Prestressed Concrete Design
Prestressed Concrete Design
11
Prestressed concrete
Chapter introduction
The analysis and design of prestressed concrete is a specialised field which
cannot possibly be covered comprehensively in one chapter. This chapter
concentrates therefore on the basic principles of prestressing, and the analysis
and design of statically determinate members in bending for the serviceability
and ultimate limit states.
A fundamental aim of prestressed concrete is to limit tensile stresses, and
hence flexural cracking, in the concrete under working conditions. Design is
therefore based initially on the requirements of the serviceability limit state.
Subsequently considered are ultimate limit state criteria for bending and shear. In
addition to the concrete stresses under working loads, deflections must be
checked, and attention must also be paid to the construction stage when the
prestress force is first applied to the immature concrete. This stage is known as
the transfer condition.
The stages in the design of prestressed concrete may therefore be
summarised as:
1. design for serviceability – cracking
2. check stresses at transfer
3. check deflections
4. check ultimate limit state – bending
5. design shear reinforcement for ultimate limit state.
They are illustrated by the flow chart in figure 11.1.
332
Structure usage
5.10.2 Stress limits
Concrete class
Shape, depth, cover,
Trial section
loss allowance etc
2.3.1 Self-weight +
permanent action moment
FINISH
Prestressed concrete 333
B
Figure 11.2
Effects of axial prestress
P P
B
C C C C
+ =
T C T C
Bending strain Prestress Bending Total
distribution
Section B–B Stress distribution – Section B–B
334 Reinforced Concrete Design
B
Figure 11.3
Effects of eccentric prestress
e e
P P
B
C C T C
+ + =
C T C C
Axial Bending Eccentricity of Total
prestress prestress
Stress distribution – Section B–B
Early attempts to achieve this effect were hampered both by the limited steel
strengths available and by shrinkage and creep of the concrete under sustained
compression, coupled with relaxation of the steel. This meant that the steel lost a large
part of its initial pretension and as a result residual stresses were so small as to be
useless. It is now possible, however, to produce stronger concretes which have good
creep properties, and very high strength steels which can be stressed up to a high
percentage of their 0.1 per cent proof stress (used in design) are also available. For
example, hard-drawn wires may carry stresses up to about three times those possible in
grade 500 reinforcing steel. This not only results in savings of steel quantity, but also the
effects of shrinkage and creep become relatively smaller and may typically amount to
the loss of only about 25 per cent of the initial applied force. Thus, modern materials
mean that the prestressing of concrete is a practical proposition, with the forces being
provided by steel passing through the beam and anchored at each end while under high
tensile load.
11.2.1 Pretensioning
In this method the steel wires or strands are stretched to the required tension and
anchored to the ends of the moulds for the concrete. The concrete is cast around the
tensioned steel, and when it has reached sufficient strength, the anchors are released and
the force in the steel is transferred to the concrete by bond. In addition to long-term
losses due to creep, shrinkage and relaxation, an immediate drop in prestress force
occurs due to elastic shortening of the concrete. These features are illustrated in
figure 11.4.
Prestressed concrete 335
Before
Stress in tendons
transfer
After
transfer
and losses
bond bond
length length
Because of the dependence on bond, the tendons for this form of construction
generally consist of small diameter wires or small strands which have good bond
characteristics. Anchorage near the ends of these wires is often enhanced by the
provision of small indentations in the surface of the wire.
The method is ideally suited for factory production where large numbers of identical
units can be economically made under controlled conditions, a development of this
being the ‘long line’ system where several units can be cast at once – end to end – and
the tendons merely cut between each unit after release of the anchorages. An advantage
of factory production of prestressed units is that specialised curing techniques such as
steam curing can be employed to increase the rate of hardening of the concrete and to
enable earlier ‘transfer’ of the stress to the concrete. This is particularly important where
re-use of moulds is required, but it is essential that under no circumstances must calcium
chloride be used as an accelerator because of its severe corrosive action on small
diameter steel wires.
One major limitation of this approach is that tendons must be straight, which may
cause difficulties when attempting to produce acceptable final stress levels throughout
the length of a member. It may therefore be necessary to reduce either the prestress or
eccentricity of force near the ends of a member, in which case tendons must either be
‘debonded’ or ‘deflected’.
1. Debonding consists of applying a wrapping or coating to the steel to prevent bond
developing with the surrounding concrete. Treating some of the wires in this way
over part of their length allows the magnitude of effective prestress force to be
varied along the length of a member.
2. Deflecting tendons is a more complex operation and is usually restricted to large
members, such as bridge beams, where the individual members may be required to
form part of a continuous structure in conjunction with in situ concrete slabs and sill
beams. A typical arrangement for deflecting tendons is shown in figure 11.5, but it
must be appreciated that substantial ancillary equipment is required to provide the
necessary reactions.
Deflection supports
Figure 11.5
(cut off after transfer)
Prestressed tendons Tendon deflection
Concrete
To jacks To jacks
336 Reinforced Concrete Design
11.2.2 Post-tensioning
This method, which is the most suitable for in situ construction, involves the stressing
against the hardened concrete of tendons or steel bars which are not bonded to the
concrete. The tendons are passed through a flexible sheathing, which is cast into the
concrete in the correct position. They are tensioned by jacking against the concrete, and
anchored mechanically by means of steel thrust plates or anchorage blocks at each end
of the member. Alternatively, steel bars threaded at their ends may be tensioned against
bearing plates by means of tightening nuts. It is of course usually necessary to wait a
considerable time between casting and stressing to permit the concrete to gain sufficient
strength under in situ conditions.
The use of tendons consisting of a number of strands passing through flexible
sheathing offers considerable advantages in that curved tendon profiles may be
obtained. A post-tensioned structural member may be constructed from an assembly of
separate pre-cast units which are constrained to act together by means of tensioned
cables which are often curved as illustrated in figure 11.6. Alternatively, the member
may be cast as one unit in the normal way but a light cage of untensioned reinforcing
steel is necessary to hold the ducts in their correct position during concreting.
After stressing, the remaining space in the ducts may be left empty (‘unbonded’
construction), or more usually will be filled with grout under high pressure (‘bonded’
construction). Although this grout assists in transmitting forces between the steel and
concrete under live loads, and improves the ultimate strength of the member, the
principal use is to protect the highly stressed strands from corrosion. The quality of
workmanship of grouting is thus critical to avoid air pockets which may permit
corrosion. The bonding of the highly stressed steel with the surrounding concrete beam
also greatly assists demolition, since the beam may then safely be ‘chopped-up’ into
small lengths without releasing the energy stored in the steel.
