May Say
May Say
May Say
User Manual
Ichill 260L_D DUO
Ichill 261L_D DUO
(Firmware version 1.9)
Pag. 1 of 149
INDEX
1. GENERAL FEATURES .............................................................................................. 8
Pag. 2 of 149
29.2 Condenser High Pressure, Condenser High Temperature Or Evaporator Low Pressure ..........................66
Pag. 3 of 149
Pag. 4 of 149
41.4 Sanitary Hot Water Production: Valves In Water Circuit ___ Fs01=1 (Air/Water, Water/Water Unit) ...91
41.4.1 - Sanitary hot water operation when the unit is producing hot water .........................................................91
41.4.2 - Sanitary hot water operation when the unit is producing cold water ........................................................92
41.5 Sanitary Hot Water Production: Valves In Gas Circuit ___ Fs01=2 (Air/Water, Water/Water Unit) .......92
41.5.1 Sanitary hot water operation when the unit is producing hot water ............................................................92
41.5.2 - Sanitary hot water operation when the unit is producing cold water ........................................................92
44.1 Fan speed control if compressors and free cooling are used for cooling (CF97=3)......................................98
Pag. 5 of 149
Pag. 6 of 149
General advice
PLEASE READ BEFORE USING THIS MANUAL
This manual is part of the product and should be kept near the instrument for easy and quick reference.
The instrument shall not be used for purposes different from those described hereunder. It cannot be
used as a safety device.
Check the application limits before proceeding
The technical data and information in the user manual could change without obligation to notice.
SAFETY PRECAUTIONS
Check the supply voltage is correct before connecting the instrument.
Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden
temperature changes with high atmospheric humidity to prevent formation of condensation
Warning: disconnect all electrical connections before any kind of maintenance.
The instrument must not be opened.
In case of failure or faulty operation send the instrument back to the distributor or to “Dixell company with
a detailed description of the fault.
Consider the maximum current which can be applied to each relay (see Technical Data).
Ensure that the wires for probes, loads and the power supply are separated and far enough from each
other, without crossing or intertwining.
Fit the probe where it is not accessible by the end user.
In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with
inductive loads could be useful.
Pag. 7 of 149
1. GENERAL FEATURES
IC260L_D/261L_D is an electronic controller for chiller unit applications having one or two circuits:
Air/air
Air/water
Water/water
Condensing unit
Additional features :
Heat pump with gas reversibility
Pag. 8 of 149
Forced defrost
Different way to enable the defrost (temperature / pressure / digital input)
Boiler:
For heating integration
Two proportional outputs for condensing fan speed control (inverter or phase cut) with configurable
signal:
PWM
0÷10Volt
4÷20mA
Four proportional control outputs 0÷10V or ON/OFF
To control the dumper
To control an external relay
Complete alarm management
Internal Data logger up to 100 events
Supervisor / monitoring
TTL output for XJ485 interface (ModBus protocol) for XWEB Dixell monitoring system
Pag. 9 of 149
Pag. 10 of 149
3. USER INTERFACE
Meaning of the LEDs
Pag. 11 of 149
KEY FUNCTION
Pag. 12 of 149
KEY COMBINANTION
In Pr3 programming level Push In Pr3 defines if the parameter can be changed
SET and then the MENU key or not in the other levels.
Pag. 13 of 149
ON = compressor 1 active
Blinking = compressor 1 delay counting
ON = compressor 2 active
Blinking = compressor 2 delay counting
ON = compressor 3 active
Blinking = compressor 3 delay counting
ON = compressor 4 active
Blinking = compressor 4 delay counting
ON = compressor 5 active
Blinking = compressor 5 delay counting
ON = compressor 6 active
Blinking = compressor 6 delay counting
Flow alarm/ (differential) pressure switch / supply fan thermal (air / air unit) : is blinking if
the configuration of the digital input is active
Real time clock: On when the bottom display show the RTC
ON during the programming with time based parameter value
In function menu indicates the defrost delay counting
Condenser fan: ON if at least one of the PWM or relay outputs for fan control is active
Pag. 14 of 149
4. REMOTE KEYBOARD
The IC200L/D can be connected with 2 remote keyboard.
The remote keyboard can have the NTC probe on board that is used to show the room temperature and also
to control the temperature regulation.
To connect the remote keyboard it is necessary to use shielded cable for a maximum lenght of 150mt. In
case of no communication between the instrument and the remote keyboard the display shows “noL” (no
link).
Mod. VI620 – standard keyboard
Mod VI620S – keyboard with internal temperature probe
Use the connection cable CAB/CJ30 (2x0.2 mm2) to interface the IC connector to the shielded wire.
5. FIRST INSTALLING
On Board Clock (Optional)
Giving power supply the bottom display shows “rtC” alternated with a temperature or pressure value: It is
necessary to set the RTC.
If the probes are not connected the display shows the corresponding probe alarm messages. In this situation
the RTC setup and the programming are available.
ATTENTION
The RTC function is an optional and it is not possible to update the instrument but it is necessary to
order the instrument already complete of this features.
With power failure the RTC back-up battery maximum duration is 1 week. After this period it is necessary to
setup the clock again.
Pag. 15 of 149
6. WIRING CONNECTIONS
Ichill 260L
10 relays
18 digital inputs (free of voltage)
10 analogue inputs: NTC probes or through configuration 6 NTC / PTC and 4 pressure transducer 4÷20mA
or ratio-metric 0÷ 5.0Volt
6 modulating outputs
1 output for remote panel (max 2 remote panels)
1 TTL output for “Hot Key 64” connection or for XJ485, interface module for monitoring system, connection.
MAX current on the relay contacts relè 5(2)A 250V - MAX common current 12A 250V
Ichill 261L
14 relays
18 digital inputs (free of voltage)
10 analogue inputs: NTC probes or through configuration 6 NTC / PTC and 4 pressure transducer 4÷20mA
or ratio-metric 0÷ 5.0Volt
6 modulating outputs
1 output for remote panel (max 2 remote panels)
1 TTL output for “Hot Key 64” connection or for XJ485, interface module for monitoring system, connection.
MAX current on the relay contacts relè 5(2)A 250V - MAX common current 12A 250V
Pag. 16 of 149
Ichill 260D
10 digital outputs (relays)
18 digital inputs (free of voltage)
10 analogue inputs: NTC probes or through configuration 6 NTC / PTC and 4 pressure transducer 4÷20mA
or ratio-metric 0÷ 5.0Volt
6 modulating outputs
1 output for remote panel (max 2 remote panels)
1 TTL output for “Hot Key 64” connection
1 RS485 output with modbus RTU protocol for monitoring system, connection.
MAX current on the relay contacts relè 5(2)A 250V - MAX common current 12A 250V
Ichill 261D
14 digital outputs (relays)
18 digital inputs (free of voltage)
10 analogue inputs: NTC probes or through configuration 6 NTC / PTC and 4 pressure transducer 4÷20mA
or ratio-metric 0÷ 5.0Volt
6 modulating outputs
1 output for remote panel (max 2 remote panels)
1 TTL output for “Hot Key 64” connection
1 RS485 output with modbus RTU protocol for monitoring system.
MAX current on the relay contacts relè 5(2)A 250V - MAX common current 12A 250V
Pag. 17 of 149
Digital Inputs
Connection diagram for IC260L / IC261L / IC260D and IC261D.
GND = Digital inputs common terminal
Pag. 18 of 149
Pag. 19 of 149
Pag. 20 of 149
Pag. 21 of 149
If the dumper motor has a common pole for the 0..10V and the power supply, the connection has to be done
as showed below.
Ground connection has to be evaluated case per case.
Pag. 22 of 149
XJ485 Connection
Connection diagram for IC260L / IC261L .
The XJ485 interface is a converter between the RS485 and the TTL connector output. The RS485 uses two
terminals (+) and (-) that must be connected respecting the polarity to build the serial line. Use the
CAB/RS02 to connect the XJ485 interface to the TTL connector.
Pag. 23 of 149
Pag. 24 of 149
Pag. 25 of 149
Parameters involved:
CF08 = Configuration PB1
CF09 = Configuration PB2
CF14 = Configuration PB7
CF15 = Configuration PB8
CF16 = Configuration PB9
CF17 = Configuration PB10
0. Not enabled
1. Temperature probe PTC for compressor 1 discharge
2. Temperature probe PTC for compressor 2 discharge
3. Temperature probe PTC for compressor 3 discharge
4. Temperature probe PTC for compressor 4 discharge
5. Temperature probe PTC for compressor 5 discharge
6. Temperature probe PTC for compressor 6 discharge
7. Temperature probe PTC for solar panel
8. Temperature probe NTC for evaporator inlet
9. Temperature probe NTC for evaporator 1 outlet
10. Temperature probe NTC for evaporator 2 outlet
11. Temperature probe NTC for common evaporator outlet
12. Temperature probe NTC for common hot water condenser / recovery inlet
13. Temperature probe NTC for hot water of the condenser / recovery circuit 1 inlet
14. Temperature probe NTC for hot water of the condenser / recovery circuit 2 inlet
15. Temperature probe NTC for hot water of the condenser / recovery circuit 1 outlet
16. Temperature probe NTC for hot water of the condenser / recovery circuit 2 outlet
17. Temperature probe NTC for hot water of the condenser / recovery common outlet
18. Temperature probe NTC for free cooling water inlet circuit
19. Temperature probe NTC for dynamic setpoint external air / boiler / change over
20. Temperature probe NTC for combined defrost circuit 1
21. Temperature probe NTC for combined defrost circuit 2
22. Temperature probe NTC for auxiliary output 1
23. Temperature probe NTC for auxiliary output 2
24. Temperature probe NTC sanitary water 1
25. Temperature probe NTC sanitary water 1
26. Temperature probe NTC solar panel
27. Temperature probe NTC for condensing circuit 1
28. Temperature probe NTC for condensing circuit 2
After the number 28 the configuration can be selected from o 1 to c73 that allows to set an analogue input as
digital input (see polarity of the digital input/outputs).
Pag. 26 of 149
Pag. 27 of 149
Pag. 28 of 149
Pag. 29 of 149
Pag. 30 of 149
Upload: How to program a “Hot Key” with the parameters of the instrument
1. Turn on the power supply.
2. Insert the hot key.
3. Enter the function Menu.
4. Select the UPL function (on the bottom display).
5. Push SET key and immediately the instrument starts transfer the parameters into the Hot key.
During the upload the regulation is locked and the top display shows the “UPL” blinking label. At the end of
the UPLOAD will appear:
“End” if the programming procedure is completely OK, after 30seconds the regulation starts automatically.
“Err” if the programming procedure has found an error and the parameter have not been transferred.
Repeat the procedure.
To exit the UPL function push the MENU key or wait the time-out (15 sec).
Pag. 31 of 149
From the Pr2 level push the UP key for 2 seconds and the bottom display will show Pr3. The top display still
shows PAS.
After selecting the level push the SET key and the top display will show the 0 blinking value where to insert
the password .
Set the password level using the UP and DOWN keys then confirm with SET key.
Dependening on the password value there will be the different level access, if the password is wrong the
instrument shows the password value again.
ATTENTION:
For all the programming levels Pr1,2,3: the CF family (or configuration parameters) can not be
changed if the unit is running in chiller, heat pump. The user can check the leds #1 and #2 and if they
are blinking it is not possible to change this parameters but it is necessary to set the unit in stand-by
and then enter the programming again.
During the defrost the dF family can’t be programmed.
Pr2 LEVEL
Remember that it is necessary to know the old password value.
1. Enter the Pr2 level
2. Select a parameter family.
3. Inside the family select the “Pr2 - 2”, Pr2 on the bottom display, the current password value 2 on the top
display. Push the SET key to change the value that now is blinking.
4. Use the UP or DOWN key to insert the NEW PASSWORD value, then push SET to confirm the new
value.
5. The top display blinks for some seconds and then shows the next parameter
6. Exit the programming pushing SET + UP together or wait the timeout.
Inside the Pr2 level it is possible to change also the Pr1 password.
Pr3 LEVEL
Remember that it is necessary to know the old password value.
1. Enter the Pr3 level
2. Select a parameter family.
3. Inside the family select the “Pr3 - 3”, Pr3 on the bottom display, the current password value “3” on the
top display. Push the SET key to change the value that now is blinking.
4. Use the UP or DOWN key to insert the NEW PASSWORD value, then push SET to confirm the new
value.
5. The top display blinks for some seconds and then shows the next parameter
6. Exit the programming pushing SET + UP together or wait the timeout.
Inside the Pr3 level it is possible to change also the Pr1 and Pr2 passwords.
Pag. 32 of 149
If the selected parameter can not be changed the leds 1 and 2 are blinking.
In Pr1 level the user can not see and change any parameter of Pr2 and Pr3.
The MENU key allows to exit from a family to reselect another without exit the Pr1 level.
To exit completely the programming push SET + UP.
Pag. 33 of 149
The MENU key allows to exit from a family to reselect another without exit the Pr2 level.
The MENU key allows to pass to Pr1 starting from a family label.
To exit completely the programming push SET + UP.
Pag. 34 of 149
Example of programming:
The bottom display shows the parameter label (CF36) Digital input ID1 configuration;
Note that the top display shows “c” or “o” before the configuration number.
The selection 7 for the digital input ID1 (CF36) means that it is the “high pressure switch of circuit 1”.
The label “o” means that the digital input is active for open contact.
Otherwise if the selection is 7 for the digital input ID1 (CF36) = “high pressure switch of circuit 1”.
The label “c” means that the digital input is active for closed contact.
Pag. 35 of 149
2. Push SET key: the o label and the configuration number are blinking, use the UP or DOWN key and
select the proper polarity ( o / c ) of the function, then push SET key to confirm it all.
3. The top display blinks for some seconds and then it will shows the next parameter.
4. To exit the programming push SET + UP together or wait the timeout (15seconds).
Par. CF79 = 1: Through digital input programmed to start/stop the unit from remote control.
This selection is enabled if there is one digital input configured as start/stop from remote (remote chiller /
heat pump). I non of the digital input are configure the unit remains in stand–by.
The “open” status of the input forces the chiller running mode.
The “closed” status of the input forces the heat pump running mode.
The keyboard selection is disabled.
The key on the front panel can start/stop the unit only with the digital input selection
Par. CF79 =2: Automatic selection of the Chiller - Heat Pump through analogue input
The analogue input selection or change over function overrides the digital input C-HP function. If the external
air temperature are within the CF81 differential, the user can change the running mode from the keyboard.
If the unit is running with CF79 = 1 or CF79=2, and it is requested a running mode change, the controller
turns off all the outputs, starts a fixed delay time signalled by the chiller or heat pump blinking led. This
blinking led indicates which running mode will be activated after the compressor delay time protection.
Change Over
To change the running status the following condition must be respected otherwise the unit remains in stand -
by:
1. CF02=3 (heat pump selected)
2. CF79=2 and a NTC probe configured as NTC external air temperature for dynamic setpoint/ boiler /
change over
3. This probe is working properly
Parameters involved with the change over function:
CF80 Change over Setpoint. If the analogue input control (from probe) function is enabled, it represents the
limit temperature of the probe value under which the unit runs the Heat Pump mode.
CF81 Change over Differential. If the analogue input control (from probe) function is enabled, it represents
the limit differential temperature of the probe value to restart in the Chiller mode.
