NE200 User Manual
NE200 User Manual
NE200 User Manual
1. Unpacking Inspection
Thank you for choosing our latest NE200 sensorless vector control type frequency
inverter Upon unpacking, please confirm the following: Any damage occurred during
transportation; Check whether the model and specifications on the nameplate of
inverter are in accordance with your order.If there is any error, please contact us or
distributors.
Please read this manual thoroughly before using to make sure our inverter working at
best condition.
NE200- 2 S 0015 G
Abbreviation Code Inverter type
380V 4
Code Power rate
3. Dimensions
NE200-2S0002G
NE200-2S 0004G
162 85 113 144 74 φ5
NE200-2S 0007G
NE200-2S 0015G
NE200 User Manual
4. Specifications
Items Specifications
Rated Single phase220V, three phase 200V, three phase
Input voltage/Frequency 380V;50Hz/60Hz
Range Voltage: ±20% voltage unbalance rate:<3%; frequency: ±5%
Rated voltage 0~200V/220V/380V
Frequency range 0Hz~500Hz(standard)
Output Frequency
0.01Hz
resolution
Overload ability 150% rated current for1minute, 180% rated current for3 seconds
Modulation modes Optimized space voltage vector SVPWM modulation
Sensorless vector control (with optimal low frequency dead time
Control mode
compensation)
Frequency Digital setting: The highest frequency×± 0.01% Analog setting:
precision The highest frequency ×±0.2%
Frequency Digital setting: 0.01Hz; Analog setting: The highest frequency×
resolution 0.1%
Start frequency 0.40Hz~20.00Hz
Torque boost Auto torque boost, manual torque boost 0.1%~30.0%
Five ways: constant torque V/F curve, 1 kind of user defined
Control function
Items Specifications
Auto energy
Saving energy by auto optimizing V/F curve according to the load
saving running
Auto current
Auto current limiting to prevent frequent over current fault trip
limiting
Multi pump
When connect with Yuanshin water supply kit can offer
constant water
multi-pump constant water pressure supply
pressure supply
RS485 standard communication port available, support
Communication MODBUS communication protocol of ASCII and RTU,
master-slave multi-machine interaction function available
Running
Control panel : control terminal :serial port :3 channels
command
switchable
channel
Control panel potentiometer : ▲、▼control panel keys:;function
Frequency code digital: serial port : terminal up/down:
setting channel analog voltage: analog current: pulse:
combination setting: all channels switchable
Runni
Switch input FWD/REV command: 8channels programmable switch inputs,
ng
channel 35kinds of function can be set separately
functi
Analog input 4~20mA(220V Model ): 0-10V:
on
channel 2 optional analog inputs for 380V Model
LED digital
Display setting frequency, output voltage, output current, etc.
display
Control panel
External meter
Display output frequency, output current, output voltage, etc.
display
Key lock All the keys can be locked
Function code parameters are able to be copied between
Parameter copy
inverters when use remote control panel
Overcurrent
Protection function protection:overvoltageprotection:undervoltageprotection:overhea
ting protection: overload protection, etc.
Indoors, free from direct sunlight, dust, corrosive gas, oil mist,
Environment
Environment
steam, water dropper salt, etc
Altitude Lower than 1000m (derating is necessary above 1000m)
Ambient
-10℃~+50℃
temperature
NE200 User Manual
Items Specifications
Humidity <90%RH, no condensation
Vibration Lower than 5.9m/s (0.6g)
Storage
-20℃~+60℃
temperature
Struct Protection level IP20(In the selection of state display unit or the keyboard state)
ure Cooling Forced air cooling
Installation Wall mounted
5. Wire Connection
◆ Before wiring, please ensure the power has been removed and
be wait for at least 10minutes.
◆ Please use twisted wire or shielded wire above 0.75mm for the
wiring of relay input/output loop (X1~X6, FWD, REV, OC,
DO).One end of shielding layer suspended, and the other side
connected to PE grounding terminal of inverter, wiring length
less than 50m .
◆ The cover can be removed only when the power is switched off,
all the LEDs on the panel are off and waiting at least for 10
minutes.
6. Installation
◆ Be away from the location full of dust or metal powder, and mount in the
location free of direct sunlight.
◆ Please try to keep the inverter away from EMI source and other electronic
devices which are sensitive to EMI.
◆ When several inverters are installed in one cabinet, they should be mounted in
parallel with special incoming and out coming ventilation and special fans.
