Chapter 05 System Parameter Settings
Chapter 05 System Parameter Settings
5.1. Overview
Launch EasyBuilder Pro, in the main menu select [Home] » [System Parameters] to open the
[System Parameter Settings] dialog box. System Parameter Settings are divided into several
tabs, these tabs will be introduced respectively in this chapter.
5.2. Device
Parameters in this tab determine the attributes of each device connected with HMI. The device
can be a Local / Remote HMI / PLC. A default device "Local HMI" exists when creating a new
project. This device is the HMI that will be updated and programmed.
“Local Device” is a device connected to the local HMI. To control/connect a Local Device, add
this type of device first. Click [System Parameters] » [New] to open [Device Properties] dialog
box. For example, when connecting MODBUS RTU as a Local Device:
Setting Description
Name The name of the device.
Timeout
If the communication has been disconnected for more
than preset time limit configured in [Timeout] (in sec),
Window No. 5 will pop up and show “Device No
Response” message.
Turn around delay
While sending the next command to the device, HMI will
delay the sending according to the time interval set in
[Turn around delay]. This may influence the efficiency of
the communication between HMI and the device. Default
value is “0”.
Note
When using a cMT / cMT X Series model, select “Local HMI” in [System Parameter Settings]
dialog box and then click [New Device] to add a “Local Device 1” under “Local HMI”.
Click the icon to watch the demonstration film. Please confirm your internet connection
before playing the film.
“Remote Device” is a device being connected to a remote HMI. To control a remote device, add
this type of device first. Please click [System Parameters] » [New] to open [Device Properties]
dialog box. For example, use MODBUS RTU as the Remote Device:
Setting Description
HMI or
In this example, a device is used, so select [Device].
Device
Location Select [Local] or [Remote]. In this example the device is
connected to Remote HMI, so select [Remote]. Set the IP
address and port number of the Remote HMI by clicking
[Settings] next to [Remote].
COM Set the correct COM port used by the Remote Device.
Device
default Set the station number of Remote Device.
station no.
After all settings are completed, a new device named “Remote Device 1” is added to the
[Device list].
Note
When using a cMT / cMT X Series model, select the defined “Remote HMI 1” in [System
Parameters] dialog box and then click [New Device] to add a “Remote PLC 1” under
“Remote HMI 1”.
Click the icon to watch the demonstration film. Please confirm your internet connection
before playing the film.
“Remote HMI” is the HMI other than “Local HMI”, and PC is also a “Remote HMI”. To control a
Remote HMI, add this type of device first. Click [System Parameters] » [New] to open [Device
Properties] dialog box as shown in the following figure:
Setting Description
HMI or
In this example, the device used is a HMI, so select [HMI].
Device
Location Select [Local] or [Remote]. In this example Remote HMI is
used, select [Remote]. Set the IP address and port number
of the Remote HMI by clicking [Device Properties] »
[Location] » [Settings].
After all settings are completed, a new device named “Remote HMI 1” is added to the [Device
list].
Note
When using a cMT / cMT X Series model, in [Device list] click [New HMI] to add a “Remote
HMI 1”.
Click the icon to watch the demonstration film. Please confirm your internet connection
before playing the film.
5.3. Model
Configure the [HMI model], [Timer], [Printer] and [Scroll bar] settings, and more.
eMT, iE, XE, mTV Series
Setting Description
HMI model Select an HMI model.
The [Resize pop-up windows / objects] dialog box will pop
up when changing to a model with a different resolution.
Select required adjustment and click [OK]. In most cases,
select all options.
Landscape/Portrait
Change the orientation of the project.
HMI station no. Set the station number of current HMI. The default value is
“0”.
Port no. Set the port number of current HMI. The default value is
“8000”.
Support cMT Supports communication with cMT / cMT X Series models.
communication
protocol cMT / cMT X Series project file should use the same
communication port.
Printer (eMT, Type
iE, XE, mTV A printer can be connected with the HMI. The HP PCL Series
Series) printer is connected through USB interface while other
printers through a COM port.
For more information, see “23 HMI Supported
Printers”.
If the printer is connected through [COM], configure the
parameters correctly. If the printer type is [SP-M, D, E, F],
the [pixels of width] has to be set accurately, i.e. the set
pixel(s) cannot exceed printer’s default setting, or the HMI
will fail to print data.
Printer (cMT, The printer driver can be installed on HMI.
cMT X Series) Type
Select printer type.
Status address
Shows printer status.
LW-n Status
0 Printer driver is not installed yet.
1 Installing printer driver.
2 Printer is ready.
3 Printer is printing.
4 Print job is canceled.
LW-n+1 Error
0 None
1 Printer is not found.
2 Unknown error.
Control address
Updates printer connection parameters.