For external air temperature within CF81 the user can manually change the status from keyboard.
GRAPH: AUTOMATIC CHANGE OVER
Keyboard selection
CF78 = 0: pushing key the unit starts in chiller, pushing key the unit starts in heat pump
CF78 = 1: pushing key the unit starts in heat pump, pushing key the unit starts in chiller
Pag. 36 of 149
Push and release the key allows to start in chiller mode if CF78 =0, in heat pump if CF78 =1. When
the unit is running the corresponding led is on.
INPORTANT: To change from chiller to heat pump and viceversa the unit must be set in stand-by before
continuing.
Push and release the key allows to start in heat pump mode if CF78 =0, in chiller if CF78 =1er. When
the unit is running the corresponding led is on.
INPORTANT: To change from chiller to heat pump and viceversa the unit must be set in stand-by before
continuing.
The unit is considered in stand by when the leds and are both off. The stand-by is reached
each time the Chiller or the Heat Pump are turned off. During the stand by the user can:
Show all the probe measurements
Detect and reset the alarm events.
With contact OFF unit on stand-by , the top display shows OFF
With contact ON unit on stand-by , the top display shows On
With active contact select the chiller mode from the keyboard (the top display shows OnC) or heat pump (the
top display shows OnH), with the funcioning mode active the step is activated, the others, if availables, will
be requested by configured digital input as resources on circuits.
Pag. 37 of 149
With active contact if the unit is being switched off by keyboard it can be switched on by keyboard. If the unit
is being switched off by keyboard, in order to switch on the unit from digital input it must be deactivated and
activated.
With contact OFF unit on stand-by , the top display shows OFF
With contact ON unit on stand-by , the top display shows OnC
With active contact unit on chiller mode is activated also a step, the others, if availables, will be requested by
configured digital input as as resources on circuits.
With active contact if the unit is being switched off by keyboard it can be switched on by keyboard. If the unit
is being switched off by keyboard, in order to switch on the unit from digital input it must be deactivated and
activated.
With contact OFF unit on stand-by , the top display shows OFF
With contact ON unit on stand-by , the top display shows OnH
With active contact unit on chiller mode is activated also a step, the others, if availables, will be requested by
configured digital input as as resources on circuits.
With active contact if the unit is being switched off by keyboard it can be switched on by keyboard. If the unit
is being switched off by keyboard, in order to switch on the unit from digital input it must be deactivated and
activated.
Example in fig.1
Led cir1 is on: the top display shows the value of the output evaporator temperature ( 7.8°C) of the circuit 1,
The bottom display shows Out 1. Push SET key to swap to the circuit 2. Fig2
Led cir2 is on: the top display shows the value of the output evaporator temperature ( 7.9°C) of the circuit 2,
the bottom display shows Out 2.
Fig.1
Pag. 38 of 149
Fig.2
The dP family of parameters allows to set a custom display read-out. The user can change the default read-
out (both for instrument and remote terminals) of the measurements depending on the application.
Top Display
Bottom display
PARAMETER CORRESPONDING
DESCRIPTION
VALUE LABEL
dP01=0 No label No label
dP01=1 temperature probe of the evaporator water inlet Ein
Out1 circuit 1
dP01=2 temperature probe of the evaporator water outlet 1 and 2
Out2 circuit 2
dP01=3 temperature probe of the uscita common evaporator water outlet Eout
CIn1 circuit 1
dP01=4 temperature probe of the condenser water inlet
CIn2 circuit 2
dP01=5 temperature probe of the common condenser water inlet Cin
Pag. 39 of 149
Cou1 circuit 1
dP01=6 temperature probe of the condenser water outlet
Cou2 circuit 2
dP01=7 temperature probe of the common condenser water outlet Cout
dP01=10 temperature probe of the free cooling external air value FCEt
PARAMETER CORRESPONDING
DESCRIPTION
VALUE LABEL
dP02=0 No label No label
dP02=1 temperature probe of the evaporator water inlet Ein
Out1 circuit 1
dP02=2 temperature probe of the evaporator water outlet 1 and 2
Out2 circuit 2
dP02=3 temperature probe of the common evaporator water outlet Eout
CIn1 circuit 1
dP02=4 temperature probe of the condenser water inlet
CIn2 circuit 2
dP02=5 temperature probe of the common condenser water inlet Cin
Cou1 circuit 1
dP02=6 temperature probe of the condenser water outlet
Cou2 circuit 2
dP01=7 temperature probe of the common condenser water outlet Cout
dP02=10 temperature probe of the free cooling external air value FCEt
Pag. 40 of 149
Pag. 41 of 149
Push and release the SET key, the leds of the circuits are off and the set value is displayed.
In stand-by the bottom display shows SetC (set chiller), by pushing SET again the next label is SetH (set
heat pump ).
If the unit is running the only set displayed is related to the running mode.
Chiller mode: push SET one time, the bottom display shows the SEtC (set chiller) while the top display
shows the set value. Only if the Energy saving or the Dynamic Setpoint are active, pushing another time the
SET key, the bottom display shows “SEtr” (real setpoint), and the top display shows the setpoint that the
unit is really using for the thermoregulation.
Chiller mode: push SET one time, the bottom display shows the SEtH (set Heat pump) while the top display
shows the set value. Only if the Energy saving or the Dynamic Setpoint are active, pushing another time the
SET key, the bottom display shows “SEtr” (real setpoint), and the top diplay shows the setpoint that the unit
is really using for the thermoregulation.
ATTENTION
The SEtr label appears only if the Energy saving or the Dynamic Setpoint are active.
To modify the working setpoint it is necessary the setpoint values is displayed on both the display
(temperature / temperature or temperature / pressure o pressure/ pressure) without any identification label,
otherwise the SET key swaps to the circuit information.
Pag. 42 of 149
Pag. 43 of 149
5. Push SET and the top display blinks 0 while the bottom shows PAS. Insert the password using UP or
DOWN key (see AL parameter family). If the password is OK the ArSt blinks for per 3seconds, if the
password value is not correct the top display blinks 0 while the bottom shows PAS. If within 5 seconds
no value is inserted the display label come back to CO1r function.
6. To exit the COtr function push MENU or wait the timeout.
7. Repeat operation 1 – 5 to reset the other alarms.
THE ALARM LIST CONTAINS 100 EVENTS IN A FIFO STRUCTURE. WHEN THE MEMORY IS FULL
ANY NEW ALARM WILL ERASE THE OLDEST.
Pag. 44 of 149
If one circuit is disabled the bottom display shows diS alternated with the label name of the measurement
selected.
Circuit 1 = diS the bottom display shows b1dS = circuit 1 disabled.
Circuit 2 = diS the bottom display shows b2dS = circuit 2 disabled.
nd
The b2dS label appears only if the 2 circuit is configured,
Pag. 45 of 149
ATTENTION:
Pag. 46 of 149
If the proportional output Pou1 - Pou2 - Pou3 - Pou4 are configured to drive an external relay the display will show 0=relay off
and 100=relay on.
How to display the tempaerature of the internal temperaure sensor of the remote terminals 1
or 2
Inside the funcion menu it is possible to see the ambient temperature detected by the NTC sensor
FUNCTION trEM to show the temperature of the remote panels
Identification label trEM.
trE1 value of the NTC probe of the remote #1
trE2 value of the NTC probe of the remote #2
Select with UP or DOWN the trEM function
Push SET the trE1 or trE2 label is shown on the bottom display, the top display shows the probe value.
Use the UP or DOWN arrow to change beteween trE1 or trE2 read-out.
Pag. 47 of 149
To exit to the normal display read-out push MENU or wait the time – out time.
ATTENTION:
THE trEm function and the labels trE1 or trE2 appear only if the CF74 = =2 or 3 (remote panel 1
configuration) or if the parameter CF75 = 2 or 3 (remote panel 2 configuration).
How to program the Energy saving and how to Switch on / Switch off the Ichill by RTC
Enter the parameter programming:
1. Select the ES parameter family.
2. Select the parameters ES07 (Monday)…ES13 (Sunday).
Configuration table Energy saving or unit ON/OFF activation with rtc programming
MONDAY
X = 0 - Y= 0: energy saving and automatic on/off are both disabled
Pag. 48 of 149
MONDAY
X = 0 - Y= 1: the energy saving is disabled, the automatic on is enabled in time band 1
MONDAY
X = 3 - Y= 7: the energy saving is enabled in time band 1 and time band 2, the automatic on is enabled in
time band 1, time band 2 and time band 3.
WEEKLY PROGRAMMING
Repeat the daily programming for the other days of the week using parameters ES08..ES13.
When the unit is in OFF by RTC and the parameter ES18 > 0, if the user switch on the controller by
keyboard the unit stay on for ES18 time; when this time is elapsed the unit return to OFF.
Pag. 49 of 149
Pag. 50 of 149
It is possible to decide how many compressors are used in chiller, heat pump and sanitary water production.
o parameter CO76: number of compressors to use in chiller
o parameter CO77: number of compressors to use in heat pump
o parameter CO78: number of compressors to use in sanitary water
In case of contemporary production of sanitary water and chiller the number of compressors is defined
by sanitary water request.
Pag. 51 of 149
Chiller regulation
Pag. 52 of 149
Pag. 53 of 149
Par. CO54 Maximum time of work in neutral zone without rotation resource
When the temperature is inside the neutral zone and only one compressor is ON, a timer is activated
(parameter CO54); when this time is elapsed, the Ichill switch off the compressor and swith on an available
compresso.
If the parameter value is 0 the function is non activated.
Direct Start- Up
It is necessary to configure one relay to drive the contactor of the compressor.
EXAMPLE
Direct start up configuration for one compressor
Set the parameter CF54 = c39 direct start-up RL1 compressor 1
Pag. 54 of 149
Fig. 1
Part Winding
Each compressor needs two relay outputs:
Part Winding coil 1 of the compressor;
Part Winding coil 2 of the compressor.
The time delay between coil 1 and coil 2 activation is CO11 (decimal of second, in a range 0..5 seconds).
The maximum number of relay outputs is 8, this means 4 compressors managed with Part Winding start-up.
EXAMPLE
Part Winding configuration of the compressor relay outputs
Set the Par CF54 = c39 Part Winding coil 1 the compressor 1;
Set the Par CF55 = c40 Part Winding coil 2 of the compressor 1.
First step: the Part winding coil 1 of the compressor 1 (relay K1 of fig2) is switched on
Second step: after the CO11 delay is turned on the Part winding coil 2 of the compressor 1 (relay K2 of fig2).
To turn off the compressor the two relay outputs are both turned off at the same time.
Fig 2
Pag. 55 of 149
switched off (relay K2 Fig.2). Then after the CO12 delay time the relay of the line #2 is turned on (relay K3
Fig.3).
Compressor switching off:
the output relay of the line #1 and line #2 are switched off together.
Fig. 3
Pag. 56 of 149
Out relay Cap. step 2 OFF Cap. step 2 ON Cap. step 2 OFF Cap. step 2 OFF
Out relay Cap. step 3 OFF Cap. step 3 OFF Cap. step 3 ON Cap. step 3 OFF
Pag. 57 of 149
Out relay Cap. step 2 OFF Cap. step 2 OFF Cap. step 2 ON Cap. step 2 ON
Out relay Cap. step OFF Cap. step OFF Cap. step 1 OFF Cap. step 1 ON
ATTENTION
When working with capacity control in sequential step in direct or reverse modes: if the power requested is
50% and 75% the unit turn on also the step 25% that must be enabled to make run the other two.
CO07=1
First capacity step is used as lower step of the regulation.
First step to be activated is always the compressor inverter controlled; it will be swiched on when the
regulation requests 100% of the compressor power.
Pag. 58 of 149
To increase / decrease the power the compressor works by step of 1% of the power; every step is delayed
by CO62 at the start-up of the compressor and CO71 when the compressor works normally.
When the compressor inverter controlled is activated, it works at power configured by CO61 parameter for
CO60 seconds; after that:
if the parameter CO62=0 the compressor modulates the power according to the regulation request
the parameter CO620 the compressor is forced to works at maximum power and then it modulates
the power according to the regulation request
It is possible to limit the output % of the inverter compressor in Chiller, Heat pump and Sanitary hot water:
o maximum % output inverter in Chiller (parameter CO79)
o maximum % output inverter in Heat pump (parameter CO80)
o maximum % output inverter in Sanitary hot water (parameter CO81)
Pag. 59 of 149
Pag. 60 of 149
Parameters involved:
Pag. 61 of 149
It is possible to choose the number of compressors the controller can use in case of regulation faulty probe;
the parameter involved is Cr08.
It is possible to choose the number of condenser fan steps the controller can use in case of faulty probe; the
parameter involved is Cr09.
The Energy Saving function, in case of compressor rack unit, has dedicated set point and differential
(parameter Cr06 = “Energy saving offset for compressor rack unit”, Cr07 = “Energy saving differential for
compressor rack unit”)
Graph of the compressors thermoregulation
Pag. 62 of 149
Parameters involved:
The regulation is a steps; if two compressors with different weight are configured, are available 3 steps
activated in regulation band ST07 or ST08.
ATTENTION:
It is possible to protect the compressor setting a maximum number of activation per hour.
Pag. 63 of 149
CIRCUIT BALANCING
CO15 = 1
If the machine has 2 compressors in the circuit 1 and 2 compressors in the circuit 2, the sequence of
activation is:
st st nd nd
1 compressor circuit 1 1 compressor circuit 2 2 compressor circuit 2 2 compressor circuit 2
PUMP DOWN with low pressure switch or pump down pressure switch
CO36 = 1 Pump down enabled during the switching off (low pressure switch or pump down switch)
Before turning off the last compressor, the solenoid valve is closed; the compressor works until the pressure
switch is activated or after a maximum time CO39; in this case an alarm is displayed (b1PH or b2PH) but the
machine continuous to work as normal.
If the alarm occurs more than AL21 times per hour, the Ichill generate a manual alarm.
Low pressure alarm (when the low pressure switch is used) is disabled for AL02 time after valve activation
(AL02=0 the alarm is disabled when the compressor is OFF).
When the first compressor of the circuit is switched on, the solenoid valve is switched on 1 seconds before it.
CO36 = 2 Pump down enabled during the switching off and switching on (low pressure switch or
pump down switch)
Before turning off the last compressor, the solenoid valve is closed; the compressor works until the pressure
switch is activated or after a maximum time CO39; in this case an alarm is displayed (b1PH or b2PH) but the
machine continuous to work as normal.
If the alarm occurs more than AL21 times per hour, the Ichill generate a manual alarm.
Low pressure alarm (when the low pressure switch is used) is disabled for AL02 time after valve activation
(AL02=0 the alarm is disabled when the compressor is OFF).
When the first compressor of the circuit is switched on, the solenoid valve is switched on 1 seconds before it
if the pressure switch is not active.
If the pump down pressure switch remains activeated, the compressors does not restart and after CO39 time
a pump-down alarm is displayed.
The parameter AL23 allows to choose if the pump down alarm (during the switching on) is automatic or
manual reset:
AL23 =0 automatic reset; the compressor will rester when the pump down pressure switch is active
AL23=1 manual reset; if the number of pump down alarm per hour is lower than AL22 the reset is
automatic, manual reset; if the number of pump down alarm per hour is higher than AL22 the reset is
manual
PAR. CO36 = 3 Pump down enabled during the switching off only in chiller mode (low pressure
switch or pump down switch)
The pump douwn procedure works as CO36=1 but only in chiller mode; in heat pump mode the solenoid
valve is activated when the first compressor is ON and de-.activated when the last compressor is OFF.
