elevation to protect
pedestrian traffic (see Policy 1.12 Retaining Wall Safety Devices).
d. Specifications for the construction materials.
e. Specifications for the backfill material and compaction requirements.
f. Structural details and dimensions of the retaining wall.
g. Bearing capacity of the foundation soil.
Page 1 of 3 Version 2019-07-19
Building Development Division. 5 County Complex Court, Prince William, VA, 22192. 703-792-6930. www.pwcgov.org/BDD
Checklist for Retaining Wall Submission and Inspection Requirements – page 2
6. Provide two copies of structural design calculations. Calculations shall address the effect of surcharges on
the walls.
7. Provide two copies of the geotechnical engineering report and global stability analysis for retaining walls
that are greater than 8 feet in height. A global stability analysis may also be required for walls
8 feet or less in height if subjected to surcharge.
8. Walls with height greater than 8 feet or walls higher than 4 feet carrying surcharge shall require special
inspections.
MENTS
REQUIRE-
SURCHARGE
SURCHARGE NR BP, IS BP, IS, SI BP, IS, GS, SI
CATEGORY NR BP, IS, GS, BP, IS, GS, BP, IS, GS, SI,
II OR III GR SI, GR GR
SOILS
BP = Building Permit Required
IS = Internal Stability Analysis, Signed and Sealed by a Registered Design Professional in the State of Virginia
GS = Global Stability Analysis Required
SI = Special Inspection Required
GR = Geotechnical Report Required; Letter Report for Category II Soils and Detailed Report for Category III Soils
NR = Not Required
TP = Mandatory Third Party Inspections Managed by Special Inspections Section
When a wall is crossing (or influencing) multiple lots, one Permit is sufficient to build the wall; however, all
addresses must be attached to the BLD case during Building Plan Intake and Code 39 is to be added to each
BLD case by the Residential Plan Reviewer.
The following Codes may apply to a Single Family Dwelling (SFD) permit with or without a Retaining Wall:
• Code 1 SFD
• Code 39 SFD with Retaining Wall on lot or within an area of influence
• Code 33 Retaining Wall only
NOTE: PLEASE CALL 703-792-6112 TO SCHEDULE A MEETING FOR ALL PROJECTS THAT FALL
UNDER SPECIAL INSPECTIONS.
No permit or inspections are required for retaining walls less than 3 feet high. The following schedule of
inspections will be required on all other retaining walls proposed for construction in the County. Inspections of
Items A shall be performed by a County Inspector or, if the owner chooses, by an approved third party engineer.
Inspection of item B shall be mandatory third party inspections managed by the Special Inspections Section.
Item B inspections will be performed by an approved third party engineer. Item C inspections shall be under the
Special Inspections Program and shall be performed by a Special Inspections Inspector. The County shall issue
the final certificate of use and occupancy only after the approved third party engineer submits the Retaining
Wall Inspection Certification, and final inspections by the County.
B. Greater than 4 feet to less than 8 feet high walls (require Mandatory Third Party Inspections
Managed by Special Inspections Section):
1. Footing (Sub-Grade)
2. Drainage System
3. Controlled Fill
4. Structural Components
5. Guardrail
6. Layout
7. Final Inspection.
C. 8 feet and higher walls or walls categorized as complex structures (Special Inspections required),
e.g., 4 feet and higher walls with up-slope and/or down-slope steeper than 1:3 or carrying any other
surcharge:
1. Footing (Sub-Grade)
2. Drainage System
3. Controlled Fill
4. Structural Components
5. Guardrail
6. Layout
7. Final Inspection.
Page 3 of 3 Version 2019-07-19