NE200 User Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 47

NE200 User Manual

1. Unpacking Inspection

Thank you for choosing our latest NE200 sensorless vector control type frequency
inverter Upon unpacking, please confirm the following: Any damage occurred during
transportation; Check whether the model and specifications on the nameplate of
inverter are in accordance with your order.If there is any error, please contact us or
distributors.

Please read this manual thoroughly before using to make sure our inverter working at
best condition.

2. Inverter model description

NE200- 2 S 0015 G
Abbreviation Code Inverter type

Voltage Code G Constant torque

220V 2 P Pump& Fan

380V 4
Code Power rate

Input voltage Code 0007 0.75KW

Single phase S 0015 1.5KW

Three phases T 0075 7.5KW

Fig 2-1 Inverter model description


NE200 User Manual

3. Dimensions

Type Number H(mm) W(mm) D(mm) H1(mm) W1(mm) φ(mm)

NE200-2S0002G

NE200-2S 0004G
162 85 113 144 74 φ5
NE200-2S 0007G

NE200-2S 0015G
NE200 User Manual

4. Specifications

Items Specifications
Rated Single phase220V, three phase 200V, three phase
Input voltage/Frequency 380V;50Hz/60Hz
Range Voltage: ±20% voltage unbalance rate:<3%; frequency: ±5%
Rated voltage 0~200V/220V/380V
Frequency range 0Hz~500Hz(standard)
Output Frequency
0.01Hz
resolution
Overload ability 150% rated current for1minute, 180% rated current for3 seconds
Modulation modes Optimized space voltage vector SVPWM modulation
Sensorless vector control (with optimal low frequency dead time
Control mode
compensation)
Frequency Digital setting: The highest frequency×± 0.01% Analog setting:
precision The highest frequency ×±0.2%
Frequency Digital setting: 0.01Hz; Analog setting: The highest frequency×
resolution 0.1%
Start frequency 0.40Hz~20.00Hz
Torque boost Auto torque boost, manual torque boost 0.1%~30.0%
Five ways: constant torque V/F curve, 1 kind of user defined
Control function

V/F curve V/F curve ,3 kinds of down torque curve(2.0/1.7/1.2times the


power)
Two ways: linear Acc./Dec.,S-curveAcc./Dec.;7 kinds of
Acc./Dec. curve Acc./Dec. time, time unit(minute/second) optional, max. time:
6000 minutes.
DC braking start frequency:0~15.00Hz
DC braking
braking time:0~60.0s braking current:0~80%
PID built-in Easily constitute a close loop control system
Multi-stage Multi-stage speed running available through built-in PLC or
speed running control terminals
Textile swing Swing frequency available with preset and centre frequency
frequency adjustable
Auto voltage When the grid voltage changes, to maintain constant output
regulation(AVR) voltage
NE200 User Manual

Items Specifications
Auto energy
Saving energy by auto optimizing V/F curve according to the load
saving running
Auto current
Auto current limiting to prevent frequent over current fault trip
limiting
Multi pump
When connect with Yuanshin water supply kit can offer
constant water
multi-pump constant water pressure supply
pressure supply
RS485 standard communication port available, support
Communication MODBUS communication protocol of ASCII and RTU,
master-slave multi-machine interaction function available
Running
Control panel : control terminal :serial port :3 channels
command
switchable
channel
Control panel potentiometer : ▲、▼control panel keys:;function
Frequency code digital: serial port : terminal up/down:
setting channel analog voltage: analog current: pulse:
combination setting: all channels switchable
Runni
Switch input FWD/REV command: 8channels programmable switch inputs,
ng
channel 35kinds of function can be set separately
functi
Analog input 4~20mA(220V Model ): 0-10V:
on
channel 2 optional analog inputs for 380V Model
LED digital
Display setting frequency, output voltage, output current, etc.
display
Control panel

External meter
Display output frequency, output current, output voltage, etc.
display
Key lock All the keys can be locked
Function code parameters are able to be copied between
Parameter copy
inverters when use remote control panel
Overcurrent
Protection function protection:overvoltageprotection:undervoltageprotection:overhea
ting protection: overload protection, etc.
Indoors, free from direct sunlight, dust, corrosive gas, oil mist,
Environment

Environment
steam, water dropper salt, etc
Altitude Lower than 1000m (derating is necessary above 1000m)
Ambient
-10℃~+50℃
temperature
NE200 User Manual

Items Specifications
Humidity <90%RH, no condensation
Vibration Lower than 5.9m/s (0.6g)
Storage
-20℃~+60℃
temperature
Struct Protection level IP20(In the selection of state display unit or the keyboard state)
ure Cooling Forced air cooling
Installation Wall mounted

Rated output Motor power


Models
current(A) (KW)
NE200 series/Input voltage: 220V single phase
NE200-2S0004G 3.0 0.4
NE200-2S0007G 4.7 0.75
NE200-2S0015G 7.5 1.5

5. Wire Connection

Security Level Safety Precautions

◆ Before wiring, please ensure the power has been removed and
be wait for at least 10minutes.

◆ Please do not connect AC power to output terminals U/V/W.

◆ To ensure the safety, the inverter and motor should be safety


grounding. It is necessary to use copper wire above 3.5mmas
ground wire, grounding resistance less than 10Ω.

◆ The inverter has gone through voltage withstand test in factory,


Attention please do not make it again.

◆ Solenoid switch or absorbing devices, such as ICEL, is


prohibited to connect inverter output.

◆ To provide input over current protection and for convenience in


maintenance, the inverter should be connected to AC power
NE200 User Manual

Security Level Safety Precautions

through circuit breaker.

◆ Please use twisted wire or shielded wire above 0.75mm for the
wiring of relay input/output loop (X1~X6, FWD, REV, OC,
DO).One end of shielding layer suspended, and the other side
connected to PE grounding terminal of inverter, wiring length
less than 50m .

◆ The cover can be removed only when the power is switched off,
all the LEDs on the panel are off and waiting at least for 10
minutes.

◆ Wiring work can be performed only when the DC voltage


between P+ and P- terminals is lower than 36V.

◆ Wiring work can only be done by trained or professional


Attention personnel.

◆ Before usage, check whether the mains voltage meets the


requirement of inverter input voltage.

6. Installation

6.1 Environment Requirements


◆ Please mount inside a well-ventilated location. The ambient temperature is
required to be within the range of -10 ~40℃. If the temperature is higher than
40 ℃, the inverter should be derated, at the same time the ventilation and heat
dissipation should be enhanced.

◆ Be away from the location full of dust or metal powder, and mount in the
location free of direct sunlight.

◆ Mount in the location free of corrosive gas or combustible gas.

◆ Humidity should be lower than 95% with no dew condensation.

◆ Mount in the location where vibration is less than 5.9m/s2(0.6G).


NE200 User Manual

◆ Please try to keep the inverter away from EMI source and other electronic
devices which are sensitive to EMI.

6.2 Mounting Space and Direction


◆ Generally in vertical way.

◆ For the requirements on mounting space and distance, refer to Fig.3-1.

◆ When several inverters are installed in one cabinet, they should be mounted in
parallel with special incoming and out coming ventilation and special fans.
When two inverters are mounted up and down, an air flow diverting plate should
be fixed as shown in Fig.3-2 to ensure good heat dissipation.

Fig.6-1 Mounting space and distance Fig.6-2 Mounting of multiple inverters


NE200 User Manual

7. Standard Wiring Diagram

Terminal name Function


L1、L2 220V 1-phase Input terminals
U、V、W 220V 3-phase Output terminals
E wiring terminals

Fig. 7-1 Single-phase control board terminal arrangement sequence diagram

Sort Terminal Name Function Specification


RS485 differential signal positive
Commu-

485+
nication

RS485 terminal Twisted or shielded


interface RS485 differential signal negative wire needed
485-
terminal
NE200 User Manual

Sort Terminal Name Function Specification

Relay output TA-TC: NC,


Relay output terminal

TA TA-TB: Normally open


terminal TA
Can be defined as multifunctional contact
Relay output Relay output terminal by capacityAC250V/2A
TB
terminal TB programming, refer to Chapter6.5 (COSΦ=1)
P4.12, P4.13 AC250V/1A
Relay output
TC (COSΦ=0.4)
terminal TC
DC30V/1A
control terminal

Forward
Operation

FWD
running Couple isolated input
Refer to chapter 6.5 P4.08
Reverse Input resistance:2KΩ
REV
running
Multifunction Optical coupling
X1 al input isolation, compatible
Multifunctional input

terminal 1 dual polarity input


terminal

Input impedance: R=2



Multifunction
Max input frequency:
X2 al input
200Hz
terminal 2
Input voltage range:
9~30V
+24V
Supply +24V power (negative
24V common
terminal: COM)
terminal
Supply+10V power (negative Max. output current:
10V +10V power
Power

terminal: GND) 50mA


+10V
Grounding of analog signal
GND common Terminal COM and
and+10V power source
terminal GND are
+24Vcommo Digital signal input, output Isolated inside
COM
n terminal common terminal
NE200 User Manual

8. Basic Wiring Diagram

Fig. 8-01
NE200-2S0002G(220V) NE200-2S0004G(220V)

NE200-2S0007G(220V) NE200-2S0015G(220V)
NE200 User Manual

9. Keypad introduce
9.1 Keypad interface
The operation panel and control terminals of the inverter can control the starting, speed
regulation, shutdown, braking, operating parameter setting and peripheral equipment of the
motor. The operation panel is shown in Figure 9-1.

Fig. 9-01 Control panel diagram

9.2 Keypad Function description

Name Description
When the light is on, the inverter is in the running state; when the light
RUN
is off, the inverter is in the stop state.
Indicates that the inverter is in
○ LOCAL/REMOT:Light off
Status the stop state
light ○ LOCAL/REMOT:Twinkling Indicates the communication
LOCAL
start and stop control mode
○ LOCAL/REMOT:Constant on Indicates the terminal start and
stop control mode
NE200 User Manual

Name Description

Indicates the unit currently displayed on the keyboard

Hz Frequency unit

Unit
indicator A Current unit

V Voltage unit

Name Description

There are 4 LED digital tubes on the operation panel of the inverter, which
display various monitoring data such as setting frequency, output frequency
and alarm codes.
Digital Corresponding Digital Corresponding Digital Corresponding
Display Letter Display Letter Display Letter

0 0 1 1 2 2
3 3 4 4 5 5
Digital
6 6 7 7 8 8
Display Area
9 9 A a b b
C C d d E E
F F H F I I
L L N N N n
o o P P r r
S S t t U U
u v . . - -
Turn left = decrement,turn right = increment .
Digital
Press potentiometer= button.
Potentiometer
NE200 User Manual

Name Description

Running Press this button for running

Multi-function Default=Reverse , can change funtion via P7.00

When VFD at normal running , press this button


to stop Inverter as pre-setting way.
Stop/Reset
When VFD has fault, press this button to reset
the inverter back to normal status.

Operation Menu/Data Enter or exit programming status


Button

Increment Data or function code increment

Decrement Data or function code decrement

At edit status, can shoose the data want to


Move/Switch change; At other status, can switch to
monitoring data display.

At edit status, to enter next level menu or save


Save/Switch
the function code data.
NE200 User Manual

10. Standard Function Parameters

10.1 Symbol Description

“○”: The parameter can be modified when the AC drive is in either stop or running state. “×”: The
parameter can not be modified when the AC drive is in the running state.
“* ”: The parameter is factory parameter and can not be modified.

10.2 Function Code Table


Func Min Factory Chan
Name Range
Code Unit Default ge

P0 Group: Basic running function parameter

Control mode 0:V/F Control


P0.00 1 0 ○
selection 1:Senseless vector control
0:Analog potentiometer on control
panel
1:▲、▼key on control panel
2:Digital setting 1,control panel given
3:Digital setting 2, UP/DOWN terminal
Frequency given given
P0.01 1 0 ○
channel selection 4:Digital setting 3, serial port given
5:VI analog given
(VI-GND)
6:CI analog given(CI-GND)
7:Pulse terminal given(PULSE)
8:Combination given (refer to P3.00)
Running Frequency P0.19lower limit freq.~P0.20upper limit
P0.02 0.01Hz 50.00Hz ○
Digital Setting freq.
0:Control panel mode
Running command
P0.03 1:Terminal control mode 1 0 ○
mode selection
2:Serial port control mode
Unit’s place: 0: Forward 1:Reverse
Running direction
P0.04 Ten’s place: 0:REV allowed REV 1:REV 1 10 ○
setting
prohibited
P0.05 FWD/REV dead 0.0~120.0s 0.1s 0.1s ○
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
time
P0.06 Max output freq. 50.00Hz~500.00Hz 0.01Hz 50.00Hz ×
P0.07 Basic running freq 1.00Hz~500.00Hz 0.01Hz 50.00Hz ×
inverter
P0.08 Max output voltage 1~480V 1V rated ×
voltage
P0.09 Torque boost 0.0%~30.0% 0.1% 2.0% ×
Torque boost cut-off
P0.10 0.00Hz~Basic running freq.P0.07 0.00 50.00Hz ○
freq.
0:Manual
P0.11 Torque boost mode 1 0 ○
1:Auto
P0.12 Carrier freq 1.0K~14.0K 0.1K 8.0K ×
Acc/Dec mode 0:Linear Acc/Dec
P0.13 1 0 ×
selection 1:S Curve Acc/Ced
Time of S curve 10.0%~50.0%(Acc/Dec time)
P0.14 0.1% 20.0% ○
start stage P0.14+P0.15《 90%
Time of S curve 10.0%~80.0%(Acc/Dec time)
P0.15 0.1% 60.0% ○
ascent stage P0.14+P0.15《 90%
0:Second
P0.16 Acc/Dec time unit 0 0 ×
1:Minute
P0.17 Acc time 1 0.1~6000.0 0.1 20.0 ○
P0.18 Dec time 1 0.1~6000.0 0.1 20.0 ○
P0.19 Upper limit freq. Lower limit freq. ~Max output freq.P0.06 0.01Hz 50.00Hz ×
P0.20 Lower limit freq. 0.00Hz~Upper limit freq. 0.01Hz 0.00Hz ×
Lower limit freq. 0:Running at lower limit freq
P0.21 1 0 ×
Running mode 1:Stopping
0:Constant torque curve
1:Reduced torque curve 1 (1.2 times
the power)
P0.22 V/F curve setting 2:Reduced torque curve 2 (1.7 times 1 0 ×
the power)
3:Reduced torque curve 3 (2.0 times
the power)
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
4:Customized V/F curve
P0.23 V/F Freq.valueF3 P0.25 ~ P0.07 Basic running freq. 0.01Hz 0.00Hz ×
P0.24 V/F Volt.valueV3 P0.26 ~ 100.0% 0.1% 0.0% ×
P0.25 V/F Freq.valueF2 P0.27 ~ P0.23 0.01Hz 0.00Hz ×
P0.26 V/F Volt.valueV2 P0.28 ~ P0.24 0.1% 0.0% ×
P0.27 V/F Freq.valueF1 0.00~P0.25 0.01Hz 0.00Hz ×
P0.28 V/F Volt.valueV1 0 ~ P0.26 0.1% 0.0% ×

P1 Group: Frequency setting function parameter

Analog filtering time


P1.00 0.01~30.00s 0.01s 0.20s ○
constant
P1.01 VI channel gains 0.01~9.99 0.01 1.00 ○
P1.02 VI min given 0.00~P1.04 0.01Hz 0.00V ○
Corresponding freq.
P1.03 0.00~Upper limit freq. 0.01Hz 0.00Hz ○
to VI min given
P1.04 VI max given P1.04~10.00V 0.01V 10.00V ○
Corresponding freq
P1.05 0.00~Upper limit freq. 0.01Hz 50.00Hz ○
to VI max given
P1.06 CI channel gains 0.01~ 9.99 0.01 1.00 ○
P1.07 CI min given 0.00~ P1.09 0.01V 0.00V ○
Corresponding freq.
P1.08 0.00~Upper limit freq 0.01Hz 0.00Hz ○
to CI min given
P1.09 CI max given P1.07 ~10.00V 0.01V 10.00V ○
Corresponding freq.
P1.10 0.00~Upper limit freq 0.01Hz 50.00Hz ○
to CI max given
Max input pulse
P1.11 0.1~20.0K 0.1K 10.0K ○
freq
P1.12 Pulse min given 0.0~P1.14(Pulse max given) 0.1K 0.0K ○
Corresponding freq.
P1.13 0.00~Upper limit freq 0.01Hz 0.00Hz ○
to pulse min given
P1.12(Pulse min given)~P1.11(Max
P1.14 Pulse max given 0.1K 10.0K ○
input pulse freq.)
P1.15 Corresponding freq. 0.00~Upper limit freq 0.01Hz 50.00Hz ○
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
to pulse max given

P2 Group: Start/Brake function parameter

0:Start from start freq.


P2.00 Start running mode 1:Brake first, then start from start freq. 1 0 ×
2:Track speed, then start.
P2.01 Start freq. 0.40~20.00Hz 0.01Hz 0.50Hz ○
Start freq. running
P2.02 0.0~30.0s 0.1s 0.0s ○
duration
DC brake current as
P2.03 0~15% 1% 0% ○
start
DC brake time as
P2.04 0.0~60.0s 0.1s 0.0s ○
start
0:Dec
P2.05 Stop mode 1:Free Stop 1 0 ×
2:Dec+DC brake
Start freq. of DC
P2.06 0.0~15.00Hz 0.0Hz 3.00Hz ○
brake as stop
DC brake time as
P2.07 0.0~60.0s 0.1s 0.0s ○
stop
DC brake current as
P2.08 0~15% 1% 0% ○
stop

P3 Group :Auxiliary running parameter

0: VI+CI
1: VI-CI
2:External pulse given+VI+control
panel▲、▼key given
3:External pulse given-VI-control
Freq. control panel▲、▼key given
P3.00 channel 4:External pulse given+CI 1 0 ×
combination 5:External pulse given-CI
6:RS485 given+VI+control panel▲、
▼key given
7:RS485 given-VI-control panel▲、
▼key given
8:RS485 given+CI+control panel▲、
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
▼key given
9:RS485 given-CI-control panel▲、
▼key given
10:RS485 given+CI+External pulse
given
11:RS485 given-CI-External pulse
given
12:RS485 given+VI+External pulse
given
13:RS485 given-VI-External pulse
given
14:VI+CI+control panel▲、▼key
given
+digital given (P0.02)
15:VI+CI-control panel▲、▼key
given
+digital given (P0.02)
16:MAX(VI,CI)
17:MIN(VI,CI)
18:MAX(VI,CI,PULSE)
19:MIN(VI,CI,PULSE)
20:VI,CI(Availability except 0,VI prior)
21:VI+Terminal UP/DOWN
22:CI+Terminal UP/DOWN
23:RS485 setting + panel analog
potentiometer fine tuning
24:RS485 setting-panel analog
potentiometer
25:RS485 setting + VCI
26:RS485 setting-VCI
27:RS485 setting + CCI
28:RS485 setting-CCI
29:VI + analog potentiometer fine
tuning
30:Fine adjustment of CI + analog
potentiometer fine tuning
31:VI + analog potentiometer
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
32:VI-analog potentiometer
33:CI + analog potentiometer
34:CI-analog potentiometer
35:RS485 setting + UPDOWN terminal
fine tuning
LED unit’s place:
0: All parameters are allowed to be
revised.
1: All parameters are not allowed to be
revised except this parameter itself.
Parameter
2: All parameters are not allowed to be
P3.01 initialization 1 0 ×
revised except P0.02 parameter and
setting
this parameter itself
LED ten’s place:
0:Inaction
1:Factory default reset
2:Clear history fault record
P3.02 Reserved ---- --- --- ×
Auto energy 0:Inaction
P3.03 1 0 ×
save running 1:Action
0:Inaction
P3.04 AVR function 1:Always action 1 0 ×
2:Inaction only in Dec
Slip freq.
P3.05 0~150% 1% 0% ×
compensation
P3.06 JOG running freq. 0.10~50.00Hz 0.01Hz 5.00Hz ○
P3.07 JOG Acc time 0.1~60.0s 0.1s 20.0s ○
P3.08 JOG Dec time 0.1~60.0s 0.1s 20.0s ○
LED unit’s place: baud rate selection
0:1200BPS
1:2400BPS
Communication 2:4800BPS
P3.09 1 005 ×
configuration 3:9600BPS
4:19200BPS
5:38400BPS
LED ten’s place: data format
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
0:1-7-2 Format, without check
1:1-7-1 Format, odd parity check
2:1-7-1 Format, even parity check
3:1-8-2 Format, without check
4:1-8-1 Format, odd parity check
5:1-8-1 Format, even parity check
6:1-8-1 Format, without check
LED hundred’s place: communication
mode
0:MODBUS,ASCII Mode
1:MODBUS,RTU Mode
0~248
P3.10 Local address 0:Broadcast address 1 1 ×
248:Host address
Communication
0.0~1000.0s
P3.11 overtime 0.1s 0.0s ×
0.0:Function invalid
detection time
Local response
P3.12 0~1000ms 1 5ms ×
delay
Multi-running
P3.13 0.01~1.00 0.01 1.00 ×
running proportion
P3.14 Acc time2 0.1~6000.0 0.1 20.0 ○
P3.15 Dec time2 0.1~6000.0 0.1 20.0 ○
P3.16 Acc time3 0.1~6000.0 0.1 20.0 ○
P3.17 Dec time3 0.1~6000.0 0.1 20.0 ○
P3.18 Acc time4 0.1~6000.0 0.1 20.0 ○
P3.19 Dec time4 0.1~6000.0 0.1 20.0 ○
P3.20 Acc time5 0.1~6000.0 0.1 20.0 ○
P3.21 Dec time5 0.1~6000.0 0.1 20.0 ○
P3.22 Acc time6 0.1~6000.0 0.1 20.0 ○
P3.23 Dec time6 0.1~6000.0 0.1 20.0 ○
P3.24 Acc time7 0.1~6000.0 0.1 20.0 ○
P3.25 Dec time7 0.1~6000.0 0.1 20.0 ○
P3.26 Multi-stage freq.1 Lower limit freq.~Upper limit freq. 0.01Hz 5.00Hz ○
P3.27 Multi-stage freq.2 Lower limit freq.~Upper limit freq. 0.01Hz 10.00Hz ○
P3.28 Multi-stage freq.3 Lower limit freq.~Upper limit freq. 0.01Hz 20.00Hz ○
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
P3.29 Multi-stage freq.4 Lower limit freq.~Upper limit freq. 0.01Hz 30.00Hz ○
P3.30 Multi-stage freq.5 Lower limit freq.~Upper limit freq. 0.01Hz 40.00Hz ○
P3.31 Multi-stage freq.6 Lower limit freq.~Upper limit freq. 0.01Hz 45.00Hz ○
P3.32 Multi-stage freq.7 Lower limit freq.~Upper limit freq. 0.01Hz 50.00Hz ○
P3.33 Jump freq.1 0.00~500.00Hz 0.01Hz 0.00Hz ×
P3.34 Jump freq.1range 0.00~30.00Hz 0.01Hz 0.00Hz ×
P3.35 Jump freq.2 0.00~500.00Hz 0.01Hz 0.00Hz ×
P3.36 Jump freq.2range 0.00~30.00Hz 0.01Hz 0.00Hz ×
P3.37 Reserved 0000~9999 1 0000 ×
Zero frequency DC
P3.38 0.0%~15.0% 0.1% 0.0% ×
braking voltage
P3.39 Set running time 0~65.535K hour 0.001K 0.000K ○
P3.40 Total running time 0~65.535K hour 0.001K 0.000K *
Slow down and start
P3.41 00.0~60.0 0.1s 02.0 s ○
wait time
Inspection speed
and start the
P3.42 00.0~150.0% 0.1% 100.0% ○
maximum output
current level
Running display
P3.43 parameter 00~15 1 00 ○
selection1
Stop display
P3.44 parameter 00~15 1 00 ○
selection2
No unit display
P3.45 0.1~60.0 0.1 29.0 ○
coefficient
JOG/REV 0:Select the JOG point operation
P3.46 1 0 ×
Switching control 1:Select the REV reverse operation

P4 Group: Terminal control function parameter

0:Idle terminal
1:Multi-stage speed control terminal 1
Input terminal X1
P4.00 2:Multi-stage speed control terminal 2 1 0 ×
function selection
3:Multi-stage speed control terminal 3
4:External FWD JOG control input
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
5:External REV JOG control input
6:Acc/Dec time terminal 1
7:Acc/Dec time terminal 2
8:Acc/Dec time terminal 3
9:3-wire control
10:Free stop input (FRS)
11:External stop command
12:Stopping DC brake input command
DB
13:Inverter running prohibited
14:Freq. increase command(UP)
15:Freq. decrease command(DOWN)
16:Acc/Dec prohibited command
17:External reset input (clear fault)
18:Peripheral equipment fault input
(normally open)
19:Freq. control channel selection 1
20:Freq. control channel selection 2
21:Freq. control channel selection 3
22:Command switched to terminal
23:Running command control mode
selection 1
24:Running command control mode
selection 2
25:Swing frequency selection
26:Swing frequency running reset
27:Close loop invalid
28:Simple PLC pause running
command
29:PLC invalid
30:PLC Reset in stopping state
31:Freq. switch to CI
32:Counter trig signal input
33:Counter clear input
34:External interrupt input
35:Pulse freq. input (only valid for X6)
P4.01 Input terminal X2 Ditto 1 0 ×
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
function selection

0:2-wire control mode 1


FWD/REV running 1:2-wire control mode 2
P4.08 1 0 ×
mode selection 2:3-wire control mode 1
3:3-wire control mode 2

P4.09 UP/DN Rate 0.01-99.99Hz/s 0.01 1.00Hz/s ○


Relay TA/TB/TC
P4.12 Ditto 1 15 ×
output selection
Freq. arrival
P4.14 0.00~400.00Hz 0.01Hz 5.00Hz ○
detection range
P4.15 FDT1(freq. level) 0.00~Upper limit freq 0.01Hz 10.00Hz ○
P4.16 FDT1 lag 0.00~50.00Hz 0.01Hz 1.00Hz ○
unit’s place :
0:Output freq.(0~upper limit freq.)
1:Output current(0~2 times
motor rated current)
2:Output voltage(0~1.2 times
DO output terminal
P4.21 inverter rated voltage) 1 0 ○
function selection
3:Bus bar voltage(0~800V)
4:PID given
5:PID feedback
6:VI(0~10V)
7:CI(0~10V/4~20mA)
DO max pulse
P4.22 0.1K~20.0K(max 20KHz) 0.1KHz 10.0KHz ○
output freq.
P4.23 Set counts given F4.20~9999 1 0 ○
Specified counts
P4.24 0~F4.19 1 0 ○
given
Overload pre-alarm
P4.25 20%~200% 1 130% ○
detection level
Overload pre-alarm
P4.26 0.0~20.0s 0.1s 5.0s ○
delay time

P5 Group: Protection function parameter

Motor overload 0:Stop outputting


P5.00 1 0 ×
protection 1:Inaction
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
mode selection
Motor overload
P5.01 protection 20~120% 1 100% ×
coefficient
Overvoltage stall 0:Prohibited
P5.02 1 1 ×
Selection 1:Allowed
Overvoltage stall 380V:120~150% 140%
P5.03 1% ○
point 220V:110~130% 120%
Auto current limit
P5.04 110%~200% 1% 150% ×
level
Freq. drop rate 0.01Hz/ 10.00Hz/
P5.05 0.00~99.99Hz/s ○
during current limit s s
0:Constant speed invalid
Auto current limit
P5.06 1:Constant speed valid 1 1 ×
mode selection
Note: Acc/Dec valid
Restart setting after 0:Inaction
P5.07 1 0 ×
power failure 1:Action
Restart waiting time
P5.08 0.0~10.0s 0.1s 0.5s ×
after power failure
0~10
Fault self-recovery 0:Self-recovery invalid
P5.09 1 0 ×
times Note: Self-recovery invalid
in overload or overheat
Self-recovery
P5.10 0.5~20.0s 0.1s 5.0s ×
interval time

P6 Group: Fault record function parameter

P6.00 Last fault record Last fault record 1 0 *


Output freq. in Output freq. in
P6.01 0.01Hz 0 *
last fault last fault
P6.02 Set freq. in last fault Set freq. in last fault 0.01Hz 0 *
Output current in Output current in
P6.03 0.1A 0 *
last fault last fault
P6.04 Set freq. in last fault Set freq. in last fault 1V 0 *
Output current in Output current in
P6.05 1V 0 *
last fault last fault
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
Output voltage in Output voltage in
P6.06 10C 0 *
last fault last fault
P6.07 Last 2 fault record Last 2 fault record 1 0 *
P6.08 Last 3 fault record Last 3 fault record 1 0 *
P6.09 Last 4 fault record Last 4 fault record 1 0 *
P6.10 Last 5 fault record Last 5 fault record 1 0 *
P6.11 Last 6 fault record Last 6 fault record 1 0 *

P7 Group: Close loop running control function parameter

Close loop running 0:Invalid


P7.00 1 0 ×
control selection 1:Valid
0:P7.05 Digital given + panel▲、▼Fine
tuning
1:VI analog 0~10V voltage given
Close loop given 2:CI analog 0~10V given
P7.01 1 0 ×
channel selection 3:Panel analog potentiometer given
4:RS485 communication given
5:Pulse input given
6:CI simulation4~20mACurrent setting
0:VI analog 0~10V input voltage
1:CI analog input
(0~10V/0~20mA)
Feedback channel 2:VI+CI
P7.02 1 0 ×
selection 3:VI-CI
4:Min{VI,CI}
5:Max{VI,CI}
6:CI analog input(4~20mA)
Given channel
P7.03 filtering time 0.01~50.00s 0.01s 0.50s ○
constant
Feedback channel
P7.04 filtering time 0.01~50.00s 0.01s 0.50s ○
constant
Given value digital
P7.05 0.001~20.000Mpa 0.001Mpa 0.000Mpa ×
setting
Close loop
0:Positive effect
P7.06 adjustment 1 0 ○
1:Negative effect
characteristics
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
Feedback channel
P7.07 0.01~10.00 0.01 1.00 ○
gain
Lower pressure limit
P7.08 0.001~P7.09 0.001 0.001 ○
Upper pressure limit
P7.09 P7.08~P7.27 0.001 1.000 ○
0:Proportional control
1:Integral control
PID Controller
P7.10 2:Proportional integral control 1 1 ×
structure
3:Proportional, integral and differential
control
Proportional gain
P7.11 0.00~5.00 0.01 0.50 ○
KP
Integral time
P7.12 0.1~100.0s 0.1 10.0s ○
constant
P7.13 Differential gain 0.0~5.0 0.1 0.0 ×

P7.14 Sampling period 0.01~1.00s 0.01 0.10 ○

P7.15 Tolerance limit 0.0~20.0% 0.1% 0.0% ○

PID Feedback
P7.16 disconnected 0~Upper limit freq 0.01Hz 0.00Hz ○
detection threshold
PID Feedback
P7.17 disconnected action 0~3 1 0 ○
selection
PID Feedback
P7.18 disconnected 0.01~5.00s 0.01s 1.00s ○
operation delay time
0.001M 0.001Mp
P7.19 Pressure level. 0.001~P7.20 ○
pa a
0.001M 1.000Mp
P7.20 Sleep pressure level P7.19~P7.27 ○
pa a
Sleep level
P7.21 0~250s 1s 10s ○
continuous time
P7.22 Sleep frequency 0.00~400.0Hz 0.01Hz 20.00Hz ○
Sleep frequency
P7.23 0~250s 1s 10s ○
continuous time
Low alarm limit 0.001M 0.001Mp
P7.24 0.001~P7.25 ○
pressure pa a
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
The alarm limit 0.001M 1.000Mp
P7.25 P7.24~P7.27 ○
pressure pa a
0:Choosing not to constant pressure
water supply mode
1:With a constant pressure water
supply mode
Constant pressure 2:A two constant pressure water supply ×
P7.26 1 0
water supply mode mode
3:A three constant pressure water
supply mode
4:A four constant pressure water supply
mode
Remote pressure 0.001M 1.000Mp
P7.27 0.001~20.000Mpa ○
gauge range pa a
Multi pump 0:Fixed sequence switch
P7.28 1 0 ○
operation mode 1:Timing of the rotation
Rotation in timed
P7.29 0.5~100.0H 0.1H 5.0H ○
intervals
Pump switching
P7.30 0.1~1000.0s 0.1s 300.0s ×
judgment time
Electromagnetic
P7.31 0.1~10.0s 0.1s 0.5s ×
switching delay time
unit’s place:
0:PID Control action
PID Control of
1:PID Control reaction
positive and
ten’s place:
P7.32 negative role and 1 00 ×
0:Feedback pressure less than the
feedback pressure
actual pressure
error polarity
1:Feedback pressure is greater than
the actual pressure
Feedback error of
0.001M 0.000Mp
P7.33 pressure adjustment 0.001~20.000Mpa ×
pa a
coefficient
Closed loop of
P7.34 Range:0~Upper limit freq 0.00Hz 0.00Hz ×
preset frequency
P7.35 Closed loop of Range:0.0~200.0s 0.1s 0.0s ×
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
preset frequency
holding time

P8 Group PLC running parameter

0000~1113
LED unit ’s place: mode selection
0:Inaction
1:Stop after single cycle
2:Running at final freq after single cycle
3:Continuous cycle
LED ten’s place: restart mode selection
0:Restart from the first stage
1:Restart from the freq. of
PLC running mode
P8.00 break stage 1 0000 ×
selection
2:Restart from the running. of
break stage
LED hundred’s place: parameter
save mode selection
0:No save
1:Save
LED thousand’s place: running time unit
0: Second
1:minute
000~621
LED unit ’s place: freq setting
0:Multi-stage freq i(i=1~7)
1: Freq. defined by P0.01 function code
LED ten’s place: direction selection
0:Forward
1:Reverse
P8.01 Stage 1 setting 1 000 ○
2:Controlled by running command
LED hundred’s place: Acc/Dec time
selection
0:Acc/Dec time 1
1:Acc/Dec time 2
2:Acc/Dec time 3
3:Acc/Dec time 4
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
4:Acc/Dec time 5
5:Acc/Dec time 6
6:Acc/Dec time 7
P8.02 Stage 1 running time 0.1~6000.0 0.1 10.0 ○
P8.03 Stage 2 setting 000~621 1 000 ○
P8.04 Stage 2 running time 0.1~6000.0 0.1 10.0 ○
P8.05 Stage 3 setting 000~621 1 000 ○
P8.06 Stage 3 running time 0.1~6000.0 0.1 10.0 ○
P8.07 Stage 4 setting 000~621 1 000 ○
P8.08 Stage 4 running time 0.1~6000.0 0.1 10.0 ○
P8.09 Stage 5 setting 000~621 1 000 ○
P8.10 Stage 5 running time 0.1~6000.0 0.1 10.0 ○
P8.11 Stage 6 setting 000~621 1 000 ○
P8.12 Stage 6 running time 0.1~6000.0 0.1 10.0 ○
P8.13 Stage 7 setting 000~621 1 000 ○
P8.14 Stage 7 running time 0.1~6000.0 0.1 10.0 ○

P9 Group Swing frequency function parameter

0:Inaction
P9.00 Swing freq. selection 1 0 ×
1:Action
0000~11
LED unit’s place: start mode
0:Auto start
Swing freq. running 1:Manual start by terminal
P9.01 1 00 ×
mode LED ten’s place: swing amplitude
control
0:Variable swing amplitude
1:Fixed swing amplitude
P9.02 Preset swing freq. 0.00~500.00Hz 0.01Hz 0.00Hz ○
Preset swing freq.
P9.03 0.0~3600.0s 0.1s 0.0s ○
waiting time
P9.04 Swing amplitude 0.0~50.0% 0.1% 0.0% ○
P9.05 Kick freq. 0.0~50.0% 0.1% 0.0% ○
P9.06 Swing freq. cycle 0.1~999.9s 0.1s 10.0s ○
delta wave ascent
P9.07 0.0~98.0% 0.1% 50.0% ○
time
NE200 User Manual

Func Min Factory Chan


Name Range
Code Unit Default ge
0:Inverter operation of fan operation
P9.08 Fan control selection 1 0 ○
1:Power on the wind turbine operation
P9.09 Reserved 0000~9999 1 0000 ○
Overpressure
P9.11 protection threshold 0~780V 1V 780V ○
value
P9.13 G、P Model set 0、1 1 0 ○
P9.14 User password 1~9999 1 0 ○

PF Group: Factory function parameter

PF.00~
Reserved - - - -
PF.10

10.3 State Monitoring Parameter Table


B-Monitoring: function parameter
Func Factory Cha
Name Range Min Unit
Code default nge
b-00 Output freq Present output freq 0.01Hz *
b-01 Set freq. Present set freq. 0.01Hz *
Effective value of present output
b-02 Output voltage 1V *
voltage
Effective value of present output
b-03 Output current 0.1A *
current
b-04 Bus bar voltage Present DC bus bar voltage 1V *
b-05 Module temperature IGBT heat sink temperature 10C *
b-06 Motor speed Present motor speed 1r/min *
b-07 Running time One continuous running time 1H *
Input/output terminal
b-08 Input/output terminal state —— *
state
b-09 Analog input VI Analog input VI value 0.01V *
b-10 Analog input CI Analog input CI value 0.01V *
b-11 External pulse input External pulse width input value 1ms *
Inverter rated
b-12 Inverter rated current 0.1A *
current
NE200 User Manual

B-Monitoring: function parameter


Func Factory Cha
Name Range Min Unit
Code default nge
Inverter rated
b-13 Inverter rated voltage 1V *
voltage
Water supply control when the set
b-14 Set pressure 0.001Mpa
pressure of the pipeline
Water supply control feedback
b-15 Feedback pressure 0.001Mpa
pipeline pressure
b-16 No unit display No unit display 1
NE200 User Manual

11. Fault Diagnosis and Processing


11.1 Failure phenomena and countermeasures
When an abnormality occurs in the inverter, the LED digital tube will display the function code
and its contents corresponding to the fault. The fault relay will operate and the inverter will
stop output. If the motor is rotating, it will stop freely until it stops rotating. The types of faults
that may occur on the NE200 are shown in Table 11-1. When the inverter is faulty, the user
should first check according to the prompts of the table, and record the fault phenomenon in
detail. When technical service is required, please contact our after-sales service and
technical support department or our agents.

Fault
Type of faults Possible fault reasons Troubleshooting
code
Acc time is too short Adjust acc time

V/F curve setup is not suitable Adjust V/F curve

Acc over Restart the motor in running Setup start mode as speed tracking restart
E-01
current

Torque boost setup is too big Adjust torque boost or set as auto mode

Inverter capacity is too low Select inverter with proper capacity

Dec time is too short Adjust Dec time

Dec over Potential load or load inertia is too


E-02 Add suitable braking device
current big

Inverter capacity is too low Select inverter with proper capacity

Load mutation Check load

Acc or Dec time is too short Adjust Acc or Dec time


Over current at
E-03 constant speed Input voltage abnormal Check input power supply
running
Load abnormal check load

Inverter capacity is too low Select inverter with proper capacity

Input voltage abnormal Check input power supply


Acc
E-04
overvoltage
Acc time is too short Adjust Acc time
NE200 User Manual

Fault
Type of faults Possible fault reasons Troubleshooting
code

Restart the motor in running Setup start mode as speed tracking restart

Dec time is too short Adjust the Dec time


Dec
E-05
overvoltage Potential load or load inertia is too
Add suitable braking device
big

Input voltage abnormal Check input power supply


Overvoltage at
Acc or Dec time is too short Adjust the Acc or Dec time
E-06 constant speed
running Abnormal change of input voltage Mount input reactor

Load inertia is too big Add suitable braking device

Overvoltage of
E-07 control power Input voltage abnormal Check input power supply
supply