PAR. CO36 = 4 Pump down enabled during the switching off and switching on inly in chiller
mode (low pressure switch or pump down switch)
The pump douwn procedure works as CO36=2 but only in chiller mode; in heat pump mode the solenoid
valve is activated when the first compressor is ON and de-.activated when the last compressor is OFF.
Pag. 64 of 149
CO36 = 1 Pump down enabled during the switching off (low pressure probe)
Before turning off the last compressor, the solenoid valve is closed; the compressor works until the pressure
falls below CO37 or after a maximum time CO39; in this case an alarm is displayed (b1PH or b2PH) but the
machine continuous to work as normal.
If the alarm occurs more than AL21 times per hour, the Ichill generate a manual alarm.
Low pressure alarm (when the low pressure switch is used) is disabled for AL02 time after valve activation
(AL02=0 the alarm is disabled when the compressor is OFF).
When the first compressor of the circuit is switched on, the solenoid valve is switched on 1 seconds before it.
CO35 = 2 Pump down enabled during the switching off and switching on (low pressure probe)
Before turning off the last compressor, the solenoid valve is closed; the compressor works until the pressure
falls below CO37 or after a maximum time CO39; in this case an alarm is displayed (b1PH or b2PH) but the
machine continuous to work as normal.
If the alarm occurs more than AL21 times per hour, the Ichill generate a manual alarm.
Low pressure alarm (when the low pressure switch is used) is disabled for AL02 time after valve activation
(AL02=0 the alarm is disabled when the compressor is OFF).
When the first compressor of the circuit is switched on, the solenoid valve is switched on 1 seconds before it.
When the first compressor of the circuit is switched on, the solenoid valve is switched on 1 seconds before it
if the pressure is higher than CO37 + CO38.
If the pressure remains lower than CO37 + CO38 the compressors does not restart and after CO39 time a
pump-down alarm is displayed.
The parameter AL23 allows to choose if the pump down alarm (during the switching on) is automatic or
manual reset:
AL23 =0 automatic reset; the compressor will rester when the pump down pressure switch is active
AL23=1 manual reset; if the number of pump down alarm per hour is lower than AL22 the reset is
automatic, manual reset; if the number of pump down alarm per hour is higher than AL22 the reset is
manual
CO36 = 3 Pump down enabled during the switching off only in chiller mode(low pressure probe)
The pump douwn procedure works as CO36=1 but only in chiller mode; in heat pump mode the solenoid
valve is activated when the first compressor is ON and de-.activated when the last compressor is OFF.
CO36 = 4 Pump down enabled during the switching off and switching on only in chiller mode (low
pressure probe)
The pump douwn procedure works as CO36=1 but only in chiller mode; in heat pump mode the solenoid
valve is activated when the first compressor is ON and de-.activated when the last compressor is OFF.
ATTENTION
If the pump down function is enabled, during the unit start-up from digital input as pump down
pressure switch and also from analogue input as low pressure transducer, the compressor will
restart only if both the inputs are satisfied.
Pag. 65 of 149
29. UNLOADING
UNLOADING ACTIVATION
When the evaporator water inlet temperature is higher than CO40 for CO42 time, the display shows and
the unit works with the number of compressors selected in CO49 parameter or CO96 speed in case of
inverter compressor.
EXAMPLE
2 circuits and 3 compressors per circuit
6 compressors are running; if CO49 = 2 in case of unloading 2 compressors are switched off and 4
continuous to work.
UNLOAD DE-ACTIVATION
When the evaporator water inlet temperature falls below CO40-CO41 the unloading function is disabled and
all compressor are available to work.
Unloading Information
If the evaporator water inlet temperature remains between CO40 and CO40-CO41, after CO43 time the
unloading function is deactivated.
EXAMPLE
2 circuits and 3 compressors per circuit
6 compressors are running; if CO49 = 2 in case of unloading 2 compressors are switched off and 4
continuous to work.
Pag. 66 of 149
EXAMPLE
2 circuits and 3 compressors per circuit
6 compressors are running; if CO49 = 2 in case of unloading 2 compressors are switched off and 4
continuous to work.
DE-ACTIVATION
Unloading function is disabled when the temperature of all the probes configured rise over CO55 + CO56 or
when the CO57 time is elapsed.
Pag. 67 of 149
When the last compressor is switched off, the water pump / supply fan is switched off after CO18 delay from
compressor.
When the unit is in stand-by or remote off and the Ar09 =1, if the regulation requires the antifreeze heaters
also the water pump is turned on.
During the defrost and when the compressor is off in dripping time the water pump/supply fan is on.
Note: During the defrost and when the compressor is off in dripping time, the pump is on.
The water pump works according the Dt between two probes, which can be choosen both in summer an
winter mode, among those configured in the instrument (Pb1, Pb2,…).
If the state of the water pump is tied to the state of the compressor, when last compressor is switched off the
water pump is forced to run at US60 speed for CO18 minutes, then it is switched off.
If the state of the water pump is not tied to the state of the compressor, when last compressor is switched off
the water pump is forced to run at US60 speed.
Chiller and chiller + sanitary hot water (machine with valves OUt1 and OUT2 in the gas circuit)
Pag. 68 of 149
Pag. 69 of 149
When the Ichill is switched on in chiller or heat pump, the water pump is immediately activated and the first
compressor is switched on after CO17 delay.
When the Ichill is in STD-BY or remote OFF the water pump is OFF (with a delay if CO23>0).
The parameter Ar09 allows to set the status of the water pump in case of antifreeze if the Ichill is in stand-by.
During the defrost and when the compressor is off in dripping time the water pump/supply fan is on.
If the water pump is OFF (reached set point), is possible to enable it to run to detect the right water
temperature.
At the end of the ON time, the controller verify if is necessary to switch on the compressor/s or not; if is not
necessary, the water pump is switched OFF for CO85 time and then switched on for another CO87 ON
cycle.
Pag. 70 of 149
If the parameter is set to 0, the maintenance signalling is disabled but the running hours counter remains
active.
Pag. 71 of 149
FA01 and FA02 parameters define the operative mode of the condenser fans.
Par. FA01 Fan regulation
0 = Output not enabled
1 = Always on
2 = ON/OFF step regulation
3 = ON/OFF continuous step regulation
4 = proportional fan speed
Par. FA02 Condenser fan operation mode
0 = Fan on only if compressor on
1 = Independent from the compressor and off during the stand–by / or from remote OFF
Example:
Par. FA01 = 1 / Par. FA02 = 0
Fans on when the compressor on (the fans work following the same output algorithm)
Pag. 72 of 149
Pag. 73 of 149
Pag. 74 of 149
in chiller and heat pump mode when first compressor is swtiched on if FA06>0 and/or FA30>0 the fan runs at
maximum speed for FA06 and/or FA30.
Post-ventilation:
in heat pump mode if FA31>0 and outside temperature > FA32, when last compressor is switched off the
condenser fan (if on at that moment) is forced at FA33 speed for FA31 seconds (outside temperature probe
is required).
Par. Ar07 = 3: function enabled; the regulation probe are evaporator water outlet circuit 1, evaporator water
outlet circuit 2 or evaporator common probe.
Par. Ar07 = 4: function enabled; the regulation probe is outside temperature.
Pag. 75 of 149
ATTENTION
When the outputs are configured as heaters circuit #1 and 2 they are both controlled by the NTC probe of
the common condenser outlet.
Boiler function
The function is enabled when:
One probe is configured as outside temperature.
Parameter Ar11 > 0.
ATTENTION
The heaters of the boiler are always off in case of:
flow switch alarm
water pump overload alarm
Pag. 76 of 149
Pag. 77 of 149
US 7 70.0 °C Dec
158 °F int
US8
50.0 Bar Dec
Auxiliary relay 1 winter maximum set point 725 Psi int
US 8 °C Dec
°F int
US6 US7
Bar Dec
Auxiliary relay 1 winter set point Psi int
US 9 0.1 25.0 °C Dec
0 45 °F int
0.1 14.0 Bar Dec
Auxiliary relay 1 summer differential 1 203 Psi int
US 10 0.1 25.0 °C Dec
0 45 °F int
0.1 14.0 Bar Dec
Auxiliary relay 1 winter differential 1 203 Psi int
US 11 Auxiliary relay 2 operating mode
0= Not enabled
1= Always available with direct action
0 4
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
US 12 Analogue input configuration for auxiliary relay 2 control . Allows to select which probe
1 10
value Pb1..Pb10 controls the relay
US 13 -30.0 °C Dec
-22 °F int
US15
0.0 Bar Dec
Auxiliary relay 2 summer minimum set point 0 Psi int
US 14 70.0 °C Dec
158 °F int
US15
50.0 Bar Dec
Auxiliary relay 2 summer maximum set point 725 Psi int
US 15 °C Dec
°F int
US13 US14
Bar Dec
Auxiliary relay 2 summer set point Psi int
US 16 -30.0 °C Dec
-22 °F int
US18
0.0 Bar Dec
Auxiliary relay 2 winter minimum set point 0 Psi int
US 17 70.0 °C Dec
158 °F int
US18
50.0 Bar Dec
Auxiliary relay 2 winter maximum set point 725 Psi int
US 18 °C Dec
°F int
US16 US17
Bar Dec
Auxiliary relay 2 winter set point Psi int
US 19 0.1 25.0 °C Dec
0 45 °F int
0.1 14.0 Bar Dec
Auxiliary relay 2 summer differential 1 203 Psi int
US 20 0.1 25.0 °C Dec
0 45 °F int
0.1 14.0 Bar Dec
Auxiliary relay 2 winter differential 1 203 Psi int
US 21 Maximum operating time of auxiliary realys 0 250 min
...
US 61 AUX 1 relay operation mode
1= only in Chiller
1 3
2= only in Heat pump
3= in Chiller and Heat pump
US 62 AUX 2 relay operation mode
1= only in Chiller
1 3
2= only in Heat pump
3= in Chiller and Heat pump
Pag. 78 of 149
1 = Function enabled, direct action, enabled also in stand-by and remote off
2 = Function enabled, direct action, enabled only if the Ichill is working in chiller or heat pump
3 = Function enabled, inverse action, enabled also in stand-by and remote off
4 = Function enabled, inverse action, enabled only if the Ichill is working in chiller or heat pump
US46=0
US46=1
US46=0
US46=1
Pag. 79 of 149
Pag. 80 of 149
US 36 -30.0 °C Dec
-22 °F int
US38
0.0 Bar Dec
Analog output 2 summer minimum set point 0 Psi int
US 37 70.0 °C Dec
158 °F int
US38
50.0 Bar Dec
Analog output 2 summer maximum set point 725 Psi int
US 38 °C Dec
°F int
US36 US37
Bar Dec
Analog output 2 summer set point Psi int
US 39 -30.0 °C Dec
-22 °F int
US41
0.0 Bar Dec
Analog output 2 winter minimum set point 0 Psi int
US 40 70.0 °C Dec
158 °F int
US41
50.0 Bar Dec
Analog output 2 winter maximum set point 725 Psi int
US 41 °C Dec
°F int
US39 US40
Bar Dec
Analog output 2 winter set point Psi int
US 42 0.0 25.0 °C Dec
0 45 °F int
0.0 14.0 Bar Dec
Analog output 2 summer differential 0 203 Psi int
US 43 0.0 25.0 °C Dec
0 45 °F int
0.0 14.0 Bar Dec
Analog output 2 winter differential 0 203 Psi int
US 44 Analog output 2 minimum value 0 US45 %
US 45 Analog output 2 maximum value US44 100 %
US 46 Operation mode under minimum value 0 1
...
US 63 AUX 1 analog output operation mode
1= only in Chiller
1 3
2= only in Heat pump
3= in Chiller and Heat pump
US 64 AUX 2 analog output operation mode
1= only in Chiller
1 3
2= only in Heat pump
3= in Chiller and Heat pump
Pag. 81 of 149
When the condenser temperature/pressure or evaporating pressure falls below dF02 and at least one
compressor is ON, the delay between two defrost dF09 starts counting.
The display of the keyboard shows the symbol blinkking.
dF09 counter is reloaded in case of power down, after a defrost cycle, when the Ichill change the operation
mode (from heat pump to chiller) or when the Ichill is in STD-BY or remote OFF.
dF09 counter is stopped if the last compressor of the circuit is turned off or if the pressure-temperature of the
condensing-evaporating probe increase over dF02.
Phase 2
When dF09 counter is elapsed the defrost procedure starts.
If one digital input is configured as “end defrost” is active, the unit waits until the contact is de-activated.
If one probe is configured as combined defrost:
If the combined defrost probe of the 1st circuit is lower than dF10 and/or the combined defrost probe of
the circuit 2 is lower than dF12, the process proceeds to phase 3.
st
If the combined defrost probe of the 1 circuit is higher than dF10 and/or the combined defrost probe of
the circuit 2 is higher than dF12, the process doesn’t proceed to phase 3
Phase 3
If dF07=0 the reversiong valve is activated without stopping any conmpressor and the defrost cycle is
immediately activated.
If df07>0:
1. Compressors are turned off
2. After dF07 / 2 the reversing valve is activated;
3. After dF07 / 2 the compressor is activated; if dF14=1 and / or dF15=1 all the compressor are activated
(with a delay of dF16).
Phase 4
Defrost ON
Condenser fan management:
If dF17=0: condenser fan are always off;
If dF17=1: condenser fans start if the condensing temperature-pressure value is higher than dF18 and
the regulation is the standard chiller regulation.
ATTENTION
The condenser fan is controlled by the condensing probe even if the evaporator probe is present and
configured.
PHASE 5
If dF08 = 0 the reversing valve is switched without stopping the compressors and the defrost ends.
If dF08 > 0:
1. All the compressors are switched off
2. After dF08 / 2 reversing valve is de-activated
3. After dF08 / 2 the heat pump regulation can restart
Pag. 82 of 149
ATTENTION: the forced defrost is not related to the dF09 /dF06 delay times, therefore the forced defrost cycle, if condition are OK, is
immediately executed.
ATTENTION: the manual defrost is not related to the dF09 /dF06 delay times, therefore the forced defrost
cycle, if condition are OK, is immediately executed for both circuits.
Pag. 83 of 149
ATTENTION:
The configuration error ACF1 is displayed if the parameter value of dF22 and dF23 is not permitted.
For only one condensing unit the dF22 and dF23 values must be not equal to 0.
ATTENTION:
also if the defrost through condenser fan is activated, if the external temperature < dF26, the defrost is
through hot gas (compressor ON).
If dF17 = 2 during dripping time (dF08 if different from 0) the ventilation is forced for the time set on dF08
only if the temperature detected by the probe configured as external temperature is > of the Par. dF26 value.
ATTENTION:
With defrost with only ventilation enabled the forced defrost is always with hot gas.
Pag. 84 of 149
If dF01=2, it determines the maximum duration of the defrost and even if, for the other cases, the end
defrost condition are still to be satisfied.
dF06 defrost delay time between the 1st and the 2nd circuit.
nd
After the interval dF09 determined by the defrost request of one of the circuits the other 2 circuits must wait
also the time dF06 before defrosting.
dF07 Compressor off time before the defrost (the led of the compressor is blinking)
After the dF09 delay and before activating the defrost, the compressors are stopped for the dF07 time.
Exactly in the middle of the dF07 time the 4-way valve is activated to equalise the pressure of the unit and when dF07 is completely
expired the compressors and the defrost can start.
This procedure does not respect the compressor on delay protection therefore the compressor is
immediately turned off and then on. If dF07 = 0 the compressor is not stopped and the 4-way valve is
immediately turned.
dF08 Compressor off time after the defrost (the led of the compressor is blinking)
After the defrost cycle the compressors are stopped for the dF08 time.
Exactly in the middle of the dF07 time the 4-way valve is activated to equalise the pressure of the unit and to
drain the external exchange unit, when dF08 is completely expired the unit restart in heat pump mode.
This procedure does not respect the compressor on delay protection therefore the compressor is
immediately turned off and then on. If dF08 = 0 the compressor is not stopped and the 4-way valve is
immediately turned.
DF09 Delay time to next defrost
It starts when the condensing/evaporating temperature/pressure probe value is lower than dF02 setpoint.
This time is reloaded if the power supply fails, after a defrost cycle or from a digital input request of defrost.
The time counting is interrupted if the compressor is turned off or if the temperature/pressure is higher then
dF02.
dF10 Temperature setpoint to start a combined defrost of the circuit #1.
It allows to set a temperature value to determines the beginning of a combined defrost.
After the dF09 counting the NTC probe of the combined defrost of the circuit #1 is compared to the dF10
setpoint, if the value is lower the defrost starts otherwise the unit runs in heat pump mode and when the
temperature decreases under dF10 the defrost immediately starts.
dF11 Temperature setpoint to end a combined defrost of the circuit #1.
It allows to set a temperature value to determine the end of a combined defrost.
When the NTC probe of the combined defrost of the circuit #1 becomes higher than dF10 setpoint the defrost
cycle stops.
dF12 Temperature setpoint to start a combined defrost of the circuit #2.
It allows to set a temperature value to determine the beginning of a combined defrost.
After the dF09 counting the NTC probe of the combined defrost of the circuit #2 is compared to the dF12
setpoint, if the value is lower the defrost starts otherwise the unit runs in heat pump mode and when the
temperature decreases under dF12 the defrost immediately starts.
dF13 Temperature setpoint to end a combined defrost of the circuit #2.
It allows to set a temperature value to determine the end of a combined defrost.
When the NTC probe of the combined defrost of the circuit #2 becomes higher than dF13 setpoint the defrost cycle stops.
dF14 All the resources on during the defrost of the circuit #1
0= Not enabled
1= Enabled
dF15 All the resources on during the defrost of the circuit #2
0= Not enabled
1= Enabled
dF16 Compressor step delay time in defrost.
dF17 Condensing fan control during defrost and dripping cycle
0= Not enabled
1 = Enabled in defrost
2= Enabled in defrost and in dripping time
If dF17 = 0: During the defrost the fan control is not active.
If dF17 = 1: when the condensing temperature/pressure value increases over dF18 the fans are turned on.
the fan control is determined by the same algorithm used in chiller mode.
If dF17 = 2: during the dripping time (dF08 <>0) the fan are turned on for the time duration set in dF08 .
dF18 Pressure / temperature setpoint to force the fans on during the defrost
When the temperature/pressure rises over this value the fan are turned on at the maximum speed.
dF19 Time delay before starting a forced defrost
It determines a delay time before starting the defrost cycle
dF20 Temperature / pressure setpoint to force a defrost
Pag. 85 of 149
It determines a temperature/pressure setpoint under which the dF19 starts counting, when dF19 is expired if
the temperature/pressure is still lower than dF20 the defrost is immediately executed.
ATTENTION If during the dF19 counting the temperature rises over df20+dF21(differential) the process is
aborted and the dF19 time reloaded.
dF21 Forced defrost differential
dF22 defrost mode for unit with two circuits
Operative mode:
0= Independent
1= The condition are satisfied in both circuits
2= At least one circuit has reached the start condition
dF23 It determines the end of the defrost for unit having two circuit and common condensing ventilation
Operative mode:
0= Independent
1= The end defrost condition are satisfied In both circuits
2= At least one circuit has reached the end defrost condition
dF24 Start / stop defrost probe
Start / stop defrost from analog input
0= start and stop with condenser temperatur / pressure probe
1= start with evaporator pressure probe / stop with condenser temperatur / pressure probe
2= start with condenser temperatur / pressure probe / stop with evaporator pressure probe
3= start and stop with evaporator pressure probe
Pag. 86 of 149
Compressors regulation:
- FS49=0 the compressors are switched on when sanitary temperature < FS03 (sanitary water
set point) – FS04 (proportional band); all the compressors are switched on with a delay of CO03
seconds each other
- FS49=1 the proportional band is divided by the number of compressors; at every step
(proportional band/number of compressors) a compressor will be switched on
Pag. 87 of 149
After all the available steps (compressors and heaters) have been enabled, they remain activated until the
sanitary water set-point has been reached. At which point the heating elements are switched off immediately,
while the compressors are switched off in order, with a CO03 delay between each one.
In the event of sanitary water probe 1 faulty (the sanitary water regulation probe), the sanitary water function
is stopped and disabled; the controller will regulate normally in chiller or heat pump mode.
In the event of sanitary water probe 2 faulty (not involved in the regulation), the alarm is signalled without
affecting heat regulation in any way; sanitary water will continue to be produced normally even if the display
probe is not working properly.
If there is an error with the heat regulation probe (for the chiller or heat pump) during production of sanitary
water, the machine will continue to operate but the regulation of the chiller or heat pump is disabled and
sanitary water continues to be produced.
Pag. 88 of 149
FS12=1 time-bands; Ichill with internal real time clock is required (you need to configure the day of
activation FS18 and the start time FS17).
To disable the function is necessary to configure FS12=0 and FS13=0 or FS12=1 and FS18=0 or FS12=2
and FS17=0:00.
The function is enabled when the machine is ON. If the request for an anti-legionella cycle is made when the
machine is switched off, the cycle will start immediately when the machine is next switched on and the
priority is given to anti-legionella cycle.
If instead heat regulation is prioritized, the anti-legionella cycle will run when the chiller/heat pump set-point
is reached.
The function must remain active for the minimum time configured with parameter FS19 (activated when the
temperature of the sanitary water reaches the anti-legionella set-point) and can last a maximum of FS29
minutes.
If FS02=0 the Anti-legionella cycle starts when cooling/heating set point is reached.
FS46=0 Compressors and heaters used at the same time in Anti-legionella cycle
When the anti-legionella cycle is active, all the compressors and heating elements configured for the sanitary
water are switched on; once the set-point (FS14) is reached, the compressors are switched off (delayed of
CO04 time) while the heating elements are switched off when the the set-point (FS14) + band (FS20) is
reached.
The anti-legionella cycle is enabled for FS19 time; during this time the machine works to maintain the anti-
legionella set point.
The Anti-legionella cycle lasts maximum FS29 minutes.
It is possible to switch off the compressors if the sanitary water temperature reaches FS50 temperature.
At the end of this procedure, the controller returns to the production of sanitary water or normal
heating/cooling regulation.
If the FS02 parameter (operating priority) gives priority to heating/cooling regulation and the production of
anti-legionella needs to be enabled, then the heat regulation set-point has to be reached beforehand.
The anti-legionella cycle has to end before heating/cooling regulation can start, even if the FS02 parameter
gives the priority to heating/cooling regulation.
Pag. 89 of 149
If FS02 =0, priority is given to the production of chilled/hot water; sanitary hot water is produced once the
chiller/heat pump requests has been satisfied.
The production of anti-legionella is stopped in case of chiller/heat pump requests.
If FS02=1, priority is given to the production of sanitary water (or anti-legionella). Chilled water or hot water
can be produced once the need for sanitary hot water has been satisfied (if required).
If FS02=2, if the digital input configured as “Sanitary water priority” is active, the priority is given to the
production of sanitary water.
If defrosting is required, this takes priority over the production of sanitary water or anti-legionella even if
FS02=1.
if CO16=2 (evaporator water pump on if at least a compressor is on), the parameter FS47 allows to
choose if the water pup is on or off in case of sanitary hot water production. If the machine has the
sanitary valves placed in the gas circuit, in case of contemporary cooling and sanitary hot water
production, the evaporator water pump is on.
If only one water pump is needed for cooling, heating and sanitary water, the evaporator water pump has to
be configured.
The times for managing the sanitary water pump are as follows:
The valve 1 and valve 2 are switched with the delay of FS27 seconds from start-up of the sanitary water
pump
The sanitary water pump is switched off with the delay of FS28 seconds from switching valve 1 and valve 2
The sanitary water flow switch is operated according to the times of the evaporator flow switch (parameter
AL15, AL16, AL17 and AL18).
Sanitary water flow switch, solar panel flow switch and overload sanitary water pump.
It is possible to enable the sanitary water flow switch by setting appropriately parameters AL65..AL68.
It is possible to enable the solar panel flow switch by setting appropriately parameters AL69..AL72.
If sanitary water flow switch or sanitary water pump overload is active, sanitary water regulation is disabled;
heating and cooling regulation proceed normally.
If solar panel flow switch is active, solar panel regulation is disabled; heating and cooling regulation proceed
normally.
Pag. 90 of 149
Inside the time band or when the digital input is active to the sanitary water set point is applied an offset
(parameter ES32) and the new differential for the regulation is ES33.
41.4 Sanitary Hot Water Production: Valves In Water Circuit ___ Fs01=1 (Air/Water,
Water/Water Unit)
41.4.1 - Sanitary hot water operation when the unit is producing hot water
When sanitary hot water production is required (and it has priority), the sequence of operation is the
following:
the sanitary water pump is switched on
after a delay of FS27 seconds, sanitary valve 1 is swithed on
after a delay of FS10 seconds the sanitary valve 2 is switched off
Sanitary hot water is produced until the FS03 set-point is reached.
Once the sanitary water set-point is reached, the sequence of operation is the following:
sanitary valve 2 is switched on
after a delay of FS10 seconds the sanitary water valve 1 is switched off
after a delay of FS28 seconds the sanitary water circulation pump is switched off
Pag. 91 of 149
41.4.2 - Sanitary hot water operation when the unit is producing cold water
When the production of sanitary water is required (and it has priority), it is necessary to reverse the cycle as
follows:
the compressors are switched off
after the dF07/2 delay the 4-way valve status is reversed
after dF07/2 the compressors are switched on
after a delay of FS27 seconds valve 1 is switched on
after the FS10 delay the sanitary water valve 2 is switched off
The production of sanitary water stops once the set-point is reached and it will be possible to return to
produce cold water (if needed):
the compressors are switched off
the valve 2 is switched on
after the FS10 delay the sanitary water valve 1 is switched off
after a delay of FS28 seconds the sanitary water circulation pump is switched off
after a delay of dF08/2 the 4-way valve status is reversed
after a delay of dF08/2 the compressors are switched on as per normal if required by the chiller
regulator
41.5 Sanitary Hot Water Production: Valves In Gas Circuit ___ Fs01=2 (Air/Water,
Water/Water Unit)
41.5.1 Sanitary hot water operation when the unit is producing hot water
When sanitary hot water production is required (and it has priority), the sequence of operation is the
following:
the sanitary water pump is switched on
after a delay of FS27 seconds the valve 1 is activated
after a delay of FS10 seconds the sanitary water valve 2 is switched off
Sanitary hot water is produced until the FS03 set-point is reached.
41.5.2 - Sanitary hot water operation when the unit is producing cold water
When the production of hot sanitary water is required, the sequence of operation is different and depend on
the status of the compressors:
Pag. 92 of 149
The following two cases could occur during the production of sanitary hot water:
The sanitary water set-point is reached when the chiller is working (the chiller set-point is not
reached):
the sanitary water valve 2 is switched on
after the FS10 delay the sanitary water valve 1 is switched off
after a delay of FS28 seconds the sanitary water circulation pump is switched off
At the end of this phase, if necessary, the machine continues to regulate in chiller mode.
The regulation temperature reaches the chiller set-point (parameter ST01) and the sanitary hot
water production is working:
the sanitary water circulation pump stays on
the sanitary water valve 2 is switched on
after the FS10 delay the sanitary water valve 1 and the compressors are switched off
after the DF07/2 delay the 4-way valve status is reversed
after dF07/2 the compressors are switched on again to produce hot sanitary water
after the FS11 delay from the 4-way valve switching, the sanitary water valve 1 is switched
on
after the FS10 delay the sanitary water valve 2 is switched off
Once the sanitary water set-point is reached:
the sanitary water valve 2 is switched on
after the FS10 delay sanitary water valve 1 is switched off
after FS28 seconds the sanitary water circulation pump and the compressors are
switched off
after the dF08/2 delay the status of the 4-way valve is reversed
If the sanitary water production is working and the temperature detected by the chiller regulation
probe is greater than ST01+ST07 (cold water required), the sequence of operatiuon is the
following:
the sanitary water pump will remain on
the sanitary valve 2 is switched on
after the FS10 delay the sanitary water valve 1 is switched off
the compressors are switched off
after the DF08/2 delay the 4-way valve status is reversed
after a delay of dF08/2 the compressors are switched on to produce chilled water and
sanitary water
When the sanitary water set-point is reached:
sanitary water valve 2 is switched on
after the FS10 delay the sanitary water valve 1 is switched off
after a delay of FS28 seconds the sanitary water circulation pump is switched off
b) None of the compressors are switched on for the production of chilled water
In this case, the cycle is reversed as follows:
the 4-way valve status is reversed
after dF07/2 the compressors are switched on
the sanitary water pump switches on after the FS11 delay from start-up of the compressors
after a delay of FS27 seconds the sanitary water valve 1 is switched on
after the FS10 delay the sanitary water valve 2 is switched off.
Once the sanitary water set-point is reached, the sequence of operation is the following:
the sanitary valve 2 is switched on
after the FS10 delay the sanitary water valve 1 and the compressors are switched off
after a delay of FS28 seconds the sanitary water circulation pump is switched off
Pag. 93 of 149
after the DF07/2 delay the 4-way valve status is reversed and normal regulation is
restored.
If chilled water is required during the production of sanitary water, operation is the same as in the
previous case.
Though appropriate configuration of FS55 and FS56 parameters is possible to use the solar panel in heating
or for sanitary hot water production.
The solar panel is managed through the valve and water pump control; their status depend from:
solar panel temperature
regulation probe (typically heating regulation probe or sanitary water regulation probe); this probe is
defined in FS57 and FS58 parameters
if sanitary water temperature < FS23-FS24, the valve of the solar panel is open and the water pump is on
if sanitary water temperature > FS23, , the valve of the solar panel is close and the water pump is off
If:
solar panel temperature – sanitary temperature > FS59 (Dt to enable solar panel in sanitary water)
the solar panel are enabled to work; sanitary probe is defined by FS57 parameter (it is possible to set
another probe, if needed).
At first compressors are not used for sanitary hot water.
It is possible to set a maximum time to use solar panel (FS61); when this time is elapsed and sanitary set
point is not reached, the solar panel are disabled and compressors are switched on.
