Stair Pressurization Calculation
Stair Pressurization Calculation
Stair Pressurization Calculation
COURSE:
PRESSURIZATION OF STAIRS AND EXTRACTION OF
CARBON MONOXIDE
STAIR PRESSURIZATION CALCULATION
5 .- Example of Calculations .
7 .- Conclusions .
8 .- Bibliography .
1.- VENTILATION CALCULATION BASED ON HEAT
Given:
Q = Thermal load of a room to be ventilated (kcal/h) p = Air density
(1.2 kg/m 3 )
Cp = Specific Heat of air. (0.24 Kcal/ kg-°C)
Tamb= Outside Temperature.(°C)
Ts = Indoor or room temperature.(°C)
V = Volumetric air flow. (m 3 /h)
Article 26.
A) Integrated Article 27. The number and width
B) . Evacuation of the stairs will be determined
81: Ventilated Previous Lobby according to the travel distance of
82: Non-Ventilated Previous Lobby the evacuator, measured from the
83: PRESSURIZED room furthest from the stairs, and
84: open the floor with the greatest
85: Closed capacity.
86: Mixed.
Article 28.- Regardless of its use, every education must have at least 2 evacuation
stairs......
(Standard A.10 – General Design Considerations – Chap. VI - Art.26)
VERTICAL CIRCULATION, OPENINGS TO THE
EXTERIOR, VANOS AND EVACUATION DOORS
Article 26.- There are 2 types of stairs:
A. INTEGRATED
They are those that are not isolated from horizontal circulation and whose objective is to
satisfy the transit needs of people between floors in a fluid and visible manner. These stairs
can be considered for calculation and support as means of evacuation, if the travel distance
allows it. They are not mandatory construction, since they depend on the architectural solution
and characteristics of the building.
B. EVACUATION
They are fire and smoke proof, they serve for the evacuation of people and access for
emergency response personnel. These stairs must meet the following requirements:
Article 32.- The suction and discharge of air from the ceiling
lights or fans must be equipped with smoke detectors
interconnected with the building's detection and alarm system in
such a way that it stops automatically. automatically in case smoke
enters through the impeller. The fan must be activated
automatically when any device in the ventilation system is
activated. tection and alarm. At least it must be activated by me
There were smoke detectors located at each access to the escape
stairs at no less than 3.0 m from the escape doors.
PRESSURIZATION OF STAIRS
| STANDARD A. 130 |
SAFETY REQUIREMENTS
Article 33.- The interconnection with the wing system mas
and detection (cables) must have cor protection tafuego for at
least 2 hours.
Article 34.- The energy supply for the mo The fan motors
must have two independent sources. teeth, automatic transfer.
The routes of these supplies must be independent and protected
with fire for 2 hours. Ali source transfer primary to secondary
mention must be made within 30 seconds after the primary
source failure. The control key must be separated from the
motorcycle pressurization switches so that the general contactor
does not act on this power supply. All sumi cables electric nitro
from the power panel to the fan motor inlet must have a pro Fire
protection for at least 2 hours.
STANDARD A.130
Article 35.- The fan must comply with the si following requirements:
a) Listed or equivalent.
PRESSURIZATION OF STAIRS
b) Preferably the radial centrifugal type.
c) In the event that the fan is driven by means of belts, the number of
these must be when I us 1.5 times the number of strips required for the
service design idea.
d) Every fan driven by means of belts must have at least two belts.
e) Calculations for selection and factory curve singing must be part of the
documents delivered.
f) Under no circumstances will the motor operate above the nameplate
power. The working power of determi It will be done by means of a field
measurement with three doors open.
g) The drive motor must have at least one fac 1.15 service tor
h) The fan must have protective guards for the belts.
i) The fan must have a base to isolate vibrations.
PRESSURIZATION OF STAIRS
| STANDARD A. 130 |
SAFETY REQUIREMENTS
Article 36.- Dampers and ducts must comply comply with the
following requirements:
2. Height =
3.2m.
3. Perimete
r = 18m .
4. Door=
1.0mx 2.15m
5. Levels =
18
Building Geometric
Data :
1. Perimeter =
103.01m .