When two inverters are mounted up and down, an air flow diverting plate should
be fixed as shown in Fig.3-2 to ensure good heat dissipation.
485+
nication
Forward
Operation
FWD
running Couple isolated input
Refer to chapter 6.5 P4.08
Reverse Input resistance:2KΩ
REV
running
Multifunction Optical coupling
X1 al input isolation, compatible
Multifunctional input
Fig. 8-01
NE200-2S0002G(220V) NE200-2S0004G(220V)
NE200-2S0007G(220V) NE200-2S0015G(220V)
NE200 User Manual
9. Keypad introduce
9.1 Keypad interface
The operation panel and control terminals of the inverter can control the starting, speed
regulation, shutdown, braking, operating parameter setting and peripheral equipment of the
motor. The operation panel is shown in Figure 9-1.
Name Description
When the light is on, the inverter is in the running state; when the light
RUN
is off, the inverter is in the stop state.
Indicates that the inverter is in
○ LOCAL/REMOT:Light off
Status the stop state
light ○ LOCAL/REMOT:Twinkling Indicates the communication
LOCAL
start and stop control mode
○ LOCAL/REMOT:Constant on Indicates the terminal start and
stop control mode
NE200 User Manual
Name Description
Hz Frequency unit
Unit
indicator A Current unit
V Voltage unit
Name Description
There are 4 LED digital tubes on the operation panel of the inverter, which
display various monitoring data such as setting frequency, output frequency
and alarm codes.
Digital Corresponding Digital Corresponding Digital Corresponding
Display Letter Display Letter Display Letter
0 0 1 1 2 2
3 3 4 4 5 5
Digital
6 6 7 7 8 8
Display Area
9 9 A a b b
C C d d E E
F F H F I I
L L N N N n
o o P P r r
S S t t U U
u v . . - -
Turn left = decrement,turn right = increment .
Digital
Press potentiometer= button.
Potentiometer
NE200 User Manual
Name Description
“○”: The parameter can be modified when the AC drive is in either stop or running state. “×”: The
parameter can not be modified when the AC drive is in the running state.
“* ”: The parameter is factory parameter and can not be modified.
0: VI+CI
1: VI-CI
2:External pulse given+VI+control
panel▲、▼key given
3:External pulse given-VI-control
Freq. control panel▲、▼key given
P3.00 channel 4:External pulse given+CI 1 0 ×
combination 5:External pulse given-CI
6:RS485 given+VI+control panel▲、
▼key given
7:RS485 given-VI-control panel▲、
▼key given
8:RS485 given+CI+control panel▲、
NE200 User Manual
0:Idle terminal
1:Multi-stage speed control terminal 1
Input terminal X1
P4.00 2:Multi-stage speed control terminal 2 1 0 ×
function selection
3:Multi-stage speed control terminal 3
4:External FWD JOG control input
NE200 User Manual
PID Feedback
P7.16 disconnected 0~Upper limit freq 0.01Hz 0.00Hz ○
detection threshold
PID Feedback
P7.17 disconnected action 0~3 1 0 ○
selection
PID Feedback
P7.18 disconnected 0.01~5.00s 0.01s 1.00s ○
operation delay time
0.001M 0.001Mp
P7.19 Pressure level. 0.001~P7.20 ○
pa a
0.001M 1.000Mp
P7.20 Sleep pressure level P7.19~P7.27 ○
pa a
Sleep level
P7.21 0~250s 1s 10s ○
continuous time
P7.22 Sleep frequency 0.00~400.0Hz 0.01Hz 20.00Hz ○
Sleep frequency
P7.23 0~250s 1s 10s ○
continuous time
Low alarm limit 0.001M 0.001Mp
P7.24 0.001~P7.25 ○
pressure pa a
NE200 User Manual
0000~1113
LED unit ’s place: mode selection
0:Inaction
1:Stop after single cycle
2:Running at final freq after single cycle
3:Continuous cycle
LED ten’s place: restart mode selection
0:Restart from the first stage
1:Restart from the freq. of
PLC running mode
P8.00 break stage 1 0000 ×
selection
2:Restart from the running. of
break stage
LED hundred’s place: parameter
save mode selection
0:No save
1:Save
LED thousand’s place: running time unit
0: Second
1:minute
000~621
LED unit ’s place: freq setting
0:Multi-stage freq i(i=1~7)
1: Freq. defined by P0.01 function code
LED ten’s place: direction selection
0:Forward
1:Reverse
P8.01 Stage 1 setting 1 000 ○
2:Controlled by running command
LED hundred’s place: Acc/Dec time
selection
0:Acc/Dec time 1
1:Acc/Dec time 2
2:Acc/Dec time 3
3:Acc/Dec time 4
NE200 User Manual
0:Inaction
P9.00 Swing freq. selection 1 0 ×
1:Action
0000~11
LED unit’s place: start mode
0:Auto start
Swing freq. running 1:Manual start by terminal
P9.01 1 00 ×
mode LED ten’s place: swing amplitude
control
0:Variable swing amplitude
1:Fixed swing amplitude
P9.02 Preset swing freq. 0.00~500.00Hz 0.01Hz 0.00Hz ○
Preset swing freq.