The sanitary water pump runs when solar panel are enabled.
In regulation, if
solar panel temperature – sanitary temperature < FS59
the solar panel are disabled and the hot sanitary water is done by compressors.
Dt control is done only at the time of the request of sanitary hot water; at this moment, if Dt< FS59 the solar
panel are not used and compressors are used for heating.
Pag. 94 of 149
the solar panel are enabled to work (valve is open and water pump on); heating probe is defined by FS58
parameter (it is possible to set another probe, if needed).
Compressors are normally managed by heating regulation.
In regulation, if
solar panel temperature – heating temperature < FS60
the solar panel are disabled and the heating is done by compressors.
Dt control is done only at the time of the request of heating; if Dt< FS60 the solar panel are not used and
compressors are used for heating.
Pag. 95 of 149
if T1 temperature – T2 temperature FS21, the Free cooling is enabled and the relay and analog
output are manages as figures below
if T1 temperature – T2 temperature < FS21 – FS22, the Free cooling is disabled
Pag. 96 of 149
Pag. 97 of 149
If the temperature detected by probe selected with FS62 parameter is lower than FS63 set point, the free
cooling is disabled.
The free cooling will be enabled when temperature detected by probe selected with FS62 parameter is
higher than FS63 + FS64.
44.1 FAN SPEED CONTROL IF COMPRESSORS AND FREE COOLING ARE USED
FOR COOLING (CF97=3)
When the free cooling is not active the condenser fan speed is managed like standard regulation.
If free cooling is active:
outside temperature > FS43 + FS44: condenser fan speed is forced at maximum speed
outside temperature < FS43: when outside temperature decreases below FS43 temperature, after
FS45 minutes the condenser fan speed is managed as standard regulation
1 Par. rC01 = 0.
2 Heat pump running mode, remote OFF or stand by.
3 The condensing temperature / pressure is higher than set rC06.
4 The input/output resources are not properly configured (alarm ACF9).
5 The remote recovery digital input is not activated.
FUNCTIONING
CIRCUIT # 1
Pag. 98 of 149
With the recovery function enabled, the unit running in chiller and with the temperature/pressure proper
condition, the unit can start the recovery of the first circuit if the corresponding digital input is active. When
the digital input is active the relay of the valve for the recovery of the first circuit is activated.
CIRCUIT # 2
With the recovery function enabled, the unit running in chiller and with the temperature/pressure proper
condition, the unit can start the recovery of the second circuit if the corresponding digital input is active.
When the digital input is active the relay of the valve for the recovery of the second circuit is activated.
After starting the function, if the digital input becomes not active the recovery function runs for the time set in
rC04 before stopping.
Between the end and the next recovery function the instrument waits the time set in the parameter rC05
even if the digital input is activated again.
RECOVERY START AND STOP OF THE TWO CIRCUITS CONFIGURED WITH CAPACITY STEPS
During the start and the stop of the function the time delay rC02 and rC03 are not counted and the valve is
immediately turned on or off.
RECOVERY START OF THE TWO CIRCUITS CONFIGURED WITH MORE THAN ONE CAPACITY STEP
Circuits 1 and 2 configured with more than one step of power (eg each circuit with three compressors), if the
thermoregulation requires to turn on one or more resources and the recovery is activated from the digital
input the unit turns on only one step and then waits the rC02 delay (this delay keep off all the other steps
after the recovery is started). After the delay the recovery valve is turned on and, after the rC03 time (this
delay keeps off all the other steps after the recovery is started), the other resources if necessary are turned
on.
RECOVERY STOP OF THE TWO CIRCUITS CONFIGURED WITH MORE THAN ONE CAPACITY STEP
Circuits 1 and 2 configured with more than one step of power (Eg. each circuit with three compressors). After
the rC04 time delay (minimum on time of the recovery function when activated) if the digital input of the
recovery is not active the units stops the new resources for the time set in rC02. After this delay the recovery
valve is turned off and the regulation restarts with its normal running condition.
RECOVERY START OF THE TWO CIRCUITS WITH ALL THE CAPACITY STEPS ACTIVATED
When the system is running with 100% (eg all the three compressor of a circuit are on) of power and the
digital input start the recovery function: before turning on the recovery valve one of the step (depending on
the time running hours), is turned off for the time set in rC02. After rC02 the recovery valve is turned on.
Then, after the rC03 time (this delay keeps off all the other steps after the recovery is started) the resource
forced off if necessary is turned on again.
RECOVERY STOP OF THE TWO CIRCUITS WITH ALL THE CAPACITY STEPS ACTIVATED
When the system is running with 100% (eg all the three compressor of a circuit are on) of power and the
digital input stop the recovery function: after the rC04 time delay (minimum on time of the recovery function
when activated) and before turning off the recovery valve, one of the step is turned off for the time set in
rC02. When the delay is expired the unit turns off the recovery valve and and the regulation restarts with its
normal running condition.
ATTENTION:
For both the circuits: when the compressor are off because of the thermoregulation and the digital input of
the recovery function is active, the recovery valve is disabled.
FUNCTIONING
Par. rC01 = 2 unit with two circuits working in parallel:
The recovery function from the digital inputs is divided in two steps:
Pag. 99 of 149
After starting, the recovery function will run at least for the time set in parameter rC04 (minimum time with
recovery on).
Between the end of a recovery cycle and the next start the unit waits the time set in Par. rC05 before starting
it again.
RECOVERY START–STOP OF THE CIRCUITS 1 AND 2 CONFIGURED WITH ONE STEP EACH
Both for recovery start or stop, the delay time rC02 and rC03 are not counted and the recovery valve is
immediately turned on or off.
RECOVERY START OF THE TWO CIRCUITS CONFIGURED WITH MORE THAN ONE CAPACITY STEP
Circuits 1 and 2 configured with more than one step of power (eg each circuit with three compressors), if the
thermoregulation requires to turn on one or more resources and the recovery is activated from the digital
input the unit turns on only one step and then waits the rC02 delay (this delay keep off all the other steps
after the recovery is started). After the delay the recovery valve is turned on and, after the rC03 time (this
delay keeps off all the other steps after the recovery is started), the other resources if necessary are turned
on.
RECOVERY STOP OF THE TWO CIRCUITS CONFIGURED WITH MORE THAN ONE CAPACITY STEP
Circuits 1 and 2 configured with more than one step of power (Eg. each circuit with three compressors). After
the rC04 time delay (minimum on time of the recovery function when activated) if the digital input of the
recovery is not active the units stops the new resources for the time set in rC02. After this delay the recovery
valve is turned off and the regulation restarts with its normal running condition.
RECOVERY START OF THE TWO CIRCUITS WITH ALL THE CAPACITY STEPS ACTIVATED
When the system is running with 100% (Eg. all the three compressor of a circuit are on) of power and the
digital input start the recovery function: before turning on the recovery valve one of the step (depending on
the time running hours), is turned off for the time set in rC02. After rC02 the recovery valve is turned on.
Then, after the rC03 time (this delay keeps off all the other steps after the recovery is started) the resource
forced off if necessary is turned on again.
RECOVERY STOP OF THE TWO CIRCUITS WITH ALL THE CAPACITY STEPS ACTIVATED
When the system is running with 100% (Eg. all the three compressor of a circuit are on) of power and the
digital input stop the recovery function: after the rC04 time delay (minimum on time of the recovery function
when activated) and before turning off the recovery valve, one of the step is turned off for the time set in
rC02. When the delay is expired the unit turns off the recovery valve and and the regulation restarts with its
normal running condition.
ATTENTION:
For both the circuits: when the compressor are off because of the thermoregulation and the digital input of
the recovery function is active, the recovery valve is disabled.
ATTENTION:
When the supply fan is on and the Ichill is forced in STD-BY or remote OFF (by digital input), the supply fan
will be switched off with a CO18 delay.
- when the number of the event is < AL20 to reset the alarm follow the procedure described in Cap.
39.2
- when the number of the event is = AL20 to reset the alarm follow the procedure described in Cap.
39.3 (a password is necessary to reset the alarm)
If the cause of alarm is already present, the display shows “Active” and it is not possible to reset the alarm.
If the cause of alarm is not present, the display shows “Reset” and it is possible to reset the alarm.
AP1 - AP2 - AP3 - AP4 - AP5 - AP6 - AP7 - AP8 - AP9 - AP10 PROBE FAILURE
Label on alarm AP1 = PB1 probe alarm…AP10 = PB10 regulator probe alarm
visualization menu
Reason Probe configured but the read-out is not in the range
Reset Probe not configured or probe in the right range
Restart Automatic
Symbol On the display the symbol is blinking
Action Alarm Relay + and buzzer on
Loads The behaviour of the load depend on witch probe is on error (regulation probe
= all loads OFF; external temperature probe = only loads involved on this
probe)
ATTENTION
The alarm relay and the buzzer are activated only if the alarm appears during normal running conditions.
When the temperature setpoint has been reached and CO16/CO21= 2, the icon blinks without alarm.
NOTE ABOUT THE FLOW ALARM
CO16 / CO21=0 Water pump not enabled.
The alarm is managed only if one digital input is configured as flow switch, the restart is always automatic.
CO16 / CO21=1 Water pump with continuous control.
The alarm is managed only if one digital input is configured as flow switch, the restart is always automatic,
in stand–by or remote OFF ( pump off), it becomes manual after AL16 time.
In chiller or heat pump only. During the functioning of the unit any flow alarm stop the loads described in
the table, the water pump follow its regulation algorithm and is turned off, after AL16 time.
CO16 / CO21=2 Compressor on – pump on
The alarm is managed only if one digital input is configured as flow switch, the restart is always automatic,
in stand–by or remote OFF ( pump off), it becomes manual after AL16 time.
During the functioning of the unit any flow alarm stop the loads described in the table, the water pump follow
its regulation algorithm and is turned off, after AL16 time it is completely locked.
MANUAL RESTART OF THE FLOW ALARM
After AL16 time it is necessary to enter the function Menu to reset the alarm itself. The alarm message
DOES NOT DISAPPEAR if the alarm condition is still on. The water pump, if configured, can start and the
alarm is by-passed for AL18 seconds.
AL15 Alarm flow delay after on pump.
When the water pump starts the AL15 delay stops any flow alarm to reach the normal flow condition.
AL16 Maximum time flow switch alarm active befor to block the water pump
It determines maximum time of flow alarm active before to block the water pump.
ATTENTION
With air/water or water/water units and CF01=1,2 the minimum number of events per hour is 1.
AL17 Active flow input duration
Within this time the flow alarm must be active and after AL17 is expired the alarm is signalled. The counter
starts after AL15 and allows to filter the improvise flow reduction or the possible bubbles of air.
AL18 Not active flow input duration
Within this time the flow alarm must be not active and, after this time, the previous alarm is automatically
reset (if automatic) or, if manual, the unit can be restarted.
Reset Digital input configured as generic alarm with stop regulation not active after
the delay in Par. AL44
Restart Automatic – It becomes manual after AL42 events/hour
Logged only if manuale
Symbol On the display the symbol is blinking
Action Alarm relay + buzzer ON
REGULATION
Alarm Alarm relay + buzzer ON
Other loads OFF
ATTENTION
If during AL44 the alarm stop and start again the AL44 time delay is reloaded.
ATTENTION
If during AL53 the alarm stop and start again the AL44 time delay is reloaded.
ATTENTION
If during AL53 the alarm stop and start again the AL44 time delay is reloaded.
ACF6
The total number of compressor of the 2 circuits ( CF04 + CF05 ) is:
>6
> 4 with no direct compressor start-up (CO10 ≠ 0) or the number of steps
is ≠ 0 (CF06),
> 2 and the intermittent valve is configurated with ON (CO08) and OFF
(CO09 ) ≠ 0
Pump-down function but at least in one circuit
The pump-down solenoid relay is not present
No pump-down pressure switch or evaporating probe when
the pump-down is enabled with unit in start
Or
No low pressure switch configurated.
The compressor configuration with CF04 and CF05 but not the relay
outputs:
Main
Intermittent valve when enabled with the ON / OFF time, CO08 / CO09
≠ 0
When the by-pass time ≠ 0 and there is no partialization or by-pass
valve configured
Motor part_2 / centre of the star with part-winding or star-delta
The necessary step valve configurated
One relay is configured
Too much compressors
Intermittent valve when ON / OFF time CO08 / CO09 ≠ 0
By-pass gas when the by-pass = 0
Compressor Motor coil 2 / center of the star with direct compressor
start-up
Wrong configuration of the capacity step valve
ACF7
Evaporator pump
√ Enabled (CO16 ≠ 0) but the relay is not configured
√ Not enabled (CO16 = 0) but the relay is configured
Condenser pump
√ Enabled (CO21 ≠ 0) but the relay is not configured
√ Not enabled (CO21 = 0) but the relay is configured
Allarm configuration water pump in antifizee alarm
if Ar24=1 and Ar25=0
or
ifAr25=1 and not probe configurated like NTC
if Ar29=1 and Ar30=0
or
Ar29=1 and wrong confìguration of the probes
ACF8
Thermoregulation probe
The thermoregulation probe (in chiller with ST09, in heat pump when
enabled with ST10) is not properly configurated (it does not exist or it is
not a NTC)
Compressor rack is configurated with termoregulation like pressure
probe and not exist a pressure probe
The parameters CO34 / CO35 define the hour set counters for the condenser water pump / Support water
pump.
They establish the load running hours limit of the pump/s or the supply fan to give a maintenance signalling.
If one of these parameters is equal to 0 the maintenance signalling of that load is disabled but the running
hours counter remains active.
b1AC - b2AC - b1Ac - b2Ac Antifreeze alarm / Low outlet temperature (Air / Air unit in Chiller
mode)
Label on alarm b1AC (anti-freeze alarm of the circuit #1 in chiller)
visualization menu b2AC (anti-freeze alarm of the circuit #2 in chiller)
b1Ac (anti-freeze alarm signalling of the circuit #1 in chiller)
b2Ac (anti-freeze alarm signalling of the circuit #2 in chiller)
Both the labels are displayed when the alarm is coming from the evaporator
inlet probe or evaporator common outlet probe or when there is only one digital
input configured.
Origin Normal conditions, stand-by, remote OFF: when the anti-freeze probe value is
lower than AL26 for AL28 seconds.
With the anti-freeze digital input is active.
Reset When the anti-freeze probe value is higher than A26+ AL27(differential)
With the anti-freeze digital input is active.
Restart Automatic – Manual after AL29 events per hours (Reset procedure in Menu
function).
If AL74=1 to reset the alarm is necessary to type the password
Symbol On the display the symbol is blinking
Action If AL30=0 only the compressors are turned off and than display shows b1Ac
b2Ac, the buzzer and the alarm relay are not activated.
If AL30=0 only the compressors are turned off and than display shows b1Ac
b2Ac, the buzzer and the alarm relay are activated.
If the alarm comes from the digital input also the anti-freeze heaters are turned
on.
b1AH - b2AH Anti-freeze alarm / Low outlet air temperaure(Air/Air unit only) on heat pump
mode
Label on alarm b1AH (anti-freeze alarm of the circuit #1 in heat pump)
visualization menu b2AH (anti-freeze alarm of the circuit #2 in heat pump)
b1Ah (anti-freeze alarm signalling of the circuit #1 in heat pump)
b2Ah (anti-freeze alarm signalling of the circuit #2 in heat pump)
Both the labels are displayed when the alarm is coming from the evaporator
inlet probe or evaporator common outlet probe or when there is only one digital
input configured.
