CREATING SAFER AND SMARTER ELECTRICITY

T E L E C O M TO W E R
S I TE S O LU T I O N
CREATING SAFER AND SMARTER ELECTRICITY

Cataloge 2020

Utility Tower Grid Power

Grid Connection

Motion Sensor
Surge Arrestor Cabinet
CCTV

Solar Panel

Smart
Shanghai Matis Electric Co.Ltd Lock
Warning
Light
Telecom Tower AC Electric DC Electric
Tel:021-6050 3668 Distribution Cabinet Distribution Cabinet Battery Tracker Air Conditioner
Cell:18291401332
Email: [email protected] AC Genset
Web:www.matismart.com
Add: Room 318-320, No.83,West Huanghu Road, Pudong, Shanghai, China 201306 Door Alarm
DC Genset
IOS Andriod

www.matismart.com
CREATING SAFER AND SMARTER ELECTRICITY
Company Brief Introduction

FOCUS ON SMART IOT ELECTRICAL SOLUTIONS


Established in 2014, Shanghai Matis Electric Co., Ltd. (MATIS) focuses on
innovated AI+IoT electrical solutions. Based on deep understanding of low
voltage electric , we integrate the cutting-edge technology: AI, IoT, Big Data,
and Cloud computing etc, and develop innovated electrical solutions. This
solution makes the electricity safer and smarter and mainly used in the follow-
ing applications: Telecom Tower, smart building, industrial automation (Indus-
try 4.0), smart utility distribution system, smart electrical fire protection, public
trasportation facility, municipal construction ( traffic light,street light ,CCTV),
ect.

OFFERING THE WHOLE SOLUTION WITH BOTH


HARDWARES AND SOFTWARES
MATIS AIoT electrical product includes: 1)AIoT metering MCCB; 2)AIoT energy
meter with protection; 3)AIoT metering MCB; 4)Smart Recloser; Supporting
these AIoT electrical hardware, we also developed various of platforms of
Smart energy cloud, Electricity safety supervision, Energy efficiency manage-
ment platform, and corresponding APPs for each products.

Matis AIoT electrical solution integrate multi-functions in one: short circuit,


overload, earth-leakage, over/under-voltage, phase loss, arc fault, phase imbal-
ance, temperature, real-time monitoring of electrical parameters, power safety
monitoring, energy management, remote control , scheduled control, electrical
fault analysis, pre-larm & alarm, billing, event report, software etc.

MATIS electrical solutions include both the connected hardware and web
software platforms & APPs. They are connected by the wired and wireless
communications. The wired communication includes RS485, Ethernet RJ45 and
wireless communication includes WiFi, GRPS 2G/3G/4G, NB-IoT, LoRa etc.
Matis Smart Power Solution gives you a complete solution approach to:
. Deliver more reliable and efficient power
. Protect your assets, processes and people
Company Culture . Provided tailored, future-ready solutions for the new digital economy
. Offer smart safety supervision and power managment
. Creating new business opportunitis for your company.

MISSION
Creating safer and smarter electricity for human being

Contents
VISION
Committed to AIOT electricity solution expert

1.Concept Introduction 01

CORE VALUE
2. Functions 02
Sincere, Innovation, Teamwork, Concentration

3.Telecom Industry Introduction 03

4.Telecom Site Introduction 06

5.Telecom Site Solution 07


MATIS Pays High Attention To Product Quality
And Technology Innovation 6.Functions and Features of Site Solution 09

By 2020, MATIS owns the followings patents: 7.Site Solution Value 11

8.Site Solution Benefits 13

9.Differentiated Power Backup Solution of 5G Site 15

10.Product Introduction 21

8 6 25 28 5 11.Case Introduction 23
Copyrights Invention Patents Utility Model Patents Design Patents Software Copyrights
Concept Introduction Functions

From the connected device to edge control, device management software, APP and application solutions on
following domains : Telecom, Grid, Buidling, Plant and industry, Matis offers the complete smart IoT electrical
solution and delivers enhanced value around safety, reliability, operational efficiency, sustainability , and connec-
tivity to our customers.

Metering & Measurement Electrical Protection


Smart Hardware Device Data Acquisition Device The device integrates CT sensor to meter The device integrates full electrical protec-
and measure each load precisely, then tion in one and realize pre-alarm, alarm of
All the electrical device connected by RS485 and Modbus RTU Data acquisition, edge control and electrical parameter computing.
provide the accurate data for in device electrical fault for electrical safety super-
protocol: Remote Control Device with Breaker, Multi-Channel Realize protocol conversion and Network interconnection. management software platform & APP and vision through software and app. And the
Meter, Smart Breaker, Smart Recloser, Surge Protector. local display. electrical parameter can be setup in
Interface port: GSM/GPRS, Ethernet Lan(RJ45), WiFi, LoRa, RS485
· Real-Time Monitoring through software and app
Communication Protocol: Modbus RTU,MQTT, UDP · Metering · Full Electrical Protection
· Billing and Online Payment · Pre-alarm & Alarm
· Electrical Parameter Setting

ro duc t s Ed
ge
e dP
ct

Co

Smart Control
ne

nt
Con

rol

The device integrates remote control mech-


anism to realize the remote control function
IoT Electrical of device or the associated device through
Solution
A p plicat

APP or software platform.


· Remote ON/OFF
· Remote Lock/Unlock
nt
ion

· Timer Control/Scheduled Control


me

· Other Scene Control


So
lu

ge

on
na
ti

& a
Se
rvi eM
ce
Devic

Efficient management Smart Interconnection


Application Solution Device Management Software Based on the features of online & offline connection All the devices integrate interface port RS485
between device and software, Human-Device interac- and communication protocol of Modbus RTU. The
Customize software, solve practical problems, offer the whole Mornitor all the electrical parameter in real-time, make edge tion, our Smart power solution can improve the smart gateway has both downlink communication
solutions and service according to the customers's demand from operation & maintainence of electrical equipment and to connect all the devices by RS485 and uplink
control, and realize remote device operation and maintaineance,
lower its cost as well. Base on data acquisition and communication to connect software platform
different industries through data acquisition of device manage- electrical safety supervision and power consumption manage- edge control, the solution make the electrial safety through wireless communcaition and MQTT
ment platform and data analysis. ment of all the sites in APP or Web software. supervision and power mangement
protocol.
· Energy Efficiency Management
· Wired communication: RS485, Ethernet
· Operation & Maintainence Management
· Wireless communiction: GPRS 2G/3G/4G, NB-IoT,
· Event report
WiFi, LoRa
· Communication Protocol: Modbus RTU,MQTT

- 01 - www.matismart.com www.matismart.com - 02 -
Telecom Industry Introduction

Since 2019, 5G business emerge and expand sharply. More than 6


millions of 5G telecom tower sites will be built in China in the next 7
6 MILLIONS
years and it initiates the new era of internet of Everything and 5G
network of high speed and low delay.
5GTOWER
SITES

The energy consumption of 5G twice more than of the one of 2G,3G,


and4G equipment and the telecom operators have big pressures on the
electricity cost. Reducing electricity cost become the most important
task. In order to realize this task, the telecom operator have the
following requirement:
1. Power-up or power-down of new and indoor 5G tower sites at the
scheduled time.
2. Making specific scenario to save energy based on the business
coverage and business difference on time of telecom tower sites.
3. Power-up or power-down of the whole tower site or different tower
cells on scheduled time and

Therefore, it is very important to realize smart management on the


telecom tower site. In order to push the 5G business development,
Matis is offering the smart electric distribution solutions of telecom
tower site for Tower company or different telecom operators such as
differentiated power backup solution , energy consumption manage-
ment solution and on-site power distribution unit resource.

- 03 - www.matismart.com www.matismart.com - 04 -
Telecom Tower Site Introduction Telecom Tower Site Introduction

Telecom Tower Site Introduction Challenge of 5G Tower Site Construction


Telecom tower site is the most important infrastructure in the communication industry. A form of
radio station refers to a radio receiving and transmitting station that transmits information with
mobile phone terminals through mobile communication switching center in a certain radio coverage The power consumption of 5G equipment is 2-3 times than the one of 2G,3G,4G.The traditional tower site
only make the measurement on the different operators, so it can't accurately measure different equip-
area. The telecom tower site is used to ensure that the mobile phone can keep the signal at any time
ment(2G,3G,3G,4G,5), so it can't make the energy efficiency management of the equipment. After the 5G
and anywhere in the process of mobile, which can guarantee the demand of calling and sending and business is undertaken, the original 2G, 3G and 4G backup power service of tower sharing station cannot be
receiving information. At present, there are many 2G, 3G and 4G telecom tower sites everywhere and guaranteed, resulting in the shortage of backup power capacity of the base station,and shorten the life the
old tower site. Therefore,it is vital important to make energy management on 5G equipment and the whole
5G tower sites are just under construction.
tower site.

Telecom Tower Site Classification For share tower sites,with the increasing
demand for differentiated power generation
Some operators will delay the electricity bill
There are various types of tower sites, which are basically divided into macro site, radio remote services of various operators,there is a
payment, the telecom shared tower company
dispute of power generation among various
site, micro site, indoor sub-site.We provide different smart electrical distribution solutions for can not stop the tower service and have no
telecom operators. Some operators would
way to deal with the delay of electricity bill
different types of telecom tower sites, and provide mart distribution solutions for Data centers and like to choose customized power generation
payment.
communication rooms in the communication industry and other special scenary requirement.

Some telecom operators will add the loads


om
e n Ro privately without permission the telecom
e Sit atio tower company, which result in billing
For 5G tower site, the capacity of small oil

e m ot nic ite
engine is insufficient, and it is difficult to
Sit Re mu S disputes among different operators, so it
cro dio Co
m cro transport large oil engine as well.
Mi must be solved smart management system
Ma Ra of telecom tower site.
te
b-Si
r Su
oo
Ind
The traditional tower site has no monitoring
of electrical safety, real-time monitoring of When lightning occurs, many telecom
electrical equipment, and no early warning electrical equipment will trip and need long
time and many labour cost to make mainte-
s ite and alarm for electrical fault. Therefore, the
5G
io n operation and maintenance is very high, but nance, which will cause communication

at the efficiency is low. accidents.


c
s s i fi
C la
宏基站
S ite
e r If there is no local security lock in the
w device, there will be security risks in
To operation and maintenance.

o m
lec
Te

- 05 - www.matismart.com www.matismart.com - 06 -
Telecom Site Introduction Telecom Site Solution
Electrical Distribution System Introduction of Telecom Tower
General Introduction
With the development of 5G business, the power consumption of tower site is increasing sharply. It is very important to realize smart
electrical supervision and power energy management of telecom tower site. In order to support the development of 5G business,our
telecom tower site solution can meet the demand of differentiated power backup and energy consumption management of different
The power system of telecom tower site consists of AC electrical distribution, Switching Power operators and different equipment of existing base stations, and the on-site resource management requirements of power unit.

supply, Battery and it includes AC power supply and DC power supply system. AC power supply
consists of Grid Power, Generator Power, Arrester and AC electrical distribution Cabinet system. DC Smart Electric Distribution System Solution includes
1.Multi-channel meter device can make accurate metering and precise management on the each load of AC electrical system and realize
power supply consists of power set (including AC power unit, Monitor, rectifier and DC power Unit)
auto-transfer between grid power and generation power;
and Battery. 2.Remote controller with breaker can realize the smart and remote control of telecom equipment according to the power backup require-
ment of different telecom equipment and control requirement;
3.The DC metering module can measure the energy consumption of each equipment of different operators and realize energy management.
4. Our device can be connected to FSU of customers' and all the data can be transmitted to the software platform of customer . We also
offer the development of the customized software platform and transfer all the data to customized software platform through the data
acquisition

AC Power Supply DC Power Suply

Utility Tower Grid Power

高频开关电源

DC CommunicationDevice
Grid Connection
SPD
DC Power Unit
Rectifier
Motion Sensor
AC DC Surge Arrestor Cabinet

Power Rectifier Controller CCTV


Grid
Supply
AC Elactrical Cabinet

Rectifier Battery
Solar Panel

Proteciton Smart
Lock
Warning
Oil Generator Monitor Telecom Tower AC Electric
Distribution Cabinet
DC Electric
Distribution Cabinet Battery Tracker
Air Conditioner
Light

AC Genset
AC
Battery Battery DC Genset
Door Alarm

Light
Advantages
High Safety,Reliability and Stability Cloud Software Platform
Reliable and fast transfering management system of grid power and We develop the special software platform to realize the smart
oil generation power;5G independent power generation manage- electrical distribution management, power management and 5G
ment;Remote and local lock and unlock function of device to assure differentiated power backup management for telecom operator
the safety of operation and maintenance;On-site maintenance, or telecom tower company. THe software system can improve the
manual control mode,remote control mode all assure safe,stable and safety and reliability of the operation and maintenance of
reliable operation of telecom tower site. telecom tower site and , reduce the operation cost by 30%. The
distribution resource system planning, operation and mainte-

High Proformance nance realize the system process management, rapid fault
response, and improve operation and maintenance management
The solution realize independent control and metering on each of telecom tower site
load,which can make smart energy efficiency management and
smart control management on telecom tower site. Modularization
The smart power unit can be customized according to requirment
of different telecom site.

- 07 - www.matismart.com www.matismart.com - 08 -
Telecom Site Solution Telecom Site Solution

Macro site Solution 1: Macro site Solution 3:


LLVD & BLVD Multi communication newtwork / multi operator
Load type: comprehensive load 2G / 3G / 4G mixed type Load type: comprehensive & operator 1 / operator 2 / operator 3
Number of users: 2-3 Number of networks / number of users: 2-3
~/ - ~/ -
Power loads: ≥ 200A MT61GP 3G Equipment Power load: ≥ 200A MT61GP operator 1
4P C50 *12 4G Equipment 4P C50 1 sets of network
No.of LLVD sub-load loads :9 5G Equipment 4 groups of distribution circuits: 3 groups of network / operator *3
LLVD1 Reserve Group1
No.of BLVD sub-load loads : 6 ~/ - load + 1 group of transmission equipment ~/ -
48V/50A 48V/50A
When grid power is off, the battery pack begins to discharge and N mode configuration
According to voltage, time or active command, smart PDU can N mode configuration *4
continues to power supply the main equipments of the station Management Transmission equipment flexibly control, lock, and unlock different network devices( Management
Transmission
platform Monitor equipment platform *3
(BTS / NodeB / eNodeB), transmission equipment, etc., to make *6 2G,3G,4G,5G)/the loads of different telecom operators. equipment
Reserve
sure the station is powered under normal operation. LLVD2 When grid power is off, the battery pack begins to discharge and Group2
When the battery voltage drops set voltage value of LLVD, the Cloud continue to supply the main equipments and transmission Cloud
server server
control module will disconnect BTS / NodeB / eNodeB, data equipment, etc., to make sure the station is powered under
Battery Battery
equipments and other power supply, the main equipments of the group normal operation. group
station are out of service, only power supply of transmission MT88C MT53RSD48 Battery When the battery voltage drops to a set value of control module, MT88C MT53RSD48 Battery
Communication +MM50HD 1P Tracker Communication +MM50HD 1P Tracker
equipment is guaranteed. module which is divided into essential and multiple classification module
Surge Surge
Smart power distribution unit sets LLVD and BLVD according to protection electrical load. Sequentially to cut power supply of data protection
the voltage and time. Equipment cabinet equipments, the master station service, and ensure power supply Equipment cabinet
Switch power(DC 48V) (DC 48V) Switch power(DC 48V) (DC 48V)
Control module: MT53RS mechanical outer shaft control module, only to transmission equipments.
equipped with high breaking circuit breaker, 8000 times electrical Smart power distribution unit can set backup power according to
life. the voltage and time.
Control module: MT53RS mechanical outer shaft control module,
equipped with high breaking circuit breaker, 8000 times electrical
life.

Macro site Solution 2: Macro site Solution 4:


LLVD and BLVD (with metering sub-load) Multi communication newtwork / multi operator (with metering sub-load)
Load type: comprehensive load 2G / 3G / 4G mixed type Load type: comprehensive Load type:2G/3G/4G
*1 *3
~/ - ~/ -
Number of users: 2-3 Load type: 2G / 3G / 4G & operator 1 / operator 2 / operator 3
MT61GP 3G Equipment MT61GP operator 1
4P C50 MT58SD *3组
4G Equipment Power load: ≥ 200A 4P C50
*3
1 sets of network Number of networks / number of users: 2-3
Sub-load meter 5G Equipment
LLVD1 Reserve NNo.of LLVD sub-load loads :9 Group1 Power load: ≥ 200A
~/ - ~/ -
*1 *3 4 groups of distribution circuits: 3 groups of network / operator
48V/50A
No.of BLVD sub-load loads : 6 48V/50A
N mode configuration *1 *2 N mode configuration MT58SD *4
Sub-load meter load + 1 group of transmission equipment
Management Transmission equipment
When grid power is off, the battery pack begins to discharge and Management
Transmission
platform MT58SD Monitor equipment continues to power supply the main equipments of the station platform *3
*3组 equipment
Sub-load meter Reserve
(BTS / NodeB / eNodeB), transmission equipment, etc., to make According to voltage, time or active command, smart PDU can
LLVD2 Group4
sure the station is powered under normal operation. flexibly control, lock, and unlock different network devices(
Cloud *1 *2 Cloud
server
When the battery voltage drops to set voltage value of LLVD, the server 2G,3G,4G,5G) / the loads of different telecom operators.
Battery Battery
group control module will disconnect BTS / NodeB / eNodeB, data group
When grid power is off, the battery pack begins to discharge and
MT88C MT53RSD48 Battery Tracker equipments and other power supply, the main equipments of the MT88C MT53RSD48 Battery
continue to supply the main equipments and transmission
Communication +MM50HD 1P
station are out of service, only power supply of transmission Communication +MM50HD 1P Tracker equipment, etc., to make sure the station is powered under normal
module module
Surge
equipment is guaranteed. Surge operation.
protection protection
Smart power distribution unit sets LLVD and BLVD according to When the battery voltage drops to a set value of control module,
Equipment cabinet Equipment cabinet
Switch power(DC 48V) (DC 48V) the voltage and time. Switch power(DC 48V) (DC 48V) which is divided intoessential and unessential with multiple
Control module: MT53RS mechanical outer shaft control module, classification electrical load. Sequentially to cut power supply of
equipped with high breaking circuit breaker, 8000 times electrical data equipments, the master station service, and ensure power
life. supply only to transmission equipments.
Metering module: MT58 metering module, with voltage/current Smart power distribution unit can set backup power according to
accuracy of 0.5%, power and energy accuracy of 1%, providing the voltage and time.
precise apportionment ratios for shared base stations. Control module: MT53RS mechanical outer shaft control module,
equipped with high breaking circuit breaker, 8000 times electrical
life.
Metering module: MT58 metering module, with voltage/current
accuracy of 0.5%, power and energy accuracy of 1%, providing
precise apportionment ratios for shared base stations.

- 09 - www.matismart.com www.matismart.com - 10 -
Telecom Site Solution Telecom Site Solution
~/ -

Macro site Solution 5: MT61GP


4P C50 *5
5G 3*AAU Equipment Macro site Solution 7: Multi communication
5G tower site Solution
MT53RSD48

newtwork (5G) / operators


5G 2*BBU Equipment
+MM50HD 1P
Operator1

Configuration1
Management
platform
Load type: 5G 3 * AAU + 2 * BBU & 5G DCDU 5G 3*AAU Equipment Load type: 2G / 3G / 4G / 5G & operator 1 / operator 2 / operator 3 ~/ -
~/ - *5 3G Equipment
5G 2*BBU Equipment
Number of networks / operators: 2 Number of networks / number of operators: 2-3 MT61GP 4G Equipment
Operator2 4P C50 MT53RSD48
Power load: ≥ 200A Cloud MT58SD
Power load: ≥ 200A +MM50HD 1P 5G Equipment

server sub-load meter ~/ - Reserve


2 sets of distribution circuits: 2 sets of 5G network / 2 sets of BBU Battery 4 groups of distribution circuits: 3 sets of network / operator
group
N mode configuration
load + 1 set of transmission equipment
MT88C Management Transmission
According to voltage, time, or active command, smart PDU can flexibly Communication platform *12 equipment
module
control different operators / different load, to open and close, lock and Surge "According to voltage, time, or active command, smart PDU can flexibly Monitor equipment
protection
unlock load. Equipment cabinet control different operators / different load, to open and close, lock and Reserve
Cloud MT53RSD48
Switch power(DC 48V) (DC 48V) unlock load.
The smart PDU can set backup power according to its voltage and time. server Power on/off
Battery
Control module: MT53RS mechanical external shaft control module, The smart PDU can set backup power according to its voltage and group

equipped with high breaking circuit breaker, 8000 times electrical life. ~/ - time." MT88C
Control module: MT53RS mechanical external shaft control module, Communication
MT61GP module
4P C50 *2 5G 2*DCDU Equipment Surge
MT53RSD48
+MM50HD 1P
equipped with high breaking circuit breaker, 8000 times electrical life. protection
Operator1
Equipment cabinet
Switch power(DC 48V) (DC 48V)

Management

Configuration2
platform
~/ - *2 5G 2*DCDU Equipment

Operator2

Cloud MT58SD
server sub-load meter

Battery
group
MT88C
Communication
module
Surge
protection
Equipment cabinet
Switch power(DC 48V) (DC 48V)
~/ -
3G Equipment
Macro site Solution 8:
MT61GP
4P C50
MT58SD
sub-load meter MT53RSD48
4G Equipment
5G Equipment
Multi communication newtwork (5G) / multi
operator (with metering sub-load)
+MM50HD 1P

~/ -
Macro site Solution 6: 5G telecom site ~/ -
Reserve

solution (with metering sub-load)


5G 3*AAU Equipment
MT61GP *5 N mode configuration
4P CS63 MT58SD 5G 2*BBU Equipment Management Transmission
MT53RSD48
sub-load meter platform
+MM50HD 1P Operator1 MT58SD *10 equipment Load type: 2G / 3G / 4G / 5G & operator 1 / operator 2 / operator 3
Monitor equipment
Number of networks / number of operators: 2-3
Reserve
Configuration1

Management
Number of networks / operators: 2 power load: ≥ 200A Cloud
platform 5G 3*AAU Equipment server
MT58MD MT58SD MT53RSD48 Power load: ≥ 200A
2 sets of distribution circuits: 2 sets of 5g network / 2 sets of BBU Meter module sub-load meter Power on/off Battery
~/ - MT58SD *5 5G 2*BBU Equipment group 4 groups of distribution circuits: 3 sets of network / operator
Operator2 According to voltage, time, or active command, smart PDU can flexibly MT88C MT99S load + 1 set of transmission equipment
Communication Local management module
Cloud
server
MT58SD MT53RSD48 control different operators / different load, to open and close, lock and module Surge
sub-load meter Power on/off
Battery unlock load.
protection According to voltage, time or active command, smart PDU can flexibly
Equipment cabinet
group
The smart PDU can set backup power according to its voltage and time. Switch power(DC 48V) (DC 48V) control, lock, and unlock different network elements / different
MT88C
Communication Surge Control module: MT53RS mechanical external shaft control module, operations.
module protection
Equipment cabinet equipped with high breaking circuit breaker, 8000 times electrical life. When grid power is off, the battery pack begins to discharge and
Switch power(DC 48V) (DC 48V)
Metering module: MT58 metering module, with voltage/current continue to supply the main equipments of 2G /3G /4G to make sure
accuracy of 0.5%, power and energy accuracy of 1%, providing precise the station is powered under normal operation.
~/ -
apportionment ratios for shared base stations. When the battery voltage drops to a set value of control module, which
MT61GP MT58SD *5
4P CS63 sub-load meter is divided into essential or secondary importance with multiple
MT53RSD48 5G 2*DCDU Equipment
+MM50HD 1P classification electrical load. Sequentially to cut power supply of data
Operatorr1
equipments, the master station service, and ensure power supply only
Management to transmission equipments.
platform Smart power distribution unit can set backup power according to the
Configuration2

~/ - MT58SD *5 5G 2*DCDU Equipment voltage and time.


Operator2 Control module: MT53RS mechanical outer shaft control module,
Cloud equipped with high breaking circuit breaker, 8000 times electrical life.
server MT58SD MT53RSD48
sub-load meter Power on/off
When the 5G network element is idle, it can be shut down regularly or
Battery
group set according to various scenarios.
MT88C
Communication
MT58M
Meter moduleD
Metering module: MT58 metering module, with voltage/current
Surge
module
protection
Equipment cabinet
accuracy of 0.5%, power and energy accuracy of 1%, providing precise
Switch power(DC 48V) (DC 48V) apportionment ratios for shared base stations.

- 11 - www.matismart.com www.matismart.com - 12 -
Telecom Site Solution Telecom Site Solution

AC electrica distribution solution Radio remote site solution


MT58SA Transmission
AC main input: grid power/ generator Load type: 2G / 3G / 4G / 5G & operator 1 / operator 2 / operator 3 sub-load meter MT53RS equipment
+MM50HD 1P
MT53RA+3P C25
Capacity: 63A / 80A Number of networks / number of operators: 2-3 Monitor equipment
Air conditioner AC sub-load output: switch power/ air conditioner / lighting / Power load: ≥ 200A MT58MA Reserve
MT58SA/OA
MT53RA+3P C25
Backup
socket / others 4 groups of distribution circuits: 3 sets of network / operator AC meter

New energy IOT Air meter


MT58SA/OA MT53RA+1P C16 load + 1 set of transmission equipment ~/ -
Mete Control Backup AC power distribution unit: Remote station has both DC and AC loads, and different types of
MT58SA/OA MT61GP 4P C63 MT58SD
MT53RA+1P C16
MT61GP 4P C80
Backup
Input grid power or generator power, will distribute the AC power metering and control equipments are used according to the Sub-load meter MT53RSD48
+MM50HD 1P
Mobile
MT58SA/OA MT53RA+1P C16 to the switching power supply rectifier module. actual site to meet the needs of remote monitoring. Transmission
Diesel generator Backup ~/ -
MT58SA/OA It contains a surge protector as the secondary lightning protec- equipment
MT53RA+1P C10
Monitor equipment
Grid power lighting tion of the station power system. N mode configuration
MT58SA/OA Control module: Management Reserve
MM50H 3P C80 MT53RA+1P C10
AC power supply system operation mode: platform
Backup MT53RS mechanical external shaft control module, equipped with MT58SD *10
MT58SA/OA MT53RA+1P C10 1. When the grid power is normal, the grid power supply;
MTSP-4P high breaking circuit breaker, 8000 times electrical life.
Backup 2. After the grid power outage, when the mobile generator does
MT58SA/OA Metering module: MT58 metering module, voltage / current Cloud
MT53RA+3P C50
not arrive at the station, the communication equipment in the server
MT58MD MT58SD MT53RSD48

Surge protection
Backup accuracy 0.5%, power and energy accuracy 1% to provide accurate DC equipmentsub-load meter Power on/off Battery
MT58SA/OA
MT53RA+3P C63 station is powered by the battery discharge; group
allocation ratio for shared base stations.
switch power 3. The mobile diesel generator arrives at the station and waits for MT88C
MT58SA/OA AC meter Communication
AC distribution box#2(AC380V ) Meter Control the generator to start. The generator power the station;
Integrated distribution box module Surge
4. The station is powered by grid, when it recovers. protection
DC equipment
Equipment cabinet
Integrated distribution box (DC 48V) (DC 48V)

Functions and features ~/ -


Indoor sub-site solution
Transmission
MT61GP 4P C63
MT58SD equipment
sub-load meter MT53RSD48
Monitor
LOAD TYPE: OMB HARDWARE
+MM50HD 1P
1. When grid power outage, PDU provides AI output to DC backup ~/ - ~/ - equipment
3G Equipment
power system; MT61GP MT58SD 4G Equipment Reserve Select different power configurations (AC / DC) depending on the
2. When diesel generator starts, PDU provides AI output to DC N mode configuration
4P C50 sub-load meter MT53RSD48
+MM50HD 1P 5G Equipment Management type of field device
backup power system ; ~/ - Reserve platform According to the load equipment of different power supply types
3. Realize the statistics of the diesel generator power record, Cloud of different operators, the electric energy situation of equipment
server
time, and kWH; MT58MD Transmission load can be counted and the energy consumption analysis can be
Meter module
4 .4 sets of tariff settings inside the meter circuit breaker, which equipment
MT58SD *10
MT58MD
DC meter
provided.
Monitor equipment MT88C
can be used to cut peaks and fill valleys and cooperate with the Communication
According to the voltage, time or active command, it can flexibly
Cloud Reserve
battery backup system to achieve different power supply server
module control the power on and off control, lock and unlock control of
MT58MD MT58SD MT53RSD48
strategies and reduce base station electricity costs. Meter module sub-load meter Power on/off Battery each load of different operators / different network elements.
group Configuration1
5. Meter circuit breakers will trip when voltage loss and ensure When the neT is idle, it can be turned off at a fixed time or set in
the safe operation of grid power and diesel generators; MT88C
MT99S a scenario.
Local management module
6. Internal tripping and safety lock to ensure safe operation on Communication Surge The distribution unit sets the standby power according to the
module protection
site and prevent misoperation; Equipment cabinet MT61GP 4P C63 MT58SD Transmission voltage and time.
sub-load meter
7. Analysis of data statistics and electricity theft events; Switch power(DC 48V) (DC 48V) MT53RSD48 equipment
+MM50HD 1P
Monitor
Control module:
Management equipment
Smart circuit breaker module: platform Reserve
MT53RS mechanical external shaft control module, equipped with
MT61GP has a voltage/current accuracy of 0.5% and a power and high breaking circuit breaker, 8000 times electrical life.
energy accuracy of 1%, providing a precise sharing ratio for Metering module:
Cloud
shared base stations . server MT58MA MT58 metering module, voltage / current accuracy 0.5%, power
AC meter
MT88C and energy accuracy 1% to provide accurate allocation ratio for
Communication shared base stations.
module Integrated distribution box AC220V Equipment AC220V
AC equipment
Configuration2 Configuration

- 13 - www.matismart.com www.matismart.com - 14 -
Functions and Features of Site Solution Functions and Features of Site Solution

Functions of site solution Features of site solution


Instantaneous fault automatic reset
Remote management of equipments
The main line and sub lines have auto reclosing function, that can be automatically reset when instantaneous fault trip caused by lightning;
Support remote power on/off, lock and unlock of independent users and independent
Reclosing program can be set on deman.
loads;
support to set operators business models through customized software or FSU system;
help customers to efficiently manage equipment, greatly save electricity bill and cut
labor cost; Pre-warning and alarm of faults
It supports pre-warning and alarm of over-voltage, under-voltage, over-current, or even over-temperature, phase loss, phase imbalance,
etc., to ensure safe electricity;
Auto transfer between grid power and diesel generator The parameters of pre-warning and alarm can be set either locally or remotely by platform.

Support the control and management of grid power and diesel generators ;
Support the metering of grid power and diesel generator.
Smart interconnection
It supports the access of analog signal mains and diesel generators to provide supportive signals for differentiated backup power system;
Local maintenance mode
The system reserves RS485 terminals, which can be connected to FSU, or wireless gateway communication module;
Local maintenance mode, the equipment is automatically locked to ensure
Standard B terminal protocol.
maintenance personnel safety;
local maintenance mode, the platform monitors the operation mode and status of
the equipment through the local gateway module and FSU.

Efficient management
The accurate metering of each loads and seperate operators Local management, or platform may monitor equipments, whenever and wherever, through communication gateway or FSU;
Interactive experience and e-workflow, will improve the efficiency of operation and maintenance, and reduce the cost of operation and
Support measurement and metering multi-user, multi-device, multi-load;
maintenance;
The measurement accuracy is 0.5%, and the metering accuracy is 1%;
Based on daily data analysis of the tower business, to improve the company management.
The platform may monitor the measurement parameters and energy consumption
equipments through local gateway module and FSU;
Independent metering module can be easily added or reduced according to the
loads on site.

Differentiated backup power


It supports to achieve differentiated power backup by variables such as timer, time duration, voltage, kWh, and duty free time, for
multiple users or multiple equipments;
It supports parameter settings through local LCD screen, remote platform and FSU;
It supports up to 14 loads of differentiated power backup settings.

The independent power generation of 5G equipments


It supports independent power generation for multiple users or multiple 5G equipments;
It solves the problem of insufficient capacity of small oil machines and difficult to move large diesel generator;
optional power generation available and flexible configuration supportive.

- 15 - www.matismart.com www.matismart.com - 16 -
Site Solution Value Site Solution Benefits

Accurate metering and efficient management of


Value of telecom site solution
equipments in each load

Traditional solution Smart power distribution soltuion


Equipment operation and maintenance management
1 Lean management of equipment assets to facilitate operation and maintenance;
2 System safety assessment, providing preventive maintenance guidance and methods; Household meatering; independent load, household metering

3 Timely and professional fault recovery guidance, reducing the technical level requirements of operation and maintenance personnel; Hall transformer is greatly affected by installation and site

4 Providing sustainable services to ensure sustainable power supply, and safety. eviroment, and the metering is inaccurate; applying metering solution of manganese copper, which
Equipment controllable; won't be affected by installation and enviroment, with high
meterig accuracy.

Energy efficiency management independent load, remote control and management of


seperate loads
1 Design energy consumption data by each load, analyze the type and trend of energy consumption, and output reports;
2 According to business features, to make energy saving plans, and combine the intelligent control procedures of
Statistics Management can be classified according to
equipments to finalize a complete set of energy efficiency management plan.
different loads or users.

Equipments can be easily and flexibly managed or controlled,


Safety supervision to improve management efficiency, largely save electricity

1 Real-time monitoring of equipment status and timely access to equipment failure alarm information; bill and operation cost.

2 Full-featured electrical protection: overload, short circuit, overvoltage, undervoltage, phase loss, phase imbalance,
and overtemperature;
3 According to safety level notification, Operation and maintenance personnel MAY handle failure warning and alarm
accordingly, to ensure equipment safe operation.
Traditional power supply

Grid power
Operator Operator

Hall sensor Hall sensor

Smart circuit breaker

Operator Operator

3G 4G 3G 4G
3G 4G 3G 4G BBU BBU
BBU BBU RRU RRU RRU RRU
RRU RRU RRU RRU

Sector Sector Sector Sector Sector Sector Sector Sector Sector Sector Sector Sector Metering loads can be statistically classified
A B C A B C A B C A B C
Statistics and management available for each operation

- 17 - www.matismart.com www.matismart.com - 18 -
Site Solution Benefits Site Solution Benefits

Power on and off according to business characteristics


Differentiated backup power to improve battery efficiency greatly save electricity and maintenance cost

