Quick Programming Sheet
PC1616/PC1832/PC1864 v4.2
1. * 8 + INSTALLER CODE (“ 5555 ”) “Enter programming mode”.
2. Section 000 (Keyboard Registration [ 000 ]) → 0
Partition address space address
1 1
2 2
3 3
4 4
5 5
6 6
7 7
8 8
Ex. To program the LED Keypad in Partition 1, Space 1
Enter: 000 → 0 → 11 and we exit with “ # # “.
LCD keyboards must be registered in Space 8 , to later be recognized by the
DLS Software.
Ex. To program the LCD keypad in Partition 1 , Space 8
Enter: 000 → 0 → 18 and we exit with “ # # “.
Ex. To program the LCD keypad in Partition 2 , Space 8
Enter: 000 → 0 → 28 and we exit with “ # # “.
3. Section 201 Activate Partition
[ 201 ] → 1 2 3 _ _ _ _ 8 and we leave with “ # “.
Partition 1 is already activated by default (“ System Partition ”).
4. Section 202 Assignment of Zones to Partitions
To assign a Zone to a specific Partition, we turn on 1 … 8 , in [ 202 ]
[ 202 ] → 1 2 3 4 _ _ _ _ and we leave with “ # “.
Zones 1 2 3 4 will be assigned to Partition 1.
Partition 1 Partition 2
[202] ________ [210] ________
1 8 1 8
[203] ________ [211] ________
9 16 9 16
[ 210 ] → _ _ _ _ 5 6 7 8 and we leave with “ # “.
Zones 5 6 7 8 will be assigned to Partition 2
Ex. To assign Zones 11 and 15 to Partition 1
[ 203 ] → _ _ 3 _ _ _ 7 _ and we leave with “ # “.
Ex. To assign Zones 10 and 14 to Partition 2
[ 210 ] → _ 2 _ _ _ 6 _ _ and we leave with “ # “.
5. Section 005 System Timing
We have three times to program for each Partition.
[ 005 ] → 01 → _ _ _ Entry Time 1 ( Entry Zone 1 ) Ex. 030
_ _ _ Entry Time 2 ( Entry Zone 2 ) Ex. 020
_ _ _ Exit Delay Time Ex. 020
The system times for Partition 1 will be programmed.
Ex. [ 005 ] → 02 → 020 030 030 and we leave with “ # “.
It will be programmed for Partition 2 , Entry Time 1 : 20 sec.,
Entry Time 2 : 30sec. an Exit Delay time of 30 sec.
Entering subsection 09 , we program the bell cut-off time
[ 005 ] → 09 → _ _ _ Bell Cutoff Time Ex. 004.
6. System date and time: command “*6”.
We enter * 6 option 3 and enter the time and date with the next.
format: “hh mm MM/DD/YY”
* 6 → 3 → 1200 01/01/10 and we exit with “ # “.
12 PM will be entered as the System Time and Date.
from January 1, 2010.
7. Program user codes: command “*5”
We enter * 5 , then the master code (1234); the user number to be programmed
(Ex. 01 ), * , and the code to be programmed, as shown below:
* 5 → “Master Code” (1 2 3 4) → 01 * _ _ _ _ and we exit with “#”
Ex. To program User 1 with code 6 6 6 6
* 5 → 1 2 3 4 → 01 * → 6666 and we exit with “ # “.
On LCD keyboards if the User is programmed,
“P” will appear in the lower right corner.
8. Assign user to a partition: command “*5”
We enter * 5 , then the Master Code ( 1234 ), the number “8” , the user number
(Ex. 01 ), “ * “ , and the Partition Number,
as it's shown in the following:
* 5 → 1 2 3 4 → 8 → 01 → * → 1
We will have assigned User 1 , Partition 1 .
Ex. To assign User 2, Partition 2.
* 5 → 1 2 3 4 → 8 → 02 → * → 2 and we exit with “ # “.
9. Section 001 Zone Definitions
We type 001 and then the attribute of each Zone,
01 (Delay Zone 1), 03 (Instant Zone), etc.
[001] → 01, 02 , 03 ,03, 05
↓ ↓ ↓ ↓ ↓
Zone1 Z2 Z3 Z4 Z5
Ex. [ 001 ] → 01, 02, 03, 03, 05 and we leave with “ # “.
We gave attribute 01 to Zone 1 , 02 to Zone 2 , 03 to Zone 3 ,
03 to Zone 4 and 05 to Zone 5 .
10. Section 350 Communication Format
[ 350 ] → 06 Residential communication format
Ex. [ 350 ] → 06 and we exit with “ # “.
11. Section 160 Number of Dialing Attempts
[ 160 ] → 001 to 255
Ex. [ 160 ] → 005 and we exit with “ # “.
12. Section 301 1st Telephone Number [301] → _ _ _ _ _ _ _ and we leave with
“#”
302 2nd telephone number [302] → _ _ _ _ _ _ _ and we exit with “ #
“
303 3rd telephone number [303] → _ _ _ _ _ _ _ and we leave with
“#”
13. Section 320 Broadcast Codes
[ 320 ] → 11, 12, 13, 14, 15, 16, 17, 18 and we leave with “ # “.
The Alarm Report Code will be transmitted per Zone.
14. Section 006 Installer Code ( 5 5 5 5 by default)
[ 006 ] → 3 3 3 3 and we leave with “ # “.
The Installer Code will be changed to 3333.
15. Section 007 Master Code ( 1 2 3 4 by default)
[ 007 ] → 1 1 1 1 and we leave with “ # “.