WEG Soft Starters 50019077 en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

SOFT-STARTERS

Advanced technology for the


soft-start of electric motors

Motors | Automation | Energy | Transmission & Distribution | Coatings


www.weg.net

2 Soft-Starters
Soft-Starters

Summary
Introduction 04

Main Functions 06

Applications 07

Connectivity 08

SSW05 10

SSW07 / SSW08 12

SSW900 16

Comparison 21
www.weg.net

ADVANCED TECHNOLOGY
FOR THE SOFT-START OF
ELECTRIC MOTORS

In view of the evolution of processes and machines, it has become increasingly clear the need to use
resources that allow driving motors in a smooth and controlled way. Using cutting-edge technology,
WEG soft-starters have been designed to ensure the best performance for each kind of
application, offering resources that enable to start and stop three-phase induction motors
in a simple and efficient way, protecting the motor and the load from torque shocks (jolts) by means of
gradual acceleration up to the rated speed.

WEG soft-starters are the ideal solutions with excellent cost-benefit for starting and stopping
three-phase induction motors in applications requiring speed and torque control during the start.

4 Soft-Starters
www.weg.net

Benefits

Simple operation and Easy installation Effective motor Free programming Special Excellent
maintenance and start-up protection software functions cost-effectiveness

Soft-Starters 5
www.weg.net

Main Functions
Kick Start Reduction of the Water Hammer
Ideal for applications where the loads require an extra effort Using an SSW to for stopping the motor softly (pump control)
from the drive at the moment of the start due to the high reduces the chances of Water Hammer.
resistant torque, being necessary feed the motor with a
higher voltage than that set in the acceleration voltage ramp.

Pump Control Voltage Ramp in the Deceleration


This is a preset (specific) configuration for pumping systems, At the controlled stop, the SSW will gradually reduce the output
where it is usually necessary to establish a voltage ramp in voltage to a minimum value in a preset time.
the acceleration and deceleration, in addition to enabling
protections in the SSW.

Motor Coasting Voltage Ramp in the Acceleration


The SSW takes the output voltage instantaneously to zero, The SSW, by controlling the variation of the firing angle of the
implying that the motor does not produce any torque on the thyristor bridge generates a gradual and continuous effective
load, which in turn will slow down until all the kinetic energy voltage at its output, increasing until the rated line voltage is
is dissipated. reached.

Current Limitation
Used in most cases where the load has a high inertia, this
function causes the grid/SSW system to feed the motor with
the current just necessary to perform the load acceleration.

Note: for more details, refer to the catalog or user’s manual of each SSW, available on our website: www.weg.net.

6 Soft-Starters
www.weg.net

Applications

Ventilation Sugar &


& Exhaust Alcohol

Cement
Agribusiness
& Mining

Water & Chemical, Petrochemical,


Wastewater Oil & Gas

Soft-Starters 7
www.weg.net

Connectivity

SuperDrive G2
Using the SuperDrive G2 software, it is possible to change, monitor and graphically view the variables of
the frequency inverter via connection to a personal computer.

Trend Function
Trend charts for online monitoring of parameters and other variables within the SuperDrive G2 software.
J Easy operation and view

J Free on www.weg.net

8 Soft-Starters
www.weg.net

WEG Programming Suite (WPS)


Integrated tool that assists in the creation of automation
applications, allowing graphical monitoring, parameter setting and
programming in Ladder language (IEC 61131-3) of various WEG
product families.
J Multi-Products, meeting the requirements of a wide range of
WEG products
J Multi-Use, allowing:

J Parameter setting of the devices

J 
Programming of the devices in Ladder language
J Monitoring of the devices

J 
Assistance in the creation and configuration of automation
applications

WEG Ladder Programmer (WLP)4)


Software for Windows® environment that enables the programming in
Ladder language of various WEG product families.
J 
Edition of the program by means of several Ladder function blocks
J Compilation of the program in Ladder for a language compatible with

the devices
J Transfer of the compiled program to the devices

J Reading of the program installed on the devices1)

J 
Online monitoring of the program running on the devices
J Point-to-point communication with the devices through serial in

RS232 or USB2)
J Serial communication in RS485 with up to 30 devices3)

J 
Online help with all the functions and blocks present in the software
Notes: 1)For devices that supports the upload function.
2) For devices that have a USB communication port.
3) Through an RS232-to-RS485 converter connected to the PC.
4) Functions valid only for SSW900.

Soft-Starters 9
www.weg.net

SSW05
The SSW05 is WEG’s most compact solid state starter with control of two motor
phases, built-in bypass and all the protections for the electric motor. Featuring DSP
control (Digital Signal Processor), the SSW05 is designed for optimal performance
in motor start and stop, with excellent cost-effectiveness. In addition, they are easily
set, simplifying the start-up activities and daily operations. Their compact
dimensions contribute to the optimization of spaces in electrical panels.

Main Characteristics
J Current ranges from 3 to 85 A J Built-in bypass J  reat reduction of the forces on the
G
J Supply voltage from 220 to 460 V ac J Electronic thermal relay couplings and on the transmission
or from 460 to 575 V ac J Built-in motor protections devices (gearboxes, pulleys, gears,
J Simple electrical installation J Easy to operate, adjust and service belts, etc.) during the start
J Compact J Remote operating interface (HMI) J Extended motor and equipment
J Control with digital processor (DSP) (optional) lifespan without mechanical shocks
J High efficiency J Operation in environments up to 55 °C

Settings and Indications

Dip switch to enable/disable the


motor protections Three-phase power supply input

Protection LED indicators


Electronics power supply and digital inputs

Status LED indicators

Pedestal voltage, acceleration and


Connector for serial or remote HMI
deceleration time, and motor current settings

Digital relay outputs


Output to the motor

Certifications

10 Soft-Starters
www.weg.net

Specifcation
The power ratings for the maximum applicable motor shown in the following tables are referential and valid for WEG 4-pole
three-phase induction motors under light load conditions (e.g., centrifugal pump). Motor rated power may vary according to the
motor data and application.
Maximum applicable motor
Frame Rated current
SSW05 220/230 V 380/400 V 440/460 V 575 V
size (A)
HP kW HP kW HP kW HP kW
SSW050003T2246TPZ 3 0.75 0.5 1.5 1.1 2 1.5 - -
SSW050010T2246TPZ 10 3 2.2 6 4.5 7.5 5.5 - -
SSW050016T2246TPZ 1 16 5 3.7 10 7.5 12.5 9.2 - -
SSW050023T2246TPZ 23 7.5 5.5 15 11 15 11 - -
SSW050030T2246TPZ 30 10 7.5 20 15 20 15 - -
SSW050045T2246TPZ 45 15 11 30 22 30 22 - -
SSW050060T2246TPZ 2 60 20 15 40 30 40 30 - -
SSW050085T2246TPZ 85 30 22 60 45 60 45 - -
SSW050003T4657TPZ 3 - - - - - - 2 1.5
SSW050010T4657TPZ 10 - - - - - - 7.5 5.5
SSW050016T4657TPZ 1 16 - - - - - - 10 7.5
SSW050023T4657TPZ 23 - - - - - - 20 15
SSW050030T4657TPZ 30 - - - - - - 25 18.9
SSW050045T4657TPZ 45 - - - - - - 40 30
SSW050060T4657TPZ 2 60 - - - - - - 50 37.8
SSW050085T4657TPZ 85 - - - - - - 75 56.7

Accessories
Model Description
SSW05-7-8-CB-RS-1M 1 m serial remote HMI cable
SSW05-7-8-CB-RS-2M 2 m serial remote HMI cable
SSW05-7-8-CB-RS-3M 3 m serial remote HMI cable
SSW05-HMI-RS Remote HMI for use with CAB-RS cable up to 3 m

Dimensions and Weights


La
L A

H Ha B

Width L (mm) Height H (mm) Mounting A Mounting B Mounting D Weight


Size Depth P (mm) Mounting
L La H Ha (mm) (mm) (mm) (kg)
1 59 60.4 130 130.7 145 51 122 61 M4 Screw/Rail 0.74
2 79 80.4 185 185.7 172 71 177 99 M4 Screw/Rail 1.64

Note: La, Ha, Mounting (only for mounting with screw).

Soft-Starters 11
www.weg.net

SSW07 /
ssw08

Developed for industrial or professional applications,


the SSW07 and SSW08 soft-starters are compact
and have built-in bypass, thus contributing to
increased lifespan, space optimization and less
heat dissipation in electrical panels.

The SSW07 and SSW08 soft-starters are equipped with the same functionalities. The SSW07 controls
three motor phases, being recommended to drive heavy loads, while the SSW08 controls two motor
phases, and it is recommended to drive light to moderate loads.

Main Characteristics
J Current ranges from 17 to 412 A J Electronic thermal relay
J Supply voltage from 220 to 575 V ac J Thermal image (monitoring of the electronics voltage,
J Simple electrical installation allowing the backup of the current and voltage values)
J Built-in bypass J Interconnection with Fieldbus communication networks:
J Kick start function to start loads with high static friction Modbus-RTU and DeviceNet (optional)
J Switched-mode power supply of the electronics with EMC J Human-Machine Interface - HMI (optional)
filter (110 to 220 V) J Free SuperDrive G2 programming software
J Full electronic motor protection

Certifications

12 Soft-Starters
www.weg.net

Settings and Indications

Supply voltage input

Trimpots for setting Dip switch to set and enable the protections

Status LED indicators

Dip switch for thermal class setting

Reset button

Plug-in accessory cap

Electronics power supply (A1 and A2)

Relay output
Run/Stop motor (DI1) and Reset
(DI2 and DI3) command

Output to the motor

Soft-Starters 13
www.weg.net

Specification
The power ratings for the maximum applicable motor shown in the following tables are referential and valid for WEG 4-pole
three-phase induction motors under light load conditions (e.g., centrifugal pump). Motor rated power may vary according to the
motor data and application.
Maximum applicable motor
Frame Rated current
SSW07/ SSW08 220/230 V 380/400 V 440/460 V 525 V 575 V
size (A)
HP kW HP kW HP kW HP kW HP kW
SSW0□0017T5SZ 17 6 4.5 10 7.5 12.5 9.2 15 11 15 11
SSW0□0024T5SZ 1 24 7.5 5.5 15 11 15 11 20 15 20 15
SSW0□0030T5SZ 30 10 7.5 20 15 20 15 25 18.5 30 22
SSW0□0045T5SZ 45 15 11 30 22 30 22 40 30 40 30
SSW0□0061T5SZ 2 61 20 15 40 30 50 37 50 37 60 45
SSW0□0085T5SZ 85 30 22 60 40 60 45 75 55 75 55
SSW0□0130T5SZ 130 50 37 75 55 100 75 125 90 125 90
SSW0□0171T5SZ 3 171 60 45 125 90 125 90 150 110 175 132
SSW0□0200T5SZ 200 75 55 125 90 150 110 200 150 200 150
SSW0□0255T5SH♦Z 255 100 75 175 130 200 150 250 185 250 185
SSW0□0312T5SH♦Z 312 125 90 200 150 250 185 300 220 300 220
4
SSW0□0365T5SH♦Z 365 150 110 250 185 300 220 350 260 350 260
SSW0□0412T5SH♦Z 412 150 110 300 220 350 260 440 315 450 330

Notes: Replace □ to the desired option, 7 for SSW07 or 8 for SSW08.


Replace ♦ by 1 for 110 V control voltage power supply or 2 for 220 V control voltage power supply.
WEG Premium motors or Plus / IV Poles - 60 Hz.

Accessories
Reference Description
SSW07-08-HMI-LOC Local Human-Machine Interface - HMI
SSW07-HMI-REM Remote human-machine interface kit (HMI LED + HMI interface module) for SSW07
SSW08-HMI-REM Remote human-machine interface kit (HMI LED + HMI interface module) for SSW08
CAB-RS-1M-SSW07/08 1 m cable to connect to remote HMI
CAB-RS-2M-SSW07/08 2 m cable to connect to remote HMI
CAB-RS-3M-SSW07/08 3 m cable to connect to remote HMI
CAB-RS-5M-SSW07/08 5 m cable to connect to remote HMI
CAB-RS-7,5M-SSW07/08 7.5 m cable to connect to remote HMI
CAB-RS-10M-SSW07/08 10 m cable to connect to remote HMI
HMI-SSW07-REM+RS485 Remote human-machine interface kit (HMI LED + HMI interface module) for SSW07
HMI-SSW08-REM+RS485 Remote human-machine interface kit (HMI LED + HMI interface module) for SSW08
SSW07-08-KRS-485 RS485 communication kit
KFB-DN-SSW07/08 DeviceNet communication module
SSW07-08-KRS-232 RS232 communication module
KRS232-SSW07/08 RS232 communication module and cable kit
CAB-SER-3M-SSW07/08 3 m cable for serial connection to PC
CAB-SER-10M-SSW07/08 10 m cable for serial connection to PC
SSW0708900-KVT-2B Ventilation kit for frame 2 (currents from 45 to 85 A)
SSW0708900-KVT-3C Ventilation kit for frame 3 (currents from 130 to 200 A)
SSW07-08-KPTC-MTR Motor PTC module
SSW07/08/900-IP20-3C IP20 kit for frame 3 (currents from 130 to 200 A)
SSW07/08/900-IP20-4D IP20 kit for frame 4 (currents from 255 to 412 A)
SSW0708900-PROT-3C Touch protection kit for frame 3 (currents from 130 to 200 A)
SSW0708900-PROT-4D Touch protection kit for frame 4 (currents from 130 to 200 A)

14 Soft-Starters
www.weg.net

Dimensions and Weights


L

B H

C
P

The SSW07 and SSW08 soft-starters have the same dimensions, according to following table:
Height Width Depth
A B C D Mounting Weight Protection
Model H L P
(mm) (mm) (mm) (mm) screw (kg) rating
(mm) (mm) (mm)
17 A
24 A 162 95 157 85 120 5 4 M4 1.3 IP20
30 A
45 A
61 A 208 144 203 132 148 6 3.4 M4 3.3 IP20
85 A
130 A
171 A 276 223 220 208 210 7.5 5 M5 7.6 IP001)
200 A
255 A
312 A
331 227 242 200 280 15 9 M8 11.5 IP001)
365 A
412 A
Note: 1) IP20 with accessory kit KIP20.

Soft-Starters 15
www.weg.net

SSW900
Combining convenience and innovation, the SSW900 is the right
choice for the full motor start, stop and protection control. Developed
for industrial or professional use, the new line of soft-starters allows
simple and quick access to information on the application and
configuration settings.
Using a menu structure, the new interface of the SSW900 line presents an unprecedented experience of
interactivity with the user, allowing settings and configurations with online parameter help right on the HMI, in
addition to event logs with date and time and setup wizard.
The equipment also has built-in bypass, which contributes to extending the lifespan of the drive, optimizing
space and reducing heat dissipation in electric panels.

Main Characteristics
J Current ranges from 10 to 1,400 A J  reat mechanical stresses reduction on
G J Built-in
 bypass: minimizing power
� Supply
 voltage from 220 to 575 V ac the couplings and transmission devices losses and heat dissipation in the
(T5) or from 380 to 690 V ac (T6) (gear boxes, pulleys, gears, belts, etc.) thyristor, providing space reduction,
J Oriented start-up during the motor start contributing to energy saving and
J Standard
 connection (3 cables) J Increased
 motor and equipment lifetime increasing the product’s life
or motor inside delta connection J Elimination
 of starting mechanical
(6 cables) shock to couplings and driven
J Integral
 motor thermal protection equipment
J Reduction of voltage drops during motor J Operation at ambient temperature up to
start 55 °C without current1) derating
J Pump
 control function for smart J Three braking methods to stop the
control of pumping systems that motor and the load faster. Braking
prevent water hammer and pressure methods with or without external
overshoots in the hydraulic piping contactors

The SSW900 can substitute direct online starters or star-delta starters,


bringing benefits to your application, such as:
J Electric energy savings

MORE
J Greater protection and increased durability of the electric motor

J Diagnosis and fault history

J Flexibility, it allows the installation of accessories in the application (plug


ADVANTAGES and play)
J Graphic monitoring

J Customizable main screens

Menu Easy Easy to Simple


Note: 1) Models A to D. navigation to install operate monitoring

16 Soft-Starters
www.weg.net

Easy to Use
Bluetooth connectivity1)
USB Port
Easy monitoring via PC or
firmware updating RTC
Real time clock with event log
including date and time

Detachable Keypad
Option to install on machine Graphic HMI
or panel door Intuitive, customizable, complete

Easy access to the control


terminals: digital and analog
inputs and outputs

Flexibility Power supply connection

LED HMI connection


Visual status indication

Two Slots
Two accessory modules
can be used

I/O
Totally programmable inputs
and outputs
RTC battery J  isolated digital
5
input 24 V dc
J 1 analog output
0-10 V dc / 4-20 mA
J 1 input for the
motor PTC
J 3 relay outputs
Quick Connect
1.0 A / 240 V ac
Detachable terminals

Motor connection

Note: 1) HMI with Bluetooth connectivity available as an accessory


item. Please consult the availability for your region.

Soft-Starters 17
www.weg.net

Specification
The power ratings for the maximum applicable motor shown in the following tables are referential and valid for WEG 4-pole
three-phase induction motors under light load conditions (e.g., centrifugal pump). Motor rated power may vary according to the
motor data and application.

Standard Connection (with 3 Cables)


Maximum applicable motor
Rated
Frame
SSW900 current 220/230 V1) 380/400 V 440/460 V 525 V 575 V 690 V2)
size
(A)
HP kW HP kW HP kW HP kW HP kW HP kW
SSW900A0010T5E2 10 3 2.2 6 4.5 7.5 5.5 7.5 5.5 10 7.5 - -
SSW900A0017T5E2 17 6 4.5 10 7.5 12.5 9.2 15 11 15 11 - -
A
SSW900A0024T5E2 24 7.5 5.5 15 11 15 11 20 15 20 15 - -
SSW900A0030T5E2 30 10 7.5 20 15 20 15 25 18.5 30 22 - -
SSW900B0045T5E2 45 15 11 30 22 30 22 40 30 40 30 - -
SSW900B0061T5E2 61 20 15 40 30 50 37 50 37 60 45 - -
B
SSW900B0085T5E2 85 30 22 60 45 60 45 75 55 75 55 - -
SSW900B0105T5E2 105 40 30 75 55 75 55 75 55 100 75 - -
SSW900C0130□E2 130 50 37 75 55 100 75 125 90 125 90 150 110
SSW900C0171□E2 C 171 60 45 125 90 125 90 150 110 175 132 220 165
SSW900C0200□E2 200 75 55 150 110 150 110 200 150 200 150 250 185
SSW900D0255□E♦ 255 100 75 175 132 200 150 250 185 250 185 340 250
SSW900D0312□E♦ 312 125 90 200 150 250 185 300 220 300 220 430 320
D
SSW900D0365□E♦ 365 150 110 250 185 300 225 350 260 400 300 470 350
SSW900D0412□E♦ 412 150 110 300 220 350 260 440 315 450 330 500 370
SSW900E0480□E♦ 480 200 150 350 260 400 300 500 370 500 370 600 450
SSW900E0604□E♦ E 604 250 185 450 330 500 370 600 450 650 485 750 550
SSW900E0670□E♦ 670 250 185 500 370 550 410 650 485 750 550 850 630
SSW900F0820□E♦ 820 350 260 550 410 700 525 800 600 850 630 1,000 750
F
SSW900F0950□E♦ 950 400 300 750 550 800 600 900 670 1,050 775 1,150 860
SSW900G1100□E♦ 1,100 450 330 800 600 900 670 1,100 810 1,200 900 1,300 1,000
G
SSW900G1400□E♦ 1,400 550 410 1,000 750 1,200 900 1,400 1,050 1,500 1,100 1,700 1,250

Notes: 1) Only for T5 versions.


2) Only for T6 versions.
Change □ by T5 for products with 220-575 V supply voltage or T6 for 380-690 V.
Change ♦ by 3 to select the control voltage of 110-130 V or by 4 to 220-240 V.
Models ≤412 A: AC-53b 3-25:335, ambient temperature of 55 °C.
Models ≥480 A: AC-53b 3-25:695, ambient temperature of 40 °C.
Models from 130 A to 200 A: with ventilation kit.
WEG motors Premium or Plus, IV poles.

Motor Inside Delta Connection (with 6 Cables)


Maximum applicable motor
Rated
Frame
SSW900 current 220/230 V1) 380/400 V 440/460 V 525 V2) 575 V2)
size
(A)
HP kW HP kW HP kW HP kW HP kW
SSW900C0130T5E2 225 75 55 150 110 175 132 200 150 250 185
SSW900C0171T5E2 C 296 125 90 200 150 200 150 250 185 300 220
SSW900C0200T5E2 346 150 110 250 185 300 220 300 220 350 260
SSW900D0255T5E♦ 441 175 132 300 220 350 260 400 300 450 330
SSW900D0312T5E♦ 540 200 150 350 260 450 330 500 370 550 410
D
SSW900D0365T5E♦ 631 250 185 450 330 500 370 600 450 650 485
SSW900D0412T5E♦ 713 250 185 500 370 600 450 700 525 800 600
SSW900E0480T5E♦ 831 350 260 600 450 700 525 800 600 900 670
SSW900E0604T5E♦ E 1,046 450 330 750 550 850 630 1,050 775 1,150 820
SSW900E0670T5E♦ 1,160 500 370 850 630 950 700 1,150 820 1,250 920
SSW900F0820T5E♦ 1,420 600 450 1,000 750 1,200 900 1,400 1,050 1,550 1,140
F
SSW900F0950T5E♦ 1,645 720 520 1,200 900 1,400 1,030 1,650 1,200 1,800 1,325
SSW900G1100T5E♦ 1,905 800 600 1,400 1,030 1,600 1,175 1,900 1,400 2,100 1,550
G
SSW900G1400T5E♦ 2,425 1,050 775 1,750 1,290 2,000 1,475 2,450 1,800 2,650 1,950

Notes: 1) Only for T5 versions.


2) Only for T6 versions.
Change ♦ by 3 to select the control voltage of 110-130 V or by 4 to 220-240 V.
Models ≤412 A: AC-53b 3-25:335, ambient temperature of 55 °C.
Models ≥480 A: AC-53b 3-25:695, ambient temperature of 40 °C.
Models from 130 A to 200 A: with ventilation kit.
WEG motors Premium or Plus, IV poles.

18 Soft-Starters
www.weg.net

Accessories
Accessory Description Image
Accessories for communication and control - Slots 1 and 2

SSW900-CAN-W CANopen and DeviceNet communication plug-in module

SSW900-CRS485-W Modbus-RTU communication plug-in module

SSW900-CDN-N DeviceNet - Anybus communication plug-in module

SSW900-CPDP-N Profibus-DP - Anybus communication plug-in module

SSW900-CETH-IP-N EtherNet/IP - Anybus communication plug-in module

SSW900-CMB-TCP-N Modbus-TCP - Anybus communication plug-in module

SSW900-CPN-IO-N PROFINET IO - Anybus communication plug-in module

SSW900-CETH-W1) Ethernet/IP communication plug-in module

SSW900-HMI-BLT Remote operating interface with Bluetooth communication

SSW900-PT100-W Temperature plug-in module for PT100 sensors - 6 channels

Accessories for mechanical installation


SSW0708900-KVT-2B Ventilation kit for frame B (currents from 45 to 105 A)
SSW0708900-KVT-3C Ventilation kit for frame C (currents from 130 to 200 A)

SSW0708900-IP20-3C IP20 kit for frame C (currents from 130 to 200 A)

SSW0708900-IP20-4D IP20 kit for frame D (currents from 255 to 412 A)

SSW0708900-PROT-3C Front cover kit for power terminals of frame C (currents from 130 to 200 A)
SSW0708900-PROT-4D Front cover kit for power terminals of frame D (currents from 255 to 412 A)
SSW900-PROT-E Front cover kit for power terminals of frame E (currents from 480 to 670 A)
Other accessories
SSW900-KMD-CB01 Frame kit for HMI + 1 m cable -
SSW900-KMD-CB02 Frame kit for HMI + 2 m cable -
SSW900-KMD-CB03 Frame kit for HMI + 3 m cable -
SSW900-KMD-CB05 Frame kit for HMI + 5 m cable -
SSW900-KMD-CB07 Frame kit for HMI + 7,5 m cable -
SSW900-KMD-CB10 Frame kit for HMI + 10 m cable -
SSW900-KMD-CB20 Frame kit for HMI + 20 m cable -
SSW900-KECA-10 Current acquisition kit for 10 A -
SSW900-KECA-17 Current acquisition kit for 17 A -
SSW900-KECA-24 Current acquisition kit for 24 A -
SSW900-KECA-30 Current acquisition kit for 30 A -
SSW900-KECA-45 Current acquisition kit for 45 A -
SSW900-KECA-61 Current acquisition kit for 61 A -
SSW900-KECA-85 Current acquisition kit for 85 A -
SSW900-KECA-105 Current acquisition kit for 105 A -
SSW900-KECA-130 Current acquisition kit for 130 A -
SSW900-KECA-171 Current acquisition kit for 171 A -
SSW900-KECA-200 Current acquisition kit for 200 A -
SSW900-KECA-255 Current acquisition kit for 255 A -
SSW900-KECA-312 Current acquisition kit for 312 A -
SSW900-KECA-365 Current acquisition kit for 365 A -
SSW900-KECA-412 Current acquisition kit for 412 A -
SSW900-6BAR-E Kit with six bars for frame E (currents from 480 to 670 A) -
SSW900-6BAR-F Kit with six busbars for frame F (currents of 820 and 950 A) -
SSW900-3BAR-G Kit with three busbars for frame G (currents of 1,100 and 1,400 A) -

Note: 1) Please check availability with your sales representative.

Soft-Starters 19
www.weg.net

Accessory Installation

1 2 3 4

Dimmensions
W
A P
B

H
D

Height (H) Width (W) Depth (P) (A) (B) (C) (D) Weight
Fastening Degree of
Frame size mm mm mm mm mm mm mm (kg)
screw protection
(in) (in) (in) (in) (in) (in) (in) (lb)

200 127 203 110 175 8.5 4.3 1.93


A M4 IP20
(7.87) (5) (7.99) (7.33) (6.88) (0.33) (0.16) (4.25)

208 144 260 132 148 6 3.4 4.02


B M4 IP20
(8.18) (5.66) (10.23) (5.19) (5.82) (0.23) (0.13) (8.86)

276 223 261 208 210 7.5 5 6.55


C M5 IP001)
(10.86) (8.77) (10.27) (8.18) (8.26) (0.29) (0.19) (14.44)

331 227 282 200 280 15 9 12.83


D M8 IP001)
(13.03) (8.93) (11.10) (7.87) (11.02) (0.59) (0.35) (28.28)

575 390 260 270 480 56 10 38


E M8 IP00
(22.63) (15.35) (10.23) (10.62) (18.89) (2.20) (0.40) (83.75)

760 464 316 320 625 72 10 75.40


F M8 IP00
(29.92) (18.27) (12.44) (12.60) (24.61) (2.83) (0.39) (166.23)

914 539 316 369 732 85 12 107.20


G M10 IP00
(35.98) (21.22) (12.44) (14.53) (28.82) (3.35) (0.47) (236.34)

Note: IP20 with optional kit.

20 Soft-Starters
www.weg.net

Comparison
Comparison SSW05 SSW07 SSW08 SSW900

Current range 3 - 85 A 17 - 412 A 17 - 412 A 10 - 1,400 A


220 - 460 V ac 220 - 575 V ac
(+10%, -15%) 220 - 575 V ac 220 - 575 V ac (+10%, -15%)
Power voltage
460 - 575 V ac (+10%, -15%) (+10%, -15%) 380 - 690 V ac
(+10%, -15%) (+10%, -15%)
Power supply
Frequency 50 / 60 Hz 50 / 60 Hz (±10%) 50 / 60 Hz (±10%) 50 / 60 Hz (±10%)
110 - 240 V ac 110 - 240 V ac 110 - 240 V ac
Control voltage 90 - 250 V ac
(+10%, -15%) (+10%, -15%) (+10%, -15%)
IP20 up to 85 A
IP20 up to 85 A IP20 up to 85 A
IP00 above 85 A
Protection rating IP00 IP00 above 85 A IP00 above 85 A
(optional IP20 kit for frames
(optional IP20 kit) (optional IP20 kit)
C and D)
Up to 412 A: 300% for 30s,
10 starts per hour (frames
300% for 30s, 300% for 20s,
A and D standard or B and
300% for 10s, 10 starts per hour (frames 10 starts per hour (frames
Overload duty Normal C with ventilation kit)
4 starts per hour A and D standard or frames A and D standard or frames
B and C with ventilation kit) B and C with ventilation kit)
Above 480 A: 300% for 30s,
5 starts per hour.
Controlled phases 2 phases 3 phases 2 phases 3 phases

Built-in bypass Yes Yes Yes Yes

Inside delta connection No No No Yes, above 105 A

Initial voltage 30 - 80% 30 - 90% 30 - 90% 25 - 90%

Starting time Yes, 1 to 20s Yes, 1 to 999s Yes, 1 to 999s Yes, 1 to 999s

Stoppage time Yes, 1 to 20s Yes, 1 to 240s Yes, 1 to 240s Yes, 1 to 999s
Yes (requires two external
Reverse braking No No No
contactors)
Braking methods DC braking No No No Yes

Optimal braking No No No Yes

Voltage ramp Yes Yes Yes Yes

Current ramp No No No Yes

Current limit No Yes Yes Yes


Control types
Kick-start No Yes Yes Yes

Torque control No No No Yes

Pump control No No No Yes


2 (110 - 230 V ac), one of 3 (110 - 240 V ac) 3 (110 - 240 V ac)
Digital 5 (24 V dc) programmable
Inputs those is programmable programmable programmable
PTC input No Yes (optional kit) Yes (optional kit) Yes (standard)
2 relay outputs with NO
1 relay output with NO 2 relay outputs with NO 2 relay outputs with NO
contact and 1 with NO/NC
Relay contact, 250 V ac, 1 A, contact, 240 V ac, 1 A, contact, 240 V ac, 1 A,
contact, 240 V ac,
programmable programmable programmable
Outputs 1 A, programmable
1 programmable
Analog No No No (1 x 0-10 V dc
or 1 x 4-20 mA)
USB3), CAN2), Ethernet2) ,
Interfaces RS232C1) CAN2), RS2322) or RS4852) CAN2), RS2322) or RS4852)
RS4852) or Bluetooth2)
DeviceNet, Profibus DP,
Profibus DP-V1,
Modbus-RTU and Modbus-RTU and
Fieldbus Protocols Modbus-RTU EtherNet/IP, Modbus-TCP,
DeviceNet DeviceNet
PROFINET IO, CANopen and
Modbus-RTU
Built-in detachable
local HMI with graphic LCD
Optional, remote Optional, local or remote Optional, local or remote display.
HMI
LED display LED display LED display HMI with Bluetooth
connectivity available as an
accessory item.

Notes: 1) Built-in interface for conection with external HMI or with RS485 network (using MIW02 accessory).
2) Available with an accessory.
3) Available
 as standard.

Soft-Starters 21
www.weg.net

Comparison
Comparison SSW05 SSW07 SSW08 SSW900
Phase loss in the power Phase loss in the power Phase loss in the power
Phase loss
supply and in the motor supply and in the motor supply and in the motor
Locked rotor Locked rotor Locked rotor Locked rotor

Motor overload Motor overload Motor overload Motor overload


Over and undercurrent in the Over and undercurrent in the Over and undercurrent in the
Overcurrent
motor motor motor
Overtemperature in the motor Overtemperature in the motor Overtemperature in the motor
- and in the and in the and in the
soft-starter soft-starter soft-starter
Fault in the thyristor Fault in the thyristor
- Fault in the thyristor
(overheating) (overheating)
Phase sequence Phase sequence Phase sequence Phase sequence
Undervoltage in the Undervoltage in the Undervoltage in the
-
electronics electronics electronics
- Fault in the bypass Fault in the bypass Fault in the bypass
Overcurrent before the Overcurrent before the Under and overcurrent before
-
bypass closes bypass closes the bypass closes
Protections
Supply line frequency out of Supply line frequency out of Supply line frequency out of
-
the range the range the range
Voltage and current Voltage and current Voltage and current
-
imbalance imbalance imbalance
Internal fault Internal fault Internal fault Internal fault
Warning for alarms before
- - -
going into fault
Under and overvoltage in the
- - -
power
- - - Ground fault

- - - Motor not connected

- - - Motor wrong connection

- - - Under and overtorque

- - - Over and underpower


Starting time
- - -
exceeded
0 - 55 °C without derating
(frames A to D)
Temperature 0 - 55 °C without derating 0 - 55 °C without derating 0 - 55 °C without derating 0 - 40 °C without derating
(frames E, F
and G)
0...90% 5...90% 5...90% 5...90%
Ambient conditions Humidity
non-condensing non-condensing non-condensing non-condensing
Up to 1,000 m without Up to 1,000 m without Up to 1,000 m without Up to 1,000 m without
derating derating derating derating
Altitude 1,000 - 4,000 m with 1% 1,000 - 4,000 m with 1% 1,000 - 4,000 m with 1% 1,000 - 4,000 m with 1%
derating every derating every derating every derating every
100 m 100 m 100 m 100 m
Communication with PC Yes Yes Yes Yes
Other resources
SoftPLC function No No No Yes

22 Soft-Starters
www.weg.net

Global presence is essential,


as much as understanding your needs.

Global Presence
With more than 30,000 employees worldwide, WEG is one of the largest electric motors, electronic equipments and systems
manufacturers. We are constantly expanding our portfolio of products and services with expertise and market knowledge. We
create integrated and customized solutions ranging from innovative products to complete after-sales service.

WEG’s know-how guarantees the line of Soft-Starters is the right choice for your application and business, assuring safety,
efficiency and reliability.

Availability is to have a global support network

Partnership is to create solutions that suit your needs

Competitive edge is to unite technology and innovation

Know More
High performance and reliable
products to improve your
production process.

Excellence is to provide a whole solution in


industrial automation that improves
our customers productivity.

Visit: www.weg.net youtube.com/wegvideos

Soft-Starters 23
For WEG’s worldwide
operations visit our website

www.weg.net

+55 47 3276.4000

[email protected]

Jaraguá do Sul - SC - Brazil


AUTOMATION

Cod: 50019077 | Rev: 14 | Date (m/a): 05/2021.


The values shown are subject to change without prior notice.
The information contained is reference values.