LW-n Command
0 None
1 Update connection parameters.
2 Restart printer driver.
LW-n+1 I/O
0 Ethernet
1 USB
LW-n+2 IP address (Total: 4 words)
LW-n+6 Port (Default port number: 9100)
Please note that using only the ppd file for a printer may
not be able to run the printer since the corresponding
driver is absent. Using tested models is recommended.
Scroll bar Set the width of Scroll Bar, when the size of the object is too
small to display the contents, a scroll bar is displayed in the
object. This feature can be applied to objects that allow
scrolling, such as Alarm Display, Event Display, History Data
Display, and Option List.
Pass through
(Virtual COM Set the port number for Pass-through communication.
port)
5.4. General
Setting Description
Options Fast display mode
In this mode, selected objects will cache the most recently
read data and display it quickly after window is changed,
achieving a faster display speed.
Controllable objects: Objects that allow variable input, such
as Toggle Switch, Numeric Input.
Uncontrollable objects: Objects that only display states,
such as Bit Lamp, Word Lamp.
The objects that support the fast display mode include: Bit
Lamp, Word Lamp, ASCII, Numeric, Function Key, Option
List, Direct / Indirect Window, Bar Graph, Meter Display,
Animation, Moving / Rotating Shape, PDF Reader, Picture
View, Energy Demand Display.
RW_A enabled
Enable or disable recipe data RW_A. Enable this, the
objects can then control RW_A .The size of RW_A is 64K.
Trigger release action anyway if touch moves out of the
button. (cMT / cMT X Series)
With this option selected, releasing the finger after
touching the button and then sliding the finger out of the
button area is still considered as button release; its release
action(s) will be triggered.
Set value when leaving focus (cMT / cMT X Series)
With this option selected, values will be written upon
leaving the input mode of an object (e.g. Numeric object),
even if not by pressing the ENTER key. For example, data
entry for the current numerical object is considered
completed and value is written when one selects another
object to enter value. An alert message shows when an
invalid value is entered.
Note
1. Values will not be retained after pressing the ESC key to
leave.
2. When the system keyboard is used, values will be
directly written after closing the keyboard.
3. With [Input order] enabled, the sequential input is
performed after leaving the object by pressing the
ENTER key. The sequential input will be stopped if
another object is touched during the input process.
CSV delimiter (cMT / cMT X Series)
Save the CSV file generated from Backup or Import/Export
with Comma (,) or Semicolon (;) delimiter.
Windows Startup window no.
Designate the window shown when start up HMI.
Common window
The objects in the common window (Window No. 4) will be
shown in each base window. This determines that the
objects in common window are placed above or below the
objects in the base window.
Object layout
If [Control] mode is selected, when operating HMI,
[Animation] and [Moving Shape] objects will be displayed
above other kinds of objects neglecting the sequence that
the objects are created. If [Nature] mode is selected, the
display will follow the sequence that the objects are
created, the first created will be displayed first.
Enable window layers (This can be used to
organize/show/hide objects)
With this option selected, layers within a window can be
created in the window tree.
Customized
A .bmp file can be selected as startup screen.
Some features are duplicated from system registers, such as, [Hide system setting bar
(LB-9020)], [Hide mouse cursor (LB-9018)], [Disable buzzer (LB-9019)], and [Disable upload
function (LB-9033)]. Users can also set these features via system tag.
To select a system tag, select [Address] » [System tag] check box when adding a new object and
then select the [Address Type].
To browse all the system tags, Select [Project] » [Tag] » [System] from the main menu of
EasyBuilder Pro.
Setting Description
Startup language after Set the language to use when HMI starts after
redownloading the the project is re-downloaded.
project
Delay time of device Certain PLC models need relatively longer
communication after startup time. In order to prevent
HMI starts communication error that occurs when HMI
attempts to communicate with a PLC that has
not yet started, a delay time can be set.
Include delaying the execution of all init.
Macros when HMI starts.
With this option selected, the macros that
have [Execute one time when HMI starts]
enabled will also be delayed.
Execute init. MACRO Designate the macro to be executed when HMI
when power on power on.
Auto logout If leaving HMI untouched for longer than the
set time, the objects protected by security
classes will not be able to operate. The user ID
and password must be entered again to unlock
it.
Hide system setting bar / Hide the system setting bar from HMI screen.
Start Button
Hide mouse cursor Hide the mouse cursor in HMI screen.
Mouse cursor size Set mouse cursor size.
Sound control With each touch on a button, a sound is
emitted: With sound enabled in object
settings, a sound is emitted when the object is
touched.