Primary and secondary power backup scheme Differentiated backup power scheme Base station business features Smart solution
(LLVD/BLVD)
According to different voltages, the device execute Load Low Platform will monitor the battery key information, SOH (State Different sites have different backup power priority, as different According to different business requirments in sectors, trying
Voltage Disconnect (LLVD) and Battery Low Voltage Disconnect of Health), SOC (State of Charge), voltage, in real time; business required in different tim; to extend backup power time duration in essential sectors, as
(BLVD); per power on in sectors;
Collect all loads power consumption in real time; Different sectors in same site, have different backup power
Load Low Voltage Disconnect (LLVD) all unessential loads. priority, as business requirements are also different; To power on/off different sites and sector, accordingly to
Battery Low Voltage Disconnect (BLVD) all loads; From platform edge computing, users may distribute different different business quirements in different time, will greatly
backup power time for different equipments, according to its 5G equipments requires huge power consumption, thus, energy save electricty bill;
Battery State of Health (SOH) changes over time. The backup importance; saving is especially important, However, traditional solution can't
time duration is different against the same LLVD; control each equipments, and thus can't control equipments Power on/off 5G each equipment independently.
Flatform may further differentiate backup power time, according to sites and sectors.
To ensure the backup time of essential equipments, operators according to voltage, needed time duration, duty-free time
need to go to the site, every period of time (six months or a period, and make it smarter;
year), to check Load Low Voltage Disconnect (LLVD).
Differentiated backup power may greatly improves battery 2X+Backup time
Smart solution Essential sector & same battery
efficiency and maximize battery capacity on key equipments, Sector
meanwhile, to achieve accurate metering;
BBU+transmission
Sector A
Differentiated backup power may avoid changing voltage on Sector B
site, and greatly reduce maintenance cost. Sector C
Sector A Power off 0.1h 1.0h 3.0h
Sites evolving available, as backup power requirements Sector B duration
are more complicated day by day No routine site adjustments Sector C

4 minute Circuit topology Power off


2600MHz
60 minute Step 1: The battery reports SOC to the platform Once battery is exhausted
1800MHz
Traditional solution all sectors will be powered off
4G equipment 700MHz
100 minute cloud service
BBU
120 minute
Step 2: Loads report real-time power consumption BBU+transmission
120 minute
transmission
Sector Sector Sector A
700M 2.1G Sector B
BBU
5G business Based on business Sector C
customization requirements Sector Sector Sector Power off 1.8h
Step 3: The platform analyzes the data and allocates A B C duration
Traditional solution: Battery State of Health (SOH) changes battery capacity to different frequency bands
The backup time duration is different against the same LLVD 120 minute BBU
100 minute Step: Disconnect by time
unit: 700M
57 30 minute 50Ah 120Mins

54 100% SOH the same LLVD-47V 2.1G 42Ah


2.6G
100Mins
10Mins

51
LLVD-47V
100% SOH 70 %SOH 4 minute
2.6G x
BBU 700M 2.6G BBU 700M 2. 6G
48 DOD 80% 50%
45
42 70% SOH Backup time 2h 1.5h
Primary power on based on sub-band, BBU backup time can reach *2 hours
39 The operator changes the power voltage every year
SOC BBU+700M+2.1G BBU+700M BBU
36 on site to ensure 700M 2 hours backup power
100.0% 50.0% 0.0%
Power off time 0.5h 1.0h 2.0h
40% 80%
BBU power consumption 900w, 100Ah battery

- 19 - www.matismart.com www.matismart.com - 20 -
Differentiated Power Backup Differentiated Power Backup
Solution of 5G Site Solution of 5G Site

5G solution application case Smart PDU introduction

3U high-density design, space saving, easy to install;


support equipment-level energy metering for 5G of two
users;
support 5G of two users to power on according to time
duration;
support 5G of two users to generate electricity on
demand;
maximum output power [email protected]
user1 user2
Metering AAU:3*63A+BBU:2*32A AAU:3*63A+BBU:2*32A
module
or DCDU:2*100A or DCDU:2*100A

Case characteristics

Support differentiated backup power for 5G users


1. Support two 5G users to power on according to time duration, and the time can be set through FSU/platform;
2. Each user supports 10 loads to meet the power distribution requirements of AAU and BBU

Support 5G user to meter energy by kWH


Case location 1. Support two 5G users the independent measurements of current, kWH and metering of all devices, and upload all data through

Customer needs the FSU or gateway;


2. High metering accuracy of 1%;
3. Use modular metering, it can add or reduce loads on demand, with simple wiring.
Specific requirements
Case location
China Tower Shanghai Branch
Differentiated backup power services to different equipments in the base
Support 5G equipments power generation on demand
Cutomer requirement station, 5G on power in time,
1. Support two 5G users to generate power on demand;
As texts description on the right picture.
different backup power demands in different operators, 2. Solve the problem of insufficient capacity of small diesel generator and difficult to move big diesel generator.
Shanghai Tower wants real time review, on web, the
3. Optional power generation and support flexible configuration.
capacity and status of device. It can remotely control
independent metering
each load, and regularly analyze the energy consump-
tion of the operator and output electricity billing.
independent electricity generation based on user's equipments
Support 5G equipments independent power-on/off control and automatic fault reset
independent control management and timely faults handling
1. Support power-on/off, lock and unlock of 5G quipments of each load;
2. Instantaneous fault automatic reset to ensure the continuity of power supply;

- 21- www.matismart.com www.matismart.com - 22 -


Differentiated Power Backup Differentiated Power Backup
Solution of 5G Site Solution of 5G Site

Application solution 1 Introduction of smart power distribution unit


PC configuration software
Application platform
FSU
Overview of smart PDU

Type Application
AI diesel generator analog signal input Signal input of grid power, diesel generator status
Communication gateway RS485 configuration
Central processing unit The local logic control and parameter setting management

Control module It executes power on/off, lock and unlock function of each sub-load.

Local metering module Local measurement data statistics storage module

Measurement acquisition module Current acquisition module


Smart power
Load output terminal User 2 Input negative busbar
distribution unit
1st group negative busbar user public Input positive busbar
DC diesel generator
Public negative busbar user 1 Input negative busbar

2nd group negative busbar user 1 Input busbar

Product Features
China Mobile DCDU China Unicom/Telecom DCDU

Control function Meter function Auxiliary function

Application solution 2 timer on-off,


time duration of backup power,
PDU owns various users metering and statistics
PDU owns sub-load metering and statistics
PDU owns sensor of power on/off, diesel generator, and real time status of grid
power or diesel generator
voltage of backup power, DC generator optional
power of backup power, RS485 / FSU / independent communication gateway, multi-mode management
Resource management
PC configuration software
duty-free period of time
Application platform System of power distribution load, remote capacity monitoring
FSU
Connect PMS system, remotely organize power distribution
resources

Communication gateway RS485 configuration Main components

Control module Metering Module Current Sensor IO terminal module Central control module Communication

Smart power

distribution unit

DC diesel generator

achieve power-on/off achieve the measurement, data acquisition module digital or analogue ports user management module Communication Management
AAU AAU AAU AAU AAU AAU
BBU BBU control metering and statistics of of current and voltage of input and output of local logic processing Module

remote lock and unlock each load center

China Mobile 5G device China Unicom/Telecom 5G device

- 23- www.matismart.com www.matismart.com - 24 -


Differentiated Power Backup Differentiated Power Backup
Solution of 5G Site Solution of 5G Site

Main technical parameters of smart power distribution unit Smart PDU installation

Functional module
Technical parameter of smart PDU Installation materials
Input voltage 8V-60V dc

Output voltage 42.3V-57.6V dc


Serial Category Name Description
Input current ≤200A number
Output current 20A / 32A / 63A / 100A optional

Central control module local monitoring management unit 1 Equipment 5 G Differentiated backup power module Differentiated backup power equipment
IO port module optional, Support state grid, and generator monitoring

2 Power cable 25mm2-35mm2 DC power cable Equipment DC input cable


Components in smart PDU

user 1 5*63A + 5*32A Multi-device management


3 Ground cable 16mm2 Yellow-green ground cable Equipment ground cable
Load control user1:3*63A + 2*32A / user2:3*63A + 2*32A 2 users, multi-device management
user2
user1:2*100A / user2: 2*100A 2 users, DCDU management,
4 Communication cable 1 Communication cable Data cable of equipment and FSU
user 1 Load control 5*63A + 5*32A Multi-device management measurement

Load metering user1:3*63A + 2*32A / user2:3*63A + 2*32A 2 users, multi-device management and measurement Interface software, Display equipment monitoring parameters,
user2 5 WEB configuring software
User user1:2*100A / user2: 2*100A 2 users, DCDU management and measurement parameter delivery, etc.

