Eclipse en LQ
Eclipse en LQ
Eclipse en LQ
Eclipse
The thermostatic radiator valve Eclipse has a unique integrated
flow limiter that eliminate over flows. The required flow rate can be
adjusted directly at the valve with a twist. The adjusted flow will not
be exceed even if there are load changes in the system, due to other
valves closing or during morning start up. The valve controls the flow
rate independently from differential pressure. Therefore, complicated
calculations to determine settings are not necessary.
Key features
> Integrated flow limiter > Perfect for renovation
Eliminates over flows Standard dimensions and easy flow
sizing
> Easy adjustment
Just a twist to reach design flow > All valve bodies with II+ marking
can be retrofitted as Eclipse
> Flow range from 10 to 150 l/ h i.e. V-exact II, Standard, Multilux,
For high flexibility Multilux 4-Set
Technical description
2
Construction
Eclipse
1. S
trong return spring in combination with high locating force
ensures that the valve does not slacken off over time
2. H
EIMEIER M30x1.5 connection for thermostatic heads and
actuators
3. Automatic flow limiter
4. Valve body in corrosion-resistant gunmetal
5. Long-life double O-ring sealing
6. Flow setting
Replaceable insert
The complete thermostatic insert can be replaced using the
HEIMEIER fitting tool without draining the system.
Function
Eclipse flow limiter
A regulating part is set to the calculated control rate by turning The set flow rate is therefore never exceeded. If the flow rate
the digit cap with the setting key or an 11 mm end wrench. If drops below the set value a spring presses the sleeve back to
the flow rate increases at the valve the rising pressure moves the its original position.
sleeve, thus constantly limiting the flow to the set value.
Application
The thermostatic radiator valve Eclipse is applied in two-pipe Renovation
pumped heating system with normal to high temperature Eclipse replaces old valves easily due to dimensions according
spread. to EN 215 standard. All HEIMEIER thermostatic radiator valves
The required design flow for each radiator is set directly on the with II+ marking, i.e. V-exact II, Standard, Multilux, Multilux 4-Set
Eclipse valve. This automatic flow limitation is done with a twist can be retrofitted as Eclipse.
and the adjusted flow will then not be exceeded. Even if there is
Noise behaviour
an oversupply of pressure, due to load changes in the system,
To ensure low-noise performance, the following conditions must
for example other valves closing or during morning start up,
be met:
Eclipse will guarantee the requested flow.
•T he differential pressure above Eclipse should not exceed
The valve controls the flow rate independently from differential 60 kPa = 600 mbar = 0,6 bar (<30 dB(A)).
pressure. Therefore, complicated calculations to determine • Flow must be correctly adjusted.
settings are not necessary. The pressure loss of pipings in old • The system must be completely deaerated.
systems does not have to be determined in renovation projects.
Only the heating capacity and the resulting max. flow rate
have to be determined (see setting chart). The min. differential
pressure has to be at the most unfavourable valve. If necessary,
it can be measured in order to optimize pump settings (see
accessories).
3
IMI HEIMEIER / Thermostatic Heads & Radiator Valves / Eclipse
Sample application
1. Eclipse
2. Lockshield Regulux/Regutec
3. STAD balancing valve for maintenance and diagnostics
4. Boiler
Notes
– To avoid damage and the formation of scale deposit in the hot – The thermostatic valve bodies can be used with all HEIMEIER
water heating system, the composition of the heat transfer thermostatic heads and HEIMEIER or TA thermal or
medium should be in accordance with the VDI guideline 2035. motorized actuators. The optimal tuning of the components
For industrial and long-distance energy systems, see the guarantees maximum safety. When using actuators from
applicable codes VdTÜV and 1466/AGFW FW 510. other manufacturers, make sure that the pressure power is
A heat transfer medium containing mineral oils, or any type of appropriate for thermostatic valve bodies with soft sealing
lubricant containing mineral oil can have extremely negative valve discs.
effects and usually lead to the disintegration of EPDM seals.
When using nitrite-free frost and corrosion resistance solutions
with an ethylene glycol base, pay close attention to the details
outlined in the manufacturers’ documentation, particularly
concerning concentration and specific additives.
–F
lush the system before changing thermostatic valves in heavy
polluted existing systems.
4
Operation
Flow setting
Stepless setting between 1 to 15 (10 to 150 l/h). • Place the setting key on the valve insert.
The setting is changed using a special setting key (article No. •T urn the setting tool so that desired setting value is pointing at
3930-02.142) or an 11 mm end wrench, to ensure tamper proof the index* of the valve body (see fig.).
setting. • Remove the key or 11 mm end wrench. The valve is now set.
*) **)
SW 11
*) Index
**) Commissioning setting
Setting 1 l l l 5 l l l l 10 l l l l 15
5
IMI HEIMEIER / Thermostatic Heads & Radiator Valves / Eclipse
Diagram
25 dB(A)*) 30 dB(A)*)
Lowest flow tolerances
160
l/h
max.