With Each operation from a button, a sound is
emitted: When sound is enabled in object
settings and the [Min. press time] is specified,
there may be a time gap between touching the
object and the action of the object. With this
option selected, the sound is emitted when
the object actions.
Disable sound output: Mute HMI. (Not
including the sound played when tapping
system setting button on HMI.)
Play next sound after stopping previous:
5.6. Remote
Parameters in this tab configure remote connections. Certain functions can be carried out
using system registers.
Setting Description
Prohibit remote HMI Prohibit the connection with a remote HMI or
connecting to this cMT Viewer. The remote HMI will not be able
machine to control the local HMI.
Prohibit password Prohibit Remote HMI to read Local HMI’s
remote-read operation project password and user password.
(or set LB9053 ON)
5.7. Security
Parameters in this tab configure the user passwords and security classes. There are two
authentication modes: General Mode and Enhanced Security Mode.
For more information, see “10 Security”.
General Mode
Up to 12 sets of user and password are available. Password should be one non-negative integer.
Once the password is entered, the objects that the user can operate are classified.
There are six security classes available: A to F.
If [None] is selected for an object, every user can access this object.
For example, when the security class of User No. 3 is set as the preceding figure, User No. 3
could only access objects of classes A, B, C and “none”.
At most 11 users can be set here. An [Administrator] user is provided in this mode. An
[Administrator] has all privileges and can operate all object classes. User passwords must be
alphanumeric, and each user can have up to 12 classes: A to L.
Setting Description
Editable Determines whether other users can change the
password settings or see passwords.
Enable read-only
Under this mode, the settings can be viewed but not
changed.
Mask password
Passwords are masked by asterisks (*).
Select operable When [Use existing user accounts on HMI] check box
classes for each is selected, the user accounts existing on HMI will not
user be erased after downloading the project file to HMI.
Extended Memory is numbered from EM0 to EM15. It works in a way similar to other device
types (i.e. LW or RW address). Users can simply select from EM0 to EM15 in the [Address]
setting while creating a new object. Maximum allowable data size for each Extended Memory
is 2G words.
Data in the extended memory is saved as a file into [SD card] or [USB disk]. By default, the files
in [EM0] to [EM15] are with the file names “em0.emi” to “em15.emi” respectively, although
users are free to change the file names. To open these files and edit the data in the extended
memory, RecipeEditor.exe may be used.
Data in the extended memory will not be erased when HMI power is cut, which means data in
the extended memory remains the same as before power off when HMI is started again. This is
a behavior similar to recipe data (RW, RW_A).
When the device used as extended memory does not exist, reading the data in the extended
memory will get “0”, and writing data to the extended memory will display "Device no
response" message on HMI.
Cutting HMI power is not necessary for inserting or removing the external device to or from
HMI, making it easy for users to immediately update or obtain data in the extended memory.
Setting Description
Enable dynamic With this option selected, the file names of
file name EM0~EM15 can be changed dynamically. Select “EM
file name index (0~15)”, enter “EM file name”, set
“Control” to 1, and then see the “Result”. After
successfully changing the file name, the new file name
will immediately be the data source of EM address.
Please note that after changing the EM file name
dynamically, the new file name is retained after
rebooting HMI, which may be different from the file
name specified in the project file.
Click the icon to watch the demonstration film. Please confirm your internet connection
before playing the film.
Configure remote printer / backup server. This feature is not supported on cMT / cMT X Series
HMI.
Setting Description
Output Orientation
settings Set how will words or pictures be printed out, [horizontal]
or [vertical].
Printer size
Set to print out in [Original size] or to [Fit to printer
margins].
Margin
Set the top, bottom, right and left margin width.
Communication IP address
settings Assign the IP address of the printer via network.
[Port], [User name], [Password]
Specify the data to log in server.
Port can be set from 1 to 65535.
Maximum length of user name or password is 12
characters.
For more information, see “26 EasyPrinter”.
Click the icon to download the demo project. Please confirm your internet connection
before downloading the demo project.
Setting Description
HMI time zone Select HMI time zone.
Enable time Automatically synchronizes HMI time with the designated
synchronization source address when HMI starts. As shown in the settings
with the external above, the time source is set to D address of the device
device when HMI Mitsubishi FX5U, so 6 consecutive word addresses starting
starts from D-0 will be the source addresses and each of them
should contain time information as follows:
D-0 → Second (range: 0~59)
Note
When the Network Time Server is configured with a static IP address, write/control
operations can be performed using addresses LW-11278 to LW-11293. However, if the
Network Time Server is configured with a domain name, modifying the IP address of the
Network Time Server via addresses LW-11278 to LW-11293 is not supported.
When DST ends, and the time falls back, the Trend Display object in Real-time mode will
stop refreshing for the overlapping hour(s) when it just going back to standard time.
However, historical data will not be affected.
When DST ends, adjusting HMI time (manually or by network) back to the DST period will
not be effective to the system. The system register LB-12355 stays OFF.
When DST ends, and the time falls back, the system will not start DST for the overlapping
hour(s). The system register LB-12355 stays OFF.
Before DST starts, adjusting HMI time (manually or by network) into the DST period will
start DST. The system register LB-12355 will be set ON. The HMI time will be the specified
For more information on system registers relevant to DST, see “22 System Registers”.
5.11. e-Mail
Setting Description
SMTP Settings Server: Set SMTP Server.
Port: Set communication port.
User name: Set e-mail address.
Password: Set e-mail password.
Confirm Password: Confirm e-mail password.
SMTP server requires authentication:
Decide whether Secure Password Authentication is needed
when log in e-mail.
Use the following type of encrypted connection:
Decide whether an encrypted connection (TLS, SSL) is
required when sending e-mails. Please note that TLS
support is limited to TLS 1.0.
Sender Name:
Information Enter the sender name or use the local HMI name in the
device list, or the name specified using system register
LW-10884 (HMI name).
Mail Address:
Setting e-mail address.
Error message When an error occurs in email delivery, the error message
sent from SMTP server can be shown in the designated
address.
For more information on system registers relevant to
mail delivery, see “22 System Registers”.
Error Turn OFF LB-12053 or LB-12054 before send an e-Mail
notification When enabled, system registers LB-12053 or LB-12054 will
be turned off before sending e-mail, otherwise, when an
error occurs in email delivery, the register remains ON.
Test SMTP Verify SMTP settings in advance by sending a test email to
Settings the specified e-mail address.
Setting Description
Contact list Add or remove contacts from the list.
Group Group up contacts.
Information No. of groups:
Set no. of contact groups, according to the number, the
groups are named from A to P and up to 16 groups can be
set.
Current group:
Displays the group that includes the contacts above.
Comment:
Enter a description for the current group.
For more information on sending Event Log, see “7 Event Log”.
For more information on e-mail related system registers, see “22.3.40 e-Mail”.
Click the icon to watch the demonstration film. Please confirm your internet connection
before playing the film.
Click the icon to download the demo project. Please confirm your internet connection
before downloading the demo project.
This tab is for setting cellular data. Cellular data network settings may differ from one model to
another.
Applicable models:
cMT X Series models
cMT-SVR (OS ver. 20151127 or later)
cMT3071/cMT3072/cMT3090/cMT3103/cMT3151 (OS ver. 20180723 or later)
cMT-HDM/cMT-FHD/cMT-FHDX (OS ver. 20190130 or later)
Setting Description
Use existing contact If this check box is selected, the cellular data currently
settings on HMI in HMI will be used. When no specific settings are
required, generally, [PIN code] is “0000”, [APN] is
“internet”, and [Username], [Password], [Dial number]
are optional.
When successfully connected, the following registers can be used to monitor and control the
connection status.
LW-11380: (16bit) : stop (set 0)/start (set 1) connection (USB
tethering)
LW-11381: (16bit) : connection status (0:no device, 1:disconnect,
2:connected, 3:fail, 4:OS not support, 5:HMI not
support) (USB tethering)
Click the icon to download the demo project. Please confirm your internet connection
before downloading the demo project.
5.13. FTP
FTP Server
Starting from OS version 20240308, the cMT/cMT X series HMIs support explicit FTPS. Users
can configure the HMI FTP server certificate with the following options:
1. Keep HMI settings: Continue using the current certificate settings on the HMI.
2. Default certificate: Use the system-provided default certificate.
3. Custom certificate: Users can import their own certificate and private key to meet specific
security requirements.
FTP Client
The FTP client function enables users to back up screen hardcopies and historical data. Once
enabled, users can backup files from the HMI to the FTP server. This feature is similar to the
eMT/iE/XE/mTV series, which uses EasyPrinter for historical data backup.
Please note that this feature is only supported on the cMT/cMT X series.
Setting Description
Enable FTP With this option selected, backup files (screen hardcopy or
Function historical data) can be transferred to FTP server.
FTP Connection FTP server’s information.
Naming Use IP address, backup folder name, or HMI name to name
Convention for the HMI folder.
HMI Folder Prefix: Add a prefix to the beginning of the folder name.
Note
When the FTP function is enabled without any configured FTP connections, the system
will direct users to the [Data/History] » [FTP Connection] settings to configure FTP server
connection parameters.