Parabolic tendons
Figure 11.6
Post-tensioned segmental
construction
Precast segments
I b
zt = Figure 11.7
yt Top fibre Sign convention and
notation
e –ve
yt
Area A = bh h Centroidal
axis
e
yb
I e +ve
zb =
yb Bottom fibre
Compressive stresses +ve Prestressing tendon
Tensile stresses –ve
The stress in the steel is unimportant in the analysis of the concrete section under
working conditions, it being the force provided by the steel that is considered in the
analysis.
The sign conventions and notations used for the analysis are indicated in figure 11.7.
B
Figure 11.8
Stresses in member with axial
prestress force
P P
P/A M/zt ft
+ =
P/A M/zb fb
Prestress Bending Total
Stress distribution – Section B–B
For this value of prestress force, substitution in the other equations will yield the stresses
in the beam under maximum load and also under minimum load. Similarly the stresses
immediately after prestressing, before losses have occurred, may be calculated if the
value of losses is known.
For example, the maximum stress in the top of the member is given by equation 11.1
P Mmax
ft ¼ þ
A zt
where
Mmax A
P¼
zb
therefore
P P zb
ft ¼ þ
A A zt
P zb þ zt
¼
A zt
It can be seen from the stress distributions in figure 11.8 that the top fibre is generally in
considerable compression, while the bottom fibre is generally at lower stresses. Much
better use of the concrete could be made if the stresses at both top and bottom can be
caused to vary over the full range of permissible stresses for the two extreme loading
conditions. This may be achieved by providing the force at an eccentricity e from the
centroid.
P Mmax Pe
8
< ft ¼ A þ z z at the top ð11:5Þ
>
>
t t
under Mmax
P Mmax Pe
ð11:6Þ
>
: fb ¼
> þ at the bottom
A zb zb
P Mmin Pe
8
< ft ¼ A þ z z at the top ð11:7Þ
>
>
t t
under Mmin
: fb ¼ P Mmin þ Pe ð11:8Þ
>
> at the bottom
A zb zb
Note that, as the prestressing force lies below the neutral axis, it has the effect of
causing hogging moments in the section.
The critical condition for no tension in the bottom of the beam is again given by
equation 11.6, which becomes
P Mmax Pe
þ ¼0
A zb zb
or
Mmax
P ¼ z ¼ minimum prestress force required for no tension in bottom fibre
b
þe
A
Thus for a given value of prestress force P, the beam may carry a maximum moment of
z
b
Mmax ¼ P þe
A
When compared with Mmax ¼ Pzb =A for an axial prestress force it indicates an
increase in moment carrying capacity of Pe.
The maximum stress in the top of the beam is given by equation 11.5 as
P Mmax Pe
ft ¼ þ
A zt zt
where
Pzb
Mmax ¼ þ Pe
A
B
Figure 11.9
Stresses in member with
eccentric prestress force
e e
P P
B
P/A M/zt Pe/zt ft
+ + =
thus
P Pzb Pe Pe
ft ¼ þ þ
A Azt zt zt
P zb þ zt
¼
A zt
which is the same as that obtained in section 11.3.1 for an axially prestressed member.
Thus the advantages of an eccentric prestress force with respect to the maximum
moment-carrying capacity of a beam are apparent.
If the stress distributions of figure 11.9 are further examined, it can be seen that the
differences in the net stress diagrams for the extreme loading cases are solely due to the
differences between the applied moment terms Mmax and Mmin . It follows that by
increasing the range of the stresses by the use of an eccentric prestress force the range of
applied moments that the beam can carry is also increased. The minimum moment Mmin
that can be resisted is generally governed by the need to avoid tension in the top of the
beam, as indicated in equation 11.7.
In the design of prestressed beams it is important that the minimum moment
condition is not overlooked, especially when straight tendons are employed, as stresses
near the ends of beams where moments are small may often exceed those at sections
nearer mid-span. This feature is illustrated by the results obtained in example 11.1.
EX AM PL E 1 1.1
Calculation of prestress force and stresses
A rectangular beam 300 150 mm is simply supported over a 4 m span, and supports a
live load of 10 kN/m. If a straight tendon is provided at an eccentricity of 65 mm below
the centroid of the section, find the minimum prestress force necessary for no tension
under live load at mid-span. Calculate the corresponding stresses under self-weight only
at mid-span and at the ends of the member.
(a) Beam properties
Self-weight ¼ 0:15 0:3 25 ¼ 1:12 kN/m
Area ¼ 45 103 mm2
bh2 150 3002
Section moduli zt ¼ zb ¼ z ¼ ¼ ¼ 2:25 106 mm3
6 6
(b) Loadings (mid-span)
ð10 þ 1:12Þ 42
Mmax ¼ ¼ 22:2 kN m
8
1:12 42
Mmin ¼ ¼ 2:2 kN m
8
(c) Calculate minimum prestress force
For no tension at the bottom under Mmax
P Mmax Pe
þ ¼0
A z z
where
e ¼ 65 mm
Prestressed concrete 341
hence
Mmax 22:2 106 103
P ¼ z ¼
þe 2:25 106
A þ 65
45 103
¼ 193 kN
The quasi-permanent loads are the permanent and prestressing load, Gk þ Pm; t , plus
a proportion of the characteristic variable imposed load. This proportion is taken as 0.3
for dwellings, offices and stores, 0.6 for parking areas and 0.0 for snow and wind
loading.
If the tensile stress in the concrete is limited to the values of fctm given in table 6.11
then all stresses can be calculated on the assumption that the section is uncracked and
the gross concrete section is resisting bending. If this is not the case then calculations
may have to be based on a cracked section. Limited cracking is permissible depending
on whether the beam is pre- or post-tensioned and the appropriate exposure class.
Generally for prestressed members with bonded tendons crack widths should be limited
to 0.2 mm under the action of the frequent loading combination taken as the permanent
characteristic and prestressing load, Gk þ Pm; t , plus a proportion of the characteristic
variable imposed load as given by equation 2.3 and table 2.4. In some, more aggressive
exposure conditions, the possibility of decompression under the quasi-permanent load
conditions may need to be considered.
At initial transfer of prestress to the concrete, the prestress force will be considerably
higher than the ‘long-term’ value as a result of subsequent losses which are due to a
number of causes including elastic shortening, creep and shrinkage of the concrete
member. Estimation of losses is described in section 11.4.7. Since these losses
commence immediately, the condition at transfer represents a transitory stage in the life
of a member and further consideration should be given to limiting both compressive and
tensile stresses at this stage. In addition, the concrete, at this stage, is usually relatively
immature and not at full strength and hence transfer is a critical stage which should be
considered carefully. The compressive stress at transfer should be limited to 0:6fck
where fck is based on the strength on the concrete at transfer. The tensile stress should be
limited to 1 N/mm2 for sections designed not to be in tension in service. Where limited
flexural stress under service loads is permitted, some limited tensile stress is permitted
at transfer.
The choice of whether to permit cracking to take place or not will depend on a
number of factors which include conditions of exposure and the nature of loading. If a
member consists of precast segments with mortar joints, or if it is essential that cracking
should not occur, then it will be designed to be in compression under all load conditions.
However a more efficient use of materials can be made if the tensile strength of the
concrete, fctm , given in table 6.11 is utilised. Provided these stresses are not exceeded
then the section can be designed, based on the gross uncracked section.
Unless the section is designed to be fully in compression under the characteristic
loads, a minimum amount of bonded reinforcement should be provided to control
cracking. This is calculated in an identical manner to the minimum requirement for
reinforced concrete (see section 6.1.5) with the allowance that a percentage of the
prestressing tendons can be counted towards this minimum area.
The design of prestressing requirements is based on the manipulation of the four
basic expressions given in section 11.3.2 describing the stress distribution across the
Prestressed concrete 343
concrete section. These are used in conjunction with permissible stresses appropriate to
the type of member and covering the following conditions:
1. Initial transfer of prestress force with the associated loading (often just the beam’s
self-weight);
2. At service, after prestress losses, with minimum and maximum characteristic
loading;
3. At service with the quasi-permanent loading.
The loadings must encompass the full range that the member will encounter during its
life, and the minimum values will thus be governed by the construction techniques used.
The partial factors of safety applied to these loads will be those for serviceability limit
state, that is 1.0 for both permanent and variable loads. The quasi-permanent loading
situation is considered with only a proportion of the characteristic variable load acting.
For a beam with a cantilever span or a continuous beam it is necessary to consider the
loading patterns of the live loads at service in order to determine the minimum and
maximum moments. For a single-span, simply supported beam it is usually the
minimum moment at transfer and the maximum moment at service that will govern, as
shown in figure 11.10. From figure 11.10 the governing equations for a single-span
beam are:
At transfer
P0 P0 e Mmin
þ ¼ ft0 fmin
0
ð11:9Þ*
A zt zt
P0 P0 e Mmin
þ ¼ fb0 fmax
0
ð11:10Þ*
A zb zb
At service
KP0 KP0 e Mmax
þ ¼ ft fmax ð11:11Þ*
A zt zt
KP0 KP0 e Mmax
þ ¼ fb fmin ð11:12Þ*
A zb zb
0 0
where fmax , fmin , fmax and fmin are the appropriate permissible stresses at transfer and
serviceability conditions. P0 is the prestressing force at transfer and K is a loss factor
that accounts for the prestress losses – for example, K ¼ 0:8 for 20 per cent loss.
wmin
Figure 11.10
Prestressed beam at transfer
f't > f'min
and service
P0 P0
Transfer
f'b < f'max
wmax
ft < fmax
KP0 KP0
fb > fmin
Service
344 Reinforced Concrete Design
and
Mv
zb 0
ð11:16Þ
ðKfmax fmin Þ
In equations 11.15 and 11.16, for zt and zb it can be assumed with sufficient accuracy,
for preliminary sizing that Mmax will depend on both the imposed and dead (self-weight)
load and Mmin will depend on the dead (self-weight) load only, so that in effect the
calculations for Mv become independent of the self-weight of the beam.
These minimum values of section moduli must be satisfied by the chosen section in
order that a prestress force and eccentricity exist which will permit the stress limits to be
met; but to ensure that practical considerations are met the chosen section must have a
margin above the minimum values calculated above. The equations for minimum
moduli depend on the difference between maximum and minimum values of moment.
The maximum moment on the section has not directly been included in these figures,
thus it is possible that the resulting prestress force may not be economic or practicable.
However, it is found in the majority of cases that if a section is chosen which satisfies
these minimum requirements, coupled with any other specified requirements regarding
the shape of the section, then a satisfactory design is usually possible. The ratio of
acceptable span to depth for a prestressed beam cannot be categorised on the basis of
deflections as easily as for reinforced concrete. In the absence of any other criteria, the
following formulae may be used as a guide and will generally produce reasonably
conservative designs for post-tensioned members.
span
span 36 m h¼ þ 0:1 m
25
span
span > 36 m h¼ m
20
In the case of short-span members it may be possible to use very much greater span–
depth ratios quite satisfactorily, although the resulting prestress forces may become very
high.
Other factors which must be considered at this stage include the slenderness ratio of
beams, where the same criteria apply as for reinforced concrete, and the possibility of
web and flange splitting in flanged members.
Prestressed concrete 345
EXA M PLE 11 .2
Selection of cross-section
Select a rectangular section for a post-tensioned beam to carry, in addition to its own
self-weight, a uniformly distributed load of 3 kN/m over a simply supported span of
10 m. The member is to be designed with a concrete strength class C40/50 and is
restrained against torsion at the ends and at mid-span. Assume 20 per cent loss of
prestress (K ¼ 0:8).
Design concrete stresses
At service:
fmax ¼ 0:6fck ¼ 0:6 40 ¼ 24 N/mm2 ;
fmin ¼ 0:0 N/mm2
At transfer: At this stage, we can assume it to be 0.4 fck
0 (as detailed calculations will be learnt in the
¼ 16 N/mm2 0:6 strength at transfer;
fmax
prestressing losses part)
0
fmin ¼ 1:0 N/mm2
Mv ¼ 3:0 102 =8 ¼ 37:5 kN m * refer to the Attachment 5a
From equations 11.15 and 11.16:
Mv 37:5 106
zt 0 ¼ ¼ 1:50 106 mm3
ðfmax Kfmin Þ ð24 0:8f1gÞ
Mv 37:5 106
zb 0
¼ ¼ 2:93 106 mm3
ðKfmax fmin Þ ð0:8 16 0:0Þ
Take b ¼ 200 mm. Hence
z ¼ 200h2 =6 2:93 106
Therefore
qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
h ð2:93 106 6=200Þ ¼ 297 mm
The minimum depth of beam is therefore 297 mm and to allow a margin in subsequent
detailed design a depth of 350 mm would be appropriate as a first attempt.
To prevent lateral buckling EC2 specifies a maximum span/breadth ratio requirement:
lot 50
with h=b 2:5
b ðh=bÞ1=3
where lot ¼ the distance between torsional restraints = 5.0 m in this example.
lot 5000
Actual ¼ ¼ 25
b 200
lot 50
maximum ¼ ¼ 41:5
b ð350=200Þ1=3
hence the chosen dimensions are satisfactory as an initial estimate of the required beam
size.
346 Reinforced Concrete Design
22 21 Figure 11.11
Mmax Maximum moment and
prestress force relationship
Max. moment
inequalities satisfied
in this zone
P0
Y'
thus
fmax zt þ fmin zb
P0 ¼ z þ z ð11:23Þ
b t
K
A
Thus the value of prestress force P0 ¼ Y 0 may be conveniently considered as a
maximum economic value beyond which any increase in prestress force would be
matched by a diminishing rate of increase in moment-carrying capacity. If a force larger
than this limit is required for a given section it may be more economic to increase the
size of this section.
EXA M PLE 11 .3
EX AM PL E 1 1.4
Stress under quasi-permanent loads
For the previous example, using minimum prestress force of 557 kN, check the stress
condition under the quasi-permanent loading condition. Assume that the 3 kN/m
imposed load consists of a permanent load of 2 kN/m as finishes and 1.0 kN/m variable
load. Take 30 per cent of the variable load contributing to the quasi-permanent load.
From the previous example:
Moment due to self-weight ¼ 21:9 kN m
Moment due to finishes ¼ 2 102 =8
¼ 25:0 kN m
Moment due to variable load ¼ 1 102 =8
¼ 12:5 kN m
Quasi-permanent moment ¼ 21:9 þ 25:0 þ ð0:3 12:5Þ
¼ 50:65 kN m
Prestressed concrete 349
These equations now express linear relationships between 1=P0 and e. Note that in
equation 11.25 the sense of the inequality has been reversed to account for the fact that
0
the denominator is negative (fmin is negative according to the chosen sign convention).
The relationships can be plotted as shown in figure 11.12(a) and (b) and the area of the
graph to one side of each line, as defined by the inequality, can be eliminated, resulting
in an area of graph within which any combination of force and eccentricity will
simultaneously satisfy all four inequalities and hence will provide a satisfactory design.
The lines marked 1 to 4 correspond to equations 11.24 to 11.27 respectively. This form
of construction is known as a Magnel Diagram.
The additional line (5) shown on the diagram corresponds to a possible physical
limitation of the maximum eccentricity allowing for the overall depth of section, cover
to the prestressing tendons, provision of shear links and so on. Two separate figures are
shown as it is possible for line 1, derived from equation 11.24, to have either a positive
or a negative slope depending on whether fmax is greater or less than Mmax =zt .
350 Reinforced Concrete Design
1 1 1
Figure 11.12 5 5
P0 3 P0 3
Magnel diagram 1 2 2
construction
4 4
e e
zb/A zt/A zb/A zt/A
(a) (b)
The Magnel diagram is a powerful design tool as it covers all possible solutions of the
inequality equations and enables a range of prestress force and eccentricity values to be
investigated. Values of minimum and maximum prestress force can be readily read from
the diagram as can intermediate values where the range of possible eccentricities for a
chosen force can be easily determined. The diagram also shows that the minimum
prestress force (largest value of 1=P0 ) corresponds to the maximum eccentricity, and as
the eccentricity is reduced the prestress force must be increased to compensate.
EX AM PL E 1 1.5
Construction of Magnel diagram
Construct the Magnel diagram for the beam given in example 11.2 and determine the
minimum and maximum possible values of prestress force. Assume a maximum possible
eccentricity of 125 mm allowing for cover etc. to the tendons.
From the previous examples:
0
fmax ¼ 16 N/mm2 fmax ¼ 24 N/mm2
0
fmin ¼ 1:0 N/mm2 fmin ¼ 0:0 N/mm2
Mmin ¼ 21:9 kN m Mmax ¼ 59:4 kN m
K ¼ 0:8 zb ¼ zt ¼ 4:08 106 mm3
A ¼ 70 000 mm2
106
1210 20:77e
P0
Prestressed concrete 351
and similarly from the other three inequalities, equations 11.25 to 11.27:
106
2243 þ 38:50e
P0
106
785 þ 13:5e
P0
106
669 þ 11:5e
P0
These inequalities are plotted on the Magnel diagram in figure 11.13 and the zone
bounded by the four lines defines an area in which all possible design solutions lie. The
line of maximum possible eccentricity is also plotted but, as it lies outside the zone
bounded by the four inequalities, does not place any restriction on the possible solutions.
From figure 11.13 it can be seen that the maximum and minimum values of prestress
force are given by:
Maximum 106 =P0 ¼ 2415; hence minimum P0 ¼ 414 kN (e ¼ 121 mm)
Minimum 106 =P0 ¼ 862; hence maximum P0 ¼ 1160 kN (e ¼ 17 mm)
The intersection of the two lines at position A on the diagram corresponds to a value
of P0 ¼ 1050 kN, established in example 11.3 as the maximum economical value of
prestress force for this section (see equation 11.23). Hence the intersection of these two
lines should be taken as the maximum prestress force and, as can be seen, this
information can be readily determined from the diagram without the need for further
calculation.
The Magnel diagram can now be used to investigate other possible solutions for the
design prestressing force and eccentricity. For a fixed value of prestress force (and hence
fixed value of 1=P0 ) the corresponding range of permissible eccentricity can be read
directly from the diagram. Alternatively, if the eccentricity is fixed, the diagram can be
used to investigate the range of possible prestress force for the given eccentricity.
Figure 11.13
106 2500
Minimum P0 = 414kN Magnel diagram for
P0
Permissible zone
example 11.5
.26
11
on
2000 u ati
Eq
1500 P0 = 700kN
.25
11
Maximum P0 = 1160kN
n
tio
ua
1000 A
Eq
Maximum economic
e = 48
e = 66
Eq
emax = 125
prestress force
ua
e = 121
tio
e = 17
500
11
.27
.2
1
4
n1
tio
ua
Eq e
At service
zt fmax zt Mmax
e þ ð11:30Þ
A KP0 KP0
zb fmin zb Mmax
e þ þ ð11:31Þ
A KP0 KP0
zb fminzb
Figure 11.14 – +
A KP0
Cable zone limits
Equation 31
zt f'minzt
+ –
A P0 Mmin
P0
Prestressed concrete 353
EXA M PLE 11 .6
concrete with particular reference to the maturity at the time of stressing. In pre-
tensioning, where the concrete is usually relatively immature at transfer, these losses
may therefore be expected to be higher than in post-tensioning.
