Data Sheet - AER SOLEIR - VERMIO WINDFARM

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Technical Particulars of HT XLPE Cables

Customer Name: AER SOLEIR


Project Name: VERMIO WINDFARM

Sr. No. 1 2 3 4
S.No Particulars 1C X 300mm2 1C X 630mm2 1C X 800mm2 1C X 1200mm2
1 Name of Manufacturer Polycab India Ltd.
2 Type of Cable Al/SM/XLPE/SM/Poly-Al/HDPE
3 Voltage Grade kV 18/30 (36) 18/30 (36) 18/30 (36) 18/30 (36)
4 No of cores X size in sqmm 1 X 300 1 X 630 1 X 800 1 X 1200
Maximum conductor temperature under normal
5 a) 90°C
operating conditions
Maximum conductor temperature at the
b) 250°C
termination of short circuit
6 a) Permissible Voltage Variation ± 10%
b) Permissible Frequency Variation ± 5%
c) Combined Voltage & Frequency variation ± 10%
7 Conductor
Milliken Aluminium
a) Material Stranded Circular Aluminium (Class 2) (Water Blocked) (Class-2)
(Water Blocked)
Maximum d.c. resistance of conductor at 20° C
b) 0.100 0.047 0.037 0.025
(ohm/km)
c) Shape Stranded Compact Circular Milliken
(ii) Radial Water Blocking over conductor
a) Material Semi-conducting Water Swellable tape
8 Conductor Screening
a) Material Extruded Semi-conducting Compound
b) Nominal thickness (mm) 0.3 0.3 0.3 0.3
9 Insulation
a) Material XLPE as per IEC 60502 - 2
b) Nominal thickness (mm) 8.0 8.0 8.0 8.0
c) Core Identification Natural
10 Insulation Screening
(i) Non - Metallic
a) Material Strippable Semi-conducting Compound
b) Nominal thickness (mm) 0.3 0.3 0.3 0.3
(ii) Radial Water Blocking
a) Material Semi-conducting Water Swellable tape
b) Nominal thickness (mm) 0.3 0.3 0.3 0.3
(iii) Metallic
a) Material Poly- Aluminium Foil
b) Approximate thickness (mm) 0.25 0.25 0.25 0.25
11 Oversheath
a) Material HDPE Type 'ST7' as per IEC 60502 - 2
b) Minimum thickness (mm) 1.64 1.96 2.04 2.20
c) Colour of Outersheath Black Black Black Black
12 Electrical Parameters
Max. a.c. resistance of conductor at 90° C
a) 0.129 0.063 0.050 0.032
(ohm/km)
b) Approx. Cable Capacitance (µF/km) 0.25 0.33 0.37 0.47
c) Approx. Cable reactance (ohm/km) 0.12 0.11 0.10 0.09
d) Impedance of cable (ohm/km) 0.18 0.12 0.11 0.10
13 Continuous Current carrying capacities :-
(a) In Ground (A) at 20°C 414 594 670 800
(b) In Air (A) at 30°C 577 891 1034 1300
Short Circuit rating of conductor for the duration of
14 28.3 59.5 75.6 113.4
1 sec (kA)
15 Standard to which the cables confirm IEC 60502 - 2
16 Approx. overall diameter (mm) 45 55 59 71
17 Embossing POLYCAB ELECTRIC 18/30 (36)KV GRADE XLPE
YEAR POLYCAB ELECTRIC 18/30 (36)KV GRADE XLPE CABLE SIZE IEC 60502-
18 Printing
2 with Sequential meter marking at every one meter interval.
Note:-The values given above are subject to tolerances as per the relevant standards.

TDS No.230628-0244
Prepared by: Shubham