6 configuring computer laptop Commissioning software bearing equipment


Control Load

Control voltage 48VDC

Power ≤1W 7 installation accessories Terminals, cable ties, insulating tape, etc.

Mechanical / Electrical life 10,000

Control open, close, lock, unlock

Local operation open, close, mode change, safety padlock


Equipment installation
Metering load Range Accuracy

Voltage -38--58V 0.5%


Standard 19-inch subrack installation Non-standard 19-inch installation, such as stock tripartite cabinet
Current 1-120A 0.5%

Energy 0~99999999.9 1.0%

Power load 0~5KW 1.0%


Installation Dimension

Input specification Output specification1 Output specification2

200A 32A 100A


50~70mm2 4mm2 35mm2

63A
4mm2

Power distribution Low current load High current load


Power (AAU / BBU) (DCDU)
Note: By default, materials will be shipped in a 19-inch Note: For non-19-inch subrack, you need to prepare a 19-inch
rack scenario bracket or a pallet on site. Place the device on the pallet and fix
the two sides with self-tapping screws to ensure that the
Main components
device is stable and not loose.

- 25 - www.matismart.com www.matismart.com - 26 -
Differentiated Power Backup Differentiated Power Backup
Solution of 5G Site Solution of 5G Site

Cable installation Software configuration of smart PDU

Step 1: DC input power cord installation Step 1: Login project account in platform Step 2: Choose the site

Subrack power Combined


power supply

1~2 way 25mm2 1~2 way 25mm2 cable, the


cable, the front stage front stage connects 1~2pcs
connects 1~2pcs MCB MCB of 100A or above, or fuse
of 100A or above

Step 3: Add a cabinet Step 4: Bind the power distribution unit

Step 2: DC output power cord installation

Load connected to DCDU Load connected


to AAU BBU...

1. Loosen the screws on the 125A MCB on the power distribution unit
2. Install the DCDU power cord to the corresponding hole of the MCB 1. Loosen the screws of MCB on the power
3. Tighten MCB screws distribution unit
2. Install the load power cable to the
corresponding hole of the MCB.
3. Tighten MCB screws Step 5: Load configuration Step 6: Device control & data review

Step 3: Ground wire & communication Step 4: Debug the platform


module installation

Back of power distribution unit

Realize power on/off control Realize power on/off control Realize power on/off control Realize power on/off control realize the metering of data collect module of
remote lock, unlock remote lock, unlock remote lock, unlock remote lock, unlock each load and statistical current and voltage
1-16mm2 yellow-green wire connected to the ground data acquisition
screw on the back 1- Log in to the project account
2-0.75mm2 wire connected to communication 2- Register power distribution unit measurement, measurement,
terminals of the communication module 3- Debug power distribution unit meter grid power, meter grid power,
3-0.75mm2 wire connected to power terminals of the circuit breakers status
communication module real-time power real-time power
consumption of generators consumption of generators

- 27 - www.matismart.com www.matismart.com - 28 -
Differentiated Power Backup Differentiated Power Backup
Solution of 5G Site Solution of 5G Site

Smart AC electrical distribution box Smart AC & DC mixed electrical distribution box

Introduction The product function


Input to grid power or the generators, the AC power distribution to the switching Grid power input to one of the AC power is allocated to the external switching power
power rectifier module, air conditioner, or load of sockets, etc.; surge protector supply rectifier module-then connected to the DC power distribution system; the
AC and DC distribution box structure

AC and DC distribution box structure


device included, a base station power supply system as a second stage lightning other line is allocated to the AC power distribution system; to achieve the metering
protection. of power consumption in the complex power use site of AC and DC mixing .

Functions of incomer side Functions of incomer


Protection and Control: Monitoring and Display: Metering : Protection and Control: Monitoring and Display: Metering :
Remote control Voltage Total Energy remote control voltage total active
Auto Recloser Current Reactive Energy fault reclosing current reactive power
Short Circuit Active Power New Active Energy short circuit active power net active
Overload( 100A default, Reactive Power Net Reactive Energy overload(overcurrent value: default reactive power reactive power
threhold settable) Power Factor Consumption of Active Energy (overcurrent value: default 100A, power factor consumption active
Over voltage Frequency Consumption of Reactive Energy parameters can be set) frequency reactive energy
Under Voltage Temperature Tariff Settable overvoltage equipment temperature rate can be set
Phase Unbalance undervoltage phase monitoring
phase imbalance

Functions of outlet Functions of outlet


Remote Control: Monitoring and Display: Metering : Remote Control: Monitoring and Display: Metering :
Remote Control Voltage Total Energy remote control of load a voltage total energy kWH
Remote Lock/Unlock Current Energy of sub-load fault reclosing, surge protection and current sub-load energy kWH
Auto Recloser Active Power surge protection remote control power
Surge Protector automatic reclosing

Type Application of Type Application of


Smart IoT metering circuit breaker Grid power remote supervision, metering, control, protection AC load metering module AC load measurement statistics analysis
Input line terminal Generator remote supervision, metering, control, protection DC load metering module AC load signal acquisition
Output circuit breaker Grid power input power line DC load acquisition module AC load measurement statistics analysis
Generator quick plug-in Optional smart circuit breaker, switching power supply, air conditioner, lighting, etc. Smart circuit breaker of total AC input line AC load signal acquisition
Smart IoT metering circuit breaker Generator input power line AC load acquisition module input line power measurement, metering, protection, control

AIOT Metering Breaker AIOT Metering Breaker Auto Reclosed MCB/RCCB Control module Metering Module Current Sensor AIOT Metering Breaker AIOT Metering Breaker Auto Reclosed MCB/RCCB DC Contol Module DC Metering Module DC Current Sensor