140
120
100
80
60
Setting table
Setting values with different radiator performances and system differential temperatures
10 2 2 3 3 4 5 6 7 8 9 10 12 14 15
15 1 1 2 2 3 3 4 5 5 6 7 8 9 10 12 13 14 15
20 1 1 1 2 2 3 3 3 4 4 5 6 7 8 9 10 10 11 12 13 14 15
30 1 1 1 1 1 2 2 2 3 3 3 4 5 5 6 6 7 8 8 9 9 10 10 11 12 14 15
40 1 1 1 1 1 2 2 2 2 3 3 3 4 4 5 5 6 6 7 7 7 8 8 9 10 11 14 15
Sample:
Q = 1000 W, Δt = 15 K
Setting value: 6 (≈ 60 l/h)
6
Articles
SW2*
)
Angle
H1
d2 DN D d2 l3 l4 l5 H1 Flow EAN Article No
l5 range[l/h]
SW*1
)
SW2*
)
Angle
H1
with reduced lengths. Brass. Not suitable for compression fitting for multi layer pipes.
d2
l5 DN D d2 l3 l4 l5 H1 Flow EAN Article No
*)
D
SW1 range[l/h]
l3
l4 10 Rp3/8 R3/8 24 49 20 24 10-150 4024052932313 3461-01.000
15 Rp1/2 R1/2 26 53 23 23,5 10-150 4024052932412 3461-02.000
20 Rp3/4 R3/4 30 63 26 21,5 10-150 4024052932511 3461-03.000
SW2*
)
Angle
H1
with Viega press connection 15 mm
d2
DN d2 l3 l4 H1 Flow EAN Article No
SW1*
)
54 range[l/h]
22
SW2*) Angle
H1 with male thread G 3/4
d2
DN d1 d2 l3 l4 H1 Flow EAN Article No
26
range[l/h]
d1 15 G3/4 R1/2 29 58 21,5 10-150 4024052930616 3935-02.000
l3
l4
H2
D d2 DN D d2 l1 l2 H2 Flow EAN Article No
range[l/h]
l1
l2 10 Rp3/8 R3/8 59 85 21,5 10-150 4024052929511 3932-01.000
15 Rp1/2 R1/2 66 95 21,5 10-150 4024052929610 3932-02.000
20 Rp3/4 R3/4 74 106 23,5 10-150 4024052929917 3932-03.000
SW1*
)
SW2*
)
Straight
H2
with reduced lengths. Brass. Not suitable for compression fitting for multi layer pipes.
D d2
DN D d2 l1 l2 H2 Flow EAN Article No
l1
l2 range[l/h]
10 Rp3/8 R3/8 50 76 22,5 10-150 4024052932610 3462-01.000
15 Rp1/2 R1/2 55 83 22,5 10-150 4024052932719 3462-02.000
20 Rp3/4 R3/4 65 97 22,5 10-150 4024052932818 3462-03.000
*) S
W1: DN 10 = 22 mm, DN 15 = 27 mm, DN 20 = 32 mm
SW2: DN 10 = 27 mm, DN 15 = 30 mm, DN 20 = 37 mm
Values H1 and H2 are at the bearing surface thermostatic head or actuator.
7
IMI HEIMEIER / Thermostatic Heads & Radiator Valves / Eclipse
SW1*
)
SW2*
) Straight
H2 with Viega press connection 15 mm
d2
15
SW2*
)
Straight
H2
with male thread G 3/4
d1 d2
DN d1 d2 H2 Flow EAN Article No
59
88 range[l/h]
15 G3/4 R1/2 21,5 10-150 4024052933013 3936-02.000
59
d2 Straight
SW2*
)
30 with bended nipple
D
H2
SW2*
)
Axial
d2
24 DN 10
27 DN 15
SW2*
) Axial
with reduced lengths. Brass. Not suitable for compression fitting for multi layer pipes.
22,0 DN 10
23,5 DN 15
26,0 DN 20
d2
DN D d2 l3 l4 H1 Flow EAN Article No
* )
SW1 range[l/h]
D
l3
H1 l4 10 Rp3/8 R3/8 24,5 50 34,5 10-150 4024052932016 3460-01.000
15 Rp1/2 R1/2 26 53 34,5 10-150 4024052932115 3460-02.000
20 Rp3/4 R3/4 30 63 34,5 10-150 4024052932214 3460-03.000
SW2*)
Axial
d2 with male thread G3/4
27
*) S
W1: DN 10 = 22 mm, DN 15 = 27 mm, DN 20 = 32 mm
SW2: DN 10 = 27 mm, DN 15 = 30 mm, DN 20 = 37 mm
Values H1 and H2 are at the bearing surface thermostatic head or actuator.
8
SW2*
)
Double angle
Connection to radiator left
d2
22 DN10
26 DN15
SW1*
) DN D d2 l3 l4 Flow EAN Article No
D range[l/h]
l3
l4 10 Rp3/8 R3/8 26 52 10-150 4024052931019 3933-01.000
15 Rp1/2 R1/2 29 58 10-150 4024052931217 3933-02.000
SW2*
)
Double angle
d2 with male thread G 3/4
26 Connection to radiator left
d1 DN d1 d2 l3 l4 Flow EAN Article No
l3
l4
range[l/h]
15 G3/4 R1/2 29 58 10-150 4024052931316 3938-02.000
SW2*
)
Double angle
d2 Connection to radiator right
22 DN10
26 DN15
SW1*
)
SW2*
)
Double angle
d2 with male thread G 3/4
26 Connection to radiator right
9
IMI HEIMEIER / Thermostatic Heads & Radiator Valves / Eclipse
Accessories
Setting key
for Eclipse. Color orange. EAN Article No
4024052937714 3930-02.142
Compression fitting
for copper or precision steel pipe Ø Pipe DN EAN Article No
according to DIN EN 1057/10305-1/2. 12 10 (3/8”) 4024052174614 2201-12.351
Female thread connection Rp 3/8 – 14 15 (1/2”) 4024052174713 2201-14.351
Rp 3/4. Metal-to-metal joint. 15 15 (1/2”) 4024052175017 2201-15.351
Brass nickel-plated. 16 15 (1/2”) 4024052175116 2201-16.351
Support sleeves should be used for a pipe 18 20 (3/4”) 4024052175215 2201-18.351
wall thickness of 0.8 – 1 mm. Follow the
specifications of the pipe manufacturer.
Support sleeve
for copper or precision steel pipe with a Ø Pipe L EAN Article No
1 mm wall thickness. 12 25,0 4024052127016 1300-12.170
Brass. 15 26,0 4024052127917 1300-15.170
16 26,3 4024052128419 1300-16.170
18 26,8 4024052128815 1300-18.170
Compression fitting
for Alu/PEX multi-layer pipe according to
DIN 16836. Ø Pipe EAN Article No
Female thread connection Rp 1/2. 16 x 2 4024052138616 1335-16.351
Nickel-plated brass.
Compression fitting
for copper or precision steel pipe Ø Pipe EAN Article No
according to DIN EN 1057/10305-1/2. 12 4024052214211 3831-12.351
Connection male thread G 3/4 according 14 4024052214310 3831-14.351
to DIN EN 16313 (Eurocone). 15 4024052214617 3831-15.351
Metal-to-metal joint. Brass nickel-plated. 16 4024052214914 3831-16.351
With a pipe wall thickness of 0.8-1 mm 18 4024052215218 3831-18.351
insert supporting sleeves. Heed pipe
manufacturer’s technical advice.
Compression fitting
for copper or precision steel pipe Ø Pipe EAN Article No
according to DIN EN 1057/10305-1/2 and 15 4024052515851 1313-15.351
stainless steel pipe. 18 4024052516056 1313-18.351
Connection male thread G 3/4 according
to DIN EN 16313 (Eurocone).
Soft sealed, max. 95°C.
Nickel-plated brass.
10
Compression fitting
for plastic pipe according to DIN 4726, Ø Pipe EAN Article No
ISO 10508. 12x1,1 4024052136018 1315-12.351
PE-X: DIN 16892/16893, 14x2 4024052134618 1311-14.351
EN ISO 15875; 16x1,5 4024052136117 1315-16.351
PB: DIN 16968/16969. 16x2 4024052134816 1311-16.351
Connection male thread G3/4 according 17x2 4024052134915 1311-17.351
to DIN EN 16313 (Eurocone). 18x2 4024052135110 1311-18.351
Nickel plated brass.
20x2 4024052135318 1311-20.351
Compression fitting
for Alu/PEX multi-layer pipe according to Ø Pipe EAN Article No
DIN 16836. Connection male thread G3/4 16x2 4024052137312 1331-16.351
according to DIN EN 16313 (Eurocone). 18x2 4024052137411 1331-18.351
Nickel-plated brass.
Fitting tool
complete with case, box spanner EAN Article No
and replacement seals, for replacing Fitting tool 4024052298914 9721-00.000
thermostatic inserts without draining off
the heating system (for DN 10 to DN 20).
Other accessories, see catalogue leaflet “Accessories and spare parts for thermostatic radiator valves”.
11
IMI HEIMEIER / Thermostatic Heads & Radiator Valves / Eclipse
The products, texts, photographs, graphics and diagrams in this document may be subject to
alteration by IMI Hydronic Engineering without prior notice or reasons being given. For the most up
to date information about our products and specifications, please visit www.imi-hydronic.com.
1217-18.483 EN Eclipse ed.3 01.2023