Origin Normal conditions, stand-by, remote OFF: when the anti-freeze probe value is
lower than AL33 for AL36 seconds.
With the anti-freeze digital input is active.
Reset When the anti-freeze probe value is higher than AL33 + AL34.
With digital input ont active
Restart Automatic – Manual after AL37 events per hour (Reset procedure in Menu
function).
If AL74=1 to reset the alarm is necessary to type the password
Symbol On the display the symbol is blinking
Action If AL38=0 only the compressors are turned off and than display shows b1Ah -
b2Ah, the buzzer and the alarm relay are not activated.
If AL38=0 only the compressors are turned off and than display shows b1AH -
b2AH, the buzzer and the alarm relay are activated.
If the alarm comes from the digital input also the anti-freeze heaters are turned
on.
Attention
Par. AL35 anti-freeze alarm delay (low outlet air temperature air/air unit) when the unit starts in heat pump
mode.
In stand-by or remote OFF: there is an anti-freeze alarm and the time delay in AL35>0, if the unit is manually
turned on in heat pump from keyboard or remote input, the alarm is reset so the unit can start at least for the
time set in AL35 in order to heat the water or the air. After the AL35 delay if the anti-freeze probe is still lower
than AL33 setpoint for AL36 seconds the unit is locked again with an anti-freeze alarm.
Label on alarm b1hP (high pressure digital input of the circuit #1)
visualization menu b2hP (high pressure digital input of the circuit #2)
Origin In chiller or heat pump, if the condensing probe is higher than AL09 setpoint.
Reset If the condensing probe value is lower than AL09 –AL10 (differential)
Restart Reset procedure in Menu function.
Always manual AL54 = 0
Always automatic AL54 =16
From manual to utomatic if AL54 value is between 1 and 15
Symbol On the display the symbol is blinking
Action Alarm Relay + and buzzer on
Regulation
Condensing fan If FA02=0 the fan is forced at maximum speed for 60 seconds then switched
off
If FA02=1 the fan is forced at maximum speed for 60 seconds then regulate
according to normal fan regulation
b1lp - b2lp Low evaporating pressure of the circuit (with pressure transducers only)
Label on alarm b1lP (low evaporator pressure from analogue input #1)
visualization menu b2lP (low evaporator pressure from analogue input #2)
Origin The alarm is activated when at least one of the probes , configured as
evaporating control, is lower than AL03 setpoint if:
In chiller or heat pump mode;
Stand-by or remote OFF when AL08 = 1
In defrost when AL06=1
The alarm is not signalled if:
In defrost ,for the time AL07, when the 4-way valve is turned on.
For the time set in AL01 after turning on the compressor.
Reset When the condensing probe temperature is higher than AL03 + AL04
(differential)
Restart Automatic– Manual after AL05 events per hour (Reset procedure in Menu
function).
Symbol On the display the symbol is blinking
Action Alarm Relay + and buzzer on
ATTENTION When the pressure transducers are configured the low pressure alarms are related only to
transducer values.
Regulation
Compressor OFF
Other loads Not modified
C1HP - C2HP - C3HP - C4HP - C5HP - C6HP compressor high pressure alarms
Label on alarm C1HP ( compressor high pressure alarm 1) – … C6HP (compressor high
visualization menu pressure alarm 6)
Origin The unit is running and the digital input of the compressor high pressure switch
is active
Reset Digital input not active
Restart Reset procedure in Menu function
Reset procedure in Menu function
Always manual AL54 = 0
Always automatic AL54 =16
From manual to utomatic if AL54 value is between 1 and 15
Symbol On the display the symbol is blinking
Action Alarm Relay + and buzzer on
Regulation
Condensing fan If FA02=0 the fan is forced at maximum speed for 60 seconds then switched
off
If FA02=1 the fan is forced at maximum speed for 60 seconds then regulate
according to normal fan regulation
C1oP - C2oP - C3oP - C4oP - C5oP - C6oP - Pressure switch alarm / compressor oil
Label on alarm C1oP (Compressor pressure switch #1) … C6oP (Compressor pressure switch
visualization menu #6)
Origin The alarm is not signalled: during the AL01 delay after turning on the
compressor, during the AL12 delay that starts after the AL11 delay when the
unit is properly running
Reset Digital input not active
Restart Automatic - Manual after AL013 events per hour (Reset procedure in Menu
function).
If AL76=1 the alarm is only a warning and the compressor remains on
Symbol On the display the symbol is blinking
Action Alarm Relay + and buzzer on
C1dt - C2dt - C3dt - C4dt - C5dt - C6dt High compressor discharge temperature alarm
Label on alarm C1dt (High discharge temperature of the compressor #1) -…C6dt (High
visualization menu discharge temperature of the compressor #6)
Origin The compressor discharge temperature is higher than AL39 setpoint.
ATTENTION
The display resolution is 0.1°C until the read-out is 99.9, over 100°C it is 1°C.
Reset If the probe value of the high discharge temperature is lower than “AL39 -
AL40 (differential)”
Restart Automatic. Manual when there are AL41 per hour (Reset procedure in Menu
function).
Symbol On the display the symbol is blinking
Action Alarm Relay and buzzer on
Compressor involved OFF
b1Cu – b2Cu Unloading disabled from High condensing temperature / pressure in chiller
Label on alarm b1CU (unloading high temperature from condenser of the circuit # 1)
visualization menu b2CU (unloading high temperature from condenser of the circuit # 2)
Origin When the temperature/pressure of condenser probe control is higher then
CO44
Reset When the temperature/pressure of condenser probe is lower than CO44 –
CO45 (differential)
After unloading is activated and after Par. CO47
Restart Automatic
Symbol On the display the symbol is blinking
Action Alarm relay + buzzer OFF
b1Cu – b2Cu: Unloading from low condensing temperature / pressure in Heat pump
Label on alarm b1CU (unloading message from condenser #1)
visualization menu b2CU (unloading message from condenser #2)
Origin During normal running condition when the temperature/pressure of
evaporator/condenser probe is lower than < CO46 setpoint
Reset when the temperature/pressure of evaporator/condenser probe value is
higher than CO46 + CO47
After unloading is activated and after Par. CO48
Restart Automatic
Symbol On the display the symbol is blinking
Action Alarm relay + buzzer OFF
b1PH - b2PH: Pump Down stop alarm from pressure switch / Low pressure switch
Label on alarm b1PH (Pump down stop alarm of the circuit 1)
visualization menu b2PH (Pump down stop alarm of the circuit 2)
Origin Pressure switch: if CO36 = 1,2,3,4 and ID not active, the pump down stops
because of the timeout CO39.
Transducer: if CO36 = 1,2,3,4 and the set CO37 is not reached: the pump
stops because of the timeout CO39.
b1PL - b2PL Alarm during the Pump Down start-up from pump down pressure switch / Low
pressure transducer
Label on alarm b1PL (pump down alarm in start-up of circuit #1)
visualization menu b2PL (pump down alarm in start-up of circuit #2)
Origin Pump down pressure switch : CO36 = 1,2,3,4 and compressors start-up and
digital input not active for the time set in CO39
Pump down transducer: CO36 = 1,2,3,4, compressors start-up and the set
CO37 is not reached in the interval time CO39.
Reset From thermoregulation start-up and ID not active
From thermoregulation start-up with evaporating pressure higher than CO37 +
CO38 (differential)
Restart Automatic - Manual and logged after AL21 events per hour if AL23=1 (reset
procedure in function menu).
If AL23 = 0 it is automatic and not logged.
Symbol On the display the symbol is blinking
Action Alarm relay + buzzer ON when it becomes manual
The alarm relay is enabled only by configurating the corresponding output resource.
Keyaboard Alarm
Label on alarm
keyaboard Alarm description
visualization menu
No data communication between the keyaboard
noL
and the regulator.
Each hour counting is divided in 16 intervals, each made of 3600 / 16 = 225 seconds (3 minuts and 45
seconds).
1°Int 2°Int 3°Int 4°Int 5°Int 6°Int 7°Int 8°Int 9°Int 10°Int 11°Int 12°Int 13°Int 14°Int 15°Int 16°Int
After the unit start-up, each interval is marked as “not active”. During the interval counting, for 255seconds, if
at least an alarm event appears, the interval itself is marked “Active”.
Starting from the first interval the instrument calculates the 16 intervals and, at the end, it restats overwriting
from the first.
In this way the last hour is always monitored and counted the active intervals. when the number of active
intervals reaches the threshold set with the corresponding parameter the alarm becomes manual.
By setting the threshold (parameter)=0 the alarm is manual from its first activation while if the threshold=16
the alarm is always automatic (In this case, to change in manual, the threshold should be 17).
49.1 Alarm
Alarm Alarm description Comp. Anti freeze Support Evaporator Condenser Sanitary Solar Ventilaz. Auxiliary
Code heaters heaters Pump / Pump Water panel cond. relay
Boiler Supply fan pump Water Cir1 Cir2
pump
AP1..AP Yes (1) Yes (1)
Probe alarm Yes (1) Yes (1) Yes (1) Yes (1) Yes (1) Yes (1) Yes (1)
10
Low air temperature of the
ALti evaporator inlet (air / air unit)
Alarm
AEFL Evaporator flow alarm Yes Yes (boiler) Yes (3) Yes
ACFL Condenser flow alarm Yes Yes (3) Yes
AHFL Sanitary water flow switch alarm Yes (6) Yes Yes
APFL Solar panel flow switch alarm Yes (6) Yes Yes
AtSF Fan supply overload alarm Yes Yes Yes Yes
Evaporator 1 water pump overload
AtE1 Yes (4) Yes (boiler) (5) Yes Yes
alarm
Evaporator 2 water pump overload
AtE2 Yes (4) Yes (boiler) (5) Yes Yes
alarm
Condenser 1 water pump overload
AtC1 Yes (4) Yes Yes
alarm
Condenser 2 water pump overload
AtC2 Yes (4) Yes Yes
alarm
AtAS Sanitary water pump overload Yes (6)
AtHS Sanitary heaters overload
Evaporator 1 water pump
AEP1
maintenance
Evaporator 2 water pump
AEP2
maintenance support
Condenser 1 water pump
ACP1
maintenance
Condenser 2 water pump
ACP2
maintenance
ASAn Sanitary water pump maintenance
Solar panel water pump
ASUn
maintenance
ArtC Clock alarm
ArtF Clock failure
ALOC Generic alarm Yes Yes Yes Yes Yes
ALSF Phase sequence alarm Yes Yes Yes Yes Yes Yes Yes Yes Yes
AEE Eeprom alarm Yes Yes Yes Yes Yes
ACF1 Yes Yes Yes Yes
Configuration alarm Yes
ACF12
ArtF Faulty clock
ArtC Clock error
Unloading signalling from high
AEUn
temp. of evaporator water
Low evaporator inlet temperature
ALti
in air/air unit
High water temperature inlat
AEht Yes
evaporator
ALC1 General alarm Yes Yes Yes Yes Yes Yes
ALC2 Genearl alarm type 2 Yes (3) Yes (3) Yes (3) Yes (3) Yes (3) Yes (3)
b(n)PH Pump down alarm in stop regulation of the circuit (n) Yes Yes
b(n)PL Pump down in regulation start-up of the circuit (n) Yes Yes
b(n)dF Bad defrost circuit (n)
b(n)Cu Unloading from condenser high temp/press of the circuit (n)
b(n)Cu Unloading from evaporator low temp/press of the circuit (n) Yes Yes
b(n)rC Recovery function disabled in circuit (n)
b(n)ds Circuit (n) disabled from keyboard Yes Yes
b(n)Ac Anti-freeze circuit (n) message in chiller
b(n)Ah Anti-freeze circuit (n) message in heat pump
Cod. Descrizione allarme Comp. Resistenze Resistenze Pompa Pompa Ventilaz. Relè
Allarme Antigelo appoggio Evap. cond. cond. ausiliario
boiler Vent. Cir1 Cir2
mand.
noL Link problem between the Ichill and the remote keyboard
Label Description
CO 4 OFF delay time between two compressors or compressor and valve. During this time
0 250 Sec
the led of the next resource is blinking.
CO 5 Output time delay after the main power supply start-up to the unit.
0 250 10 Sec 10 sec
All the loads are delayed in case of frequently power failures.
Capacity Control
CO 6 Functioning (see Capacity Control)
0= With on/off steps
1= Continuous with steps and direct action 0 3
2= Continuous with steps and reverse action
3= Continuous with steps and direct total action
CO 7 Start-up with minimum compressor power / automatic start-unloading valve
0 = Only at the compressor start-up (Minimum power automatic start-unloading valve
off)
1= At the compressor start-up and during the termoregulation (Minimum power /
automatic start-unloading valve off) 0 3
2 = Only at the screw compressor start-up (Minimum power automatic start-unloading
valve off)
3= At the compressor start-up and during the termoregulation (Minimum power /
Unloading valve ON with compressor off)
CO 8 Relay ON time of the Solenoid valve Intermittent for screw compressor, with 0 the
0 250 Sec
function is not enabled.
CO 9 Relay OFF time of the Solenoid valve Intermittent for screw compressor 0 250 Sec
Compressor start-up
CO 10 Kind of compressor start-up
0= Direct ( vedi avviamento compressors )
0 2
1= Part - winding
2= Star-delta
CO 11 If CO10= 1 part - winding start-up time. To change the time delay between the two
contactors of the two compressor circuits.
1/10
Se CO10= 2 Star-delta start-up time. To change the time delay between the contactor 0 100 0.1 sec
Sec
of the line 1 and the contactor of the centre of the star. (see part – winding /start-
triangle functioning)
CO 12 If CO10= 2 Time of Star-delta start. Time delay to turn off the centre star contactor and 1/10
0 50 0.1 sec
to turn on the line 2 contactor (see Star-delta functioning) Sec
CO 13 By-pass gas valve start-up time / automatic start-unloading valve (capacity step
0 250 sec
control)
Rotating – Balancing – Compressors Thermoregulation
CO 14 Compressor rotation (See compressor rotation)
0 = Sequential
0 2
1 = Compressors rotation based on time running hours
2 = Compressors rotation based on number of starts-up
CO 15 Circuit balancing (See Circuit balancing)
0= Circuit saturation 0 1
1= Circuit balancing
Evaporator water pump
CO 16 Operative mode of the evaporator pump / supply fan (See Evaporator pump function)
0= Not enabled (evaporator pump or supply fan).
1= Continuous. When the unit is running in Chiller or HP the pump or the supply fan is
0 2
running.
2= With compressor. When a compressor is running also the pump or the supply fan is
running.
CO 17 ON compressor delay after water pump / supply fan start-up (See water pump
1 250 10 sec
functioning).
CO 18 OFF delay evaporator water pump / supply fan after compressor switching OFF. This
delay is also active when the unit is turned in stand-by (See evaporator water pump 0 250 Min
function).
CO 19 Number of time running hours for pump rotation (See water pump group function) 0 999 10Hr 10Hr
CO 20 Time to make run the pumps together before rotating from one to the other (See water
0 250 Sec
pump group function)
Condenser water pump
CO 21 Operative mode for condenser water pump (See condenser water pump function)
0= Not enabled.
