Building Design With Limited Ductility Walls
Building Design With Limited Ductility Walls
Building Design With Limited Ductility Walls
The project to be designed consists of an 8-story multifamily building with four apartments per floor (32) on a land of
387.70 m2, located on the coast.
The area of the 1st level is 387.70 m² and that of the other floors is 394.66 m², with a mezzanine height of 2.40 m.
circulation or common areas 36.00 m² on each floor.
The general architectural plan shows two defined blocks with two departments each of which has common circulation on
all levels.
Due to the high density of walls in both directions, reinforced concrete walls will be used on the 8 floors.
WALLS
10 cm walls will be assumed for the entire building, which will be verified with the seismic analysis. If greater height is
required, where appropriate. f'c=210 kg/cm² will be used.
The final thickness of the walls will depend on the design, and the plate can be increased to 15 cm.
SLABS
The slabs are 10 cm thick and a continuous bottom mesh that meets the minimum amount of 0 will be considered.
common (hall) will be considered 15 cm. Consider 8 mm and 12 mm canes. In bathrooms, using a 20 c slab will use
f'c=175 kg/cm².
FOUNDATION
For the design of the foundation, the use of a foundation plate with a minimum thickness of 0.30, load-bearing 1.50
kg/cm² and concrete of f'c=210 kg/cm² has been proposed.
Other considerations:
SYMMETRY: The building to be designed in this project has adequate symmetry in both directions, an important
network.
RESISTANCE: The resistance is basically provided by the 0.10 m reinforced concrete walls, thus guaranteeing adequate
resistance of the whole, also having appropriate continuity and thus avoiding high
DUCTILITY: The characteristics of the project with the use of thin walls which makes us presuppose the use of double
mesh, which do not have a significant inelastic deformation capacity.
According to standard E.030, the maximum relative displacement of the mezzanine should not exceed 0.005. Seismic
resistance E-0.30 establishes that the seismic reduction factor is R=4.
LATERAL RIGIDITY: The elements that provide rigidity to the building are the reinforced concrete walls, in order to
adequate density and distribution of them in both important directions. resist the hori forces
Material Data:
Specific weight of Reinforced Concrete 2400kg/m3
Bedrooms, living room, dining
Weight of the Solid Slab h= 0.10 240kg/m2 room and kitchen
Weight of the Solid Slab h= 0.15 360kg/m2 Hall and common circulations
Weight of the Solid Slab h= 0.20 480kg/m3 Bathrooms
Period T (sec)
Other Factors:
XX displacement calculation factor: 0.75 (Regular structure)
DIPLOMATURE IN STRUCTURAL STUDY AND DESIGN
DIPLOMATURE IN STRUCTURAL STUDY AND DESIGN
IN THE XX ADDRESS
Relative mezzanine displacement Relative displacement
Story h Load Driftmax Displacement Diaphragm ux
Roof 8 2.50m Specter X 0.000891 2.673 ‰ D8 1.3667cm
Roof 7 2.50m Specter X 0.000919 2.757 ‰ D7 1.1614cm
Roof 6 2.50m Specter X 0.000925 2.775 ‰ D6 0.9489 cm
Roof 5 2.50m Specter X 0.000897 2.691 ‰ D5 0.7347 cm
Roof 4 2.50m Specter X 0.000825 2.475 ‰ D4 0.5266 cm
Roof 3 2.50m Specter X 0.000699 2.097 ‰ D3 0.3349cm
Roof 2 2.50m Specter X 0.000511 1.533 ‰ D2 0.1723 cm
Roof 1 2.50m Specter X 0.000228 0.684 ‰ D1 0.0531cm
↑
Comply!
<max. Drift
Roof 8 D8 1.0852671633 Does not apply Regular Does not apply Regular
Roof 7 D7 1.0808407742 Does not apply Regular Does not apply Regular
Roof 6 D6 1.0796942773 Does not apply Regular Does not apply Regular
Roof 5 D5 1.0777571118 Does not apply Regular Does not apply Regular
Roof 4 D4 1.0756641737 Does not apply Regular Does not apply Regular
Roof 3 D3 1.0745844633 Does not apply Regular Does not apply Regular
Roof 2 D2 1.072051962 Does not apply Regular Does not apply Regular
Roof 1 D1 1.0735676348 Does not apply Regular Does not apply Regular
Observation : In all cases, the relative displacements between floors do not exceed 1.2 or 1.5 of the displacement, so it is no
longer appropriate to verify if the maximum relative displacement between floors exceeds 50% of the displacement.