P9.03 0.0~3600.0s 0.1s 0.0s ○
waiting time
P9.04 Swing amplitude 0.0~50.0% 0.1% 0.0% ○
P9.05 Kick freq. 0.0~50.0% 0.1% 0.0% ○
P9.06 Swing freq. cycle 0.1~999.9s 0.1s 10.0s ○
delta wave ascent
P9.07 0.0~98.0% 0.1% 50.0% ○
time
NE200 User Manual
PF.00~
Reserved - - - -
PF.10
Fault
Type of faults Possible fault reasons Troubleshooting
code
Acc time is too short Adjust acc time
Acc over Restart the motor in running Setup start mode as speed tracking restart
E-01
current
Torque boost setup is too big Adjust torque boost or set as auto mode
Fault
Type of faults Possible fault reasons Troubleshooting
code
Restart the motor in running Setup start mode as speed tracking restart
Overvoltage of
E-07 control power Input voltage abnormal Check input power supply
supply
Fault
Type of faults Possible fault reasons Troubleshooting
code
Motor chocked or sudden change
Check load
of load
Under voltage
E-11 Mains voltage is too low Check mains voltage
in running
Inverter over current Refer to over current troubleshooting
Air duct obstruction or fan damaged Clean air duct or replace a new fan
E-13 Peripheral fault Close external fault terminals Check the reason
Fault
Type of faults Possible fault reasons Troubleshooting
code
The MODBUS communication protocol of this inverter supports the RTU mode. The
following is a detailed description of the inverter communication protocol.
◆ As the host, the inverter uses the broadcast address to send commands to the slave,
and the slave does not answer.
◆ The user can set the local address, baud rate and data format of the inverter by
keyboard or serial communication.
◆ The slave reports the current fault information in the response frame of the last
polling of the host.
The default data format is: 1 bit start bit, 8 data bits, 2 stop bits, no check.
The default rate is 9600bps. For the communication parameter settings, see PC.00~PC.05
function code.
NE200 User Manual
Start bit BIT 0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Stop bit Stop bit
Even
Start bit BIT 0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Stop bit
parity
Start bit BIT 0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Stop bit Stop bit
Even
Start bit BIT 0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Stop bit
parity
RTU mode:
DATA(n - 1)
DATA 0
Address:
ASCII mode:
RTU mode:
ASCII mode:
RTU mode:
This command is used to test the communication between main control equipment and
inverter. Inverter receives and sends back the message to the main control equipment.
NE200 User Manual
RTU mode:
Check code:
Calculation method:
For message sending end, the calculation of LRC is the method of continuous
NE200 User Manual
accumulation the byte from "slave address" to "running data" which is not converted
to ASCII code, discarding carry-over, reversing the 8 bit data, then plus 1 ( converting
to complement), finally converted to ASCII code, putting into the checkout area, high
byte in front, low byte in post. For The message receiving end, the same LRC method
is used to calculating checksum of received data, and comparing it with the received
checksum. If they are equal, the message received is correct. If not equal, the received
message is wrong. If error, the message frame is discarded with no answering, while
the end continuing to receive the next frame data.
The CRC domain is two bytes, including a binary value of 16 bits. It is calculated and
added to the message by the sending end; while low byte added in front, and high byte
added in post then, so the high byte of CRC is the last of the message. The receiving
device re-calculates the CRC of the message, and compares it with the CRC in
receiving domain, if the two values are different, it means there is error in received
message, and the message frame is discarded, while there is no responding but
waiting for the next frame data. CRC checksum calculation method reference to
MODBUS protocol specification.
State of inverter
BIT0:STOP sign,0:STOP;1:RUN
Error code: