0% found this document useful (0 votes)
15 views274 pages

Manualcompaqlogix

Manual de Compaqlogix de la seria 5069
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
15 views274 pages

Manualcompaqlogix

Manual de Compaqlogix de la seria 5069
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 274

This manual links to Logix 5000 Controller and I/O Fault Codes,

publication 1756-RD001; download the spreadsheet now for offline access.

CompactLogix 5380 and


Compact GuardLogix 5380
Controllers
Bulletin 5069

User Manual Original Instructions


CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual

Important User Information


Read this document and the documents listed in the additional resources section about installation, configuration, and operation of this equipment before
you install, configure, operate, or maintain this product. Users are required to familiarize themselves with installation and wiring instructions in addition to
requirements of all applicable codes, laws, and standards.

Activities including installation, adjustments, putting into service, use, assembly, disassembly, and maintenance are required to be carried out by suitably
trained personnel in accordance with applicable code of practice.

If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this
equipment.

The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with
any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.

No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.

Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.

Throughout this manual, when necessary, we use notes to make you aware of safety considerations.

WARNING: Identifies information about practices or circumstances that can cause an explosion in a hazardous environment,
which may lead to personal injury or death, property damage, or economic loss.

ATTENTION: Identifies information about practices or circumstances that can lead to personal injury or death, property
damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence.

IMPORTANT Identifies information that is critical for successful application and understanding of the product.

These labels may also be on or inside the equipment to provide specific precautions.

SHOCK HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous
voltage may be present.

BURN HAZARD: Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may
reach dangerous temperatures.

ARC FLASH HAZARD: Labels may be on or inside the equipment, for example, a motor control center, to alert people to
potential Arc Flash. Arc Flash will cause severe injury or death. Wear proper Personal Protective Equipment (PPE). Follow ALL
Regulatory requirements for safe work practices and for Personal Protective Equipment (PPE).

The following icon may appear in the text of this document.

Identifies information that is useful and can help to make a process easier to do or easier to understand.

2 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Table of Contents

Preface
About This Publication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Download Firmware, AOP, EDS, and Other Files . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Summary of Changes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Chapter 1
CompactLogix 5380 and Minimum Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Compact GuardLogix 5380 CompactLogix 5380 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
5069-L310ER-NSE No Stored Energy (NSE) Controller. . . . . . . . . . . . . . . . . . . . . . . 15
Systems and Controllers
CompactLogix 5380 Process Controllers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Compact GuardLogix 5380 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Design the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Controller Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Features Supported by Compact GuardLogix 5380 Controllers
via the Safety Task . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
CIP Security . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Secure Controller Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Power the System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Real-time Clock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Chapter 2
How to Power CompactLogix Two Types of Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5380 Controllers MOD Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
MOD Power Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
SA Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Track SA Power Bus Current Draw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Use a 5069-FPD Field Potential Distributorto Create a New SA Power Bus . . . . . 29
SA Power—Additional Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

Chapter 3
How to Power Compact Two Types of Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
GuardLogix 5380 Controllers MOD Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
MOD Power Bus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
SA Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Track SA Power Bus Current Draw. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Use a 5069-FPD Field Potential Distributor to Create a New SA Power Bus . . . . 36
Restrictions When You Connect SA Power to a
Compact GuardLogix 5380 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
SA Power—Additional Notes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 3


Table of Contents

Chapter 4
Safety Concept of Functional Safety Capability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Compact GuardLogix 5380 Safety Network Number. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Safety Signature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Controllers
Distinguish Between Standard and Safety Components . . . . . . . . . . . . . . . . . . . . . . . 45
Controller Data-flow Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Safety Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Chapter 5
Connect to the Controller Before You Begin . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Connection Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Connect an Ethernet Cable. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Connect a USB Cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Set the IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Other Methods to Set the IP Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Use a Secure Digital Card to Set the Controller IP Address . . . . . . . . . . . . . . . . . 52
Duplicate IP Address Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Duplicate IP Address Resolution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
DNS Addressing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Update Controller Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Firmware Upgrade Guidelines for Safety Controllers . . . . . . . . . . . . . . . . . . . . . . 54
Controller Firmware and Logix Designer Application Compatibility. . . . . . . . . . . 55
Determine Required Controller Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Obtain Controller Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Use ControlFLASH Plus Software to Update Firmware . . . . . . . . . . . . . . . . . . . . . 56
Use AutoFlash to Update Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
Controllers with Firmware Earlier than Revision 31 . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Chapter 6
Start to Use the Controller Create a Logix Designer Application Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Additional Configuration for a Compact GuardLogix Controller. . . . . . . . . . . . . . . . . . 67
Assign the Safety Network Number (SNN). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Copy and Paste a Safety Controller Safety Network Number. . . . . . . . . . . . . . . . 70
Go Online with the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Use RSWho . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72
Use a Recent Communications Path . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73
Additional Considerations for Going Online with a Controller . . . . . . . . . . . . . . . . . . . 75
Match Project to Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75
Firmware Revision Matching . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Additional Considerations for Going Online with a Compact GuardLogix Controller. . 76
Safety Signature and Safety-locked and -unlocked Status . . . . . . . . . . . . . . . . . 76
Checks for Going Online with a GuardLogix Controller . . . . . . . . . . . . . . . . . . . . . . 77
Download to the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Use Who Active . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Use the Controller Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Additional Considerations for Download to a Compact GuardLogix Controller. . . . . . 79
Upload from the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80

4 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Table of Contents

Use Who Active . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80


Use the Controller Status Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Additional Considerations for Upload to a Compact GuardLogix Controller . . . . . . . . 82
Choose the Controller Operation Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Use the Mode Switch to Change the Operation Mode . . . . . . . . . . . . . . . . . . . . . . 84
Use the Logix Designer Application to Change the Operation Mode . . . . . . . . . . 85
Change Controller Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Reset Button. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Stage 1 Reset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Stage 2 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88

Chapter 7
Use the Secure Digital Card Considerations for Storing and Loading a Safety Project . . . . . . . . . . . . . . . . . . . . . . 94
Store to the SD Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
Load from the SD Card. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Controller Power-up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
User-initiated Action . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Other Secure Digital Card Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

Chapter 8
EtherNet/IP Network Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
EtherNet/IP Network Functionality . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Nodes on an EtherNet/IP Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Devices Included in the Node Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Devices Excluded from the Node Count . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
EtherNet/IP Network Topologies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Device Level Ring Network Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Linear Network Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Star Network Topology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
Integrated Architecture Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
EtherNet/IP Network Communication Rates. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 109
Simple Network Management Protocol (SNMP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 111
Use a CIP Generic MSG to Enable SNMP on the Controller. . . . . . . . . . . . . . . . . . . . 111
Use a CIP Generic MSG to Disable SNMP on the Controller . . . . . . . . . . . . . . . . . . 113
Socket Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
TLS Support. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114
HTTP(S) REST API Client Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

Chapter 9
Use EtherNet/IP Modes Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Available Network Levels. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Enterprise-level Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117
Device-level Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
EtherNet/IP Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Dual-IP Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Linear/DLR Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121
Overlapping IP Address Ranges. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123
Configure EtherNet/IP Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 5


Table of Contents

Configure Dual-IP Mode in the Logix Designer Application. . . . . . . . . . . . . . . . . . 124


Configure Dual-IP Mode in RSLinx Classic Software . . . . . . . . . . . . . . . . . . . . . . . 125
Configure Linear/DLR Mode in the Logix Designer Application . . . . . . . . . . . . . . 126
Configure Linear/DLR Mode in RSLinx Classic Software . . . . . . . . . . . . . . . . . . . . 128
Change the EtherNet/IP Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 129
Change the EtherNet/IP Mode in the Logix Designer Application. . . . . . . . . . . . . 130
Change the EtherNet/IP Mode in RSLinx Classic Software . . . . . . . . . . . . . . . . . . 131
DNS Requests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
DNS Request Routing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
SMTP Server . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133
Use Socket Object. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Send Message Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Software Display Differences for EtherNet/IP Modes . . . . . . . . . . . . . . . . . . . . . . 135

Chapter 10
Manage Controller Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 137
Communication Controller Communication Interaction with Control Data . . . . . . . . . . . . . . . . . . . . . . 137
Produce and Consume (Interlock) Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 138
Requested Packet Interval (RPI) of Multicast Tags . . . . . . . . . . . . . . . . . . . . . . . . 139
Send and Receive Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 139
Determine Whether to Cache Message Connections . . . . . . . . . . . . . . . . . . . . . . 140

Chapter 11
Standard I/O Modules Local I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 141
Add Local I/O Modules to a Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Electronic Keying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 147
Remote I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148
Add Remote I/O Modules to a Project. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150
Add to the I/O Configuration While Online. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 157
Modules and Devices That Can Be Added While Online. . . . . . . . . . . . . . . . . . . . . 157
Determine When Data Is Updated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Input Data Update Flowchart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 158
Output Data Update Flowchart. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159

Chapter 12
Safety I/O Devices Add Safety I/O Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Configure Safety I/O Devices. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 161
Using Network Address Translation (NAT) with CIP Safety Devices . . . . . . . . . . . . . . 163
Set the SNN of a Safety I/O Device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 164
Change a Safety I/O device SNN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Copy and Paste a Safety I/O Device SNN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Safety I/O Device Signature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168
Configuration via the Logix Designer Application. . . . . . . . . . . . . . . . . . . . . . . . . 168
Reset Safety I/O Device to Out-of-box Condition . . . . . . . . . . . . . . . . . . . . . . . . . 168
I/O Device Address Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Monitor Safety I/O Device Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Replace a Safety I/O Device. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169
Configuration Ownership . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169

6 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Table of Contents

Replacement Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 170


Only Allow Automatic Configuration When No Safety Signature Exists . . . . . . . . 172
Always Allow Automatic Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 175

Chapter 13
Develop Standard Applications Elements of a Control Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Tasks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 177
Event Task with Compact 5000 I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Task Priority . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180
Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181
Scheduled and Unscheduled Programs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 182
Routines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183
Parameters and Local Tags. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Program Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 185
Programming Languages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Add-On Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 186
Extended Properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187
Access the Module Object from an Add-On Instruction . . . . . . . . . . . . . . . . . . . . . . . . 188
Monitor Controller Status. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Monitor I/O Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189
Determine If I/O Communication Has Timed Out . . . . . . . . . . . . . . . . . . . . . . . . . 190
Determine If I/O Communication to a Specific I/O Module Has Timed Out . . . . . 190
Automatic Handling of I/O Module Connection Faults. . . . . . . . . . . . . . . . . . . . . . 190
Sample Controller Projects. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191

Chapter 14
Develop Safety Applications Safety Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193
Program Safety Applications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194

Chapter 15
Develop Secure Applications Controller Security Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 196
Security Checklists . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Configure User-definable Major Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Create a Fault Routine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
Configure the Program to Use the Fault Routine . . . . . . . . . . . . . . . . . . . . . . . . . 201
Jump to the Fault Routine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 201
License-based Source and Execution Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . 202
Enable License-based Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Configure Change Detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
Configure Component Tracking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206
Configure Controller Logging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
Disable Controller Ethernet Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 208
Disable the Ethernet Port on the Port Configuration Tab . . . . . . . . . . . . . . . . . . 209
Disable the Ethernet Port with a MSG Instruction . . . . . . . . . . . . . . . . . . . . . . . . . 210
Disable the Controller CIP Security Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 212
Use the Disable CIP Security Checkbox in FactoryTalk Linx. . . . . . . . . . . . . . . . . 212
Use a CIP Generic MSG Instruction in the Studio 5000 Logix Designer Application . . 213
Disable the Controller USB Port . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 7


Table of Contents

Disable the Controller SD Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216


Disable the 4-character Status Display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Disable All Categories of Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218
Disable Individual Categories of Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220
Disable Controller Webpages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 222
Studio 5000 Logix Designer Application Version 33 or Later . . . . . . . . . . . . . . . 222
Studio 5000 Logix Designer Application Version 32 or Earlier . . . . . . . . . . . . . . 223
Controller Web Page Default Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 223
Use a CIP Generic MSG to Disable the Controller Web Pages . . . . . . . . . . . . . . . 223
Use a CIP Generic MSG to Enable the Controller Web Pages. . . . . . . . . . . . . . . . 226

Chapter 16
Develop Motion Applications Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Motion Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Program Motion Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 230
Obtain Axis Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231

Chapter 17
Troubleshoot the Controller Automatic Diagnostics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 233
Considerations for Communication Loss Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . 233
Controller Diagnostics with Logix Designer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Warning Symbol in the I/O Configuration Tree . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Categories on I/O Module Properties Dialog . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Notification in the Tag Monitor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Fault Information in the Controller Properties Dialog Box . . . . . . . . . . . . . . . . . 238
Port Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
Advanced Time Sync . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 241
Controller Diagnostics with Linx-based Software . . . . . . . . . . . . . . . . . . . . . . . . . . . 244
Controller Web Pages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 245
Home Web Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 246
Tasks Web Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 247
Diagnostics Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 248
Ethernet Port Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 249
Advanced Diagnostics Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250
Browse Chassis Web Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Other Potential Issues to Troubleshoot. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 252
Continuous Task Sends Output Data at High Rate . . . . . . . . . . . . . . . . . . . . . . . 252
Immediate Output Instructions Issued at High Rate . . . . . . . . . . . . . . . . . . . . . . 252
Integrated Motion On an EtherNet/IP Network Traffic Priority Status . . . . . . . . 252

Appendix A
Status Indicators Status Display and Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
General Status Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 253
Compact GuardLogix Status Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 255
Fault Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
Major Fault Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
I/O Fault Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 256
Controller Status Indicators. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257

8 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Table of Contents

RUN Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257


FORCE Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
SD Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 257
OK Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
EtherNet/IP Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
NET A1 and NET A2 Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 258
LINK A1 and LINK A2 Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Power Status Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
MOD Power Indicator. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
SA Power Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 259
Thermal Monitoring and Thermal Fault Behavior . . . . . . . . . . . . . . . . . . . . . . . . . . . . 260

Appendix B
Change Controller Type Change from a Standard to a Safety Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Change from a Safety to a Standard Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 261
Change Safety Controller Types . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 262

Appendix C
History of Changes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 263

Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 267

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 9


Table of Contents

Notes:

10 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Preface

About This Publication This manual provides information on how to design a system, operate a CompactLogix™ or
Compact GuardLogix-based controllers system, and develop applications.

You must be trained and experienced in the creation, operation, and maintenance of safety
systems.

For information on Safety Integrity Level (SIL) and Performance Level (PL) requirements and
safety application requirements, see the GuardLogix 5580 and Compact GuardLogix 5380
Controller Systems Safety Reference Manual, publication 1756-RM012.

Download Firmware, AOP, Download firmware, associated files (such as AOP, EDS, and DTM), and access product release
notes from the Product Compatibility and Download Center at rok.auto/pcdc.
EDS, and Other Files
Summary of Changes This publication contains the following new or updated information. This list includes
substantive updates only and is not intended to reflect all changes.
Topic Page
CompactLogix 5380 controllers support IEC-62443-4-2 SL 1 security requirements throughout
Added the Secure Controller Systems section to Chapter 1 23
Revised the Safety Signature section in Chapter 4 45
Added 1784-SDHC8 and 1784-SDHC32 memory cards 91
Added Chapter 15, Develop Secure Applications 195
Updated Device Level Ring Network Topology section 106

Additional Resources These documents contain additional information concerning related products from Rockwell
Automation. You can view or download publications at rok.auto/literature.
Resource Description
CompactLogix 5380 Controllers Installation
Instructions, publication 5069-IN013 Provides installation instructions for CompactLogix™ 5380 controllers.
Compact GuardLogix 5380 SIL 2 Controllers Provides installation instructions for Compact GuardLogix® 5380 SIL 2 controllers.
Installation Instructions, publication 5069-IN014
Hardware installation
Compact GuardLogix 5380 SIL 3 Controllers Provides installation instructions for Compact GuardLogix 5380 SIL 3 controllers.
Installation Instructions, publication 5069-IN023
Industrial Automation Wiring and Grounding Provides general guidelines for installing a Rockwell Automation industrial system.
Guidelines, publication 1770-4.1
Compact 5000 I/O Modules Specifications Technical Provides specifications for Compact 5000™ I/O EtherNet/IP™ adapters and
Data, publication 5069-TD001 Compact 5000 I/O modules.
Technical Data CompactLogix 5380 and Compact GuardLogix 5380 Provides specifications for CompactLogix 5380 and Compact GuardLogix 5380
Controllers Specifications Technical Data, controllers.
publication 5069-TD002
EtherNet/IP Network Devices User Manual, Describes how to configure and use EtherNet/IP™ devices with a Logix 5000™
Networks publication ENET-UM006 controller and communicate with various devices on the Ethernet network.
Provides requirements for achieving and maintaining Safety Integrity Level (SIL) 2 and
GuardLogix 5580 and Compact GuardLogix 5380
Safety Application Performance Level (PL) d and Safety Integrity Level (SIL) 3 and Performance Level (PL)
Controller Systems Safety Reference Manual,
Requirements e requirements with the GuardLogix 5580 and Compact GuardLogix 5380 controller
publication 1756-RM012 system using the Studio 5000 Logix Designer® application.
Integrated Motion on the EtherNet/IP Network Provides descriptions of the AXIS_CIP_DRIVE attributes and the Logix Designer
Reference Manual, publication MOTION-RM003 application Control Modes and Methods.
Motion
Logix 5000 Controllers Motion Instructions Reference Provides information on how to use Motion instructions.
Manual, publication MOTION-RM002

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 11


Preface

Resource Description
Logix 5000 Controllers Design Considerations Provides information on how to design and plan Logix 5000 controller systems.
Reference Manual, publication 1756-RM094
Ethernet Design Considerations Reference Manual, Provides additional information on network design for your system.
Design Considerations publication ENET-RM002
Provides guidelines on how to replace the following:
Replacement Guidelines: Logix 5000 Controllers
Reference Manual, publication 1756-RM100 • ControlLogix® 5560/5570 controller with a ControlLogix 5580 controller
• CompactLogix 5370 L3 controllers with a CompactLogix 5380 controller
Logix 5000 Controllers Common Procedures Provides access to the Logix 5000 Controllers set of programming manuals. The
Programming Manual, publication 1756-PM001 manuals cover such topics as how to manage project files, organize tags, program
logic, test routines, handle faults, and more.
Programming Tasks and
Procedures Logix 5000 Controllers General Instructions Provides information on the programming instructions available to use in Logix
Reference Manual, publication 1756-RM003 Designer application projects.
GuardLogix Safety Application Instruction Set Provides information on the GuardLogix Safety application instruction set.
Reference Manual, publication 1756-RM095
Product Certifications website, rok.auto/
Product Certifications certifications. Provides declarations of conformity, certificates, and other certification details.

12 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 1
CompactLogix 5380 and Compact
GuardLogix 5380 Systems and Controllers
This chapter describes features of the following CompactLogix™ 5380 and Compact
GuardLogix® 5380 controllers.
Controller Type Cat. No.
5069-L306ER, 5069-L306ERM, 5069-L310ER, 5069-L310ERM, 5069-L310ERMK,
CompactLogix 5380 5069-L310ER-NSE, 5069-L320ER, 5069-L320ERM, 5069-L320ERMK, 5069-L330ER,
Standard controllers 5069-L330ERM, 5069-L330ERMK, 5069-L340ER, 5069-L340ERM, 5069-L350ERM,
5069-L350ERMK, 5069-L380ERM, 5069-L3100ERM
CompactLogix 5380 5069-L320ERP, 5069-L340ERP
Process controllers
5069-L306ERS2, 5069-L306ERMS2, 5069-L310ERS2, 5069-L310ERS2K,
5069-L310ERMS2, 5069-L310ERMS2K, 5069-L320ERS2, 5069-L320ERS2K, 5069-
Compact GuardLogix® 5380 L320ERMS2, 5069-L320ERMS2K, 5069-L330ERS2, 5069-L330ERS2K, 5069-L330ERMS2,
SIL 2 controllers 5069-L330ERMS2K, 5069-L340ERS2, 069-L340ERMS2, 5069-L350ERS2,
5069-L350ERS2K, 5069-L350ERMS2, 5069-L350ERMS2K, 5069-L380ERS2,
5069-L380ERMS2, 5069-L3100ERS2, 5069-L3100ERMS2
Compact GuardLogix 5380 5069-L306ERMS3, 5069-L310ERMS3, 5069-L310ERMS3K, 5069-L320ERMS3,
5069-L320ERMS3K, 5069-L330ERMS3, 5069-L330ERMS3K, 5069-L340ERMS3,
SIL 3 controllers 5069-L350ERMS3, 5069-L350ERMS3K, 5069-L380ERMS3, 5069-L3100ERMS3

Minimum Requirements The controllers have these minimum requirements:


Applies to these controllers:
• CompactLogix 5380 and Compact GuardLogix 5380 controllers have minimum hardware
requirements. For more information on the hardware requirements, see Table 1 on
CompactLogix 5380 page 18.
Compact GuardLogix 5380 SIL 2
• The controller firmware revision must be compatible with the software version that you
Compact GuardLogix 5380 SIL 3 use. For more information, see Controller Firmware and Logix Designer Application
Compatibility on page 55.
• Programming software
Studio 5000 Logix
System Cat. No.
Designer® Application(1)
CompactLogix 5069-L320ER, 5069-L340ERM Version 28 or later
5069-L306ER, 5069-L306ERM, 5069-L310ER, 5069-L310ER-NSE,
5069-L310ERM, 5069-L310ERMK, 5069-L320ERM,
CompactLogix Version 29 or later
5069-L320ERMK, 5069-L330ER, 5069-L330ERM,
5069-L330ERMK, 5069-L340ER
5069-L350ERM, 5069-L350ERMK, 5069-L380ERM,
CompactLogix Version 30or later
5069-L3100ERM
5069-L306ERS2, 5069-L306ERMS2, 5069-L310ERS2,
5069-L310ERS2K, 5069-L310ERMS2, 5069-L310ERMS2K,
5069-L320ERS2, 5069-L320ERS2K, 5069-L320ERMS2,
Compact GuardLogix 5069-L320ERMS2K, 5069-L330ERS2, 5069-L330ERS2K,
Version 31 or later
SIL 2 controllers(2) 5069-L330ERMS2, 5069-L330ERMS2K, 5069-L340ERS2,
5069-L340ERMS2, 5069-L350ERS2, 5069-L350ERS2K,
5069-L350ERMS2, 5069-L350ERMS2K, 5069-L380ERS2,
5069-L380ERMS2, 5069-L3100ERS2, 5069-L3100ERMS2
5069-L306ERMS3, 5069-L310ERMS3, 5069-L310ERMS3K,
Compact GuardLogix 5069-L320ERMS3, 5069-L320ERMS3K, 5069-L330ERMS3,
Version 32 or later
SIL 3 controllers(2) 5069-L330ERMS3K, 5069-L340ERMS3, 5069-L350ERMS3,
5069-L350ERMS3K, 5069-L380ERMS3, 5069-L3100ERMS3
CompactLogix
Process controllers 5069-L310ERxK, 5069-L320ERP, 5069-L340ERP Version 33 or later
(1) For compatible Linx-based communication software and ControlFLASH™ software, see the Product Compatibility and
Download Center (PCDC).
(2) For more information on safety ratings, see Safety Concept of Compact GuardLogix 5380 Controllers on page 43.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 13


Chapter 1 CompactLogix 5380 and Compact GuardLogix 5380 Systems and Controllers

IMPORTANT If safety connections or safety logic is required for your application,


then you must use a Compact GuardLogix controller.

IMPORTANT This equipment is supplied as open-type equipment for indoor use. It


must be mounted within an enclosure that is suitably designed for those
specific environmental conditions that are present and appropriately
designed to help prevent personal injury resulting from accessibility to
live parts.
The enclosure must have suitable flame-retardant properties to help
prevent or minimize the spread of flame, complying with a flame spread
rating of 5VA or be approved for the application if nonmetallic. The
interior of the enclosure must be accessible only by the use of a tool.
For more information about enclosure type ratings that are required to
comply with certain product safety certifications, see the following:
• Compact GuardLogix 5380 SIL 2 Controllers Installation Instructions,
publication 5069-IN014.
• Compact GuardLogix 5380 SIL 3 Controllers Installation Instructions,
publication 5069-IN023.

Waste Electrical and Electronic Equipment (WEEE)

At the end of its life, this equipment should be collected separately from any
unsorted municipal waste.

CompactLogix 5380 System CompactLogix 5380 control systems are DIN rail-mounted systems that can operate in various
applications.

One of the simplest controller configurations is a standalone controller with I/O assembled in
one chassis, as shown in Figure 1.
Figure 1 - CompactLogix 5380 Controller in a Standalone System

CompactLogix 5380 Controller Compact 5000™ I/O Analog and Digital Modules

The controllers can also operate in more complex systems with devices that are connected to
the controller via an EtherNet/IP™ network, as shown in Figure 2.

14 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 1 CompactLogix 5380 and Compact GuardLogix 5380 Systems and Controllers

Figure 2 - CompactLogix 5380 Controller in a More Complex System

Compact 5000 I/O EtherNet/IP Adapter


Compact 5000 I/O Modules
CompactLogix 5380 Controller
Compact 5000 I/O Modules

Stratix® 5400 Switch

PanelView™ Plus 7 Terminal

Kinetix® 5500 Drive

PowerFlex® 527 Drive


1734 POINT I/O™ Adapter
1734 POINT I/O Modules

5069-L310ER-NSE No Stored Energy (NSE) Controller


The NSE controller is intended for use in applications that require the installed controller to
deplete its residual stored energy to specific levels before transporting it into or out of your
application.
The residual stored energy of the NSE controller depletes to 400µJ or less in 40 seconds.

WARNING: If your application requires the NSE controller to deplete its residual
stored energy to 400 µJ or less before you transport it into or out of the
application, complete these steps before you remove the controller.
• Turn off power to the chassis. After you turn off power, the controller’s OK
status indicator transitions from Green to Solid Red to OFF.
• Wait at least 40 seconds for the residual stored energy to decrease to
400 µJ or less before you remove the controller. There is no visual indication
of when the 40 seconds has expired. You must track that time period.

IMPORTANT The Real Time Clock (RTC) does not retain its time and date when the
power is off.

Some applications require that the installed controller to deplete its residual stored energy to
specific levels before transporting it into or out of your application. This requirement can
include other devices that also require a wait time before removing them. See the
documentation of those products for more information.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 15


Chapter 1 CompactLogix 5380 and Compact GuardLogix 5380 Systems and Controllers

CompactLogix 5380 Process Controllers


CompactLogix 5380 Process controllers (5069-L320ERP, 5069-L340ERP) are extensions of the
Logix 5000 controller family that focus on plant-wide process control, and support motion.

The process controllers come configured with a default process tasking model and dedicated
PlantPAx® process instructions that are optimized for process applications, and that improve
design and deployment efforts.

The process controllers are conformal coated to add a layer of protection when exposed to
harsh, corrosive environments.

Compact GuardLogix 5380 Compact GuardLogix 5380 SIL 2 and SIL 3 controllers are programmable automation
controllers with integrated safety.
System
For SIL 3/PLe safety applications, the Compact GuardLogix 5380 SIL 3 controller system
consists of a primary controller with an internal safety partner, that functions together in a
1oo2 architecture.

Compact GuardLogix 5380 SIL 2 Controller Compact GuardLogix 5380 SIL 3 Controller

For more information on safety ratings, see Safety Concept of Compact GuardLogix 5380
Controllers on page 51.

The Compact GuardLogix system can communicate with safety I/O devices via CIP Safety™
over an EtherNet/IP™ network (Guard I/O™ modules, integrated safety drives, integrated safety
components).

With a Compact GuardLogix controller, you can interface to standard I/O via standard tasks
while you interface with safety I/O via the safety task.

IMPORTANT For the safety task, Compact GuardLogix 5380 controllers support Ladder
Diagram only.
For standard tasks, Compact GuardLogix 5380 controllers support:
• Ladder Diagram (LD)
• Structured Text (ST)
• Function Block Diagram (FBD)
• Sequential Function Chart (SFC)

16 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 1 CompactLogix 5380 and Compact GuardLogix 5380 Systems and Controllers

The controllers can operate in various applications that range from standalone systems that
contain local I/O modules, as shown in Figure 3.
Figure 3 - Compact GuardLogix 5380 Controller in a Standalone System
Compact GuardLogix 5380 Controller Compact 5000 I/O Safety Digital, Standard Analog,
and Standard Digital Modules

The controllers can also operate in more complex systems with devices that are connected to
the controller via an EtherNet/IP network, as shown in Figure 4.
Figure 4 - Compact GuardLogix 5380 Controller on an EtherNet/IP DLR Network

Compact GuardLogix 5380 SIL 2 or Compact 5000 I/O EtherNet/IP Adapter


SIL 3 Controller Compact 5000 I/O Analog, Digital, and
Compact 5000 I/O Safety, Analog, and Safety Modules
Digital Modules

1734 POINT I/O Adapter


Compact 5000 I/O EtherNet/IP Adapter
1734 POINT I/O Modules
Compact 5000 I/O Analog, Digital, and
1734 POINT Guard I/O™ Modules
Safety Modules

Kinetix® 5500 Drives


(with Safe Torque
Off functionality) 1732ES ArmorBlock® Guard I/O™ Module PowerFlex® 527 Drive
(CIP Safety enabled)

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 17


Chapter 1 CompactLogix 5380 and Compact GuardLogix 5380 Systems and Controllers

Compact GuardLogix 5380 controllers can communicate with safety devices on a DeviceNet®
network via a 1788-EN2DN linking device, as shown in Figure 5
Figure 5 - Compact GuardLogix 5380 Controller Connected to Devices on a DeviceNet Network

Compact GuardLogix 5380 SIL 2 or SIL 3 Controller


Compact 5000 I/O Safety, Analog, and Digital Modules

1788 EtherNet-to-DeviceNet
Linking Device

DeviceNet Network

1791DS CompactBlock™ 1791DS CompactBlock Guard


Guard I/O™ Module I/O Module

1732DS ArmorBlock 1732DS ArmorBlock


1732DS Guard
ArmorBlock
I/O Module Guard I/O Module
Guard I/O Module

Design the System When you design a system, you must decide what system components your application needs.
Table 1 describes components that are commonly used in CompactLogix 5380 and Compact
Applies to these controllers: GuardLogix 5380 control systems.
CompactLogix 5380
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3

Table 1 - System Components


Component Purpose Required For More Information
DIN rail Mounting system Yes
The end cap covers the exposed interconnections on
the last module in the system.
If you do not install the end cap before powering the
system, equipment damage or injury from electric
shock can result. CompactLogix 5380 Controllers Installation
End cap (5069-ECR) IMPORTANT: You install the end cap after the last Instructions, publication 5069-IN013
IMPORTANT: The end cap Yes
module is installed on the DIN rail. This design helps to Compact GuardLogix 5380 SIL 2 Controllers
ships with the controller. prevent the end cap from going beyond the locked Installation Instructions, publication 5069-IN014
position. Compact GuardLogix 5380 SIL 3 Controllers
If you push the end cap beyond the locked position or Installation Instructions, publication 5069-IN023
insert it from the backwards direction, you can damage
the MOD power bus and SA power bus connector.
Removable terminal blocks Connect these power types to the controller:
MOD power Yes
(RTBs) SA power

18 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 1 CompactLogix 5380 and Compact GuardLogix 5380 Systems and Controllers

Table 1 - System Components (Continued)


Component Purpose Required For More Information
(1) Provides Module (MOD) Power to the system Yes
External power supply
Yes - Only if the system
requires SA power.
If the system does not Power the System on page 23
External power supply(1) Provides Sensor/Actuator (SA) Power to the system require SA power, the
external power supply is not
needed.
Minimum Requirements on page 13
Studio 5000 Logix Designer Configure the project that is used to define controller Yes Create a Logix Designer Application Project
application activity during system operation on page 65
For compatible Linx-based communication
Linx-based communication Used as follows: software and, see the
Assign the controller an IP address Yes
software Product Compatibility and Download Center (PCDC).
Maintain communication over the EtherNet/IP network Connect to the Controller on page 49
For compatible ControlFLASH software, see the
ControlFLASH software Update controller firmware Yes Product Compatibility and Download Center (PCDC).
Update Controller Firmware on page 54
Complete tasks that only require a temporary
USB programming port connection to the controller, for example, when you — Connect a USB Cable on page 50
download a project or update firmware
Connects to these network types:
Ethernet port A1 Enterprise-level network —
Device-level network Use EtherNet/IP Modes , on page 117
Ethernet port A2 Connect to device-level networks —
We recommend that you
Secure Digital (SD) card Store data, such as the controller project and leave the SD card installed, so
IMPORTANT: The 1784-SD2 diagnostics that are required by technical support to if a fault occurs, diagnostic Use the Secure Digital Card on page 91
card ships with obtain information if non-recoverable controller faults data is automatically written
the controller. occur. to the card.
Used as follows:
Access the controller from the workstation over an
EtherNet/IP network to set IP address, update firmware, Yes
Ethernet cables Connect an Ethernet Cable on page 50
download, and upload projects
Connect controller to an EtherNet/IP network and
perform tasks that are required for normal operations
Access the controller directly from the workstation to Yes - Only if you perform
set IP address, update firmware, download, and upload tasks that are listed in the
previous column via the USB
projects.
USB Cable port. Connect a USB Cable on page 50
The USB port is intended for temporary local You can also perform the
programming purposes only and not intended for tasks via the controller
permanent connection. Ethernet ports.
Connected to safety input and output devices, for
Integrated Safety I/O example, Compact 5000 I/O safety modules or Yes for Compact GuardLogix
devices on an EtherNet/IP Guardmaster® Multifunctional Access Box. Safety I/O Devices on page 161
network IMPORTANT: CompactLogix 5380 controllers cannot use 5380 controllers.
safety devices.
Used as follows:
Local standard I/O modules that are installed in the
CompactLogix 5380 system
Remote standard I/O modules that are accessible via Standard I/O Modules on page 141
Compact 5000 I/O modules the EtherNet/IP network Yes Safety I/O Devices on page 161
Local safety I/O modules that are installed in the
CompactLogix 5380 system
Remote safety I/O modules that are accessible via the
EtherNet/IP network
Dependent upon device type. Examples include:
Remote standard I/O modules Standard I/O Modules on page 141
Devices that are installed on Remote safety I/O modules Yes Safety I/O Devices on page 161
an EtherNet/IP network Ethernet switches Develop Motion Applications on page 229
Motion control devices, such as drives
HMI devices
(1) We strongly recommend that you use separate external power supplies for MOD power and SA power, respectively.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 19


Chapter 1 CompactLogix 5380 and Compact GuardLogix 5380 Systems and Controllers

Controller Features CompactLogix 5380 and Compact GuardLogix 5380 Controller Features lists features available
on the controllers. The features are described in detail in the rest of this manual.
Table 2 - CompactLogix 5380 and Compact GuardLogix 5380 Controller Features
Feature CompactLogix 5380 Controllers Compact GuardLogix 5380 Controllers
5069-L306ER, 5069-L306ERM 0.6 MB 5069-L306ERS2, 5069-L306ERMS2, 5069-L306ERMS3 0.6 MB
5069-L310ER, 5069-L310ER-NSE, 5069-L310ERS2, 5069-L310ERS2K, 5069-L310ERMS2, 5069-L310ERMS2K,
1 MB 1 MB
5069-L310ERM, 5069-L310ERMK 5069-L310ERMS3, 5069-L310ERMS3K
5069-L320ER, 5069-L320ERM, 5069-L320ERS2, 5069-L320ERS2K, 5069-L320ERMS2, 5069-L320ERMS2K,
2 MB 2 MB
5069-L320ERP 5069-L320ERMS3, 5069-L320ERMS3K
5069-L330ERS2, 5069-L330ERS2K, 5069-L330ERMS2, 5069-L330ERMS2K,
5069-L330ER, 5069-L330ERM 3 MB 3 MB
User memory 5069-L330ERMS3, 5069-L330ERMS3K
5069-L340ER, 5069-L340ERM, 4 MB 5069-L340ERS2, 5069-L340ERMS2, 5069-L340ERMS3 4 MB
5069-L340ERP
5069-L350ERS2, 5069-L350ERS2K, 5069-L350ERMS2, 5069-L350ERMS2K,
5069-L350ERM 5 MB 5 MB
5069-L350ERMS3, 5069-L350ERMS3K
5069-L380ERM 8 MB 5069-L380ERS2, 5069-L380ERMS2, 5069-L380ERMS3 8 MB
5069-L3100ERM 10 MB 5069-L3100ERS2, 5069-L3100ERMS2, 5069-L3100ERMS3 10 MB
— 5069-L306ERS2, 5069-L306ERMS2, 5069-L306ERMS3 0.3 MB
— 5069-L310ER, 5069-L310ER-NSE, 5069-L310ERM, 5069-L310ERMK 0.5 MB
5069-L320ERS2, 5069-L320ERS2K, 5069-L320ERMS2, 5069-L320ERMS2K,
— 1 MB
5069-L320ERMS3, 5069-L320ERMS3K
5069-L330ERS2, 5069-L330ERS2K, 5069-L330ERMS2, 5069-L330ERMS2K,
— 1.5 MB
Safety memory 5069-L330ERMS3, 5069-L330ERMS3K
— 5069-L340ERS2, 5069-L340ERMS2, 5069-L340ERMS3 2 MB
5069-L350ERS2, 5069-L350ERS2K, 5069-L350ERMS2, 5069-L350ERMS2K,
— 2.5 MB
5069-L350ERMS3, 5069-L350ERMS3K
— 5069-L380ERS2, 5069-L380ERMS2, 5069-L380ERMS3 4 MB
— 5069-L3100ERS2, 5069-L3100ERMS2, 5069-L3100ERMS3 5 MB
32 tasks
32 tasks 31 standard tasks
Controller tasks 1000 programs/task 1 safety task
Event tasks; all event triggers 1000 programs/task
Event tasks; all event triggers
1 - USB port, 2.0 full-speed, Type B
Communication ports 2 - Embedded Ethernet ports, 10 Mbps, 100 Mbps, 1 Gbps
CIP Security™ See CIP Security on page 23.
Device Level Ring (DLR)
EtherNet/IP network Star
topologies supported Linear

20 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 1 CompactLogix 5380 and Compact GuardLogix 5380 Systems and Controllers

Table 2 - CompactLogix 5380 and Compact GuardLogix 5380 Controller Features (Continued)
Feature CompactLogix 5380 Controllers Compact GuardLogix 5380 Controllers
Linear/DLR mode
EtherNet/IP modes Dual-IP mode - Available with the Logix Designer application, version 29 or later.
5069-L306ER, 5069-L306ERM 16 nodes 5069-L306ERS2, 5069-L306ERMS2, 5069-L306ERMS3 16 nodes
5069-L310ER, 5069-L310ER-NSE, 5069-L310ERS2, 5069-L310ERS2K, 5069-L310ERMS2,
24 nodes 5069-L310ERMS2K, 5069-L310ERMS3, 5069-L310ERMS3K 24 nodes
5069-L310ERM, 5069-L310ERMK
5069-L320ER, 5069-L320ERM, 40 nodes 5069-L320ERS2, 5069-L320ERS2K, 5069-L320ERMS2, 5069-L320ERMS2K 40 nodes
5069-L320ERP 5069-L320ERMS3, 5069-L320ERMS3K
5069-L330ERS2, 5069-L330ERS2K, 5069-L330ERMS2, 5069-L330ERMS2K,
EtherNet/IP nodes 5069-L330ER, 5069-L330ERM 60 nodes 5069-L330ERMS3, 60 nodes
(1)
5069-L330ERMS3K
supported, max
5069-L340ER, 5069-L340ERM, 90 nodes 5069-L340ERS2, 5069-L340ERMS2, 5069-L340ERMS3 90 nodes
5069-L340ERP
120 nodes 5069-L350ERS2, 5069-L350ERS2K, 5069-L350ERMS2, 5069-L350ERMS2K,
5069-L350ERM 120 nodes
5069-L350ERMS3, 5069-L350ERMS3K
5069-L380ERM 150 nodes 5069-L380ERS2, 5069-L380ERMS2, 5069-L380ERMS3 150 nodes
5069-L3100ERM 180 nodes 5069-L3100ERS2, 5069-L3100ERMS2, 5069-L3100ERMS3 180 nodes
5069-L306ERM 2 axes 5069-L306ERMS2, 5069-L306ERMS3 2 axes
5069-L310ERM, 5069-L310ERMK 4 axes 5069-L310ERMS2, 5069-L310ERMS2K, 5069-L310ERMS3, 5069-L310ERMS3K 4 axes
Integrated motion axes 5069-L320ERM, 5069-L320ERP 5069-L320ERMS2, 5069-L320ERMS2K, 5069-L320ERMS3, 5069-L320ERMS3K 8 axes
8 axes
supported
Only controllers with an 5069-L330ERM 16 axes 5069-L330ERMS2, 5069-L330ERMS2K, 5069-L330ERMS3, 5069-L330ERMS3K 16 axes
‘M’ or ‘P’ in the catalog
number support 5069-L340ERM, 5069-L340ERP 20 axes 5069-L340ERMS2, 5069-L340ERMS3 20 axes
motion. 5069-L350ERM 24 axes 5069-L350ERMS2, 5069-L350ERMS2K, 5069-L350ERMS3, 5069-L350ERMS3K 24 axes
5069-L380ERM 28 axes 5069-L380ERMS2, 5069-L380ERMS3 28 axes
5069-L3100ERM 32 axes 5069-L3100ERMS2, 5069-L3100ERMS3 32 axes
5069-L306ER, 5069-L306ERM, 5069-L306ERS2, 5069-L306ERMS2, 5069-L306ERMS3, 5069-L310ERS2,
5069-L310ER, 5069-L310ER-NSE, 8 modules 5069-L310ERS2K, 5069-L310ERMS2, 5069-L310ERMS2K, 5069-L310ERMS3, 8 modules
5069-L310ERM, 5069-L310ERMK 5069-L310ERMS3K
5069-L320ER, 5069-L320ERM, 16 modules 5069-L320ERS2, 5069-L320ERS2K, 5069-L320ERMS2, 5069-L320ERMS2K, 16 modules
5069-L320ERP 5069-L320ERMS3, 5069-L320ERMS3K
Local I/O modules, max 5069-L330ERS2, 5069-L330ERS2K, 5069-L330ERMS2, 5069-L330ERMS2K,
5069-L330ER(2), 5069-L330ERM(2), 5069-L330ERMS3, 5069-L330ERMS3K, 5069-L340ERS2, 5069-L340ERMS2,
31 modules 5069-L340ERMS3,
5069-L340ER, 5069-L340ERM, 5069-L350ERS2, 5069-L350ERS2K,5069-L350ERMS2, 31
5069-L340ERP, 5069-L350ERM, 5069-L350ERMS2K, 5069-L350ERMS3, 5069-L350ERMS3K, 5069-L380ERS2, modules
5069-L380ERM, 5069-L3100ERM 5069-L380ERMS2, 5069-L380ERMS3, 5069-L3100ERS2, 5069-L3100ERMS2,
5069-L3100ERMS3
• For the safety task, Compact GuardLogix controllers support Ladder Diagram only.
• Ladder Diagram (LD) • For standard tasks, Compact GuardLogix controllers support:
Programming • Structured Text (ST) – Ladder Diagram (LD)
languages • Function Block Diagram (FBD) – Structured Text (ST)
• Sequential Function Chart (SFC) – Function Block Diagram (FBD)
– Sequential Function Chart (SFC)
• Data access control
• Data access control
• Firmware Supervisor
Supported controller • Firmware Supervisor
• Secure Digital (SD) card
Features • Secure Digital (SD) card
• Standard Connections
• Standard Connections
• Safety Connections
(1) A node is an EtherNet/IP device that you add directly to the I/O configuration, and counts toward the node limits of the controller. For more information on EtherNet/IP nodes, see page 104.
(2) When you use this controller with the Logix Designer application, version 29, the application limits the number of local I/O modules in the project to 16. For more information, see
Knowledgebase Article 5380 CompactLogix controllers limited to 16 local Compact 5000 I/O modules in V29 of Studio 5000.®
With the Logix Designer application, version 30 or later, the controller supports as many as 31 local I/O modules.