Air duct obstruction Clean air duct

Environment temperature is too Improve the ventilation or decrease the


Inverter
E-08 high carrier frequency
overheat
Fan damaged Replace a new fan

Inverter module abnormal Contact supplier

Acc time is too short Adjust Acc time

Decrease DC braking current and increase


DC braking value is too high
braking time
Inverter
E-09 V/F curve setup is not suitable Adjust V/F curve
overload
Restart the motor in running Setup start mode as speed tracking restart

Mains voltage is too low Check mains voltage

Too heavy load Select inverter with proper capacity

V/F curve setup is not suitable Adjust V/F curve

Mains voltage is too low Check mains voltage

E-10 Motor overload General motor runs at low speed


Use a special motor for long term running
with heavy load for long term

Wrong setting of motor overload


Set the factor right
protection factor
NE200 User Manual

Fault
Type of faults Possible fault reasons Troubleshooting
code
Motor chocked or sudden change
Check load
of load
Under voltage
E-11 Mains voltage is too low Check mains voltage
in running
Inverter over current Refer to over current troubleshooting

Output 3-phase fault or ground


Re-wiring
short

Air duct obstruction or fan damaged Clean air duct or replace a new fan

Environment temperature too high Decrease environment temperature


Inverter module
E-12 Control board connecting wire or
protection Check and re-wiring
plug-in unit loose

Current waveform abnormal due to


Check wiring
output missing phase, etc.

Auxiliary power damaged, or


Contact supplier
driving voltage under voltage

Control board abnormity Contact supplier

E-13 Peripheral fault Close external fault terminals Check the reason

Loose wiring or terminal


Check and re-wiring
connections
Current
E-14 detecting circuit Auxiliary power source damaged Contact supplier
fault Hall component damaged Contact supplier

Abnormal amplifier circuit Contact supplier

Wrong baud rate setting Set baud rate properly

Press Key to reset or contact


Serial port communication fault supplier
RS232/485
E-15 Communication
Improper fault alarm parameter
fault Revise function code P3.09~P3.12
setting

Check upper computer and connecting


Upper computer doesn’t work
cable

System Press key to reset or install input


E-16 Serious interference
interference power source filter
NE200 User Manual

Fault
Type of faults Possible fault reasons Troubleshooting
code

DSP read/write error Reset or contact supplier

EP2PPROM Read/write error of control press key to reset or install input


E-17
error parameter power source filter

Motor parameter Power range of Motor and inverter Contact supplier


E-18
over current fault do not match press key to reset

Input phase Press key to reset


E-19 One of R, S, T port has no voltage
loss protection check voltage of R, S, T

over current press key to reset


Over current when inverter restart
E-20 fault when
and check speed adjust relevant parameters
restart
PID feedback
PID external signal feedback
E-31 disconnected Check external wiring and signals
disconnected
failure
Pump water
Check the pump for water shortage or
shortage
E-53 Water pump idling protection check Whether P9.04 / P9.06 related
protection
parameter settings are appropriate
failure

11.2 Fault Record Query


This series inverter record the fault codes occurred in the last 6times and inverter
running parameter when last fault occurred. The fault information is saved in P6 group.
NE200 User Manual

12. Serial Port RS485 Communication Protocol


12.1 Communication Overview
The company's series of inverters provide users with a common RS485 communication
interface for industrial control. The communication protocol adopts the MODBUS
standard communication protocol. The inverter can be used as a slave to communicate
with the host computer (such as PLC controller and PC) with the same communication
interface and using the same communication protocol to realize centralized monitoring
of the inverter. Can use a frequency converter as The host computer connects several
inverters of the company as slaves through the RS485 interface. To achieve
multi-machine linkage of the inverter. The remote control keyboard can also be
connected through the communication port. Realize the user's remote operation of the
inverter.

The MODBUS communication protocol of this inverter supports the RTU mode. The
following is a detailed description of the inverter communication protocol.

12.2 Communication Protocol Description


12.2.1 Communication Network Mode
(1) The inverter acts as a slave network:

Figure 12-1 Schematic diagram of the unit network


NE200 User Manual

(2) Multi-machine linkage networking mode:

Figure 12-2 Schematic diagram of multi-machine linkage networking

12.2.2 Communication protocol mode


The inverter can be used as a host or as a slave in the RS485 network. When used as
a master, it can control other inverters of the company to achieve multi-level linkage.
When used as a slave, the PC or PLC can be used as a host. Control the inverter to
work. The specific communication methods are as follows:

◆ The inverter is a slave, master-slave point-to-point communication. When the host


sends a command using the broadcast address, the slave does not answer.

◆ As the host, the inverter uses the broadcast address to send commands to the slave,
and the slave does not answer.

◆ The user can set the local address, baud rate and data format of the inverter by
keyboard or serial communication.

◆ The slave reports the current fault information in the response frame of the last
polling of the host.

12.2.3 Communication interface mode


Communication is RS485 interface, asynchronous serial, half duplex transmission. The
default communication protocol mode uses RTU mode.

The default data format is: 1 bit start bit, 8 data bits, 2 stop bits, no check.

The default rate is 9600bps. For the communication parameter settings, see PC.00~PC.05
function code.
NE200 User Manual

12.3 Communication protocol


Character structure:

10-character box (For ASCII)

(1-7-2 format, no parity)

Start bit BIT 0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Stop bit Stop bit

(1-7-1 format, Odd parity)


Odd
Start bit BIT 0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Stop bit
parity

(1-7-1 format, Even parity)

Even
Start bit BIT 0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Stop bit
parity

11-character box (For RTU)

(1-8-2 format, no parity)

Start bit BIT 0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Stop bit Stop bit

(1-8-1 format, Odd parity)


Odd
Start bit BIT 0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Stop bit
parity

(1-8-1 format, Even parity)

Even
Start bit BIT 0 BIT1 BIT2 BIT3 BIT4 BIT5 BIT6 BIT7 Stop bit
parity

Communications data structures


ASCII mode
Frame header Start character=“:”(3AH)
Address Hi Address: 8-bit address combined with two ASCII code
NE200 User Manual

Frame header Start character=“:”(3AH)


Address Lo
Function Hi Function code:
Function Lo 8-bit address combined with two ASCII code
DATA(n - 1) Data content:
…………… n * 8-bit data content combined with 2 * n ASCII code, in which high
DATA 0 in front and low in post, n <= 4, 8 ASCII code as maximum
LRC CHK Hi LRC Check code:
LRC CHK Lo 8 check code combined with two ASCII code
END Hi End character:
END Lo END Hi = CR(0DH), END Lo = CR(0AH)

RTU mode:

START Keep no input signal greater than or equal to 10ms

Address Mailing address: 8-bit binary address

Command Function code: 8-bit binary address

DATA(n - 1)

…………… Data content: N*8-bit data, N<=8, maximum 8 bytes

DATA 0

CRC CHK Low CRC check code

CRC CHK High 16-bit CRC is composed of 2 8-bit binary combinations

END Keep no input signal greater than or equal to 10ms

Address:

00H:All broadcast from inverters


01H: Communication with inverter of 01 address
0FH:Communication with inverter of 15 address
10H:Communication with inverter of 15 address, and so on, maximum to 254(FEH)。
Function and DATA code:
03H:Read data from a register
06H:Write data to the register.
08H:Loop detection.
NE200 User Manual

Function code 03H:Read data from a register:


For example:read data from the address 2104H of register (Output current)

ASCII mode:

Asking for information string format Answering information string format

Header “:”----3AH Header “:”----3AH


“0”----30H “0”----30H
Address Address
“1”----31H “1”----31H
“0”----30H “0”----30H
Function code Function code
“3”----33H “3”----33H
“2”----32H
“0”----30H
“1”----31H
Information number
“0”----30H
“2”----32H
content
“0”----30H
“4”----34H Content of address “0”----30H
2104H “0”----30H
“0”----30H
“D” ----44H “D” ----44H
LRC CHECK LRC CHECK
“7” ----37H “7” ----37H
CR ----0DH CR ----0DH
END END
LF ----0AH LF ----0AH

RTU mode:

Asking for information string format Answering information string format

Address 01H address 01H


Function code 03H Function code 03H
21H Information number 02H
content 00H
04H content
00H
CRC CHECK Low E8H CRC CHECK Low 0EH
CRC CHECK High 4BH CRC CHECK High 37H

Function code 06H:Write to register


For example:writing function code P0.02=50.00HZ to inverter address 01H.
NE200 User Manual

ASCII mode:

Asking for information string format Answering information string format

Header “:”----3AH Header “:”----3AH


“0”----30H “0”----30H
Address Address
“1”----31H “1”----31H
“0”----30H “0”----30H
Function code Function code
“6”----36H “6”----36H
“0”----30H “0”----30H
“0”----30H “0”----30H
content
“0”----30H “0”----30H
“2”----32H “2”----32H
content
“1”----31H “1”----31H
“3”----33H “3”----33H
Data of address 2104H
“8”----38H “8”----38H
“8”----38H “8”----38H
“5” ----35H “5” ----35H
LRC CHECK LRC CHECK
“C” ----43H “C” ----43H
CR ----0DH CR ----0DH
END END
LF ----0AH LF ----0AH

RTU mode:

Asking for information string format Answering information string format

Address 00H Address 01H


Function code 06H Function code
00H 00H
02H 02H
Content Content
13H 13H
88H 88H
CRC CHECK Low 25H CRC CHECK Low 25H
CRC CHECK High 5CH CRC CHECK High 5CH

Function code:08H Communication loop test

This command is used to test the communication between main control equipment and
inverter. Inverter receives and sends back the message to the main control equipment.
NE200 User Manual

Asking for information string format Answering information string format

header “:”----3AH Header “:”----3AH


Address “0”----30H Address “0”----30H
“1”----31H “1”----31H
Function code “0”----30H Function code “0”----30H
“8”----38H “8”----38H
“0”----30H “0”----30H
“1”----31H “1”----31H
content
“0”----30H “0”----30H
“2”----32H “2”----32H
content
“0”----30H “0”----30H
“3”----33H Data from address “3”----33H
“0”----30H 2104H “0”----30H
“4”----34H “4”----34H
“E” ----45H “E” ----45H
LRC CHECK LRC CHECK
“D” ----44H “D” ----44H
CR ----0DH CR ----0DH
END END
LF ----0AH LF ----0AH

RTU mode:

Asking for information string format Answering information string format

Address 01H Address 01H


Function code 08H Function code 08H
01H 01H
02H 02H
Content content
03H 03H
04H 04H
CRC CHECK Low 41H CRC CHECK Low 41H
CRC CHECK High 04H CRC CHECK High 04H

Check code:

ASCII mode:Double byte ASCII code

Calculation method:

For message sending end, the calculation of LRC is the method of continuous
NE200 User Manual

accumulation the byte from "slave address" to "running data" which is not converted
to ASCII code, discarding carry-over, reversing the 8 bit data, then plus 1 ( converting
to complement), finally converted to ASCII code, putting into the checkout area, high
byte in front, low byte in post. For The message receiving end, the same LRC method
is used to calculating checksum of received data, and comparing it with the received
checksum. If they are equal, the message received is correct. If not equal, the received
message is wrong. If error, the message frame is discarded with no answering, while
the end continuing to receive the next frame data.

RTU mode: two bytes of 16 hex

The CRC domain is two bytes, including a binary value of 16 bits. It is calculated and
added to the message by the sending end; while low byte added in front, and high byte
added in post then, so the high byte of CRC is the last of the message. The receiving
device re-calculates the CRC of the message, and compares it with the CRC in
receiving domain, if the two values are different, it means there is error in received
message, and the message frame is discarded, while there is no responding but
waiting for the next frame data. CRC checksum calculation method reference to
MODBUS protocol specification.

Communication protocol parameter definition

definition Parameter address Function description


Internal setting GG means parameter group,nn means parameter
GGnnH
parameters number
0001H:RUN
0002H:FWD
0003H:REV
0004H:JOG
Commands to 0005H:FWD JOG
2000H
inverter 0006H:REV JOG
(06H) 0007H:DEC and STOP
0008H:STOP
0009H:JOG STOP
000AH:RESET
2001H Freq. setting
NE200 User Manual

definition Parameter address Function description

2100H Read ERROR code

State of inverter

BIT0:STOP sign,0:STOP;1:RUN

BIT1: Under voltage sign,1: Under voltage;0:Normal

BIT2:FWD REV sign,1:REV;0:FWD

BIT3:JOG sign,1:JOG;0:NON JOG。

BIT4:Close loop control,1:Close;0:Non close

Monitoring BIT5: swing freq. sign,1:swing;0:non swing。


inverter
2101H BIT6:PLC run sign,1:PLC run,0:non PLC
(03H)
BIT7:terminal multi-stage speed,1:multi-stage 0:non
multi-stage
BIT8:normal running,1:normal;0:non.

BIT9:Freq. from comm.,1:yes;0:no.

BIT10:Freq. from analog input,1:yes;0:no.

BIT11:run commands from comm.,1:yes;0:no.

BIT12: parameter password protection


,1:yes;0:no.

2102H Read Freq. setting

2103H Read output Freq.

2104H Read output current

2105H Read bus voltage

2106H Read output voltage

2107H Read motor speed

2108H Read module temp.

2109H Read VI analog input

210AH Read CI analog input

210BH Read software version


NE200 User Manual

definition Parameter address Function description


GGnnH
Read function (GG:function code
Responding function code
code(03H) number。nn :function
code number)
GGnnH
Read function (GG:function code
Function code writing into inverter
code(06H) number。nn :function
code number)

Error code:

Error code Description

01H Function code error。it can not be identified:03H,06H,08H。


02H Address error。it can not be identified
03H Data error. Data overrun
NE200 User Manual