In addition to losses from these causes, which will generally total between 20 and
30 per cent of the initial prestress force at transfer, further losses occur in post-tensioned
concrete during the stressing procedure. These are due to friction between the strands
and the duct, especially where curved profiles are used, and to mechanical anchorage
slip during the stressing operation. Both these factors depend on the actual system of
ducts, anchorages and stressing equipment that are used.
Thus although the basic losses are generally highest in pre-tensioned members, in
some instances overall losses in post-tensioned members may be of similar magnitude.
Elastic shortening
The concrete will immediately shorten elastically when subjected to compression, and
the steel will generally shorten by a similar amount (as in pre-tensioning) with a
corresponding loss of prestress force. To calculate this it is necessary to obtain the
compressive strain at the level of the steel.
If the transfer force is P0 and the force after elastic losses is P0 then
P0 ¼ P0 loss in force
and the corresponding stress in the concrete at the level of the tendon
P0 ðP0 eÞ e
cp ¼ þ þ cg
A I
where cg is the stress due to self-weight which will be relatively small when averaged
over the length of the member and may thus be neglected. Hence
P0 e2 A
cp ¼ 1þ
A I
and concrete strain ¼ cp =Ecm , thus reduction in steel strain ¼ cp =Ecm and
cp
reduction in steel stress ¼ Es ¼ e cp
Ecm
thus with Ap ¼ area of tendons
loss in prestress force ¼ e cp Ap
e2 A
Ap 0
¼ e P 1 þ
A I
hence
e2 A
Ap 0
P 0 ¼ P0 e P 1 þ
A I
so that
P0
remaining prestress force P0 ¼
e2 A
Ap
1þ e 1þ
A I
In pre-tensioned construction this full loss will be present; however when post-
tensioning the effect will only apply to previously tensioned cables and although a
356 Reinforced Concrete Design
Creep of concrete
The sustained compressive stress on the concrete will also cause a long-term shortening
due to creep, which will similarly reduce the prestress force. As above, it is the stress in
the concrete at the level of the steel which is important, that is
P0 e2 A
cp ¼ 1þ
A I
and
loss of steel stress ¼ Es cp specific creep strain
then
e2 A
Ap 0
loss of prestress force ¼ Es P 1þ specific creep strain
A I
The value of specific creep used in this calculation will be influenced by the factors
discussed in section 6.3.2, and may be obtained from the values of the final creep
coefficient ð1, t0 Þ given in table 6.12 in chapter 6 using the relationship
ð1, t0 Þ
Specific creep strain ¼ N/mm2
1:05Ecm
Table 6.12 may be used where the concrete stress does not exceed 0:45fck at transfer,
where fck relates to the concrete strength at transfer.
Relaxation of steel
Despite developments in prestressing steel manufacture, relaxation of the wire or strand
under sustained tension may still be expected to be a significant factor. The precise
value will depend upon whether pre-tensioning or post-tensioning is used and the
characteristics of the steel type. Equations allowing for method of construction are given
in EC2 section 3.3.2(7) which should be applied to 1000-hour relaxation values
provided by the manufacturer. The amount of relaxation will also depend upon the
initial tendon load relative to its breaking load. In most practical situations the transfer
steel stress is about 70 per cent of the characteristic strength and relaxation losses are
likely to be approximately 4–10 per cent of the tendon load remaining after transfer.
Shrinkage of concrete
This is based on empirical figures for shrinkage/unit length of concrete ("cs ) for
particular curing conditions and transfer maturity as discussed in chapter 6. Typical
values range from 230 106 for UK outdoor exposure (80% relative humidity) to
Prestressed concrete 357
550 106 for indoor exposure, (50% relative humidity), depending on the notional
size of the member. See table 6.13.
The loss in steel stress is thus given by "cs Es , hence
loss in prestress force ¼ "cs Es Ap
EX AM PL E 1 1.7
Estimation of prestress losses at mid-span
A post-tensioned beam shown in figure 11.15 is stressed by two tendons with a parabolic
profile and having a total cross-sectional area Ap ¼ 7500 mm2. The total initial prestress
force is P0 ¼ 10 500 kN and the total characteristic strength is Ppk ¼ 14000 kN.
Figure 11.15
1800
Post-tensioned beam Centroidal axis
e=0
θ ec = 640
30m 1200
P0
P0 ¼
7:5 103 6
2 1:05 10
1 þ 0:5 6:41 1 þ 427
1:05 106 0:36 1012
¼ 0:966P0 ¼ 10 143 kN
Loss P ¼ 10 500 10 143 ¼ 357 kN ¼ 3:4 per cent
Total short-term losses ¼ 460 þ 357 ¼ 817 kN
P0 ¼ P0 short-term losses
¼ 10 500 817 ¼ 9683 kN
(3) Creep
Es A p A
Loss P ¼ 1 þ e 2 P0
ð1:05Ecm ÞA I
205 103 7:5 103 6
2 1:05 10
¼ 1:6 1 þ 427 9683
ð1:05 32Þ 103 1:05 106 0:36 1012
¼ 1034 kN ( ¼ 9:8 per cent of P0 )
(4) Shrinkage
Loss P ¼ "cs Es Ap
¼ 330 106 205 7:5 103
¼ 507 kN ( ¼ 4:8 per cent of P0 )
(5) Relaxation
Long-term relaxation loss factor ¼ 2:5 for class 2 strand estimated from equation 3.29
of EC2
loss P ¼ ð2:5 2:5=100ÞP0 ¼ 0:0625 9683
¼ 605 kN ( ¼ 5:8 per cent of P0 )
Total estimated losses ¼ 817 þ 1034 þ 507 þ 605 ¼ 2963 kN
¼ 28 per cent of P0
Figure 11.16
P P
Parabolic tendon profile
ex ec
L/2
Prestressed concrete 361
P P
Figure 11.17
Parabolic tendon profile
e0 eccentric at ends of beam
e'c
x
L/2
If the prestress force does not lie at the centroid of the section at the ends of the beam,
but at an eccentricity e0 as shown in figure 11.17, the expression for deflection must be
modified. It can be shown that the deflection is the same as that caused by a force P
acting at a constant eccentricity e0 throughout the length of the member, plus a force P
following a parabolic profile with mid-span eccentricity e0c as shown in figure 11.17.
The mid-span deflection thus becomes
where the value of ð1, t0 Þ, the creep coefficient can be obtained from table 6.12
It can be shown in some instances that when net upward deflections occur, these often
increase because of creep, thus the most critical downward deflection may well be
before creep losses occur, while the most critical upward deflection may be long-term.
This further complicates a procedure which already has many uncertainties as discussed
in chapter 6; thus deflections must always be regarded as estimates only.
362 Reinforced Concrete Design
EX AM PL E 1 1.8
Calculation of deflection
Estimate transfer and long-term deflections for a 200 350 mm beam of 10 m span. The
prestressing tendon has a parabolic profile with mid-span eccentricity ¼ 75 mm and the
end eccentricity ¼ 0 at both ends. The initial prestress force at transfer, P0 , is 560 kN
and there are 20 per cent losses. The imposed load consists of 2.0 kN/m finishes and
1.0 kN/m variable load. Ecm ¼ 35 kN/mm2 and the creep factor ð1, t0 Þ ¼ 2:0.
Self-weight ¼ 0:2 0:35 25 ¼ 1:75 kN/m
bh3 200 3503
I¼ ¼ ¼ 715 106 mm4
12 12
(a) At transfer
5 wmin L4 5 ðP0 ec ÞL2
Deflection ya ¼
384 Ecm I 48 Ecm I
5 1:75 104 1012 5 560 103 75 102 106
¼ 3 6
384 35 10 715 10 48 35 103 715 106
¼ 9:1 17:5
¼ 8 mm (upwards)
Figure 11.18
Stress distribution in end
blocks
0.5P
Figure 11.19
Ac1 P Bursting tensile force in
.60
0.33P
0 end blocks
P 33.70°
Ac0
0.6
Ac 0P
0.5P
(a) Anchorage zone (b) Strut and tie model
(end view) of load dispersion
364 Reinforced Concrete Design
force. EC2 suggests that in determining the geometry of this truss the prestressing force
can be assumed to disperse at an angle of 33.78 to the longitudinal axis of the beam as
shown in figure
11.19(b).
The compressive stresses in the assumed struts should not
fck
exceed 0:4 1 fck and the reinforcement is designed to act at a design strength of
250
0:87fyk . However if the stress in the reinforcement is limited to 300 N/mm2 then no
checks on crack widths are necessary. This reinforcement, in the form of closed links, is
then distributed over a length of the end-block equal to the greater lateral dimension of
the block, this length being the length over which it is assumed that the lateral tensile
stresses are acting.
EX AM PL E 1 1.9
Design of end block reinforcement
The beam in figure 11.20 is stressed by four identical 100 mm diameter conical
anchorages located as shown, with a jacking force of 250 kN applied to each. The area
may be subdivided into four equal end zones of 200 150 mm each. Determine the
reinforcement required around the anchorages: fck ¼ 40 N/mm2 , fyk ¼ 500 N/mm2 .
Consider one anchor.
150
Figure 11.20
End block reinforcement
example
200
200
400
200
1000kN
100
400
(a) (b)
End section: four anchorages Area for combined anchorage
Prestressed concrete 365
(b) Reinforcement
From figure 11.19b, the tensile force in the tie of the equivalent truss is given by
T ¼ 0:33 1:2 250 ¼ 100 kN
Area of tensile steel required (assuming stress in the steel is limited to 300 N/mm2)
100 103
As ¼
300
¼ 330 mm2
This can be provided by three 10 mm closed links (471 mm2) around each anchor
at, say, 50, 125 and 200 mm from the end face; that is, distributed over a length
equal to the largest dimension of the anchorage block (200 mm). Note that in each
direction there are two legs of each link acting to resist the tensile force.
(c) Check compressive stress in the struts
Allowable compressive stress ¼ 0:4ð1 fck =250Þfck
¼ 0:4ð1 40=250Þ40 ¼ 13:44 N/mm2
Force in strut
Actual stress in strut ¼
Cross-sectional area
0:60 1:2 250 103
¼
ð200 150 cos 33:7degÞ
¼ 7:21 N/mm2
The effect of the combined anchorage can be considered by considering the total
prestress force of 1000 kN acting on an effective end block of 400 400 mm.
The tensile force in the tie of the equivalent truss is given by
T ¼ 0:33 1:2 1000 ¼ 400 kN
Area of tensile steel required
400 103
As ¼
300
¼ 1333 mm2
This can be provided by six 12 mm closed links (1358 mm2) enclosing all four anchors
distributed over a length equal to the largest dimension of the anchorage block, that is,
400 mm.
fp0,1k
Figure 11.21
γm
Stress-strain curve for
prestressing steel
Stress N/mm2
205kN/mm2
Strain
EX AM PL E 1 1.1 0
Calculation of ultimate moment of resistance
The section of a pretensioned beam shown in figure 11.22 is stressed by ten 5 mm wires
of 0.1% proof stress fp0; 1k ¼ 1600 N/mm2 . If these wires are initially stressed to
1120 N/mm2 and 30 per cent losses are anticipated, estimate the ultimate moment of
resistance of the section if class C35/45 concrete is used. The stress–strain curve for
prestressing wire is shown in figure 11.23.
Area of 5 mm wire ¼ 52 =4 ¼ 19:6 mm2
Stress in steel after losses ¼ p 1120 0:7 ¼ 0:9 1120 0:7 ¼ 705 N/mm2
therefore
fs 705
Strain in steel after losses ¼ ¼ ¼ 0:0034
Es 205 103
which is less than "y , the yield strain.
Prestressed concrete 367
x 0.8x
Fc
neutral
axis z
300 εsa
100
Fs
25
εsb
fp0,1k 1600
= = 1390 Figure 11.23
γm 1.15 Stress–strain curve for
1390
prestressing wire
Stress N/mm2
205kN/mm2
0.00678 Strain
A depth x of neutral axis must be found for which the compressive force Fc in the
concrete is balanced by the tensile force Fs in the steel. Then the ultimate moment of
resistance is given by
Mu ¼ Fc z ¼ Fs z ð11:33Þ
where z is the lever arm between Fc and Fs .
As a first attempt try x ¼ 130 mm, approximately equal to 0:5d.