Table 1 Typical leakage areas for walls and floors of
commercial buildings
Table 2 Minimum Design Pressure Differences Across FORCE APPLIED TO A DOOR FOR SMOKE CONTROL
SYSTEM
Smoke Barriers. (NFPA 92A – 2009 Edition).
5.20WA\p
F — F for
+ 2(Wd}
0=776CA./2Ap/p
where
The flow coefficient depends on the geometry of the flow path, as well as on turbulence and friction. In the present context, the flow coefficient is generally
0.6 to 0.7. For p = 0.075 Ibm/ft3 and C = 0.65, can be expressed as
Q = 2610A /Ap
5.2. - CALCULATIONS.
1. Flow area between the Building and the Exterior: Abo =
3548.13x0.00017=0.603 ft² Abo = Building Lateral Area *Typical leak areas.
2. Flow area between Staircase and Building : Asb = 620x0.00011 + 0.271 =0.34 ft² Asb =
Staircase Lateral Area * Typical leakage areas Staircases + Leakage area around closed door.
4. Differential pressure at the bottom of the Staircase : DPsbb =0.08 in.wc (this to provide a
degree of protection above the chosen minimum, in this case greater than 0.05 in.wc)
5. Distance above the bottom of the Ladder Y =NxH = 18x10.50 = 188.98 ft.
DPmax =(F-Fdc)x2x(Wd)/(5.2xWxA)
W= Door width =1.0m = 3.281ft; d= 0.25ft.
A=door area = 1.0 x 2.15 = 2.15m² = 23.142ft².
Dpmax =(30-10)x2x(3.281- 0.25)/(5.2x3.281x23.142) = 0.31 in.wc
(see the formula for the force applied to a door).
7. Differential pressure at the top of the ladder: D Psbt, we apply the pressure
equation based on the height "y".
D Psbt = 0.08 + 0.000227x188.98 / [1 + (0.34/0.603)²] = 0.11 in.wc
Differential Pressure at the bottom of the staircase D Psbb= 0.8 Temperature Fact B=0.000227.
Distance above the bottom of the ladder Y=188.98ft.
Flow area Staircase – Building = 0.34ft².
Flow area Staircase – Exterior =0.603ft².
5.2.1. - AIR FLOW WITH ALL DOORS
Q = 1740 x 18 x 0.34 x [ 0.113^3/2 - 0.08^3/2] / [0.113 – 0.08]: Q1 = 4942.47 CFM .
• Turn on the equipment in manual mode, regulate the air flow with the
frequency inverter such that with all the doors closed a pressure of 0.05”ac is achieved in
each of them, record the frequency of the inverter (Minimum Frequency).
• Measure the flow in each of the grids, record this individual and total flow, we will call the
total flow Minimum Flow.
• Record what pressure is being achieved in the Differential Pressure Sensor installed on the
ladder (Dwyer).
• Measure the phase currents in the electric motor, and record them.
With 3 Open Doors.
• Open the 1st Floor door to 90° (Mandatory) and 2 interior doors (any,
contiguous or non-contiguous).
• Turn on the equipment in manual mode, regulate the air flow with the frequency
inverter such that in all the doors that are closed a pressure of 0.05”ac is
achieved in each of them, record the frequency of the inverter (Maximum
Frequency), the Maximum Frequency is less than or equal to 60Hz.
• Measure the flow in each of the grids, record this individual and total flow, we
will call the total flow Maximum Flow.
A barometric relief damper is a backdraft damper with an adjustable start-open pressure. It is used for
gravity ventilation and low velocity systems. Counterbalance weights provide the ability to fine tune start-to-open and
full-open operation.
BR series dampers are constructed with a galvanized steel frame and aluminum
blades. The SEBR series is constructed of 316 stainless steel for severe or
corrosive environments. Vinyl blade seals are used on both series of dampers.
They are rated for velocities up to 2000 ft/min. (10.2 m/s) and back pressure up to
2 in. wg (0.5 kPa). The start-open pressure is selectable from .05 to .13 in. wg
(0.01 kPa to .03 kPa).
BR and SEBR series dampers can be used in applications for:
• Gravity hood intake and exhaust
• Stairwell pressurization
• Room pressurization
• Ductwork outlets
DM-2000-LCD DM-2100-LCD
Differential Pressure Transmitter
The Dwyer SERIES DM -2000 Differential Pressure Transmitter senses the pressure of air and
compatible gases and sends a standard 4-20 mA output signal. The DM-2000 housing is specifically
designed to mount in the same diameter cutout as a standard Magnehelic® gage. A wide range of
models are available factory calibrated to specific ranges.
Pressure connections are inherent to the glass filled plastic molded housing making installation quick
and easy. Digital push-button zero and span simplify calibration over typical turn-potentiometers. An
optional 3.5 digit LCD shows process and engineering units. A single push button allows field selection
of 4 to 6 engineering units depending on range.
Differential Pressure Transmitter
FEATURES/BENEFITS
* Zero and span controls provide easy calibration checks and shorter installation time to get device
running and monitoring
* Quick response to pressure changes means no delay in signaling and alerting to critical situations
* Easy to read LCD display provides immediate local alerts allowing corrective action to be taken
quicker to eliminate the problem from becoming popular
* Same size as Magnehelic simplifies field upgrade to digital pressure gage by reducing install steps
* Tamper proof button configuration to prevent accidental changes to the settings
APPLICATIONS
* Differential pressure across filters
* Fan control
* Static pressures in ducts or buildings
Differential Pressure Transmitter
Differential Pressure Transmitter
MODEL CHART
model Range (in Da mm toilet mBar kPa psi
DM-2O01-LCD toilet)
Oto .100 0 24.9 2.54 .249
DM-2O02-LCD to .250 0 to .500 62.2 6.35 .622
DM-20O3-LCD Other 1,000 124.3 12.70 1.243
DM-2O04-LCD 0 to 2.00 0 to 249 25.4 2.49 .124
DM-20O5-LCD 3.00 497 50.8 4.97 .249
.108
DM-20O6-LCD 76.2 .497
0 to 5.00 0 to 746 7.46 .180
DM-20O7-LCD 127-0 .746
DM-2012-LCD ±.250 1243 0 to ±62.2 0 to ±6.35 12.43 0 to 1.243
DM-2013-LCD Oto ±.500 Oto ±124.3 Oto ±12.70 ±.622
DM-2019-LCD 0 to ±.200 49.8 5.08 Oto
±1.243 .498
Note: For white overlay change -20 to -21. Example: DM-2102-LCD
Schemes
□pressure relief
ampere 0.2" H,0
Gakanized sheet metal duct from
the fan to the entrance of the
Transfer board in NEMA 4
staircase (referential according
type cabinet. Provide
to architecture)
electrical power point.
Variable frequency
drive, or the acronym
AFD
Smoke detector
connected to the
detection and alarm
system.
Sensor Pressure
diferencial
Recommendations:
3) THE SYSTEM:
- YOU MUST ALWAYS MAINTAIN THE PRESSURE OF 0.25" CA INSIDE THE
STAIRCASE.
/Ih
wiMi T Man g rtxm. one H. gnu mu mmi (i
HE-. DE
ceawn< IH n
HMF
DC
DELAI TH
nuupipn
PEIL-DE
EEFHAPIH m
Duuren
LETMIDA
cuue FANMOIF
T2T2 •mLML•IEéMT
ÚABLVM FkbIL6MI
PEL-.D
TETH4 ■nuM MEEEOI BEFLHAPIH DOH
Duuren
OML YE KA••OOMLA•O•I•
mTFE
PEIL-DE FFAFH ™
nuuren—1_1
F AM EM LJ.TC 225:5a
+ * Mimüim
EIEE2"TF
RAI iWi
>7.1
fUP.W
EEBLAF.H ™ üuure
——
28"xdF DAPE FOR MJWJ
nmunanorCmrAoOTL.rünELzmAcmTANOID(2
Milke)
7. Author's Experience.
PRESSURIZATION OF STAIRS
By John H. Klote
& James A-Milke
STAIRS
Ministry of
Housing. —r
PRESSURIZATION OF STAIRS
PRESSURIZATION OF STAIRS
Underwriters
L)
Laboratories
PRESSURIZATION OF STAIRS