Fire Detection and Alarm System Testing Procedure

The document describes the testing procedure for the fire alarm and detection system. It includes inspecting and testing devices such as monitoring modules, smoke and temperature detectors, and manual stations. Explains how to activate a simulated alarm using the manual station or by spraying artificial smoke on a smoke detector, and how to reset the system after clearing the simulated event.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
72 views6 pages

Fire Detection and Alarm System Testing Procedure

The document describes the testing procedure for the fire alarm and detection system. It includes inspecting and testing devices such as monitoring modules, smoke and temperature detectors, and manual stations. Explains how to activate a simulated alarm using the manual station or by spraying artificial smoke on a smoke detector, and how to reset the system after clearing the simulated event.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 6

LUMAR

ENGINEERING AND ELECTROMECHANICAL SOLUTIONS SAC


SYSTEM TESTING PROCEDURE
FIRE ALARM AND DETECTION

The Fire Alarm and Detection System must be inspected and tested. This is to comply with
the provisions of the NFPA 72 standard, and manufacturers recommend that all initiating
devices such as supervision modules, detectors and manual stations be subjected to a test
and inspection, which must be completed in a protocol. of operation that will validate what
was reported .

1. Control Panel (4007ES)


It is responsible for receiving the signal from initiation devices such as supervision
modules, smoke and temperature detectors or sensors, in addition to manual stations and
giving warning through sound or light notification systems (Horn Strobe) .

Taking into consideration the Buttons:

Fire: Fire.
Alarm Function: Alarm functions.
Signal Silence: Silence the Sirens with Strobe.
Drill: Drill button.

Ate - Lima + 51 949 071


343
www.lumar.com.peventas
@lumar.com.pe
LUMAR
ENGINEERING AND ELECTROMECHANICAL SOLUTIONS SAC

2. Manual Station
It is a manual action device that requires the human factor to activate. This device sends a
signal to the alarm panel indicating the possibility of a fire or situation that requires an
evacuation.

Fig. Activation is manual

3. Smoke Sensor
It is a system device that is activated by the presence of smoke
in the area where it was installed; generally, the alarm panel
indicates the precise place where it is presumed there may be a
fire.

smoke

Ate - Lima + 51 949 071


343
www.lumar.com.peventas
@lumar.com.pe
LUMAR
ENGINEERING AND ELECTROMECHANICAL SOLUTIONS SAC

Fig. Artificial smoke is applied to the Sensor to simulate its activation, this activation will
be reported to the VIGILANT Panel.

4. Temperature Sensor
It is a system device that is activated with the rise of Temperature in the area
Where it was installed, generally, the alarm panel indicates the precise place where I
where there may be a fire . know

Ate - Lima + 51 949 071


343
www.lumar.com.peventas
@lumar.com.pe
LUMAR
ENGINEERING AND ELECTROMECHANICAL SOLUTIONS SAC

5. PROCEDURE FOR ACTIVATION OF AN ALARM


STEP 1.- In the first instance, the manual station will be activated or the drill will be carried
out with the sensor, spraying artificial smoke on it at a safe distance of 15cm. If there is a
lack of distance to reach the sensor, then the sensor will be placed. A ladder on one side of
the sensor for ease of testing .
LUMAR
ENGINEERING AND ELECTROMECHANICAL SOLUTIONS SAC

STEP 2.- The event will be displayed on the LDC screen of the Panel as shown in the Figure.

First Floor Hallway


ZONELIST POINT FIRE ALARM

first Floor. Main Lobby ZONELIST POINT FIRE ALARM

Alarm Indicator Supervisory Color LCD AC Power 3 programmable LEDs with custom label
LED Network Indicator touchscreen green LED insert, top two selectable as red or yellow,
bottom selectable as
____________green or yellow____________
Priority 2 Network Trouble Indicator Alarm Silenced Indicator
LED indicator yellow LED Yellow LED

The evacuation system is activated, with strobe sirens being the notification devices.

V 9 Ate - Lima
© + 51 949 071 343
www.lumar.com.pe
[email protected] . pe
LUMAR
ENGINEERING AND ELECTROMECHANICAL SOLUTIONS SAC
STEP 3.- Once the event has been resolved, we proceed to reset the activated manual stations, then in the
menu shown of the faults that the screen sends us directly, we will find the Alarm Functions option, we
press this option where it will send us to another menu where You will find the Alarm silence and System
Reset options, of which you will first press the option to silence the alarms and then be able to restart the
system.

© + 51 949 071 343


® www.lumar.com.pe

[email protected]