IMPORTANT When you use a CompactLogix 5380 or Compact GuardLogix 5380 controller, you do not need to configure a System
Overhead Time Slice value.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 21


Chapter 1 CompactLogix 5380 and Compact GuardLogix 5380 Systems and Controllers

Features Supported by Compact GuardLogix 5380 Controllers via the


Safety Task
You can use the Compact GuardLogix 5380 controllers in safety applications via the Safety
task in the Logix Designer application.

In the Logix Designer application, the Safety task supports a subset of features that are
supported in the standard task as listed in this table.
Studio 5000 Logix Designer Application,
Feature Version 31 or Later(1)
Safety Task Standard Task
Add-On Instructions X X
Instruction-based alarms and events — X
Tag-based alarms — X
Controller logging X X
Event tasks(2) — X
Function Block Diagrams (FBD) — X
Integrated motion X(3) X
Drive Safety Instructions X —
Ladder Diagram (LD) X X
Language switching X X
License-based source protection — X
Import program components — X
Export program components X X
Sequential Function Chart (SFC) routines — X
Structured Text (ST) — X
(1) Compact GuardLogix 5380 SIL 2 controllers are compatible with Studio 5000 Logix Designer Application, version 31 or later.
Compact GuardLogix 5380 SIL 3 controllers are compatible with Studio 5000 Logix Designer Application, Version 32 or later
(2) While the safety task cannot be an Event task, standard Event tasks can be triggered with the use of the Event instruction in
the safety task.
(3) Limited to the use of Drive Safety Instructions with Kinetix 5700 ERS4 drives.

IMPORTANT Safety Consideration


Compact GuardLogix 5380 controllers can produce standard tags as unicast or multicast, but they can only produce
safety tags as unicast. The controllers can consume safety tags as either unicast or multicast.
When you configure a produced safety tag, you are only allowed to configure unicast connection options. Logix
Designer does not allow you to configure multicast connection options.
When you configure a consumed tag, you must consider the capabilities of the producer:
• If the producer in the I/O tree of this controller is a GuardLogix 5580 or Compact GuardLogix 5380 controller, and you
are consuming a safety tag, you must configure the consumed tag to use unicast.
• If the producer in the I/O tree of this controller is a GuardLogix 5570 or GuardLogix 5560 controller, or a Compact
GuardLogix 5370 controller, the safety consumed tag can be configured as either unicast or multicast. A GuardLogix
5560 controller requires Studio 5000 Logix Designer application version 19 or later for unicast produce/consume safety
tags.

22 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 1 CompactLogix 5380 and Compact GuardLogix 5380 Systems and Controllers

CIP Security CIP Security is a standard, open-source communication mechanism that helps to provide a
secure data transport across an EtherNet/IP network. CIP Security lets CIP™-connected
Applies to these controllers: devices authenticate each other before transmitting and receiving data.
CompactLogix 5380
Compact GuardLogix 5380 SIL 2 CIP Security uses the following security properties to help devices protect themselves from
Compact GuardLogix 5380 SIL 3 malicious communication:
• Device Identity and Authentication
• Data Integrity and Authentication
• Data Confidentiality

Rockwell Automation uses the following products to implement CIP Security:


• FactoryTalk® Policy Manager software (includes FactoryTalk System Services, version
6.20 or later)
• FactoryTalk Linx software, version 6.11 or later (lets workstation software communicate
securely using CIP Security)
• Studio 5000 Logix Designer® application, version 31 or later
This application is required to interface with CIP Security-enabled Logix controllers. The
minimum application version varies by controller product family.

For more information on CIP Security, for example, a list of CIP Security-capable products and
publications that describe how to use the products, including limitations and
considerations.see the following:
• The website is available at: https://www.rockwellautomation.com/en-us/capabilities/
industrial-security/security-products/cip-security.html.
• CIP Security with Rockwell Automation Products Application Technique, publication
SECURE-AT001.

Secure Controller Systems The CompactLogix 5380 controller, firmware revision 32, supports IEC-62443-4-2 SL 1
requirements. For security features and system requirements, see Develop Secure
Applications on page 195.

Power the System The controller provides power to the system as follows:
Applies to these controllers:
• MOD Power—System-side power that powers the system and lets modules transfer data
and execute logic.
CompactLogix 5380
Compact GuardLogix 5380 SIL 2
System-side power is provided through the MOD Power RTB.
Compact GuardLogix 5380 SIL 3 • SA Power—Field-side power that powers some Compact 5000 I/O modules and field-side
devices that are connected to them.
Field-side power is provided through the SA Power RTB.

There are specific considerations and restrictions that you must be aware of before you
connect MOD power and SA power to a CompactLogix 5380 system or to a Compact GuardLogix
5380 system.

For more information on how to connect MOD power and SA power to the different systems,
see the following:
• How to Power CompactLogix 5380 Controllers—Chapter 2 on page 25
• How to Power Compact GuardLogix 5380 Controllers—Chapter 3 on page 31

Real-time Clock CompactLogix 5380 controllers can retain the date and time of the real-time clock (RTC) for a
number of days, depending on the temperature of the controller.
Applies to these controllers:
CompactLogix 5380 Table 3 - RTC- Hold-up Time Duration
Compact GuardLogix 5380 SIL 2 Ambient Temperature Hold-up Time (Typical)
Compact GuardLogix 5380 SIL 3 40 °C (104 °F) 7 days
60 °C (140 °F) 5 days

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 23


Chapter 1 CompactLogix 5380 and Compact GuardLogix 5380 Systems and Controllers

Notes:

24 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 2
How to Power CompactLogix 5380 Controllers
This chapter explains how to power standard CompactLogix™ 5380 controllers.

For information on how to power Compact GuardLogix® 5380 controllers, see Chapter 3, How
to Power Compact GuardLogix 5380 Controllers on page 31.

Two Types of Power The CompactLogix 5380 controllers provide power to the system as follows:
Applies to these controllers:
• MOD Power—System-side power that powers the system and lets modules transfer data
and execute logic.
CompactLogix 5380
System-side power is provided through the MOD Power RTB.
• SA Power—Field-side power that powers some Compact 5000™ I/O modules and field-
side devices that are connected to them.
Field-side power is provided through the SA Power RTB.

Connect external power supplies to the RTBs to provide MOD power and SA power. Figure 6
shows the RTBs on a CompactLogix 5380 controller.
Figure 6 - MOD Power and SA Power RTBs on a CompactLogix 5380 Controller

MOD Power Connection

SA Power Connection

Power begins at the controller and passes across the Compact 5000 I/O module internal
circuitry via power buses.

MOD power passes across a MOD power bus, and SA power passes across a SA power bus. The
MOD power bus and SA power bus are isolated from each other.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 25


Chapter 2 How to Power CompactLogix 5380 Controllers

IMPORTANT We recommend that you use separate external power supplies for MOD
power and SA power, respectively. This practice can help prevent
unintended consequences that can result if you use one supply.
If you use separate external power supplies, the loss of power from one
external power supply does not affect the availability of power from the
other supply. For example, if separate MOD and SA external power supplies
are used and SA power is lost, MOD power remains available for the
CompactLogix 5380 controller and Compact 5000 I/O modules. As such,
data transfer continues in the system.

For more information on how to connect MOD power and SA power, see the CompactLogix 5380
Controllers Installation Instructions, publication 5069-IN013

MOD Power MOD power is a DC power source that is required to operate a CompactLogix 5380 system.
Applies to these controllers:
IMPORTANT You can only use DC power on the MOD power bus. Do not connect AC power
CompactLogix 5380 to the MOD power bus.

When external power is disconnected, the 5380 controller stores enough power
to save the project to the on-board NVS memory.
Remember the following:
• Every module in the CompactLogix 5380 system draws current from the MOD power bus
and passes the remaining current to the next module.
• MOD power lets Compact 5000 I/O modules transfer data and the controller
execute logic.
• A CompactLogix 5380 system uses only one MOD power bus.
• The total continuous current draw across the MOD power bus must not be more than 10
A, max, at 18...32V DC.
• We recommend that you use an external power supply that is adequately sized for the
total MOD power bus current draw in the system.
You must consider inrush current requirements when you calculate the total MOD
power bus current draw in the system.
Figure 7 - External Power Supply Provides MOD Power

24V DC +
Power
Supply –

26 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 2 How to Power CompactLogix 5380 Controllers

MOD Power Bus


When the MOD power source is turned on, the following occurs.
1. The CompactLogix 5380 controller draws current from the MOD power bus and passes
the remaining current through to the next module.
2. The next module draws MOD power bus current and passes the remaining current
through to the next module.
3. The process continues until MOD power bus current needs are met for all modules in the
system.
For more information on the current that the Compact 5000 I/O modules draw from the MOD
power bus, see the Compact 5000 I/O Modules Specifications Technical Data, publication
5069-TD001.

SA Power SA power provides power to devices that are connected to some of the Compact 5000 I/O
modules in the CompactLogix 5380 system. SA power is connected to the controller via an SA
Applies to these controllers: power RTB.
CompactLogix 5380
Remember the following:
• Some Compact 5000 I/O modules draw current from the SA power bus and pass the
remaining current to the next module.
• Some Compact 5000 I/O modules only pass current along the SA power bus to the next
module.
• A CompactLogix 5380 system can have multiple SA power buses. The first SA power bus
starts at the controller and passes across the I/O modules that are installed to the right
of the controller.
You use a 5069-FPD field potential distributor to establish a new SA power bus. The new
SA power bus is isolated from the SA power bus to its left in the system.
For more information on how to use a 5069-FPD field potential distributor in a
CompactLogix 5380 system, see page 29.
• If the SA power source uses DC voltage, the total continuous current draw across the SA
power bus must not be more than to 10 A, max at 18…32V DC.
• We recommend that you use an external power supply that is adequately sized for the
total SA power bus current draw on an individual bus.
You must consider inrush current requirements when you calculate the total SA power
bus current draw in the system.
• Connections to an SA power bus use a shared common. All inputs that draw current
from an SA power bus to power field-side devices have a return through circuitry to the
SA - terminal on the SA power connector.

IMPORTANT Each SA power bus has a shared common unique to that bus
because SA power buses are completely isolated from each other.
The SA power bus that the CompactLogix 5380 controller establishes
has a shared common. If you use a 5069-FPD field potential
distributor to establish a new SA power bus in the system, that
second bus has its own shared common for modules that draw
current from it.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 27


Chapter 2 How to Power CompactLogix 5380 Controllers

Figure 8 - External Power Supply Provides SA Power

AC or DC +
Power
Supply –

When the SA power source is turned on, the following occurs.


1. The CompactLogix 5380 controller draws current from the SA power bus and passes the
remaining current through to the next module.

IMPORTANT The level of current that the CompactLogix 5380 controller draws
from the SA power bus is negligible. It draws 10 mA (DC Power), 25 mA
(AC power).
2. The next module completes one of these tasks.
- If the module uses SA power, the module draws current from the SA power bus and
passes the remaining current through to the next module.
- If the module does not use SA power bus current, the module passes the remaining
current through to the next module.
3. The process continues until all SA power bus current needs are met for the modules on
the SA power bus.
If your system includes AC and DC modules that require SA power, you must use a 5069-FPD
field potential distributor to establish a separate SA power bus and separate the module types
on the isolated SA power buses.

For more information on the current that the Compact 5000 I/O modules draw from the SA
power bus, see the Compact 5000 I/O Modules Specifications Technical Data, publication
5069-TD001.

Track SA Power Bus Current Draw


We recommend that you track the SA power bus current draw, max, per module, and
collectively for the CompactLogix 5380 system.

You must make sure that the Compact 5000 I/O modules that are installed on an SA power bus
do not consume more than 10 A. If so, you must establish another SA power bus.

Consider the following with this example:


• The values in this example represent a worst-case calculation. That is, all modules that
draw SA power bus current, draw the maximum available on the module.
• Not all modules that are shown in Figure 9 use SA power bus current. For example, the
5069-ARM and 5069-OW4I modules only pass SA power bus current to the next module.
Other modules that do not use SA power bus current, but are not shown in the graphic,
include the 5069-OB16, 5069-OB16F, 5069-OX4I, and 5069-SERIAL modules.

28 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 2 How to Power CompactLogix 5380 Controllers

• System SA power bus current, max, is calculated as each module draws SA power bus
current. The calculation begins with the controller. The controller SA power bus current
draw used for the calculation is 10 mA for DC power
In Figure 9, after the 5069-IB16 module in slot 1 draws SA power bus current, the system
SA power bus current, max, is 210 mA.
After the 5069-IB16 module in slot 2 draws SA power bus current, the system SA power
bus current draw is 410 mA. This process continues until the system SA power bus
current, max, is 7.160 A.
Figure 9 - CompactLogix 5380 System - Calculate SA Power Bus Current Draw

Continuous MOD Power Bus Limited to 10 A, Max

Continuous SA Power Bus Limited to 10 A, Max

SA Power Bus Current, Max, 10 mA 200 mA 200 mA 150 mA 0 mA 3A 3A 100 mA 100 mA 150 mA 250 mA
Per Module

System SA Power Bus Current, Max = 7.160 A

Use a 5069-FPD Field Potential Distributor


to Create a New SA Power Bus
You can use a 5069-FPD field potential distributor to establish a new SA power bus in a
CompactLogix 5380 system.

The field potential distributor blocks the current that passes across the SA power bus to its
left. At that point, the field potential distributor establishes a new SA power bus for modules to
the right. The new SA power bus is isolated from the SA power bus to its left in the system.

You can connect either a 24V DC or 120/240V AC external power supply to a 5069-FPD field
potential distributor in a CompactLogix 5380 system.

Figure 10 shows a CompactLogix 5380 system that uses a 5069-FPD field potential distributor
to create a second SA power bus.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 29


Chapter 2 How to Power CompactLogix 5380 Controllers

Figure 10 - CompactLogix 5380 System - Create a New SA Power Bus

5069-FPD Field Potential Distributor

MOD Power Bus

First SA Power Bus Second SA Power Bus

You can install multiple 5069-FPD field potential distributors in the same system, if necessary.

SA Power—Additional Notes
• Other examples of system configurations that use multiple SA power buses include:
- The modules in the system collectively draw more than 10 A of SA power. That is, the
maximum current that one SA power bus can provide.
- The modules in the system must be isolated according to module types, such as
digital I/O and analog I/O modules.
- The modules in the system are isolated according to the type of field-side device to
which they are connected.
For example, you can separate modules that are connected to field-side devices that
use DC voltage from modules that are connected to field-side devices that require
AC voltage.
• The actual current in CompactLogix 5380 system changes based on the operating
conditions at a given time.
For example, the SA power bus current draw on some modules is different if all
channels power field devices or half of the channels power field devices.
• Some Compact 5000 I/O modules use field-side power but do not draw it from a SA
power bus. The modules receive field-side power from an external power supply that is
connected directly to the I/O module.
For example, the 5069-OB16 and 5069-OB16F modules use Local Actuator (LA) terminals
on the module RTB, that is, LA+ and LA– terminals for all module channels.
In this case, you can use the same external power supply that is connected to the SA
power RTB on the controller to the LA+ and LA– terminals.

IMPORTANT You must consider the current limit of an external power supply if
you use it to provide power to the SA power RTB on the controller and
the LA+ and LA– terminals on a 5069-OB16 or 5069-OB16F module.

30 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 3
How to Power Compact GuardLogix 5380
Controllers
This chapter explains how to power Compact GuardLogix® 5380 controllers.

For information on how to power standard CompactLogix™ 5380 controllers, see Chapter 2,
How to Power CompactLogix 5380 Controllers on page 25.

Two Types of Power The Compact GuardLogix 5380 controllers provide power to the system as follows:
Applies to these controllers:
• MOD Power - System-side power that powers the system and lets modules transfer data
and execute logic.
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3
System-side power is provided through the MOD Power RTB.
• SA Power - Field-side power that powers some Compact 5000™ I/O modules and field-
side devices that are connected to them.
Field-side power is provided through the SA Power RTB.

IMPORTANT Both the MOD and SA Power must be DC power on the controller side.
DC power for the Compact GuardLogix controllers must come from an
SELV/PELV-rated power source.
If you use an AC voltage for local I/O modules, then you must connect
through a 5069-FPD field potential distributor module. An AC voltage
cannot be terminated on the controller.

Connect external power supplies to the RTBs to provide MOD power and SA power. Figure 11
shows the RTBs on a Compact GuardLogix 5380 controller.
Figure 11 - MOD and SA Power RTBs on Compact GuardLogix 5380 SIL2 and SIL 3 Controllers

MOD Power MOD Power


Connection Connection

SA Power SA Power
Connection Connection

Power begins at the controller and passes across the Compact 5000 I/O module internal
circuitry via power buses.

MOD power passes across a MOD power bus, and SA power passes across a SA power bus. The
MOD power bus and SA power bus are isolated from each other.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 31


Chapter 3 How to Power Compact GuardLogix 5380 Controllers

IMPORTANT We recommend that you use separate external power supplies for MOD
power and SA power, respectively. This practice can help prevent
unintended consequences that can result if you use one supply.
If you use separate external power supplies, the loss of power from one
external power supply does not affect the availability of power from the
other supply. For example, if separate MOD and SA external power
supplies are used and SA power is lost, MOD power remains available for
the Compact GuardLogix 5380 controller and Compact 5000 I/O
modules. As such, data transfer continues in the system.

For more information on how to connect MOD power and SA power, see these publications:
• Compact GuardLogix 5380 SIL2 Controllers Installation Instructions, publication
5069-IN014.
• Compact GuardLogix 5380 SIL3 Controllers Installation Instructions, publication
5069-IN023.

MOD Power MOD power is a DC power source that is required to operate a Compact GuardLogix 5380
system. Remember the following:
Applies to these controllers:
• You must use SELV or PELV power supplies to provide MOD power to Compact
Compact GuardLogix 5380 SIL 2 GuardLogix 5380 controllers.
Compact GuardLogix 5380 SIL 3
• Every module in the Compact GuardLogix 5380 system draws current from the MOD
power bus and passes the remaining current to the next module.
• MOD power lets Compact 5000 I/O modules transfer data and the controller
execute logic.
• A Compact GuardLogix 5380 system uses only one MOD power bus.
• You must limit the MOD power source to 5 A, max, at 18...32V DC.
• We recommend that you use an external SELV/PELV rated power supply that is
adequately sized for the total MOD power bus current draw in the system. You must
consider current inrush requirements when you calculate the total MOD power bus
current draw in the system.

32 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 3 How to Power Compact GuardLogix 5380 Controllers

Figure 12 - External Power Supply Provides MOD Power

24V DC
+
SELV/PELV-
listed power –

24V DC
+
SELV/PELV-
listed power –

MOD Power Bus


When the MOD power source is turned on, the following occurs.
1. The Compact GuardLogix 5380 controller draws current from the MOD power bus and
passes the remaining current through to the next module.
2. The next module draws MOD power bus current and passes the remaining current
through to the next module.
3. The process continues until MOD power bus current needs are met for all modules in the
system.

For more information on the current that the Compact 5000 I/O modules draw from the MOD
power bus, see the Compact 5000 I/O Modules Specifications Technical Data, publication
5069-TD001.

SA Power SA power provides power to devices that are connected to some of the Compact 5000 I/O
modules in the Compact GuardLogix 5380 system. SA power is connected to the controller via
Applies to these controllers: an SA power RTB.
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 Remember the following:

IMPORTANT More specific restrictions apply when you connect SA power to a


Compact GuardLogix 5380 controller or 5069-FPD field potential distributor.
For more information, see page 38.
• You must use SELV or PELV power supplies to provide SA power to Compact GuardLogix
5380 controllers.
• If the SA power source uses DC voltage, you must limit the SA power source to 10 A, max
at 18…32V DC.
• Some Compact 5000 I/O modules draw current from the SA power bus and pass the
remaining current to the next module.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 33


Chapter 3 How to Power Compact GuardLogix 5380 Controllers

• Some Compact 5000 I/O modules only pass current along the SA power bus to the next
module.
• If the SA power source is an AC power supply, or non-SELV/PELV DC source, then you
must terminate from an FPD before consuming the power on the SA power bus.
• A Compact GuardLogix 5380 system can have multiple SA power buses. The first SA
power bus starts at the controller and passes across the I/O modules that are installed
to the right of the controller.
You can use a 5069-FPD field potential distributor to establish a new SA power bus. The
new SA power bus is isolated from the SA power bus to its left in the system.
For more information on how to use a 5069-FPD field potential distributor in a
CompactLogix 5380 system, see page 36.
• We recommend that you use an external power supply that is adequately sized for the
total SA power bus current draw on an individual bus. You must consider current inrush
requirements when you calculate the total SA power bus current draw on a specific
bus.
• Connections to an SA power bus use a shared common. All inputs that draw current
from an SA power bus to power field-side devices have a return through circuitry to the
SA - terminal on the SA power connector.

IMPORTANT Each SA power bus has a shared common unique to that bus because
SA power buses are completely isolated from each other.
The SA power bus that the controller establishes has a shared common.
If you use a 5069-FPD field potential distributor to establish a new SA
power bus in the system, that second bus has its own shared common
for modules that draw current from it.
Figure 13 - External Power Supply Provides SA Power

24V DC +
SELV/PELV-listed
power supply –

24V DC +
SELV/PELV-listed
power supply –

34 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 3 How to Power Compact GuardLogix 5380 Controllers

When the SA power source is turned on, the following occurs.


1. The controller draws current from the SA power bus and passes the remaining current
through to the next module.

IMPORTANT The level of current that the Compact GuardLogix 5380 controller
draws from the SA power bus is negligible. It draws 10 mA.
2. The next module completes one of these tasks.
- If the module uses SA power, the module draws current from the SA power bus and
passes the remaining current through to the next module.
- If the module does not use SA power bus current, the module passes the remaining
current through to the next module.
3. The process continues until all SA power bus current needs are met for the modules on
the SA power bus.
For more information on the current that the Compact 5000 I/O modules draw from the SA
power bus, see the Compact 5000 I/O Modules and EtherNet/IP Adapters Technical Data,
publication 5069-TD001.

Track SA Power Bus Current Draw


We recommend that you track the SA power bus current draw, max, per module, and
collectively for the Compact GuardLogix 5380 system. You must make sure that the
Compact 5000 I/O modules that are installed on an SA power bus do not consume more than 10
A. If so, you must establish another SA power bus.

Consider the following with this example:


• The values in this example represent a worst-case calculation. That is, all modules that
draw SA power bus current, draw the maximum available on the module.
• Not all modules that are shown in Figure 14 on page 36 use SA power bus current. For
example, the 5069-OBV8S, 5069-ARM and 5069-OB16 modules only pass SA power bus
current to the next module. Other modules that do not use SA power bus current, but
are not shown in the graphic, include the 5069-OB16F and 5069-OX4I modules.
• System SA power bus current, max, is calculated as each module draws SA power bus
current. The calculation begins with the controller. The controller SA power bus current
draw used for the calculation is 10 mA for DC power
In Figure 14, after the 5069-IB8S module in slot 1 draws SA power bus current, the
system SA power bus current, max, is 90 mA.
After the 5069-IB8S module in slot 2 draws SA power bus current, the system SA power
bus current draw is 170 mA. This process continues until the system SA power bus
current, max, is 1.27 A.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 35


Chapter 3 How to Power Compact GuardLogix 5380 Controllers

Figure 14 - Compact GuardLogix 5380 System - Calculate SA Power Bus Current Draw(1)

Continuous MOD Power Bus Limited to 5 A, Max

Continuous SA Power Bus Limited to 10 A, Max

SA Power Bus Current, Max, 10 mA 80 mA 80 mA 0 mA 0 mA 900 mA 0 mA 100 mA 100 mA 0 mA 0 mA


Per Module

System SA Power Bus Current, Max = 1.27 A

Use a 5069-FPD Field Potential Distributor to Create a New


SA Power Bus

IMPORTANT If you use local Compact 5000 I/O relay modules, or an AC voltage for
locl Compact 5000 I/O modules, then you must connect through a
5069-FPD field potential distributor module. An AC voltage cannot be
terminated on the controller.
You can use a 5069-FPD field potential distributor to establish a new SA power bus in a
Compact GuardLogix 5380 system.
The field potential distributor blocks the current that passes across the SA power bus to its
left. At that point, the field potential distributor establishes a new SA power bus for modules to
the right. The new SA power bus is isolated from the SA power bus to its left in the system.

You can connect either a 24V DC or 120/240V AC external power supply to a 5069-FPD field
potential distributor in a Compact GuardLogix 5380 system.

IMPORTANT Some restrictions apply when you connect SA power to a 5069-FPD field
potential distributor. For more information, see page 38.

Figure 15 shows a Compact GuardLogix 5380 system that uses a 5069-FPD field potential
distributor to create a second SA power bus.

(1) Although a Compact GuardLogix 5380 SIL2 controller is shown, this example also applies to Compact GuardLogix 5380 SIL 3
controllers.

36 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 3 How to Power Compact GuardLogix 5380 Controllers

Figure 15 - Compact GuardLogix 5380 System - Create a New SA Power Bus(1)


5069-FPD Field Potential Distributor

MOD Power Bus

First SA Power Bus Second SA Power Bus

You can install multiple 5069-FPD field potential distributors in the same system, if necessary.

(1) Although a Compact GuardLogix 5380 SIL2 controller is shown, this example also applies to Compact GuardLogix 5380 SIL 3
controllers.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 37


Chapter 3 How to Power Compact GuardLogix 5380 Controllers

Restrictions When You Connect SA Power to a


Compact GuardLogix 5380 System
Remember these restrictions in Table 4 hen you connect SA power to a
Compact GuardLogix 5380 system.
Table 4 - SA Power Restrictions - Compact GuardLogix 5380 System
Component to Which SA Restrictions
Power Is Connected
• You must use SELV/PELV-listed power supplies to provide SA power to Compact GuardLogix 5380 controllers.
Compact GuardLogix 5380 SIL • You can only connect a 24V DC SELV/PELV-listed power supply.
2 or SIL 3 Controller
• The total continuous current draw across the SA power bus must not be more than 10 A, max at 0…32V DC.
Example Compact GuardLogix System
24V DC +
SELV-listed MOD Power—from SELV-listed
Power Supply – Power Supply

Compact 5000 I/O 24V DC safety and


standard input module
*Although a Compact GuardLogix 5380 SIL2
controller is shown, this example also applies to
Compact GuardLogix 5380 SIL 3 controllers.

SA Power Bus—From
SELV-listed Power Supply

24V DC
+
SELV-listed
Power Supply –

Ground

38 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 3 How to Power Compact GuardLogix 5380 Controllers

Table 4 - SA Power Restrictions - Compact GuardLogix 5380 System (Continued)


Component to Which SA Restrictions
Power Is Connected
In addition to the restrictions on page 38, these restrictions also apply:
• You can use non-SELV or PELV power supplies if only Compact 5000 I/O standard modules are installed to the right of the 5069-FPD field
potential distributor.
• You can connect a 24V DC or 120/240V AC power supply. The example uses a 120/240V AC power supply.
– If the SA power that is connected to the 5069-FPD field potential distributor is DC voltage, the total continuous current draw across
the SA power bus must not be more than 10 A, max at 0…32V DC.
5069-FPD Field Potential – If a Compact GuardLogix 5380 system includes Compact 5000 I/O relay modules (5069-OW4I, 5069-OX4I, 5069-OW16), or I/O modules
Distributor With Compact 5000 that require SA power that is AC voltage, you must install these modules to the right of a 5069-FPD field potential distributor, as
I/O Standard Modules Only shown.
IMPORTANT: This requirement applies even if it means that you must install the 5069-FPD field potential distributor immediately to
the right of the Compact GuardLogix 5380 controller.
• If a Compact GuardLogix 5380 system includes Compact 5000 I/O standard modules that use SA power that is provided by a power
supply that is not SELV/PELV-listed, the I/O modules must be installed to the right of a 5069-FPD field potential distributor.
IMPORTANT: The SA power bus that the 5069-FPD field potential distributor establishes cannot include any Compact 5000 I/O safety
modules.
Example Compact GuardLogix System
24V DC
+
SELV-listed
Power Supply – MOD Power - from SELV-listed Power Supply

Compact 5000 I/O 24V D C relay modules


Compact 5000 I/O 24V DC safety and

Compact 5000 I/O 120/240V AC


standard input modules
standard input module

SA Power Bus - From SA Power Bus - From SA Power Bus - From


SELV-listed Power Supply Standard or SELV-listed Standard Power Supply
Power Supply

24V DC + 24V DC Standard + 120/240V AC +


SELV-listed or SELV-listed Standard
Power Supply – Power Supply – Power Supply –

Ground Ground Ground

*Although a Compact GuardLogix 5380 SIL2 controller is shown, this


example also applies to Compact GuardLogix 5380 SIL 3 controllers.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 39


Chapter 3 How to Power Compact GuardLogix 5380 Controllers

Table 4 - SA Power Restrictions - Compact GuardLogix 5380 System (Continued)


Component to Which SA Restrictions
Power Is Connected
5069-FPD Field Potential In addition to the restrictions on page 38 and page 39, this restriction also applies:
Distributor With Compact 5000
I/O Safety and Standard • You must use SELV or PELV power supplies to provide SA power to Compact 5000 I/O safety modules that are installed to the right of the
Modules 5069-FPD field potential distributor.
Example Compact GuardLogix 5380 System

24V DC +
SELV-listed
MOD Power - from SELV-listed Power Supply
Power Supply –

Compact 5000 I/O 24V DC safety and

Compact 5000 I/O 24V DC safety and


Compact 5000 I/O 120/240V AC

standard output module


standard input module

standard input module

SA Power Bus - From SA Power Bus - From SA Power Bus - From


SELV-listed Power Supply Standard Power Supply SELV-listed Power Supply

24V DC 120/240V AC 24V DC


+ + +
SELV-listed Standard SELV-listed
Power Supply – Power Supply – Power Supply –

Ground Ground Ground

*Although a Compact GuardLogix 5380 SIL2 controller is shown, this


example also applies to Compact GuardLogix 5380 SIL 3 controllers.

40 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 3 How to Power Compact GuardLogix 5380 Controllers

SA Power—Additional Notes
• Other examples of system configurations that use multiple SA power buses include:
- The modules in the system collectively draw more than 10 A of SA power. That is, the
maximum current that one SA power bus can provide.
- The modules in the system must be isolated according to module types, such as
digital I/O and analog I/O modules.
- The modules in the system are isolated according to the type of field-side device to
which they are connected.
For example, you can separate modules that are connected to field-side devices that
use DC voltage from modules that are connected to field-side devices that require
AC voltage.
• The actual current in a Compact GuardLogix 5380 system changes based on the
operating conditions at a given time.
For example, the SA power bus current draw on some modules is different if all
channels power field devices or half of the channels power field devices.
• Some Compact 5000 I/O modules use field-side power but do not draw it from a SA
power bus. The modules receive field-side power from an external power supply that is
connected directly to the I/O module.
For example, the 5069-OB16, 5069-OB16F, and 5069-OBV8S modules use Local Actuator
(LA) terminals on the module RTB, that is, LA+ and LA– terminals for all
module channels.
In this case, you can use the same external power supply that is connected to the SA
power RTB on the controller to the LA+ and LA– terminals.

IMPORTANT You must consider the current limit of an external power supply
if you use it to provide power to the SA power RTB on the
controller and the LA+ and LA– terminals on a 5069-OB16,
5069-OB16F, or 5069-OBV8S module. The 5069-OBV8S module
requires a SELV/PELV-rated power supply.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 41


Chapter 3 How to Power Compact GuardLogix 5380 Controllers

Notes:

42 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 4
Safety Concept of
Compact GuardLogix 5380 Controllers
Functional Safety Capability The Compact GuardLogix® 5380 controller systems are certified for use in safety applications
up to and including SIL 2/PLd and SIL 3/PLe where the de-energized state is the safe state.
Applies to these controllers:
Compact GuardLogix 5380 SIL 2 IEC 61508 IEC 62061 ISO 13849-1
Compact GuardLogix 5380 SIL 3 Controller System Type-approved and certified Suitable for use in Suitable for use in safety
for use in safety applications safety applications applications up to and
up to and including: up to and including: including:
Compact GuardLogix 5380
SIL 2 SIL CL2 Performance Level PLd (Cat. 3)
SIL 2 controller systems (1)
Compact GuardLogix 5380
SIL 3 controller SIL 3 SIL CL3 Performance Level PLe (Cat. 4)
systems(2)(3)
(1) Compact GuardLogix 5380 SIL 2 controller catalog numbers have a ‘2’ at the end, for example, 5069-L3xxxxxS2, and are for
use in safety applications up to and including SIL 2.
(2) Compact GuardLogix 5380 SIL 3 controller catalog numbers have a ‘3’ at the end, for example, 5069-L3xxxxxS3, and are for
use in safety applications up to and including SIL 3.
(3) For SIL 3/PLe safety applications, the Compact GuardLogix® 5380 SIL 3 controller system consists of a primary controller
with an internal safety partner, that function together in a 1oo2 architecture.

For SIL 2/PLd and SIL 3/PLe safety system requirements, including functional validation test
intervals, system reaction time, and PFD/PFH calculations, see to the GuardLogix 5580 and
Compact GuardLogix 5380 Controller Systems Safety Reference Manual, publication
1756-RM012.

You must read, understand, and fulfill these requirements before you operate a Compact
GuardLogix safety system.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 43


Chapter 4 Safety Concept of Compact GuardLogix 5380 Controllers

Safety Network Number The safety network number (SNN) uniquely identifies CIP Safety™ subnets within a routable
safety network. The combination of SNN + Node Address uniquely identifies each CIP Safety
Applies to these controllers: port on each device in the routable safety network.
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 The application assigns an SNN to each CIP Safety subnet attached to a
Compact GuardLogix 5380 controller, including the backplane. If there are other Logix Safety
controllers on an attached Ethernet network, assign the same SNN for this network in each
controller application. This allows you to use Logix Designer's automatic assignment of safety
network numbers for devices added to the application.

For an explanation of the Safety Network Number, see the GuardLogix 5580 and
Compact GuardLogix 5380 Controller Systems Safety Reference Manual,
publication 1756-RM012.
To assign SNNs, see Assign the Safety Network Number (SNN) on page 67.
Figure 16 - Safety Network Numbers

44 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 4 Safety Concept of Compact GuardLogix 5380 Controllers

Safety Signature The GuardLogix® system uses a safety signature to verify the integrity of a safety application:
Applies to these controllers:
• The safety signature applies to the entire safety portion of the controller project. The
ability to create, record, and verify the safety signature is a mandatory part of the
Compact GuardLogix 5380 SIL 2 safety-application development process. The safety signature must be present to
Compact GuardLogix 5380 SIL 3 operate as a SIL 2/PLd or SIL 3/PLe safety controller. Nothing in the standard
application is included in the safety signature.
• The safety signature is a hierarchy of multiple safety signature elements. For example,
the safety task, programs, and routines are examples of safety signature elements.
Safety signature elements can help you during impact analysis by identifying the
individual changes within a controller project. If your validation plan does not require
revalidation of unchanged elements, your certification effort can be reduced.
All safety signature elements are created at the time that you generate the safety
signature for the project. To view all safety signature elements for a project, you can
run the Safety Signature report.

The safety signature and each of its elements have the following:
• Safety signature ID--A unique 64-character alphanumeric identification number.
• Time stamp—The date and time that the safety signature was generated. For a safety
signature element, the time stamp changes whenever its signature ID changes.
Figure 17 - Safety Signature

For details about the safety signature, safety signature elements, and how to generate the
safety signature and the Safety Signature report, see the GuardLogix 5580 and Compact
GuardLogix 5380 Controller Systems Safety Reference Manual, publication 1756-RM012.

Distinguish Between Slots of a Compact GuardLogix 5380 system chassis that are not used by the safety function
can be populated with other Compact 5000™ I/O modules that are certified to the Low Voltage
Standard and Safety and EMC Directives. See http://www.rockwellautomation.com/rockwellautomation/
Components certification/ce.page to find the CE certificate for the CompactLogix™ Product Family and
determine the modules that are certified.
Applies to these controllers:
Compact GuardLogix 5380 SIL 2 You must create and document a clear, logical, and visible distinction between the safety and
Compact GuardLogix 5380 SIL 3 standard portions of the controller project. As part of this distinction, the Studio 5000 Logix
Designer® application features safety identification icons to identify the safety task, safety
programs, safety routines, and safety components.

In addition, the Logix Designer application displays a safety class attribute whenever safety
task, safety programs, safety routine, safety tag, or safety Add-On Instruction properties are
displayed.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 45


Chapter 4 Safety Concept of Compact GuardLogix 5380 Controllers

Controller Data-flow This illustration explains the standard and safety data-flow capabilities of the
Compact GuardLogix 5380 controllers.
Capabilities
Figure 18 - Data-flow Capabilities
Applies to these controllers:
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 Controllers
Compact GuardLogix 5380 SIL 3

Standard Safety
Safety Task
Standard Tasks
Safety Programs
Standard Programs
Safety Routines
Standard Routines

Program Safety Data


Program Data

Controller Standard Tags Controller Safety Tags

No. Description
1 Standard tags and logic behave the same way that they do in a standard CompactLogix 5380 controller.
2 Standard tag data, program- or controller-scoped, can be exchanged with external HMI devices, personal
computers, and other controllers.
Compact GuardLogix 5380 controllers are integrated controllers with the ability to move (map) standard tag
data into safety tags for use within the safety task. This is the only way to get standard tag data in to the
safety task. Safety logic in the safety task cannot read or write the standard tag that is the source in the
tag mapping data transfer; it can only reference the safety tag destination of the mapping. But, it can read
3 and write that safety tag.

ATTENTION: Mapped tag data must not be used to control a


SIL 2/PLd or SIL 3/PLe output directly.
4 Controller-scoped safety tags can be read directly by standard logic.
5 Safety tags can be read or written by safety logic.
Safety tags can be exchanged between safety controllers over Ethernet networks, including 1756
6 GuardLogix controllers and 5069 Compact GuardLogix controllers.
Safety tag data, program- or controller-scoped, can be read by external devices, such as HMI devices,
7 personal computers, or other standard controllers. External devices cannot write to safety tags (whether
the controller is protected or not). Once this data is read, it is considered standard data, not safety data.

46 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 4 Safety Concept of Compact GuardLogix 5380 Controllers

Safety Terminology The following table defines terms that are used in this manual.
Abbreviation Full Term Definition
1oo1 One Out of One Identifies the programmable electronic controller architecture. 1oo1 is a single-channel system.
1oo2 One Out of Two Identifies the programmable electronic controller architecture. 1oo2 is a dual-channel system.
CIP Safety Common Industrial Protocol—Safety Certified SIL 3/PLe-rated version of CIP™.
DC Diagnostic Coverage The ratio of the detected failure rate to the total failure rate.
PFD Probability of a dangerous failure on demand The average probability of a dangerous failure on demand.
PFH Probability of dangerous failure per hour The average frequency of a dangerous failure per hour.
PL Performance Level ISO 13849-1 safety rating.
A relative level of risk-reduction that is provided by a safety function, or to specify a target level of risk
SIL Safety Integrity Level reduction.
SIL CL SIL Claim Limit The maximum safety integrity level (SIL) that can be achieved.
SNN Safety Network Number A unique number that identifies a section of a safety network.
Unique Node ID (also called unique node reference) The unique node reference is a combination of a safety network number (SNN) and the node address
UNID of the node.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 47


Chapter 4 Safety Concept of Compact GuardLogix 5380 Controllers

Notes:

48 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 5
Connect to the Controller
Before You Begin Before you can connect to the controller through the EtherNet or USB port, you must configure
the EtherNet/IP™ or USB driver in Linx-based software on your workstation:
Applies to these controllers:
• The controller has an Ethernet port that supports 10 Mbps, 100 Mbps, or 1 Gbps
CompactLogix™ 5380
Compact GuardLogix® 5380 SIL 2
• The controller has a USB port that uses a Type B receptacle. The port is USB 2.0
compatible and runs at 12 Mbps.
Compact GuardLogix 5380 SIL 3
• Install and configure a communication module in the chassis with the controller as
described in the installation instructions for the communication module.

The EtherNet/IP driver:


• Supports runtime communications
• Requires that the workstation and the controller are configured
• Supports communications over longer distances when compared to the USB driver
USB driver:
• Convenient method to connect to an unconfigured controller and configure the Ethernet
port
• Convenient method to connect to a controller when the Ethernet port configuration is
unknown
• Convenient method to update the controller firmware
• Not intended for runtime connections; it is a temporary-use only connection with a
limited cabling distance

For information on how to configure EtherNet/IP or USB drivers, see the EtherNet/IP Network
Devices User Manual, publication ENET-UM006.

Connection Options Before you can begin using your controller, you must make a connection to the controller.
Make sure that you have already configured the EtherNet/IP or USB communication drivers.
Applies to these controllers: See the EtherNet/IP Network Devices User Manual, publication ENET-UM006.
CompactLogix 5380
Compact GuardLogix 5380 SIL 2 Connection options with the controller include:
Compact GuardLogix 5380 SIL 3 • Ethernet cable to an Ethernet port - The controller Ethernet ports support
communication rates of 10 Mbps, 100 Mbps, and 1 Gbps. See Connect an Ethernet Cable
on page 50.
• USB cable to the USB port - The controller USB port uses a Type B receptacle and is
USB 2.0 compatible. The port runs at 12 Mbps. See Connect a USB Cable on page 50.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 49


Chapter 5 Connect to the Controller

Connect an Ethernet Cable


The example graphic shows a Compact GuardLogix 5380 controller. You perform the same
task to connect an Ethernet cable to a CompactLogix 5380 controller.

WARNING: If you connect or disconnect the communications cable with power


applied to this module or any device on the network, an electric arc can occur.
This could cause an explosion in hazardous location installations. Be sure that
power is removed or the area is nonhazardous before proceeding.

If you are connecting a controller directly to an EtherNet/IP network, connect a CAT 5e or CAT
6 Ethernet cable with an RJ45 connector to an Ethernet port on the bottom of the controller.

Port A1

Port A2

For information on how to select the proper cable, see Guidance for Selecting Cables for
EtherNet/IP Networks, publication ENET-WP007-EN-P.

Connect a USB Cable


Use the USB connection to update firmware and download programs.

The example graphic shows a CompactLogix 5380 controller. You perform the same task to
connect an Ethernet cable to a Compact GuardLogix 5380 controller.

The USB port is intended only for temporary local programming purposes and
not intended for permanent connection. The USB cable is not to exceed 3.0 m
(9.84 ft) and must not contain hubs.

WARNING: Do not use the USB port in hazardous locations.

50 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 5 Connect to the Controller

Figure 19 - USB Connection

Set the IP Address When the controller is in the out-of-the-box condition, the following apply regarding IP
addresses:
Applies to these controllers:
• The controller embedded Ethernet ports are configured to obtain an IP address via a
CompactLogix 5380 DHCP server.
Compact GuardLogix 5380 SIL 2
If there is no DHCP server or the DHCP server is not configured to set the IP address, you
Compact GuardLogix 5380 SIL 3 must set the IP address manually.
• The controller is configured so that you must set the IP address each time that power is
cycled.
You can configure your controller so that you are not required to set an IP address each
time that power is cycled.
• The controller is configured to use Dual-IP mode. As a result, you must set a unique IP
address for port A1 and port A2.

Requirements
To set the IP address, have the following:
• EtherNet/IP or USB drivers installed on the programming workstation
• MAC ID from the device, which is on the label on the side of the device
• Recommended IP address for the device

Other Methods to Set the IP Address


The controller supports the following methods to change the IP address:
• BOOTP/DHCP utility
• RSLinx® Classic software
• Studio 5000 Logix Designer® application

For more information on how to use these methods, see EtherNet/IP Network Devices User
Manual, publication ENET-UM006.

IMPORTANT The EtherNet/IP mode in which the controller operates affects the
setting and use of IP addresses on the controller. For example, if the
controller operates in Dual-IP mode, you must set an IP address for
each controller Ethernet port. That is, you must complete the steps that
are described in this section twice–once for each port.
For more information on how the EtherNet/IP modes affect the
controller IP address, see Use EtherNet/IP Modes on page 117.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 51


Chapter 5 Connect to the Controller

Use a Secure Digital Card to Set the Controller IP Address


You can use an SD card to set the controller IP address. The SD card can set the IP address
when it loads a project onto the controller.

For more information on how to use an SD card, see Use the Secure Digital Card on page 91.

Duplicate IP Address The controller verifies that its IP address does not match any other network device IP address
when you perform either of these tasks:
Detection
• Connect the controller to a EtherNet/IP network.
Applies to these controllers: • Change the controller IP address.
CompactLogix 5380
Compact GuardLogix 5380 SIL 2 If the controller IP address matches that of another device on the network, the controller
Compact GuardLogix 5380 SIL 3 Ethernet port transitions to Conflict mode. In Conflict mode, these conditions exist:
• Network (NET) status indicator is solid red.
• The 4-character display indicates the conflict.
The display scrolls: <IP_address_of_this_module> Duplicate IP
<Mac_address_of_duplicate_node_detected>
For example: 192.168.1.1 Duplicate IP - 00:00:BC:02:34:B4

Duplicate IP Address Resolution


When two devices on a network have IP addresses that conflict, the resolution depends on the
conditions in which the duplication is detected. This table describes how duplicate IP
addresses are resolved.
Duplicate IP Address Detection Conditions Resolution Process
1. The device that began operation first uses the IP
• Both devices support duplicate IP address detection. address and continues to operate without
• Second device is added to the network after the first interruption.
device is operating on the network. 2. The device that begins operation second detects the
duplication and enters Conflict mode.
Both EtherNet/IP devices enter Conflict mode.
• Both devices support duplicate IP address detection. To resolve this conflict, follow these steps.
• Both devices were powered up at approximately the 1. Assign a new IP address to the controller.
same time.
2. Cycle power to the other device.
1. Regardless of which device obtained the IP address
first, the device that does not support IP address
detection uses the IP address and continues to
One device supports duplicate IP address detection and operate without interruption.
a second device does not.
2. The device that supports duplicate IP address
detection detects the duplication and enters Conflict
mode.

52 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 5 Connect to the Controller

DNS Addressing You can also use DNS addressing to specify a host name for a controller, a domain name, and
DNS servers. DNS addressing makes it possible to configure similar network structures and IP
Applies to these controllers: address sequences under different domains.
CompactLogix 5380
Compact GuardLogix 5380 SIL 2 IMPORTANT Safety Considerations
Compact GuardLogix 5380 SIL 3 • Safety connections are not allowed to use host names (this requires DNS
lookup, which is not allowed for Safety I/O). Safety devices on
EtherNet/IP networks do not present the host name parameter.
Standard devices do present the host name parameter, regardless of
whether the project is safety or standard.
• Compact GuardLogix 5380 controllers can have safety connections or
standard connections. When used in a standard project, GuardLogix
5580 controllers are considered standard devices (the only connections
are standard consumed tags), so the controller presents the host name
parameter.
• When Compact GuardLogix 5380 controllers are used in a safety project,
it is assumed to be a safety device, and the host name parameter is not
presented.

DNS addressing is necessary only if you refer to the controller by host name, such as in path
descriptions in MSG instructions.

To use DNS addressing, follow these steps.


1. Assign a host name to the controller.
A network administrator can assign a host name. Valid host names must be IEC-1131-3
compliant.
2. Configure the controller parameters.
3. Configure the IP address, subnet mask, gateway address, a host name for the controller,
domain name, and primary/secondary DNS server addresses.
In the DNS server, the host name must match the IP address of the controller.
4. In the Logix Designer application, add the controller to the I/O configuration tree.

IMPORTANT Remember the following:


• If a child module resides in the same domain as its parent module, type
the host name. If the domain of the child module differs from the
domain of its parent module, type the host name and the domain name
(hostname.domainname)
• You can also use DNS addressing in a module profile in the I/O
configuration tree or in a message path. If the domain name of the
destination module differs from the domain name of the source module,
then use a fully qualified DNS name (hostname.domainname). For
example, to send a message from EN2T1.location1.companyA to
EN2T1.location2.companyA, the host names match, but the domains
differ. Without the entry of a fully qualified DNS name, the module adds
the default domain name to the specified host name.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 53


Chapter 5 Connect to the Controller

Update Controller Firmware You can use these tools to update the controller firmware:
Applies to these controllers:
• ControlFLASH™ or ControlFLASH Plus™ software
CompactLogix 5380 • AutoFlash feature of the Logix Designer application
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3
Firmware Upgrade Guidelines for Safety Controllers

IMPORTANT Safety Consideration


You cannot update a controller that is safety locked.
The IEC 61508 functional safety standard requires impact analysis before upgrading or
modifying components in a certified, functional safety system. This section provides high-
level guidance on how you can perform the impact analysis for safety controller hardware/
firmware upgrades. Reference the standard to make sure you fulfill all of the requirements as
they relate to your application.
When you upgrade controller firmware to a newer version, consider the following:
• All major and minor firmware releases for Compact GuardLogix controller systems are
certified for use in safety applications. As part of the certification process, Rockwell
Automation tests the safety-related firmware functions (for example the CIP Safety™
communication subsystems, embedded safety instruction execution, and safety-
related diagnostic functions). The firmware release notes identify changes to safety-
related functions.
• Perform an impact analysis of the planned firmware upgrade.
- Review of the firmware release notes for changes in safety-related functionality.
- Review of hardware and firmware compatibility in the Product Compatibility and
Download site to identify potential compatibility conflicts.
- Any modification, enhancement, or adaptation of your validated software must be
planned and analyzed for any impact to the functional safety system as described in
the 'Edit Your Safety Application' section in the safety reference manual for your
controller.
• You must remove and re-generate the safety signature as part of the firmware upgrade
process. Use the online and offline edit process described in the safety reference
manual for your controller.

For more controller-specific information, see the GuardLogix 5580 and Compact GuardLogix
5380 Safety Reference Manual, publication 1756-RM012.

IMPORTANT Compact GuardLogix 5380 controllers have a different compiler than


earlier controllers. You must re-validate that applications on earlier
controllers compile correctly on Compact GuardLogix 5380 controllers.
For product change management guidelines and definitions of how Rockwell Automation
manages product versions, see System Security Design Guidelines Reference Manual,
publication SECURE-RM001.

Example:
1. From the Product Compatibility and Download Center:
a. Review all firmware release notes, starting with the original firmware revision
through the new firmware revision, to identify any changes that impact the safety-
related implementation of the application.
b. Review hardware and firmware compatibility to identify any restrictions between the
original system components and the new system components.
2. Perform a hazard and risk assessment for any changes identified during the impact
analysis and determine what additional testing is necessary.
3. Perform the online and offline edit process described in the safety reference manual
for your controller. You can restrict the 'Test the Application' block to the testing
identified by the hazard and risk assessment.

54 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 5 Connect to the Controller

Controller Firmware and Logix Designer Application Compatibility


In Logix 5000™ control systems, the controller firmware and the Logix Designer application
must be of the same major revision level. For example, if the controller firmware revision is
31.xxx, you must use the Logix Designer application, version 31.

There are minimum software version requirements for the software applications that you use
in your system.

Compatible builds of software have been tested together to verify they work properly. Versions
of software that are not identified as being compatible with each other have not been tested
together and are not guaranteed to work.

For more information on controller firmware revisions and software application minimum
requirements, go to the Product Compatibility and Download Center (PCDC) at rok.auto/pcdc.
In the PCDC:
• The Download section has the firmware for your controller.
• The Compare section has software compatibility information for software applications
that are used in a CompactLogix 5380 and Compact GuardLogix 5380 control system.

Determine Required Controller Firmware


The controller ships with firmware revision 1.xxx installed. You must update the firmware
revision before you can use it in a Logix Designer application project.

In Logix 5000™ control systems, the controller firmware and the Logix Designer application
must be of the same major revision level. For example, if the controller firmware revision is
31.xxx, you must use the Logix Designer application, version 31.

IMPORTANT The controller must be in Remote Program or Program mode and all
major recoverable faults must be cleared to accept updates.

Obtain Controller Firmware


You can obtain controller firmware in these ways:
• Firmware is packaged as part of the Studio 5000 Logix Designer environment
installation.

IMPORTANT The firmware that is packaged with the software installation is


the initial release of the controller firmware. Subsequent
firmware revisions to address anomalies may be released during
a product’s life.
We recommend that you check the Product Compatibility and
Download Center (PCDC) to determine if later revisions of the
controller firmware are available. For more information, see the
next bullet.
• From the Rockwell Automation Product Compatibility and Download Center (PCDC). You
can check for available revisions of controller firmware, and download controller
firmware, associated files, and product release notes.
To visit PCDC, go to http://compatibility.rockwellautomation.com/Pages/home.aspx.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 55


Chapter 5 Connect to the Controller

Use ControlFLASH Plus Software to Update Firmware

ATTENTION: If the Secure Digital (SD) card is locked and set to load on power-
up, this update can be overwritten by firmware on the SD card.

To update your controller firmware with ControlFLASH Plus software, complete the following
steps.
If your application network cannot access the PCDC during operation, make sure
that you download controller firmware revision to which you want to update the
controller before beginning these steps.
1. Verify that the network connection is made.
2. From the Windows Start Menu, click FLASH Programming Tools > ControlFLASH Plus.

When the software starts, it automatically browses the network to which the
workstation and the controllers are connected.
If the devices on the network have changed since the last time you connected, the
Refresh Firmware dialog box appears and asks if you want to refresh all firmware.
3. Click Next.

56 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 5 Connect to the Controller

4. If the controller appears on the Flash Device tab in the ControlFLASH Plus dialog box,
click the controller and move to step 7.
5. If the controller does not appear on the Flash Devices tab in the ControlFLASH Plus
dialog box, click the browse button.

6. On the Network Browser dialog box, complete the following steps.


a. Drill down to the controller.
b. Select the controller.
c. Click OK.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 57


Chapter 5 Connect to the Controller

7. On the Flash Devices tab, complete the following steps.


a. To select the controller, click the check box to the left of the controller Device Name.
b. Confirm the current controller firmware revision and the revision to which you want
to upgrade.
The Flash To column gives you the option to the latest revision available at
the PCDC, as shown in the example. You must have access to the PCDC to
use this option, however.
Otherwise, ControlFLASH Plus flashes to the latest revision on the computer.
c. Click Next.
If you are not logged into the Rockwell Automation Technical Support site, you are
prompted to do so.

8. If the Download Center License Agreement dialog box appears, click Accept.
This dialog box only appears if you choose to flash to the latest revision at the PCDC.

The firmware installation file is downloaded to your workstation.

58 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 5 Connect to the Controller

9. Click Next.

You can receive an alert to read and understand all warnings before the flash operation
begins.
10. Click Close and read the warnings.
The warning is describes in the Status column.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 59


Chapter 5 Connect to the Controller

11. Click Flash.

12. When ControlFLASH Plus indicates that the update was successful, click Close.

13. Click Done.

60 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 5 Connect to the Controller

Use AutoFlash to Update Firmware


To update the controller firmware with the AutoFlash feature, complete these steps.

ATTENTION: If the Secure Digital Card is locked and set to load on power-up,
this update can be overwritten by firmware on the SD card.

1. Verify that the network connection is made and the network driver has been configured
in Linx-based communication software.
2. Start the Logix Designer application, and create a project.
3. In the project, click RSWho.

4. Expand the communication path and select the controller.

5. Select the controller and click Go Online.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 61


Chapter 5 Connect to the Controller

6. On the Who Active dialog box, select the controller under the communication driver you
.
want to use, and click Update Firmware.

7. On the Choose Firmware Revision dialog, browse to the location of the firmware files
(C:\Program Files (x86)\ControlFlash).
8. Select the firmware revision, and click Update.
9. On the Confirmation dialog, click Yes.

10. On the ControlFLASH Attention dialog, click OK.

A progress dialog box indicates the progress of the firmware update. The controllers
indicate progress in updates and blocks.

IMPORTANT Let the firmware update complete before you cycle power or
otherwise interrupt the update.
If the ControlFLASH update of the controller is interrupted, the
controllers revert to boot firmware, that is, revision 1.xxx.
When the update is complete, the Update Status dialog box indicates that the update is
complete.
11. Click OK on the Who Active dialog box.

62 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 5 Connect to the Controller

Controllers with Firmware For controllers with firmware revisions earlier than revision 31, you must be aware of the
following before you set the IP address and update the controller firmware:
Earlier than Revision 31
• Controller state before you make changes
Applies to these controllers: • Firmware revision to which you are updating the controller
CompactLogix 5380
• Order in which you set the IP address and update the firmware revision
Controller State Firmware Revision of Task Completion Order
Before Making Description Result of Completing Tasks in Order Indicated
Update/Change
Changes
• The controller EtherNet/IP mode is automatically set to Dual-
IP mode.
1. Change the EtherNet/IP mode • The port A1/A2 IP address, network mask, default gateway
from Dual-IP mode to Linear/ settings are applied to port A2.
• No IP address set DLR mode. • Other port A1/A2 settings, for example, DNS servers and
• Unique MAC addresss are 2. Set IP address on port A1/A2. Domain Name, are lost.
used for port A1 and 3. Install controller firmware. • The port A1/A2 MAC address is applied to port A1, and a
port A2, respectively Revision 29.011 or separate MAC address is applied to Port A2.
• Each port on the later • You must set the IP address configuration
controller is • The controller EtherNet/IP mode remains set to Dual-IP mode
DHCP-enabled after the firmware is installed.
Out-of-box • Firmware revision 1.xxx 1. Install controller firmware. • The controller EtherNet/IP mode is set to Dual-IP mode when
2. Set IP addresses on port A1 it is in the out-of-box state.
and port A2. • A unique MAC address is assigned to each controller port.
• You must set the IP address and related parameters for port
A1 (enterprise port) and port A2 (device-level port).
• No IP address is set Revision 28.xxx 1. Set IP address on port A1/A2.
• One MAC address is used IMPORTANT: Only the 2. Install controller firmware. • The controller EtherNet/IP mode is automatically set to
for port A1/A2 5069-L320ER and Linear/DLR mode.
• Port A1/A2 is 5069-L340ERM 1. Install controller firmware.
controllers support • The IP address settings on port A1/A2 remain the same.
DHCP-enabled 2. Set IP address on port A1/A2.
• Firmware revision 1.xxx revision 28.xxx.
• EtherNet/IP mode changes to Dual-IP mode.
• The port A1/A2 IP address, network mask, default gateway
settings are applied to port A2.
• Other port A1/A2 settings, for example, DNS servers and
Domain Name, are lost.
• IP address set on port A1/
A2 • The port A1/A2 MAC address is applied to port A1. A separate
Revision 29.011 or Update controller firmware MAC address is applied to Port A2.
• Firmware revision 28.xxx later
is installed • The I/O Configuration section in the Logix Designer
application project is automatically assigned to port A1.
• You can change the I/O configuration in the Logix Designer
application project to assign it to port A2.
• If necessary, you can change to DLR/Linear mode after the
Operating firmware revision update.
• Controller operates in
Linear/DLR mode
• IP address set on port A1/ Downgrade to revision Downgrade controller firmware • EtherNet/IP mode remains in Linear/DLR mode
A2 28.xxx • IP address settings remain the same
• Firmware revision 29.011 IMPORTANT: You can
or later is installed perform this
• Controller operates in download only on the
Dual-IP mode 5069-L320ER and • EtherNet/IP mode automatically changes from Dual-IP mode
• IP addresses are set on 5069-L340ERM to Linear/DLR mode
port A1 and port A2 controllers. Downgrade controller firmware
• After the change is made, the port A2 Internet Protocol
• Firmware revision 29.011 configuration is applied to the A1/A2 port.
or later is installed

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 63


Chapter 5 Connect to the Controller

Notes:

64 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6
Start to Use the Controller
Create a Logix Designer Out-of-the-box, the controller does not contain a Studio 5000 Logix Designer® application
project. To create a Logix Designer application project, complete these steps.
Application Project
1. Start the application. The Logix Designer application is part of the Studio 5000®
Applies to these controllers: environment.
CompactLogix™ 5380
Compact GuardLogix® 5380 SIL 2
Compact GuardLogix 5380 SIL 3

2. Click New Project.

3. On the New Project dialog box, complete these steps:


a. Select the controller.
b. Name the project.
c. Browse to the location where the project file is created.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 65


Chapter 6 Start to Use the Controller

d. Click Next.

4. Select the following:


• Revision
• Security Authority (optional)
• Secure With (only available if Security Authority is used)
For information on security, refer to the Logix 5000™ Controllers Security Programming
Manual, publication 1756-PM016.

5. Click Finish.

66 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6 Start to Use the Controller

Additional Configuration for Compact GuardLogix 5380 controllers require additional configuration after you create the
project. These topics describe how to configure the additional parameters.
a Compact GuardLogix
Controller Topic Page
Assign the Safety Network Number (SNN) 67
Applies to these controllers: Go Online with the Controller 72
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 For a Compact GuardLogix controller, the Logix Designer application creates a safety task and
a safety program. A main Ladder Diagram safety routine that is called MainRoutine is also
created within the safety program.

A red bar under the icon distinguishes safety programs and routines from standard project
components in the Controller Organizer.

Assign the Safety Network Number (SNN)


When you create controller projects, the Studio 5000 Logix Designer application generates an
SNN value automatically whenever it recognizes a new subnet that contains CIP Safety™
devices:
• Each CIP Safety-capable port on the controller is assigned an SNN. The Compact
GuardLogix 5380 controllers have up to three safety network numbers: a separate SNN
for each Ethernet port, and one SNN for the backplane.
• If a bridge or adapter device is in the I/O tree and a child CIP Safety device is added, the
subnet that is created by the bridge or adapter is assigned an SNN.

For typical users, the automatic assignment of a time-based SNN is sufficient. However,
manual assignment of the SNN is required if the following is true:
• One or more controller ports are on a CIP Safety subnet that already has an established
SNN.
• A safety project is copied to another hardware installation within the same routable CIP
Safety system.

Rockwell Automation recommends changing each SNN to the SNN already established for that
subnet, if one exists. That way, devices created later in the project are automatically assigned
the correct SNN.
For information regarding whether the controller or Ethernet ports are being added to existing
subnets, see the GuardLogix 5580 and Compact GuardLogix 5380 Controller Systems Safety
Reference Manual, publication 1756-RM012.

Each safety network must have a unique safety network number. You must be sure that a
unique SNN is assigned to each CIP Safety network that contains safety devices.
Multiple safety network numbers can be assigned to a CIP Safety subnet or a
ControlBus™ chassis that contains multiple safety devices. However, for
simplicity, we recommend that each CIP Safety subnet has only one unique SNN.
For an explanation on the Safety Network Number, see the GuardLogix 5580 and Compact
GuardLogix 5380 Controller Systems Safety Reference Manual, publication 1756-RM012.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 67


Chapter 6 Start to Use the Controller

The SNN can be software-assigned (time-based) or user-assigned (manual). These two


formats of the SNN are described in the following sections:
• Automatic Assignment of Time-based SSN
• Manual Assignment of SSN
Automatic Assignment of Time-based SSN

When a new controller or device is created, a time-based SNN is automatically assigned.


• Devices that are created directly under the controller port default to having the same
SNN as that port on the controller.
• For devices not directly under a controller port, subsequent new safety device additions
to the same CIP Safety network are assigned the same SNN defined within the lowest
address on that CIP Safety network.

The time-based format sets the SNN value as the date and time when the number was
generated, according to the computer running the configuration software.
Figure 20 - Time-based Format

Manual Assignment of SSN

Manual assignment is useful if you lay out your network and put the SNNs on your network
diagram. It may be easier to read SNNs from a diagram than it is to copy and paste them from
multiple projects.

Manual assignment of the SNN is required if the following is true:


• One or more controller ports are on a CIP Safety subnet that already has an established
SNN.
• A safety project is copied to another hardware installation within the same routable CIP
Safety system.

68 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6 Start to Use the Controller

IMPORTANT If you assign an SNN automatically or manually, make sure that system
expansion does not result in a duplication of SNN and unique node
reference combinations.
A warning appears if your project contains duplicate SNN and unique
node reference combinations. You can still verify the project, but
Rockwell Automation recommends that you resolve the duplicate
combinations.
However, there can be safety devices on the routable safety network
that have the same SNN and node address and are not in the project. In
this case, these safety devices are unknown to the Logix Designer
application, and you will not see a warning.
If two different devices have the same node references, the safety
system cannot detect a packet received by one device that was intended
for the other device.
If there are duplicate unique node references, as the system user, you
are responsible for proving that an unsafe condition cannot result.

Follow these steps to change the controller SNNs to a manual assignment:


1. On the Online toolbar, click the Controller Properties icon.
2. On the Controller Properties dialog box, click the Safety tab.
3. On the Safety tab, click to the right of the safety network number for the port that
you want to change.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 69


Chapter 6 Start to Use the Controller

4. On the Safety Network Number dialog box, select Manual.


5. Enter the SNN as a value from 1…9999 (decimal).

6. Click OK.

Copy and Paste a Safety Controller Safety Network Number


If you must apply a Safety Network Number (SNN) to other safety controllers, you can copy and
paste the SNN.
Copy a Safety Controller SNN
1. On the Online toolbar, click the Controller Properties icon .
2. On the Controller Properties dialog box, click the Safety tab.
3. On the Safety tab, click to the right of the safety network number.

70 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6 Start to Use the Controller

4. On the Safety Network Number dialog box, either click Copy and then OK.

5. On the Controller Properties dialog box, click OK.


Paste a Safety Controller SNN
1. On the Online toolbar, click the Controller Properties icon .
2. On the Controller Properties dialog, click the Safety tab.
3. On the Safety tab, click to the right of the safety network number.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 71


Chapter 6 Start to Use the Controller

4. On the Safety Network Number dialog box, click Paste and then click OK.

5. On the Controller Properties dialog box, click OK.

Go Online with the Controller To go online with the controller, you must first specify a communication path in the Logix
Designer application.
Applies to these controllers:
CompactLogix 5380 For this section, the USB port was chosen as the communication path. Another
Compact GuardLogix 5380 SIL 2 path through the embedded Ethernet ports is also possible.
Compact GuardLogix 5380 SIL 3
Use RSWho
1. Open or create a Logix Designer application project.
2. In the application, click RSWho.

3. Expand the communication path and select the controller.

4. If you want to store the path in the project file, click Set Project Path.
If you store the project path in the project, you do not have to choose the path each
time you go online.
5. After you choose the communication path, click Go Online in the Who Active dialog box.

72 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6 Start to Use the Controller

Go Online uses the highlighted node in the Who Active tree, regardless of the setting for Path in
Project. For more information on the Who Active dialog box, see the Logix Designer Online
Help.
See Additional Considerations for Going Online with a Controller on page 75.

Use a Recent Communications Path


You can also select a recent communications path and go online or apply it to your project.
1. Click the Recent Communication Path button next to the Path bar.

2. On the Select Recent Communications Path dialog box, choose the path.

3. To store the path in your project, click Set Project Path.


4. Click Go Online.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 73


Chapter 6 Start to Use the Controller

For more information on the Select Recent Communications Path dialog box, see the Logix
Designer Online Help.

Once you have established a communication path, then you can choose Go Online from the
Controller Status menu when you are working in the project.

See Additional Considerations for Going Online with a Controller on page 75.

74 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6 Start to Use the Controller

Additional Considerations The Logix Designer application determines whether you can go online with a target controller
based on whether the offline project is new, or whether changes occurred in the offline
for Going Online with a project.
Controller • If the project is new, you must first download the project to the controller.
Applies to these controllers: • If changes occurred to the project, you are prompted to upload or download.
CompactLogix 5380 • If no changes occurred, you can go online to monitor the execution of the project.
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3
For information on uploading a project, downloading a project, and the upload and
download dialog boxes, see the Logix Designer Online Help.
A number of factors affect these processes, including the Match Project to Controller feature
and the Firmware Revision Match feature.

For Compact GuardLogix controllers, additional considerations include the safety status and
faults, the existence of a safety signature, and the safety-lock/-unlock status of the project
and the controller. See Additional Considerations for Going Online with a Compact GuardLogix
Controller on page 76.

Match Project to Controller


The Match Project to Controller feature affects the download, upload, and go online processes
of standard and safety projects. This feature is on the Advanced tab of the controller
properties.
Figure 21 - Match Project to Controller

If the Match Project to Controller feature is enabled in the offline project, the Logix Designer
application compares the serial number of the controller in the offline project to that of the
connected controller. If they do not match, you must cancel the download/upload, connect to
the correct controller, or confirm that you are connected to the correct controller that updates
the serial number in the project to match the target controller.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 75


Chapter 6 Start to Use the Controller

Firmware Revision Matching


Firmware revision matching affects the download process. If the revision of the controller
does not match the revision of the project, you are prompted to update the firmware of the
controller. The Logix Designer application lets you update the firmware as part of the
download sequence.

IMPORTANT To update the firmware of the controller, first install a firmware


update kit. An update kit ships on a supplemental DVD along with the
Studio 5000® environment.
You can also upgrade the firmware by choosing ControlFLASH™ from the Tools
menu in the Logix Designer application.

Additional Considerations You can upload program logic and go online regardless of safety status. Safety status and
faults only affect the download process.
for Going Online with a
Compact GuardLogix You can view the safety status via the Safety tab on the Controller Properties dialog box.
Controller Safety Signature and Safety-locked and -unlocked Status
Applies to these controllers:
Compact GuardLogix 5380 SIL 2 The existence of a safety signature and the safety-locked or -unlocked status of the controller
Compact GuardLogix 5380 SIL 3 affect both the upload and download processes.
The safety signature and the safety lock status are uploaded with the project. For example, if
the project in the controller was safety-unlocked, the offline project remains safety-unlocked
following the upload, even if it was locked before the upload.

Following an upload, the safety signature in the offline project matches the controller safety
signature.

The safety lock status always uploads with the project, even when there is no safety signature.
The existence of a safety signature, and the controller safety-lock status, determines if a
download can proceed.
Table 5 - Effect of Safety-lock and Safety Signature on Download Operation
Safety-lock Status Safety Signature Status Download Functionality
Safety signature in the offline project The entire application downloads. Safety lock status matches the status in the offline project.
matches the safety signature in the The safety signature does not change.
Controller safety-unlocked controller.
If the controller had a safety signature, it is automatically deleted, and the entire project is
Safety signatures do not match. downloaded. Safety lock status matches the status in the offline project.
If the offline project and the controller are safety-locked, all standard project components are
downloaded.
Safety signatures match. If the offline project is not safety-locked, but the controller is, the download is blocked and you
Controller safety-locked must first unlock the controller to allow the download to proceed.
You must first safety-unlock the controller to allow the download to proceed. If the controller
Safety signatures do not match. had a safety signature, it is automatically deleted, and the entire project is downloaded. Safety
lock status matches the status in the offline project.

76 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6 Start to Use the Controller

Checks for Going Online with a GuardLogix Controller


For a safety project, the Logix Designer application checks for the following:
• Do the offline project and controller serial numbers match (if Project to Controller Match
is selected)?
• Does the offline project contain changes that are not in the controller project?
• Do the revisions of the offline project and controller firmware match?
• Are either the offline project or the controller safety-locked?
• Do the offline project and the controller have compatible safety signatures?
Table 6 - Connect to the Controller with a Safety Project
If the Software Indicates Then
Connect to the correct controller, select another project file, or choose the Update
Unable to connect to controller. Mismatch between the offline project and the project serial number checkbox and choose Go Online… to connect to the controller and
controller serial number. Selected controller can be the wrong controller. update the offline project serial number to match the controller.
Choose one of the following options:
Choose Update Firmware. Choose the required revision and click Update. Click Yes to
Unable to connect to controller. The revision of the offline project and the confirm your selection.
controller firmware are not compatible. IMPORTANT: The online project is deleted.
To preserve the online project, cancel the online process and install a version of the
Studio 5000 environment that is compatible with the firmware revision of your controller.
Choose one of the following options:
Upload to update the offline project.
You must upload or download to go online by using the open project. Download to update the controller project.
Choose File to select another offline project.
To preserve the safety signature when the firmware minor revision is incompatible,
update the firmware revision in the controller to exactly match the offline project. Then
Unable to connect in a manner that preserves safety signature. The firmware go online to the controller.
minor revision on the controller is not compatible with safety signature in To proceed with the download despite the safety signature incompatibility, click
offline project. Download. The safety signature is deleted.
IMPORTANT: The safety system requires revalidation.
Unable to connect to controller. Incompatible safety signature cannot be Cancel the online process. You must safety-unlock the offline project before attempting
deleted while project is safety-locked. to go online.

When the controller and the Logix Designer application are online, the safety-locked status
and safety signature of the controller match the controller project. The safety-lock status and
safety signature of the offline project are overwritten by the controller. If you do not want the
changes to the offline project to be permanent, do not save the project file following the go
online process.

Download to the Controller When you download a project to the controller, it copies the project from the Logix Designer
application onto the controller. You can download a project in two ways:
Applies to these controllers:
• Use Who Active on page 78
CompactLogix 5380
Compact GuardLogix 5380 SIL 2
• Use the Controller Status Menu on page 78
Compact GuardLogix 5380 SIL 3

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 77


Chapter 6 Start to Use the Controller

Use Who Active


You can use the features of the Who Active dialog box to download to the controller after you
have set the communication path. Complete these steps to download to the controller.
1. After choosing the communication path, click Download in the Who Active dialog box.

2. After reading the warnings in the Download dialog box, click Download.

Use the Controller Status Menu


After you choose a communication path in the Logix Designer application, you can use the
Controller Status menu to download to the controller. To download, from the Controller Status
menu, choose Download.
Figure 22 - Download Via the Controller Status Menu

After the download completes, the project name appears on the scrolling status
display.

78 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6 Start to Use the Controller

Additional Considerations For a safety project, the Logix Designer application compares the following information in the
offline project and the controller:
for Download to a Compact
• Controller serial number (if project to controller match is selected)
GuardLogix Controller • Firmware major and minor revisions
Applies to these controllers: • Safety status
Compact GuardLogix 5380 SIL 2 • Safety signature (if one exists)
Compact GuardLogix 5380 SIL 3
• Safety-lock status

After the checks pass, a download confirmation dialog box appears. Click Download.

The Logix Designer application displays status messages in the download dialog, progress
screen, and the Errors window.
If the Software Indicates: Then:
Unable to download to the controller. Mismatch between the offline Connect to the correct controller or verify that this is the correct controller. If it is the correct
project and the controller serial number. Selected controller can be the controller, check the Update project serial number checkbox to allow the download to proceed.
wrong controller. The project serial number is modified to match the controller serial number.
Unable to download to the controller. The major revision of the offline Choose Update Firmware. Choose the required revision and click Update. Click Yes to confirm
project and the controller firmware are not compatible. your selection.
Unable to download to controller. The internal safety partner hardware Replace the Compact GuardLogix SIL 3 controller.
has failed.
Unable to download to the controller. Safety partnership has not been Cancel the download process and attempt a new download to the Compact GuardLogix SIL 3
established. controller.
Unable to download to controller. Incompatible safety signature cannot Cancel the download. To download the project, you must safety-unlock the offline project, delete
the safety signature, and download the project.
be deleted while the project is safety-locked. IMPORTANT: The safety system requires revalidation.
If the firmware minor revision is incompatible, to preserve the safety signature, update the
firmware revision in the controller to exactly match the offline project. Then download the offline
Cannot download in a manner that preserves the safety signature. project.
Controller firmware minor revision is not compatible with safety To proceed with the download despite the safety signature incompatibility, click Download. The
signature in offline project. safety signature is deleted.
IMPORTANT: The safety system requires revalidation.
Choose Unlock. The Safety Unlock for Download dialog box appears. If the Delete Signature
Unable to download to controller. Controller is locked. Controller and checkbox is selected and you choose Unlock, click Yes to confirm the deletion.
offline project safety signatures do not match. IMPORTANT: The safety system requires revalidation.
Downloading safety signature... The safety signature is present in the offline project and is downloading.

Following a successful download, the safety-locked status and safety signature of the
controller match the project that was downloaded.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 79


Chapter 6 Start to Use the Controller

Upload from the Controller When you upload a project from the controller, it copies the project from the controller to the
Logix Designer application. To upload a project, use one of these methods:
Applies to these controllers:
• Use Who Active on page 80
CompactLogix 5380
Compact GuardLogix 5380 SIL 2
• Use the Controller Status Menu on page 81
Compact GuardLogix 5380 SIL 3
Use Who Active
You can use the features of the Who Active dialog box to upload from your controller after you
have set the communication path. Complete these steps to upload from the controller.
1. In the Logix Designer application project, click RSWho.

2. Expand the communication path and select the controller.


3. Click Upload on the Who Active dialog box.

4. On the Connected to Upload dialog box, verify that the project is the one you want to
upload and click Upload.
5. Click Upload.

80 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6 Start to Use the Controller

For more information on the Connected To upload dialog box, see the Logix Designer Online
Help.

Use the Controller Status Menu


After you have chosen a communication path in the Logix Designer application, you can use
the Controller Status menu to upload from the controller.
1. From the Controller Status pull-down menu, choose Upload.

2. On the Connected to Upload dialog box, verify the project to upload.


3. Click Upload.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 81


Chapter 6 Start to Use the Controller

Additional Considerations For a safety project, the Logix Designer application compares the following information in the
project and the controller:
for Upload to a Compact
• Controller serial number (if project to controller match is selected)
GuardLogix Controller • Open project to the controller project
Applies to these controllers: • Firmware major and minor revisions
Compact GuardLogix 5380 SIL 2 • Safety signature (if one exists)
Compact GuardLogix 5380 SIL 3
IMPORTANT An upload is allowed regardless of the Safety status and the Safety
Locked state of the offline project and controller. The locked status
follows the state of the uploaded project.

Table 7 - Upload Behavior


Upload Behavior Response
• Connect to the correct controller or verify that this is the correct controller.
• Select a new project to upload into or select another project by choosing Select
If the project to controller match is enabled, the Logix Designer application checks File.
whether the serial number of the open project and the serial number of the
controller match. • If it is the correct controller, select the Update project serial number checkbox to
allow the download to proceed. The project serial number is modified to match the
controller serial number.
• If the projects do not match, you must select a matching file or cancel the upload
The Logix Designer application checks whether the open project matches the process.
controller project. • If the projects match, the software checks for changes in the offline (open)
project.
• If there are no changes in the offline project, you can go online without uploading.
Click Go Online.
The Logix Designer application checks for changes in the offline project.
• If there are changes in the open project that are not present in the controller, you
can choose to upload the project, cancel the upload, or select another file.
This message appears during the upload only if a safety signature matching the one
Uploading safety signature... in the controller does not exist in the offline project.

If you choose Upload, the standard and safety applications are uploaded. If a safety signature
exists, it is also uploaded. The safety-lock status of the project reflects the original status of
the online (controller) project.

Before the upload, if an offline safety signature exists, or the offline project is
safety-locked but the controller is safety-unlocked or has no safety signature, the
offline safety signature and safety-locked state are replaced by the online values
(safety-unlocked with no safety signature). If you do not want to make these
changes permanent, do not save the offline project following the upload.

82 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6 Start to Use the Controller

Choose the Controller Use this table as a reference when determining your controller operation mode.
Operation Mode
Applies to these controllers:
CompactLogix 5380
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3

Mode Switch
Available Controller Modes In This Mode You Can: In This Mode You Cannot: ATTENTION:
Position(1)
• Turn outputs to the state commanded by • Turn outputs to their configured
Run mode—The controller is actively the logic of the project. state for Program mode
controlling the process/machine. • Execute (scan) tasks • Change the mode of the controller
RUN Projects cannot be edited in the Logix • Send messages via the Logix Designer application Run mode is used only when
all conditions are safe.
Designer application when in Run • Send and receive data in response to a • Download a project
mode. message from another controller • Schedule a ControlNet® network
• Produce and consume tags • While online, edit the project
• Turn outputs to the state commanded by
the logic of the project.
• Execute (scan) tasks You are able to modify a
Remote Run mode—This mode is • Change the mode of the controller via the • Turn outputs to their configured project file online in Remote
identical to Run mode except you can Logix Designer application state for Program mode Run mode.
edit the project online, and change the • While online, edit the project • Download a project Be sure to control outputs
controller mode through the Logix with care to avoid injury to
Designer application. • Send messages • Schedule a ControlNet network personnel and damage to
• Send and receive data in response to a equipment.
message from another controller
• Produce and consume tags
• Turn outputs to their configured state for
Program mode
• Change the mode of the controller via the
Remote Program mode—This mode Logix Designer application • Turn outputs to the state
functions like Program mode, except • Download a project commanded by the logic of the
REM you can change the controller mode • Schedule a ControlNet network project.
through the Logix Designer
application. • While online, edit the project • Execute (scan) tasks
• Send and receive data in response to a
message from another controller Outputs are commanded to
• Produce and consume tags their Program mode state,
• Turn outputs to their configured state for which can cause a dangerous
Remote Test mode—This controller Program mode situation.
mode executes code, but I/O is not • Execute (scan) tasks • Turn outputs to the state
controlled. You can edit the project • Change the mode of the controller via the commanded by the logic of the
online, and change the controller Logix Designer application project.
mode through the Logix Designer • Download a project
• While online, edit the project
application.
Output modules are commanded to • Send messages • Schedule a ControlNet network
their Program mode state (on, off, or • Send and receive data in response to a • Send messages
hold). message from another controller
• Produce and consume tags
Program mode—This controller mode • Turn outputs to their configured state for Do not use Program mode as
does not execute code or control I/O, Program mode • Turn outputs to the state
commanded by the logic of the an emergency stop (E-stop).
but editing operations are available. • Download a project Program mode is not a safety
Output modules are commanded to project.
• Schedule a ControlNet network device.
PROG their Program mode state (On, Off, or • Execute (scan) tasks
• While online, edit the project Outputs are commanded to
Hold). • Change the mode of the controller their Program mode state,
In this position, controller modes • Send and receive data in response to a via the Logix Designer application
message from another controller which can cause a dangerous
cannot be changed through the Logix • Send messages situation.
Designer application. • Produce and consume tags
(1) Moving the mode switch from Run to Remote leaves the controller in the Remote Run mode, while moving the switch from Program to Remote leaves the controller in the Remote Program
mode. You cannot choose Remote Test mode by the mode switch alone, it is only available via the Logix Designer application.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 83


Chapter 6 Start to Use the Controller

Use the Mode Switch to Change the Operation Mode


To change the operating mode, use the controller mode switch. The controller mode switch
provides a mechanical means to enhance controller and control system security. You must
physically move the mode switch on the controller to change its operating mode from RUN, to
REM, or to PROG.
When the mode switch on the controller is set to RUN mode, features like online editing,
program downloads, and firmware updates are prohibited. See Choose the Controller
Operation Mode on page 83 for a list of prohibited features.

The mode switch can complement other authorization and authentication methods that
similarly control user-access to the controller, such as the FactoryTalk® Security service.

IMPORTANT During runtime, we recommend that you place the controller mode
switch in RUN mode. This can help discourage unauthorized access to
the controller or potential tampering with the program of the controller,
configuration, or device firmware.
Place the mode switch in REM or PROG mode during controller
commissioning and maintenance and whenever temporary access is
necessary to change the program, configuration, or firmware of the
product.

The mode switch on the front of the controller can be used to change the controller to one of
these modes:
• Run (RUN)
• Remote (REM)
• Program (PROG)

Mode Switch Mode Switch on both


Compact GuardLogix SIL 2
and SIL 3 controllers.

84 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6 Start to Use the Controller

Use the Logix Designer Application to Change the Operation Mode


When you are online with the controller, and the controller mode switch is set to Remote (REM,
the center position), then you can use Logix Designer to change the operation mode.

The Controller Status menu in the upper-left corner of the application window lets you specify
these operation modes:
• Remote Program
• Remote Run
• Remote Test
1. From the Controller Status pull-down menu, choose the operation mode.

For this example, the controller mode switch is set to Remote mode. If the
controller mode switch is set to Run or Program modes, the menu options change.

Change Controller After the project is created, you can change some configuration parameters on the Controller
Properties dialog box while the controller is offline. Examples of configurable parameter that
Configuration you can change offline include the following:
Applies to these controllers: • EtherNet/IP™ Mode on the General tab
CompactLogix 5380 • Enable Time Synchronization on the Date/Time tab
Compact GuardLogix 5380 SIL 2 • Execution Control on the SFC Execution tab
Compact GuardLogix 5380 SIL 3
To change the controller configuration while the project is offline, complete these steps.
1. On the Online toolbar, click the Controller Properties button.

2. On the Controller Properties dialog box, click the General tab.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 85


Chapter 6 Start to Use the Controller

Reset Button You can reset the CompactLogix and Compact GuardLogix controllers with the reset button.
The reset button is only read during a power-up or restart. If you press the reset button at
another time, it has no effect.

For a Compact GuardLogix controller, the Safety Locked status or safety signature does not
prevent you from performing a controller reset. Because the application is cleared from the
controller during a reset, the safety level of the controller is cleared also. When you download a
safety project to the controller, the safety level is set to the level specified in the project.

For a Compact GuardLogix SIL 3 controller, the reset button resets both the primary safety
controller and the safety partner.

A controller has two stages of reset:


• A Stage 1 reset clears the application program and memory, but retains the IP address,
all network settings, and firmware revision. A stage 1 reset occurs only if the controller
contains a user application. See Stage 1 Reset on page 87.
• A Stage 2 reset returns the controller to out-of box settings (including firmware), and
clears all network settings. A stage 2 reset occurs only if the controller does not contain
a user application, and the current controller firmware is not a 1.x version. See Stage 2
Reset on page 88.

IMPORTANT Because port enable/disable status is associated with the application


program, the Ethernet port becomes enabled after a Stage 1 or Stage 2
reset.

WARNING: When you press the reset button while power is on, an Electric Arc
can occur. This could cause an explosion in hazardous location installations.
Be sure that power is removed or the area is nonhazardous before proceeding.

Reset Button on both


Reset Button Compact GuardLogix SIL 2
and SIL 3 controllers.

86 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6 Start to Use the Controller

Stage 1 Reset

IMPORTANT A stage 1 reset occurs only if the controller contains a user application.

The stage 1 reset completes the following:


• Clears the application program.
• Retains the network settings for the embedded Ethernet port.
• Retains APR (motion position info) information.
• Retains all PTP configuration (Time Synchronization) parameters.
• Retains Wall Clock Time within the energy retention capability of the module.
• Creates a timestamped entry in the Controller Log that a Stage 1 Reset event has
occurred.
• Resets the controller to begin the controller start up process.
• Prevents the controller from loading firmware or software from the SD card on this first
start up after the reset, regardless of the setting on the SD card, and without modifying
the SD card contents (the write-protect setting is irrelevant). An SD card reloads (if
configured to do so) on subsequent powerup situations.
• Enables the Ethernet port, if it was previously disabled.

To perform a Stage 1 reset, complete these steps. This process assumes that an SD card is
installed in the controller.
1. Power down the controller.
2. Open the front door on the controller.
3. To press and hold the reset button, use a small tool with a diameter of a paper clip.
4. While holding in the reset button, power up the controller.
5. Continue to hold the reset button while the 4-character display cycles through CLR, 4, 3,
2, 1, Project Cleared.
6. After Project Cleared appears, release the reset button.

IMPORTANT If you release the reset button before Project Cleared scrolls
across the display, the controller continues with powerup and
does not reset.
After a Stage 1 reset is performed, load a Logix Designer application project to the controller in
these ways:
• Download the project from the Logix Designer application - For more information, see
Download to the Controller on page 77
• Cycle power on the controller to load a project from the SD card.
This option works only if the project stored on the SD card is configured to load the
project on powerup.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 87


Chapter 6 Start to Use the Controller

Stage 2 Reset

IMPORTANT A stage 2 reset occurs only if the controller does not contain a user
application, and the current controller firmware is not a 1.x revision.

The stage 2 reset completes the following:


• Returns the module to revision 1.x firmware, that is, the out-of-box firmware revision.
• Clears all user settings, including network and time synchronization settings.
If the controller uses firmware revision 29.011 or later, the EtherNet/IP mode is reset to
Dual-IP mode, that is, the default mode.
• Resets the controller to begin the controller start up process.
• There are no entries in the controller log after a Stage 2 reset, but saved logs on the SD
card remain.

To perform a Stage 2 reset, complete these steps. This process assumes that an SD card is
installed in the controller.
1. Power down the controller.
2. Open the front door on the controller.
3. Remove the SD card.
4. To press and hold the reset button, use a small tool with a diameter of a paper clip.
5. While holding in the reset button, power up the controller.
6. Continue to hold the reset button while the 4-character display cycles through DFLT, 4,
3, 2, 1, Factory Default
7. After Factory Default appears, release the reset button.
8. On your workstation, delete the files on the SD card.
9. Power down the controller.
10. Reinstall the SD card.
11. Powerup the controller.
12. Verify that the controller is at firmware revision 1.x, and the controller is set to DHCP-
enabled.

After a Stage 2 reset is performed, you must complete these tasks to use the controller again:
• Configure the Ethernet ports, set the desired EtherNet/IP mode, and set the controller IP
address configuration.
For more information, see Set the IP Address on page 51.
• Update the firmware revision—For more information, see Update Controller Firmware
on page 54.
• Download a Logix Designer application project to the controller in one of these ways:
- Download the project from the Logix Designer application - For more information,
see Download to the Controller on page 77.
- Cycle power on the controller to load a project from the SD card.
This option works only if the project stored on the SD card is configured to load the
project on powerup.

88 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 6 Start to Use the Controller

Notes:

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 89


Chapter 6 Start to Use the Controller

90 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 7
Use the Secure Digital Card
The controllers ship with an SD card installed. We recommend that you leave the SD card
Applies to these controllers:
installed, so if a fault occurs, diagnostic data is automatically written to the card. Rockwell
Automation can then use the data to help investigate the cause of the fault.
CompactLogix™ 5380
Compact GuardLogix® 5380 SIL 2 We recommend that you use the SD cards available from Rockwell Automation:
Compact GuardLogix 5380 SIL 3 • 1784-SD2 card—2 GB card that ships with the controller
• 1784-SD1 card—1 GB card
• 1784-SDHC8—8 GB card
• 1785-SDHC32—32 GB card
• CodeMeter CmCard SD, 4 GB, catalog number 9509-CMSDCD4 (when license-based
source protection and execution protection features are enabled)

While other SD cards can be used with the controller, Rockwell Automation has not tested the
use of those cards with the controller and you could experience data corruption or loss. SD
cards that are not provided by Rockwell Automation can have different industrial,
environmental, and certification ratings as those cards that are available from Rockwell
Automation. These cards can have difficulty with survival in the same industrial environments
as the industrially rated versions available from Rockwell Automation.

The memory card that is compatible with your controller is used to load or store the contents
of user memory for the controller. When you use the Store feature, the project that is stored on
the SD card matches the project in the controller memory at that time. Changes that you make
after you store the project are not reflected in the project on the SD card.

If you make changes to the project in the controller memory without storing them, the next
time that you load the project from the SD card to the controller, you overwrite the changes.

IMPORTANT Do not remove the SD card while the controller is reading from, or writing to, the card. If you remove the card during
either activity, the data on the card or controller can become corrupt.
The controller firmware at the time when the card is removed can become corrupted. Leave the card in the controller
until the OK status indicator turns solid green.

If an SD card is installed, its content appears on the Nonvolatile Memory tab of the Controller
Properties dialog box. If a safety application is stored on the card, the safety-lock status and
the safety signature are shown. The project must be online to see the content of the SD card.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 91


Chapter 7 Use the Secure Digital Card

Figure 23 - Nonvolatile Memory Tab

92 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 7 Use the Secure Digital Card

Remember the following:


• An SD card slot is on the front of the controller behind the door.

SD Card Slot SD Card Slot

SD Card Slot

• If the card is installed and a fault occurs, diagnostic data is automatically written to the
card. Diagnostic data helps the investigation and correction of the fault cause.
• The controller detects the presence of an SD card at power-up or if a card is inserted
during controller operation.
• The SD card can store all configuration data that is stored in nonvolatile memory, for
example, the controller IP address.
• The SD card can store the back-up program.

IMPORTANT Rockwell Automation recommends that you back up your Studio 5000
Logix Designer® program to an SD card regularly.
If a major non-recoverable fault occurs that removes the program from
the controller memory, the backup copy on the SD card can be
automatically restored to the controller and quickly resume normal
controller operation.

For detailed information on how to use nonvolatile memory, refer to the Logix 5000 Controllers
Nonvolatile Memory Programming Manual, publication 1756-PM017.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 93


Chapter 7 Use the Secure Digital Card

Considerations for Storing Only Compact GuardLogix 5380 controllers support safety projects. CompactLogix 5380
controllers do not support safety projects.
and Loading a Safety Project
Applies to these controllers: You cannot store a safety project if the safety status is Safety Task Inoperable. When you store
a safety project, the controller firmware is also stored to the SD card.
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 For a Compact GuardLogix 5380 SIL 3 controller, if no application exists in the controller but a
valid safety partnership exists, you can save only the firmware of the internal safety partner.

If a safety signature exists when you store a project, the following occurs:
• Both safety and standard tags are stored with their current values.
• The current safety signature is saved.

When you store a safety application project on an SD card, Rockwell Automation recommends
that you select Program (Remote Only) as the Load mode, that is, the mode that the controller
enters after a project is loaded from the SD card.

IMPORTANT To help prevent the firmware that is stored on the SD card from
overwriting newly updated firmware:
• The update process first checks the load option on the SD card, and
changes the load option to User Initiated if necessary.
• The firmware update proceeds.
• The controller resets.
• The load option remains set to User Initiated.
If the SD card is locked, the load option does not change, and the
firmware that is stored on the SD card can overwrite the newly updated
firmware.

Store to the SD Card We recommend that you back up your Studio 5000 Logix Designer® application to an SD card
regularly.
Applies to these controllers:
CompactLogix 5380 If a major non-recoverable fault occurs that removes the program from the controller memory,
Compact GuardLogix 5380 SIL 2 the backup copy on the SD card can be automatically restored to the controller to quickly
Compact GuardLogix 5380 SIL 3 resume normal controller operation.

To store a project to the SD card, complete these steps.


1. Make sure that the controller is online and in Program mode or Remote Program mode.
2. From the Controller Status pull-down menu, click Controller Properties.

94 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 7 Use the Secure Digital Card

3. On the Nonvolatile Memory tab, click Load/Store.

If Load/Store is dimmed (unavailable), verify the following:


• The controller is in Program mode or Remote Program mode
• You have specified the correct communication path.
• The SD card is installed.
• The SD card is unlocked. The locked status appears in the bottom-left
corner of the Nonvolatile memory/Load Store dialog box.
If the SD card is not installed, a message in the lower-left corner of the
Nonvolatile Memory tab indicates the missing card as shown here.

4. Change the Load Image properties according to your application requirements.

The following table describes the Load Image options.


Table 8 - Load Image Options
If You Want to Load the Then Select This Notes Safety Considerations
Project Load Image Option
• During a power cycle, you lose any online changes,
tag values, and network schedule that you have not
stored in the nonvolatile memory. • For a safety application, On Power Up loads whether or not the
controller is safety-locked or there is a safety signature.
Whenever you turn on or On Power Up • The controller loads the stored project and
cycle power firmware at every powerup regardless of the • If the application is configured to load from the SD card on
firmware or application project on the controller. power up, then the application in the controller is overwritten
even if the controller is safety locked.
• You can always use the Studio 5000 Logix Designer
application to load the project.
• If the project has been cleared from memory, this
option loads the project back into the controller on
power-up.
Whenever there is no • The controller updates the firmware on the
project in the controller On Uninitialized controller, if necessary. The application project • The controller also updates the firmware on the safety partner, if
and you turn on or cycle Memory that is stored in nonvolatile memory is also loaded necessary.
chassis power and the controller enters the selected mode, either
Program or Run.
• You can always use the Logix Designer application
to load the project.
• You can initiate a load, regardless of the safety status.
• You can load a project to a safety-locked controller only when
the safety signature of the project that is stored in nonvolatile
memory matches the project on the controller.
• If the signatures do not match or the controller is safety-locked
without a safety signature, you are prompted to first unlock the
• If the controller type and the major and minor controller.
Only through the Logix revisions of the project in nonvolatile memory • IMPORTANT: When you unlock the controller and initiate a load
User Initiated
Designer application match the controller type and major and minor from nonvolatile memory, the safety-lock status, passwords, and
revisions of the controller, you can initiate a load. safety signature are set to the values contained in nonvolatile
memory once the load is complete.
• If the firmware on the primary controller matches the revision in
nonvolatile memory, the safety partner firmware is updated, if
necessary, the application that is stored in nonvolatile memory
is loaded so that the safety status becomes Safety Task
Operable and the controller enters the Program mode.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 95


Chapter 7 Use the Secure Digital Card

IMPORTANT To help prevent the firmware that is stored on the SD card from overwriting newly updated firmware:
• The update process first checks the load option on the SD card, and changes the load option to User Initiated if necessary.
• The firmware update proceeds.
• The controller resets.
• The load option remains set to User Initiated.
If the SD card is locked, the load option does not change, and the firmware that is stored on the SD card can overwrite the
newly updated firmware.

5. Change the Load Mode properties according to your application requirements.


If You Want the Controller to Go to This Mode after Loading Then Choose Menu Items
Program Program (remote only)

Run Run (remote only)

IMPORTANT Safety Consideration


Rockwell Automation recommends that you use Program (Remote Only), when you set the Load Mode for a safety
application project.
6. According to your application requirements, set the Automatic Firmware Update
properties for I/O devices in the configuration tree of the controller. The Automatic
Firmware Update property is also referred to as the Firmware Supervisor feature.

IMPORTANT Safety Consideration


Some Safety I/O devices do not support the Firmware Supervisor feature. For example, Safety I/O devices on
DeviceNet® networks and POINT Guard I/O™ modules do not support the Firmware Supervisor feature.
The following table describes the Automatic Firmware Update options for I/O devices.
Setting Description Menu Items

Disables any automatic firmware updates. This item only appears in the menu when you
Disable initially save the image.

Enables automatic firmware updates for I/O devices in the configuration tree of the
Enable and Store Files controller. Saves I/O device firmware and controller firmware to the image.
to Image Only I/O devices that are configured for Exact Match Keying participate in the Automatic
Firmware Update process.(1)
Disables automatic firmware updates for I/O devices in the configuration tree of the
Disable and Delete controller. Removes I/O device firmware from the image, but does not remove controller
Files from Image firmware from image.This item only appears in the menu on subsequent saves of the image.
(1) The devices that are used with this option must support the revision of firmware being updated to.

7. Click Store.
8. Click Yes in the confirmation dialog box that appears.

96 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 7 Use the Secure Digital Card

If you enabled Automatic Firmware Update, a dialog box informs you which modules are
not included in the Automatic Firmware Update operation.

IMPORTANT Do not remove the SD card while the controller is reading from,
or writing to, the card. If you remove the card during either
activity, the data on the card or controller can become corrupt.
Additionally, the controller firmware at the time when the card is
removed can become corrupted. Leave the card in the controller
until the OK status indicator turns solid green.
9. On the Automatic Firmware Update dialog box, click Yes.
The project is saved to the SD card as indicated by the controller status indicators.
These Indications Show the Store Status
While the store is in progress, the following occurs:
• OK indicator is flashing green
• SD indicator is flashing green
• Saving…Do Not Remove SD Card is shown on the status display
• A dialog box in the Logix Designer application indicates that the store is in progress
• Controller Resets
• SAVE is shown on the status display
When the store is complete, the following occurs:
• The controller resets.

IMPORTANT Allow the store to complete without interruption. If you interrupt the
store, data corruption or loss can occur.

Load from the SD Card After you have set the communication path, are online with the controller, and have changed
the controller to Program mode, you can load a project to the controller from the memory card.
Applies to these controllers:
CompactLogix 5380 IMPORTANT With the SD card and brand new, out-of-box controllers:
Compact GuardLogix 5380 SIL 2 • If you insert an SD card with an image into a brand new, out-of-box
Compact GuardLogix 5380 SIL 3 controller (firmware 1.x), then at power-up the controller automatically
updates the firmware up to the version of firmware that is stored on the
SD card. The update happens regardless of the Load Image setting in the
image on the SD card (User Initiated, On Power Up, or On Uninitialized
Memory).
• If the image was created with either On Power Up or On Uninitialized
Memory settings, then the controller both updates the firmware and loads
in the controller application.
You can load from an SD card to a controller in one of these ways:
• Controller Power-up
• User-initiated Action

You can always use the Logix Designer application to load the project.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 97


Chapter 7 Use the Secure Digital Card

Controller Power-up
The following table shows what happens at power-up when the SD card in the controller
contains an image.
Controller Is in Out-of-box Condition Firmware > 1.xxx and Internal Nonvolatile Firmware > 1.xxx and Internal Nonvolatile
Image Setting (v1.xxx Firmware) Memory Is Not Valid(1) Memory Is Valid(1)
User Initiated Loads Firmware Only(2) Does Nothing Does Nothing

• Loads Firmware if there is a revision mismatch • mismatch


Loads Firmware if there is a revision
On Power Up Loads both Firmware and Application
• Loads Application • Loads Application
• Loads Firmware if there is a revision mismatch
On Uninitialized Memory Loads both Firmware and Application(1) • Loads Application
Does Nothing
(1) “Valid” includes the No Project condition.
(2) Indicates change in behavior from CompactLogix 5370 and older controllers.

User-initiated Action

IMPORTANT For an out-of-box controller that uses firmware revision 1.xx, you must
manually update the controller to the required firmware revision before
you can load a project on the controller.

You must complete the following before you can load a project to the controller from the SD
card when the controller is already powered-up:
• Make sure that the controller has a working firmware revision.
• Establish the communication path.
• Go online with the controller.
• Make sure that the controller is in Program mode.
To load a project to the controller from the SD card, complete these steps.
1. From the Controller Status pull-down menu, click Controller Properties.

98 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 7 Use the Secure Digital Card

2. On the Nonvolatile Memory tab, verify that the project that is listed is the correct one.

If no project is stored on the SD card, a message on the Nonvolatile Memory


tab indicates that an image (or project) is not available.

For information on how to change the project that is available to load from nonvolatile
memory, see the Logix 5000 Controllers Nonvolatile Memory Programming Manual,
publication 1756-PM017.
3. Click Load/Store.

If Load/Store is dimmed (unavailable), verify the following:


• You have specified the correct communication path and are online with the
controller.
• The SD card is installed.
Verify that the controller is not in Run Mode.
4. Click Load.

5. Click Yes in the confirmation dialog box that appears.

After you click Yes, the project is loaded to the controller as indicated by the controller
status indicators. A dialog box in the Logix Designer application also indicates that the
store is in progress.
Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 99
Chapter 7 Use the Secure Digital Card

Table 9 - Indications for Load Status


OK LED on
Controller SD Indicator 4-Character Display Message
Controller
CompactLogix 5380 controller when restoring firmware or project Flashing Green Solid Red “LOAD”, then followed by “UPDT”
Compact GuardLogix 5380 SIL 2 controller when restoring firmware or project Flashing Green Solid Red “LOAD”, then followed by “UPDT”
Compact GuardLogix 5380 SIL 3 controller during primary controller firmware update Flashing Green Solid Green “Updating Firmware…Do Not Remove SD Card”
Compact GuardLogix 5380 SIL 3 controller during Safety Partner firmware update Flashing Green Blinking Red “Updating Firmware…Do Not Remove SD Card”
Compact GuardLogix 5380 SIL 3 controller during when loading project Flashing Green Solid Green “Loading…Do Not Remove SD Card”

IMPORTANT Let the load to complete without interruption. If you interrupt the load,
data corruption or loss can occur.

When the load is complete, the controller reboots.

Other Secure Digital You can perform these tasks with the SD card:
Card Tasks • Change the image that is loaded from the card.
• Check for a load that was completed.
Applies to these controllers:
CompactLogix 5380
• Clear an image from the SD card.
Compact GuardLogix 5380 SIL 2 • Store an empty image.
Compact GuardLogix 5380 SIL 3 • Change load parameters.
• Read/write application data to the card.
• View safety-lock status and safety signatures on the Non-volatile Memory tab—
Compact GuardLogix 5380 controllers only.

For more information to complete any of these tasks, see the Logix 5000 Controllers Memory
Card Programming Manual, publication 1756-PM017.

100 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 7 Use the Secure Digital Card

Notes:

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 101


Chapter 7 Use the Secure Digital Card

102 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 8
EtherNet/IP Network
Overview CompactLogix™ 5380 and Compact GuardLogix® 5380 controllers operate on EtherNet/IP™
networks. Before your controller can operate on EtherNet/IP network, you must configure
Applies to these controllers: driver in RSLinx® Classic software. For information on how to configure EtherNet/IP or USB
CompactLogix 5380 drivers, see the EtherNet/IP Network Devices User Manual, publication ENET-UM006.
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 IMPORTANT Some example graphics in this chapter use CompactLogix 5380
controllers and some use Compact GuardLogix 5380 controllers.
The controller used is for example purposes only. Each example can use
either controller type. For example, the graphics shown in section Linear
Network Topology beginning on page 107 use Compact GuardLogix 5380
controllers. You can use CompactLogix 5380 controllers in the same
examples.
The EtherNet/IP network offers a full suite of control, configuration, and data collection
services by layering the Common Industrial Protocol (CIP™) over the standard Internet
protocols, such as TCP/IP and UDP. This combination of well-accepted standards provides the
capability that is required to support information data exchange and control applications.

The controllers use socket interface transactions and conventional communication over the
EtherNet/IP network to communicate with Ethernet devices that do not support the EtherNet/
IP application protocol.

EtherNet/IP Network The CompactLogix 5380 and Compact GuardLogix 5380 controllers support the following:
Functionality • Dual built-in EtherNet/IP network ports - Port A1 and port A2
• Support for these EtherNet/IP modes:
Applies to these controllers:
CompactLogix 5380
- Dual-IP mode - Available with the Logix Designer® application, version 29 or later
Compact GuardLogix 5380 SIL 2 - Linear/DLR mode
Compact GuardLogix 5380 SIL 3 • Support for these EtherNet/IP network topologies:
- Device Level Ring (DLR)
- Linear
- Star
• Support for these EtherNet/IP network communication rates:
- 10 Mbps
- 100 Mbps
- 1 Gbps
• Support for only full-duplex operation

IMPORTANT If a device supports only half-duplex, you must connect it to a


switch to communicate with a CompactLogix 5380 or
Compact GuardLogix 5380 controller.
• Support for CIP Sync™ technology that is based on Time Synchronization using the
IEEE-1588 Precision Time Protocol
• Duplicate IP address detection

For more information about network design, see the Ethernet Design Considerations
Reference Manual, publication ENET-RM002.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 103


Chapter 8 EtherNet/IP Network

Nodes on an EtherNet/IP When you configure your CompactLogix 5380 or Compact GuardLogix 5380 control system, you
must account for the number of EtherNet/IP nodes that you include in the I/O configuration
Network section of your project.
Applies to these controllers:
CompactLogix 5380
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3
Table 10 - CompactLogix 5380 and Compact GuardLogix 5380 Controller EtherNet/IP Nodes
Nodes Supported,
CompactLogix 5380 Controllers Compact GuardLogix 5380 Controllers
Max(1)
5069-L306ER, 5069-L306ERM 5069-L306ERS2, 5069-L306ERMS2, 5069-L306ERMS3 16
5069-L310ER, 5069-L310ER-NSE, 5069-L310ERM, 5069-L310ERS2, 5069-L310ERS2K, 5069-L310ERMS2, 5069-L310ERMS2K, 24
5069-L310ERMK 5069-L310ERMS3, 5069-L310ERMS3K
L320ERS2, 5069-L320ERS2K, 5069-L320ERMS2, 5069-L320ERMS2K,
5069-L320ER, 5069-L320ERM, 5069-L320ERP 40
5069-L320ERMS3, 5069-L320ERMS3K
5069-L330ERS2, 5069-L330ERS2K, 5069-L330ERMS2, 5069-L330ERMS2K,
5069-L330ER, 5069-L330ERM 60
5069-L330ERMS3, 5069-L330ERMS3K
5069-L340ER, 5069-L340ERM, 5069-L340ERP 5069-L340ERS2, 5069-L340ERMS2, 5069-L340ERMS3 90
5069-L350ERS2, 5069-L350ERS2K, 5069-L350ERMS2, 5069-L350ERMS2K
5069-L350ERM 120
5069-L350ERMS3, 5069-L350ERMS3K
5069-L380ERM 5069-L380ERS2, 5069-L380ERMS2, 5069-L380ERMS3 150
5069-L3100ERM 5069-L3100ERS2, 5069-L3100ERMS2, 5069-L3100ERMS3 180
(1) With controller firmware revision 31 or later. Earlier firmware revisions can have lower node counts.

Devices Included in the Node Count


Any EtherNet/IP devices that you add to the I/O configuration section are counted toward the
controller node limit. The following are examples of devices that must be counted:
• Remote communication adapters
• Switches that are included in the I/O configuration section
• Devices with an embedded Ethernet port, such as drives, I/O modules, and linking
devices
• Remote controllers when a produce/consume connection is established between the
two controllers
• HMI devices that are included in the I/O configuration section
• Third-party devices that are directly connected to the EtherNet/IP network

Devices Excluded from the Node Count


When you calculate the EtherNet/IP node limitation of a controller, do not count devices that
exist on the EtherNet/IP network but are not added to the I/O configuration section.

The following devices are not added to the I/O configuration section and are not counted
among the number of nodes:
• Computer
• HMIs that are not added to the I/O configuration section
• Devices that are the target of MSG Instructions but were not added to the I/O
configuration section
• Standard Ethernet devices with which the controller communicates via a socket
interface

104 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 8 EtherNet/IP Network

Figure 24 shows nodes in the I/O tree.


Figure 24 - Example EtherNet/IP Nodes

Node

Node

Node

Node

The Capacity tab in the Controller Properties dialog box displays the number of Ethernet nodes
that are used in a project. The following graphic represents the project in Figure 24.
Figure 25 - Capacity Tab

EtherNet/IP Network CompactLogix 5380 and Compact GuardLogix 5380 controllers support these EtherNet/IP
network types:
Topologies
• Device Level Ring Network Topology
Applies to these controllers: • Linear Network Topology
CompactLogix 5380
• Star Network Topology
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 Some examples in this section use a CompactLogix 5380 controller and other examples use
Compact GuardLogix 5380 controllers. This is for example purposes only. Either controller type
can be used in each example.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 105


Chapter 8 EtherNet/IP Network

Device Level Ring Network Topology


Device Level Ring (DLR) is an EtherNet/IP protocol that is defined by ODVA. DLR provides a
means to detect, manage, and recover from single faults in a ring-based network.

A DLR network includes the following types of ring nodes.


Node Description
A ring supervisor provides these functions:
• Manages traffic on the DLR network
Ring supervisor • Collects diagnostic information for the network
A DLR network requires at least one node to be configured as ring supervisor.
By default, the supervisor function is disabled on supervisor-capable devices.
Ring participants provide these functions:
• Process data that is transmitted over the network.
Ring participants • Pass on the data to the next node on the network.
• Report fault locations to the active ring supervisor.
When a fault occurs on the DLR network, ring participants reconfigure themselves and
relearn the network topology.
Redundant gateways are multiple switches that connect to a DLR network and also
Redundant gateways connect together through the rest of the network.
(optional) Redundant gateways provide DLR network resiliency to the rest of the network.

Depending on their firmware capabilities, both devices and switches can operate as
supervisors or ring nodes on a DLR network. Only some devices, such as switches, can operate
as redundant gateways.

For more information about DLR, see the EtherNet/IP Device Level Ring Application Technique,
publication ENET-AT007.

IMPORTANT A CompactLogix 5380 or Compact GuardLogix 5380 controller is


typically in Linear/DLR mode when it is used in a DLR topology. If the
controller operates in Dual-IP mode, it must connect to a DLR topology
via an ETAP that is connected to an Ethernet port on the controller.

Figure 26 - CompactLogix 5380 Controller in a DLR Topology

CompactLogix 5380 Controller Compact 5000 I/O EtherNet/IP Adapter


Compact 5000™ I/O Modules Compact 5000 I/O Modules

Device Level Ring Network

PowerFlex® 527 Drive Compact 5000 I/O EtherNet/IP Adapter


Compact 5000 I/O Modules

PanelView™ Plus 7
Terminal

1734-AENTR Adapter
Kinetix® 5500 Drives
1734 POINT I/O™ Modules

106 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 8 EtherNet/IP Network

Linear Network Topology


A linear network topology is a collection of devices that are daisy-chained together across an
EtherNet/IP™ network. Devices that can connect to a linear network topology use embedded
switch technology to remove any need for a separate switch, as required in Star network
topologies.
Figure 27 - Compact GuardLogix 5380 Controller in a Linear Network Topology

Compact 5000 I/O EtherNet/IP Adapter


Compact 5000 I/O Modules
1794-AENTR Adapter
1794 FLEX™ I/O Modules

Workstation

PanelView Plus 7 Terminal

Kinetix 5500 Drives 1734-AENTR Adapter


Compact GuardLogix 5380 SIL 2 or SIL 3 Controller
1734 POINT I/O Modules
Compact 5000 I/O Safety, Analog, and Digital Modules

For more information on how to design a DLR network, see the EtherNet/IP Embedded Switch
Technology Application Guide, publication ENET-AP005

Star Network Topology


A star network topology is a traditional EtherNet/IP network that includes multiple devices that
are connected to each other via an Ethernet switch. The controller can operate in Linear/DLR
or Dual-IP mode when it is connected to a star network topology.

If the controller operates in Dual-IP mode, the Ethernet ports have unique IP configurations
and must be connected to different subnets.

For more information on how to configure a controller that uses Dual-IP mode, see Use
EtherNet/IP Modes on page 117.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 107


Chapter 8 EtherNet/IP Network

Figure 28 - CompactLogix 5380 Controllers in a Star Network Topology


CompactLogix 5380 Controller
Compact 5000™ I/O Modules
5069-AENTR Adapter
Compact 5000 I/O Modules

Stratix® 5400 Switch

PanelView Plus 7 Terminal

Kinetix 5500 Drive

PowerFlex 527 Drive


1734-AENTR Adapter
1734 POINT I/O Modules

Integrated Architecture Tools


For more information when you design your CompactLogix 5380 system, see the Integrated
Architecture® Tools and Resources web page. For example, you can access the Popular
Configuration Drawings with different EtherNet/IP network topologies.

The tool and resources are available at: http://www.rockwellautomation.com/global/products-


technologies/integrated-architecture/tools/overview.page

108 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 8 EtherNet/IP Network

EtherNet/IP Network The CompactLogix 5380 and Compact GuardLogix 5380 controllers support these EtherNet/IP
network communication rates:
Communication Rates
• 10 Mbps
Applies to these controllers: • 100 Mbps
CompactLogix 5380
• 1 Gbps
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 Network performance in a CompactLogix 5380 system is optimal if the 1 Gbps network
communication rate is used. However, many Ethernet devices do not support the 1 Gbps
network communication rate. Instead, they support a maximum rate of 100 Mbps.

The difference in maximum network communication rates impacts your CompactLogix 5380
system and, in some applications, restricts you from using the 1 Gbps network communication
rate on a controller.

When you design a CompactLogix 5380 system and consider using the 1 Gbps rate on the
controller, remember the following:
• You can use the 1 Gbps network communication rate on the controller ports when all
network devices support the 1 Gbps, for example, 5069-AEN2TR adapters with Compact
5000 I/O modules and a gigabit-capable switch.
When you use the 1 Gbps network communication rate, configure the controller ports to
use Auto-Negotiate.
CompactLogix 5380 Controller
Compact 5000 I/O Modules

1 Gbps

Stratix 5400 Switch

1 Gbps
1 Gbps

1 Gbps Compact 5000 I/O EtherNet/IP Adapter


1 Gbps
Compact 5000 I/O Modules
Workstation

Compact 5000 I/O EtherNet/IP Adapter


Compact 5000 I/O Modules

• You can use the 1 Gbps network communication rate on the controller ports when some
network devices support a maximum network communication rate of 100 Mbps.
However, in this case, the controller must be connected to those devices through a
managed switch.

The port to which the controller is connected must be configured for Auto-Negotiate and the 1
Gbps network communication rate.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 109


Chapter 8 EtherNet/IP Network

Compact 5000 I/O EtherNet/IP Adapter


Compact 5000 I/O Modules
CompactLogix 5380 Controller
Compact 5000 I/O Modules

Stratix 5400 Switch


100 Mbps 1 Gbps

100 Mbps
PanelView Plus 7 Terminal 1 Gbps

100 Mbps

Compact 5000 I/O EtherNet/IP Adapter


Compact 5000 I/O Modules
PowerFlex 527 Drive Kinetix 5500 Drive

We recommend that you do not use the 1 Gbps network communication rate on the controller
ports if it operates on a linear or DLR network topology and at least one device on the network
supports the maximum network communication rate of 100 Mbps.
That is, do not use different network communication rates on device ports in the same
EtherNet/IP network without a managed switch.
All network communication on this 1794-AENTR Adapter
network uses the 100 Mbps rate. 1794 FLEX™ I/O Modules
Compact 5000 I/O EtherNet/IP Adapter
Compact 5000 I/O Modules

Workstation
PanelView Plus 7 Terminal

CompactLogix 5380 Controller Kinetix 5500 Drives 1734-AENTR Adapter


Compact 5000 I/O Modules 1734 POINT I/O Modules

110 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 8 EtherNet/IP Network

Simple Network SNMP enables the controller to be remotely managed through other network management
software. SNMP defines the method of communication among the devices and also denotes a
Management Protocol manager for the monitoring and supervision of the devices. SNMP is disabled on the controller
(SNMP) by default.
For more information about SNMP, see the Ethernet Reference Manual, publication
ENET-RM002.

Use a CIP Generic MSG to Enable SNMP on the Controller

IMPORTANT You cannot add a MSG instruction to your program if the controller mode
switch is in RUN mode, or if the FactoryTalk Security settings deny this
editing option.
1. Add a MSG instruction to your program.
2. Configure the Configuration tab on the Message Configuration dialog box as described
in Table 11.

Table 11 - Enable SNMP


Field Description
Message Type CIP Generic
Service Type Custom
Service Code 4c
1 for Linear/DLR mode
Instance 2 for Dual-IP mode
Class f5

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 111


Chapter 8 EtherNet/IP Network

Table 11 - Enable SNMP (Continued)


Field Description
Attribute 0
Controller tag of USINT[5] data type.
In this example, the controller tag is named onArray and must match the following
graphic:

Source Element

IMPORTANT: The Source Element tag in your Logix Designer application project must
match the values that are shown in the graphic. If you use values that are different
than the ones shown, SNMP will not be enabled.
Source Length 5

3. Configure the Communication tab to use a Path of THIS.

IMPORTANT Messages to THIS must be unconnected messages.

112 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 8 EtherNet/IP Network

Use a CIP Generic MSG to Disable SNMP on the Controller


1. Add a MSG instruction to your program.

IMPORTANT You cannot add a MSG instruction to your program if the controller
mode switch is in RUN mode, or if the FactoryTalk Security
settings deny this editing option.
2. Configure the Configuration tab on the Message Configuration dialog box as described
in Table 12.

Table 12 - Disable SNMP


Field Description
Message Type CIP Generic
Service Type Custom
Service Code 4c
1 for Linear/DLR mode
Instance 2 for Dual-IP mode
Class f5
Attribute 0
Controller tag of USINT[5] data type.
In this example, the controller tag is named offArray and must match the following
graphic:

Source Element

IMPORTANT: The Source Element tag in your Logix Designer application project must
match the values that are shown in the graphic. If you use values that are different
than the ones shown, SNMP will not be disabled.
Source Length 5

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 113


Chapter 8 EtherNet/IP Network

3. Configure the Communication tab to use a Path of THIS.

IMPORTANT Messages to THIS must be unconnected messages.

Socket Interface The controller can use socket interfaces to communicate with Ethernet devices that do not
support the EtherNet/IP application protocol. The socket interface is implemented via the
Applies to these controllers: socket object. The controller communicates with the socket object via MSG instructions.
CompactLogix 5380
Compact GuardLogix 5380 SIL 2 The controllers support up to 32 socket instances.
Compact GuardLogix 5380 SIL 3
IMPORTANT Keep these in mind when you use sockets with the controllers:
• All CompactLogix 5380 and Compact GuardLogix 5380 controllers must
use unconnected MSG instructions for socket servers. When you
configure a message for a CompactLogix 5380 and Compact
GuardLogix 5380 controller, make sure that the Connected checkbox on
the Message Configuration dialog box is cleared.
• When the controller operates in Dual-IP mode and uses a socket object,
you can use an IP address with a Socket_Create service type. For more
information, see Use Socket Object on page 134.

These products support a secure socket object:


• Controllers, firmware revision 35.011 and later
• 1756-EN4TR modules, firmware revision 5.001 and later

For more information on the socket interface, see the following:


• EtherNet/IP Socket Interface Application Technique, publication ENET-AT002
• Knowledgebase Article Socket Communication in ControlLogix and CompactLogix

TLS Support
The secure socket option adds support for Transport Layer Security (TLS) to the socket object.

114 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 8 EtherNet/IP Network

HTTP(S) REST API Client Support


You can develop your application to send HTTP REST API requests and implement HTTPS via
the socket interface with TLS. For more information, see the documentation for these objects
in the Common Application Library available from the Product Compatibility and Download
Center at rok.auto/pcdc:
• raC_Impl_HTTPClient
• raC_Impl_HTTPCmdGET
• raC_Impl_HTTPCmdPOST
• raC_Impl_HTTPCmdPUT

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 115


Chapter 8 EtherNet/IP Network

Notes:

116 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 9
Use EtherNet/IP Modes
Overview This chapter describes the EtherNet/IP™ modes that are available with the
CompactLogix™ 5380 and Compact GuardLogix® 5380 controllers.
Applies to these controllers:
• Dual-IP
CompactLogix 5380
Compact GuardLogix 5380 SIL 2
• Linear/DLR
Compact GuardLogix 5380 SIL 3 We expect you to have a working knowledge of both modes before using a CompactLogix 5380
or Compact GuardLogix 5380 controller. This chapter describes specific tasks in each
application that are related to the EtherNet/IP modes.
Other chapters in this publication describe how to perform more general tasks in the Studio
5000 Logix Designer® application and RSLinx® Classic software. If necessary, read those
chapters to understand better the tasks that are described in this chapter.

Available Network Levels The controllers can connect to these EtherNet/IP network levels:
Applies to these controllers:
• Enterprise-level Network
CompactLogix 5380 • Device-level Network
Compact GuardLogix 5380 SIL 2
The advantage of connecting to separate network levels is that you can segment the networks
Compact GuardLogix 5380 SIL 3 and isolate the communication on each. For example, communication that is required for the
controller to execute a task is restricted to the device-level network.

Network segmentation and the resulting communication isolation can help provided enhanced
security in your application. Additionally, the option to connect to separate network levels
helps you organize the networks in your application in a more logical manner.

Enterprise-level Network
Remember the following when you connect to enterprise-level networks:
• You can connect only port A1 to an enterprise-level network.

IMPORTANT When you set the IP address and subnet mask, you establish an IP
address range for the port. Make sure that the IP address ranges that are
established for each port on the controller do not overlap.
For more information on overlapping IP address ranges, see Overlapping
IP Address Ranges on page 123.

When you connect a port to an enterprise-level network, you configure the following
parameters:
• IP address (required)
• Subnet mask, also called the network mask (required)
• Gateway address (optional)
• Host name (optional)
• Domain name (optional)
• Primary DNS server address (required if your controller makes DNS requests.)
• Secondary DNS server address (required if your controller makes DNS requests.)

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 117


Chapter 9 Use EtherNet/IP Modes

Device-level Network
Remember the following when you connect to device-level networks:
• You are not required to connect the controller to an enterprise-level network to connect
to device-level networks.
• You can connect port A1, port A2, or ports A1 and A2 to device-level networks.

When you connect a port to a device-level network, you configure the following parameters:
• IP address (Required)
• Subnet mask, also called the network mask (Required)
• Gateway address (Optional)
• Host name (Optional)

EtherNet/IP Modes With the Logix Designer application, version 29 or later, the controllers support these
EtherNet/IP modes:
Applies to these controllers:
• Dual-IP Mode
CompactLogix 5380
Compact GuardLogix 5380 SIL 2
• Linear/DLR Mode
Compact GuardLogix 5380 SIL 3 Out-of-the-box, the controller EtherNet/IP mode is Dual-IP mode.

Dual-IP Mode
Dual-IP mode lets you connect ports A1 and A2 to separate networks. In this mode, port A1 can
connect to an enterprise-level network or a device-level network. Port A2 can only connect to
a device-level network.

IMPORTANT Dual-IP mode is first available with CompactLogix 5380 controller


firmware revision 29.011 or later.

In this mode, each port requires its own network configuration. For more information on how
to configure the Ethernet ports when the controller uses Dual-IP mode, see Configure
EtherNet/IP Modes on page 124.

You must avoid overlapping IP address ranges when you configure the Ethernet ports in Dual-
IP mode. For more information, see Overlapping IP Address Ranges on page 123.

118 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 9 Use EtherNet/IP Modes

Figure 29 shows a CompactLogix 5380 controller using Dual-IP mode in with connections to an
enterprise-level network and a device-level network.
Figure 29 - Controller in Dual-IP Mode with Enterprise-level and Device-level Network Connections

Plant-wide Operations System

Stratix® 5410 Switch

CompactLogix 5380 Controller


Compact 5000™ I/O Modules

PanelView™ Plus 7 Terminal

Port A1 Connected to an
Enterprise-level Network

Port 2 Connected to a Device-level Network


Stratix 2000 Switch

PowerFlex® 527 Drive

Compact 5000 I/O EtherNet/IP Adapter


Compact 5000 I/O Modules

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 119


Chapter 9 Use EtherNet/IP Modes

Figure 30 shows a CompactLogix 5380 controller using Dual-IP mode in with connections to
separate device-level networks, including a DLR network.

IMPORTANT If a controller is using Dual-IP mode, it can connect to a DLR network


topology only through a 1783 Ethernet tap, in this case via port A2.
Figure 30 - Controller in Dual-IP Mode with Device-level Network Connections Only

CompactLogix 5380 Controller


Compact 5000 I/O Modules
Port A1 Connected to Another Device-level Network

Port A2 Connected to a
DLR Network

Compact 5000 I/O EtherNet/IP Adapter


Compact 5000 I/O Modules

1783-ETAP

Compact 5000 I/O EtherNet/IP Adapter


PowerFlex 527 Drive Compact 5000 I/O Modules

PanelView Plus 7 Terminal


Kinetix 5500 Drives

1734-AENTR Adapter
1734 POINT I/O™ Modules

PanelView Plus 7 Terminal PowerFlex 527 Drive

Compact 5000 I/O EtherNet/IP Adapter


Compact 5000 I/O Modules
Kinetix® 5700 Drives

120 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 9 Use EtherNet/IP Modes

Controller Functionality Considerations in Dual-IP Mode

Remember these controller functions when you use Dual-IP mode:


• The controller does not support these functions:
- TCP routing or switching between the two separate networks.
- CIP™ bridging of I/O connections (including produce/consume) between the two
separate networks.
• The controller supports these functions:
- CIP bridging for non-I/O connections such as HMI, messaging, or sockets between
the two separate networks.
- CIP bridging for Unconnected CIP messages between the two separate networks.

Linear/DLR Mode
When controllers operate in Linear/DLR mode, they can only connect to one network with one
network configuration. The two physical ports allow the controller to connect to linear or DLR
media topologies.
After firmware revision 29.011 or later is installed on a controller, the EtherNet/IP mode is
automatically set to Dual-IP mode. You must change the EtherNet/IP Mode to use Linear/DLR
mode.

For more information on how to change the controller to Linear/DLR mode, see Change the
EtherNet/IP Mode on page 129.
Figure 31 - CompactLogix 5380 Controller in Linear/DLR Mode in a DLR Network

CompactLogix 5380 Controller Compact 5000 I/O EtherNet/IP Adapter


Compact 5000 I/O Modules Compact 5000 I/O Modules

Compact 5000 I/O EtherNet/IP Adapter


Compact 5000 I/O Modules

PowerFlex 527 Drive

1734-AENTR Adapter PanelView Plus 7 Terminal


Kinetix 5500 Drives
1734 POINT I/O Modules

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 121


Chapter 9 Use EtherNet/IP Modes

Figure 32 - Compact GuardLogix 5380 Controller in Linear/DLR Mode in a Linear Network

Compact GuardLogix 5380 SIL 2 or SIL 3 Controller


PowerFlex 527 Drive
Compact 5000 I/O Safety, Analog, and Digital Modules

PanelView Plus 7 Terminal

Compact 5000 I/O EtherNet/IP Adapter Compact 5000 I/O EtherNet/IP Adapter Kinetix 5500 Drives
Compact 5000 I/O Modules Compact 5000 I/O Modules
h

Figure 33 - CompactLogix 5380 Controller in Linear/DLR Mode in a Star Network

CompactLogix 5380 Controller


Compact 5000 I/O Modules Compact 5000 I/O EtherNet/IP Adapter
Compact 5000 I/O Modules

Stratix 5700 Switch

PanelView Plus 7 Terminal

Kinetix 5500 Drive

PowerFlex 527 Drive


1734-AENTR Adapter
1734 POINT I/O Modules

122 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 9 Use EtherNet/IP Modes

Overlapping IP Address
Ranges IMPORTANT Overlapping IP address ranges only applies when the controller operates in
Dual-IP mode.
Applies to these controllers:
CompactLogix 5380
If you use the controller in Linear/DLR mode, you can skip this section and
proceed to Linear/DLR Mode on page 121.
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 The IP address and subnet mask values that you assign to an Ethernet port establish an IP
address range for the port. The subnet mask value is used to establish the network part of the
IP address.

Overlapping IP address ranges occurs when any IP address from one range is also present in
the other IP address range. When a controller uses Dual-IP mode, the network parts cannot
overlap between the Ethernet ports.

The following examples describe conditions in which IP address ranges do not or do overlap.

EXAMPLE IP Address Ranges Do Not Overlap


The table describes port A1 and port A2 configurations that use IP address
ranges that do not overlap.
None of the IP addresses in either port IP address range exists in the IP
address range for the other port.

Subnet Mask/ IP Address Range


Port Number IP Address Network Mask (Low to High)
A1 192.168.1.5 255.255.255.0 192.168.1.1…192.168.1.254
A2 192.168.2.1 255.255.255.0 192.168.2.1…192.168.2.254

EXAMPLE IP Address Ranges Do Overlap


The table describes port A1 and port A2 configurations that use IP address
ranges that do overlap.
All IP addresses in the port A2 IP address range are in the port A1 IP
address range.