0 2
1= Continuous. When the unit is running in Chiller or HP the is running.
2= With compressor. When a compressor is running also the pump is running.
CO 22 Free
CO 23 OFF delay condenser water pump after compressor switching OFF. This delay is also
0 250 Min
active when the unit is turned in stand-by (See evaporator water pump function).
CO 24 Number of time running hours for pump rotation (See water pump group function). 0 999 10Hr 10Hr
CO 25 Time to make run the pumps together before rotating from one to the other (See water
0 250 Sec
pump group function).
Load maintenance
CO 26 Compressor 1 operation time to generate maintenance warning 0 999 10 Hr 10 Hr
CO 27 Compressor 2 operation time to generate maintenance warning 0 999 10 Hr 10 Hr
CO 28 Compressor 3 operation time to generate maintenance warning 0 999 10 Hr 10 Hr
CO 29 Compressor 4 operation time to generate maintenance warning 0 999 10 Hr 10 Hr
CO 30 Compressor 5 operation time to generate maintenance warning 0 999 10 Hr 10 Hr
CO 31 Compressor 6 operation time to generate maintenance warning 0 999 10 Hr 10 Hr
CO 32 “Evaporator pump / Supply fan” operation time to generate maintenance warning 0 999 10 Hr 10 Hr
CO 33 2nd Evaporator pump operation time to generate maintenance warning 0 999 10 Hr 10 Hr
CO 34 Condenser pump operation time to generate maintenance warning 0 999 10 Hr 10 Hr
CO 35 2nd Condenser pump operation time to generate maintenance warning 0 999 10 Hr 10 Hr
Pump down
4 way valve
CO 75 Forced time to reverse the 4 way valve when the compressor is switched off 0 250 sec
Compressors capacity
CO 76 Maximum number of compressors to use in Chiller 1 10
CO 77 Maximum number of compressors to use in Heat pump 1 10
CO 78 Maximum number of compressors to use in Sanitary water 1 10
CO 79 Maximum % output of the inverter compressor in Chiller 1 100 %
CO 80 Maximum % output of the inverter compressor in Heat pump 1 100 %
CO 81 Maximum % output of the inverter compressor in Sanitary water 1 100 %
CO 82 Outside temperature to reduce inverter compressor speed in Heat pump -50.0 70.0 °C Dec
-58 158 °F int
0.0 50.0 Bar Dec
0 725 Psi int
CO 83 Hysteresis temperature to reduce inverter compressor speed in Heat pump 0.1 25.0 °C Dec
0 45 °F int
0.1 14.0 Bar Dec
1 203 Psi int
CO 84 Compressor speed if outside temperature > CO82 0 100 %
CO 85 Evaporator water pump OFF time if the set point is reached 0 250 10 min
CO 86 Evaporator water pump OFF time if the machine is STD-BY or OFF 0 250 10 Ore
CO 87 Evaporator water pump ON time 0 250 Sec 10sec
CO 88 Condenser water pump OFF time if the set point is reached 0 250 10 min
CO 89 Condenser water pump OFF time if the machine is STD-BY or OFF 0 250 10 Ore
CO 90 Condenser water pump ON time 0 250 Sec 10sec
CO 91 Minimum time between to switch on of the compressor 0 250 Sec
CO 92 Compressor activation delay starting from water solenoid valve activation 0 250 Sec
CO 93 Water solenoid valve de-activation delay starting from compressor de-activation 0 250 Sec
CO 94 % output of the inverter compressor in defrost 0 100 %
CO 95 Free cooling water pump operation time to generate maintenance warning 0 999 10 Hr 10 Hr
CO 96 % output of the inverter compressor in unloading 0 100 %
Auxiliary relay menu function
Auxiliary relay of the circuit 1
US 1 Auxiliary relay 1 operating mode (See graph and auxiliary relay functions)
0= Not enabled
1= Always available with direct action
0 4
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
US 2 Analog input configuration for auxiliary relay 1 control. Allows to select which probe value
1 10
Pb1..Pb10 controls the relay
US 3 -30.0 °C Dec
-22 °F int
US5
0.0 Bar Dec
Auxiliary relay 1 summer minimum set point 0 Psi int
US 4 70.0 °C Dec
158 °F int
US5
50.0 Bar Dec
Auxiliary relay 1 summer maximum set point 725 Psi int
US 5 °C Dec
°F int
US3 US4
Bar Dec
Auxiliary relay 1 summer set point Psi int
US 6 -30.0 °C Dec
-22 °F int
US8
0.0 Bar Dec
Auxiliary relay 1 winter minimum set point 0 Psi int
US 7 70.0 °C Dec
158 °F int
US8
50.0 Bar Dec
Auxiliary relay 1 winter maximum set point 725 Psi int
US 8 °C Dec
°F int
US6 US7
Bar Dec
Auxiliary relay 1 winter set point Psi int
US 9 0.1 25.0 °C Dec
0 45 °F int
0.1 14.0 Bar Dec
Auxiliary relay 1 summer differential 1 203 Psi int
US 10 0.1 25.0 °C Dec
0 45 °F int
0.1 14.0 Bar Dec
Auxiliary relay 1 winter differential 1 203 Psi int
Auxiliary relay circuit 2
US 11 Auxiliary relay 2 operating mode (See graph and auxiliary relay functions)
0= Not enabled
1= Always available with direct action
0 4
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
US 12 Analogue input configuration for auxiliary relay 2 control . Allows to select which probe
1 10
value Pb1..Pb10 controls the relay
US 13 -30.0 °C Dec
-22 °F int
US15
0.0 Bar Dec
Auxiliary relay 2 summer minimum set point 0 Psi int
US 14 70.0 °C Dec
158 °F int
US15
50.0 Bar Dec
Auxiliary relay 2 summer maximum set point 725 Psi int
US 15 °C Dec
°F int
US13 US14
Bar Dec
Auxiliary relay 2 summer set point Psi int
US 16 -30.0 °C Dec
-22 °F int
US18
0.0 Bar Dec
Auxiliary relay 2 winter minimum set point 0 Psi int
US 17 70.0 °C Dec
158 °F int
US18
50.0 Bar Dec
Auxiliary relay 2 winter maximum set point 725 Psi int
US 18 °C Dec
°F int
US16 US17
Bar Dec
Auxiliary relay 2 winter set point Psi int
US 19 0.1 25.0 °C Dec
0 45 °F int
0.1 14.0 Bar Dec
Auxiliary relay 2 summer differential 1 203 Psi int
US 20 0.1 25.0 °C Dec
0 45 °F int
0.1 14.0 Bar Dec
Auxiliary relay 2 winter differential 1 203 Psi int
US 21 Maximum operating time of auxiliary realys 0 250 min
Auxiliary proportional output n° 1
US 22 Auxiliary proportional output n° 1 operating mode
0= Not enabled
1= Always available with direct action
0 4
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
US 23 Analogue input configuration for auxiliary control 1
1 10
Allows to select which probe value Pb1..Pb10 controls output
US 24 -30.0 °C Dec
-22 °F int
US26
0.0 Bar Dec
Analog output 1 summer minimum set point 0 Psi int
US 25 70.0 °C Dec
158 °F int
US26
50.0 Bar Dec
Analog output 1 summer maximum set point 725 Psi int
US 26 °C Dec
°F int
US24 US25
Bar Dec
Analog output 1 summer set point Psi int
US 27 -30.0 °C Dec
-22 °F int
US29
0.0 Bar Dec
Analog output 1 winter minimum set point 0 Psi int
US 28 70.0 °C Dec
158 °F int
US29
50.0 Bar Dec
Analog output 1 winter maximum set point 725 Psi int
US 29 °C Dec
°F int
US27 US28
Bar Dec
Analog output 1 winter set point Psi int
US 30 0.0 25.0 °C Dec
0 45 °F int
0.0 14.0 Bar Dec
Analog output 1 summer differential 0 203 Psi int
US 31 0.0 25.0 °C Dec
0 45 °F int
0.0 14.0 Bar Dec
Analog output 1 winter differential 0 203 Psi int
US 32 Analog output 1 minimum value 0 US33 %
US 33 Analog output 1 maximum value US32 100 %
Auxiliary proportional output n° 2
US 34 Auxiliary proportional output n° 2 operating mode
0= Not enabled
1= Always available with direct action
0 4
2= Available only when the unit is on with direct action
3= Always available with reverse action
4= Available only when the unit is on with reverse action
US 35 Analogue input configuration for auxiliary 2 control
1 10
Allows to select which probe value Pb1..Pb10 controls output
US 36 -30.0 °C Dec
-22 °F int
US38
0.0 Bar Dec
Analog output 2 summer minimum set point 0 Psi int
US 37 70.0 °C Dec
158 °F int
US38
50.0 Bar Dec
Analog output 2 summer maximum set point 725 Psi int
US 38 °C Dec
°F int
US36 US37
Bar Dec
Analog output 2 summer set point Psi int
US 39 -30.0 °C Dec
-22 °F int
US41
0.0 Bar Dec
Analog output 2 winter minimum set point 0 Psi int
US 40 70.0 °C Dec
158 °F int
US41
50.0 Bar Dec
Analog output 2 winter maximum set point 725 Psi int
US 41 °C Dec
°F int
US39 US40
Bar Dec
Analog output 2 winter set point Psi int
US 42 0.0 25.0 °C Dec
0 45 °F int
0.0 14.0 Bar Dec
Analog output 2 summer differential 0 203 Psi int
US 43 0.0 25.0 °C Dec
0 45 °F int
0.0 14.0 Bar Dec
Analog output 2 winter differential 0 203 Psi int
US 44 Analog output 2 minimum value 0 US45 %
US 45 Analog output 2 maximum value US44 100 %
US 46 Operation mode under minimum value 0 1
Modulating evaporator water pump
US 47 Probe 1 selection for evaporator water pump modulation in chiller 0 10
US 48 Probe 2 selection for evaporator water pump modulation in chiller 0 10
US 49 Set point for maximum speed of modulationg evaporator water pump in chiller 30.0 70.0 °C Dec
-58 158 °F int
0.0 50.0 Bar Dec
0 725 Psi int
US 50 Proportional band for maximum speed of modulationg evaporator water pump in chiller 0.0 25.0 °C Dec
0 45 °F int
0.0 14.0 Bar Dec
0 203 Psi int
US 51 Minimum speed of the evaporator water pump in chiller 0 100 %
US 52 Maximum speed of the evaporator water pump in chiller 0 100 %
US 53 Probe 1 selection for evaporator water pump modulation in Heat Pump 0 10
US 54 Probe 2 selection for evaporator water pump modulation in Heat Pump 0 10
US 55 Set point for maximum speed of modulationg evaporator water pump in Heat Pump 30.0 70.0 °C Dec
-58 158 °F int
0.0 50.0 Bar Dec
0 725 Psi int
US 56 Proportional band for maximum speed of modulationg evaporator water pump in Heat 0.0 25.0 °C Dec
Pump 0 45 °F int
0.0 14.0 Bar Dec
0 203 Psi int
US 57 Minimum speed of the evaporator water pump in Heat Pump 0 100 %
US 58 Maximum speed of the evaporator water pump in Heat Pump 0 100 %
US 59 Speed of the water pump in Free Cooling 0 100 %
US 60 Speed of the water pump when compressor OFF 0 100 %
AUX output enable
US 61 AUX 1 relay operation mode
1= only in Chiller
1 3
2= only in Heat pump
3= in Chiller and Heat pump
US 62 AUX 2 relay operation mode
1= only in Chiller
2= only in Heat pump
3= in Chiller and Heat pump
US 63 AUX 1 analog output operation mode
1= only in Chiller
2= only in Heat pump
3= in Chiller and Heat pump
US 64 AUX 2 analog output operation mode
1= only in Chiller
2= only in Heat pump
3= in Chiller and Heat pump
Condenser fan
Parameters Description min max M. U. Resolution
FA 22 Over ride CUT- OFF in Heat pump. To set a temperature/pressure differential to keep 0.0 25.0 °C Dec
the minimum fan speed. 0 45 °F int
0.0 14.0 Bar Dec
0 203 Psi int
FA 23 Night speed in Heat pump. To set the maximum fan speed percentage value
0 100 %
(30..100%), it is related to the fan power supply.
Hot start
FA 24 Hot start setpoint -30.0 70.0 °C Dec
-22 158 °F int
FA 25 Hot start differential 0.0 25.0 °C Dec
0 45 °F int
3 / 4 step condenser Fan in Chiller mode
FA 26 ON/OFF regulation FA01 = 2/3 -30.0 70.0 °C Dec
SETpoint step n° 3 -22 158 °F int
0.0 50.0 Bar Dec
0 725 Psi int
FA 27 ON/OFF regulation FA01 = 2/3 -30.0 70.0 °C Dec
SETpoint step n° 4 -22 158 °F int
0.0 50.0 Bar Dec
0 725 Psi int
3 / 4 step condenser Fan in heat pump
FA 28 ON/OFF regulation FA01 = 2/3 -30.0 70.0 °C Dec
SETpoint step n° 3 -22 158 °F int
0.0 50.0 Bar Dec
0 725 Psi int
FA 29 ON/OFF regulation FA01 = 2/3 -30.0 70.0 °C Dec
SETpoint step n° 4 -22 158 °F int
0.0 50.0 Bar Dec
0 725 Psi int
FA 30 Pre ventilation in Heat Pump
0 250 Sec Sec
(only if FA01 = 4 )
FA 31 Post ventilation in Heat Pump 0 250 Sec 10Sec
FA 32 Outside temperature to enable post ventilation in Heat Pump -50.0 70.0 °C Dec
-58 158 °F int
FA 33 Condenser fan speed during post ventilation 0 100 %
Antifreeze heaters – Integration heating - boiler
Parameter Description min max m. u. Risoluzione
Ar 1 Anti-freeze heaters/integration heating setpoint for air/air unit in Chiller mode. -30.0 70.0 °C Dec
To set a temperature value, below this value the anti-freeze relay is activated. -22 158 °F int
Ar 2 Regulation band for antifreeze in Chiller mode. Dec
0.1 25.0 °C
Int
0 45 °F
Ar 3 Set Anti-freeze heaters/integration heating setpoint for air/air unit in HP mode. -30.0 70.0 °C Dec
To set a temperature value, below this value the anti-freeze relay is activated. -22 158 °F int
Ar 4 Regulation band for antifreeze in HP mode. -30.0 70.0 °C Dec
-22 158 °F int
Ar 5 Antifreeze heaters / integration heating in defrost
0= ON only with thermoregulation control 0 1
1= ON with thermoregulation and during the defrosting cycle
Ar 6 Antifreeze probe to manage heaters / support heaters in Chiller mode.
0= Not enabled
1= Evaporator inlet 0 3
2= Evaporator outlet 1 and 2
3= Evaporator outlet 1 and 2 and common outlet
Ar 7 Antifreeze probe to manage heaters / support heaters in HP mode.
0= Not enabled
1= Evaporator inlet. 0 3
2= Evaporator outlet 1 and 2.
3= Evaporator outlet 1 and 2 and common outlet.
Ar 8 Thermoregulation probe for anti-freeze / condenser heaters.
0= not enabled.
1= Condenser common water inlet probe.
0 4
2= Condenser common water inlet and condenser inlet 1 / 2 probe.
3= Condenser water outlet 1 / 2 probe.
4= Condenser water outlet 1 / 2 and common outlet.
Ar 9 Anti-freeze heaters or condenser/evaporator water pump control with unit in remote
OFF or stand-by mode:
0 1
0= Control not enable
1=Controlled by anti-freeze thermoregulation.
Ar 10 Anti-freeze heaters control for condenser/evaporator faulty probe:
0= Anti-freeze heaters OFF 0 1
1= Anti-freeze heaters ON
Boiler function
Ar 11 Boiler function
0=Not enabled
0 2
1=Enabled for integration heating
2= Enabled for heating
Ar 12 External air temperaure setpoint for boiler heaters (on) -30.0 70.0 °C Dec
-22 158 °F int
Ar 13 Temperature differential for boiler heaters (off) 0 25.0 °C Dec
0 45 °F int
Ar 14 Time delay before turning the boiler on 0 250 Min
Boiler function in Chiller mode
FS 34 Free cooling water pump OFF time if chiller only Free cooling 0 250 min
FS 35 Free cooling water pump ON time if chiller only Free cooling 0 250 sec
FS 36 Free cooling maximum time 0 250 min
FS 37 Set point Free cooling -50.0 70.0 °C Dec
-58 158 °F int
0.0 50.0 bar Dec
0 725 psi int
FS 38 Proportional band Free coling 0.1 25.0 °C Dec
0 45 °F int
0.1 14.0 Bar Dec
1 203 Psi int
FS 39 Minimum value Free cooling analog output 0 100 %
FS 40 Maximum value Free cooling analog output 0 100 %
FS 41 T1 probe selection for Free cooling
0 10
0=disabled, 1=Pb1, 2=Pb2, etc.
FS 42 T2 probe selection for Free cooling
0 10
0=disabled, 1=Pb1, 2=Pb2, etc.
FS 43 Outside temperature set point to force the maximum speed of condenser fan -50.0 70.0 °C
-58 158 °F
FS 44 Outside temperature differential to force the maximum speed of condenser fan 0.1 25.0 °C
0 45 °F
FS 45 Delay time of condenser fan regulation during Free cooling 0 250 min
FS 46 Antilegionella cycle opreration mode
0= compressors and heaters
1= compressors are first inserted and then heaters 0 3
2= only heaters
3= only compressors
FS 47 Evaporator water pump enabled is Sanitary water
0= enabled 0 1
1= disabled
FS 48 Probe selection to force exit from Sanitary water
0= disabled
1= probe Pb1 0 10
2= probe Pb2
...
FS 49 Start production Sanitary water
0= when all compressors are requested 0 1
1= when at least one compressor is requested
FS 50 Set point to force OFF the compressors during antilegionella cycle -50.0 70.0 °C
-58 158 °F
FS 51 Compressors safety time in sanitary water
0= safety time enabled 0 1
1= safety time disabled
FS 52 Set point to enable heaters for low sanitary water temperature -50.0 70.0 °C
-58 158 °F
FS 53 Proportional band to enable heaters for low sanitary water temperature 0.1 25.0
0 45
FS 54 Probe selection for low sanitary water temperature
0= disabled
1= Pb1 0 10
2= Pb2
...
FS 55 Solar panel opration mode for sanitary water
0= disabled
0 2
1= integration to heat pump
2= substitution to heat pump
FS 56 Solar panel opration mode for heating
0= disabled
0 2
1= integration to heat pump
2= substitution to heat pump
FS 57 Probe selection to calculate Dt of solar panel in sanitary water
0= disabled
1= Pb1 0 10
2= Pb2
…
FS 58 Probe selection to calculate Dt of solar panel in heating
0= disabled
1= Pb1 0 10
2= Pb2
…
FS 59 Dt to enable solar panel in sanitary water 0.1 25.0
0 45
FS 60 Dt to enable solar panel in heating 0.1 25.0
0 45
FS 61 Maximum operation time of solar panel if set point not reached 0 250
FS 62 Probe selection to disable the Free cooling for low temperature 0 10
FS 63 Set point to disable the Free cooling for low temperature -50.0 110.0 °C
-58 230 °F
FS 64 Differential to disable the Free cooling for low temperature 0.1 25.0 °C
0 45 °F
Alarms
Parameters Description min max m. u. Resolution
Low alarm
AL 1 Low pressure alarm delay from analog and digital input 0 250 Sec
AL 2 Low pressure alarm delay from digital input after compressor stop if the low pressure
switch is used for the pump down.
0 250 Sec 10 Sec
AL02= 0 low pressure alarm not enable with compressor OFF
AL02≠ 0 low pressure alarm enable after AL02 time with compressor OFF
AL 3 Low pressure alarm setpoint from analogue input -30.0 70.0 °C Dec
-22 158 °F int
0.0 50.0 bar Dec
0 725 psi int
AL 4 Low pressure alarm differential from analogue input 0.1 25.0 °C Dec
0 45 °F int
0.0 14.0 bar Dec
0 203 psi Int
AL 5 Maximum number of low pressure events from digital/analogue inputs:
Manual reset if AL05 = 0
0 16
Automatic reset if AL05 =16
From automatic to manual reset if AL05= 1..15
AL 6 Low temperature/pressure alarm during defrost
0= Not enabled 0 1
1= Enabled
AL 7 Low temperature/pressure alarm delay during defrost 0 250 Sec
AL 8 Low temperature/pressure alarm with unit in OFF or stand – by:
0 = Not enabled 0 1
1= Alarm enabled
High Alarm
AL 9 High temperature/pressure alarm from analogue input -30.0 70.0 °C Dec
-22 158 °F int
0.0 50.0 bar Dec
0 725 psi int
AL 10 High temperature/pressure alarm differential from analogue input 0.1 25.0 °C Dec
0 45 °F int
0.0 14.0 bar Dec
0 203 psi int
Oil Alarm
AL 11 Low oil pressure / level delay from digital input 0 250 Sec
AL 12 Minimum time for low oil pressure / level from digital input activation in normal working
0 250 Sec
condition.
AL 13 Maximum number of low oil pressure/level events:
Always manual reset if AL13= 0
0 16
Always automatic reset if AL13 =16
From automatic to manual reset if AL13 = 1..15
Flow alarm
AL 14 Configuration
0= Not enabled
1= Only for chiller 0 3
2= Only for heat pump
3= For both chiller and heat pump
AL 15 “Flow switch / supply fan overload” alarm delay after pump/fun activation. 0 250 Sec
AL 16 Flow switch time activation before blocking evaporator water pump 0 250 Sec
AL 17 “Flow switch / supply fan overload” activation time to generate the alarm 0 250 Sec
AL 18 “Flow switch / supply fan overload” de-activation time to reset the alarm 0 250 Sec
Compressor overload alarm
AL 19 Compressor overload alarm delay after compressor start-up 0 250 Sec
AL 20 Maximum number of compressor overload alarm events
Always manual reset if AL20 = 0
0 16
Always automatic reset if AL20 =16
From automatic to manual reset if AL20 =1..15
Pump down alarm
AL 21 Maximum number of pump down alarm events per hour in stop condition. After this
number the alarm is logged, displayed and signalled with alarm relay + buzzer.
Manual reset if AL21 = 0 0 16
Automatic reset if AL21 =16
From automatic to manual reset if AL21 =1..15
AL 22 Maximum number of pump down alarm events per hour in start-up condition. After this
number the alarm is logged, displayed and signalled with alarm relay + buzzer.
Always manual reset if AL22 = 0 0 16
Always automatic reset if AL22 =16
From automatic to manual reset if AL21 =1..15 and parameter AL23 config.
AL 23 Select if the pump down alarm must change from automatic to manual reset:
0= Always automatic reset 0 1
1= Manual reset after AL21 alarm events
Anti-freeze alarm in Chiller mode
AL 24 Minimum antifreeze setpoint in chiller (from –30 °C to AL24) -30.0 °C Dec
AL26
-22 °F int
AL 25 Maximum antifreeze setpoint in chiller (from AL24 to 70 °C) 70.0 °C Dec
AL26
158 °F int
AL 26 Setpoint temperature for low anti-freeze alarm, low ambient temperature (air/air), low
AL24 AL25 °C/°F Dec/int
temperature air outlet (air/air). From AL24 to AL25.
AL 27 Differential of alarm reset in Chiller mode for anti-freeze, low ambient air temperature 0 25.0 °C Dec
or low outlet air temperature alarms. 0 45 °F int
AL 28 Alarm delay for anti-freeze, low ambient air temperature or low outlet air temperature.
The temperature must be lower than AL26 for this time duration before having the 0 250 Sec
alarm event.
AL 29 Maximum number of alarm events anti-freeze, low ambient air temperature or low
outlet air temperature before changing from automatic to manual alarm reset:
Always manual reset if AL29 = 0 0 16
Always automatic reset if AL29 = 16
From automatic to manual if AL29 = 1. .15
AL 30 Anti-freeze alarm configuration in chiller
0= to turn the compressors off when the anti-freeze control probe is lower than AL26
(after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are not activated. 0 1
1= to turn the compressors off when the anti-freeze control probe is lower than AL26
(after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are activated.
Anti-freeze alarm in Heat pump mode
AL 31 Setpoint of the minimum limit in heat pump (va da – 30 °C a AL32) -30.0 °C Dec
AL33
-22 °F int
AL 32 Setpoint of the maximum limit in heat pump (va da AL31 a 70 °C) 70.0 °C Dec
AL33
158 °F int
AL 33 Anti-freeze alarm setpoint in heat pump
Setpoint temperature for low anti-freeze alarm, low ambient temperature (air/air), low AL31 AL32 °C/°F Dec/int
temperature air outlet (air/air). (from AL31 to AL32)
AL 34 Alarm differential in heat pump. To reset the anti-freeze, low ambient Temperature 0 25.0 °C Dec
(air/air), low temperature air outlet (air/air) alarms. 0 45 °F int
AL 35 Anti-freeze alarm delay in HP for low outlet air temperature (air/air)
Attention
If during the Stand-by or remote off there is an anti-freeze alarm event, and the AL35
<>0, starting the heat pump mode, from keyboard or digital input. In this case the anti-
freeze alarm is aborted and the compressor starts for the AL35 time to heat the air or 0 250 Sec
the water.
After the AL35 time if the antifreeze probe value is still lower than AL33 setpoint, for
maximum AL36 seconds, the unit is stopped and the anti-freeze alarm is generated
again.
AL 36 Anti-freeze alarm delay for low air ambient temperature or low outlet air temperature in
heat pump normal condition.
0 250 Sec
The detected temperature must be lower than AL33 for the time AL36 before giving the
alarm
AL 37 Maximum number of anti-freeze alarm events for low air ambient temperature or low
outlet air temperature in heat pump. It sets the alarm reset condition:
Always manual reset AL37 = 0 0 16
Always automatic reset AL37 = 16
From automatic to manual reset if AL37 = 1..15
AL 38 Anti-freeze alarm configuration in heat pump
0= to turn the compressors off when the anti-freeze control probe is lower than AL33
(after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are not activated. 0 1
1= to turn the compressors off when the anti-freeze control probe is lower than AL33
(after the time delay), the display shows the alarm label.
Buzzer and Alarm relay are activated.
Compressor high discharge temperature
AL 39 Compressor high discharge temperature setpoint 0 150 °C Dec / int
0 302 °F int
AL 40 Compressor high discharge temperature differential 0 25.0 °C Dec
0 45 °F int
AL 41 Number of compressor high discharge temperature events per hour to determine the
alarm reset condition:
Always manual reset if AL41 = 0 0 16
Always automatic reset if AL41 =16
From automatic to manual if AL41 = 1..15
Generic alarm 1
AL 42 Maximum number of generic alarm events (each event stop the regulation) before
turning the alarm from automatic to manual:
Always manual AL42 = 0 0 16
Always automatic AL42 =16
From manual to utomatic if AL42 value is between 1 and 15
AL 43 Generic alarm delay time after the digital input activation 0 250 Sec
AL 44 Generic alarm delay time after the digital input is not activate 0 250 10 sec 10 sec
Alarm relay
AL 45 Enable alarm relay with unit in off or stand – by:
0= Alarm output not enabled 0 1
1= Alarm output enabled
Password reset: Alarm log – Compressor overload
AL 46 Password value to reset the alarm log, the compressor overload alarm and antifreeze
0 999
alarm
AL 47 Thermal alarm of the compressor
0= lock the compressor 0 1
1= lock the whole circuit
AL 48 Thermal alarm when the compressor is OFF
0 = Not enabled 0 1
1= Alarm enabled
Oil alarm in OFF
AL 49 Oil alarm when the compressor is OFF
0 = Not enabled 0 1
1= Alarm enabled
Generic alarm / signal 2
51. BLACK-OUT
165
150
31
Ø3 x2
WALL MOUNTING: use the vertical V-KIT (black, white and grey) as described in the following scheme:
The LW30 KIT is the complete kit with MOLEX + 3 mt wires already connected and the STELVIO terminals.
Check the connecitons and the line voltage before turning on the power supply.
Keep low voltage cables far from power cables and terminals to prevent.
Respect the maximum load current of each relay output, in case of power loads use filtered contactors.
54. ACCESSORIES
Power supply
230Vac Input
0 - 230Vac output
-10 - 65°C Operating temperature
Naylon supports
D 15mm
Height
Model XV05PK XV10PK XW22PK
Y 25mm 42mm 64mm
Connections
A 1(+), 2(-) PWM input control
B 3(+), 4(-) PWM output repetition signal
F Phase
N Neutral
5-6 Fan output
Terminals 3 and 4 allows to connect another board in parallel to control two separate fans with the same
input control.
Terminals 1 / 2 / 3 / 4 are for screw for a 2.5mm wire
Terminals 5 / 6 / F / N are 6,3mm faston
Transformer
The standard power supply is 12 volt AC/DC or 24 volt AC/DC (optional)
Trasnformer models: 230/12 Vac , 230 /24 Vac, 110 / 12 Vac, 24 / 12 Vac
Display:
Top Display 3 digits with d.p.
Bottom Display 4 digits with d.p.
Connections: Removable screw terminal block 2,5mm2.
Power supply:
12Vac/dc,-10% ÷ l+15% or
24 Vac/dc±10%. 50/60 Hz
Power absorption: 10VA max
Probes: 6 temperature probes (NTC/PTC) + 4 temperature or pressure probes (NTC/PTC/4 ÷ 20ma / 0 ÷
5Volt)
Digital inputs: 18 (free voltage)
Relay outputs: 10 (IC260D/L) or 14 (IC261D/L): SPDT 5(2) A, 250Vac.
Data storing: on the non-volatile memory (EEPROM)
Operating temperature: -10÷55 °C
Storage temperature: -30÷85 °C
Relative humidity: 20 ÷ 85% (no condensing)
Measuring range:
Temperature measured by NTC probe: - 50÷110 °C (-58 ÷ 230 °F)
Temperature measured by PTC probe: -50÷150 °C (-58÷302 °F )
Pressure: 0÷ 50 bar (0÷725 psi)
Resolution: 0,1 °C or 1 °F (selectable)
Accuracy of the controller at 25°C: ±0,7 °C ±1 digit