Bottom layer
"sb ¼ 0:0034 þ "0sb
ð275 xÞ
¼ 0:0034 þ "cc ð11:35Þ
x
ð275 130Þ
¼ 0:0034 þ 0:0035
130
¼ 0:0073
Table 11.1
In terms of the tensile force in the steel, the ultimate moment of resistance of the
section is given by
X
Mu ¼ Fs z ¼ ½fs As ðd 0:4xÞ ð11:39Þ
¼ 5 19:6½1000ð175 0:4 123Þ þ 1390ð275 0:4 123Þ
¼ 43:1 106 N mm
If x had been incorrectly chosen as 130 mm then using equation 11.39 Mu would equal
42.0 kN m, or in terms of the concrete
Mu ¼ 0:567fck b 0:8xz
0:567 35 120 0:8 130ð225 0:4 130Þ 106
43 kN m
Comparing the average of these two values of Mu (¼ 42:5 kN m) with the correct
answer, it can be seen that a slight error in the position of the neutral axis does not have
any significant effect on the calculated moment of resistance.
EXA M P LE 11 .1 1
x 0.8x
Fc
neutral
245
275
axis z
εsa
2H10
Fs
εsb
hence
ultimate moment of resistance ¼ 253 123 103 ¼ 31:1 kN m
Untensioned steel is therefore required to permit the beam to support an ultimate
moment of 40 kNm.
Additional moment capacity to be provided ¼ 40 31:1 ¼ 8:9 kN m
Effective depth of additional steel ¼ 245 mm
then
lever arm to additional steel 220 mm
and
8900
additional tension force required ¼ ¼ 40:5 kN
220
thus
estimated area of untensioned steel required at its yield stress
40 500
¼ ¼ 93 mm2
0:87 500
Try two 10 mm diameter bars (157 mm2).
(b) Check steel strain
If additional steel has yielded, force in two H10 bars ¼ 157 500 103 =1:15
¼ 68:3 kN, therefore
total tensile force if all the steel has yielded ¼ 123 þ 68:3
¼ 191:3 kN
thus
191:3 103
depth of neutral axis at ultimate ¼
0:567 40 120 0:8
¼ 88 mm
Therefore
275 88
prestressing steel strain "sb ¼ 0:0035 þ 0:0034
88
¼ 0:0108 ( > yield)
Prestressed concrete 371
and
245 88
untensioned steel strain "sa ¼ 0:0035
88
¼ 0:0062
This value is greater than the yield strain of 0.00217 from section 4.1.2.
(c) Check ultimate moment of resistance
Taking moments about the centre of compression
Mu ¼ 123ð275 0:40xÞ þ 68:3ð245 0:40xÞ
¼ ½123ð275 0:40 88Þ þ 68:3ð245 0:40 88Þ103
¼ 43:8 kN m
If it had been found in (b) that either the prestressing steel or untensioned steel had not
yielded, then a trial and error approach similar to example 11.10 would have been
necessary.
11.5.3 Shear
Shear in prestressed concrete is considered at the ultimate limit state. Design for shear
therefore involves the most severe loading conditions, with the usual partial factors of
safety being applied to the actions for the ultimate limit state being considered.
The response of a member in resisting shear is similar to that for reinforced concrete,
but with the additional effects of the compression due to the prestressing force. This will
increase the shear resistance considerably and this is taken into account in EC2 by
enhancing the equation for the shear capacity (VRd; c ) of the section without shear
reinforcement. With a few slight modifications, the Code gives an almost identical
approach, based on the Variable Strut Inclination Method of shear design, in prestressed
sections as is used in reinforced concrete sections as outlined in Chapter 5.
In calculating the design shear force, VEd , it is permissible to take into account the
vertical component of force in any inclined tendons which will tend to act in a direction
that resists shear, thus enhancing the shear capacity of the section. In such a case the
prestressing force should be multiplied by the partial factor of safety, p ¼ 0:9.
where:
VRd; c ¼ the design shear resistance of the section without shear reinforcement
rffiffiffiffiffiffiffiffi!
200
k ¼ 1þ 2:0 with d expressed in mm
d
As1
1 ¼ 0:02
bw d
As1 ¼ the area of tensile reinforcement that extends beyond the section being
considered by at least a full anchorage length plus one effective depth (d)
bw ¼ the smallest width of the section in the tensile area (mm)
cp ¼ axial stress in section due to prestress ( p KP0 =A) ( < 0:133fck )
It can be seen that equations 11.40 and 11.41 are practically identical to equations 5.1
and 5.2 for shear in reinforced concrete sections. The additional term of 0:15cp
indicates that the effect of the prestress is to enhance the shear capacity of the section by
15% of the longitudinal stress due to prestressing.
For the special case of a single span beam, in regions which are uncracked in bending
(i.e where sagging moments are relatively small near to the supports), the shear strength
of the concrete section could be governed by the development of excessive tensile
stresses in the concrete. These regions are defined as where the flexural tensile stress in
the uncracked section does not exceed fctk = c , where fctk is the characteristic axial
tensile strength of the concrete. The applicable equations in EC2 can be developed as
follows.
vco At an uncracked section, a Mohr’s circle analysis of a beam element shown in
fc fc
figure 11.25 which is subject to a longitudinal compressive stress, fc and a shear stress
vco gives the principal tensile stress as:
vco v" ffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
u 2 #
u fc fc
Figure 11.25 ft ¼ t þv2co
Stress in uncracked section 2 2
The actual shear stress at any level of a beam subject to a shear force, V , can be
shown to be:
V ðAyÞ vco bI
vco ¼ or V ¼
bI ðAyÞ
where Ay is the first moment of area of the part of the section above the level considered
about the centroidal axis of the beam, as shown in figure 11.26, b is the breadth of the
section at the level considered and I is the second moment of area of the whole section
about its centroidal axis.
Prestressed concrete 373
A
Figure 11.26
Shear stress distribution
y
centroidal
axis
b
Hence if fctd is the limiting value of principal tensile stress, the ultimate shear
resistance VRd; c of the uncracked section becomes:
bI
qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
VRd; c ¼ 2 þf f Þ
ðfctd c ctd
Ay
This equation forms the basis of the design equation given in EC2 which is
expressed as:
bw I
qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
VRd; c ¼ 2 þ
ðfctd 1 cp fctd Þ ð11:42Þ
Ay
where:
EC2 states that, for the special case of a simply supported beam, equation 11.42
should be used in those regions where the flexural tensile stress in the uncracked section
does not exceed fctk = c and where the beam is cracked in bending equation 11.40 should
be used. Determining where the beam is uncracked at the ultimate limit state is not
straight-forward and, in practice, both these equations should be applied at each section
considered and the lowest of the two values calculated then taken as the shear capacity
of the section.