IN THE YY DIRECTION
Relative mezzanine displacement Displacement
Story h Load Driftmax Displacement Diaphragm oops
Roof 8 2.50m Spectrum Y 0.000871 2.613 ‰ D8 0.7945 cm
DIPLOMATURE IN STRUCTURAL STUDY AND DESIGN
After testing, the thickness of the M3 walls of axes 1-1 and 12-12 will be increased, from 0.10m to 0.15m.
CALCULATING AGAIN:
Mass Source
0 Additional Mass
IN THE XX ADDRESS
Relative mezzanine displacement Relative displacement
Displaceme
Story h Load Driftmax Diaphragm ux
nt
Roof 8 2.50m Specter X 0.000872 2.616 ‰ D8 1.3603 cm
Roof 7 2.50m Specter X 0.000900 2.700 ‰ D7 1.1562 cm
Roof 6 2.50m Specter X 0.000906 2.718 ‰ D6 0.9448cm
Roof 5 2.50m Specter X 0.000879 2.637 ‰ D5 0.7317cm
Roof 4 2.50m Specter X 0.000808 2.424 ‰ D4 0.5247cm
Roof 3 2.50m Specter X 0.000685 2.055 ‰ D3 0.3339 cm
Roof 2 2.50m Specter X 0.000502 1.506 ‰ D2 0.1720 cm
Roof 1 2.50m Specter X 0.000227 0.681 ‰ D1 0.0532cm
↑
Comply!
<max. Drift
DIPLOMATURE IN STRUCTURAL STUDY AND DESIGN
Roof 8 D8 1.0681038707 Does not apply Regular Does not apply Regular
Roof 7 D7 1.064333018 Does not apply Regular Does not apply Regular
Roof 6 D6 1.0628812764 Does not apply Regular Does not apply Regular
Roof 5 D5 1.0615942029 Does not apply Regular Does not apply Regular
Roof 4 D4 1.0587002096 Does not apply Regular Does not apply Regular
Roof 3 D3 1.0577516986 Does not apply Regular Does not apply Regular
Roof 2 D2 1.0563973064 Does not apply Regular Does not apply Regular
Roof 1 D1 1.0667293233 Does not apply Regular Does not apply Regular
Observation : In all cases, the relative displacements between floors do not exceed 1.2 or 1.5 of the displacement, so it is no
longer appropriate to verify if the maximum relative displacement between floors exceeds 50% of the displacement.
IN THE YY DIRECTION
Relative mezzanine displacement Displacement
Story h Load Driftmax Displacement Diaphragm oops
Roof 8 2.50m Spectrum Y 0.000797 2.391 ‰ D8 0.7607 cm
Roof 7 2.50m Spectrum Y 0.000803 2.409 ‰ D7 0.6392cm
Roof 6 2.50m Spectrum Y 0.000789 2.367 ‰ D6 0.5136cm
Roof 5 2.50m Spectrum Y 0.000747 2.241 ‰ D5 0.3905 cm
Roof 4 2.50m Spectrum Y 0.000669 2.007 ‰ D4 0.2746 cm
Roof 3 2.50m Spectrum Y 0.000551 1.653 ‰ D3 0.1700 cm
Roof 2 2.50m Spectrum Y 0.000391 1.173 ‰ D2 0.0855cm
Roof 1 2.50m Spectrum Y 0.000173 0.519 ‰ D1 0.0260 cm
↑
Comply!
<max. Drift
IN THE XX ADDRESS
Story Diaphragm h Load Ux (lbl 142) Ux (lbl 572) Average
Roof 8 D8 2.50m Specter X 1.4409 cm 1.2693 cm 1.3551 cm
Roof 7 D7 2.50m Specter X 1.2235 cm 1.0788cm 1.1512 cm
Roof 6 D6 2.50m Specter X 0.9993 cm 0.8820 cm 0.9407 cm
Roof 5 D5 2.50m Specter X 0.7736cm 0.6835cm 0.7286 cm
Roof 4 D4 2.50m Specter X 0.5545 cm 0.4905 cm 0.5225cm
Roof 3 D3 2.50m Specter X 0.3528 cm 0.3124 cm 0.3326 cm
Roof 2 D2 2.50m Specter X 0.1816cm 0.1610cm 0.1713cm
Roof 1 D1 2.50m Specter X 0.0561 cm 0.0498 cm 0.0530 cm
by Joint Spacements
IN THE YY DIRECTION
Oops (lbl Oops (lbl
Story Diaphragm h Load 142) 572) Average
Roof 8 D8 2.50m Spectrum Y 1.1823 cm 0.5398 cm 0.8611 cm
Roof 7 D7 2.50m Spectrum Y 0.9906 cm 0.4521 cm 0.7214 cm
Roof 6 D6 2.50m Spectrum Y 0.7977 cm 0.3641 cm 0.5809cm
Roof 5 D5 2.50m Spectrum Y 0.6081 cm 0.2776 cm 0.4429 cm
Roof 4 D4 2.50m Spectrum Y 0.4287 cm 0.1959 cm 0.3123 cm
Roof 3 D3 2.50m Spectrum Y 0.2679 cm 0.1227cm 0.1953 cm
Roof 2 D2 2.50m Spectrum Y 0.1354cm 0.0622 cm 0.0988 cm
Roof 1 D1 2.50m Spectrum Y 0.0415cm 0.0193cm 0.0304 cm
by Joint Spacements
DIPLOMATURE IN STRUCTURAL STUDY AND DESIGN
Lbl 142
DIPLOMATURE IN STRUCTURAL STUDY AND DESIGN
FORMATIVE
DATA
DESIGN OF THIN-WALL REINFORCED CONCRETE BUILDINGS 1
DESIGN OF AN 8-STORY BUILDING 1
GROUP N° 02 1
01. PROJECT DESCRIPTION 1
02. STRUCTURING AND PRE-SIZED. 2
WALLS 2
SLABS 2
FOUNDATION 2
DESIGN OF THIN-WALL REINFORCED CONCRETE BUILDINGS 4
DESIGN SPECTRUM 4
Period T (sec) 4
Other Factors: 4
DESIGN OF THIN-WALL REINFORCED CONCRETE BUILDINGS 5
DESIGN OF AN 8-STORY BUILDING 5
GROUP N° 02 5
03.02. Location of CM and CR 5
DESIGN OF THIN-WALL REINFORCED CONCRETE BUILDINGS 6
DESIGN OF AN 8-STORY BUILDING 6
GROUP N° 02 6
DESIGN OF THIN-WALL REINFORCED CONCRETE BUILDINGS 7
DESIGN OF AN 8-STORY BUILDING 7
GROUP N° 02 7
03.05. Location of CM and CR 7
Therefore the eccentricity in MASS SOURSE will be: 7
DESIGN OF THIN-WALL REINFORCED CONCRETE BUILDINGS 8
DESIGN OF AN 8-STORY BUILDING 8
GROUP N° 02 8
DESIGN OF THIN-WALL REINFORCED CONCRETE BUILDINGS 9
DESIGN OF AN 8-STORY BUILDING 9
GROUP N° 02 9
DESIGN OF THIN-WALL REINFORCED CONCRETE BUILDINGS 10
DESIGN OF AN 8-STORY BUILDING 10
GROUP N° 02 10
DESIGN OF THIN-WALL REINFORCED CONCRETE BUILDINGS 11
DESIGN OF AN 8-STORY BUILDING 11
GROUP N° 02 11
Lbl 142 11
↑ 19
CMy-CRy 20
↑ 21
↑ 23
Lbi 572 24
PRE-SIZING OF SOLID SLABS 23
Dead Loads: 24
Live Load or Overload: 24
LOAD METERING OF SOLID SLABS 24
TYPICAL APARTMENT 24
ROOF FLOOR 24
SOLID SLAB DESIGN 25
Ø 12mm 25
CHARACTERISTICS OF THE MATERIALS 25
CALCULATION OF THE LONGITUDINAL STEEL OF THE SLABS: 26
SOLID SLAB DESIGN 28
Ø 12mm 28
CHARACTERISTICS OF THE MATERIALS 28
As= 1.31 cm2 30
As= -3.17 30
Acting Shear: 32
0.00 39
@ 0.275m kg.m itive 39
Ø 6mm 41
0.00 46
@0.180m kg.m itive 46
cm2 cm 46
MEASUREMENT OF WALL LOADS 49
FLEXURE DESIGN (PLATE EDGE ELEMENTS) 52
÷ 24.00 52