Subnet Mask/ IP Address Range


Port Number IP Address Network Mask (Low to High)
A1 192.168.1.5 255.255.252.0 192.168.0.1…192.168.3.254
A2 192.168.2.1 255.255.255.0 192.168.2.1…192.168.2.254

The difference between the port configurations in the examples is the Subnet Mask/Network
Mask value for port A1.

In the first example, the value is 255.255.255.0. In the second example, the value
255.255.252.0.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 123


Chapter 9 Use EtherNet/IP Modes

Configure EtherNet/IP You can configure both Dual-IP and Linear/DLR EtherNet/IP modes with these
software applications:
Modes
• Logix Designer application, version 29 or later
Applies to these controllers: • RSLinx Classic software, version 3.81.00 or later
CompactLogix 5380
• With the Logix Designer application, version 28, the 5069-L320ER and 5069-L340ERM
Compact GuardLogix 5380 SIL 2 controllers only support Linear/DLR mode.
Compact GuardLogix 5380 SIL 3
IMPORTANT Keep in mind that the applicable minimum software versions vary
by controller catalog number. That is, you can use some
controllers in lower software minimum versions than others.
The screens can be slightly different on the Controller Properties dialog box for Compact
GuardLogix 5380 controllers. For example, the Compact GuardLogix 5380 Controller Properties
dialog box includes a Safety tab that does not exist in the CompactLogix 5380 Controller
Properties dialog box.

Configure Dual-IP Mode in the Logix Designer Application


In the Logix Designer application version 29 or later, the EtherNet/IP mode is Dual-IP by default
and is displayed on the General tab in the Controller Properties dialog box.

You set the IP address and subnet mask on the Internet Protocol tab.
When you set the IP address and subnet mask, we recommend that you use a USB
connection from the workstation to the controller.
1. Confirm that the project is online.
2. Confirm that the controller is in one of these modes:
• Program mode
• Remote Program mode
• Remote Run mode
You cannot change the IP address or subnet mask if the controller is in Run mode.
3. Click the Internet Protocol tab.
4. From the Port pull-down menu, choose A1.

124 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 9 Use EtherNet/IP Modes

5. Click Manually configure IP settings.


6. Assign the IP address and network mask values.
7. Click Apply.

8. Repeat the previous steps, beginning at step 4.


In step 4, make sure that you choose A2 in the Port field.

Configure Dual-IP Mode in RSLinx Classic Software


In RSLinx Classic software, the IP Mode for which the controller is configured is displayed on
the General tab in the Configuration dialog box.

For example, this graphic displays that the controller is in Dual-IP mode.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 125


Chapter 9 Use EtherNet/IP Modes

You set the IP Address and Network Mask on the Port Configuration tab.
When you set the IP address and Subnet Mask, we recommend that you use a USB
connection from the workstation to the controller.
1. From the Port pull-down menu, choose A1.
2. Click Manually configure IP settings.
3. Assign IP Address and Network Mask values.
4. Click Apply.

5. Repeat the steps.


In step 1, make sure that you choose A2 from the Port pull-down menu.

Configure Linear/DLR Mode in the Logix Designer Application


Remember, with firmware revision 29.011 or later, the EtherNet/IP Mode is Dual-IP by default.
You must change the mode to use Linear/DLR mode.

IMPORTANT For more information on how to change the controller EtherNet/IP mode,
see Change the EtherNet/IP Mode on page 129.

126 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 9 Use EtherNet/IP Modes

After you change the EtherNet/IP mode to Linear/DLR mode, the new mode choice is displayed
on the General tab in the Controller Properties dialog box.

You set the IP address and subnet mask on the Internet Protocol tab.
1. Confirm that the project is online and the controller is in Program mode, Remote
Program mode, or Remote Run mode.
You cannot change the IP address or subnet mask if the controller is in Run mode.
2. Click the Internet Protocol tab.
3. Click Manually configure IP settings.
4. Assign the IP address and network mask values and click Apply.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 127


Chapter 9 Use EtherNet/IP Modes

Configure Linear/DLR Mode in RSLinx Classic Software


Remember, with firmware revision 29.011 or later, the EtherNet/IP Mode is Dual-IP by default.
You must change the mode to use Linear/DLR mode.

IMPORTANT For more information on how to change the controller EtherNet/IP mode,
see Change the EtherNet/IP Mode on page 129.

The new mode choice is displayed on the General tab in the Controller Properties dialog box.

You set the IP Address and Subnet Mask on the Internet Protocol tab.
1. Confirm that the project is online.
2. Click the Port Configuration tab.
3. Click Manually configure IP settings.
4. Assign IP Address and Network Mask values.
5. Click Apply.

128 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 9 Use EtherNet/IP Modes

Change the EtherNet/IP You can change the EtherNet/IP mode in the Logix Designer application or RSLinx Classic
software.
Mode
Applies to these controllers: IMPORTANT Remember the following:
CompactLogix 5380 • Exercise caution when you change the EtherNet/IP mode on your
Compact GuardLogix 5380 SIL 2 controller, and consider the possible effects of the change.
Compact GuardLogix 5380 SIL 3 • You cannot change the controller EtherNet/IP mode from Dual-IP to
Linear/DLR when you are connected through port A1 port. You must be
connected to the controller via port A2 to change from Dual-IP mode to
Linear/DLR mode.
The effects of changing the EtherNet/IP mode are different based on mode change. Make sure
that you are aware of them before changing the EtherNet/IP mode.
Table 13 - Effect of Changing the EtherNet/IP Mode
EtherNet/IP Effects
Mode Change
• The port A2 IP address, network mask, default gateway settings are applied to the A1/A2 port.
• The MAC address of port A1 is applied to port A1/A2.
• This scenario exists if the controller firmware is upgraded to revision 29.011 or greater before
Dual-IP Mode to an IP address is set.
Linear/DLR Mode • Attempts to change from Dual-IP mode to Linear/DLR mode are only successful if the I/O
configuration section in at least one port does not contain modules.
• If the I/O configuration sections for both ports include modules, you cannot change the
EtherNet/IP mode from Dual-IP mode to Linear/DLR mode.
• The port A1/A2 IP address, network mask, default gateway settings are applied to port A2.
• Other port A1/A2 settings, for example, DNS servers and Domain Name, are lost.
• The port A1/A2 MAC address is applied to port A1. A separate MAC address is applied to Port
A2.
Linear/DLR Mode
to Dual-IP Mode • Port A1 is DHCP-enabled.
• The I/O Configuration section in the Logix Designer application project is automatically
assigned to port A1.
• You can change the I/O configuration in the Logix Designer application project to assign it to
port A2.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 129


Chapter 9 Use EtherNet/IP Modes

Change the EtherNet/IP Mode in the Logix Designer Application

IMPORTANT This example shows the EtherNet/IP mode change from Dual-IP mode to
Linear/DLR mode. The same tasks apply to change from Linear/DLR
mode to Dual-IP mode.

To change the EtherNet/IP mode in the Logix Designer application, complete these steps.
1. Confirm that the project is offline.
2. On the General tab of the Controller Properties dialog box, click Change IP Mode.

3. From the New mode pull-down menu, choose the new mode and click OK.

4. Click OK on the Controller Properties dialog box.


5. Save the project.
6. Download the updated project to the controller.
7. When the following warning appears, read it carefully.

IMPORTANT Before you change the EtherNet/IP mode, make sure that you
understand the impact on your controller when you change
the mode.
For more information on the impact of changing the EtherNet/IP
mode, see Table 13 on page 129.

130 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 9 Use EtherNet/IP Modes

8. Click Yes to continue.

Change the EtherNet/IP Mode in RSLinx Classic Software


To change the EtherNet/IP mode in RSLinx Classic software, complete these steps.
1. Confirm that the controller is online and there is no project in the controller.
2. Confirm that the controller is in one of these modes:
- Program mode
- Remote Program mode
- Remote Run mode
You cannot change the IP Address or Subnet Mask if the controller is in Run mode.
3. Right-click the controller and choose Module Configuration.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 131


Chapter 9 Use EtherNet/IP Modes

4. On the General tab of the Configuration dialog box, click Change IP Mode.

5. From the New mode pull-down menu, choose the new mode and click OK.

6. When the following warning appears, read it carefully.

IMPORTANT Before you change the EtherNet/IP mode, make sure that you
understand the impact on your controller when you change
the mode.
For more information on the impact of changing the EtherNet/IP
mode, see Table 13 on page 129.

7. Click Yes to continue.

132 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 9 Use EtherNet/IP Modes

DNS Requests
To qualify the address of a module, use DNS addressing to specify a host name for a module,
which also includes specifying a domain name and DNS servers. DNS addressing makes it
possible to configure similar network structures and IP address sequences under different
domains.
DNS addressing is necessary only if you refer to the module by host name, such as in path
descriptions in MSG instructions.

IMPORTANT Safety Consideration


For information on DNS Addressing for Compact GuardLogix 5380
controllers, see DNS Addressing on page 53.

For more information on DNS addressing, see the EtherNet/IP Network Configuration User
Manual, publication ENET-UM001.

DNS Request Routing


DNS requests can be generated from port A1 or port A2.
DNS Request Generated From Port A1
• If the DNS server address is in the local subnet of port A1, DNS requests leave through A1
port.
• If port A2 is enabled and the DNS server address is in local subnet of port A2, DNS
requests leave through A2 port.
• If the DNS server address is outside of all local subnets, DNS requests leave through A1
port towards port A1 default gateway.
DNS Request Generated From Port A2
• If port A1 is enabled and the DNS server address is in local subnet of port A1, DNS
requests leave through A1 port.
• If the DNS server address is in local subnet of port A2, DNS requests leave through A2
port.
• If port A1 is enabled and the DNS server address is outside of all local subnets, DNS
requests leave through A1 port towards port A1 default gateway.
• If port A1 is disabled and the DNS server address is outside of all local subnets, DNS
requests leave through A2 port towards port A2 default gateway.

SMTP Server
The SMTP server is only available via the enterprise port. Therefore, emails can only be sent on
the enterprise port.

For more information on how to send emails via an Ethernet port, see the EtherNet/IP Network
Configuration User Manual, publication ENET-UM001.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 133


Chapter 9 Use EtherNet/IP Modes

Use Socket Object


When the controller operates in Dual-IP mode and uses a socket object, you can use an IP
address with a Socket_Create service type. By default this IP address is INADDR_ANY.

Remember the following:


• If you use INADDR_ANY, IP communication that the Socket Object instance initiates
follows the same routing rules as DNS request routing rules described in DNS Request
Routing on page 133.
• If you use the IP address of port A1 instead of INADDR_ANY, IP packets can only go to the
port A1 subnet or via its default gateway.
• If you use the IP address of port A2 instead of INADDR_ANY, IP packets can go only to
port A2 subnet or via its default gateway.
• If you use an IP address other than the port A1 or A2 IP addresses or INADDR_ANY, the
Create_Socket_Service request is rejected.

Send Message Instructions


You can send Message (MSG) instructions out the enterprise port or the device-level port. The
only difference between the MSG instruction configurations is the path.

When you configure an MSG instruction on a controller that operates in Dual-IP mode, use
these paths:
• Enterprise port (Port A1) - 3
• Device-level port (Port A2) - 4
If the controller operates in Linear/DLR mode, the path is 2.

For more information on how to use MSG instructions, see the Logix 5000 Controllers General
Instructions Reference Manual, publication 1756-RM003.

134 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 9 Use EtherNet/IP Modes

Software Display Differences for EtherNet/IP Modes


Table 14 shows differences in the Logix Designer application when the controller uses Dual-IP
mode or Linear/DLR mode.
Table 14 - EtherNet/IP Mode Display Differences in the Logix Designer Application
EtherNet/IP Mode
Section in Application Dual-IP Mode Linear/DLR Mode

I/O Configuration Tree in


Controller Organizer

General Tab on Controller


Properties Dialog Box

Internet Protocol on
Controller Properties
Dialog Box

If you connect port A1 to a device-level network, some parameters


appear as configurable but are not used. For more information on
what parameters you configure to connect a port to a device-level
network, see Device-level Network on page 118.

The Controller Properties dialog box also provides a Network tab in the Logix Designer
application when the controller uses Linear/DLR mode. The Network tab is not available when
the controller uses Dual-IP mode.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 135


Chapter 9 Use EtherNet/IP Modes

Table 15 shows differences in RSLinx Classic software when the controller uses Dual-IP mode
or Linear/DLR mode.
Table 15 - EtherNet/IP Mode Display Differences in the RSLinx Classic Software
EtherNet/IP Mode
Section in Dual-IP Mode Linear/DLR Mode
Software

General Tab

Port Configuration
Tab

If you connect port A1 to a device-level network, some parameters


appear as configurable but are not used. For more information on
what parameters you configure to connect a port to a device-level
network, see Device-level Network on page 118.

The Configuration dialog box also provides a Network tab in RSLinx Classic software when the
controller uses Linear/DLR mode. The Network tab is not available when the controller uses
Dual-IP mode.

136 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 10
Manage Controller Communication
Connections Connections are used when the system contains these conditions:
Applies to these controllers:
• I/O modules, communication modules, and adapters are present in the I/O configuration
of the user project.
CompactLogix™ 5380
Compact GuardLogix® 5380 SIL 2
• Produced or Consumed tags are configured in the user project.
Compact GuardLogix 5380 SIL 3 • Connected Messages are executed in the user application.
• External devices, programming terminals, or HMI terminals communicate with the
controller.

Controller Communication The controller runs the communications task separately from the application code. The
controller runs communications asynchronously to the application. Therefore, it is important
Interaction with Control Data to make sure communications that are delivered to the controller are complete before the
Applies to these controllers: application executes on the newly delivered data. This applies to data that is coming into the
controller and data that is going out from the controller.
CompactLogix 5380
Compact GuardLogix 5380 SIL 2 For example, if an HMI device writes a large block of recipe data to the controller, the
Compact GuardLogix 5380 SIL 3 application code can start to execute on that data before the data is written. This action
results in half of the current recipe and half of the last recipe in the application space.

Traditionally, programmers have used the following to control the effects of asynchronous
communications:
• UID/UIE pairs
• Moving data with CPS instructions.

These options rely on controlling when the main core can switch tasks. As a result, the
communication task cannot change data when the control task is using it. Because the
controller processes communications on an independent CPU core, these methods are no
longer effective in all cases.

Table 16 highlights the controller behavior.


Table 16 - CompactLogix 5380 and Compact GuardLogix 5380 Controller Behavior
Tag Access
Application Construct
HMI MSG I/O Update Produce/Consume Other User Tasks Motion Planner
UID/UIE Allows Allows Allows Allows Blocks Allows
CPS Blocks Blocks Blocks Blocks Allows Allows
Blocks - Hel0ps to prevents source data values from change by communications during application execution.
Allows - Communications can change source data values during application execution.

Because the controllers have 32-bit data integrity, this only applies to data structures larger
than 32 bits. If word-level integrity is your primary concern, the 32-bit data integrity does not
impact your data use.

Good programming practice dictates the use of two unique words at the beginning and the end
of data. The controller validates the words to verify the entire structure has data integrity. We
recommend that the handshake data is changed and the application code validates it every
transaction before the controller application code or higher-level system reading controller
data acts on it.

Table 17 shows two data elements that are added to a structure for data integrity checking.
That is, Start Data and End Data are added. We recommend that the controller validates the
Start Data value and the End Data value match before the controller acts on My_Recipe1.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 137


Chapter 10 Manage Controller Communication

If the Start Data and End Data values do not match, it is likely communications is in the
process of filling the structure. The same applies to higher-level systems that are receiving
data from the controller.
Table 17 - Data Elements
Structure My_Recipe1 My_Recipe2 My_Recipe3
Start Data 101 102 103
Sugar 3 4 8
Flour 4 3 9
Chocolate 2 2 4
Oil 6 7 2
End Data 101 102 103

We recommend that you perform this test on a buffered copy of the data and not
the actual data element being written to by the communications core. If you use
buffered data, you help prevent the risk of the communication core changing data
after you have passed the data valid test.

Produce and Consume The controllers let you produce (transmit) and consume (receive) controller-scoped tags.
CompactLogix 5380 and Compact GuardLogix 5380 controllers produce the same standard tag
(Interlock) Data through the Ethernet ports and the backplane, and consumer counts apply to the total
Applies to these controllers: consumers from all ports.
CompactLogix 5380 Figure 34 - Example Produced and Consumed Tags
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 Controller_1 Controller_2

Produced Tag Consumed Tag

Controller_3

Consumed Tag

Controller_4
Consumed Tag

Table 18 describes the system-shared tags.

Table 18 - Produced and Consumed Tag Descriptions


Tag Description
A tag that a controller makes available for use by other controllers. Multiple controllers can
simultaneously consume (receive) the data.
Produced tag A produced tag sends its data to one or more consumed tags (consumers) without using
logic.
A tag that receives the data of a produced tag. The data type of the consumed tag must
Consumed tag match the data type (including any array dimensions) of the produced tag. The RPI of the
consumed tag determines the period at which the data updates.

For two controllers to share produced or consumed tags, the controllers must be attached to
the same network. You cannot bridge produced and consumed tags over two networks.

Produced and consumed tags use connections of the controller and the communication
modules being used.

138 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 10 Manage Controller Communication

The Compact GuardLogix 5380 controllers can also use produced and consumed safety tags.
For more information on how to use them, see the GuardLogix 5580 and Compact GuardLogix
5380 Controller Systems Safety Reference Manual, publication 1756-RM012.

Requested Packet Interval (RPI) of Multicast Tags


The first consumer of a multicast produced tag on any given communications port establishes
the RPI value for that port. All subsequent consumers that use the same port must request the
same RPI value as the first consumer, otherwise they fail to connect. Controllers with
backplane and Ethernet ports can produce data at an independent RPI value on each port.

For more information about produced/consumed tags, see the Logix 5000 Controllers
Produced and Consumed Tags Programming Manual, publication 1756-PM011.

Send and Receive Messages Messages transfer data to other devices, such as other controllers or operator interfaces. The
MSG instruction is a Ladder Diagram output instruction that asynchronously reads or writes a
Applies to these controllers: block of data to or from another module over the backplane or a network. The size of the
CompactLogix 5380 instruction depends on the data types and message command that you program.
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 Messages use connection resources to send or receive data. Messages can leave the
connection open (cached) or can close the connection when the message is done transmitting.

Messages can be unconnected or connected. Unconnected messages depend on the


availability of unconnected buffers in all devices through which the message passes.
Connected messages begin with a request to allocate connection buffers in all of those
devices, before sending the actual message. If you choose to cache a connected message, the
controller keeps the connection open after the message is complete. Cached message
improves efficiency if you intend to send the message repeatedly.
Connected messages use connection resources, and are less efficient than connected cached
messages or unconnected messages. If the connected message is uncached, the resources
are used temporarily each time the message is triggered. As long as a cached connected
message remains in the cache, the resources remain allocated and are not available for other
messages. Cached messages can get pushed from the cache if the application exceeds the
cache capacity of the controller.

Each message uses one connection out of the controller, regardless of how many devices are
in the message path.
Table 19 - Message Types
Message Type Communication Method Connected Message Message Can Be Cached
CIP™ data table read or write — Configurable Yes(2)
CIP No No
PLC-2®, PLC-3®, PLC-5®, or SLC™ CIP with Source ID No No
(all types)
DH+™ Yes Yes(2)
CIP generic — Optional (1) Yes(2)
Block-transfer read or write — Yes Yes(2)
(1) You can connect CIP generic messages. However, for most applications we recommend that you leave CIP generic messages
unconnected.
(2) We recommend that you cache connected messages that occur more frequently than once every 60 seconds, if possible.

For more information about how to use messages, see the Logix 5000 Controllers Messages
Programming Manual, publication 1756-PM012.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 139


Chapter 10 Manage Controller Communication

Determine Whether to Cache Message Connections


When you configure a message instruction, you can cache the connection. Use Table 20 to
decide to cache a connection.
.

Table 20 - Options for Caching Connections


If the Message Then
Executes
Cache the connection.
Repeatedly When you cache the connection, the connection remains open and execution time is optimized. If
a connection is opened each time that the message executes, execution time is increased.
Do not cache the connection.
When you do not cache the connection, the connection closes upon completion of the message.
Infrequently As a result, the connection is available for other uses. Unconnected messages are best used for
infrequent cached message connections.

Cached connections transfer data faster than uncached connections. The


controller can cache as many as 256 connections.

140 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 11
Standard I/O Modules
CompactLogix™ 5380 and Compact GuardLogix® 5380 systems support these
I/O module options:
• Local I/O modules
• Remote I/O modules

Local I/O Modules The CompactLogix 5380 system uses Compact 5000™ I/O modules as local I/O modules. The
modules are installed to the right of the controller.
Applies to these controllers:
CompactLogix 5380 The number of local Compact 5000 I/O modules that you can install in a CompactLogix 5380
Compact GuardLogix 5380 SIL 2 system varies based on the controller that is used, up to a maximum of 31 modules.
Compact GuardLogix 5380 SIL 3
Table 21 lists the number of local I/O modules that controllers support.
Table 21 - Local I/O Modules in CompactLogix 5380 System
Local I/O Modules
CompactLogix 5380 Controllers Compact GuardLogix 5380 Controllers Supported, Max.
5069-L306ER, 5069-L306ERM, 5069-L310ER, 5069-L306ERS2, 5069-L306ERMS2, 5069-L306ERMS3, 5069-L310ERS2, 5069-L310ERS2K, 8
5069-L310ERM, 5069-L310ERMK, 5069-L310ER-NSE 5069-L310ERMS2, 5069-L310ERMS2K, 5069-L310ERMS3, 5069-L310ERMS3K
5069-L320ERS2, 5069-L320ERS2K, 5069-L320ERMS2, 5069-L320ERMS2K, 5069-L320ERMS3,
5069-L320ER, 5069-L320ERM, 5069-L320ERP 16
5069-L320ERMS3K
5069-L330ERS2, 5069-L330ERS2K, 5069-L330ERMS2,5069-L330ERMS2K, 5069-L330ERMS3,
5069-L330ER(1), 5069-L330ERM(1), 5069-L340ER, 5069-L330ERMS3K, 5069-L340ERS2, 5069-L340ERMS2, 5069-L340ERMS3, 5069-L350ERS2,
5069-L340ERM, 5069-L340ERP, 5069-L350ERM, 5069-L350ERS2K, 5069-L350ERMS2, 5069-L350ERMS2K, 5069-L350ERMS3, 5069-L350ERMS3K, 31
5069-L380ERM, 5069-L3100ERM 5069-L380ERS2, 5069-L380ERMS2, 5069-L380ERMS3, 5069-L3100ERS2, 5069-L3100ERMS2,
5069-L3100ERMS3
(1) When you use this controller with the Studio 5000 Logix Designer® application, version 29.00.00, the application limits the number of local I/O modules in the project to 16. For more
information, see the Knowledgebase Article5380 CompactLogix controllers limited to 16 local Compact 5000 I/O modules in V29 of Studio 5000.® With the Logix Designer application, version
30.00.00 or later, the controller supports as many as 31 local I/O modules.

The following are some of the factors to consider when you decide how to use local I/O
modules in a CompactLogix 5380 system:
• Number of local I/O modules that the controller supports
• Features available on different modules, for example, sequence of events per point
timestamping on only some Compact 5000 I/O digital input modules
• I/O module power usage, including MOD power and SA power

For more information on Compact 5000 I/O modules, see Additional Resources on page 11.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 141


Chapter 11 Standard I/O Modules

Figure 35 - CompactLogix 5380 and Compact GuardLogix 5380 Systems

CompactLogix 5380 Controller Compact 5000 I/O Local Modules

Compact GuardLogix 5380 Controller Compact 5000 I/O Local Modules

Add Local I/O Modules to a Project


Before you can add local I/O modules to a Logix Designer application project, you must open an
existing project or create a project. For information on how to create a project, see Create a
Logix Designer Application Project on page 65.

There are two methods to add local I/O modules to the project:
• Discover Modules
• New Module

142 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 11 Standard I/O Modules

Discover Modules

The Discover Modules feature is useful when I/O modules are already installed and you can
connect the Logix Designer application to the controller.

To discover a local I/O module, complete these steps.


1. Go online with your Logix Designer application.
2. Right-click 5069 Backplane and choose Discover Modules.

The Logix Designer application automatically detects available modules that are
installed in the system.
3. On the Select Module Type dialog box, click Create to add a discovered module to your
project.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 143


Chapter 11 Standard I/O Modules

4. On the New Module dialog box, configure the module properties and click OK.

5. When the following warning message appears, choose whether to inhibit the module
connection, and then click Yes.
If you inhibit the module connection, remember to uninhibit the connection
later.

144 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 11 Standard I/O Modules

New Module

You can add a standard I/O module offline or online. If you do not have physical I/O installed, or
you cannot connect to the controller, this is the easiest method to add I/O.

To add a local I/O module, complete these steps.


1. Right-click 5069 Backplane and select New Module.

2. Select the module to add and click Create to open the New Module dialog box.

3. On the General tab, set the Series and Revision parameters.

IMPORTANT If the Series and Revision parameter values do not match those
of the module for which this configuration is intended, your
project can experience module faults.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 145


Chapter 11 Standard I/O Modules

4. Configure the rest of the module as needed and click OK.


For information on electronic keying, see Electronic Keying on page 147.
5. If you are online and the following warning appears, choose whether to inhibit the
module coonection and then click Yes.

If you inhibit the module connection, remember to uninhibit the connection later.

6. To add additional local I/O modules:


- If you cleared the Close on Create checkbox when you created the first I/O module,
repeat steps 2…3.
- If you did not clear the Close on Create checkbox when you created the first I/O
module, repeat steps 1…3.

146 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 11 Standard I/O Modules

Electronic Keying
Electronic Keying reduces the possibility that you use the wrong device in a control system. It
compares the device that is defined in your project to the installed device. If keying fails, a
fault occurs. These attributes are compared.
Attribute Description
Vendor The device manufacturer.
Device Type The general type of the product, for example, digital I/O module.
Product Code The specific type of the product. The Product Code maps to a catalog number.
Major Revision A number that represents the functional capabilities of a device.
Minor Revision A number that represents behavior changes in the device.

The following Electronic Keying options are available.


Keying Option Description
Lets the installed device accept the key of the device that is defined in the project when the
installed device can emulate the defined device. With Compatible Module, you can typically
replace a device with another device that has these characteristics:
Compatible • Same catalog number
Module • Same or higher Major Revision
• Minor Revision as follows:
– If the Major Revision is the same, the Minor Revision must be the same or higher.
– If the Major Revision is higher, the Minor Revision can be any number.
Indicates that the keying attributes are not considered when attempting to communicate with
a device. With Disable Keying, communication can occur with a device other than the type
specified in the project.
ATTENTION: Be cautious when using Disable Keying; if used incorrectly, this option can lead to
Disable Keying personal injury or death, property damage, or economic loss.
We strongly recommend that you do not use Disable Keying.
If you use Disable Keying, you must take full responsibility for understanding whether the
device being used can fulfill the functional requirements of the application.
Indicates that all keying attributes must match to establish communication. If any attribute
Exact Match does not match precisely, communication with the device does not occur.

Carefully consider the implications of each keying option when selecting one.

IMPORTANT When you change Electronic Keying parameters online, it interrupts


connections to the device and any devices that are connected through the
device. Connections from other controllers can also be broken.
If an I/O connection to a device is interrupted, the result can be a loss of
data.
For more detailed information on Electronic Keying, see Electronic Keying in Logix 5000
Control Systems Application Technique, publication LOGIX-AT001.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 147


Chapter 11 Standard I/O Modules

Remote I/O Modules Remote I/O modules do not reside in the same chassis as the CompactLogix 5380 or
Compact GuardLogix 5380 controller. The controller connects to the I/O modules via an
Applies to these controllers: EtherNet/IP™ network. The controllers support the use of a wide range of remote I/O modules.
CompactLogix 5380 For maximum performance, we recommend that you use Compact 5000 I/O modules when you
Compact GuardLogix 5380 SIL 2 use remote I/O modules.
Compact GuardLogix 5380 SIL 3
For example, CompactLogix 5380 and Compact GuardLogix 5380 controllers can connect to
following:
• Chassis-based I/O module families, such as Compact 5000 I/O, 1756 ControlLogix® I/O,
1769 Compact I/O™, or 1746 SLC™ I/O modules
• In-cabinet I/O module families, such as 1734 POINT I/O™ or 1794 FLEX™ I/O modules
• On-Machine™ I/O module families, such as 1732E ArmorBlock® I/O modules

IMPORTANT The following network examples are solely intended to show remote I/O
modules in various network topologies. The examples do not address
network communication rates between the controller and the I/O modules.
We recommend, however, that you consider network communication rates
when you determine the best way to incorporate remote I/O modules in your
CompactLogix 5380 system.
For more information, see EtherNet/IP Network Communication Rates on
page 109.
Figure 36 - Remote I/O Modules in a CompactLogix 5380 System on a DLR Network Topology

Compact 5000 I/O EtherNet/IP Adapter


CompactLogix 5380 Controller
Compact 5000 I/O Modules
Compact 5000 I/O Modules

Compact 5000 I/O EtherNet/IP Adapter


Compact 5000 I/O Modules

Remote I/O Modules

PowerFlex® 527 Drive

1734-AENTR Adapter PanelView™ Plus 7 Terminal


Kinetix® 5500 Drives 1734 POINT I/O Modules

148 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 11 Standard I/O Modules

Figure 37 - Remote I/O Modules in a CompactLogix 5380 System on a Linear Network Topology

CompactLogix 5380 Controller 1734-AENTR Adapter


Compact 5000 I/O Modules PowerFlex 527 Drive 1734 POINT I/O Modules

Remote I/O Modules

PanelView Plus 7 Terminal

Compact 5000 I/O EtherNet/IP Adapter Kinetix 5500 Drives


Compact 5000 I/O EtherNet/IP Adapter
Compact 5000 I/O Modules Compact 5000 I/O Modules

Figure 38 - Remote I/O Modules in a CompactLogix 5380 System on a Star Network Topology

CompactLogix 5380 Controller


Compact 5000 I/O Modules
Compact 5000 I/O EtherNet/IP Adapter
Compact 5000 I/O Modules

Stratix® 5700 Switch

Remote I/O Modules


PanelView Plus 7 Terminal

Kinetix 5500 Drive

PowerFlex 527 Drive


1734-AENTR Adapter
1734 POINT I/O Modules

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 149


Chapter 11 Standard I/O Modules

Add Remote I/O Modules to a Project


Before you can add remote I/O modules to a project, you must add the EtherNet/IP
communication module that facilitates communication between the controller and the remote
I/O modules.

There are two methods to add remote I/O modules to the project:
• Discover Modules
• New Module
Discover Modules

The Discover Modules feature is useful when I/O modules are already installed and connected
to the network. When you use Discover Modules to find Ethernet devices, the Logix Designer
application browses based on how Ethernet browsing is configured in RSLinx® Classic
software.
• If the EtherNet/IP driver is used in RSLinx Classic software, the Logix Designer
application automatically detects remote I/O modules.
• If the Ethernet devices driver is used in RSLinx Classic software, you must configure the
IP address for each Ethernet device that you want to display in the Select Module Type
dialog box that is shown on page 150.
• If the Ethernet bus is browsed via a CIP™ router, you must configure the IP address for
each Ethernet device that you want to display in the Select Module Type dialog box that
is shown on page 150.
The tasks in this section apply when you use the EtherNet/IP driver in RSWho to browse the
network.

To use Discover Modules to add a remote I/O module, complete these steps.
1. Go online with your Logix Designer application.
2. Right-click Ethernet and choose Discover Modules.

The Logix Designer application automatically detects available modules that are
installed in the system.
3. At the Select Module Type window, click Create to add a discovered adapter to your
project.

150 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 11 Standard I/O Modules

4. At the New Module window, configure the module properties and click OK.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 151


Chapter 11 Standard I/O Modules

5. At the warning dialog box, click Yes.


If you inhibit the module connection, you must remember to uninhibit the
connection later.

6. Close the Select Module Type dialog box.


7. Right-click 5069 Backplane and choose Discover Modules.

The Logix Designer application automatically detects available modules that are
installed in the system.
8. At the Select Module Type window, click Create to add a discovered module to your
project.

152 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 11 Standard I/O Modules

9. At the New Module window, configure the module properties and click OK.

10. At the warning dialog box, click Yes.


If you inhibit the module connection, you must remember to uninhibit the
connection later.

11. Close the Select Module Type dialog box.

After you add the remote I/O module, consider the following:
• To add remote I/O modules in the same remote location:
- If you cleared the Close on Create checkbox when you created the first I/O module,
repeat steps 8…11.
- If you did not clear the Close on Create checkbox when you created the first I/O
module, repeat steps 7…11.
• To add remote I/O modules in another new remote location, repeat steps 2…11.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 153


Chapter 11 Standard I/O Modules

New Module

You can add a standard I/O module offline or online. If you do not have physical I/O installed, or
you cannot connect to the controller, this is the easiest method to add I/O. To use New Module
to add a remote I/O module, complete these steps.
1. Right-click Ethernet and choose New Module.

2. Select the EtherNet/IP adapter and click Create.


For some modules, the Select Major Revision dialog box can appear. If the
dialog box appears, choose the major revision of the module and click OK.
Remember, if the Series and Revision parameter values do not match those
of the module for which this configuration is intended, your project can
experience module faults.

154 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 11 Standard I/O Modules

3. At the New Module window, configure the module properties and click OK.

4. If you add a module while online, then at the warning dialog box, click Yes.
If you inhibit the module connection, you must remember to uninhibit the
connection later.

5. Close the Select Module Type dialog box.


6. Right-click the newly added EtherNet/IP communication module or the backplane and
choose New Module.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 155


Chapter 11 Standard I/O Modules

7. Select the I/O module that you want to add and click Create.
If you must add multiple I/O modules to the same remote location, you can clear
the Close on Create checkbox before you click Create to skip step 6.
When the Close on Create checkbox is cleared, the select Module Type dialog box
appears automatically after you complete configuration for an I/O module.

8. On the New Module dialog box, configure the I/O module and then click OK.

9. If you add a module while online, choose whether to inhibit the module connection, and
then click Yes.
If you inhibit the module connection, remember to uninhibit the connection
later.

156 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 11 Standard I/O Modules

After you add the remote I/O module, consider the following:
• To add remote I/O modules in the same remote location:
- If you cleared the Close on Create checkbox when you created the first I/O module,
repeat steps 7…8.
- If you did not clear the Close on Create checkbox when you created the first I/O
module, repeat steps 6…8.
• To add remote I/O modules in another new remote location, repeat steps 1….

Add to the I/O Configuration You can add local and remote I/O modules and other devices to the controller configuration
while the project is online.
While Online
Applies to these controllers: IMPORTANT To add I/O modules when the controller is online, the controller mode
CompactLogix 5380 switch must be in the REM or PROG position.
Compact GuardLogix 5380 SIL 2 The Compact 5000 I/O modules must already be installed in the system. You
Compact GuardLogix 5380 SIL 3 cannot install Compact 5000 I/O modules when the system is powered.

The modules and devices you can add while online depends on the software version that you
use. Later versions have more modules and devices that can be added while online.

Add-on Profiles (AOP) for modules are made available between releases of different Logix
Designer application versions. There are cases in which, after you download and install the
AOP file for a module, you can add the module to a project while online.

To see a list of the available AOP files, go to:


https://download.rockwellautomation.com/esd/download.aspx?downloadid=addonprofiles

For more information about how to add to the I/O Configuration while online, see the Logix
5000 Controllers Design Considerations Reference Manual, publication 1756-RM094.

Modules and Devices That Can Be Added While Online


You can add these modules and devices to the CompactLogix 5380 or Compact GuardLogix
5380 controller I/O configuration while online with Logix Designer, version 28 or later.
• Compact 5000 I/O modules - As local or remote I/O modules
• Compact 5000 I/O EtherNet/IP adapters
• 1756 ControlLogix EtherNet/IP modules
• 1756 ControlLogix I/O modules

IMPORTANT These modules cannot be added while online:


• 1756 ControlLogix Motion modules (1756-MO2AE, 1756-HYD02,
1756-MO2AS, 1756-MO3SE, 1756-MO8SE, 1756-MO8SEG, 1756-M16SE)
• ControlLogix 1756-RIO
• ControlLogix 1756-SYNCH
• Safety I/O

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 157


Chapter 11 Standard I/O Modules

Determine When Data CompactLogix 5380 and Compact GuardLogix 5380 controllers update data asynchronously
with the execution of logic. See these flowcharts to determine when a controller, input module,
Is Updated or bridge sends data:
Applies to these controllers: • Input Data Update Flowchart
CompactLogix 5380 • Output Data Update Flowchart
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 Input Data Update Flowchart

IMPORTANT Safety Consideration


Compact GuardLogix standard inputs are updated just like
CompactLogix standard inputs, but Compact GuardLogix safety input
tags (inputs, consumed, and mapped) are updated and frozen at the
beginning of safety task execution. For more information, see the
GuardLogix 5580 and Compact GuardLogix 5380 Controller Systems
Safety Reference Manual, publication 1756-RM012.

Digital without events, analog without RTS, produced tag

Method of Input Data Production Produced tag with data state change events

Digital with Events Enabled

Analog with RTS Enabled

RTSRPI? No

Yes

The module sends data at


The module sends data at the RTS.
the RTS and RPI.

The module sends data at the RPI and


at the change of a specified point.

The producing controller sends data at


the RPI and when an IOT executes.
The Event task in a consuming controller
is only triggered when an IOT instruction
is executed in the producer.

The module or the producing


controller sends data at the RPI.

New data can appear in Input tags at any point in the program scan. If the
control logic reads input tag values in multiple locations, do not assume
that the data remains unchanged throughout the scan of the logic.

158 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 11 Standard I/O Modules

Output Data Update Flowchart

Automatic output
processing of each task.
Method of Output Data Production Output Module Profile Configuration

Cyclic data production at IOT instruction executes. We


the RPI. recommend to minimize the use of IOT
instructions to critical outputs that
must be updated immediately. Module profile lets data be Module profile lets data be
Safety Consideration
sent at the RPI only sent at the RPI or at the end
The safety output RPI is
of task scans
the safety task period.

Data is sent by the Data is sent by the Data is sent by the controller
controller triggered controller triggered No data is sent by automatic triggered by the end of task.
at the RPI. by the user program. output processing

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 159


Chapter 11 Standard I/O Modules

160 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 12
Safety I/O Devices
Add Safety I/O Devices When you add a safety I/O device to the system, define a configuration for the device:
Applies to these controllers:
• Node address for DeviceNet® networks.
Compact GuardLogix 5380 SIL 2
IMPORTANT A Compact GuardLogix® 5380 controller can access devices on a
Compact GuardLogix 5380 SIL 3
DeviceNet network only via a linking devices, for example, the
1788-EN2DN linking device.
The controller can communicate with devices on the DeviceNet
network. However, typically Compact GuardLogix 5380 controllers
use EtherNet/IP™ networks to communicate with safety devices.
• IP address for EtherNet/IP networks.
• Safety network number (SNN). To set the SNN, see page 164.
• Configuration signature. For information on when the configuration signature is set
automatically and when you must set it, see page 168.
• Reaction time limit. For information on setting the reaction time limit, see the
GuardLogix 5580 and Compact GuardLogix 5380 Controller Systems Safety Reference
Manual, publication 1756-RM012.
• Safety input, output, and test parameters complete the device configuration.

IMPORTANT You cannot add safety I/O devices while online with the controller.

Configure Safety I/O Devices Add the safety I/O device to the I/O configuration of the controller project.
Applies to these controllers: Some safety I/O devices support both standard and safety data. The device
Compact GuardLogix 5380 SIL 2 definition settings define what data is available.
Compact GuardLogix 5380 SIL 3 1. Right-click the Ethernet network and select New Module.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 161


Chapter 12 Safety I/O Devices

2. On the Select Module Type dialog box, select the safety I/O device and click Create.

Use the filters to reduce the list of devices to choose from.

3. Enter a name and IP address for the new device.


If your network uses network address translation (NAT), see Using Network Address
Translation (NAT) with CIP Safety Devices on page 163.

4. To modify the module definition settings, click Change.

IMPORTANT For safety I/O devices, do not use Disable Keying.


See Electronic Keying on page 147.
5. To modify the safety network number, click the button.
See Set the SNN of a Safety I/O Device on page 164.

162 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 12 Safety I/O Devices

6. Set the connection reaction time limit on the Safety tab.


For more information, see the GuardLogix 5580 and Compact GuardLogix 5380
Controller Systems Safety Reference Manual, publication 1756-RM012.
7. To complete the configuration of the safety I/O device, refer to the user documentation
and the Logix Designer online help.

Using Network Address NAT translates one IP address to another IP address via a NAT-configured router or switch.
The router or switch translates the source and destination addresses within data packets as
Translation (NAT) with CIP traffic passes between subnets.
Safety Devices
This service is useful if you must reuse IP addresses throughout a network. For example, NAT
Applies to these controllers: makes it possible for devices to be segmented into multiple identical private subnets while
Compact GuardLogix 5380 SIL 2 maintaining unique identities on the public subnet, such as for multiple identical machines or
Compact GuardLogix 5380 SIL 3 lines.

This section only applies to safety users where the controller and the devices it talks to are on
separate sides of the NAT-configured router or switch.

With CIP Safety™, the IP address of the device is part of the unique node reference that is part
of the protocol. The device compares the IP address portion of the unique node reference in
CIP Safety packets to its own IP address, and rejects any packets where they do not match.
The IP address in the unique node reference must be the NAT'ed IP address. The controller
uses the translated address, but the CIP Safety protocol requires the actual address of the
device.

If you are using NAT to communicate with a CIP Safety device, follow these steps to set the IP
address.
1. In the IP Address field, type the IP address that the controller will use.
This is usually the IP address on the public network when using NAT.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 163


Chapter 12 Safety I/O Devices

2. Click Advanced to open the Advanced Ethernet Settings dialog box.

3. Select the checkbox to indicate that this device and the controller communicate
through NAT devices.
4. Enter the actual device address.
If you configured the IP address using the rotary switches, this is the
address that you set on the device. Alternately, the actual device address is
the same address that is shown on the Internet Protocol tab.
5. Click OK.

Set the SNN of a Safety I/O A time-based SNN is automatically assigned when you add the first safety I/O device on the
network. This does not apply to the controller backplane or Ethernet ports since the controller
Device counts as a device on the network.
Applies to these controllers:
When subsequent safety devices are added to the same network, they are assigned the same
Compact GuardLogix 5380 SIL 2
SNN as defined in the lowest address on that CIP Safety network or the controller itself in the
Compact GuardLogix 5380 SIL 3 case of ports attached to the controller. For most applications, the automatic, time-based SNN
is sufficient.

If your application requires you to manually assign the SNN of safety I/O devices, you only have
to assign the SNN of the first safety I/O device you add in a remote network or backplane.
Logix Designer then assigns the SNN of the first device to any additional devices that you add
to that same remote network or backplane.
For an explanation of the SNN, see the GuardLogix 5580 and Compact GuardLogix 5380
Controller Systems Safety Reference Manual, publication 1756-RM012.

164 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 12 Safety I/O Devices

Change a Safety I/O device SNN


Follow these steps to change the safety I/O device SNN to a manual assignment:
1. In the I/O configuration, right-click the remote EtherNet/IP communication device and
select New Module.
2. Select the safety I/O device and click Create.
3. On the New Module dialog box, click to the right of the safety network number.

4. On the Safety Network Number dialog box, select Manual.


5. Enter the SNN as a value from 1…9999 (decimal) and click OK.

6. On the New Module dialog box, click OK.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 165


Chapter 12 Safety I/O Devices

Copy and Paste a Safety I/O Device SNN


If you must apply an SNN to other safety I/O devices, you can copy and paste the SNN.
Copy an SNN
1. On the General view of the Module Properties dialog box, click to the right of the
SNN.

2. On the Safety Network Number dialog box, click Copy.

166 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 12 Safety I/O Devices

Paste an SNN
1. On the General tab of the Module Properties dialog box, click to the right of the SNN.

2. On the Safety Network Number dialog, click Paste.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 167


Chapter 12 Safety I/O Devices

Safety I/O Device Signature Each safety device has a unique configuration signature that defines the device configuration.
The configuration signature is composed of an ID number, date, and time, and is used to verify
Applies to these controllers: the device’s configuration.
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 Configuration via the Logix Designer Application
When the I/O device is configured via the Logix Designer application, the configuration
signature is generated automatically. You can view and copy the configuration signature via
the Safety tab of the device properties.
Figure 39 - View and Copy the Configuration Signature

Reset Safety I/O Device to Out-of-box Condition


If a Guard I/O™ device was used previously, clear the existing configuration before installing it
on a safety network by resetting the device to its out-of-box condition.

When the controller project is online, the Safety tab of the device properties displays the
current configuration ownership. When the opened project owns the configuration, Local is
displayed. When a second device owns the configuration, Remote is displayed, along with the
SNN and node address or slot number of the configuration owner. Communication error is
displayed if the device read fails.

If the connection is local, you must inhibit the device connection before you reset ownership.
Follow these steps to inhibit the device.
1. Right-click the device and choose Properties.
2. Click the Connection tab.
3. Check Inhibit Connection.
4. Click Apply and then OK.

168 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 12 Safety I/O Devices

Follow these steps to reset the device to its out-of-box configuration when online.
1. Right-click the device and choose Properties.
2. Click the Safety tab.
3. Click Reset Ownership.
.

You cannot reset ownership when there are pending edits to the device
properties, when a safety signature exists, or when safety-locked.

I/O Device Address Format When you add a device to the I/O configuration, the Logix Designer application creates
controller-scoped tags for the device.
Applies to these controllers:
Compact GuardLogix 5380 SIL 2 I/O information is presented as a set of tags. Each tag uses a structure of data, depending on
Compact GuardLogix 5380 SIL 3 the type and features of the I/O device. The name of a tag is based on the name of the device.
A safety I/O device address follows this example: devicename:Type.Member
Table 22 - Safety I/O Device Address Format
Where Is
devicename The name of the safety I/O device
Input: I
Type Type of data Output: O
Specific data from the I/O device
devicename:I.RunMode(1)
Input-only device devicename:I.ConnectionFaulted(1)
devicename:I.Input Members
devicename:I.RunMode(1)
Member Output-only device devicename:I.ConnectionFaulted(1)
devicename:O.Output Members
devicename:I.RunMode(1)
Combination I/O devicename:I.ConnectionFaulted(1)
devicename:I.Input Members
devicename:O.Output Members
(1) This member is required.

For more information on addressing standard I/O devices, see the Logix 5000 Controllers I/O
and Tag Data Programming Manual, publication 1756-PM004.

Monitor Safety I/O You can monitor safety I/O device status via Explicit Messaging or via the status indicators on
the device. For more information, see the product documentation for the device.
Device Status
Replace a Safety I/O Device You can replace safety I/O devices while they are connected to Compact GuardLogix
controllers.
Applies to these controllers:
Compact GuardLogix 5380 SIL 2 Configuration Ownership
Compact GuardLogix 5380 SIL 3
When the controller project is online, the Safety tab of the device Properties dialog box
displays the current configuration ownership:
• When the opened project owns the configuration, Local is displayed.
• When a second device owns the configuration, Remote is displayed, along with the
safety network number (SNN), and node address or slot number of the configuration
owner.
• If the device read fails, Communication error is displayed.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 169


Chapter 12 Safety I/O Devices

If the connection is local, you must inhibit the device connection before you reset ownership.
Follow these steps to inhibit the device.
1. Right-click the device and choose Properties.
2. Click the Connection tab.
3. Check Inhibit Connection.
4. Click Apply and then OK.

Replacement Configuration
You can use the Logix Designer application to replace a safety I/O device on an Ethernet
network.

To replace a Guard I/O™ device on a DeviceNet network, your choice depends on the type of
device.
Table 23 - Software
If you are using a Use See
Safety I/O device on EtherNet/IP network The Logix Designer Below
application
1791DS Guard I/O device via a 1788-EN2DN Logix Designer application Below
linking device
1734 POINT Guard I/O™ device via a RSNetWorx™ for DeviceNet See the POINT Guard I/O Safety devices
1788-EN2DN linking device and a software User Manual, publication 1734-UM013.
1734-PDN adapter

• If you are relying on a portion of the CIP Safety system to maintain SIL or PL-rated
behavior during device replacement and functional testing, the Always Allow Automatic
Configuration option cannot be used.
For more information, see Only Allow Automatic Configuration When No Safety
Signature Exists on page 172.
• If the entire routable CIP Safety control system is not being relied on to maintain SIL or
PL-rated behavior during the replacement and functional testing of a device, the Always
Allow Automatic Configuration option can be used.
For more information, see Always Allow Automatic Configuration on page 175.

Safety I/O device replacement is configured on the Safety tab of the Controller Properties
dialog box.

170 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 12 Safety I/O Devices

Figure 40 - Safety I/O Device Replacement

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 171


Chapter 12 Safety I/O Devices

Only Allow Automatic Configuration When No Safety Signature Exists


When a safety I/O device is replaced, the configuration is downloaded from the safety
controller if the DeviceID of the new device matches the original. The DeviceID is a
combination of the node/IP address and the SNN and is updated whenever the SNN is set.

If you select the Only Allow Automatic Configuration When No Safety Signature Exists option,
follow the guidance in Table 24 to replace a safety I/O device based on your scenario. After you
complete the steps, the DeviceID matches the original and enables the safety controller to
download the proper device configuration and re-establish the safety connection.
Table 24 - Replace a Device
Replacement Device
Safety Signature Exists Action Required
Condition
No No SNN (out-of-box) None. The device is ready for use.
Same SNN as original safety None. The device is ready for use.
Yes or No task configuration
See Scenario 1—Replacement Device Is Out-of-box and
Yes No SNN (out-of-box) Safety Signature Exists on page 172.
See Scenario 2—Replacement Device SNN Is Different
Yes
Different SNN from original from Original and Safety Signature Exists on page 173.
safety task configuration See Scenario 3—Replacement Device SNN Is Different
No from Original and No Safety Signature Exists on page 175.

Scenario 1—Replacement Device Is Out-of-box and Safety Signature Exists


1. Remove the old I/O device and install the new device.
2. Right-click the replacement safety I/O device and choose Properties.
3. To open the Safety Network Number dialog box, click to the right of the safety
network number.

172 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 12 Safety I/O Devices

4. Click Set.

5. Verify that the Network Status (NS) status indicator is alternating red/green on the
correct device before clicking Yes on the confirmation dialog box to set the SNN and
accept the replacement device.
6. Follow your company-prescribed procedures to functionally test the replaced I/O device
and system and to authorize the system for use.
Scenario 2—Replacement Device SNN Is Different from Original and Safety Signature
Exists
1. Remove the old I/O device and install the new device.
2. Right-click your safety I/O device and select Properties.
3. In the navigation pane, click Safety.
4. Click Reset Ownership.

5. Click OK.
6. Right-click the device and select Properties.
7. Click to the right of the safety network number to open the Safety Network
Number dialog box.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 173


Chapter 12 Safety I/O Devices

8. Click Set.

9. Verify that the Network Status (NS) status indicator is alternating red/green on the
correct device before clicking Yes on the confirmation dialog box to set the SNN and
accept the replacement device.
10. Follow your company-prescribed procedures to functionally test the replaced I/O device
and system and to authorize the system for use.

174 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 12 Safety I/O Devices

Scenario 3—Replacement Device SNN Is Different from Original and No Safety Signature
Exists
1. Remove the old I/O device and install the new device.
2. Right-click your safety I/O device and select Properties.
3. In the navigation pane, select Safety.
4. Click Reset Ownership.

5. Click OK.
6. Follow your company-prescribed procedures to functionally test the replaced I/O device
and system and to authorize the system for use.

Always Allow Automatic Configuration

ATTENTION: Select the Always Allow Automatic Configuration option only if


the entire CIP Safety Control System is not being relied on to maintain SIL 2
or SIL 3 behavior during the replacement and functional testing of a device.
Do not place devices that are in the out-of-box condition on a CIP Safety
network when the Always Allow Automatic Configuration option is selected,
except while following this replacement procedure.
When the Always Allow Automatic Configuration option is selected in the controller project, the
controller automatically checks for and connects to a replacement device that meets all of
these requirements:
• The controller has configuration data for a compatible device at that network address.
• The device is in out-of-box condition or has an SNN that matches the configuration.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 175


Chapter 12 Safety I/O Devices

If the Always Allow Automatic Configuration option is selected, follow these steps to replace a
safety I/O device.
1. Remove the old I/O device and install the new device.
a. If the device is in out-of-box condition, go to step 5.
No action is needed for the Compact GuardLogix controller to take ownership of the
device.
b. If an SNN mismatch error occurs, go to the next step to reset the device to out-of-
box condition.
2. Right-click the safety I/O device and select Properties.
3. Click the Safety tab.
4. Click Reset Ownership and click OK.

5. Follow your company-prescribed procedures to functionally test the replaced I/O device
and system and to authorize the system for use.

176 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 13
Develop Standard Applications
Elements of a A control application consists of several elements that require planning for efficient
application execution. Application elements include the following:
Control Application
• Tasks
Applies to these controllers: • Programs
CompactLogix™ 5380
• Routines
Compact GuardLogix® 5380 SIL 2
Compact GuardLogix 5380 SIL 3
• Parameters and Local Tags
• Add-On Instructions
Figure 41 - Elements of a Control Application

Controller Fault Handler

Task 32

Task 1
Configuration

Status

Program 1000 Watchdog

Program 1 Program Tags


and Program
Main Routine
Parameters

Fault Routine

Other Routines

Add-On Instruction
Controller (global) Tags I/O Data System-shared Data
Definition

Tasks The controller lets you use multiple tasks to schedule and prioritize the execution of your
programs based on criteria. This multitasking allocates the processing time of the controller
among the operations in your application:
• The controller executes one task at a time.
• One task can interrupt the execution of another and take control based on its priority.
• In any given task, you can use multiple programs. One program executes at a time.
• You can display tasks in the Controller or Logical Organizer views, as necessary.

A large number of tasks can make it difficult to optimally tune your system.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 177


Chapter 13 Develop Standard Applications

Figure 42 - Task Within a Control Application


Controller Fault Handler

Task 32

Task 1
Configuration

Status

Period
Program 1000
Watchdog
Program 1
Program Tags and
Main Routine Program
Parameters
Fault Routine

Other
Routines

Controller (global) Add-On Instruction System-shared


I/O Data
Tags Definition Data

Figure 43 - Tasks
Controller Organizer Logical Organizer

Main Task
(continuous)

Main Task
(continuous)

Task 2 Task 2
(periodic) (periodic)

A task provides scheduling and priority information for a set of one or more programs. Use the
Task Properties dialog box to configure tasks as continuous, periodic, or event.

178 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 13 Develop Standard Applications

Figure 44 - Configuring the Task Type

Table 25 explains the types of tasks you can configure.


Table 25 - Task Types and Execution Frequency
Task Type Task Execution Description
The continuous task runs in the background. Any CPU time that is not allocated to other operations (such as motion
and other tasks) is used to execute the programs in the continuous task.
Continuous Constant • The continuous task runs constantly. When the continuous task completes a full scan, it restarts immediately.
• A project does not require a continuous task. If used, you use only one continuous task.
A periodic task performs a function at an interval.
• Whenever the time for the periodic task expires, the task interrupts any lower priority tasks, executes once, and
At a set interval, such as every
Periodic returns control to where the previous task left off.
100 ms
• You can configure the time period from 0.1…2,000,000.00 ms. The default is 10 ms. It is also controller and
configuration dependent.
An event task performs a function when an event (trigger) occurs. The trigger for the event task can be the following:
• Module input data change of state
• A consumed tag trigger
• An EVENT instruction
Event Immediately when an event occurs • An axis trigger
• A motion event trigger
You can configure an optional timeout interval for missed event triggers. The timeout interval causes the event tasks
to execute even in the absence of the trigger. Set the Check the Execute Task If No Event Occurs Within <timeout
period> checkbox for task.

The CompactLogix 5380 and Compact GuardLogix 5380 controllers support up to 32 tasks.
Only one of the tasks can be continuous.

A task can have up to 1000 programs, each with its own executable routines and program-
scoped tags. Once a task is triggered (activated), the programs that are assigned to the task
execute in the order in which they are grouped. Programs can appear only once in the
Controller Organizer and multiple tasks cannot share them.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 179


Chapter 13 Develop Standard Applications

Event Task with Compact 5000 I/O Modules

Compact 5000™ I/O safety input modules cannot trigger events.

Some Compact 5000 I/O digital input modules can trigger an Event task. For example,
complete these steps to configure an Event task with a 5069-IB16F module input state change
that triggers the event.
1. Configure the 5069-IB16F input module to trigger the Event task. The following tasks are
required.
a. Use the Data with Events connection type in the 5069-IB16F module definition.
b. Enable the Event.
c. Select at least one point on the module to participate in the event.
d. Define what constitutes an event, for example, a state change from Off to On.
e. Choose which edge of the event triggers the event. That is, the rising edge, the falling
edge, or both can trigger an event.
You can also latch an event and enable independent point triggers.
2. Create an Event task in your project.
3. Configure the Event task.
- You must choose the event trigger. For example, you can choose Module Input Data
State Change as the trigger.
- Link the task to the appropriate Event Input tag on the module.

For more information on how to use event tasks with Compact 5000 I/O modules, see the
Compact 5000 I/O Digital and Safety Module User Manual, publication 5000-UM004

For more information on how to use event tasks in general, see the Logix 5000 Controllers
Tasks, Programs, and Routines Programming Manual, publication 1756-PM005.

Task Priority
Each task in the controller has a priority level. The operating system uses the priority level to
determine which task to execute when multiple tasks are triggered. A higher priority task
interrupts any lower priority task. The continuous task has the lowest priority and a periodic or
event task interrupts it.

The continuous task runs whenever a periodic task is not running. Depending on the
application, the continuous task could run more frequently than the periodic tasks, or much
less frequently. There can also be large variability in the frequency that the task is called, and
its scan time (due to the effect of the other periodic tasks).

IMPORTANT If you configure multiple tasks with the same priority, the controller
timeslices them, which de-optimizes their application. This is not
recommended.

You can configure periodic and event tasks to execute from the lowest priority of 15 up to the
highest priority of 1. Use the Task Properties dialog box to configure the task priority.

180 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 13 Develop Standard Applications

Figure 45 - Configure Task Priority

Programs The controller operating system is a pre-emptive multitasking system that is in compliance
with IEC 61131-3. This system provides the following:
• Programs to group data and logic
• Routines to encapsulate executable code that is written in one programming language

Each program contains the following:


• Local Tags
• Parameters
• A main executable routine
• Other routines
• An optional fault routine

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 181


Chapter 13 Develop Standard Applications

Figure 46 - Program Within a Control Application

Controller Fault Handler

Task 32

Task 1
Configuration

Status

Watchdog
Program 1000

Program 1
Program Tags and
Main Routine Program
Parameters

Fault Routine

Other Routines

Add-On Instruction
Controller (global) Tags I/O Data System-shared Data
Definition

Figure 47 - Programs

Scheduled and Unscheduled Programs


The scheduled programs within a task execute to completion from first to last. Programs that
are not attached to any task show up as unscheduled programs.

Unscheduled programs within a task are downloaded to the controller with the entire project.
The controller verifies unscheduled programs but does not execute them.

You must schedule a program within a task before the controller can scan the program. To
schedule an unscheduled program, use the Program/Phase Schedule tab of the Task
Properties dialog box.

182 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 13 Develop Standard Applications

Figure 48 - Scheduling an Unscheduled Program

Routines A routine is a set of logic instructions in one programming language, such as Ladder Diagram.
Routines provide the executable code for the project in a controller.

Each program has a main routine. The main is the first routine to execute when the controller
triggers the associated task and calls the associated program. Use logic, such as the Jump to
Subroutine (JSR) instruction, to call other routines.
You can also specify an optional program fault routine. The controller executes this routine if it
encounters an instruction-execution fault within any of the routines in the
associated program.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 183


Chapter 13 Develop Standard Applications

Figure 49 - Routines in a Control Application

Controller Fault Handler

Task 32

Task 1
Configuration

Status

Watchdog
Program 1000

Program 1
Program Tags and
Main Routine Program
Parameters

Fault Routine

Other Routines

Add-On Instruction
Controller (global) Tags I/O Data System-shared Data
Definition

Figure 50 - Routines

Routine

Routine Routine

Routine

Parameters and Local Tags With a Logix 5000™ controller, you use a tag (alphanumeric name) to address data (variables).
In Logix 5000 controllers, there is no fixed, numeric format. The tag name identifies the data
and lets you do the following:
• Organize your data to mirror your machinery.
• Document your application as you develop it.

The following example shows data tags that are created within the scope of the Main Program
of the controller.

184 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 13 Develop Standard Applications

Figure 51 - Tags Example


Controller Organizer —Main Program Parameters and Local Tags Logical Organizer —Main Program Parameters and Local Tags

Program Tags Window—Main Program Parameters and Local Tags

Analog I/O Device

Integer Value
Storage Bit
Counter
Timer
Digital I/O Device

There are several guidelines for how to create and configure parameters and local tags for
optimal task and program execution. For more information, see the Logix 5000 Controllers and
I/O Tag Data Programming Manual, publication 1756-PM004.

Program Parameters
Program parameters define a data interface for programs to facilitate data sharing. You can
achieve data sharing between programs through either pre-defined connections between
parameters, or directly through a special notation.

Unlike local tags, all program parameters are publicly accessible outside of the program.
Additionally, HMI external access can be specified on individual basis for each parameter.

There are several guidelines for how to create and configure parameters and local tags for
optimal task and program execution:
• Logix 5000 Controllers and I/O Tag Data Programming Manual, publication 1756-PM004
• Logix 5000 Controllers Program Parameters Programming Manual, publication 1756-
PM021
• Logix 5000 Controllers Design Considerations Reference Manual, publication 1756-RM094

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 185


Chapter 13 Develop Standard Applications

Programming Languages The Studio 5000 Logix Designer® application supports these programming languages.
Language Is best used in programs with
Continuous or parallel execution of multiple operations (not sequenced)
Boolean or bit-based operations
Complex logical operations
Message and communication processing
Ladder Diagram (LD) Machine interlocking
Operations that service or maintenance personnel have to interpret to
troubleshoot the machine or process
IMPORTANT: Ladder Diagram is the only programming language that can
be used with the Safety Task on Compact GuardLogix 5380 controllers.
Continuous process and drive control
Function Block Diagram (FBD) Loop control
Calculations in circuit flow
High-level management of multiple operations
Repetitive sequence of operations
Sequential Function Chart (SFC) Batch process
Motion control that uses Structured Text
State machine operations
Complex mathematical operations
Structured Text (ST) Specialized array or table loop processing
ASCII string handling or protocol processing

For information about programming in these languages, see the


Logix 5000 Controllers Common Procedures Programming Manual, publication 1756-PM001.

Add-On Instructions With the Logix Designer application, you can design and configure sets of commonly used
instructions to increase project consistency. Similar to the built-in instructions that are
contained in Logix 5000 controllers, these instructions you create are called Add-On
Instructions.

Add-On Instructions reuse common control algorithms. With them, you can do the following:
• Ease maintenance by creating logic for one instance.
• Apply source protection to help protect intellectual property.
• Reduce documentation development time.

You can use Add-On Instructions across multiple projects. You can define your instructions,
obtain them from somebody else, or copy them from another project. Table 26 explains some
of the capabilities and advantages of use Add-On Instructions.
Table 26 - Add-On Instruction Capabilities
Capability Description
With Add-On Instructions, you can combine your most commonly used logic into sets of reusable instructions. You save time when you
create instructions for your projects and share them with others. Add-On Instructions increase project consistency because commonly used
Save Time algorithms all work in the same manner, regardless of who implements the project.
IMPORTANT: You cannot edit AOIs while online. You can overwrite existing AOIs by using the partial import online feature.
You use one of these editors to create Add-On Instructions:
• Ladder Diagram
Use Standard Editors
• Function Block Diagram
• Structured Text
You can export Add-On Instructions to other projects and copy and paste them from one project to another. Give each instruction a unique,
Export Add-On Instructions descriptive name to make it easier to manage and reuse your collection of Add-On Instructions.
Use Context Views Context views let you visualize the logic of an instruction to perform instant and simple online troubleshooting of your Add-On Instructions.
When you create an instruction, you enter information for the description fields. Each instruction definition includes revision, change
Document the Instruction history, and description information. The description text also becomes the help topic for the instruction.
When you create Add-On Instructions, you can limit users of your instructions to read-only access. You can also bar access to the internal
Apply Source Protection logic or local parameters that the instructions use. This source protection lets you stop unwanted changes to your instructions and helps
protect your intellectual property.

186 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 13 Develop Standard Applications

Once defined in a project, Add-On Instructions behave similarly to the built-in instructions in
Logix 5000 controllers.

With Studio 5000 Logix Designer Version 31 and greater, Add-On Instructions appear under the
Assets folder in the organizer. They appear on the instruction tool bar for easy access along
with internal instructions.
Figure 52 - Add-On Instructions (Studio 5000 Logix Designer Version 31 Example)

Instruction Toolbar

Extended Properties The Extended Properties feature lets you define more information, such as limits, engineering
units, or state identifiers for various components within the controller project.
Component Extended Properties
Tag In the tag editor, add extended properties to a tag.
User-defined data type In the data type editor, add extended properties to data types.
In the properties that are associated with the Add-On Instruction definition,
Add-On Instructions add extended properties to Add-On Instructions.

Pass-through behavior is the ability to assign extended properties at a higher level of a


structure or Add-On Instruction and have that extended property automatically available for all
members. Pass-through behavior is available for descriptions, state identifiers, and
engineering units and you can configure it.

Configure pass-through behavior on the Project tab of the Controller Properties dialog box. If
you choose not to show pass-through properties, only extended properties that are configured
for a given component are displayed.

Pass-through behavior is not available for limits. When an instance of a tag is created, if limits
are associated with the data type, the instance is copied.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 187


Chapter 13 Develop Standard Applications

Use the .@Min and .@Max syntax to define tags that have limits. There is no indication in the
tag browser that limits extended properties are defined for a tag. If you try to use extended
properties that have not been defined for a tag, the editors show a visual indication and the
routine does not verify. Visual indicators include:
• A rung error in Ladder Logic.
• A verification error X in Function Block Diagrams.
• The error underlined in Structured Text.

You can access limit extended properties that the .@Min and .@Max syntax defines. However,
you cannot write to extended properties values in logic.

For more information on Extended Properties, see the Logix 5000 Controllers I/O and Tag Data
Programming Manual, publication 1756-PM004.

Access the Module Object The MODULE object provides status information about a module. To select a particular module
object, set the Object Name operand of the GSV/SSV instruction to the module name. The
from an Add-On Instruction specified module must be present in the I/O Configuration section of the controller organizer
and must have a device name.

You can access a MODULE object directly from an Add-On Instruction. Previously, you could
access the MODULE object data but not from within an Add-On Instruction.

You must create a Module Reference parameter when you define the Add-On Instruction to
access the MODULE object data. A Module Reference parameter is an InOut parameter of the
MODULE data type that points to the MODULE Object of a hardware module. You can use
module reference parameters in both Add-On Instruction logic and program logic.

For more information on the Module Reference parameter, see the Logix Designer application
online help and the Logix 5000 Controllers Add-On Instructions Programming Manual,
publication 1756-PM010.

The MODULE object uses these attributes to provide status information:


• EntryStatus
• FaultCode
• FaultInfo
• FWSupervisorStatus
• ForceStatus
• Instance
• LEDStatus
• Mode
• Path

188 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 13 Develop Standard Applications

Monitor Controller Status The controller uses Get System Value (GSV) and Set System Value (SSV) instructions to get and
set (change) controller data. The controller stores system data in objects.

The GSV instruction retrieves the specified information and places it in the destination. The
SSV instruction sets the specified attribute with data from the source. Both instructions are
available from the Input/Output tab of the Instruction toolbar.
Figure 53 - GSV and SSV Instructions for Monitoring and Setting Attributes

When you add a GSV/SSV instruction to the program, the object classes, object names, and
attribute names for the instruction are shown. For the GSV instruction, you can get values for
the available attributes. For the SSV instruction, only the attributes that you can set are shown.

Some object types appear repeatedly, so you have to specify the object name. For example,
there can be several tasks in your application. Each task has its own Task object that you
access by the task name.

The GSV and SSV instructions monitor and set many objects and attributes. See the online help
for the GSV and SSV instructions.

Monitor I/O Connections If communication with a device in the I/O configuration of the controller does not occur in an
application-specific period, the communication times out and the controller produces
warnings.

The minimum timeout period that, once expired without communication, causes a timeout is
100 ms. The timeout period can be greater, depending on the RPI of the application. For
example, if your application uses the default RPI = 20 ms, the timeout period is 160 ms.

For more information on how to determine the time for your application, see the
Knowledgebase Article EtherNet/IP Reduced Heartbeats as of RSLogix5000 version 16.

When a timeout does occur, the controller produces these warnings;


• I/O Fault status information scrolls across the 4-character status display of the
controller.
• A shows over the I/O configuration folder and over the devices that have timed out.
• A module fault code is produced. You can access the fault code via the following:
- The Module Properties dialog box
- A GSV instruction

For more information about I/O faults, see the Logix 5000 Controllers Major, Minor, and I/O
Faults Programming Manual, publication 1756-PM014.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 189


Chapter 13 Develop Standard Applications

Determine If I/O Communication Has Timed Out


This example can be used with the CompactLogix 5380 or Compact GuardLogix 5380
controllers, and help determine if controller communication has timed out:
• The GSV instruction gets the status of the I/O status indicator (via the LEDStatus
attribute of the Module object) and stores it in the IO_LED tag.
• IO_LED is a DINT tag that stores the status of the I/O status indicator or status display
on the front of the controller.
• If IO_LED equals 2, at least one I/O connection has been lost and the Fault_Alert is set.
Figure 54 - GSV Used to Identify I/O Timeout

IMPORTANT Safety Consideration


Each Safety I/O module has a connection status in the module defined
tag.

Determine If I/O Communication to a Specific I/O Module Has Timed Out


If communication times out with a device (module) in the I/O configuration of the controller,
the controller produces a fault code and fault information for the module. You can use GSV
instructions to get fault code and information via the FaultCode and FaultInfo attributes of the
Module object.

For safety I/O modules, see the GuardLogix 5580 and Compact GuardLogix 5380 Controller
Systems Safety Reference Manual, publication 1756-RM012.

Automatic Handling of I/O Module Connection Faults


You can use an I/O connection error to cause the Controller Fault Handler to execute. To do so,
set the module property that causes a major fault to result from an I/O connection error. The
major fault causes the execution of the Controller Fault Handler.

IMPORTANT You cannot program Safety I/O module connections or safety


produce/consume connections to automatically cause a major fault on
the controller. See Develop Standard Applications on page 177.

It can be important to interrupt your normal program scan to handle an I/O connection fault. In
this case, set the 'Major Fault On Controller If Connection Fails While In Run Mode' and put the
logic in the Controller Fault Handler.

190 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 13 Develop Standard Applications

Figure 55 - I/O Connection Fault Causes Major Fault

You can configure the application so that a response to a failed I/O module connection can
wait until the next program scan. In this case, put the logic in a normal routine and use the GSV
technique that is described on page 190 to call the logic.
First, develop a routine in the Controller Fault Handler that can respond to
I/O connection faults. Then, in the Module Properties dialog box of the I/O module or parent
communication module, check Major Fault On Controller If Connection Fails While in Run Mode.
It takes at least 100 milliseconds to detect an I/O connection loss, even if the
Controller Fault Handler is used.
For more information about programming the Controller Fault Handler, see the Logix 5000
Major, Minor, and I/O Faults Programming Manual, publication 1756-PM014.

Sample Controller Projects


Logix Designer includes sample projects that you can copy and modify to fit your application.
To access the sample projects, choose Sample Project in the Studio 5000® environment.
Figure 56 - Opening Sample Projects

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 191


Chapter 13 Develop Standard Applications

Notes:

192 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 14
Develop Safety Applications
You can use both standard (non-safety-related) and safety-related components in the
GuardLogix® control system. Within a GuardLogix project, you can perform standard
automation control from standard tasks. GuardLogix 5580 controllers and Compact GuardLogix
5380 controllers provide the same functionality as other controllers. What differentiates the
controllers from standard controllers is that the controllers also provide a SIL 2 or SIL 3
capable safety task.

However, a logical and visible distinction is required between the standard and safety-related
portions of the application. The Studio 5000 Logix Designer® application provides this
differentiation via the safety task, safety programs, safety routines, safety tags, and safety I/O
devices:
• GuardLogix 5580 controllers support both SIL 2 and SIL 3 levels of safety control with
the safety task.
• Compact GuardLogix 5380 controllers support SIL 2 or SIL 3 levels(1) of safety control
with the safety task.

Safety Overview This chapter explains the components that make up a safety project and the features that help
protect safety application integrity, such as the safety signature and safety-locking.
Applies to these controllers:
Compact GuardLogix 5380 SIL 2 The GuardLogix 5580 and Compact GuardLogix 5380 Controller Systems Safety Reference
Compact GuardLogix 5380 SIL 3 Manual, publication 1756-RM012 addresses the following topics:
• Guidelines and requirements for developing and commissioning safety applications,
including the use of Add-on Profiles
• Creating a detailed project specification
• Writing, documenting, and testing the application
• Generating the safety signature to identify and help protect the project
• Confirming the project by printing or displaying the uploaded project and manually
comparing the configurations, safety data, and safety program logic
• Verifying the project through test cases, simulations, functional verification tests, and
an independent safety review, if required
• Locking the safety application
• Calculating system reaction time

ATTENTION: Performing an on-line modification (to logic, data, or


configuration) can affect the Safety Functions of the system if the
modification is performed while the application is running. A modification
should only be attempted if absolutely necessary. Also, if the modification is
not performed correctly, it can stop the application. Therefore, when the
safety signature is deleted to make an online edit to the safety task, before
performing an online modification alternative safety measures must be
implemented and be present for the duration of the update.

(1) SIL level support depends on the catalog number. See the GuardLogix 5580 and Compact GuardLogix 5380 Controller Systems
Reference Manual, 1756-RM012.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 193


Chapter 14 Develop Safety Applications

Program Safety Applications Figure 57 shows the steps that are required for commissioning a GuardLogix system. For an
explanation of those steps, see the GuardLogix 5580 and Compact GuardLogix 5380 Controller
Systems Safety Reference Manual, publication 1756-RM012.
Figure 57 - Commission the System
Specification of the Safety Function

Create the Project Create the Project


Online Offline

Attach to Controller and Download

Test the Application Program

Generate the Safety Signature Make Required


Modifications

Validate the Project

Validation No Delete Safety Signature


Successful?

Yes

Confirm the Project

Record Safety Signature

Fill out the Safety Checklists

Safety Assessment

Project No
Valid?

Yes

Lock the Controller

194 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15

Develop Secure Applications

These CompactLogix™ 5380 controllers support IEC-62443-4-2 SL 1 security requirements:


Applies to these controllers: • CompactLogix 5380 standard controllers, firmware revision 36 or later
CompactLogix 5380 • CompactLogix 5380 NSE, XT, K, and Process controllers, firmware revision 36 or later

Compact GuardLogix® 5380 safety controllers do not support IEC-62443-4-2 SL 1 security


requirements.

To help meet these requirements, you must use this publication and the Security Configuration
User Manual, publication SECURE-UM001. The Security Configuration User Manual describes
how to configure and use Rockwell Automation products to improve the security of your
industrial automation system.

The controller accepts all values appropriate for a tag data type, and it is the responsibility of
the user program to specify valid ranges and perform validity to check for those ranges. The
controller verifies incoming messages for syntax, length, and format.

You can apply these same measures to other CompactLogix and Compact GuardLogix
controllers, but without the certification.
Resource Description
Provides guidance on how to conduct vulnerability
Security Design Guide Reference Manual, assessments, implement Rockwell Automation products in a
publication SECURE-RM001 secure system, harden the control system, manage user
access, and dispose of equipment.
Describes how to configure security for the Studio 5000 Logix
Logix 5000 Controllers Security Programming Designer® application, and explains how to configure source
Manual, publication 1756-PM016 protection for your logic and projects.
CIP Security Application Technique, publication Describes how to plan an implement a Rockwell Automation
SECURE-AT001 system that supports the CIP Security™ protocol.
Defines manufacturing-focused reference architectures to
Converged Plantwide Ethernet (CPwE) Design and help accelerate the successful deployment of standard
Implementation Guide, publication ENET-TD001 networking technologies and convergence of manufacturing
and enterprise/business networks.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 195


Chapter 15 Develop Secure Applications

Controller Security Features For the CompactLogix controller to comply with the certification requirements, implement the
control system with these other security-focused products.
FactoryTalk® FactoryTalk FactoryTalk
Domain Controller Directory Server AssetCentre Server View SE Server Syslog Collector

Stratix® 5400 Switch

MOD MOD MOD MOD MOD


NET NET NET NET NET

2 2 2 2 2

1 1 1 1 1

1 I/O I/O-A I/O-B I/O-A I/O-B I/O-A I/O-B


1 6 1 6 1 6 1 6 1 6 1 6 1 6

4
I/O

5 10 5 10 5 10 5 10 5 10 5 10 5 10
UFB UFB-A UFB-B UFB-A UFB-B UFB-A UFB-B

D+ D+ D+ D+ D+ D+
D- D- D- D- D- D-

MF-A MF-B MF-A MF-B MF-A MF-B

-
MBRK
+

Kinetix® 5700 CompactLogix 5380 Studio 5000 Logix Designer FactoryTalk


Drive Controller ControlFLASH Plus™ or View SE Client
ControlFLASH™ software

196 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

Security Checklists
Follow the security checklists in this chapter to secure the system and controller. It is your
responsibility to monitor the system periodically to make sure that the security settings
function as you configured them.

Table 27 - Requirements for Identification and Authorization


Required to Meet
Product Details
IEC-62443-4-2 SL 1
Configure FactoryTalk Security to define policies, user groups, and other permission sets.
• The Studio 5000 Logix Designer application enforces the policy based on the access policies
that are provided to it by FactoryTalk Security for the software authenticated user. Once
authenticated, the Studio 5000 Logix Designer application acts as your interface to the
FactoryTalk® Security software controller. This applies to all protected CIP™ communications to the controller, whether from
Studio 5000 Logix Designer application Yes Ethernet, backplane, or USB.
• The FactoryTalk Services Platform offers feature access control to manage user access to
product features such as controller download, project import, project create, and firmware
update.
For more information, see Configure System Security Features User Manual, SECURE-UM001.

Table 28 - Requirements for Use Control


Required to Meet
Product Details
IEC-62443-4-2 SL 1
Configure the controller project in the Studio 5000 Logix Designer application to use these user
access methods:
• License-based source protection limits access to projects to only users with the required
license. Users without the required license cannot open the project or import components
that are protected by the license.
May be required based • License-based execution protection allows execution of the component only on a specific
on system design, controller family, or only on controllers in a specific controller family that contain the
Studio 5000 Logix Designer application threat model, and risk execution license.
assessment. • Password-based protection uses a source key (password) to help protect source logic. All
source keys are stored in the sk.dat file.
• The Studio 5000 Logix Designer application has two tag attributes that control access to tag
data. The External Access attribute controls how external applications can access tags. The
Constant attribute value determines if controller logic can change a tag.
For more information, see Logix 5000 Controllers Security Programming Manual, 1756-PM016.
Configure FactoryTalk Security to define policies, user groups, and other permission sets.
• The Studio 5000 Logix Designer application enforces the policy based on the access policies
that are provided to it by FactoryTalk Security for the software authenticated user. Once
authenticated, the Studio 5000 Logix Designer application acts as your interface to the
controller, including all protected CIP™ communications to the controller, whether from
Ethernet, backplane, or USB.
• The FactoryTalk Services Platform offers feature access control to manage user access to
FactoryTalk Security software product features, such as controller download, project import, project create, and firmware
Yes
Studio 5000 Logix Designer application update.
• In FactoryTalk Security, define which users can change controller modes and download
projects to the controller.
• Security authority binding restricts the controller to a specific FactoryTalk Security instance.
This binding reduces the attack surface for security server spoofing because the client
software and the security software determine the identity of the security authority
responsible for controlling access.
For more information, see Configure System Security Features User Manual, SECURE-UM001.
Place the keyswitch in RUN position to help prevent unauthorized remote configuration changes
to the controller, and restrict some communication services.
May be required based Remove the keyswitch from a running controller to help prevent modifications to the
on system design,
Controller keyswitch position configuration or program.
threat model, and risk IMPORTANT: Do not apply a new security policy while the controller is in RUN mode. RUN mode
assessment. does not help prevent updates to the security policy, and a policy change has the potential to
disrupt a running control system.
May be required based The Ethernet port is enabled by default. Disable the Ethernet port if required by the system
on system design,
Disable the controller Ethernet port design, threat model, or risk assessment.
threat model, and risk For more information, see page 208.
assessment.
May be required based CIP Security ports on the controller are enabled by default. Disable the CIP Security ports if
Disable the controller CIP Security™ on system design, required by the system design, threat model, or risk assessment.
ports threat model, and risk For more information, see page 212.
assessment.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 197


Chapter 15 Develop Secure Applications

Table 28 - Requirements for Use Control (Continued)


Required to Meet
Product Details
IEC-62443-4-2 SL 1
May be required based The USB port on the controller is enabled by default. Disable the USB port if required by the
on system design,
Disable the controller USB ports system design, threat model, or risk assessment.
threat model, and risk For more information, see page 215.
assessment.
May be required based The SD card is enabled by default. Disable the SD card if required by the system design, threat
on system design,
Disable the controller SD card model, or risk assessment.
threat model, and risk For more information, see page 216.
assessment.
May be required based Controller webpages for diagnostics are read-only. With Studio 5000 Logix Designer application
on system design, version 33 or later, controller webpages are disabled by default. Disable the controller webpages
Disable controller webpages threat model, and risk if required by the system design, threat model, or risk assessment.
assessment. For more information, see page 222.

Table 29 - Requirements for System Integrity


Required to Meet
Product Details
IEC-62443-4-2 SL 1
FactoryTalk AssetCentre software The FactoryTalk AssetCentre server centrally tracks and manages configuration changes and
restricts who can make changes based on FactoryTalk Security settings. This server
functionality assists with diagnostics and troubleshooting and reduces maintenance time for
Yes
FactoryTalk Security software production assets.
Configure the Device Monitor - Change Detect operation for the controller.
For more information, see Configure System Security Features User Manual, SECURE-UM001.
Use ControlFLASH Plus™ or ControlFLASH™ software to update controller firmware.
ControlFLASH Plus™ or ControlFLASH™ Digitally signed firmware files have a .DMK (Device Management Kit) extension. ControlFLASH
Yes
software software authenticates the origin of a DMK file and validates the file before download in the
device.
You can generate a signature on an Add-On Instruction. This signature seals (encrypts) the Add-
Studio 5000 Logix Designer application Yes On Instruction to help prevent modification.
To meet IEC-62443-4-2 SL 1 security requirements, you must use a certified version of the
controller firmware. We recommend that you use the latest minor revision of your firmware.
The controller is designed such that:
Controller firmware update Yes • You cannot update firmware when the keyswitch is in the RUN position.
• You cannot go online with a controller that is in a firmware update process.
For more information, see page 54.
May be required based If your application requires a major fault in addition to those already monitored by the controller,
on system design,
User-definable major controller faults threat model, and risk define a predetermined state with a major fault so that outputs are off.
For more information, see page 208.
assessment.

Table 30 - Requirements for Data Confidentiality


Required to Meet
Product Details
IEC-62443-4-2 SL 1
Configure FactoryTalk Security to define policies, user groups, and other permission sets.
• The FactoryTalk Services Platform offers feature access control to manage user access to
product features such as controller download, project import, project create, and firmware
update.
• In FactoryTalk Security, define which users can change controller modes and download
FactoryTalk Security software Yes projects to the controller.
• Security authority binding restricts the controller to a specific FactoryTalk Security instance.
This binding reduces the attack surface for security server spoofing because the client
software and the security software determine the identity of the security authority
responsible for controlling access.
For more information, see Configure System Security Features User Manual, SECURE-UM001.

198 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

Table 30 - Requirements for Data Confidentiality (Continued)


Required to Meet
Product Details
IEC-62443-4-2 SL 1
Use the FactoryTalk Policy Manager software to define a secure data transport over an
FactoryTalk Policy Manager software Yes EtherNet/IP™ network to the controller.
For more information, see Configure System Security Features User Manual, SECURE-UM001.
If your system allows SD card use, the load process to the SD card encrypts and digitally signs
the project by using the controller key. The SD card itself is not encrypted.
May be required based When you save (load) firmware to the SD card, the process stores encrypted firmware and
on system design, certificates on the SD card.
SD card encryption threat model, and risk Do not use a Message to Self (MSG with a Path of THIS) to auto-write controller logs or manually
assessment. force a write of controller logs to the SD card. This can help prevent against potential loss of
controller logs before FactoryTalk AssetCentre can read them.
For more information, see page 94.
Configure licenses to manage access to controller source logic and execution of that logic.
These licenses are not enabled by default.
• License-based source protection limits access to projects to only users with the required
license. Users without the required license cannot open the project or import components
that are protected by the license.
May be required based • License-based execution protection allows execution of the component only on a specific
License-based source and execution on system design, controller family, or only on controllers in a specific controller family that contain the
protection threat model, and risk execution license.
assessment. • Password-based protection uses a source key (password) to help protect source logic. All
source keys are stored in the sk.dat file.
• The Studio 5000 Logix Designer application has two tag attributes that control access to tag
data. The External Access attribute controls how external applications can access tags. The
Constant attribute value determines if controller logic can change a tag.
For more information, see page 202.

Table 31 - Requirements for Restricted Data Flow


Required to Meet
Product Details
IEC-62443-4-2 SL 1
Use FactoryTalk Policy Manager software to define conduits.
CIP Security Yes For more information, see CIP Security with Rockwell Automation Products Application
Technique, SECURE-AT001.

Table 32 - Requirements for Timely Response to Events


Required to Meet
Product Details
IEC-62443-4-2 SL 1
Configure and use the following:
• Audit log accessibility
• Continuous monitoring
FactoryTalk AssetCentre software Yes For more information, see the following:
• Configure System Security Features User Manual, SECURE-UM001.
• System Security Design Guidelines Reference Manual, SECURE-RM001
The controller supports syslog event logging. Choose a syslog collector that supports the
following:
• RFC-5424 syslog protocol
• Ability to receive messages from the controller
Yes, if not using
FactoryTalk IMPORTANT: The controller sends events to a syslog collector through its front Ethernet port.
Syslog collector AssetCentre for The Ethernet port must be connected to the same network as the syslog collector.
logging
To set the IP address of the syslog collector, use FactoryTalk Policy Manager software. For more
information, see CIP Security with Rockwell Automation Products Application Technique,
publication SECURE-AT001.
To view a list of syslog messages and their descriptions, see 1756-RD001.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 199


Chapter 15 Develop Secure Applications

Table 32 - Requirements for Timely Response to Events


Required to Meet
Product Details
IEC-62443-4-2 SL 1
Enable the change detection feature to monitor program components to determine whether they
Controller change detection Yes change. The change detection feature is not enabled by default.
For more information, see page 205.
May be required based Enable component tracking to monitor configurable program components to determine whether
on system design,
Controller component tracking threat model, and risk they change. Component tracking is not enabled by default.
For more information, see page 206.
assessment
The controller log stores security-related events that can be accessed via FactoryTalk
AssetCentre software.
To help prevent the potential loss of controller logs before FactoryTalk AssetCentre can access
them, follow these guidelines:
Disabled controller log auto-write Yes • Do not use a Message to Self (MSG with a Path of THIS) to auto-write controller logs to the
SD card.
• Do not manually force a write of controller logs to the SD card.
By default, the controller log auto-write is disabled.
For more information, see page 207.

Table 33 - Requirements for Resource Availability


Required to Meet
Product Details
IEC-62443-4-2 SL 1
Configure and use the following:
• Asset inventory
FactoryTalk AssetCentre software Yes • Control system backup
• Disaster recovery
For more information, see Configure System Security Features User Manual, SECURE-UM001.
Provide your own UPS with separate battery unit and redundant power supplies.
UPS Yes Size the UPS so that is correctly supports the system and provides enough power to properly
shut down servers and workstations.

200 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

Configure User-definable To suspend (shut down) the controller based on conditions in the application, create a user-
defined major fault. With a user-defined major fault:
Major Faults
• The fault type = 4.
• Define a value for the fault code. Choose a value between 990…999. These codes are
reserved for user-defined faults.
• The controller handles the fault the same as other major faults:
• The controller changes to the Program mode and stops running the logic. Outputs are
set to their configured state or value for faulted mode.

To create a user-defined major fault, do the following:


1. Create a fault routine for the program.
2. Configure the program to use the fault routine.
3. Jump to the fault routine.

Create a Fault Routine


To create a fault routine, do the following:
1. In the Controller Organizer, right-click the program and click Add > New Routine.
2. On the New Routine dialog box, in the Name field, type a name for the fault routine.
3. In the Type field, use the default setting, Ladder Diagram.
4. In the In Program or Phase field, select the program or phase where the routine will
reside.
5. In the Assignment field, select Fault.
6. (optional) Select the Open Routine checkbox, to open the ladder logic program
immediately.
7. Click OK.

Configure the Program to Use the Fault Routine


To configure the program to use the fault routine, do the following:
1. In the Controller Organizer, right-click the program and click Properties.
2. On the Properties dialog box, click the Configuration tab.
3. In the Fault field, select the fault routine.
4. Click OK.

Jump to the Fault Routine


In the main routine of the program, enter the following rung, where:
• Fault_Routine_1 is the name of the fault routine for the program.
• 999 is the value for the fault code.

When Tag_1.0 = 1, execution jumps to name_of_fault_routine, a major fault occurs and the
controller enters the faulted mode. Outputs go to the faulted state. The Controller Properties
dialog box, Major Faults tab, displays the code 999.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 201


Chapter 15 Develop Secure Applications

License-based Source and Source protection helps prevent logic components from being modified based on a license.
Execution Protection Execution protection adds additional protection to controller logic. Execution protection
makes sure that the right controller has access to execute the protected program. Use this
with source protection to make sure that the right programmer has access to modify the logic.

Each controller or computer requires an activation to access protection features. Each logic
component or program requires a license to be accessed or executed.

FactoryTalk Activations
for Protection

SD Card
9509-CMSDCD4 CMStick
9509-CMSTICKC
9509-CMSTICK8
Activation Activation
+ +
Execution License Source License

To execute protected logic, each controller


requires an SD card with the following: To execute protected logic with the Studio 5000
• FactoryTalk activation for protection Logix Designer application, each computer
• Execution license requires a CmStick with the following:
• FactoryTalk activation for protection
• Source license
Licensing Web Portal
• Source License
• Execution License

To apply license-based protection, you need the following:


• A CmStick that contains a license with Use permission must be present locally on any
USB port on the computer. Use permission cannot be obtained from a network license
server. All other license privileges can be contained on the local CmStick, or provided by
a license server on the network.
• A license that contains the Protect permission, either on a local CmStick or provided by
a license server on the network. When components are locked, unauthorized users
cannot view or edit the component, but authorized users can run the project without a
CmStick.

202 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

Enable License-based Protection


1. Click Tools > Security > Configure Source Protection to open the Source Protection
Configuration dialog box.

2. Insert the CmStick that contains the license that you want to use to help protect the
component into the USB port on the computer. Licenses must contain the Protect
permission to be used to protect components. If a license does not contain the Protect
permission, it does not appear in the list of licenses.
3. In the Source Protection Configuration dialog box, select the component to be protected
and click Protect.
4. In the Protect dialog box, select the license to apply.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 203


Chapter 15 Develop Secure Applications

5. Select the execution protection type:


- Protect with controller key only. This option is selected by default. With this option
selected, the component, when locked, runs only on a controller in the same family
as the one specified for the project. For example, if you lock a License-based
Protected component for a project on a CompactLogix 5380 controller, the
component can only be executed on another CompactLogix 5380 controller.
- Protect with controller key and specific license. When you select this option, the
component runs only on a controller in the same family as the one specified for the
project and that contains a CmCard with the execution license that you select. If you
select Protect with controller key and specific license, select the execution license
from the list of available licenses.
After components are protected, they can also be locked. When you lock a
component, it helps prevent users from viewing or editing the component, but allows
authorized users to run it.
6. To return to the Source Protection Configuration dialog box, click OK.
To save changes to a component that is protected with License-Based
Source Protection, a CmStick that contains the required license must be
plugged into the computer that runs the Studio 5000 Logix Designer
application.
Make sure that you save your edits to the project or lock the protected
components before removing the CmStick that contains the required
license. If the license is not present, you could lose your edits to the project.

204 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

Configure Change Detection On the Security tab of the controller properties, the Change Detection feature tracks changes
to a controller and generates an audit value when a monitored change occurs.

For more information about change detection, see the Logix 5000 Controller Information and
Status Programming Manual, publication 1756-PM015.

Changes to Detect
Click Configure to open the Configure Changes to Detect dialog box. We recommend tracking
the changes that are shown in the following image for a standard CompactLogix 5380
controller. By default, all event types can cause the audit value to change, resulting in a default
value of 0xFFFFFFFFFFFFFFFF.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 205


Chapter 15 Develop Secure Applications

Audit Value

A unique value that is generated when a project is downloaded to the controller or loaded from
a storage device. This value is updated when a change to an event occurs. Some events
always cause an Audit Value change, while others are selectable in the Configure Changes to
Detect dialog box. When the controller is offline, the Audit Value box is blank.

Configure Component On the Security tab of the controller properties, component tracking enables you to determine
whether tracked routines, Add-On Instructions, I/O modules, and constant tags have been
Tracking changed. The Logix Designer application creates a tracked state value to indicate the current
state of all components.

For more information about component tracking, see the Logix 5000 Controller Information
and Status Programming Manual, publication 1756-PM015.

206 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

Configure Controller Logging The controller log stores various security-related events that can be written to an SD card or
accessed via FactoryTalk Asset Center or a third-party syslog collector. Some of these events
are Studio 5000 Logix Designer application request errors, control system events, backup/
restore events, and configuration changes.

For more information on how to access the controller log, see the Logix 5000 Controller
Information and Status Programming Manual, publication 1756-PM015.

For more robust logging and to help prevent rollover, use FactoryTalk AssetCentre or a syslog
collector.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 207


Chapter 15 Develop Secure Applications

Disable Controller You can disable the controller Ethernet ports with the Studio 5000 Logix Designer application,
version 28 or later.
Ethernet Ports
IMPORTANT Remember the following:
• When you use the Studio 5000 Logix Designer application, version 29 or
later, you can disable either of the Ethernet ports whether the controller
uses Dual-IP mode or Linear/DLR mode.
• Once an Ethernet port is disabled, you lose any connection that is
established through that port.
• You cannot disable Ethernet ports if the controller is in Run mode or if
the FactoryTalk® Security settings deny this editing option.

Ethernet ports return to the default setting after the following occur on the controller:
• Stage 1 reset
• Stage 2 reset
• New project is downloaded - In this case, the settings in the new project take effect.
• Program is cleared from the controller - The following are examples of what clears the
program from a controller:
- Major non-recoverable fault occurs.
- Firmware update occurs.

You must reconfigure the settings to disable an Ethernet port after the port returns to its
default settings.

There are two ways to disable the Ethernet port:


• Disable the Ethernet Port on the Port Configuration Tab on page 209
• Disable the Ethernet Port with a MSG Instruction on page 210

208 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

Disable the Ethernet Port on the Port Configuration Tab


You can disable the embedded Ethernet port on the controller. This method retains the setting
in the project, so every time you download the project to the controller, the Ethernet port is
disabled.
1. On the Online toolbar, click the Controller Properties button.

2. On the Controller Properties dialog box, click the Port Configuration tab.
3. On the Port Configuration tab, clear the Enable checkbox.

4. On the Port Configuration tab, click Apply.


- If you are online when you make this change, then an Alert dialog box appears. On
the dialog box, click Yes. The change takes effect immediately.
- If you are offline, then the change takes effect when you download the program to
the controller.
5. On the Port Configuration tab, click OK.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 209


Chapter 15 Develop Secure Applications

Disable the Ethernet Port with a MSG Instruction


You use a CIP™ Generic MSG with a Path of THIS to execute this option. You cannot use this
MSG instruction to disable the Ethernet port on a different controller.
1. Add a MSG instruction to your program.
This message only needs to execute once, it does not need to execute with every
program scan.

IMPORTANT You cannot add a MSG instruction to your program if the


controller is in Run mode or if the FactoryTalk Security settings
deny this editing option.
2. Configure the Configuration tab on the Message Configuration dialog box as described
in Table 34.

IMPORTANT The values that are listed below are stored to NVS memory in
such a way that the MSG instruction is not required to be
executed each time the controller powers up.

Table 34 - Disable an Ethernet Port


Field Description
Message Type CIP Generic
Service Type Set Attribute Single
1 to disable Port A1
Instance 2 to disable Port A2
Class f6
Attribute 9
Controller tag of SINT data type.
Source Element In this example, the controller tag is named Port_Configuration.
Source Length 1

210 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

3. Configure the Communication tab to use a Path of THIS.

IMPORTANT Messages to THIS must be unconnected messages.

4. Before you enable the MSG instruction, make sure that the Source Element tag value is
2.

IMPORTANT You can re-enable an Ethernet port after it is disabled.


To re-enable the port, complete the steps that are described in
this section. Before you enable the MSG instructions, however,
make sure that the Source Element tag value is 1.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 211


Chapter 15 Develop Secure Applications

Disable the Controller There are two ways to disable the CIP Security ports on the controller:
CIP Security Ports • Use the Disable CIP Security checkbox in FactoryTalk Linx software, version 6.30.00 or
later
• Use a CIP Generic MSG in the Studio 5000 Logix Designer application, version 32 or later

Use the Disable CIP Security Checkbox in FactoryTalk Linx


1. If the Device Configuration menu in FactoryTalk Linx is not enabled, go to the Advanced
Settings dialog box and select Enable Device Configuration.

2. From the Device Configuration menu, click the CIP Security tab, and then select Disable
CIP Security (Port 2221).

212 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

Use a CIP Generic MSG Instruction in the


Studio 5000 Logix Designer Application
IMPORTANT This procedure disables CIP Security ports. To re-enable the ports, use
the controller reset button to perform a Stage 2 reset, which returns
the controller to a factory default state.
See Stage 2 Reset on page 88.

You cannot use this MSG instruction to disable the CIP Security ports on another controller.

The message only has to execute once rather than with every program scan.
1. Create a controller tag with the SINT[9] data type.
In this example, the controller tag is named CIPSEC_DISABLE and must match the
following image.

Before you enable the MSG instruction, consider the following:


- The element CIPSEC_DISABLE[4] is responsible for disabling UDP port 2221 and
EtherNet/IP™ over DTLS, transport class 0/1.
- The element CIPSEC_DISABLE[8] is responsible for disabling TCP port 2221 and
EtherNet/IP over TLS, UCMM, and transport class 3.
- To disable the controller CIP Security ports, the elements CIPSEC_DISABLE[4] and
CIPSEC_DISABLE[8] in the SINT array for the Source Element CIPSEC_DISABLE must
be 0.
2. Add an MSG instruction to your program.
IMPORTANT You cannot add an MSG instruction to your program if the
controller keyswitch is in RUN mode or if the FactoryTalk
Security settings deny this editing option.
3. Configure the Configuration tab on the Message Configuration dialog box as described
in Table 35 on page 214.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 213


Chapter 15 Develop Secure Applications

Table 35 - Disable the CIP Security Ports


Field Description
Message Type CIP Generic
Service Type Custom
Service Code 4c
Instance 1
Class f5
Attribute 0
Controller tag of SINT[9] data type.
Source Element This is the controller tag that you created in step 1.
Source Length 9

4. Configure the Communication tab to use a Path of THIS.

IMPORTANT Messages to THIS must be unconnected messages.

5. Cycle power on the controller for the configuration to take effect.

214 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

Disable the Controller With the Studio 5000 Logix Designer application, version 32 or later, you can use a CIP Generic
MSG with a Path of THIS to execute this option.
USB Port
1. Add an MSG instruction to your program.
This message has to execute only once and not with every program scan.

IMPORTANT You cannot add an MSG instruction to your program if the


controller keyswitch is in Run mode, or if the FactoryTalk Security
settings deny this editing option.
2. Configure the Configuration tab on the Message Configuration dialog box as described
in Table 36.

IMPORTANT These values are stored to non-volatile controller memory in such a


way that the MSG instruction is not required to execute up each time
the controller powers up.

Table 36 - Disable the USB Port


Field Description
Message Type CIP Generic
Service Type Set Attribute Single
Instance 1
Class 33a
Attribute 4
Controller tag of SINT data type.
Source Element In this example, the Source Element is named Port_Configuration.
Source Length 1

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 215


Chapter 15 Develop Secure Applications

3. Configure the Communication tab to use a Path of THIS.

IMPORTANT Messages to THIS must be unconnected messages.

Disable the Controller With the Studio 5000 Logix Designer application, version 32 or later, you can use a CIP Generic
MSG with a Path of THIS to execute this option.
SD Card
IMPORTANT Remember the following:
• An SD card can only be disabled with a Message to Self.
• Once an SD slot is disabled, you lose all ability to communicate to an SD
card inserted into the slot. This includes any diagnostic information.
1. Add an MSG instruction to your program.
This message only has to execute once, it does not need to execute with every program
scan.

IMPORTANT You cannot add an MSG instruction to your program if the


controller keyswitch is in Run mode, or if the FactoryTalk Security
settings deny this editing option.
2. Configure the Configuration tab on the Message Configuration dialog box as described
in Table 37 on page 217.

216 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

IMPORTANT These values are stored to non-volatile controller memory in such a


way that the MSG instruction is not required to execute each time the
controller powers up.

Table 37 - Disable the SD Card


Field Description
Message Type CIP Generic
Service Type Set Attribute Single
Instance 1
Class 3a4
Attribute 4
Controller tag of SINT Array.
Source Element In this example, the Source Element is named src_array.
Source Length 1
3. Configure the Communication tab to use a Path of THIS.

IMPORTANT Messages to THIS must be unconnected messages.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 217


Chapter 15 Develop Secure Applications

Disable the 4-character With the Studio 5000 Logix Designer application, version 29 or later, you can disable certain
categories of messages on the 4-character status display:
Status Display
• Disable All Categories of Messages on page 218
• Disable Individual Categories of Messages on page 220

You use a CIP Generic MSG to execute each option.

IMPORTANT You cannot disable these system messages, and they will always
display:
• Power-up messages, such as TEST, PASS, CHRG
• Catalog number message
• Firmware revision message
• Major/Critical failure messages

The 4-character status display returns to the default setting after one of these actions occurs
on the controller:
• Stage 1 reset
• Stage 2 reset
• New project is downloaded - In this case, the settings in the new project take effect.
• Program is cleared from the controller - these examples can clear the program from a
controller:
- A major nonrecoverable fault occurs.
- A firmware update occurs.

You must reconfigure the settings to disable the 4-character status display after it returns to
its default settings.

Disable All Categories of Messages


When you disable all categories of messages, this information no longer shows:
• Project name
• Link status
• Port status
• IP address

Complete these steps.


1. Add an MSG instruction to your program.
2. Configure the Configuration tab on the Message Configuration dialog box as described
in Table 38.

218 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

Table 38 - Disable All Categories of Messages


Field Description
Message Type CIP Generic
Service Type Set Attribute Single
Instance 1
Class 3a5
Attribute 1
Controller tag of SINT data type.
Source Element In this example, the controller tag is named LCD_SINT.
Source Length 1
3. Configure the Communication tab to use a Path of THIS.

IMPORTANT Messages to THIS must be unconnected messages.

4. Before you enable the MSG instruction, make sure that the Source Element tag value is 1.

IMPORTANT You can re-enable the 4-character display after it is disabled.


To re-enable the 4-character display, complete the steps that are
described in this section. Before you enable the MSG instructions,
however, make sure that the Source Element tag value is 0.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 219


Chapter 15 Develop Secure Applications

Disable Individual Categories of Messages


You can disable a subset of the information that scrolls across the controller 4-character
display. You can disable these subsets:
• Project name and link status
• Port status and IP address

Complete these steps.


1. Add an MSG instruction to your program.
This message only has to execute once, it does not need to execute with every program
scan.

IMPORTANT You cannot add an MSG instruction to your program if the


controller keyswitch is in Run mode, or if the FactoryTalk
Security settings deny this editing option.
2. Configure the Configuration tab on the Message Configuration dialog box as described
in Table 39.

Table 39 - Disable Individual Categories of Messages


Field Description
Message Type CIP Generic
Service Type Set Attribute Single
Instance 1
Class 3a5
Attribute 2
Controller tag of DINT data type.
Source Element In this example, the controller tag is named Line_MASK.
Source Length 4

220 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

3. Configure the Communication tab to use a Path of THIS.

IMPORTANT Messages to THIS must be unconnected messages.

4. Before you enable the MSG instruction, make sure that the Source Element uses one of
the following tag values that are based on what information that you want to disable:
- Project name and link status - Bit 0 of the Source Element = 1
- Port status and IP address - Bit 1 of the Source Element = 1

IMPORTANT You can re-enable the subsets of information on the 4-character


display after they are disabled.
To re-enable the subsets, complete the steps that are described in
this section. Before you enable the MSG instructions, be sure that
the appropriate bit in the Source Element tag value is 0.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 221


Chapter 15 Develop Secure Applications

Disable Controller Webpages You can disable the controller webpages with the Studio 5000 Logix Designer application,
version 28 or later.

Studio 5000 Logix Designer Application Version 33 or Later


With the Studio 5000 Logix Designer application, version 33 or later, controller web pages are
disabled by default.

While using a CIP Generic MSG to disable controller web pages is supported in version 33 or
later, Rockwell Automation recommends the following method to disable the controller web
pages.

If the controller web pages are enabled, disable them by clearing the Enable Controller Web
Pages check box on the Security tab for the controller properties.

222 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

Studio 5000 Logix Designer Application Version 32 or Earlier


For the Studio 5000 Logix Designer application, version 32 or earlier, use a CIP Generic MSG to
enable or disable controller web pages:
• Use a CIP Generic MSG to Disable the Controller Web Pages on page 223
• Use a CIP Generic MSG to Enable the Controller Web Pages on page 226

Controller Web Page Default Settings


The default settings for controller web pages are as follows:
• Web pages are enabled for controller firmware revision 32 or earlier
• Web pages are disabled for controller firmware revision 33 or later

Controller web pages return to the default setting in these situations:


• A stage 1 reset for all versions of the Studio 5000 Logix Designer application.
• A stage 2 reset for all versions of the Studio 5000 Logix Designer application.

IMPORTANT When you update the controller firmware to revision 33 or later


without a reset, the controller retains the previous controller web
page configuration (web pages enabled) and does not
automatically change to the default setting for V33 (disable the
web pages).
• You must reconfigure the settings to disable the controller web pages after it returns to
its default settings.

The setting of the controller web pages changes after the following occurs on the controller:
• New project is downloaded—in this case, the settings in the new project take effect.
• When the controller receives a configuration message, it takes the setting from the
configuration message.

Use a CIP Generic MSG to Disable the Controller Web Pages


1. Add a MSG instruction to your program.

IMPORTANT You cannot add a MSG instruction to your program if the


controller is in Run mode or if the FactoryTalk Security settings
deny this editing option.
2. On the Configuration tab of the Message Configuration dialog box, complete the fields
as described in Table 40.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 223


Chapter 15 Develop Secure Applications

Table 40 - Disable the Webpages


Field Description
Message Type CIP Generic
Service Type Custom
Service Code 4c
1 for Linear/DLR mode
Instance 2 for Dual-IP mode
Class f5
Attribute 0
Controller tag of SINT[5] data type.
In this example, the controller tag is named WP_Disable and must match the following
graphic:

Source Element

IMPORTANT: The Source Element tag in your Studio 5000 Logix Designer application
project must match the values that are shown in the graphic. If you use values that are
different than the ones shown, the controller webpages are not disabled.
Source Length 5

224 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

3. On the Communication tab, configure a communication path of THIS.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 225


Chapter 15 Develop Secure Applications

Use a CIP Generic MSG to Enable the Controller Web Pages


1. Add a MSG instruction to your program.

IMPORTANT You cannot add a MSG instruction to your program if the


controller mode switch is in RUN mode, or if the FactoryTalk
Security settings deny this editing option.
2. On the Configuration tab of the Message Configuration dialog box, complete the fields
as described in Table 41.

Table 41 - Enable the Webpages


Field Description
Message Type CIP Generic
Service Type Custom
Service Code 4c
1 for Linear/DLR mode
Instance 2 for Dual-IP mode
Class f5
Attribute 0
Controller tag of SINT[5] data type.
In this example, the controller tag is named WP_Enable and must match the following
graphic:

Source Element

IMPORTANT: The Source Element tag in your Logix Designer application project must
match the values that are shown in the graphic. If you use values that are different
than the ones shown, the controller webpages are not enabled.
Source Length 5

226 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 15 Develop Secure Applications

3. On the Communication tab, configure a communication path of THIS.

IMPORTANT Messages to THIS must be unconnected messages.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 227


Chapter 15 Develop Secure Applications

Notes:

228 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 16
Develop Motion Applications
Overview Some CompactLogix™ 5380 and Compact GuardLogix® 5380 controllers support Integrated
Motion over an EtherNet/IP™ network on digital and integrated motion interfaces.
Applies to these controllers:
• The controllers support these numbers of integrated motion axes:
CompactLogix 5380 Motion Controllers
Compact GuardLogix 5380 SIL 2 Motion CompactLogix 5380 Controllers Compact GuardLogix 5380 Controllers
Controllers 5069-L306ERM 2 5069-L306ERMS2, 5069-L306ERMS3 2
Compact GuardLogix 5380 SIL 3 Motion 5069-L310ERMS2, 5069-L310ERMS2K,
Controllers 5069-L310ERM, 5069-L310ERMK 4 4
5069-L310ERMS3, 5069-L310ERMS3K
5069-L320ERMS2, 5069-L320ERMS2K, 5069-L320ERMS3,
5069-L320ERM, 5069-L320ERP 8 8
5069-L320ERMS3K
5069-L330ERMS2, 5069-L330ERMS2K, 5069-L330ERMS3,
5069-L330ERM 16 16
5069-L330ERMS3K
5069-L340ERM, 5069-L340ERP 20 5069-L340ERMS2, 5069-L340ERMS3 20
5069-L350ERMS2, 5069-L350ERMS2K, 5069-L350ERMS3,
5069-L350ERM 24 24
5069-L350ERMS3K
5069-L380ERM 28 5069-L380ERMS2, 5069-L380ERMS3 28
5069-L3100ERM 32 5069-L3100ERMS2, 5069-L3100ERMS3 32
• Digital drive interfaces include EtherNet/IP connected drives.
• Integrated Motion over an EtherNet/IP network supports some Kinetix® drives and some
PowerFlex® drives. For example, Kinetix 5700 and PowerFlex 755 drives.
• All CompactLogix 5380 and Compact GuardLogix 5380 controllers support single-axis
motor control with PowerFlex variable frequency drives over an EtherNet/IP network.
This functionality is available on CompactLogix 5380 and Compact GuardLogix 5380
controllers that do not support other aspects of Integrated Motion over an EtherNet/IP
network.
For more information, see the following:
• Integrated Motion on the EtherNet/IP network Configuration and Startup User Manual,
publication MOTION-UM003.
• Integrated Motion on the EtherNet/IP network Reference Manual, Publication
MOTION-RM003.

Motion Overview The controllers support up to 256 axes of integrated motion. The 256 axes can be any
combination of CIP™, Virtual, and Consumed axes. You can add all axes to one Motion Group,
Applies to these controllers: and you can assign any combination of axes to different axis update schedules. You can
CompactLogix 5380 Motion Controllers associate Integrated Motion axes to any appropriate drive.
Compact GuardLogix 5380 SIL 2 Motion
Controllers The controllers do not support Analog or SERCOS motion.
Compact GuardLogix 5380 SIL 3 Motion
Controllers The configuration process varies, depending on your application and your drive selection. The
following are general steps to configure a motion application.
1. Create a controller project.
2. Select the type of drive.
3. Create axis tags as needed.
4. Configure the drive.
5. Create axes as needed.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 229


Chapter 16 Develop Motion Applications

Program Motion Control The controller provides a set of motion control instructions for your axes:
Applies to these controllers:
• The controller uses these instructions just like the rest of the Logix 5000™ instructions.
CompactLogix 5380 Motion Controllers • Each motion instruction works on one or more axes.
Compact GuardLogix 5380 SIL 2 Motion • You can use motion control instructions in these programming languages:
Controllers
- Ladder Diagram (LD)
Compact GuardLogix 5380 SIL 3 Motion
Controllers - Structured Text (ST)
- Sequential Function Chart (SFC)
• Each motion instruction needs a motion control tag. The tag uses a
MOTION_INSTRUCTION data type and stores the information status of the instruction.

For more information, see the Logix 5000 Controller Motion Instructions Reference Manual,
publication MOTION-RM002.

ATTENTION: Use each motion control tag in only one motion instruction.
Unintended operation can result if you reuse the same motion control tag in
other motion instructions, or if you write to any of the motion control tag
elements.

In this example, a simple ladder diagram that homes, jogs, and moves an axis.

If Initialize_Pushbutton = on and the axis = off (My_Axis_X.ServoActionStatus = off), the MSO instruction turns on the axis.

If Home_Pushbutton = on and the axis hasn’t been homed (My_Axis_X.AxisHomedStatus = off), the MAH instruction homes the axis.

If Jog_Pushbutton = on and the axis = on (My_Axis_X.ServoActionStatus = on), the MAJ instruction jogs the axis forward at 8 units/second.

230 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 16 Develop Motion Applications

If Jog_Pushbutton = off, the MAS instruction stops the axis at 100 units/.second2. Make sure that Change Decel is Yes. Otherwise, the axis
decelerates at its maximum speed.

If Move_Command = on and the axis = on (My_Axis_X.ServoActionStatus = on), the MAM instruction moves the axis. The axis moves to the
position of 10 units at 1 unit/second.

Obtain Axis Information You can obtain axis information via these methods:
Applies to these controllers:
• Double-click the axis to open the Axis Properties dialog box.
CompactLogix 5380 Motion Controllers • Use a Get System Value (GSV) or Set System Value (SSV) instruction to read or change
Compact GuardLogix 5380 SIL 2 Motion
the configuration at runtime.
Controllers • View the Quick View pane to see the state and faults of an axis.
Compact GuardLogix 5380 SIL 3 Motion • Use an axis tag for status and faults.
Controllers
Figure 58 - Obtain Axis Information

Axis Properties Dialog Box

Axis Tag SSV (or GSV) Instruction

Quick View Pane

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 231


Chapter 16 Develop Motion Applications

Notes:

232 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 17
Troubleshoot the Controller
This chapter describes how to troubleshoot the controller if issues occur during normal
operation.

You can use messages on the 4-character display to troubleshoot the controller. For more
information, see Appendix A, Status Indicators on page 253.

Automatic Diagnostics Automatic Diagnostics is a system-level feature in Logix 5000 controllers that provides device
diagnostics to HMIs and other clients, with zero programming. The diagnostics include device
description conditions and state events.

Automatic Diagnostics is enabled by default in Logix 5000 controllers with firmware revision
33 and later. You can disable and enable the whole feature while online or offline from the
Advanced tab on the Controller Properties dialog. You can also disable Automatic Diagnostics
for a specific device in the device's configuration.

Considerations for The response time and diagnostic information for a loss of communication depends on the
device and configuration settings.
Communication Loss
Diagnostics Type of Connection Device Behavior
Direct connection to a Logix 5000 Device reports communication loss.The device communication loss
controller can be replaced by the diagnostics of a communication adapter
Communication adapters that do not have a connection to the
No connection to a Logix 5000 controller controller do not report communication loss diagnostics.
To enable timely reporting of any communication loss, we recommend
that you configure communication adapters for a status connection.
Device reports communication loss.
Data connection The device communication loss can be replaced by the diagnostics of
a communication adapter
Device does not report communication loss diagnostics. The
communication adapter reports communication loss diagnostics.
Rack-optimized connection A device with a rack optimized connection has a reduced set of
diagnostics as compared to a direct connection.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 233


Chapter 17 Troubleshoot the Controller

When enabled, the Automatic Diagnostics feature enables:


• Communication loss diagnostics for all devices in the controller I/O configuration
• Device-level automatic diagnostics evaluations for all uninhibited and enabled devices.

You can disable Automatic Diagnostics for a specific device in the device configuration. The
communication loss diagnostic remains active even if the device disables Automatic
Diagnostics. To disable communication loss diagnostic, inhibit the device or disable Automatic
Diagnostics at the controller.

Controller Diagnostics with You can use the Controller Properties in the Studio 5000 Logix Designer® application to view
fault conditions in these ways:
Logix Designer
• Warning Symbol in the I/O Configuration Tree
Table 42 -
• Categories on I/O Module Properties Dialog
Applies to these controllers: • Notification in the Tag Monitor
CompactLogix™ 5380
• Fault Information in the Controller Properties Dialog Box
Compact GuardLogix® 5380 SIL 2
• Port Diagnostics
Compact GuardLogix 5380 SIL 3
• Advanced Time Sync

Warning Symbol in the I/O Configuration Tree

IMPORTANT Safety Consideration


You cannot configure safety connections to automatically fault the
controller.

A warning symbol appears in the controller organizer next to the I/O module. This occurs when
there are faults or other conditions in the I/O module, or if the connection to the I/O module
fails while in run mode.
Figure 59 - Warning Symbol on I/O Module

The following conditions are possible:


• When the I/O module is configured to cause a major fault on the controller and an I/O
module fault occurs, the following can result:
- Controller state displays Faulted.
- Controller status displays Controller Fault and is steady red.
- I/O module status displays I/O Not Responding and blinks green.

IMPORTANT The descriptions in the Logix Designer application can change based on
the controller mode and status.

234 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 17 Troubleshoot the Controller

IMPORTANT Safety Consideration


You cannot configure safety connections to automatically fault the
controller.
• When the I/O module is not configured to cause a major fault on the controller and an I/
O module fault occurs, the following result:
- Controller state displays the current state, for example, Rem Run.
- Controller status displays Controller OK and is steady green.
- I/O module status displays I/O Not Responding and blinks green.

Categories on I/O Module Properties Dialog


The Module Properties dialog for I/O modules includes a series of categories. You can use
some of the categories to troubleshoot the controller.

IMPORTANT The number and type of categories varies by I/O module type.

The following are examples of ways to use categories on the Module Properties dialog box
when you troubleshoot a controller:
• Module Status on General Category
• Module Fault Descriptions on Connection Category
• Module Fault Descriptions on Module Info Category
• Diagnostics Option on Module Info Category

The categories that are described in this section display the module status. When a fault
exists, the text is Status: Faulted in the module status line as shown in Figure 60.
Module Status on General Category

The General category displays the module status.


Figure 60 - Module Status in Fault Message Line

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 235


Chapter 17 Troubleshoot the Controller

Module Fault Descriptions on Connection Category

The Connection category displays the module fault description that includes an error code that
is associated with the specific fault type.
Figure 61 - Fault Description with Error Code

Module Fault Descriptions on Module Info Category

When you click the Module Info category, a dialog box displays the module fault description
and the corresponding fault code. Click OK to access the Module Info category.
The Module Info tab requires successful communications to help you troubleshoot
the fault effectively. Consider the following:
• If communication to the I/O module is OK, but the module is faulted, we
recommend that you use the Module Info category to troubleshoot the fault.
• If communication to the I/O module is faulted, we recommend that you use the
Connection category to troubleshoot the fault.
On the Module Info category, the Status section displays the following about the I/O module:
• Major and Minor Faults
• Internal State
Figure 62 - Major and Minor Fault Information

236 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 17 Troubleshoot the Controller

Diagnostics Option on Module Info Category

You can access the diagnostics for a module from the Module Info category. Click Diagnostics,
to access the Module Diagnostics dialog box.
Figure 63 - Module Diagnostics

Notification in the Tag Monitor


General and diagnostic module faults are reported in the Tag monitor of your Logix Designer
application project.
The Value field indicates a fault with the number 1.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 237


Chapter 17 Troubleshoot the Controller

Fault Information in the Controller Properties Dialog Box


You can use these tabs on the Controller Properties dialog box to troubleshooting the
controller:
• Major Faults
• Minor Faults
• Network
Major Faults

You can monitor information about recent major faults and also clear major faults on the Major
Faults tab.
Figure 64 - Major Faults Tab in Controller Properties Dialog Box
CompactLogix 5380 Controller

Minor Faults

You can monitor information about recent minor faults and also clear minor faults on the Minor
Faults tab.
Figure 65 - Minor Faults Tab in Controller Properties Dialog Box
CompactLogix 5380 Controller

238 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 17 Troubleshoot the Controller

Network

Typically, the Network tab is used to monitor for faults that occur when the controller is used
in a DLR network.

IMPORTANT The Network tab is not available when the controller operates in
Dual-IP mode.

Figure 66 - Network Tab in Controller Properties Dialog Box

Port Diagnostics
When your project is online, you can view the status of the embedded Ethernet ports on the
controller.
1. Access the Controller Properties.
2. Click the Port Configuration tab.
3. On the Port Configuration tab, click the Port Diagnostics button for an active port.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 239


Chapter 17 Troubleshoot the Controller

The Port Diagnostics page, displays information for the port. See Table 43 on page 240 for
parameter descriptions.

Table 43 - Port Diagnostics Parameters - Logix Designer


Parameter Description
The Interface Counters values have no value when you cannot communicate
Interface Counters out of the port.
Octets Inbound Displays the number of octets that are received on the interface.
Octets Outbound Displays the number of octets that are transmitted to the interface.
Unicast Packets Inbound Displays the number of unicast packets that are received on the interface.
Displays the number of unicast packets that are transmitted on the
Unicast Packets Outbound interface.
Displays the number of non-unicast packets that are received on the
Non-unicast Packets Inbound interface.
Displays the number of non-unicast packets that are transmitted on the
Non-unicast Packets Outbound interface.
Displays the number of inbound packets that are received on the interface
Packets Discarded Inbound but discarded.
Displays the number of outbound packets that are transmitted on the
Packets Discarded Outbound interface but discarded.
Displays the number of inbound packets that contain errors (excludes
Packets With Errors Inbound discarded inbound packets).
Displays the number of outbound packets that contain errors (excludes
Packets With Errors Outbound discarded outbound packets).
Unknown Protocol Packets Inbound Displays the number of inbound packets with unknown protocol.
The Media Counters values have no value when you are offline or online and
Media Counters there is a communication error.
Displays the number of frames received that are not an integral number of
Alignment Errors octets in length.
FCS Errors Displays the number of frames received that do not pass the FCS check.
Displays the number of successfully transmitted frames that experienced
Single Collisions exactly one collision.
Displays the number of successfully transmitted frames that experienced
Multiple Collisions multiple collisions.
SQE Test Errors Displays the number of times an SQE test error message was generated.
Displays the number of frames for which the first transmission attempt is
Deferred Transmissions delayed because the medium is busy.
Displays the number of times a collision is detected later than 512 bit-times
Late Collisions into the transmission of a packet.
Displays the number of frames for which transmission fails due to excessive
Excessive Collisions collisions.
Displays the number of frames for which transmission fails due to an
MAC Transmit Errors internal MAC sub layer transmit error.
Displays the number of frames for which reception on an interface fails due
MAC Receive Errors to an internal MAC sub layer receive error.

240 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 17 Troubleshoot the Controller

Table 43 - Port Diagnostics Parameters - Logix Designer (Continued)


Parameter Description
Displays the number of times that the carrier sense condition was lost or
Carrier Sense never asserted when attempting to transmit a frame.
Displays the number of frames received that exceed the maximum
Frame Too Long permitted frame size.
Click Reset Counter to cause the interface and media counter values on the
module to set to zero, and the values in the dialog to update.
Reset Counters Reset Counter appears dimmed when:
• offline
• online and a communication error has occurred

Advanced Time Sync


The Advanced Time Sync dialog displays information that is related to CIP Sync™ time
synchronization, also known as Precision Time Protocol (PTP). The information appears only if
the project is online and Enable Time Synchronization is selected on the Date/Time tab. Also,
when the controller operates in Dual-IP mode, the Advanced Time Sync tab provides data for
each port.

IMPORTANT • Access to software that manages/updates the PTP on a control system


network should be limited to users who are trained on the
administration of industrial control system time including PTP. This
includes the PTP update tool supplied by Rockwell Automation, or other
publicly available PTP management software.Incorrect updates while a
control system is running can disrupt the operation of the control
system (including major faults and some devices taken off line).
• When disabling PTP on a controller, to give the controller time to
process the disable, use a two-second delay before setting the
WallClockTime (WCT) in the controller. Otherwise, there is a risk of the
grandmaster clock overwriting the WCT.
1. On the Date/Time tab, click the Advanced button.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 241


Chapter 17 Troubleshoot the Controller

The Advanced Time Sync dialog box opens. See Table 44 for parameter descriptions.

Table 44 - Time Sync Parameters


Grandmaster Clock
Displays information about the Grandmaster clock. The vendor of the Grandmaster device controls
this information. The following information is specified:
• User Name
• User Location
• Protocol Address
• Physical Address
• Clock Type
• Manufacturer Name
• Model
Description
• Serial Number
• Hardware Revision
• Firmware Revision
• Software Version
• Profile Identity
• Physical Protocol
• Network Protocol
• Port Number
Use the vertical scroll bar to view the data.
Displays the unique identifier for the Grandmaster clock. The format depends on the network
Identity protocol. Ethernet network encodes the MAC address into the identifier.
Displays a measure of the quality of the Grandmaster clock. Values are defined from 0…255 with
Class zero as the best clock.
Indicates the expected absolute accuracy of the Grandmaster clock relative to the PTP epoch. The
Accuracy accuracy is specified as a graduated scale that starts at 25 nsec and ends at greater than 10
seconds or unknown. The lower the accuracy value, the better the clock.
Displays the measure of inherent stability properties of the Grandmaster clock. The value is
Variance represented in offset scaled log units. The lower the variance, the better the clock.
Displays the time source of the Grandmaster clock. The available values are:
• Atomic Clock
• GPS
• Radio
Source • PTP
• NTP
• HAND set
• Other
• Oscillator
Priority 1 / Displays the relative priority of the Grandmaster clock to other clocks in the system. The priority
Priority 2 values range from 0…255. The highest priority is zero. The default value for both settings is 128.

242 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 17 Troubleshoot the Controller

Table 44 - Time Sync Parameters (Continued)


Local Clock
Synchroniza Displays whether the local clock is synchronized or not synchronized with the Grandmaster
reference clock. A clock is synchronized if it has one port in the slave state and is receiving updates
tion Status from the time master.
Offset to Displays the amount of deviation between the local clock and the Grandmaster clock in
Master nanoseconds.
Displays the current state of the backplane. The available values are as follows:
• Initializing
• Faulty
• Disabled
• Listening
Backplane • PreMaster
State
• Master
• Passive
• Uncalibrating
• Slave
• None
Displays the state of the Ethernet port. The available values are as follows:
• Initializing
• Faulty
• Disabled
• Listening
• PreMaster
• Master
Ethernet
State • Passive
• Uncalibrating
• Slave
• None
IMPORTANT: When the controller operates in Dual-IP mode, this attribute provides data for each
controller port. The fields appear as follows:
• A1, Ethernet State
• A2, Ethernet State
Displays the unique identifier for the local clock. The format depends on the network protocol.
Identity Ethernet network encodes the MAC address into the identifier.
Displays a measure of quality of the local clock. Values are defined from 0…255, with zero as the
Class best clock.
Indicates the expected absolute accuracy of the local clock relative to the PTP epoch. The accuracy
Accuracy is specified as a graduated scale that starts at 25 nsec and ends at greater than 10 seconds or
unknown. The lower the accuracy value, the better the clock.
Displays the measure of inherent stability properties of the local clock. The value is represented in
Variance offset scaled log units. The lower the variance, the better the clock.
Displays the time source of the local clock. The available values are:
• Atomic Clock
• GPS
• Terrestrial Radio
Source • PTP
• NTP
• HAND set
• Other
• Oscillator

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 243


Chapter 17 Troubleshoot the Controller

Controller Diagnostics with You can also view diagnostic information in Linx-based software.
Linx-based Software 1. Use the RSWho button to browse.
2. Navigate to the Ethernet network.
Applies to these controllers:
CompactLogix 5380
3. Right-click the controller and choose Module Statistics.
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3

The Module Statistics dialog provides this information:


• The General tab shows device information, and any faults on the controller.
• The Port Diagnostics tab shows information for the Ethernet port.
• The Connection Manager Tab shows information on connection requests.
• The USB tab shows information about the USB port.

244 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 17 Troubleshoot the Controller

Controller Web Pages The controller provides diagnostic web pages that track controller perfo rmance, network
performance, and backplane performance.
Applies to these controllers:
CompactLogix 5380 IMPORTANT With the Studio 5000 Logix Designer application version 33.00.00 and
Compact GuardLogix 5380 SIL 2 later, controller web pages are disabled by default.
Compact GuardLogix 5380 SIL 3 To enable the controller web pages, select the checkbox on the Logix
Designer Controller Properties Security tab.

To access the diagnostic web pages, follow these steps.


1. Open your web browser.
2. In the Address field, type the IP address of the controller and press Enter.
3. To access the information that you need, use the links in the left-side navigation bar.

IMPORTANT The controller web pages are slightly different based on the EtherNet/
IP™ mode that is used. The web pages look different and provide
different information.
For example, consider the following:
• When the controller operates in Linear/DLR mode, the left-side
navigation bar displays a Ethernet Port A1/A2 folder with three tabs.
There is one Ethernet Port web page for both ports, and the controller
web pages provide one set of Ethernet data.
• When the controller operates in Dual-IP mode, the left-side navigation
bar displays an Ethernet Port A1 folder and an Ethernet Port A2 folder.
Each folder has three tabs. There is an Ethernet Port web page for each
port, and the controller web pages provide one set of Ethernet data for
port A1 and another set of Ethernet data for port A2.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 245


Chapter 17 Troubleshoot the Controller

Home Web Page


The Home web page provides device information and controller status.

Linear/DLR Mode

Dual-IP Mode

246 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 17 Troubleshoot the Controller

Tasks Web Page


On the Tasks web page, the pie chart shows the percentage of the control core's CPU
consumed by the tasks that are on that core. The gauges show the CPU utilization of the
control and communications cores.

The table shows the tasks that are running on the Control core (all system tasks are
summarized as one task).

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 247


Chapter 17 Troubleshoot the Controller

Diagnostics Web Pages


The Diagnostics web pages use a series of tabs to provide information about the following:
• Module Diagnostics
• Application Connections
• Bridge Connections
• Ring Statistics

248 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 17 Troubleshoot the Controller

Ethernet Port Web Pages


The Ethernet Port web pages use a series of tabs to provide information about the following:
• Diagnostic Overview
• Network Settings
• Ethernet Statistics

Linear/DLR Mode

Dual-IP Mode

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 249


Chapter 17 Troubleshoot the Controller

Advanced Diagnostics Web Pages


The Advanced Diagnostics web pages provide information about the following:
• TCP/IP Network - Provide information about the following:
- ICMP Statistics
- IP Statistics
- UDP Statistics
- TCP Statistics
- TCP Connection
- UDP Table
• Ethernet Port A1/A2- Provide information about the following:
- Interface Statistics
- ARP Table
- IP Route Table

IMPORTANT This information is listed separately for, and is unique to, each
port when the controller operates in Dual-IP mode.
• 1588 PTP (Time Sync)

250 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Chapter 17 Troubleshoot the Controller

Linear/DLR Mode

Dual-IP Mode

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 251


Chapter 17 Troubleshoot the Controller

Browse Chassis Web Page


The Browse Chassis provides information about the devices in the system. You can click the
link for each catalog number to access more information about that device.

Other Potential Issues to Your controller can experience other issues that you must troubleshoot.
Troubleshoot Continuous Task Sends Output Data at High Rate
Applies to these controllers:
CompactLogix 5380 A free-running Continuous Task can keep sending outputs at a high rate. If the Continuous
Compact GuardLogix 5380 SIL 2 Task executes repetitively with a short task execution time, and local output or produced data
Compact GuardLogix 5380 SIL 3
is changing, the controller can produce data faster than the receiving modules can react. We
recommend that you program appropriately to avoid this condition.

Immediate Output Instructions Issued at High Rate


CompactLogix 5380 and Compact GuardLogix 5380 controllers can issue Immediate Output
(IOT) instructions faster than I/O modules can react to them. We recommend that you program
IOT instructions so that they are sent at a rate appropriate for the I/O module and the
corresponding physical devices.

Integrated Motion On an EtherNet/IP Network Traffic Priority Status


When you use a Stratix® managed switch to change the network communication rate from 1
Gbps to 100 Mbps, the system can fail to prioritize the Integrated Motion On an EtherNet/IP
network communication higher than standard I/O communication.

For more information on when to use a Stratix managed switch to change the network
communication rate from 1 Gbps to 100 Mbps, see page 109.

For more information on managed switches in general, see the EtherNet/IP Network section of
the product directory accessible at this address:
http://ab.rockwellautomation.com/networks-and-communications/ethernet-ip-network.

252 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Appendix A
Status Indicators
The CompactLogix™ 5380 and Compact GuardLogix® 5380 controllers have a four-character
scrolling status display, controller status indicators, EtherNet/IP™ network status indicators,
and power indicators.

Status Display and Figure 67 shows the status display and indicators on CompactLogix 5380 and
Compact GuardLogix 5380 controllers.
Indicators
Figure 67 - Status Display and Indicators

3 3

1 1

2 2
4

Item Description
1 4-Character Scrolling Status Display, see page 253
2 Controller Status Indicators, see page 257
3 EtherNet/IP™ Status Indicators, see page 258
4 Power Status Indicators, see page 259

General Status Messages The scrolling messages that are described in this table are typically indicated upon powerup,
powerdown, and while the controller is running to show the status of the controller.
Applies to these controllers:
CompactLogix 5380 Table 45 - Controller General Status Messages
Compact GuardLogix 5380 SIL 2 Message Interpretation
Compact GuardLogix 5380 SIL 3 The controller is Off.
No message is Check the MOD POWER status indicator to see if power is applied to the system.
indicated Check the OK indicator to determine if the controller is powered and to determine the state
of the controller.
Identity Mismatch—
Contact Tech Support
Missing Vendor
Certificate—Contact Beginning with firmware revision 34.011, if a firmware update identifies the controller as
Tech Support not authentic, the hardware is permanently disabled.
Bad Vendor
Certificate—Contact
Tech Support
TEST The controller is conducting power-up tests.
CHRG The embedded energy storage circuit is charging.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 253


Appendix A Status Indicators

Table 45 - Controller General Status Messages (Continued)


Message Interpretation
PASS Power-up tests have completed successfully.
Saving...Do Not The controller is about to save an image to the SD card.
Remove SD Card
A project is being saved to the SD card. For more information, see SD Indicator on
page 257.
Let the save operation complete before you:
SAVE • Remove the SD card.
• Disconnect the power.
IMPORTANT: Do not remove the SD card while the controller is saving to the SD card. Let the save
complete without interruption. If you interrupt the save, data corruption or loss can occur.
A project is being loaded from the SD card. For more information, see SD Indicator on
page 257.
One of the following: Let the load operation complete before doing the following:
• LOAD • Remove the SD card
• Loading…Do Not • Disconnect the power
Remove SD Card IMPORTANT: Do not remove the SD card while the controller is loading from the SD card.
Let the load complete without interruption. If you interrupt the load, data corruption or loss
can occur.
A firmware update is being conducted from the SD card upon powerup. For more
information, see SD Indicator on page 257.
UPDT
If you do not want the firmware to update upon powerup, change the Load Image property
of the controller.
Rev XX.xxx The firmware major and minor revision of the controller.
5069-L3xxx The controller catalog number and series.
Message appears when an Ethernet port does not have a network connection. Message
scrolls continuously during operation.
Link Down IMPORTANT: When the controller operates in Dual-IP mode, this information is provided for
each link, that is, Link A1 and Link A2. The link name appears before the information.
Message appears when you have disabled an Ethernet port. Message scrolls continuously
during operation.
Link Disabled IMPORTANT: When the controller operates in Dual-IP mode, this information is provided for
each link, that is, Link A1 and Link A2. The link name appears before the information.
Message appears when the controller is set for DHCP, but not configured on a network. The
message shows the MAC address of the controller. Message scrolls continuously during
DHCP- operation if no IP address is set.
00:00:XX:XX:XX:XX IMPORTANT: When the controller operates in Dual-IP mode, this information is provided for
Port A1 and Port A2. The port name appears before the information.
The current port rate and duplex state when an Ethernet port has a connection. Message
Ethernet Port Rate/ scrolls continuously during operation.
Duplex State IMPORTANT: When the controller operates in Dual-IP mode, this information is provided for
each link, that is, Link A1 and Link A2. The link name appears before the information.
The IP address of the controller. Appears on powerup and scrolls continuously during
operation. If the IP address is not yet set, the MAC address appears.
IP Address IMPORTANT: When the controller operates in Dual-IP mode, this information is provided for
Port A1 and Port A2. The port name appears before the information.
Message appears when the controller detects a device with the same IP address on the
network. The message shows the MAC address of the device with the duplicate IP address.
Duplicate IP - Message scrolls continuously during operation.
00:00:XX:XX:XX:XX IMPORTANT: When the controller operates in Dual-IP mode, this information is provided for
Port A1 and Port A2. The port name appears before the information.
The controller communicated with the DHCP server to renew the IP address. The server
either did not reply or did not renew the IP address.
DHCP-Address Lost The controller continues to operate, but with no Ethernet connectivity out of this port.
IMPORTANT: When the controller operates in Dual-IP mode, this information is provided for
Port A1 and Port A2. The port name appears before the information.
The DHCP server responded with an unusable combination.
IP Address/Mask/
Gateway/DNS Invalid IMPORTANT: When the controller operates in Dual-IP mode, this information is provided for
Port A1 and Port A2. The port name appears before the information.
The IP Address that is used in the port configuration is not valid.
IP Address Invalid IMPORTANT: When the controller operates in Dual-IP mode, this information is provided for
Port A1 and Port A2. The port name appears before the information.
The Subnet/Network Mask used in the port configuration is not valid.
Mask Invalid IMPORTANT: When the controller operates in Dual-IP mode, this information is provided for
Port A1 and Port A2. The port name appears before the information.

254 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Appendix A Status Indicators

Table 45 - Controller General Status Messages (Continued)


Message Interpretation
The Gateway Address that is used in the port IP configuration is not valid.
Gateway Invalid IMPORTANT: When the controller operates in Dual-IP mode, this information is provided for
Port A1 and Port A2. The port name appears before the information.
DNS Invalid The DNS used in the port IP configuration is not valid.
No project is loaded on the controller.
To load a project:
No Project • Use the Studio 5000 Logix Designer® application to download the project to the
controller
• Use an SD card to load a project to the controller
Project Name The name of the project that is loaded on the controller.
The I/O modules that are associated with the controller are not yet fully powered.
BUSY Let powerup and I/O module self-testing complete.
The security certificate that is associated with the firmware is corrupted.
Corrupt Certificate Go to http://www.rockwellautomation.com/support/ and download the firmware revision
Received to which you are trying to update. Replace the firmware revision that you have previously
installed with that posted on the Technical Support website.
The firmware file is corrupted.
Corrupt Image Go to http://www.rockwellautomation.com/support/ and download the firmware revision
Received to which you are trying to update. Replace the firmware revision that you have previously
installed with that posted on the Technical Support website.
A failure with the embedded storage circuit has occurred, and the controller is incapable of
Backup Energy HW saving the program in the event of a powerdown. If you see this message, save your
Failure - Save Project program to the SD card before you remove power and replace the controller.
The embedded storage circuit does not have sufficient energy to enable the controller to
Backup Energy Low - save the program in the event of a powerdown. If you see this message, save your program
Save Project to the SD card before you remove power and replace the controller.
A firmware update that is initiated via ControlFLASH™ or AutoFlash software is in progress.
Flash in Progress Let the firmware update complete without interruption.
The controller is using boot firmware, that is, revision 1.xxx, and requires a
firmware update.
Firmware Installation The Compact GuardLogix SIL3 controller also shows "Firmware Installation Required", when
Required the controller and the internal safety partner have incompatible firmware. Update the
module to correct firmware version.
SD Card Locked An SD card that is locked is installed.
Download in Progress An active download is occurring
An active download is being canceled. This can be due to a user initiated cancel, a
Aborting Download download failure, or connection loss.

Compact GuardLogix Status The Compact GuardLogix 5380 controller display can show these scrolling messages.
Messages Table 46 - Safety Status Messages
Applies to these controllers: Message Interpretation
Compact GuardLogix 5380 SIL 2 No Safety Signature Safety Task is in Run mode without a safety signature. Generate a safety signature.
Compact GuardLogix 5380 SIL 3 The controller is in Run mode with a safety signature, but is not safety-locked. Safety
Safety Unlocked lock the controller.
The safety logic is invalid. For example, a watchdog timeout occurred, or memory is
corrupt.
Safety Task Inoperable For a Compact GuardLogix 5380 SIL3 controllers, a mismatch occurred between the
primary controller and the safety partner.
For Compact GuardLogix 5380 SIL3 controllers, the safety partner is missing or
Safety Partner Missing unavailable.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 255


Appendix A Status Indicators

Fault Messages If the controller displays a fault, these messages can appear on the status display.
Applies to these controllers: Table 47 - Fault Messages
CompactLogix 5380 Message Interpretation
Compact GuardLogix 5380 SIL 2 A major fault of Type XX and Code XX has been detected.
Compact GuardLogix 5380 SIL 3 Major Fault TXX:CXX message For example, if the status display indicates Major Fault T04:C42 Invalid JMP
Target, a JMP instruction is programmed to jump to an invalid LBL instruction.
An I/O fault has occurred on a module in the local chassis. The slot number
and fault code are indicated along with a brief description.
I/O Fault Local:X #XXXX message For example, I/O Fault Local:3 #0107 Connection Not Found indicates that a
connection to the local I/O module in slot three is not open.
Take corrective action specific to the type of fault indicated.
An I/O fault has occurred on a module in a remote chassis. The name of the
faulted module is indicated with the fault code and brief description of the
I/O Fault ModuleName #XXXX fault.
message For example, I/O Fault My_Module #0107 Connection Not Found indicates that
a connection to the module named My_Module is not open.
Take corrective action specific to the type of fault indicated.
An I/O fault has occurred on a module in a remote chassis. The parent name
of the module is indicated because no module name is configured in the I/O
I/O Fault ModuleParent:X #XXXX Configuration tree of Logix Designer application. In addition, the fault code is
message indicated with a brief description of the fault.
Take corrective action specific to the type of fault indicated.
I/O faults are present and X = the number of I/O faults present.
If there are multiple I/O faults, the controller indicates that the first fault
X I/O Faults reported. As each I/O fault is resolved, the number of indicated faults
decreases and the I/O Fault message indicates the next reported fault.
Take corrective action specific to the type of fault indicated.

For details about major recoverable faults and I/O fault codes, see the Logix 5000 Major, Minor,
and I/O Fault Codes Programming Manual, publication 1756-PM014.

Major Fault Messages The Major Fault TXX:CXX message on the controller status display indicates major faults.
Applies to these controllers:
CompactLogix 5380 This manual links to Logix 5000 Controller and I/O Fault Codes,
Compact GuardLogix 5380 SIL 2 publication, 1756-RD001; the file automatically downloads when you click
Compact GuardLogix 5380 SIL 3 the link.

For suggested recovery methods for major faults, see the Logix 5000 Major, Minor, and I/O
Fault Codes Programming Manual, publication 1756-PM014.

I/O Fault Codes The controller indicates I/O faults on the status display in one of these formats:
Applies to these controllers:
• I/O Fault Local:X #XXXX message
CompactLogix 5380 • I/O Fault ModuleName #XXXX message
Compact GuardLogix 5380 SIL 2 • I/O Fault ModuleParent:X #XXXX message
Compact GuardLogix 5380 SIL 3
The first part of the format is used to indicate the location of the module with a fault. How the
location is indicated depends on your I/O configuration and the properties of the module that
are specified in the Studio 5000 Logix Designer application.
The latter part of the format, #XXXX message, can be used to diagnose the type of I/O fault
and potential corrective actions.

This manual links to Logix 5000 Controller and I/O Fault Codes,
publication, 1756-RD001; the file automatically downloads when you click
the link.

256 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Appendix A Status Indicators

For suggested recovery methods for I/O faults, see the Logix 5000 Major, Minor, and I/O Fault
Codes Programming Manual, publication 1756-PM014.

Controller Status Indicators The controller status indicators display the state of the controller.
Table 48 -
IMPORTANT Safety Consideration
Applies to these controllers: Status indicators are not reliable indicators for safety functions. Use
CompactLogix 5380 them only for general diagnostics during commissioning or
Compact GuardLogix 5380 SIL 2 troubleshooting. Do not attempt to use status indicators to determine
Compact GuardLogix 5380 SIL 3 operational status.

RUN Indicator
The RUN indicator shows the current mode of the controller.

To change the controller mode, you can use the mode switch on the front of the controller or
the Controller Status menu in the Logix Designer application.

Table 49 - RUN Indicator


State Description
Off The controller is in Program or Test mode.
Steady green The controller is in Run mode.

FORCE Indicator
The Force indicator shows if I/O forces are enabled on the controller.

Table 50 - FORCE Indicator


State Description
Off No tags contain I/O force values.
I/O forces are enabled. If any I/O force values exist, they are active.
Solid yellow IMPORTANT: Use caution if you change any force values. In this state, the changes take
effect immediately.
I/O forces exist in the application, but are not active because I/O forces are not enabled.
Flashing IMPORTANT: Use caution if you enable I/O forces. All existing I/O force values take effect
yellow immediately.

SD Indicator
The SD indicator shows if the SD card is in use.
Table 51 - SD Indicator
State Description
Off No activity is occurring with the SD card.
Flashing green The controller is reading from or writing to the SD card.
IMPORTANT: Do not remove the SD card while the controller is reading or writing. Let the read/
Solid green write complete without interruption. If you interrupt the read/write, data corruption or loss can
occur.
One of the following exists:
Flashing red • The SD card does not have a valid file system.
• The SD card drew excessive current and power has been removed from the card.
Solid red The controller does not recognize the SD card.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 257


Appendix A Status Indicators

OK Indicator
The OK indicator shows the state of the controller.
Table 52 - OK Indicator
State Description
Off No power is applied.
One of the following exists:
• The controller requires a firmware update. Typically, the controller is in its out-of-box state when
a firmware update is required.
If a firmware update is required, the 4-character display indicates Firmware Installation
Required. For more information on how to update firmware,
see Upload from the Controller on page 80.
• A firmware update is in progress.
If a firmware update is in progress, the 4-character display indicates Flash in Progress. For more
Flashing red information on how to update firmware, see Upload from the Controller on page 80.
• The controller has a major fault. The fault can be recoverable or nonrecoverable. If the fault is
nonrecoverable, the program has been cleared from the controller memory.
If a fault has occurred, the 4-character display shows information about the fault, for example,
the Type and Code.
For details about major faults, see the following:
– The fault descriptions in the General Status Messages that begin on page 253.
– Logix 5000 Major, Minor, and I/O Fault Codes Programming Manual, publication 1756-PM014.
• All user tasks, that is, standard and safety, are stopped.
• One of the following:
• The controller is completing power-up diagnostics.
• The controller is depleting its residual stored energy upon powerdown.
• The controller is powered, but is inoperable.
Solid red • The controller is loading a project to nonvolatile memory.
• The controller is experiencing a Hardware Preservation Fault due to a high internal module
temperature.
In this condition, only the status indicator receives power. Once the controller cools down to an
acceptable temperature, full power is applied.
Solid green The controller is operating normally.

EtherNet/IP Status The EtherNet/IP indicators show the state of the controller Ethernet ports and network
communication activity.
Indicators
Applies to these controllers: NET A1 and NET A2 Indicators
CompactLogix 5380
Compact GuardLogix 5380 SIL 2 The NET A1 and NET A2 indicators show the state of the Ethernet port.
Compact GuardLogix 5380 SIL 3 Table 53 - NET A1 and NET A2 Indicators
State Description
One of the following:
• The controller is not configured, or does not have an IP address.
Off • The port is administratively disabled.
• The EtherNet/IP mode is Linear/DLR mode. In this case, the NET A2 indicator is off. The NET
A1 indicator remains on.
Flashing green The controller has an IP address, but no active connections are established.
Steady green The controller has an IP address and at least one established active connection.
Steady red Duplicate IP address or invalid configuration.

258 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Appendix A Status Indicators

LINK A1 and LINK A2 Indicators


The LINK A1 and LINK A2 indicators show the state of the EtherNet/IP links.
Table 54 - LINK A1 and LINK A2 Indicators
State Description
The link is down. One or more of these conditions exists:
• Ethernet cables are not properly connected at both ends. That is, the cables are not
properly connected the controller Ethernet port and to the connected device.
Off • No link exists on the port. For example, the connected device is not powered.
• The port is administratively disabled.
• LINK A2 only - The controller is the active ring supervisor in a DLR network and has
detected a rapid ring fault.
All of these conditions exist:
• The port is enabled.
Flashing green • A link exists. That is, the cable is properly connected to an enabled controller Ethernet port
on to another device.
• There is activity on the port.
All of these conditions exist:
• The port is enabled.
• A link exists. That is, the cable is properly connected to an enabled controller Ethernet port
Steady green on to another device.
• LINK A2 only - The controller is the active ring supervisor in a DLR network, and the ring is
not broken. This is normal operation.
• There is no activity on the port.

Power Status Indicators The power status indicators show the status of module power and sensor/actuator power,
known as MOD Power and SA Power, respectively.
Applies to these controllers:
CompactLogix 5380 MOD Power Indicator
Compact GuardLogix 5380 SIL 2
Compact GuardLogix 5380 SIL 3 Table 55 describes the MOD Power indicator on a CompactLogix 5380 and Compact GuardLogix
5380 controller.
Table 55 - MOD Power Indicator
State Description
Off Module Power is not present
Steady green Module Power is present(1)
(1) Although unlikely, it is possible that there is enough Module Power present for the indicator to turn steady green but the
power is not valid. Valid power is 18…32V DC to operate a CompactLogix 5380 system. If the system does not power up and
operate successfully, Module Power can be invalid.
If Module Power is invalid, we recommend that you make sure that the external power supply is working correctly, properly
sized for your application and that all wiring is correct.

SA Power Indicator
Table 56 describes the SA Power indicator on a CompactLogix 5380 and Compact GuardLogix
5380 controller.
Table 56 - SA Power Indicator
State Description
One of the following:
Off • Sensor Actuator Power is not present
• Status of Sensor Actuator power is unknown
Steady green Sensor Actuator Power is present(1)
(1) Although unlikely, it is possible that there is enough Sensor/Actuator Power present for the indicator to turn steady green but
the power is not valid. Valid power is 18…32V DC in applications that require DC voltage and 18…240V AC in applications that
require AC voltage.
If Sensor/Actuator Power is invalid, we recommend that you make sure that the external power supply is working correctly,
properly sized for your application and that all wiring is correct.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 259


Appendix A Status Indicators

Thermal Monitoring and The controllers monitor internal module temperatures. As shown below, the controller takes
actions as the temperature increases.
Thermal Fault Behavior

All power to the controller is


disabled except to run the
red OK status indicator and Threshold for controller to declare a `Hardware Preservation
monitor the temperature. Fault’, resetting the module and disabling power.
Power to the controller
is disabled In the disabled power condition, only the OK status indicator is
illuminated, and it is red. The module does not apply power until
it has cooled below the Hardware Preservation Hysteresis limit.
Power does not The module then enters fault mode, records the fault in the
become enabled when major fault log, and displays `CPU Temperature Fault’ on the
Hardware Preservation in this range front panel.
Hysteresis Limit

Threshold for controller to declare a `CPU Temperature Fault’


major recoverable fault.
If a fault handler does not clear the fault, then the module
enters fault mode, records the fault in the major fault log, and
displays `T17:C34 CPU Temperature Fault’ on the front panel.
Applies to these controllers:
CompactLogix 5380
Compact GuardLogix 5380 SIL 2 Threshold for controller to declare a `T17:C35 Controller
internal temperature is approaching operating limit’ minor
Compact GuardLogix 5380 SIL 3
fault and set the Diagnostics minor fault bit.
The fault is recorded in the minor fault log, but is not displayed
on the front panel. If the temperature returns to an acceptable
range, the Diagnostics minor fault bit clears, but the minor
fault record remains.

IMPORTANT If you follow the recommended limits for ambient (inlet) temperature and apply the required clearances around the
system, the controller is unlikely to reach the initial warning (minor fault) temperature.
For more information on CompactLogix 5380 and Compact GuardLogix 5380 controller specifications, see
CompactLogix 5380 and Compact GuardLogix 5380 Controller Specifications Technical Data, publication 5069-TD002.

IMPORTANT The presence of any temperature warning indicates that measures must be taken to reduce the ambient temperature
of the module.
Instructions for how to use Ladder Diagram to check for a minor fault can be found in the Logix 5000 Controllers Major,
Minor, and I/O Faults Programming Manual, publication 1756-PM014.
You can use a GSV instruction to read the MinorFaultBits attribute of the FaultLog class name. If the Diagnostics minor
fault bit (Bit 17) is set, a temperature minor fault can be present. Check the Minor Faults tab of the Controller Properties
dialog box in Logix Designer to see if the minor fault is a temperature warning.

260 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Appendix B
Change Controller Type
Safety controllers have special requirements and do not support certain standard features.
You must understand the behavior of the system when changing the controller type from
standard to safety, or from safety to standard, in your controller project.

Changing controller type affects the following:


• Supported features
• Physical configuration of the project
• Controller properties
• Project components such as tasks, programs, routines, and tags
• Safety Add-On Instructions

Change from a Standard to a You can change from a CompactLogix™ 5380 controller to a Compact GuardLogix® 5380
controller in safety applications.
Safety Controller
Applies to these controllers: Upon confirmation of a change from a standard controller to a safety controller project, safety
components are created to meet the minimum requirements for a safety controller:
CompactLogix 5380
Compact GuardLogix 5380 SIL 2 • The safety task is created only if the maximum number of downloadable tasks has not
been reached. The safety task is initialized with its default values.
Compact GuardLogix 5380 SIL 3
If your project already contains 32 tasks, and you try to change from a
standard to a safety controller, the project does not convert and stays with
the standard controller.
• Safety components are created (safety task, safety program, and so forth).
• A time-based safety network number (SNN) is generated for the local chassis.
• A time-based safety network number (SNN) is also generated for each embedded
EtherNet/IP™ port.
• Standard controller features that are not supported by the safety controller, such as
redundancy, are removed from the Controller Properties dialog box (if they existed).

Change from a Safety to a Upon confirmation of a change from a safety controller project to a standard controller, some
components are changed and others are deleted:
Standard Controller
• Safety I/O devices and their tags are deleted.
Applies to these controllers: • The safety task, programs, and routines are changed to a standard task, programs, and
CompactLogix 5380 routines.
Compact GuardLogix 5380 SIL 2 • All safety tags, except safety consume tags, are changed to standard tags. Safety
Compact GuardLogix 5380 SIL 3 consume tags are deleted.
• Safety tag mappings are deleted.
• The safety network numbers (SNNs) are deleted.
• Safety-lock and -unlock passwords are deleted.
• If the standard controller supports features that were not available to the safety
controller, those new features are visible in the Controller Properties dialog box.
Peer safety controllers are not deleted, even if they have no
connections remaining.

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 261


Appendix B Change Controller Type

• Instructions can still reference modules that have been deleted and can produce
verification errors.
• Consumed tags are deleted when the producing module is deleted.
• As a result of the above changes to the system, safety-specific instructions and safety
I/O tags do not verify.

If the safety controller project contains safety Add-On Instructions, you must remove them
from the project or change their class to standard before changing the controller type.

Change Safety When you change from one safety controller type to another, the class of tags, routines, and
programs remain unaltered. Any I/O devices that are no longer compatible with the target
Controller Types controller are deleted.
Applies to these controllers:
If you change from a safety controller with a SIL 3/PLe application to a Compact GuardLogix
Compact GuardLogix 5380 SIL 2
5380 SIL 2 controller, the application changes to SIL 2/PLd.
Compact GuardLogix 5380 SIL 3
If you change from a safety controller with a SIL 3/PLe application to a Compact GuardLogix
5380 SIL 3 controller, the application remains SIL 3/PLe.

If you change from a safety controller with a SIL 2/PLe application to a Compact GuardLogix
5380 SIL 3 controller, the representation of the safety partner is updated to appear
appropriately for the target controller.
Safety Network Numbers are also preserved when you change to a Compact GuardLogix 5380
controller.

262 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Appendix C
History of Changes
This appendix contains the new or updated information for each revision of this
publication. These lists include substantive updates only and are not intended to reflect all
changes. Translated versions are not always available for each revision.
5069-UM001J-EN-P, November 2022
Change
Moved information about connection reaction time limit to publication 1756-RM012
Added Real-time Clock section to Chapter 1: CompactLogix 5380 and Compact GuardLogix 5380 Systems and
Controllers
Revised information about the safety signature
Added information about secure socket objects
Added Monitor Safety I/O Device Status section in Chapter 12: Safety I/O Devices
Added introduction and Program Safety Applications section to Chapter 14: Develop Safety Applications and moved
other safety topics from Chapter 14 to publication 1756-RM012

5069-UM001I-EN-P, March 2022


Change
Updated Appearance Change section
Added CIP Security™ to controller features table
Added new section about CIP Security
Updated general status messages for the controller

5069-UM001H-EN-P, October 2021


Change
Updated graphics throughout
Added MOD Power note
Updated the Use ControlFLASH Plus Software to Update Firmware section
Updated general status messages
Updated major fault messages
Updated I/O fault codes

5069-UM001G-EN-P, August 2020


Change
Added CompactLogix™ 5380 Process controllers
Updated safety signature definition
Added Simple Network Management Protocol (SNMP)
Added Automatic Diagnostics
Added Considerations for Communication Loss Diagnostics
Updated the Disable Controller Web Pages procedure

5069-UM001F-EN-P, May 2020


Change
Added Compact GuardLogix® 5380 SIL 3 controller information
Added links to access Controller and I/O fault code information from the Knowledgebase Support Center
Added Firmware Upgrade Guidelines for Safety Controllers

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 263


Appendix C History of Changes

5069-UM001E-EN-P, January 2020


Change
Updated the description of Ethernet ports A1 and A2
Updated the Connect an Ethernet Cable section
Added the 1784-SDHC8 and 1784-SDHC32 SD cards

5069-UM001D-EN-P, April 2018


Change
Added Compact GuardLogix® 5380 and Safety information throughout
Chapter 3, How to Power Compact GuardLogix 5380 Controllers
Chapter 4, Safety Concept of Compact GuardLogix 5380 Controllers
Chapter 12, Safety I/O Devices
Chapter 14, Develop Safety Applications

5069-UM001C-EN-P, December 2016


Change
Added CompactLogix 5380 controllers 5069-L350ERM, 5069-L380ERM, 5069-L3100ERM

264 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Appendix C History of Changes

Notes:

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 265


Appendix C History of Changes

266 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Index

Numerics communication path


set 72
10/100/1000 49 Compact 5000 I/O modules 141, 148
1732 ArmorBlock Guard I/O modules 148
CompactLogix 5380
1732D ArmorBlock I/O modules 148 design system 18
1734 POINT I/O modules 148 CompactLogix 5380 Process controllers 16
1746 SLC I/O modules 148 configuration owner
1756 ControlLogix I/O modules 148 identifying 168
1769 Compact I/O modules 148 resetting 168, 169
1784-SD1 and 1784-SD2 cards configuration signature
load from 97 - 100 components 168
other tasks 100 copy 168
store to 94 definition 168
1794 FLEX I/O modules 148 configure
4-character status display motion 229
fault messages 256 configure change detection 205
general status messages 253 audit value 206
I/O fault codes 256 consume data 138
continuous task 179
control data 137
A controler security 196
add I/O modules while online 157 ControlFLASH software 56, 76
Add-On Instructions 186, 262 controller
Advanced Diagnostics web page available modes 83
use to troubleshoot 250 behavior 137
allow communication 137 change type 261 - 262
API 114 design system with 18
application download project 77
elements 177 firmware
obtain 55
audit value 206
go online 72
AutoFlash match 75
update 61 serial number 75
axes serial number mismatch 77, 79
consumed 229 set communication path 72
virtual 229 upload project 80
axis controller firmware
obtain information 231 update with AutoFlash 61
update with ControlFLASH 56
controller log 207
B controller operation mode
block communication 137 change with Logix Designer application 85
Browse Chassis web page change with mode switch 84
use to troubleshoot 252 controller reset
stage 1 87
stage 2 88
C controller status
4-character status display
changing controllers 262 fault messages 256
CIP Safety 176 general status messages 253
CIP Safety I/O I/O fault codes 256
adding 161 controller status indicators 257
configuration signature 168 FORCE indicator 257
node address 161 OK indicator 258
CIP Security ports RUN indicator 257
disable 212 SD indicator 257
communication controller tasks 177
allow 137
block 137
with EtherNet/IP devices via socket
interface 114

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 267


Index

controller web pages EtherNet/IP mode


disable 222 change 129 - 132
troubleshoot with Advanced Diagnostics change via Logix Designer application 130
web page 250 change via RSLinx Classic software 131
troubleshoot with Browse Chassis web page configure 124 - 128
252 configure Dual-IP mode via Logix Designer
troubleshoot with Diagnostics web page 248 application 124
troubleshoot with Ethernet Port A1/A2 web configure Dual-IP mode via RSLinx Classic
page 249 software 125
troubleshoot with Home web page 246 configure Linear/DLR mode via Logix
troubleshoot with Tasks web page 247 Designer application 126
use to troubleshoot 245 - 252 configure Linear/DLR mode via RSLinx
create a fault routine 201 Classic software 128
Dual-IP mode 118
overlapping IP address ranges 123
D Linear/DLR mode 121
EtherNet/IP network
data update
communication via socket interface 114
I/O data 158 linear network topology 107
design network communication rates 109
system 18 nodes 104
diagnostics optimize network performance 109
with Logix Designer 234 - 244 star network topology 107
with RSLinx Classic software 244 topologies 105 - 107
Diagnostics web page EtherNet/IP status indicators 258
use to troubleshoot 248 LINK A1 and LINK A2 indicators 259
disable CIP Security ports 212 NET A1 and NET A2 indicators 258
disable controller web pages 222 event tasks 179
disable Ethernet ports 208
disable SD card 216
disable the 4-character status display 218
F
disable USB port 215 fault
DLR network topology 148 cpu temperature 260
hardware preservation 260
DNS addressing 53 recoverable 260
download fault codes 256
effect of controller match 75 use GSV instruction to get 190
effect of firmware revision match 76 fault handler
effect of safety status 76 execute at I/O module fault 190
project 77 fault messages
Dual-IP mode 118
on 4-character status display 256
overlapping IP address ranges 123 FBD
duplicate IP address
using 186
detection 52 firmware
resolution 52
obtain 55
update controller firmware 54 - 62
E update with AutoFlash 61
update with ControlFLASH 56
electronic keying firmware revision
about 147 match 76
elements mismatch 77, 79
control application 177 firmware upgrade kit 76
enable license-based protection 203 FORCE status indicator 257
Ethernet 49
Ethernet Port A1/A2 web page
use to troubleshoot 249 G
Ethernet ports GSV instruction
disable 208 monitor a connection 190
Dual-IP mode 118 use to get fault codes 190
Linear/DLR mode 121

H
handshake 137
Home web page
use to troubleshoot 246

268 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Index

I Logix Designer application


I/O add I/O modules while online 157
add local I/O modules to a project 142 - 146
determine data update 158 add remote I/O modules to a project 150 -
I/O fault codes 157
on 4-character status display 256 Add-On Instructions 186
I/O modules change controller operation mode 85
about local I/O modules 141 change EtherNet/IP mode 130
about remote I/O modules 148 configure Dual-IP mode 124
add local I/O modules to Logix Designer configure Linear/DLR mode 126
application project 142 - 146 continuous tasks 179
add remote I/O modules to Logix Designer develop applications 177
application project 150 - 157 develop motion applications 229 - 231
add while online 157 diagnotics 234 - 244
connection error 190 download project 77
local event tasks 179
example 142 go online 72
on a DLR network topology 148 motion instructions 230
on a linear network topology 149 obtain motion axis information 231
on a star network topology 149 parameters 184
remote periodic tasks 179
example 148 programming languages 186
instructions programs 181
motion 230 routine 183
IP addresses routines 183
set communication path 72
Dual-IP mode 118
tags 184
overlapping IP address ranges 123
tasks in project 177
duplicate address detection 52
troubleshoot with Advanced Time Sync
duplicate address resolution 52
dialog box 241
Linear/DLR mode 121
troubleshoot with Connection category 236
troubleshoot with Ethernet Port Diagnostics
J dialog box 239
troubleshoot with General category 235
jump to the fault routine 201 troubleshoot with I/O module properties
dialog box 235 - 237
troubleshoot with Module Info category 236
L upload project 80
Ladder Logic
using 186 M
license-based source and execution protection
match project to controller 75
202
memory card
enable license-based protection 203
linear network topology 107, 149 load project from card 97 - 100
other tasks 100
Linear/DLR mode 121 store project to card 94
LINK A1 and LINK A2 status indicators 259 message
load about 139
from memory card 97 - 100 messages
load a project safety status 255
on corrupt memory 95 MOD power indicator 259
on power up 95 mode switch
user initiated 95 change controller operation mode 84
local I/O modules
position 83
about 141 module
add to a Logix Designer application project
properties
142 - 146 connection tab 168
example 142
monitor I/O connections 189
motion
about 229
instructions 230
obtain axis information 231
program 230

N
NET A1 and NET A2 status indicators 258

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 269


Index

network address R
DNS addressing 53
receive messages 139
network address translation (NAT)
remote I/O modules
set the IP address 163
network communication rates 1732 ArmorBlock Guard I/O 148
1732D ArmorBlock I/O 148
on an EtherNet/IP network 109
1734 POINT I/O 148
network status
1746 SLC I/O 148
indicator 173, 174 1756 ControlLogix I/O 148
node address 161 1769 Compact I/O 148
nodes on an EtherNet/IP network 104 1794 FLEX I/O 148
nonvolatile memory about 148
tab 91 add to a Logix Designer application project
150 - 157
Compact 5000 I/O modules 148
O example 148
replace
obtain configure only… enabled 172
axis information 231 Guard I/O module 170 - 176
firmware 55 reset
OK status indicator 258
module 168
online ownership 169
go 72 reset button 86
optimize EtherNet/IP network performance 109 stage 1 reset 87
out-of-box 172 stage 2 reset 88
reset module 168 reset module 169
overlapping IP address ranges 123 routines 183
ownership in project 183
configuration 168 RSLinx Classic software
resetting 168 change EtherNet/IP mode 131
configure Dual-IP mode 125
configure Linear/DLR mode 128
P diagnotics 244
parameters RSWho
in project 184 set communication path 72
path RUN status indicator 257
set 72
Performance Level 43
periodic tasks 179
S
Power status indicators 259 SA power indicator 259
MOD power indicator 259 safety network number
SA power indicator 259 automatic assignment 68
produce data 138 copy 70, 166
produce/consume data 138 description 67
managing 67
programming languages 186 manual assignment 68
FBD 186 paste 70, 166
Ladder Logic 186 set 164
SFC 186 time-based 68
Structured Text 186 safety signature
programs
effect on download 76
in project 181 effect on upload 76
scheduled 182 storing a project 94
unscheduled 182 safety status
project
effect on download 76
download 77 view 76
elements 177 safety tab
go online 72 configuration signature 168
programs 181
module replacement 170
routines 183
view safety status 76
tasks 177
safety-lock
upload 80
projects effect on download 76
Add-On Instructions 186 effect on upload 76
scheduled programs 182
parameters 184
programming languages 186
tags 184

270 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


Index

SD card troubleshoot with General category


disable 216 235
load from 97 - 100 troubleshoot with I/O module proper-
other tasks 100 ties dialog box 235 - 237
store to 94 troubleshoot with Module Info category
SD status indicator 257 236
secure applications 195 upload project 80
RSLinx Classic
configure change detection 205 change EtherNet/IP mode 131
audit value 206 configure Dual-IP mode 125
controller log 207 configure Linear/DLR mode 128
controller security 196 diagnostics 244
disable CIP Security ports 212 stage 1 reset 87
disable controller web pages 222
disable port 215 stage 2 reset 88
disable SD card 216 star network topology 107, 149
disable the 4-character status display 218 status
disable the Ethernet porst 208 messages 255
license-based source and execution status indicators
protection 202 controller status 257
enable license-based protection 203 EtherNet/IP status indicators 258
user-definable major faults 201 FORCE indicator 257
Secure Digital (SD) card LINK A1 and LINK A2 indicators 259
disable 216 MOD power indicator 259
secure socket objects 114 NET A1 and NET A2 indicators 258
send messages 139 OK indicator 258
sercos 229 Power status indicators 259
serial number 75 RUN indicator 257
SA power indicator 259
SFC SD indicator 257
using 186 status messages
socket interface 114 on 4-character status display 253
software store
add I/O modules while online 157 to memory card 94
add local I/O modules to a Logix Designer store a project 94
project 142 - 146 Structured Text
add remote I/O modules to a Logix Designer
project 150 - 157 using 186
change EtherNet/IP mode 129 - 132
configure EtherNet/IP mode 124 - 128
go online 72 T
Logix Designer application tags
Add-On Instructions 186 consume 138
change controller operation mode 85 in project 184
change EtherNet/IP mode 130 naming 169
configure Dual-IP mode 124 produce 138
configure Linear/DLR mode 126 tasks
continuous tasks 179 continuous 179
develop applications 177 event 179
develop motion applications 229 - 231 in Logix Designer application project 177
diagnostics 234 - 244 periodic 179
download project 77 priority 180
event tasks 179 Tasks web page
motion instructions 230
motion overview 229 use to troubleshoot 247
obtain motion axis information 231 temperature
periodic tasks 179 limit 260
programming languages 186 warning 260
programs in project 181 thermal monitoring 260
project parameters 184 TLS 114
project tags 184 topologies
routines in project 183 available on an EtherNet/IP network 105 -
set communication path 72 107
tasks 177 linear 107
troubleshoot with Advanced Time Sync star 107
dialog box 241
troubleshoot with Connection category
236
troubleshoot with Ethernet Port Diag-
nostics dialog box 239
Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 271
Index

troubleshoot
with Advanced Diagnostics web page 250
with Advanced Time Sync dialog box in Logix
Designer application 241
with Browse Chassis web page 252
with Connection category in Logix Designer
application 236
with controller web pages 245 - 252
with Diagnostics web page 248
with Ethernet Port A1/A2 web page 249
with Ethernet Port Diagnostics dialog box in
Logix Designer application 239
with General category in Logix Designer
application 235
with Home web page 246
with I/O module properties dialog box in
Logix Designer application 235 -
237
with Module Info category in Logix Designer
application 236
with Tasks web page 247

U
unscheduled programs 182
update
determine frequency 158
update controller firmware 54 - 62
update firmware
AutoFlash 61
upload
effect of controller match 75
effect of safety signature 76
effect of safety-lock 76
project 80
USB port
disable 215
use a fault routine 201
use GSV instruction to get fault codes 190
user-definable major faults 201
create a fault routine 201
jump to the fault routine 201
use a fault routine 201

V
view
safety status 76

W
webpages
disable 222

272 Rockwell Automation Publication 5069-UM001K-EN-P - November 2023


CompactLogix 5380 and Compact GuardLogix 5380 Controllers User Manual

Notes:

Rockwell Automation Publication 5069-UM001K-EN-P - November 2023 273


Rockwell Automation Support
Use these resources to access support information.
Find help with how-to videos, FAQs, chat, user forums, Knowledgebase, and product
Technical Support Center rok.auto/support
notification updates.
Local Technical Support Phone Numbers Locate the telephone number for your country. rok.auto/phonesupport
Quickly access and download technical specifications, installation instructions, and user
Technical Documentation Center rok.auto/techdocs
manuals.
Literature Library Find installation instructions, manuals, brochures, and technical data publications. rok.auto/literature
Product Compatibility and Download Center Download firmware, associated files (such as AOP, EDS, and DTM), and access product rok.auto/pcdc
(PCDC) release notes.

Documentation Feedback
Your comments help us serve your documentation needs better. If you have any suggestions on how to improve our content, complete the
form at rok.auto/docfeedback.

Waste Electrical and Electronic Equipment (WEEE)

At the end of life, this equipment should be collected separately from any unsorted municipal waste.

Rockwell Automation maintains current product environmental compliance information on its website at rok.auto/pec.

Allen-Bradley, ArmorBlock, Compact 5000, Compact I/O, CompactBlock, CompactLogix, ControlBus, ControlFLASH, ControlFLASH Plus, ControlLogix, DH+, expanding human possibility,
FactoryTalk, FLEX, Guard I/O, Guardmaster, GuardLogix, Integrated Architecture, Kinetix, Logix 5000, On-Machine, PanelView, PlantPAx, PLC-2, PLC-3, PLC-5, POINT I/O, POINT Guard I/O,
PowerFlex, Rockwell Automation, RSLinx, RSNetWorx, SLC, Stratix, Studio 5000, and Studio 5000 Logix Designer are trademarks of Rockwell Automation, Inc.
CIP, CIP Safety, CIP Sync, ControlNet, DeviceNet, and EtherNet/IP are trademarks of ODVA, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.
Rockwell Otomasyon Ticaret A.Ş. Kar Plaza İş Merkezi E Blok Kat:6 34752, İçerenköy, İstanbul, Tel: +90 (216) 5698400 EEE Yönetmeliğine Uygundur

Publication 5069-UM001K-EN-P - November 2023


Supersedes Publication 5069-UM001J-EN-P - November 2022 Copyright © 2023 Rockwell Automation, Inc. All rights reserved. Printed in the U.S.A.

You might also like