.AC input .AC input .AC input . AC input .AC input .AC input .AC input .AC input .AC input .DC 48V . DC 48V . DC 48V
. Single phase, Max.80A . Three phase, Max.80A .Auto-reclose the associated . Monitoring and Measuring . Monitoring and Measuring . Data acquisition of current . Single phase, Max.80A . Three phase, Max.80A .Auto-reclose the associated .Remote On/OFF by RS485 . Monitoring and Measuring . Data acquisition of current
.Monitoring and Measurement .Monitoring and Measurement device after untimely trip of current, voltage of each load current, voltage of each load and voltage of each load .Monitoring and Measurement .Monitoring and Measurement device after untimely trip of .Remote Lock/Unlock current, voltage of each load and voltage of each load
. Metering grid power and . Metering grid power and breakers . Metering energy of each . Metering energy of each . Metering grid power and . Metering grid power and breakers .Auto Recloser . Metering energy of each
diesel generator diesel generator . 3 times of auto-reclosing load load diesel generator diesel generator . 3 times of auto-reclosing .Scheduled On/OFF load
. Auto Transfer between grid . Auto Transfer between grid program fixed in the device . Auto Transfer between grid . Auto Transfer between grid program fixed in the device
power and generator power and generator . Local operation mode by power and generator power and generator . Local operation mode by
. Remote On/OFF, Remote . Remote On/OFF, Remote hand for safety . Remote On/OFF, Remote . Remote On/OFF, Remote hand for safety
Lock/Unlock, Schedule Control Lock/Unlock, Schedule Control Lock/Unlock, Schedule Control Lock/Unlock, Schedule Control

- 29 - www.matismart.com www.matismart.com - 30 -
Production Introduction Production Introduction

Key components
AC system DC System

MT88M/MT88C MT61GP 2P MT61GP 4P MT61SR 2P MT61SR 4P MT53-RSD48 MT58SA-P63/125 MT58MD

Smart Metering MCCB AIOT Metering Breaker Smart Recloser Remote Control Breaker Solid-core current sensor Multi-channel meter device

Main switch of AC incomer and remote control; Main switch of AC incomer and remote control; Main switch of AC incomer and remote control; Remote On/OFF by RS485 Data acquistion of current and voltage Metering energy and power consumption of
Metering grid power and generator power Metering grid power and generator power Auto-reclose the device after lightning happened in Remote Lock/Unlock by RS485 Plug-in type multi-loads
Auto-transfer between grid power and generator power Auto-transfer between grid power and generator power telecom sites On/off status feedback of the associated breaker Active energy accuracy: class 1 Monitoring the voltage of all the loads
Detecting the status of grid power and generator Detecting the status of grid power and generator power Over/under voltage protection Scheduled On/OFF Max. current 125A Over/under voltage threshold setting
power Max.current 80A Leakage protection and auto-reclose after leakage fault RS485 and Modbus RTU DC 48V Over current threhold setting
Max.current 630A RS485,Ethernet, 4G, 2G,3G,WIFI disappeared DC 48V DC 48V
RS485,Ethernet, 4G Electrical alarm
Max.current 125A
RS485 and Modbus RTU

Monitoring Device Smart Gateway

MT53-RS220 + MCB/RCBO MT53RA-ML50 2P MT53RA-ML50 4P MT51RA-ML50 2P MT51RA-ML50 4P

Remote Control Breaker Auto Reclosed RCCB Auto Reclosed RCCB


Remote On/OFF by RS485 Auto-reclose the device after lightning happened in Auto-reclose the device after lightning happened in
Remote Lock/Unlock by RS485 telecom sites telecom sites
MT20-ST MT99BT MT88C
On/off status feedback of the associated breaker Leakage protection and auto-reclose after leakage fault Leakage protection and auto-reclose after leakage fault
Scheduled On/OFF disappeared disappeared
RS485 and Modbus RTU Auto recloser fault alarm Auto recloser fault alarm Air conditioner smart socket Battery Monitoring Device Communication Module
Reclosing sequence adjustable Reclosing sequence adjustable
Monitor battery string voltage, charge and discharge Downlink communicatio: RS485, Modbus RTU
current Uplink communication: GPRS 4G, GPS positioning, Ethernet
Calculate battery string SOC RJ45 port
Auto-balancing Uplink communication protocol: MQTT
Auto-sensing for the battery sensor's ID address AC/DC both available
Setpoint alarming (upper limit/lower limit)
Data collecting
RS485 (Modbus-RTU) & Ethernet (TCP or SNMP)
Check battery string status: equalizing, discharging,
floating charge, stand by and abnormal status
MT58MA MT58SA-S63 MT58SA-O50

Multi-channel meter device Solid-core current sensor Open-core current sensor

Metering energy and power consumption of Data acquistion of current and voltage Data acquistion of current and voltage
multi-loads Solid-core type with hole Open-core type with hole
Monitoring the voltage of all the loads Active energy accuracy: class 1 Active energy accuracy: class 2
Over/under voltage threshold setting Max. current 63A Max. current 50A
Over current threhold setting

- 31 - www.matismart.com www.matismart.com - 32-


Case Introduction

After the site reconstruction


Case 1: Shanghai Tower Indoor Telecom Tower Station
(China Mobile Qingxiaolai Station)

Site information 2 way 35mm2 cable

Unicom 5G AAU
The power supply adopts Emerson R48-2900U communication power supply module, equipped with 150A power module, actual load 100A, and sufficient power

supply capacity;

China Unicom and China Mobile share stations, China Mobile has 3pcs 4G RRUs, 3pcs 3G RRUs, China Unicom 3pcs 4G RRUs, and 3pcs 5G AAU, plus 1 transmission

device;

DC metering module has been connected, using Hall acquisition module. smart power
distribution unit(PDU)

Before the site reconstruction

Reconstruction plan

1. Reuse the original power distribution and add a new smart PDU.

2. Smart power distribution unit for 5G main equipment users, was replaced with power on.

3. System parameters are set according to user.

Achieved results
1. Control: 10 outputs, all have open and close control, lock and unlock functions.

Customer demand 2. Metering: 10 outputs, all of which have measurement and measurement functions. The accuracy is 1%.

3. Independent control: independent control of sector equipment.


Now Unicom's 5G equipment has high power consumption,

accurate measurement and Hall measurement for data comparison;

4G and 5G equipment remotely control, open, close, lock, unlock.

- 33 - www.matismart.com www.matismart.com - 34 -
Case Introduction Case Introduction

After the site reconstruction


Case 2: China Tower Shanghai Outdoor Tower Station
(China Unicom Qingshenxi)
2way35mm2cable
Combined Switching
Site information Powerr Supply

Combined switching power supply, equipped with a 300A power module, the actual load is 200A, and the power capacity is sufficient;

Telecom and China Unicom share stations. Telecom has 3pcs 4G RRUs, 3pcs 3G RRUs, China Unicom 3pcs 4G RRUs, and 3pcs 3G RRU devices;

already connected with a DC metering module and a Hall acquisition module.

Before the site reconstruction AC PDU

Old PDU
Smart PDU

Reconstruction plan

1. Reuse the original power distribution and add a new smart power distribution unit.

2. Telecom and China Unicom equipment are replaced with live electricity by users.

3. System parameters are set according to users

Customer demand Achieved results


1. Realize remote management and control (open, close, lock, unlock) of existing equipments, and metering of operator equipments 1. Control: 10 outputs, all have opening and closing control, and locking and unlocking functions.

2. Hope to be able to remotely manage power distribution resources and allocate power distribution switches on/off reasonably; 2. Meter: 10 outputs, all of which have measurement and measurement functions. The accuracy is 1%

3. Miscellaneous cable routing, The on-site reconstruction is highly complex, and it is easy to cause flashing due to loosen cable connection; 3. Independent control: independent control of sector equipments

4. It is difficult to route the power cabinet to the integrated cabinet;

5. The cables are not marked with the main equipment information and need to be confirmed one by one

- 35 - www.matismart.com www.matismart.com - 36 -