The variable strut inclination method for sections that do require shear
reinforcement
As previously noted the design for shear and the provision of shear reinforcement in
prestressed concrete is practically identical to that for reinforced concrete and is
summarised below.
compressive struts of the assumed truss, leading possibly to compressive failure of the
concrete. The maximum shear force is given by:
cw bw zv1 fck
VRd; max ¼
½1:5ðcot þ tan Þ
where v1 ¼ 0:6ð1 fck =250Þ. As for reinforced concrete, we will take z ¼ 0:9d.
According to EC2 this approximation for z is strictly only applicable to reinforced
concrete but to calculate z at each section where shear is being considered is a tedious
process and the consequential effects on the shear calculations are likely to be small. In
this text we have therefore adopted the approximation that z ¼ 0:9d but for complex
loading or heavily loaded situations it may be necessary to calculate the variation of z
throughout the beam. Hence:
cw bw 0:9d0:6ð1 fck =250Þfck
VRd; max
½1:5ðcot þ tan Þ
ð11:43Þ
cw 0:36bw dð1 fck =250Þfck
½cot þ tan
This equation is practically identical to equation 5.4 in Chapter 5 except that it
includes a coefficient cw given by:
cw ¼ 1 þ 1:5cp =fck for 0 < cp 0:167fck
cw ¼ 1:25 for 0:167fck < cp 0:333fck
cw ¼ 2:5ð1 1:5cp =fck Þ for 0:333fck < cp < 0:667fck
where cp ¼ the mean compressive stress, taken as positive, in the concrete due to the
prestress force.
For the two limiting values of cot comparison with equations 5.6 and 5.7 gives:
with cot ¼ 2:5: VRd; maxð22Þ ¼ cw 0:124bw dð1 fck =250Þfck ð11:44Þ
and with cot ¼ 1:0: VRd; maxð45Þ ¼ cw 0:18bw dð1 fck =250Þfck ð11:45Þ
and for values of that lie between these two limiting values the required value of can
be obtained by equating VEd to VRd; max . Thus the equation, analogous to equation 5.8,
for the calculation of is as follows:
VEd
¼ 0:5 sin1 458 ð11:46aÞ*
cw 0:18bw dð1 fck =250Þfck
where VEf is the shear force at the section being considered and the calculated value of
the angle can then be used to determine cot and to calculate the shear reinforcement
Asw =s at that section from equation 11.47 below (when 228 < < 458).
If the web of the section contains grouted ducts with diameter greater than one-eighth
of the web thickness, in the calculation of VRd; max , the web thickness should be reduced
by one-half of the sum of the duct diameters measured at the most unfavourable section
of the web. For non-grouted ducts, grouted plastic ducts and unbonded tendons the web
thickness should be reduced by 1.2 times the sum of the duct diameters. If the design
shear force exceeds VRd; max then it will be necessary to increase the size of the section.
Prestressed concrete 375
To provide for this force untensioned longitudinal reinforcement of area Asl , working at
its full design strength, must be provided to ensure that this force is developed and/or
the profile of the prestressing tendons may be adjusted to provide greater resistance to
the design shear force.
EX AM PL E 1 1.1 2
Design of shear reinforcement
The beam cross-section shown in figure 11.27 is constant over a 30 m simply supported
span with a parabolic tendon profile and an eccentricity varying between 300 mm at the
ends and 750 mm at mid-span, measured below the neutral axis in both cases. The beam
supports an ultimate uniformly distributed load of 40 kN/m and fck ¼ 35 N/mm2 .
Given data:
Prestress force after losses ¼ 2590 kN
I ¼ 145 106 106 mm4
A ¼ 500 103 mm2
Ap ¼ 3450 mm2 ( ¼ As1 )
fyk ¼ 500 N/mm2 for the shear links
fctk ¼ 2:2 N/mm2
The calculations will be presented for a section at the support and then repeated and
tabulated at 3 m intervals along the span.
Prestressed concrete 377
1000
Figure 11.27
Shear reinforcement example
centroidal
axis
1500
300
850
location of tendons
at the supports
where:
d ¼ 1:5 0:85 þ e ¼ 1:5 0:85 þ 0:3 ¼ 0:95 m at the support
rffiffiffiffiffiffiffiffi! rffiffiffiffiffiffiffiffi!
200 200
k ¼ 1þ ¼ 1þ ¼ 1:46 ( 2:0)
d 950
As1 3450
1 ¼ ¼ ¼ 0:0242 ( > 0:02) ; 1 ¼ 0:02
bw d 150 950
cp ¼ cp KP0 =A ¼ 0:9 2590 103 =ð500 103 Þ
¼ 4:66 N/mm2 f 0:133fck ¼ 0:133 35 ¼ 4:66 OKg
Hence:
h i
VRd; c ¼ 0:12kð1001 fck Þ1=3 þ 0:15cp bw d
h i
¼ 0:12 1:46ð100 0:02 35Þ1=3 þ 0:15 4:66 150 950 103
¼ 202 kN
Note: a check on equation 11.41 will show that the minimum value of VRd; c as given by
equation 11.41 is not critical in this case.
As this is a simply supported beam equation 11.42 should also be used to check the
shear capacity of the concrete section. From equation 11.42:
bw I
qffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffiffi
VRd; c ¼ 2 þ
ðfctd 1 cp fctd Þ
Ay
378 Reinforced Concrete Design
where:
cp ¼ axial stress in section due to prestress ¼ 4:66 N/mm2 , as before
fctd ¼ the design tensile strength of the concrete ¼ 2:2=1:5 ¼ 1:47 N/mm2
1 ¼ 1 for post-tensioned tendons.
Hence:
cp 4:66
¼ ¼ 0:133 ( < 0:167)
fck 35
cp
; cw ¼ 1 þ 1:5 ¼ 1 þ 1:5 0:133 ¼ 1:200
fck
; VRd; maxð22Þ ¼ cw 0:124bw dð1 fck =250Þfck
35
¼ 1:200 0:124 150 950 1 35 103 ¼ 638 kN
250
As the shear force at the end of the beam is 600 kN then the upper limit to the shear force
is not exceeded.
(4) Calculate the area and spacing of links
Where the shear force exceeds the capacity of the concrete section, allowing for the
enhancement from the inclined tendon force, shear reinforcement must be provide to
resist the net shear force taking into account the beneficial effect of the inclined tendons.
From equation 11.48 this is given by:
Asw VEd ð600 0:9 155Þ 103
¼ ¼ ¼ 0:497
s 1:95dfyk 1:95 950 500
1 Equation 11.40.
2 Equation 11.44.
Support
400
3 6 9 12 15
Distance along span (m)